Data Sheet-Genset-Abc Af25
Data Sheet-Genset-Abc Af25
Data Sheet-Genset-Abc Af25
Powered by AGG
Generator Specification
Performance Data
AU
E
VER
I
Starter motor voltage 12V
ISO 9001 R T
U AS
BUREAU VERITASB
Certification
1 82 8 Frequency 60HZ
Engine speed (RPM) 1800
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 7.2
·2006/42/EC Machinery safety. Fuel
·2006/95/EC Low voltage 100% prime power 6.5
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN
Consumption
75% prime power 4.9
12601 : 2010 (L/H)
50% prime power 3.4
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable power
sequence, which may be run for an unlimited number of hours per year, between stated Standard reference Conditions
maintenance intervals. The permissible average power output during at 24 hours period shall Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30% relative
not exceed 80% of the prime power. 10% overload available for governing purposes only. humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and conforming to
BS 2869: 1998, Class A2
220/127 33 26 30 24 86.6
Always Reliable
408 +1%
Poles 4 +1% 380
-1%
Winding Connections (standard) Star-serie 352
Terminals 12 296
IP rating IP23
50
-1%
46
38
30
0 1 2 3 4 5 6 7 8 9 10 1 1 1 2
δf%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1.955s
Three phase Reliable Single phase
δf%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0.54s
Options
· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD
· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable earth leakage
relay
Control Panel
Configuration Benefits
Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· 3 phase generator set monitoring
· Storage temp: -30 ˚C to + 80 ˚C
· Support of engines equipped with electronic control unit
· Operating humidity: 95% w/o condensation
· Vibration: 5-25Hz, ±1.6 mm
· Comprehensive diagnostic message
5-100Hz, a=4g
· Automatic or manual start/ stop of the gensets
· Shocks: a= 500m/s²
· Push buttons for simple control, lamp test
· Graphic back-lit LCD display
Options
· Parameters adjustable via keyboard or PC
· Mains measurements ( 50HZ/60HZ) · Ethernet interface (Remote monitoring and control)
· Generator measurements ( 50HZ/ 60HZ) · GSM modem/wireless internet (Remote monitoring and control)
· Comprehensive shutdown or warning on fault condition · RS232-RS485 Dual port interface
· 3 phase Generator protections · Synchronizing control panel
- Over-/under voltage · Distribution board with sockets kit and power busbar
· Battery trickle charge ammeter
- Over-/ under frequency
· Earth leakage protection
- Current/voltage asymmetry
· Earth fault protection
- Over current/overload · Low fuel level alarm
· 3 phase AMF function · Low fuel level shutdown
- Over-/under frequency · High fuel level alarm
- Over-/under voltage · Fuel transfer system control
- Voltage asymmetry · Low coolant level shutdown
· Configurable analog inputs · High lube oil temp shutdown
· Battery voltage, engine speed (pick-up) measurement · Overload via alarm switch on breaker
· Configurable programmable binary inputs and outputs · Engine coolant heater controls
· Warm-up and cooling functions · Control panel heater
· Generator C.B. and Mains C.B. control with feedback and · Speed adjust switch
return timer
· Oil temp displayed on LCD screen
· RS232 interface
· Additional 8 inputs and outputs
· Modem communication support
· Hours counter
· Sealed to Ip65
· Event log
All information in the document is substantially correct at time of printing but may be subsequently altered by the company.