SYMBOL GENERAL NOTES

LED RECESSED LIGHT


1. THE ELECTRICAL INSTALLATION WORK HEREIN SHALL BE DONE IN ACCORDANCE
WITH THIS PLANS AND SPECIFICATIONS APPLICABLE PROVISIONS OF THE LATEST
EDITION OF THE PHILIPPINE ELECTRICAL CODE, RULES AND REGULATIONS OF THE
2-T20 LED FLOURESCENT TUBE
LOCAL ENFORCING AUTHORITY, THE ELECTRICAL WORKS SHALL BEDONE UNDER
THE EMEDIATE SUPERVISION OF A DULY LICENSED ELCTRICAL ENGINEER.
WALL LAMP
2. POWER SERVICE SHALL BE 230 VOLTS, SINGLE PHASE,60 HZ TWO WIRE SYSTEM.
S ONE GANG SWITCH
3. CONTRACTOR SHALL SECURE ALL WIRING PERMIT AND ALL FEES REQUIRED FOR
S2 TWO GANG SWITCH THE WORKS AND FURNISH THE OWNER THE CERTIFICATE OF FINAL ELECTRICAL
INSPECTION.
S3 THREE GANG SWITCH
4. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE FOR THE
PARTICULAR LOCATION AND PURPOSE OF USAGE.
AL15-6 CIRCUIT HOMERUN
5. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND POWER CIRCUIT
DUPLEX CONVINIENCE OUTLET AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENTS.

SD SMOKE DETECTOR 6. ALL WORK SHALL BE DONE PROVIDED WITH PROPER SUPPORT OR AND
ANCHORAGE NECESSARY FOR PERMANENT CONNECTION WITH CONCRETE
FIRE ALARM WALLING.

7. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANEL BOARDS, LIGHTING


SPRINKLER
FITURES AND NON-CURRENT CARRYING METAL SHALL BE PROPERLY GROUNDED IN
ACCORDANCE WITH THEPHILIPPINE ELCTRICAL CODE.
SPECIAL PURPOSE OUTET
8. WIRING METHOD SHOULD BE AS FOLLOWS:
FAN COIL UNIT (FCU)
A. FEEDERS AND RISER - PVC CONDUIT.
WCC WATER COOLED CHILLER (WCC) B. LIGHTING AND POWER RECEPTACLE - PVC CONDUIT.

9. ALL WIRES SHALL BE COPPER THHN UNLESS OTHERWIRE INDICATED IN THE PLAN.
AHU AIR HANDLING UNIT (AHU)
THE MINIMUM SIZE OF WIRE FOR POWER, SPECIAL PURPOSE OUTLET AND
LIGHTING OUTLET CIRCUIT HOMERUN SHALL BE 3.5 mm^2 AND INSULATED FOR
P WATER PUMP
600 VOLTS. SMALLEST RACEWAY SHALL BE “15 m DIAMETER” TRADE/NOMINAL
SIZE.
TELEPHONE

10. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS:


CCTV CAMERA

A. LIGHT SWITCH - 1.2 m ABOVE THE FINISHED FLOOR


DISTRIBUTION PANEL
B. CONVINIENCE OUTLET - .3 m ABOVE FINISHED FLOOR
C. SPECIAL PURPOSE OUTLET - .9 m ABOVE FINISHED FLOOR
D. PANEL BOARD - 1.5 m ABOVE FINISHED FLOOR
E. FIRE ALARM STATION OUTLET - 1.3 m ABOVE FINISHED FLOOR
F. FIRE ALARM BELL - 5 m ABOVE FINISHED FLOOR
G. TELEPHONE OUTLET - .5 m ABOVE FINISHED FLOOR

DESIGNED BY: TITLE SHEET DESCRIPTION SHEET #:


TABOBO, JONEL MARK F.
CARAGAY, JORENCE Q. JJAM MALL LEGENDS /
POQUIZ, ARJAY Z.
FERRERIA, MARK HECTOR A.
MOHAMMED, SEMIR ABDELLA IBRAHIM
NASSER, NASSER ALI MOHAMMED (5 STOREY MALL) GENERAL NOTES 40