Electrical Grounding Techniques
Electrical Grounding Techniques
Electrical Grounding Techniques
Ground Resistance -
Principles, Testing,
Techniques
q & Applications
pp
Table of Contents
email: luk@lem.com
Measuring Soil Resistivity 4 - Pole Method 5
Why Ground ?
There are a number of good reasons to ground but primary among them Ground resistance values
is to ensure personnel safety. The following agencies and organizations There is a good deal of confusion
all have recommendations and / or standards for grounding, to ensure as to what constitutes a good ground
that personnel safety is being protected. The organizations that provide and what the ground resistance value
needs to be. Ideally a ground should
guidelines/rules for grounding are: The International Electrotechnical
be of zero ohms resistance. The
Commission (IEC), European Committee for Electrotechnical
NEC has stated that "A single
Standardization (CENELEC), Underwriters Laboratories (UL), National
electrode consisting of a rod, pipe,
Fire Protection Association (NFPA), American National Standards Institute or plate which does not have a
(ANSI), Mine Safety Health Administration (MSHA), Occupational Safety resistance to ground of 25 ohms or
Health Administration (OSHA), Telecommunications Industry Standard less shall be augmented by one
(TIA) and others. additional electrode...". Once you
Good grounding is not only for the safety of personnel but to provide for have added the supplemental ground
you have met the requirement for
the protection of plants and equipment. A good ground system will
the NEC. This does not mean that
improve the reliability of equipment and reduce the likelihood of damage
the value of the ground now has to
as a result of lightning or fault currents. be 25 ohms or less. The ground
resistance values objectives vary
from industry to industry.
What is a ground and what does it do ? Telecommunications industry has
often used 5 ohms or less as their
The NEC, National Electrical Code defines a ground as: "a conducting value for grounding and bonding.
connection, whether intentional or accidental between an electrical circuit The goal in ground resistance values
is to achieve the lowest ground
or equipment and the earth, or to some conducting body that serves in
resistance value possible that makes
place of the earth." When talking about grounding it is actually two
sense economically and physically.
different subjects, earth grounding and equipment grounding. Earth
grounding is an intentional connection from a circuit conductor usually
the neutral to a ground electrode placed in the earth. Equipment grounding
is to ensure that operating equipment within a structure is properly
grounded. These two grounding systems are required to be kept separate
except for a connection between the two systems to prevent differences
in potential from a possible flashover from a lightning strike. The purpose
of a ground besides the protection of people plants and equipment is to
provide a safe path for the dissipation of Fault Currents, Lightning Strikes,
Static Discharges, EMI and RFI signals and Interference.
1
round Electrodes
Sphere of influence:
2
Ground Electrodes
Multiple ground electrodes - Interaction
A) The resistance of the ground 1. The ground Itself To assist you in installing a
electrode and it's connection is 2. The length/depth of the ground ground rod that will meet your
generally very low, ground rods are electrode specific resistance require-
generally made of highly conductive/ 3. Diameter of the ground electrode. ments you can use the table
low resistance material such as of ground resistances on page
copper of copper clad. Increasing the diameter of the ground 5. Remember this is to be
electrode has very little effect in used only as a rule of thumb,
B) The contact resistance of the earth lowering the resistance. For example because soil is in layers and
to the electrode: The Bureau of you could double the diameter of a is rarely homogenous, so the
Standards has shown this resistance ground electrode and your resistance resistance values will vary
to be almost negligible providing that would only decrease by as much as greatly.
the ground electrode is free from 10 %.
paint, grease etc. and that the ground Another system to lowering
electrode is in firm contact with the One very effective way of lowering
resistance is to drive ground ground resistance is through
earth. the use of multiple ground
electrodes deeper. Because the earth
C) The resistance of the surrounding is in layers resistivity changes and electrodes. In this system more
earth: The ground electrode is varies considerably on the layer and than one electrode is driven
surrounded by earth which is made the depth within that layer. Soil is not into the ground and connected
up of concentric shells all having the consistent in its resistivity but highly in parallel to lower the resis-
same thickness. Those shells closest unpredictable. With that in mind it is tance. Each ground electrode
to the ground electrode have the of critical importance that when has it's own sphere of influence
smallest amount of area resulting in installing the ground electrode that it and for additional electrodes
the greatest degree of resistance. is below the frost line so that the to be effective the spacing of
Each subsequent shell incorporates resistance to ground will not be greatly additional rods needs to be at
a greater area resulting in lower increased by the freezing of the least equal to the depth of the
resistance. This finally reaches a point surrounding soil. Generally speaking driven rod. Without proper spa-
where the additional shells offer little by doubling the length of the ground cing of the ground electrodes
resistance to the ground surrounding electrode you can reduce the the spheres of influence will
the ground electrode. resistance level by an additional intersect and the lowering of
40 %. There are occasions where it the resistance will be minimal
The NEC specifies that the ground is physically impossible to drive and of little value.
electrode shall be installed so that it ground rods deeper, areas that are
is at least 2,4 m in length and in composed of rock, granite etc. In
contact with the soil. There are 3 these instances alternative methods
variables that affect the resistance of such as grounding cement are a
a ground electrode: viable alternative.
3
ypes of Ground Systems
The reason for measuring soil The second factor affecting soil resis- As shown in the table there can be
resistivity when selecting a location tivity is moisture or the amount of a change in resistivity from top to
for a sub-station or central office is water in the ground. Moisture content bottom by a factor of 50.
to find a location that has the lowest changes seasonally, varies according
possible resistance. Once a site has to the nature of the sub layers of earth
been selected, measuring the soil and the depth of the permanent water
resistivity will give you the information table. The table on page 5 shows
necessary to design and build a different types of soil and the affects
ground field that will meet your ground that moisture has on their resistivity.
resistance requirements.
There are a number of factors Since soil resistivity is so closely
affecting soil resistivity, soil related to moisture and moisture is
composition being one of them. Soil present in the soil we can logically
is rarely homogenous and the assume that as moisture increases
resistivity of the soil will vary resistivity will decrease and vice versa.
geographically and at different depths.
4
Ground Resistance Values
5
oil Resistivity Testing
The ground stakes are positioned in
a straight line equidistant from one
another and at a distance between
To test soil resistivity connect the ground one another reflecting the depth to
tester as indicated: be measured. The ground stakes
should be screwed in no deeper than
1/3 the distance from one another. A
known fixed current is generated by
the GEO between the two outer
ground stakes and a drop in potential
(which is a result of the resistance)
is then measured automatically
between the two inner ground stakes.
The GEO then displays this resistance
value in ohms.
6
Stake Setting To test the accuracy of the Often the driving of a single
results and to ensure that the ground rod into the earth does
To achieve the highest degree of
ground stakes are outside the not result in a resistance
accuracy when performing a 3 - Pole
7
round Resistance Testing
Existing Systems 'Selective' Clamp-on
NO DISCONNECTION REQUIRED!
Connect the ground tester as shown in the picture above. Press START, and
read out the RE value. This is the actual value of the ground electrode under
test.
8
Ground Resistance Testing
and to ensure that the ground stakes
are outside the 'spheres of influence'
reposition ground stake P2/S 1 m in
either direction and take a new
measurement. If the measured value
remains fairly constant the distance
between the ground stakes is
sufficient. If there is a significant
change in the reading (30 %) you
need to increase the distance
between the ground rod under test
and P2/S and C2/H until the measu-
red values remain fairly constant when From the picture above we can see that the total resistance of an
repositioning the P2/S ground stake individual tower is the parallel sum of all grounds. The tower has 4
1 m or so. individual grounds you must measure all 4, generating the individual
Ground resistance measurements resistance and then calculate according to the formula above.
are often corrupted and or prevented
by the existence of ground currents
and their harmonics. To prevent this
from occurring the SATURN GEO X
uses an Automatic Frequency Control
System (AFC), that automatically
selects the testing frequency with the
least amount of noise enabling you
'Selective' Clamp-on
to get a clear and accurate reading.
'Selective' Measuring of
High Voltage Transmission
Towers
Testing individual ground electrode
resistances of high voltage trans-
mission towers with overhead ground
or static wire requires that these wires
be disconnected. If a tower has more
than one ground at it's base, these
must also be disconnected one by
one and tested.The SATURN GEO
X with the 31 cm diameter clamp-on
current transformer can measure the
individual resistances of each leg
without disconnecting any ground
leads or overhead static/ground wires.
9
round Resistance Testing
Existing Systems - 'Stakeless'
How it Works...
The first current transformer induces a voltage in the Ground Resistance Testing 2 - Pole
circuit while the second current transformer measures
In situations where the driving of ground stakes is neither
the actual current flowing allowing the GEO X to calculate practical or possible the GEO does give you the ability to
the resistance of the ground path after synchronous do 2 - pole ground resistance/continuity measurements.
rectification of current and voltage. To perform this test requires a good known ground such
as an all metal water pipe. The water pipe should be
extensive enough and be metallic throughout without any
insulating couplings or flanges. Unlike many testers the
GEO performs the test with a relatively high current (short
circuit current >250mA) ensuring stable results.
10
G r o u n d I m p e d a n c e M e a s u r e m e n ts
When attempting to calculate possible short circuit currents
in power plants and other high voltage/current situations,
determining the complex grounding impedance is important
After having completed the 3-Pole test for the entire grid
we to measure individual ground rods and their
connections in the grid using the selective clamp-on
method. We measure each connection separately without
having to disconnect. The purpose of the selective clamp
on is to ensure that the resistances within the grid are
fairly uniform.
11
easuring Ground Resistance
At Central Offices ...
When conducting a grounding audit of a central office there are 3 or 4 Measurements would be accurate but
different measurements required. First locate the MGB (Master Ground Bar) would not show how the system
within the central office to determine behaves as a network, because in
the type of ground. The MGB will have real life in the event of a lightning
a ground lead going to the MGN (Multi- strike or fault current everything is
Grounded Neutral) or incoming service, connected. To prove this out you can
measure each leg separately discon-
a separate ground lead from the MGB nected via the 3-pole method and
to the ground field, another ground lead record each measurement. Using
from the MGB connected to the water Ohm's law again these measure-
pipe and a ground lead connected to ments should be equal to the resis-
structural or building steel. The first mea- tance of the entire system. From the
surement to take is stakeless measure- calculations you will see that you are
ment of all the individual grounds coming from 20 - 30 % off the total RE value.
off of the MGB. The purpose is to ensure that all the grounds are connected
especially the MGN. It is important to note that you are not measuring the The final way to measure the
individual resistance rather the loop resistance of what you are clamped resistances of the various legs of the
around. Connect the GEO X and measure the loop resistance of the MGN, MGB is the 'Selective Stakeless
the ground field the water pipe and the building steel. Method'. It works similat to the
Stakeless Method but it differs in the
vidual way we use the two separate CT's.
We clamp the inducing voltage CT
around the cable going to the MGB,
and since the MGB is connected to
the incoming power which is straight
parallel to earth system we have
achieved that requirement.
12
... at Cellular Sites/Microwave and
13
easuring Ground Resistance at
Remote Switching Sites ...
14
... and for Lightning Protection
There are 3 ground resistance measurements required when conducting an audit of a lightning/fault current
protection system. Most lightning fault current protection systems follow the design of having all 4 corners of
the building grounded and these are usually connected via a copper cable. Depending on the size of the
building and the resistance value that was tried to be obtained number of ground rods will vary.
15
Ground Testing Instruments
Universal ground testing instruments for testing installations and lightning protection. All instruments operate with a
battery, have automatic switch-off, display illumination, adjustable limits, and display probe and auxiliary earth
resistances. Auto-ranging and parasitic current suppression provide reliable measuring results. For standard 3-pole
measurements, many additional special functions are available.
16
Accessories
HEME GEO 15
Clamp-on ground loop tester
· Fast, efficient and simple checking
of ground loops without any
auxiliary earth electrodes by using
a hand-held clamp
· Ideal for use in multi-ground
systems, rapid diagnosis earth
system faults
· Non intrusive continuity with
buzzer
· Current ranges 200 A - 15 A
· High accuracy, light weight and
easy to use
Accessories
17
AUSTRIA FRANCE JAPAN SWITZERLAND
LEM NORMA GmbH LEM France NANALEM K.K. LEM ELMES
Verkauf Österreich La Ferme de Courtaboeuf 2-1-2 Nakamachi, Machida Bahnhofstrasse 15
Liebermannstraße F01 19, avenue des Indes 194-0021 TOKYO 8808 Pfäffikon
2345 Brunn am Gebirge 91969 Courtaboeuf Cedex Tel.: + 81 42 725 8151 Tel.: + 41 55 415 75 75
Tel.: + 43 2236 691 502 Tel.: + 33 1 69 18 17 50 Fax: + 81 42 728 8119 Fax: + 41 55 415 75 55
Fax: + 43 2236 691 400 Fax: + 33 1 69 28 24 29 e-mail: nle@lem.com E-mail: lel@lem.com
E-mail: lna@lem.com E-mail: lfr@lem.com www.lem.co.jp
Distributor/Vertragshändler/Distributeur/Distribuidor/Distributore
LEM Instruments
www.lem.com
Right to change specification reserved
Publication: A24415E
Printed in Germany