Unicont: PDF - Loop Indicator and Converter To HART
Unicont: PDF - Loop Indicator and Converter To HART
Unicont: PDF - Loop Indicator and Converter To HART
Manufacturer:
NIVELCO Process Control Co.
H-1043 Budapest, Dugonics u. 11.
Phone: (36-1) 889-0100 Fax: (36-1) 889-0200
E-mail: sales@nivelco.com www.nivelco.com
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 1 / 20
1. INTRODUCTION ...........................................................................................................................................................................................3
2. ORDER CODES ............................................................................................................................................................................................3
3. TECHNICAL DATA .......................................................................................................................................................................................4
3.1 GENERAL DATA ........................................................................................................................................................................................4
3.2 DIMENSIONS.............................................................................................................................................................................................6
3.3 ACCESSORIES ..........................................................................................................................................................................................6
4. INSTALLATION AND ELECTRIC CONNECTION........................................................................................................................................6
4.1 WIRING ....................................................................................................................................................................................................7
4.2 SAFETY REGULATIONS FOR THE EX CERTIFIED UNITS ...............................................................................................................................10
5. PUTTING INTO OPERATION, PROGRAMMING.......................................................................................................................................10
5.1 DEFAULT ...............................................................................................................................................................................................11
5.2 DISPLAY OF THE SAP-202 AND KEYS OF THE UNIT ...................................................................................................................................11
5.3 PROGRAMMING ......................................................................................................................................................................................12
5.3.1. STEPS OF PROGRAMMING ......................................................................................................................................................................................12
5.3.2. PARAMETERS – DESCRIPTION AND PROGRAMMING ...................................................................................................................................................14
5.4 ERROR INDICATIONS ...............................................................................................................................................................................19
5.4.1. VALID LED IS BLINKING AND A MESSAGE OF ERRX APPEARS ON THE DISPLAY ...........................................................................................................19
5.4.2. VALID LED AND THE DISPLAYED VALUE IS BLINKING ................................................................................................................................................19
5.4.3. ERROR INDICATION ON THE OUTPUT CURRENT (FOR 3-WIRE MODELS ONLY)...............................................................................................................19
6. MAINTENANCE AND REPAIR...................................................................................................................................................................20
7. STORAGE ...................................................................................................................................................................................................20
8. WARRANTY................................................................................................................................................................................................20
2 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
1. INTRODUCTION
The UNICONT PDF-01 and PDF-01-6/A/C Ex devices are 2-wire on-site indicators that can be inserted into a 4 … 20 mA current loop without the need for
additional power supply. Since the displayed value is proportional to the input, the units are suitable for indication of temperature, pressure, level, etc. values,
the information carried by the loop current. The customer can program the engineering units and the indication range.
The HART capable UNICONT PF-01-4 and PF-01-8/B/D Ex 3-wire process indicators require additional power supply. Besides displaying the loop
current or the process values, these units convert input current to HART signals and so enable devices that have analogue outputs only to be integrated into
HART multidrop systems. The ratio between the input and output current can be programmed.
The intelligent electronics and HART communication enables versatile signal processing and remote programming. The software uses the Universal HART
commands No. 1-3, 6, 7, 11-18 and device specific commands No128-132, 135 and 139 of the HART Revision 5.
Robust enclosure makes applications under harsh conditions also possible. Explosion proof versions are available for hazardous environments.
2. ORDER CODES
UNICONT P F – 0 1 – *
FUNCTION CODE HOUSING CODE OUTPUT / EX CODE
With display D Aluminium 4 Display 2
Without display T Plastic 5 4 ... 20 mA + HART 4
Stainless steel 6 Display / Ex ia 6
4 ... 20 mA + HART / Ex ia 8
Display /Ex d A
Not all combinations are possible! 4 ... 20 mA + HART / Ex d B
* The order code of an Ex version should end in “Ex” Display / Ex d+ia C
4 ... 20 mA + HART / Ex d+ia D
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 3 / 20
4 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 5 / 20
4.2
4.0
5.5
~100
~145
A
5.4
Type A,
Standard, Ex ia ~137 mm
Ex d, Ex d+ia ~145 mm
3.3 ACCESSORIES
Standard, Ex ia: Ex d, Ex d+ia:
– Installation and programming manual – 2 cable glands – Installation and programming manual – Sticker set of engineering units
– Warranty Card – Sticker set of engineering units – Warranty Card – HART-os készüléknél CDROM
– Declaration of Conformity – Declaration of Conformity az EView2 programmal
6 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
!
After wiring and programming the housing cover should be closed properly and the hex socket set screw or the safety locking bolt should be
tightened! The sealing ring must be replaced if damaged, otherwise the IP class of the device can be jeopardized.
Ex Ex Ex Ex P F-401-8/B/D Ex
PDF- 401-6/A/C Ex
Us
Us
R ≥ 250 Ω
Figure 2. Wiring of a 2-wire Unicont in the current loop of a transmitter Figure 3. Wiring of a HART capable (3-wire) Unicont
in the current loop of a transmitter
Shielding should be grounded at one point.
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 7 / 20
Us Transmitter
R ≥ 250 Ω
Figure 4. Wiring of a HART capable (3-wire) Unicont in the current loop of a 4-wire transmitter.
Ex Ex
P F- 01-8/B/D Ex
Multicont 1 6
Ex L+ Transmitter Ex
+Us 1
R = 250 Ω
L- HART
4-20mA
SH
HART
P F- 01-8/B/D Ex
1 6
Transmitter Ex
2
4-20mA
Figure 5. Wiring of 3-wire Uniconts with Multicont controller and 2-wire transmitters
8 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
4-20mA
(0-20mA)
Multicont 1 6
L+ Transmitter
+Us 1
R = 250 Ω L- HART
SH
HART
P F- 01-4
4-20mA
1 6 (0-20mA)
Transmitter
15
Figure 6. Wiring of 3-wire Uniconts with Multicont controller and 4-wire transmitters
R=10
R=5
I- I+
1 6 1 6
Figure 7. Internal wiring of the 2-wire Unicont Figure 8. Internal wiring the of 3-wire Unicont
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 9 / 20
10 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
The percental (%) value shown on the display is proportional to the input
(4 mA→ 0%, 20 mA →100.0%).
Damping: 3 s
Noise suppression frequency: 50 Hz
Bargraph indication is proportional to the input ( 0/4 mA→ 0%, 20 mA →100.0%).
The output of the 3-wire models can be 4…20 mA current and / or HART signal
During operation:
COM LED flashes during HART communication
While pressing the key the input current appears on the display of the 2-wire models.
While pressing the key the output current appears on the display of the 3-wire models.
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 11 / 20
12 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 13 / 20
P0: ---a Setting input current (Ia) that is to be assigned to displayed value (Da) See Figure 9, 10 and 11 FACTORY DEFAULT: 4 mA
P1: ---a Setting input current (Ib) to be assigned to displayed value (Db) FACTORY DEFAULT: 20 mA
The current value can be entered in P0 and P1 manually
For instance, entering 5.6 mA in P0 should be performed as shown below:
1. Press E + to get into PROGRAMMING mode
2. Press to go to P0
3. Press E to go to the parameter value
4. Press / / to adjust the display to 5.6
5. Press E + to return to MEASUREMENT mode
If the actual current value is to be entered in P0 or P1 it can automatically be set by the GET VALUE function. To do so the above described
procedure should be performed, but pressing + (instead of / / ) (step 4.). Successful setting is indicated by the message ‘SET’
displayed.
Remarks:
If the input current range is set for 4 … 20 mA, than the value of P11 can not be set below 4 mA in P0 and the value of P1 can not exceed 20 mA.
An input current value outside of this range would make VALID LED and current value display blinking.
P2: Setting displayed value (Da) to be assigned to input current Ia See Figure 9, 10 and 11 FACTORY DEFAULT: 0.0
P3: Setting displayed value (Db) to be assigned to input current Ib FACTORY DEFAULT: 100.0
P4: Setting output current pertaining to the input current Ia (for 3-wire models only) FACTORY DEFAULT: 4 mA
P5: Setting output current pertaining to the input current Ib (for 3-wire models only) FACTORY DEFAULT: 20 mA
14 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
3,85mA
3,85mA
3,9mA
Iin (mA) Ia Iin (mA) Iin (mA)
Ia
Ia
0
0
0 0 0
20,5mA
20,5mA
Input
21mA
Input
21mA
21mA
Da Da Input
Da current
current current
-9999 -9999 -9999
Figure 9. Display curve of 2-wire models Figure10. Display curve of 3-wire models Figure 11. Display curve of 3-wire models
with input range set for 4…20 mA with input range set for 0…20 mA
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 15 / 20
*- If an error indication of 22 mA arrives (from a transmitter) to the input of the Unicont, with settings 5 (under d) than it means that the current
output of the Unicont is 3.8 mA (and with setting 6 it is 22 mA)
- If an error indication of 3.8 mA arrives (from a transmitter) to the input of the Unicont, with settings 1 (under d) than it means that the current
output of the Unicont is 22 mA (and with setting 6 it is 3.8 mA mA)
16 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
P13: 00ba HART short address (for 3-wire models only) FACTORY DEFAULT: 00
The short address of the unit for the multidrop system (HART network) is to be given here.
Please note that in accordance with the HART standards the address of a single device should be 00. In this case current output will change
according to the settings in the range of 3.8 ... 22 mA and HART communication is also available.
For systems with more than one device 01 …15 addresses should be given. In these cases the output current will be fixed to 4 mA. Thus,
information is transferred by the HART communication only ( i.e. current output does not carry any information and error indication on the current
output is not possible). (See also ‘Description of Eview’ supplied with HART capable devices.)
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 17 / 20
Codes over 240 are engineering units defined by NIVELCO They might be different at other manufacturers.
18 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1
5.4.3. ERROR INDICATION ON THE OUTPUT CURRENT (FOR 3-WIRE MODELS ONLY)
Output current is 3.8 mA or 22 mA, depending on setting of character d in P11
BKI15ATEX0013X/1 ♦ pdf4012a0600p_06 ♦ 19 / 20
7. STORAGE
Ambient temperature: -25 °C ... +60 °C
Relative humidity: max. 98 %
8. WARRANTY
NIVELCO provides warranty of 3 (three) years in compliance with details described in the Warranty Card.
pdf4012a0600p_06
2016 April
NIVELCO reserves the right to change technical specifications without notice.
20 / 20 ♦ pdf4012a0600p_06 ♦ BKI15ATEX0013X/1