UGD Scope of Works - TPG
UGD Scope of Works - TPG
UGD Scope of Works - TPG
Description Remarks
No.
department, or will be reimbursed by the department after due
certification by the line department and authentication by the
Executive Engineer concerned) maintenance tools, safety
arrangements as per IE rules etc., The drawings of the
mechanical, electrical connections of the pumping station and
transformer & sub stations are to be got approved by the
department. The electrification and illumination with sufficient
exhaust fans in the pumping stations and yard lighting should be
provided as decided by the departmental officers. Approval from
Chief Electrical Inspectorate shall be obtained for all Electrical
installations.
28) The Wet well is to be designed for required demand and for uplift
pressure at worst condition i.e. water level up to GL (Ground
Level).
29) All the pumping mains are to be designed economically for
required demand taking into account static head, friction losses
other losses and surge as per IS codes and CPHEEO manual.
Surge control devices such as air cushion valves as per design are
to be placed at appropriate places. Designs should be got
approved by the department.
30) The STP should be designed for seismic and wind loads as per IS
codes.
31) All the components should be provided with name boards as
directed by the departmental officers.
32) All the surplus excavated earth of each item is to be conveyed and
leveled as directed by the departmental officers.
33) All the Excavated trenches shall be restored to original condition
as per the existing road pavement structure.
34) Submission of requisite design / drawings to statutory bodies like
CPCB / APPCB / Chief Electrical Inspectorate and facilitating for
the clearances / NOC /Approval for installations.
44
Sl. Description Remarks
No.
3 Construction of Lift stations To be
provided as
Lift Station (LS-1) at Housing Board of Zone- I including Inlet per design
works such as Inlet chamber, Screens, Grit Chamber etc. approved by
Dept.
Lift station (LS-2) at Sanjeev Nagar of Zone III including Inlet
works such as Inlet Chamber, Screens, Grit Chamber etc.
Columns and Beam Structure with VRCC M30 for Pump House with
a height of 5.5m along with Gantry arrangements. Super structure
with Brick Masonry in CM (1:5), Plastering with CM(1:4) 12mm
thick, and colour washing two coats on primer coat.
Complete electrical wiring with all light, fan points, sockets and other
facilities as required including concealed wiring with PVC pipes.
Providing impervious coat to exposed RCC roof slab surface with
CM (1:3) 20mm thick with 1 kg of water proof compound per bag of
cement laid over roof.
Columns and Beam Structure with VRCC M30 for pump house with
a height of 5.5m with gantry arrangements. Super structure with
Brick Masonry in CM (1:5), Plastering with CM(1:4) 12mm thick,
and colour washing two coats on primer coat. Plastering with CM
(1:3) 12mm thick; Plastering with CM (1:3) 20mm thick for
45
Sl. Description Remarks
No.
impervious coating to roof slab. Roof slab with VRCC M30
minimum 150mm thick
Complete electrical wiring with all light, fan points, sockets and other
facilities as required including concealed wiring with PVC pipes.
Providing impervious coat to exposed RCC roof slab surface with
CM (1:3) 20mm thick with 1 kg of water proof compound per bag of
cement laid over roof.
5 To be
Supply, delivery, erection, commissioning and testing of non-clog provided as
submersible pump-sets sets at 3 pumping stations (i.e., at Housing per design
Board Colony Pumping Station (with minimum of 41 KW), at approved by
Sanjeev Nagar Pumping Station (with minimum of 45 KW) & at Dept.
Kadakatla Pumping Station (with minimum of 75 KW)) with passing
of 100 mm solids and of suitable discharge and head as per the design
with high efficiency and 100% standby as IE standards, repute make
including panel boards and all other accessories including suction and
delivery pipes with DI K9 double flange pipes of suitable diameter
including DI valves, reflex valves, surge control devices, MS/DI/CI
specials and fittings, all valve chambers with VRCC etc. complete as
per relevant BIS codes and CPHEEO manual.
Main Panel Board with LT Sheet steel clad, free standing, floor
mounting unitized, Dust and vermin proof Indoor, Cubicle powder
coated panel board made out of 16 SWG CRCA sheet suitable for use
3 ph, 440v, 50 Hz. Panel board comprising with all accessories with
bus-bars, capacitors of adequate capacity, incoming and outgoing
connections, control wiring etc., as required.
Transformer yard of suitable size with not less than 15m x 12 m.
Transformer foundation and yard development with VRCC M20
beam column structures. All round fencing, earthing, filling with
gravel/ Metal etc. Separate Energy Meter cubicle with requisite
components to measure the energy consumption for various treatment
components of STP.
Approval from Chief Electrical Inspectorate shall be obtained for all
Electrical installations.
7 Providing Pumping Main (HDPE of OD 630mm Dia) from Kadakatla Pumping
Pumping Station to the Proposed STP for Zone I, II &III for a length Main HDPE
of 2.5 Km of OD 630mm
Dia –of
Length 2.50
Kms
8 Providing Trunk Main (RCC Pipes-NP3 ) from Sanjeev Nagar (Zone Trunk Main
III) to Kadakatla MPS and HB Colony (Zone I) to Kadakatla MPS RCC Pipes-
for a length of 3832 Rmt. NP3 – Length
of 3832 Rmt
9 Designing, constructing, hydraulic testing, commissioning and 5 MLD, To be
conducting satisfactorily trials of 5 MLD STP of Advanced modern provided as
technology which can be accommodated in limited identified land per design
space consisting of Primary, Secondary and Tertiary Treatment Units approved by
as per the requirement of designed CPHEEO norms relevant IS codes Dept.
etc. necessary piping work with required valves, gates, drains, path
Ways, Administration Block cum Laboratory, Toilet Block,
Laboratory Equipment, Internal Roads, Pathways, Compound Wall,
Tools and plants, Treated effluent arrangements complete as turnkey
job with all involved Civil, electrical, Instrumentation and
mechanical works Inclusive of following Items, units as per detailed
specifications for civil, electrical, Instrumentation and mechanical
components complete to achieve the effluent discharge standards: pH
6.5 - 8.5, BOD < 10mg/lit, COD < 50mg/lit, TSS < 10mg/lit, TN <
10mg/lit, TP < 2mg/lit, NH4N < 5mg/lit, FC < 100 MPN / 100 ml to
get recyclable quality of water for Industrial/ agricultural purposes.
The Coagulant Dosing System shall be provided as an optional/
backup. All units shall be interconnected with administration building
47