Chapter 3 Loads: WSDOT Bridge Design Manual M 23-50.20 Page 3-I September 2020
Chapter 3 Loads: WSDOT Bridge Design Manual M 23-50.20 Page 3-I September 2020
3.1 Scope
AASHTO Load and Resistance Factor Design (LRFD) Specifications shall be the minimum
design criteria used for all bridges except as modified herein.
3.2 Definitions
The definitions in this section supplement those given in LRFD Section 3.
Permanent Loads – Loads and forces that are, or are assumed to be, either constant upon
completion of construction or varying only over a long time interval.
Transient Loads – Loads and forces that can vary over a short time interval relative to the
lifetime of the structure.
Temporary Loads – Loads that occur for a limited duration during pre-service conditions
The modifier, ηi is the product of factors for ductility, redundancy, and importance. For
simplicity use a value of 1.0 for ηi except for the design of columns when a minimum value
of γi is appropriate. In such a case, use ηi = 0.95. Compression members in seismic designs
are proportioned and detailed to ensure the development of significant and visible
inelastic deformations at the extreme event limit states before failure.
The load factor for live load in the Service III load combination shall be as specified
in Section 3.5.
The design live load factor for the Service III Limit State load combination shall be
as follows:
γLL = 0.8 when the requirements of Sections 5.6.1 and 5.6.2 are satisfied and stress
analysis is based on gross section properties.
γLL = 1.0 when the requirements of Sections 5.6.1 and 5.6.2 are satisfied and stress
analysis is based on transformed section properties.
In special cases that deviate from the requirements of Sections 5.6.1 and 5.6.2 and have
been approved by the WSDOT Bridge Design Engineer, γLL, shall be as specified in the
AASHTO LRFD.
The Service III live load factor for load rating shall be 1.0.
The live load factor for Extreme Event-I Limit State load combination, γEQ as specified in
the AASHTO LRFD Table 3.4.1-1 for all WSDOT bridges and walls shall be taken equal
to 0.50. The γEQ factor applies to the live load force effect obtained from the bridge live
load analysis. Associated mass of live load need not be included in the dynamic analysis.
The AASHTO LRFD allow the live load factor in Extreme Event-I load combination, γEQ,
be determined on a project specific basis. The commentary indicates that the possibility
of partial live load, i.e., γEQ < 1.0, with earthquakes should be considered. The application
of Turkstra’s rule for combining uncorrelated loads indicates that γEQ = 0.50 is reasonable
for a wide range of values of average daily truck traffic (ADTT). The NCHRP Report 489
recommends live load factor for Extreme Event-I Limit State, γEQ equal to 0.25 for all
bridges. This factor shall be increased to γEQ equal to 0.50 for bridges located in main
state routes and congested roads.
Since the determination of live load factor, γEQ based on ADTT or based on bridges
located in congested roads could be confusing and questionable, it is decided that live
load factor of γEQ equal to 0.50 to be used for all WSDOT bridges regardless the bridge
location or congestion.
The base construction temperature may be taken as 64°F for the determination of
Temperature Load.
The load factors γTG and γSE are to be determined on a project specific basis in accordance
with Articles 3.4.1 and 3.12 of the AASHTO LRFD. Load Factors for Permanent Loads, γp
are provided in AASHTO LRFD Table 3.4.1-2.
The load factor for down drag loads shall be as specified in the AASHTO LRFD Table
3.4.1-2. The Geotechnical Report will provide the down drag force (DD). The down
drag force (DD) is a load applied to the pile/shaft with the load factor specified in the
Geotechnical Report. Generally, live loads (LL) are less than the down drag force and
should be omitted when considering down drag forces.
Table 3.5-4 below provides general guidelines for when to use the maximum or minimum
shaft/pile/column permanent load factors for axial capacity, uplift, and lateral loading.
In general, substructure design should use unfactored loads to obtain force distribution in
the structure, and then factor the resulting moment and shear for final structural design.
All forces and load factors are as defined previously.
In the table above, “causing moment” and “causing shear” are taken to be the moment and
shear causing axial, uplift, and lateral loading respectively. “Resisting” is taking to mean
those force effects that are diminishing axial capacity, uplift, and lateral loading.
For falsework and formwork design loads, see Standard Specifications Section
6-02.3(17)A. The base construction temperature shall be taken as 64°F
for the determination of Temperature Load.
Secondary prestressing forces (i.e. secondary moments) are the force effects in
continuous members, as a result of continuous post-tensioning. In frame analysis
software, the secondary moments are generally obtained by subtracting the primary
moment (P*e) from the total PS moment obtained by applying an equivalent static load
which represents the forces due to post-tensioning. A load factor, γPS, of 1.0 is appropriate
for the superstructure. For fixed columns a 50 percent reduction in PS force effects could
be used given the elasto-plastic characteristics of the soil surrounding the foundation
elements.
For lightweight concrete barrier, multiply the normal weight concrete barrier weight from
Table 3.8-1 by the ratio of the actual material weight to the unit weight of normal weight
concrete (155 lb/ft3).
Vehicular traffic will generate wear and rutting on a concrete bridge deck over the life of
a bridge. One option to correct excessive wear is to add a Hot Mix Asphalt (HMA) overlay
on top of the existing concrete deck. This type of overlay requires less construction time
and is less expensive compared to removing a portion of the deck and adding a modified
concrete overlay. The initial bridge design needs to incorporate the future overlay
dead load. All new bridge designs with a concrete driving surface, excluding modified
concrete overlays, shall be designed for a 35 psf future wearing surface load. The future
wearing surface load does not apply to girder deflection, “A” dimension, creep, or profile
grade calculations.
Concrete bridge deck protection systems shall be in accordance with Section 5.7.4 for
new bridge construction and widening projects.
Live load design criteria are specified in the lower right corner of the bridge preliminary
plan sheet. The Bridge Preliminary Plan Engineer determines the criteria using the
following guideline:
• New bridges and Bridge widening with addition of substructure – HL-93
• Bridge superstructure widening with no addition of substructure – Live load criteria of
the original design
• Temporary widening of existing bridges: Live load criteria of the existing bridge
• Detour and other temporary bridges, except as required by Section 10.13.2 –
75 percent of HL-93
The effect of one design tandem combined with the effect of the design lane load
specified in LRFD Article 3.6.1.2.4 and, for negative moment between the points of
contraflexure under a uniform load on all spans and reactions at interior supports, shall
be investigated a dual design tandem spaced from 26.0 feet to 40.0 feet apart, measured
between the trailing axle of the lead vehicle and the lead axle of the trailing vehicle,
combined with the design lane load. For the purpose of this article, the pairs of the design
tandem shall be placed in adjacent spans in such position to produce maximum force
effect. Axles of the design tandem that do not contribute to the extreme force effect
under consideration shall be neglected.
3.9.2 Loading for Live Load Deflection Evaluation
The loading for live load deflection criteria is defined in LRFD Article 3.6.1.3.2.
Live load deflections for the Service I limit state shall satisfy the requirements of
LRFD Section 2.5.2.6.2.
3.9.3 Distribution to Superstructure
The live load distribution factor for exterior girder of multi girder bridges designated
in LRFD Table 4.6.2.2.1-1 as type a, b, c, e, k and also i, j if sufficiently connected to
act as a unit, shall be as follows:
• For exterior girder design with slab cantilever length equal or less than 40 percent
of the adjacent interior girder spacing, use the live load distribution factor for
interior girder. The slab cantilever length is defined as the distance from the
centerline of the exterior girder to the edge of the slab.
• For exterior girder design with slab cantilever length exceeding 40 percent of
the adjacent interior girder spacing, use the lever rule with the multiple presence
factor of 1.0 for single lane to determine the live load distribution. The live load
used to design the exterior girder shall not be less than the live load used for the
adjacent interior girder.
• The special analysis based on the conventional approximation of loads on piles as
described in LRFD Article C4.6.2.2.2d shall not be used unless the effectiveness of
diaphragms on the lateral distribution of truck load is investigated. In accordance
with the AASHTO LRFD Bridge Design Specifications, 7th Edition, 2014 and later,
the special analysis is only applicable to steel beam-slab bridge cross-sections with
diaphragms or cross-frames.
The load distribution factor for multi-cell cast in place concrete box girders shall be
per AASAHTO LRFD for interior girders from Table 4.6.2.2.2b-1 for bending moment,
and Table 4.6.2.2.3a-1 for shear. The live load distribution factor for interior girders
shall then be multiplied by the number of webs to obtain the design live load for the
entire superstructure. The live load distribution need not exceed the total number of
design lanes. The correction factor for live load distribution for skewed support as
specified in Tables 4.6.2.2.2e-1 for bending moment and 4.6.2.2.3c-1 for shear shall
be considered.
DF = Nb x Dfi Live load distribution factor for multi-cell box girder (3.9.4-1)
Where:
Dfi = Live load distribution factor for interior web
Nb = Number of webs
A reduction factor will be applied in the substructure design for multiple lane loadings
in accordance with AASHTO 3.6.1.1.2.
D. Distribution to Substructure
The number of traffic lanes to be used in the substructure design shall be determined
by dividing the entire roadway slab width by 12. No fractional lanes shall be used.
Roadway slab widths of less than 24 feet shall have a maximum of two design lanes.
E. Distribution to Crossbeam
The design and load rating live loading is distributed to the substructure by placing
wheel line reactions in lane configurations that generate the maximum stress in the
substructure. A wheel line reaction is one-half of the reaction of a single lane of live
load. For integral and hinged continuity diaphragms, live loads are considered to act
directly on the substructure without further distribution through the superstructure
as illustrated in Figure 3.9‑1. For girder configurations where there is a clear load
path through the girders to the cross beam, such as at expansion piers with girders
supported on individual bearings, live load reactions are applied through the bearings.
Normally, substructure design will not consider live load torsion or lateral distribution.
Sidesway effects shall be taken into account.
CROSSBEAM
CROSSBEAM
For steel and prestressed concrete superstructure where the live load is transferred to
substructure through bearings, cross frames or diaphragms, the girder reaction may be
used for substructure design. Live load placement is dependent on the member under
design. Some examples of live load placement are as follows. The exterior vehicle wheel
is placed 2 feet from the curb for maximum crossbeam cantilever moment or maximum
eccentric foundation moment.
For crossbeam design between supports, the lanes are placed to obtain the maximum
positive moment in the member; then re-located to obtain the maximum shear or
negative moment in the member.
For column design, the design lanes are placed to obtain the maximum transverse
moment at the top of the column; then re-located to obtain the maximum axial force
of the column.
Bridge designers are responsible for Design, Legal, and Permit load rating of new
bridges in accordance with the National Bridge Inspection Standards (NBIS) and the
AASHTO Manual Bridge Evaluation. See Chapter 13 for detailed information on loading
requirements for bridge load rating.
For the usual girder and slab bridges having individual span length of not more than
150 ft and a maximum height of 33 feet above low ground or water level, the following
simplified wind pressure on structure (WS), could be used in lieu of the general method
described in AASHTO LRFD Article 3.8.1.2:
For the usual girder and slab bridges having individual span length of not more than 150
feet and a maximum height of 33 feet above low ground or water level, the following
simplified wind pressure on vehicle (WL), could be used in lieu of the general method
described in AASHTO LRFD Article 3.8.1.3:
• 0.10 kip per linear foot, transverse
• 0.04 kip per linear foot, longitudinal
Wind forces shall be applied to the substructure units in accordance with the
loadings specified in AASHTO. Transverse stiffness of the superstructure may be
considered, as necessary, to properly distribute loads to the substructure provided
that the superstructure is capable of sustaining such loads. Vertical wind pressure, per
AASHTO LRFD Section 3.8.2, shall be included in the design where appropriate, for
example, on single column piers. Wind loads shall be applied through shear keys or
other positive means from the superstructure to the substructure. Wind loads shall be
distributed to the piers and abutments in accordance with the laws of statics. Transverse
wind loads can be applied directly to the piers assuming the superstructure to act
as a rigid beam. For large structures a more appropriate result might be obtained by
considering the superstructure to act as a flexible beam on elastic supports.
Wind on Noise Walls shall be as specified in LRFD 3.8.1, 3.8.1.2.4, and 15.8.2.
The current AASHTO LRFD require a load factor of 1.2 on CR, SH, and TU deformations,
and 0.5 on other CR/SH/TU force effects. The lower value had been rationalized as
dissipation of these force effects over time, particularly in the columns and piers.
Changing the load factors for creep and shrinkage is not straight-forward because CR,
SH are “superimposed deformations”, that is, force effects due to a change in material
behavior that cause a change in the statical system. For safety and simplicity in design,
they are treated as loads--despite not being measurable at time t = 0. However, behavior
is nonlinear and application of the load factor must also be considered. Some software
will run service load analysis twice: once with and once without CR, SH effects. The CR
and SH can then be isolated by subtracting the results of the two runs. Other software
will couple the CR and SH with the dead load, giving a shrinkage- or creep-adjusted
dead load.
The proposed compromise is to assign creep and shrinkage the same load factor as
the DC loads, but permit a factor of 1.0 if the project-specific creep coefficient can be
determined and is then used in the linear analysis software.
Thermal and shrinkage loadings are induced by movements of the structure and can
result from several sources. Movements due to temperature changes are calculated
using coefficients of thermal expansion of 0.000006 feet/foot per degree for concrete
and 0.0000065 feet/foot per degree for steel. Reinforced concrete shrinks at the rate
of 0.0002 feet/foot.
In accordance with WSDOT HQ Hydraulics Office criteria, an ice thickness of 12″ shall be
used for stream flow forces on piers throughout Washington State.
The design thermal movement associated with a uniform temperature change may
be calculated using the ranges of temperature as specified herein. The temperature
ranges shown below reflect the difference between the extended lower and upper
boundary to be used to calculate thermal deformation effects.
• Concrete Bridges (All Regions): 0° to 100°
• Steel Bridges (Eastern Washington): −30° to 120°
• Steel Bridges (Western Washington): 0° to 120°
Where the design choice is to provide structural resistance, the pier or abutment shall be
designed for an equivalent static force of 600 kip, which is assumed to act in a direction
of zero to 15 degrees with the edge of the pavement in a horizontal plane, at a distance
of between 2.0 and 5.0 ft above the ground, whichever produces the critical shear or
moment in the pier component and the connections to the foundation or pier cap.
2. Reinforced concrete pier components that are at least 3.0-ft thick and have a
concrete cross-sectional area greater than 30.0 ft2 as measured in the horizontal
plane at all elevations from the top of the pier foundation to a height of at least 5.0 ft
above the grade.
3. Pier systems with three or more columns where the designer shows by calculation
that the superstructure will not collapse with one column missing when subjected
to the full dead load with a 1.1 load factor and the live load in the permanent travel
lanes with a load factor of 1.0.
5. Pier walls and multi-column piers with struts between columns that have been
designed and detailed as longitudinal traffic barriers according to Section 13.
Where the design choice is to redirect or absorb the collision load, protection shall consist
of one of the following:
• For new or retrofit construction, a minimum 42.0-in. high crash tested rigid TL-5
barrier, as specified in AASHTO LRFD Section 13, located such that the top edge of
the traffic face of the barrier is 3.25 ft or more from the face of the pier component
being protected.
• For retrofit construction, a minimum 42.0-in. high crash tested rigid TL-5 barrier may
be placed closer than 3.25 ft from the top edge of the traffic face of the barrier to
the nearest traffic face of the pier component being protected when there is no other
practical option. Such rigid barriers shall be structurally and geometrically capable of
surviving the crash test as specified in AASHTO LRFD Section 13.
3.99 References
1. AASHTO LRFD Bridge Design Specifications, 8th Edition, November 2017.