Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual PXC e TEC Siemens

Download as pdf or txt
Download as pdf or txt
You are on page 1of 139

SIEMENS

INDUSTRY
Siemens Industries
Building Automation

12001 Network Blvd.


Suite 318
San Antonio, Texas 78249
USA

Phone: (210) 332-2835

10/7/11

FOR INFORMATION
CONTACT
Esteban Diego

O&M DATA FOR


TXSU – Mitte Expansion

601 University Drive


San Marcos, TX 78666

44OP-095017

.
APOGEE Unit Conditioner
Controller — Electronic
Output Owner’s Manual
125-1941 Rev. 4, May, 2005

Siemens Building Technologies, Inc.


Rev. 4, May, 2005
NOTICE
The information contained within this document is subject to change without notice and should not be construed as a
commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility
for any errors that may appear in this document.
All software described in this document is furnished under a license and may be used or copied only in accordance
with the terms of such license.
WARNING
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance
with the instructions manual, may cause interference to radio communications. It has been tested and found to
comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to
provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area is likely to cause interference in which case users at their own expense will be
required to take whatever measures may be required to correct the interference.
SERVICE STATEMENT
Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical
components must be regularly serviced to optimize their operation. All Siemens Building Technologies branch offices
and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system
performance.
For further information, contact your nearest Siemens Building Technologies, Inc. representative.
Copyright 1995—2005 by Siemens Building Technologies, Inc.
TO THE READER
Your feedback is important to us. If you have comments about this manual, please submit them to
SBT_technical.editor@siemens.com
CREDITS
APOGEE is a registered trademark of Siemens Building Technologies, Inc.
Insight for Minicomputers is a registered trademark of Siemens Building Technologies, Inc.
Insight for Personal Computers is a registered trademark of Siemens Building Technologies, Inc.
UniTrak™ is a trademark of Siemens Building Technologies, Inc.
Teflon is a registered trademark of DuPont.

Country of Origin: US
Table of Contents
How To Use This Manual..............................................................................................III
Manual Organization..................................................................................................III
Manual Conventions ..................................................................................................III
Manual Symbols ........................................................................................................IV
Datamate Software ....................................................................................................IV
Getting Help ...............................................................................................................IV
Where To Send Comments .......................................................................................IV
Product Overview..........................................................................................................1
Introduction ................................................................................................................1
Ordering Notes...........................................................................................................2
Hardware Inputs ......................................................................................................3
Hardware Outputs ...................................................................................................3
Power Wiring ...........................................................................................................4
Communication Wiring ............................................................................................4
Controller LED Indicators ........................................................................................4
Temperature Sensors ................................................................................................5
Room Temperature Sensor.....................................................................................5
Duct Temperature Sensor.......................................................................................5
Actuators....................................................................................................................5
Related Equipment ....................................................................................................5
Applications...................................................................................................................7
Basic Operation .........................................................................................................7
Control Temperature Setpoints..................................................................................7
Day/Night Mode .........................................................................................................7
Night Mode Override Switch ......................................................................................7
Control Loops.............................................................................................................7
Calibration..................................................................................................................7
Fail-safe Operation ....................................................................................................7
Secure Mode Operation.............................................................................................8
Heating and Cooling Switchover................................................................................8
Hot Water Reheat ......................................................................................................8
Electric Reheat...........................................................................................................8
Staged Cooling ..........................................................................................................8
Fan Operation ............................................................................................................8
Notes..........................................................................................................................8
Application 2040/2140 Variable Air Volume Pressure Dependent Cooling or Heating.
........................................................................................................................................9
Overview ....................................................................................................................9

I
APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Application 2041/2141 Variable Air Volume Pressure Dependent with Hot Water Reheat
........................................................................................................................................10
Overview ....................................................................................................................10
Application 2050/2150 Two-Pipe Fan Coil Unit Cooling or Heating.........................11
Overview ....................................................................................................................11
Application 2051/2151 Fan Coil Unit Cooling and Heating .......................................12
Overview ....................................................................................................................12
Application 2052/2152 Fan Coil Unit Cooling and Electric Heat ..............................13
Overview ....................................................................................................................13
Application 2053/2153 Fan Coil Unit 2-Stage Cooling and Hot Water Heat ............14
Overview ....................................................................................................................14
Application 2054/2154 Fan Coil Unit Cooling and Electric Heat ..............................15
Overview ....................................................................................................................15
Application 2090/2188 Slave Mode..............................................................................16
Overview ....................................................................................................................16
Using Auxiliary Points ................................................................................................16
Using the Controller as a Point Extension Device .....................................................16
Point Database ..............................................................................................................19
Overview ....................................................................................................................19
Glossary.........................................................................................................................31
Overview ....................................................................................................................31
Index ...............................................................................................................................35

II
How To Use This Manual
This section covers manual organization, conventions, and symbols used in the manual, and
other information that will help you understand and use a Unit Conditioner Controller —
Electronic Output.

Manual Organization
This manual contains the following sections:
• Chapter 1 Product Overview describes the hardware components and the
accessories that are used with the controller.
• Chapter 2 Applications describes the control applications available in the controller.
• Chapter 3 Point Database defines the point database descriptors and includes
address and applications.
• The Glossary describes terms and acronyms.
• The Index helps you find information.

Manual Conventions
The following table lists conventions used in this manual.

Convention Example
Actions that you should Type F for Field panels.
perform are specified in Click OK to save changes and close the dialog box.
boldface font.
Error and system The message Report Definition successfully renamed
messages are displayed appears in the status bar.
in Courier New font.
New terms appearing for The Open Processor continuously executes a user-defined set of
the first time are instructions called the control program.
italicized.

Siemens Building Technologies, Inc. III


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Manual Symbols
The following table lists symbols that are used to draw your attention to important information.

Notation Symbol Meaning


CAUTION: Indicates that equipment damage or loss of data may occur
if the user does not follow a procedure as specified.
WARNING: Indicates that personal injury or loss of life may occur to the
user if a procedure is not performed as specified.

Datamate Software
Datamate is a customer software tool for all controller communications. There are two
versions: Datamate Base, and Datamate Advanced. Datamate Base works on an IBM-
compatible Personal Computer (PC), or a Handheld PC or Pocket PC™ running Windows
CE. Datamate Advanced works only on an IBM-compatible Personal Computer. With
Datamate, you can backup, restore, and edit any APOGEE database (but only Datamate
Advanced allows you to edit points offline). Backing up and restoring a database can be
accomplished while connected to any APOGEE field panel, or to the Building Level Network
(BLN) or Floor Level Network (FLN) device in question. A modem and telephone lines can
also be used. Databases can be saved to a hard or floppy disk and kept for permanent
storage or used as backup.
For more information on Datamate software, refer to the appropriate user guide based on
which version of Datamate you are using (Base or Advanced), or contact your local Siemens
Building Technologies, Inc. representative.

Getting Help
If at any time you find that you need help with a Terminal Box Controller issue not covered in
this manual, contact your local Siemens Building Technologies, Inc. representative.

Where To Send Comments


Your feedback is important to us. If you have comments about this manual, please submit
them to SBT_technical.editor@siemens.com.

IV Siemens Building Technologies, Inc.


1
Product Overview
Introduction
The Unit Conditioner Controller — Electronic Output is the Siemens Building Technologies,
Inc. APOGEE Terminal Equipment Controller used in pressure dependent box, fan coil unit,
and induction unit applications (Figure 1-1). It provides Direct Digital Control (DDC) for 14
applications. The controller can operate as an independent, stand-alone DDC room controller
or it can be networked with an APOGEE field panel.
The controller provides all termination, input/output, system, and local communication
connections. The controller hardware consists of the controller with cover and mounting
bracket.

Table 1-1 lists thethat Table 1 -1. Unit Conditioner Controller—Electronic Output Applications.
Standard Applications Secure Mode Applications
2040 Variable Air Volume Pressure Dependent 2140 Variable Air Volume Pressure Dependent Cooling or
Cooling or Heating Heating with Secure Mode
2041 Variable Air Volume Pressure Dependent 2141 Variable Air Volume Pressure Dependent with Hot Water
with Hot Water Reheat Reheat with Secure Mode
2050 Two-Pipe Fan Coil Unit Cooling or Heating 2150 Two-Pipe Fan Coil Unit Cooling or Heating with Secure
Mode
2051 Fan Coil Unit Cooling and Heating 2151 Fan Coil Unit Cooling and Heating with Secure Mode
2052 Fan Coil Unit Cooling and Electric Heat 2152 Fan Coil Unit Cooling and Electric Heat with Secure
Mode
2053 Fan Coil Unit 2-Stage Cooling and Hot Water 2153 Fan Coil Unit 2-Stage Cooling and Hot Water Heat with
Heat Secure Mode
2054 Fan Coil Unit Cooling and Electric Heat 2154 Fan Coil Unit Cooling and Electric Heat with Secure
Mode
2090 Slave Mode 2188 Slave Mode with Secure Mode

NOTE: Application 2054 and 2154 can also control a Variable Air Volume pressure
dependent terminal box with electric heat. See the application description for
Application 2054 and 2154.

Siemens Building Technologies, Inc. 1


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Ordering Notes
Unit Conditioner Controller – Electronic Output 540-110

Unit Conditioner Controller – Electronic Output with Secure Mode 540-110C

COVER

CONTROLLER
BOARD

MOUNTING
HOLE
(2)

24 V-AC DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 DI 3 DI 2 FLN
NO C NO C NO C NO C NO C NO C AI 3 TRUNK
E C H 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TX RX + - S BST RTS

MOUNTING
RAIL
C H
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 + - S
TEC0168R5

POWER DO LEDS
TRUNK FLN TRUNK
TERMINATIONS TERMINATIONS

INPUT/OUTPUT TERMINATIONS
TRANSMIT LED

RECEIVE LED BST LED ROOM TEMPERATURE


SENSOR/MMI PORT

Figure 1-1. Unit Conditioner Controller — Electronic Output.

2 Siemens Building Technologies, Inc.


Product Overview

Hardware Inputs

Analog
• Room temperature sensor (RTS) (10K Ω thermistor)
• Room temperature setpoint dial (optional)
• Duct temperature sensor (optional) — Application 2040, 2140 (100K Ω thermistor)
• Pipe temperature sensor (optional) — Application 2050, 2150 (100K Ω thermistor)

Digital
• Night mode override (optional)
• Wall switch (optional)

Hardware Outputs

Analog
• None

Digital
Application

• Damper actuator 2040, 2140, 2041, 2141

• Valve actuator; or, damper 2054, 2154


actuator

• First valve actuator (required) 2041, 2141, 2050, 2150

• Second valve actuator (optional) 2041, 2141, 2050, 2150

• Second Cooling valve actuator 2051, 2151

• Heating valve actuator 2051, 2151, 2053, 2153

• Fan (switched 24 Vac, pilot duty) 2050, 2150, 2051, 2151, 2052, 2152, 2053,
2153, 2054, 2154
• Stage 1 cooling (2-position valve 2052, 2152, 2053, 2153
actuator, or cooling compressor)

• Stage 2 cooling (2-position valve 2052, 2152, 2053, 2153


actuator, or cooling compressor)

• Stage 1 electric heat 2052, 2152, 2054, 2154

• Stage 2 electric heat 2052, 2152, 2054, 2154

• Stage 3 electric heat 2052, 2152, 2054, 2154

Siemens Building Technologies, Inc. 3


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Power Wiring
The controller is powered by 24 Vac. Power wiring connects to the two screw terminals on
the controller labeled “C” (Common) and “H” (Hot) on the terminal block labeled 24 VAC. No
earth ground connection is required (Figure 1-2).

Communication Wiring
The controller connects to the field panel by means of a Floor Level (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled "+"
(positive), "-" (negative), and "S" (ShieId) (Figure 1-3).

FLN TRUNK
24 V-AC DO 1 DO 2 DO 3 DO 4 DO 5 + - S
NO C NO C NO C NO C NO C NO
E C H 1 2 3 4 5 6 7 8 9 10 11 1

1 2 3 4 5 6 7 8 9 10 11 12

COMMON
(SHIELD) (SHIELD)
TEC0470R1

24 VAC HOT (-)


(-)
CONTROLLER POWER WIRING
(+) (+)
TEC0253R2

NOTE: NO EARTH GROUND CONNECTION

Figure 1-2. Power Wiring. Figure 1-3. Communication Wiring.

Controller LED Indicators


The controller has nine Light Emitting Diode (LED) indicators (Figure 1-1). Table 1-1 lists the
type, the abbreviation on the controller, and the indication of each LED.

Table 1-1. Controller LEDs.

LED Type Label LED Number Indication


(if present)*
DO LED 1 - LED 6 1-6 Indicates the ON/OFF status of the DO
associated with it. A glowing LED indicates that
the DO is energized.
Transmit TX 7 Indicates, when flashing, that the controller is
transmitting information to the field panel.
Receive RX 8 Indicates, when flashing, that the controller is
receiving information from the field panel.
BST BST 9 Indicates, when flashing ON and OFF once per
”Basic Sanity second, that the controller is functioning
Test” properly.
* Some LED labels and numerals may be hidden by the controller cover.

4 Siemens Building Technologies, Inc.


Product Overview

Temperature Sensors
Temperature sensors used with the Unit Conditioner Controller — Electronic Output include
an electronic room temperature sensor and an optional duct temperature sensor.

Room Temperature Sensor


The Unit Conditioner Controller—Electronic Output room temperature sensor connects to the
controller by means of a cable terminated at both ends with a 6-conductor RJ-11 plug-in
connector. See Figure 1-1 for the location of the room temperature sensor/Man Machine
lnterface (MMl) port.

Duct Temperature Sensor


An optional duct temperature sensor provides duct air temperature sensing input to the
controller.
For more information about temperature sensors, contact your local Siemens Building
Technologies, Inc. representative.

Actuators
Actuators used with the Unit Conditioner ControIler — Electronic Output include electronic
damper motors, electronic valve motors, and electronic valve assemblies. These actuators
are powered through the controller to position reheat valves or supply air dampers.

Related Equipment
Pipe Temperature Sensor (optional)
Damper actuator(s)
Valve actuator(s)
Duct Temperature Sensor (100K Ω) (optional)
TEC Room Temperature Sensor
Contact your local Siemens Building Technologies, Inc. representative for product numbers and more
information.

Siemens Building Technologies, Inc. 5


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

6 Siemens Building Technologies, Inc.


2
Applications
Basic Operation
The Unit Conditioner Controller — Electronic Output provides Direct Digital Control (DDC)
technology for pressure dependent Variable Air Volume (VAV), fan coil, and induction unit
applications. The pressure dependent VAV applications control space temperature by
directly driving the damper. There is no airflow measurement and no explicit flow control.
The fan coil and induction applications control temperature with hot water or up to three
stages of electric reheat, chilled water, or up to two stages of direct expansion cooling.

Control Temperature Setpoints


The controller maintains a specified temperature based on Day/Night mode or the setpoint
dial (if used).

Day/Night Mode
The controller maintains the specified day setpoint temperature during daytime hours and the
specified night setpoint at night.

Night Mode Override Switch


If the RTS has an override switch, it can be used to command the controller into day mode.
This only affects a controller in night mode.

Control Loops
Temperature Loop – Heating Loop – Cooling Loop – maintains temperature setpoint by
modulating the heating source, cooling source, or damper.

Calibration
Calibration may be set to take place automatically or manually.
..Valve – Calibration of a hot water valve (if used) is done by briefly commanding the valve
closed. .

Fail-safe Operation
If the RTS fails, then the controller operates using the last known temperature value.

Siemens Building Technologies, Inc. 7


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Secure Mode Operation


The Unit Conditioner Controller—Electronic Output with Secure Mode, product number 540-
110C, has Secure Mode. When Secure Mode is enabled, any attempts to make point
changes in the TEC through the MMI port or connected RTS will be rejected and result in an
error message indicating that the priority is too low. This mode can only be enabled/disabled
through the Insight workstation.

Heating and Cooling Switchover


The heating/cooling switchover determines whether the controller is in heating or cooling
mode by monitoring the room temperature and the demand for heating and cooling (as
determined by the temperature control loops).
Hot Water ReheatWhen the controller is in cooling mode, the heating valve(s) are closed.
The heating loop modulates the heating valve(s) to warm up the room. In cooling mode, the
heating valve is closed.
If more than one valve is present, the two valves can be sequenced in series or parallel.

Electric Reheat
CAUTION:
Verify that the equipment is supplied with safeties by others to ensure that there is airflow
across the heating coils when they are to be energized.
The heating loop controls up to three stages of electric reheat to warm up the room. The
electric reheat is time modulated using a duty cycle. When the controller is in cooling mode,
the electric heat is OFF at all times.

Staged Cooling
When the controller is in cooling mode, up to two stages of cooling can be cycled to maintain
temperature. In heating mode, the cooling stages are off.

Fan Operation
In day mode, the fan can be set to be ON all the time or cycle on when heating or cooling is
needed.
In night mode, the fan cycles ON when heating or cooling is needed.

Notes
1. If the temperature swings in the room are excessive, or if there is trouble in maintaining
the setpoint, contact your local Siemens Building Technologies, Inc. representative for
more information.
2. The Unit Conditioner Controller — Electronic Output, as shipped from the factory, keeps
all associated equipment OFF. The controller and its equipment are released to
application control at start-up.

8 Siemens Building Technologies, Inc.


Applications

Application 2040/2140 Variable Air Volume Pressure


Dependent Cooling or Heating.
Overview
In Application 2040 and 2140, the controller modulates the supply air damper of the terminal
box for cooling and heating. In order for it to work properly, the central air-handling unit must
provide cool supply air in the cooling mode and warm supply air in the heating mode. See
Figure 2-1.
SUPPLY AIR
DAMPER

SUPPLY
AIR

THERMISTOR
TEMPERATURE
SENSOR
MODULATING MECHANICAL STOPS
(OPTIONAL)
DAMPER TO PROVIDE MAXIMUM
ACTUATOR AND MINIMUM
AIR FLOW SETTINGS
PROVIDED BY OTHERS

24 V-AC
DO1
DO2
DO3
DO4
DO5
DO6
DI3/AI3
DI2
N.O. FLN TRUNK
TEC2040CDR3

RTS
WALL
SWITCH UNIT CONDITIONER
(OPTIONAL) RTS CONTROLLER

Figure 2-1. Application 2040 and 2140 Control Drawing.

Siemens Building Technologies, Inc. 9


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Application 2041/2141 Variable Air Volume Pressure


Dependent with Hot Water Reheat
Overview
In Application 2041 and 2141, the controller modulates the supply air damper of the terminal
box for cooling and modulates a reheat valve(s) for heating. When heating, minimum airflow
(limited by a mechanical stop on the terminal box) is provided to the room. In order for the
terminal box to work properly, the central air-handling unit must provide cool supply air. See
Figure 2-2.

SUPPLY AIR
DAMPER

SUPPLY REHEAT REHEAT


AIR COIL 2 COIL 1

MODULATING
DAMPER
ACTUATOR
REHEAT
VALVE 2
(OPTIONAL) REHEAT
VALVE 1

24 V-AC
DO1
DO2
DO3
DO4
DO5
DO6
DI3/AI3
DI2
MECHANICAL STOPS N.O. FLN TRUNK
RTS
TEC2041CDR3

TO PROVIDE MAXIMUM
AND MINIMUM WALL
AIR FLOW SETTINGS SWITCH UNIT CONDITIONER
(OPTIONAL) RTS CONTROLLER
PROVIDED BY OTHERS

Figure 2-2. Application 2041 and 2141 Control Drawing.

10 Siemens Building Technologies, Inc.


Applications

Application 2050/2150 Two-Pipe Fan Coil Unit Cooling


or Heating
Overview
In Application 2050 and 2150, the controller modulates a valve in the fan coil unit for heating
or cooling mode. It can also control an optional second valve for heating. The fan coil unit
also has a fan to circulate room air. In order for the fan coil unit to work properly, the central
plant must provide chilled water in the cooling mode and hot water in the heating mode. See
Figure 2-3.
HEATING
VALVE
(OPTONAL) SAFETIES
BY
OTHERS

HEATING /
COOLING
HEATING COIL VALVE 24 V-AC
DO1
HEATING / COOLING DO2
COIL DO3
24 V-AC
FAN DO4
CONTACTOR DO5
DO6
DI3/AI3
FAN DI2
THERMISTOR FLN TRUNK
N.O.
TEC2050BCDR4

TEMPERATURE RTS
SENSOR
WALL
(OPTIONAL) UNIT CONDITIONER
SWITCH RTS
(OPTIONAL) CONTROLLER

Figure 2-3. Application 2050 and 2150 Control Drawing.

Siemens Building Technologies, Inc. 11


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Application 2051/2151 Fan Coil Unit Cooling and


Heating
Overview
In Application 2051 and 2151, the controller modulates separate valves in the fan coil unit for
cooling and heating. The fan coil unit also has a fan to circulate room air. In order for the fan
coil unit to work properly, the central plant must provide chilled and hot water. See Figure 2-4.
HEATING
VALVE
SAFETIES
BY
OTHERS

COOLING
VALVE
HEATING COIL 24 V-AC
DO1
COOLING COIL DO2
DO3
DO4
DO5
24 V-AC DO6
FAN DI3/AI3
FAN CONTACTOR DI2
N.O. FLN TRUNK
TEC2051CDR3

RTS
WALL
SWITCH UNIT CONDITIONER
RTS
(OPTIONAL) CONTROLLER

Figure 2-4. Application 2051 and 2151 Control Drawing.

12 Siemens Building Technologies, Inc.


Applications

Application 2052/2152 Fan Coil Unit Cooling and


Electric Heat
Overview
In Application 2052 and 2152, the controller energizes a maximum of two stages of cooling
and a maximum of three stages of electric heat in the fan coil unit. The fan coil unit also has a
fan to circulate room air. See Figure 2-5.

SAFETIES
BY
N.C. OTHERS
2 - POSITION
COOLING
VALVES N.C.
STAGE 1
3 - STAGE
ELECTRIC 24 V-AC
ELECTRIC HEATING
HEATING DO1
CONTACTOR DO2
G COIL DO3
COOLIN STAGE 2
DO4
ELECTRIC
DO5
HEATING
DO6
CONTACTOR
DI3/AI3
FAN STAGE 3 DI2
ELECTRIC N.O. FLN TRUNK
TEC2052CDR3

HEATING RTS
CONTACTOR WALL
SWITCH UNIT CONDITIONER
FAN (OPTIONAL) RTS
CONTROLLER
CONTACTOR

Figure 2-5. Application 2052 and 2152 Control Drawing.

Siemens Building Technologies, Inc. 13


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Application 2053/2153 Fan Coil Unit 2-Stage Cooling


and Hot Water Heat
Overview
In Application 2053 and 2153, the controller energizes a maximum of two stages of cooling
and a hot water valve for heating in the fan coil unit. The fan coil unit also has a fan to
circulate room air. In order for the fan coil unit to work properly, the central plant must provide
hot water in the heating season. See Figure 2-6.
HEATING SAFETIES
VALVE BY
OTHERS

HEATING
24 V-AC
COIL
N.C. DO1
2 - POSITION DO2
G COIL COOLING DO3
COOLIN
VALVES DO4
N.C.
DO5
DO6
DI3/AI3
FAN DI2
N.O. FLN TRUNK
TEC2053CDR3

RTS
WALL
FAN SWITCH UNIT CONDITIONER
CONTACTOR (OPTIONAL) RTS
CONTROLLER

Figure 2-6. Application 2053 and 2153 Control Drawing.

14 Siemens Building Technologies, Inc.


Applications

Application 2054/2154 Fan Coil Unit Cooling and


Electric Heat
Overview
In Application 2054 and 2154, the controller energizes a valve or damper for cooling and
controls a maximum of three stages of electric heat for heating in the fan coil unit. The fan
coil unit also has a fan to circulate room air. This application can also be used to control a
pressure dependent terminal box with electric heat. If a damper is being controlled, then the
central plant must supply chilled air in the cooling mode in order for the terminal box to work
properly. See Figure 2-7 and Figure 2-8.
COOLING SAFETIES
VALVE BY
OTHERS

STAGE 1
3 - STAGE
ELECTRIC 24 V-AC
ELECTRIC HEATING
HEATING DO1
CONTACTOR DO2
G COIL DO3
COOLIN STAGE 2
DO4
ELECTRIC
DO5
HEATING
DO6
CONTACTOR
DI3/AI3
FAN STAGE 3 DI2
ELECTRIC N.O. FLN TRUNK
TEC2054CDR3

HEATING RTS
CONTACTOR WALL
SWITCH UNIT CONDITIONER
FAN RTS
(OPTIONAL) CONTROLLER
CONTACTOR

Figure 2-7. Application 2054 and 2154 with Cooling Valve Control Drawing.
SUPPLY AIR
DAMPER

STAGE 1 MODULATING
ELECTRIC DAMPER
HEATING ACTUATOR
CONTACTOR

STAGE 2
ELECTRIC
HEATING 24 V-AC
CONTACTOR DO1
DO2
DO3
STAGE 3 DO4
ELECTRIC DO5
HEATING DO6
CONTACTOR DI3/AI3
DI2
MECHANICAL STOPS N.O. FLN TRUNK
TEC2054BCDR5

TO PROVIDE MAXIMUM RTS


AND MINIMUM WALL
AIR FLOW SETTINGS SWITCH UNIT CONDITIONER
(OPTIONAL) RTS CONTROLLER
PROVIDED BY OTHERS

Figure 2-8. Application 2054 and 2154 with Modulating Damper Control Drawing.

Siemens Building Technologies, Inc. 15


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Application 2090/2188 Slave Mode


Overview
Application 2090 is the slave mode application for the Unit Conditioner Controller —
Electronic Output (P/N 540-110). Application 2188 is the slave mode application with Secure
Mode (P/N 540-110C). Slave mode is the default application that comes up when power is
first applied to the controller. Slave mode provides no control. Its purpose is to allow the
operator to perform equipment checkout before a control application is put into effect and to
set some basic controller parameters (CTLR ADDRESS, APPLICATION, etc.).

Using Auxiliary Points


It is possible to have extra points available on a Unit Conditioner Controller — Electronic
Output in addition to the ones used by the current application that is running in the controller.
If these extra points are to be controlled by a field panel, then they must be unbundled at the
field panel.

Using the Controller as a Point Extension Device


If the controller is only used as a point extension device, with no control application in affect,
then its application must be set to slave mode and the points must be unbundled at the field
panel. All points must be controlled from the field panel in order to be used.
All DOs can be used as separate DOs. They can also be used in pairs, (DO 1 and DO 2),
(DO 3 and DO 4), and (DO 5 and DO 6), to control a motor as shown in the example.
NOTE: If using either a motor or DOs as auxiliary points, be sure to set MTR SETUP
(Point 58) to the correct value. See Table 2-2. If using a pair of DOs to control a
motor, then the DOs can not be unbundled or commanded separately. Only MTR
1 COMD (Point 48), MTR 2 COMD (Point 52), and MTR3 COMD (Point 37) can
be unbundled to control the motors.

Table 2-2. Motor Enable/Reverse Values for MTR SETUP (Point 58).
Motor 1 Enabled Motor 1 Enabled and Reversed Motor 1 Not Used
Motor 2 Motor 2 Motor 2 Motor 2 Motor 2 Motor 2 Motor 2 Motor 2 Motor 2
Not Used Enabled Enabled Not Used Enabled Enabled Not Used Enabled Enabled
and and and
Reversed Reversed Reversed
Motor 3 1 5 13 3 7 15 0 4 12
Not Used
Motor 3 17 21 29 19 23 31 16 20 28
Enabled
Motor 3 49 53 61 51 55 63 48 52 60
Enabled
and
Reversed

16 Siemens Building Technologies, Inc.


Applications

Example
If using DO 1 and DO 2 as the physical terminations for a direct acting motor, then follow
these steps:

Set MTR SETUP to 1 to enable the motor.


1. Unbundle MTR 1 COMD at the field panel to command the motor from the field panel.
Contact your local Siemens Building Technologies, Inc. representative for other combinations
of DOs and motors.

Siemens Building Technologies, Inc. 17


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

18 Siemens Building Technologies, Inc.


3
Point Database
Overview
Chapter 3 presents a description of the Unit Conditioner Controller — Electronic Output point
database including point descriptors, point addresses, and a listing of applications in which
each point is found.

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
CTLR ADDRESS 01 All Identifies the controller on the FLN trunk. 1.000 0.000
APPLICATION 02 All The identification number of the program 1.000 0.000
running in the controller.
RMTMP OFFSET 03 2140, 2141 Compensates for deviations between the 0.250 -31.75
2150, 2151 value of ROOM TEMP (Point 4) and the (0.140) (-17.78)
2152, 2153 actual room temperature. This corrected
2154, 2188 value is displayed in CTL TEMP (Point
78).
RMTMP OFFSET + ROOM TEMP =
CTL TEMP
ROOM TEMP {04}3 All Actual reading from the room 0.250 48.000
temperature sensor. (0.140) (8.889)
HEAT.COOL {05} All except Current mode of operation for – –
2090, 2188 applications that can be in either a
heating mode or a cooling mode.
DAY CLG STPT 06 All except The temperature setpoint, in degrees, 0.250 48.000
2090, 2188 that the controller maintains during day (0.140) (8.889)
periods in cooling mode if a room
temperature sensor setpoint dial is not
present or is not used. See STPT DIAL
(Point 14).
DAY HTG STPT 07 All except The temperature setpoint, in degrees, 0.250 48.000
2090, 2188 that the controller maintains during day (0.140) (8.889)
periods in heating mode if a room
temperature sensor setpoint dial is not
present or is not used. See STPT DIAL
(Point 14).
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

Siemens Building Technologies, Inc. 19


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
NGT CLG STPT 08 All except The temperature setpoint, in degrees, 0.250 48.000
2090, 2188 that the controller maintains during night (0.140) (8.889)
periods in cooling mode.
NGT HTG STPT 09 All except The temperature setpoint, in degrees, 0.250 48.000
2090, 2188 that the controller maintains during night (0.140) (8.889)
periods in heating mode.
RM STPT MIN 11 All except The minimum temperature setpoint, in 0.250 48.000
2090, 2188 degrees, that the controller can use from (0.140) (8.889)
the setpoint dial. This overrides any
temperature setpoint from the setpoint
dial that falls below this minimum.
RM STPT MAX 12 All except The maximum temperature setpoint, in 0.250 48.000
2090, 2188 degrees, that the controller can use from (0.140) (8.889)
the setpoint dial. This overrides any
temperature setpoint from the setpoint
dial that falls above this maximum.
RM STPT DIAL {13}3 All The temperature setpoint, in degrees, 0.250 48.000
from the room temperature sensor (not (0.140) (8.889)
available on all temperature sensor
models). This setpoint will be used for
control in day mode (heating or cooling)
when enabled by STPT DIAL (Point 14).
STPT DIAL 14 All except YES indicates that there is a room – –
2090, 2188 setpoint dial on the room temperature
sensor and it is to be used as the
temperature setpoint for control in day
mode. NO indicates that the appropriate
preset setpoint (Point 6) will be used as
the temperature setpoint for control in
day heating mode or cooling mode.
Valid input. YES or NO.
AUX TEMP {15} All except Actual reading from a 100K Ω thermistor 0.500 37.500
2040, 2140 connected to the controllers Al 3 input. (0.280) (3.056)
2050, 2150 When a thermistor is connected at Al 3,
DI 3 is not available. See DI 3 (Point
25).
SUPPLY TEMP {15} 2040, 2140 Actual reading from a 100K Ω thermistor 0.500 37.500
2050, 2150 connected to the controller's Al 3 input. (0.280) (3.056)
The controller uses this value to
determine whether it is in heating mode
or cooling mode.
VLV 1 START 16 2041, 2141 When HTG LOOPOUT (Point 80) is 0.400 0.000
2050, 2150 above this value, Valve 1 starts to open.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

20 Siemens Building Technologies, Inc.


Point Database

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
VLV 1 END 17 2041, 2141 When HTG LOOPOUT (Point 80) is 0.400 0.000
2050, 2150 below this value, valve 1 is at the end of
its stroke.
WALL SWITCH 18 All YES indicates that the controller is to – –
monitor the status of a wall switch that is
connected to DI 2. NO indicates that the
controller will not monitor the status of a
wall switch, even if one is connected.
Valid input: YES or NO.
DI OVRD SW {19}3 All Actual indication of the status of the – –
override switch (not physically available
on all temperature sensor models) at the
room temperature sensor. ON indicates
that the switch is being pressed. OFF
indicates that the switch is released.
Valid input: ON or OFF.
OVRD TIME 20 All except The amount of time, in hours, that the 1.000 0.000
2090, 2188 controller will operate in day mode when
the override switch is pressed while the
controller is in night mode.
NGT OVRD {21} All except Indicates the mode that the controller is – –
2090, 2188 operating in with respect to the override
switch. NIGHT indicates that the switch
has not been pressed and the override
timer is not active. DAY indicates that
the switch has been pressed and the
override timer is active. The controller
then uses a day mode temperature
setpoint. This point is only in effect when
DAY.NGT (Point 29) indicates night
mode.
VLV 2 START 22 2041,2141 When HTG LOOPOUT (Point 80) is 0.400 0.000
2050, 2150 above this value, Valve 2 starts to open.
VLV 2 END 23 2041, 2141 When HTG LOOPOUT (Point 80) is 0.400 0.000
2050, 2150 below this value, valve 2 is at the end of
its stroke.
DI 2 {24} All Actual status of a contact connected to – –
the controller at DI 2. ON indicates that
the contact is closed; OFF indicates that
the contact is open. If a wall switch is
used, then it is connected to DI 2. See
WALL SWITCH (Point 18).
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

Siemens Building Technologies, Inc. 21


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
3
DI 3 {25} All except Actual status of a contact connected to – –
2040, 2140, the controller at DI 3/Al 3. ON indicates
2050, 2150 that the contact is closed; OFF indicates
that the contact is open. When a contact
is connected at DI 3, Al 3 is not
available. See AUX TEMP (Point 15).
DAY.NGT {29} All Indicates the mode in which the – –
controller is operating. Day temperature
setpoints will be used in day mode.
Night temperature setpoints will be used
in night mode. This point is normally set
by the field panel.
MTR 3 COMD {37} 2040,2140, The value to which the Motor 3 actuator 0.400 0.000
2090, 2188 is commanded in percent of full value.
VLV 2 COMD {37} 2041, 2141 The value to which the Valve 2 actuator 0.400 0.000
is commanded in percent of full travel
for applications using a second water
valve.
MTR 3 POS {38} 2040, 2140, The current position of the Motor 3 0.400 0.000
2090, 2188 actuator in percent of full travel. This
value is calculated based on motor run
time.
VLV 2 POS {38} 2041, 2141 The current position of Valve 2 in 0.400 0.000
percent of full travel. This value is
calculated based on valve run time.
MTR 3 TIMING 39 2040, 2140 The time required for the Motor 3 1.000 0.000
2041, 2141, actuator to travel from the full closed
2090, 2188 position to the full open position.
CLG STG 1 {41} 2052, 2152 This point is DO 1 in applications with – –
2053, 2153 staged cooling. This digital output
controls the contactor for the first
cooling stage and has a status of ON or
OFF.
DO 1 {41} All except Digital output 1 controls a 24 Vac load – –
2052, 2152 with an ON or OFF status. If Motor 1 is
2053, 2153 enabled, then DO 1 is coupled with DO
2 to control an actuator.
CLG STG 2 {42} 2052, 2152, This point is DO 2 in applications with – –
2053, 2153 staged cooling. This digital output
controls the contactor for the second
cooling stage and has a status of ON or
OFF.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

22 Siemens Building Technologies, Inc.


Point Database

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
DO 2 {42}3 All except Digital output 2 controls a 24 Vac load – –
2052, 2152, with an ON or OFF status. If Motor 1 is
2053, 2153 enabled, then DO 2 is coupled with DO
1 to control an actuator.
DO 3 {43} All except Digital output 3 controls a 24 Vac load – –
2052, 2152, with an ON or OFF status. If Motor 2 is
2054, 2154 enabled, then DO 3 is coupled with DO
4 to control an actuator.

HTG STG 1 {43} 2052, 2152 This point is DO 3 in applications with – –


2054, 2154 electric reheat. This digital output
controls the contact for the first stage of
heating and has a status of ON or OFF.
DO 4 {44} All except Digital output 4 controls a 24 Vac load – –
2052, 2152 with an ON or OFF status. If Motor 2 is
2054, 2154 enabled, then DO 4 is coupled with DO
3 to control an actuator.
HTG STG 2 {44} 2052, 2152 This point is DO 4 in applications with – –
2054, 2154 electric reheat. This digital output
controls the contact for the second
stage of heating and has a status of ON
or OFF.
DO 5 {45} All except Digital output 5 controls a 24 Vac load – –
2052, 2152 with an ON or OFF status. If Motor 3 is
2054, 2154 enabled, then DO 5 is coupled with DO
6 to control an actuator.
HTG STG 3 {45} 2052, 2152 This point is DO 5 in applications with – –
2054, 2154 electric reheat. This digital output
controls the contact for the third stage
of heating and has a status of ON or
OFF.
DO 6 {46} 2040, 2140 Digital output 6 controls a 24 Vac load – –
2041, 2141 with an ON or OFF status. If Motor 3 is
2090, 2188 enabled, then DO 6 is coupled with DO
5 to control an actuator.
FAN {46} All except This point is a digital output used to – –
2040, 2140 control the fan. ON indicates that the
2041, 2141 DO is energized; OFF indicates that the
2090, 2188 DO is de-energized.
DMPR COMD {48} 2040, 2140 The value to which the damper motor is 0.400 0.000
2041, 2141 commanded in percent of full travel.
VLV 1 COMD {48} 2050, 2150 The value to which the Valve 1 actuator 0.400 0.000
2051, 2151 is commanded in percent of full travel
2054, 2154 for applications using a water valve.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

Siemens Building Technologies, Inc. 23


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
MTR 1 COMD {48}3 2090, 2188 The value to which the Motor 1 actuator 0.400 0.000
is commanded in percent of full travel.
DMPR POS {49} 2040, 2140, The current position of the damper 0.400 0.000
2041, 2142 motor in percent of full travel. This value
is calculated based on motor run time.
VLV POS {49} 2050, 2150 The current position of Valve 1 in 0.400 0.000
2051, 2151 percent of full travel for applications
2054, 2154 using a water valve. This value is
calculated based on motor run time.
MTR 1 POS {49} 2090, 2188 The current position of damper Motor 1 0.400 0.000
in percent of full travel. This value is
calculated based on motor run time.
See MTR1 TIMING (Point 51).
MTR1 TIMING 51 All except The time required for the Motor 1 1.000 0.000
2052, 2152 actuator to travel from full closed to the
2053, 2153 full open position.
MTR 2 COMD {52} 2040, 2140 The value to which the Motor 2 actuator 0.400 0.000
2090, 2188 is commanded in percent of full travel
(for use as an auxiliary slave point).

VLV COMD {52} 2053, 2153 The value to which the valve actuator is 0.400 0.000
commanded in percent of full travel for
applications using a water valve.
VLV 1 COMD {52} 2041, 2141 The value to which the Valve 1 actuator 0.400 0.000
is commanded in percent of full travel
for applications using a water valve.

VLV 2 COMD {52} 2050, 2150 The value to which the Valve 2 actuator 0.400 0.000
2051, 2151 is commanded in percent of full travel
for applications using a water valve.
MTR 2 POS {53} 2040, 2140 The current position of the Motor 2 0.400 0.000
2090, 2188 actuator in percent of full travel (for use
as an auxiliary slave point). This value
is calculated based on motor run time.
See MTR2 TIMING (Point 55).

VLV POS {53} 2053, 2153 The current position of the valve in 0.400 0.000
percent of full travel for applications
using a water valve. This value is
calculated based on motor run time.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

24 Siemens Building Technologies, Inc.


Point Database

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
VLV 1 POS {53}3 2041, 2141 The current position of Valve 1 in 0.400 0.000
percent of full travel for applications
using a water valve. This value is
calculated based on motor run time.
VLV 2 POS {53} 2050, 2150 The current position of Valve 2 in 0.400 0.000
2051, 2151 percent of full travel for applications
using a water valve. This value is
calculated based on motor run time.
MTR2 TIMING 55 All except The time required for the Motor 2 1.000 0.000
2052, 2152 actuator to travel from full closed to the
2054, 2154 full open position.
MTR1 ROT ANG 56 All except The number of degrees that Motor 1 is 1.000 0.000
2052, 2152 free to travel.
2053, 2153
MTR2 ROT ANG 57 All except The number of degrees that Motor 2 is 1.000 0.000
2052, 2152 free to travel.
2054, 2154
MTR SETUP 58 All The configuration setup code for Motors 1.000 0.000
1 and 2. This enables the motors
individually and sets each motor to be
either direct or reverse acting.
Note: When a motor is enabled, its
associated DOs are enabled.
DO DIR.REV 59 All The configuration setup code for DOs. 1.000 0.000
Allows the DOs to be direct or reverse
acting (enabled equals energized or
enabled equals de-energized).
CYCLE FAN 60 All except ON indicates the fan will cycle during – –
2040, 2140 day mode. OFF indicates the fan is on
2041, 2141 all the time in day mode.
2090, 2188
COOL TEMP 61 2040, 2140 The discharge air temperature where 0.500 37.500
2050, 2150 the controller will switch from heating (0.280) (3.056)
mode to cooling mode. Used only in
applications with SUPPLY TEMP (Point
15).
HEAT TEMP 62 2040, 2140 The discharge air temperature where 0.500 37.500
2050, 2150 the controller will switch from cooling (0.280 (3.056)
mode to heating mode. Used only in
applications with SUPPLY TEMP (Point
15).
CLG P GAIN 63 All except The proportional gain value for the 0.250 0.000
2090, 2188 cooling temperature control loop. (0.450)
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

Siemens Building Technologies, Inc. 25


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
CLG I GAIN 64 All except The integral gain value for the cooling 0.001 0.000
2090, 2188 temperature control loop. (0.002)
CLG D GAIN 65 All except The derivative gain value for the cooling 2.000 0.000
2090, 2188 temperature control loop. (3.600)
CLG BIAS 66 All except The biasing of the cooling temperature 0.400 0.000
2090, 2188 control loop. See CLG LOOPOUT
(Point 79).
HTG P GAIN 67 All except The proportional gain value for the 0.250 0.000
2090, 2188 heating temperature control loop. (0.450)
HTG I GAIN 68 All except The integral gain value for the heating 0.001 0.000
2090, 2188 temperature control loop. (0.002)
HTG D GAIN 69 All except The derivative gain value for the heating 2.000 0.000
2090, 2188 temperature control loop. (3.600)
HTG BIAS 70 All except The biasing of the heating temperature 0.400 0.000
2090, 2188 control loop. See HTG LOOPOUT
(Point 80).
CLG 1 ON 71 2052, 2152, The value, in percent, which the cooling 0.400 0.000
2053, 2153 loop (CLG LOOPOUT, Point 79) must
exceed for the first stage of cooling to
turn ON.
CLG 1 OFF 72 2052, 2152, The value, in percent, which the cooling 0.400 0.000
2053, 2153 loop (CLG LOOPOUT, Point 79) must
go below for the first stage of cooling to
turn OFF.
CLG 2 ON 73 2052, 2152 The value, in percent, which the cooling 0.400 0.000
2053, 2153 loop (CLG LOOPOUT, Point 79) must
exceed for the second stage of cooling
to turn ON.
CLG 2 OFF 74 2052, 2152 The value, in percent, which the cooling 0.400 0.000
2053, 2153 loop (CLG LOOPOUT, Point 79) must
go below for the second stage of
cooling to turn OFF.
CLG STG CNT 75 2052, 2152 The number of cooling stages used by 1.000 0.000
2053, 2153 the application. DOs associated with
unused stages may be used as spare
DOs.
CLG MIN ON 76 2052, 2152 The minimum time, in minutes, which 1.000 0.000
2053, 2153 the cooling stages will remain ON
before turning OFF.
CLG MIN OFF 77 2052, 2152 The minimum time, in minutes, which 1.000 0.000
2053, 2153 the cooling stages will remain OFF
before turning ON.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

26 Siemens Building Technologies, Inc.


Point Database

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
CTL TEMP {78}3 All except The temperature used as input for the 0.250 48.000
2090, 2188 temperature control loops. This value (0.140) (8.889)
will be the same as the value in ROOM
TEMP (Point 4), unless it is overridden.
CLG LOOPOUT {79} All except The cooling temperature control loop 0.400 0.000
2090, 2188 output value, in percent.
HTG LOOPOUT {80} All except The heating temperature control loop 0.400 0.000
2090, 2188 output value, in percent.
AVG HEAT OUT {81} 2052, 2054 This value is equal to HTG LOOPOUT x 2.000 0.000
HTG STG CNT in applications with
electric heat. It is used to determine
what stages of electric heat are used for
a given loop output value. The ranges
for the value are determined by the
number of stages used: 0 to 100 for 1
stage of electric heat, 0 to 200 for 2
stages of electric heat, and 0 to 300 for
3 stages of electric heat.
AVG HEAT OUT {81} 2152, 2154 This value is equal to HTG LOOPOUT x 0.400 0.000
HTG STG CNT in applications with
electric heat. It is used to determine
what stages of electric heat are used for
a given loop output value. The ranges
for the value are determined by the
number of stages used: 0 to 100 for 1
stage of electric heat, 0 to 200 for 2
stages of electric heat, and 0 to 300 for
3 stages of electric heat.
HTG STG MAX 82 2052, 2152 The value, in percent, which the heating 0.400 0.000
2054, 2154 loop (HTG LOOPOUT, Point 80) must
exceed for the electric heat to be ON for
the full duty cycle (HTG STG TIME,
Point 89).
HTG STG MIN 83 2052, 2152 The value, in percent, which the heating 0.400 0.000
2054, 2154 loop (HTG LOOPOUT, Point 80) must
go below for the electric heat to be OFF
for the full duty cycle (HTG STG TIME,
Point 89).
STAGE FAN 84 All except The value that the output of the current 0.400 0.000
2040, 2140 temperature loop must exceed in order
2041, 2141 for the fan to turn ON in night mode.
2090, 2188
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…

Siemens Building Technologies, Inc. 27


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
SWITCH LIMIT 85 All except The active temperature control loop 0.400 0.000
2040, 2140 output must be less than this value to
2090, 2188 switch between cooling mode and
heating mode. Actual switchover
depends on SWITCH DBAND (Point 90)
being exceeded and is subject to
SWITCH TIME (Point 86) being expired.
SWITCH TIME 86 All except The time, in minutes, before the 1.000 0.000
2040, 2140 heat/cool mode can change over when
2050, 2150 the other parameters are appropriate.
2090, 2188
HTG STG CNT 88 2052, 2054 The number of electric heating stages 1.000 0.000
used by the application. DOs associated
with unused stages may be used as
spare DOs.
VALVE CNT 88 2041, 2141 The number of heating valves available. 1.000 0.000
2050, 2150
HTG STG TIME 89 2052, 2152 The cycle time, in minutes, for the 1.000 0.000
2054, 2154 electric reheat stages. For example, if
there are three stages of electric heat
and STAGE TIME=10 minutes, HTG
STG CNT=3, and AVG HEAT
OUT=150% then, Stage 1 will be ON for
10 minutes (100% of the time), Stage 2
will be ON for 5 minutes (50% of 10
minutes) and OFF for 5 minutes, and
Stage 3 will be OFF.
SWITCH DBAND 90 All except The temperature range, in degrees, 0.250 0.000
2040, 2140 which is compared to the difference (0.140)
2050, 2150 between CTL TEMP (Point 78) and CTL
2090, 2188 STPT (Point 92). The difference must
exceed this value for temperature
control mode to change over.
Changeover is also subject to SWITCH
TIME (Point 86) being expired.
CTL STPT {92}3 All except The actual setpoint value being used as 0.250 48.000
2090, 2188 input for the active temperature control (0.140) (8.889)
loop.
CAL TIMER 96 All except Time interval, in hours, between the 1.000 0.000
2152 calibration sequence.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.

Continued on next page…

28 Siemens Building Technologies, Inc.


Point Database

Descriptor Address1 Application Description Slope2 Intercept


(SI Units) (SI Units)
LOOP TIME 98 All except The time, in seconds, between control 1.000 (0.000)
2090, 2188 loop calculations.
ERROR STATUS {99}3 All The status code indicating any errors – –
detected during controller power up. A
status of 0 indicates there are no
problems.
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.

Siemens Building Technologies, Inc. 29


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

30 Siemens Building Technologies, Inc.


Glossary
Overview
This section contains a glossary of terms and acronyms that are used in this manual. For
definitions of point database descriptors, see Section 3, Point Database, in this manual. For
definitions of commonly used terms as well as acronyms and abbreviations associated with
the APOGEE Automation System, see the Technical Glossary of Building Controls
Terminology and Acronyms (125-2185). This book is available from your local Siemens
Building Technologies, Inc. representative.

Al
Analog Input. Point that receives a signal that represents a condition which has more than
two states. For example, flow rate sensors (water or air), temperature sensors (room or duct),
pressure sensors (static or velocity), and humidity sensors (room, duct, or outdoor).

airflow
Rate at which a volume of air moves through a duct. Usually expressed in cubic feet per
minute (cfm).

algorithm
Mathematical formula that uses varying inputs to calculate an output value.

AVS
Air Velocity Sensor.

centralized control
Type of control offered by a controller that is connected by means of a Floor Level Network
(FLN) with an APOGEE field panel.

CFM
Cubic Feet per Minute.

control loop
PID algorithm that is used to control an output based on a setpoint and an input reading from
a sensor.

DDC
Direct Digital Control.

Siemens Building Technologies, Inc. 31


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

DI
Digital Input. Physical input point that receives a two-state signal (ON/OFF, OPEN/CLOSED,
YES/NO).

DO
Digital Output. Physical output point that sends a two-state signal (ON/OFF, OPEN/CLOSED,
YES/NO).

English units
The foot-pound-second system of units for weights and measurements.

equipment controller
FLN device that provides additional point capacity to a field panel or provides individual room
or mechanical equipment control.

FLN
Floor Level Network. Formerly Local Area Network (LAN). Network consisting of Terminal
Equipment Controller (TEC), Unitary Controllers (UC), fume hoods, etc.

field panel
A device containing a microprocessor for centralized control of system components and
equipment controllers.

intercept
Factor that converts signals that the field panel uses for analog points into the engineering
units that represent point values. The formulas used to calculate intercept are determined by
the type of field panel or Floor Level Network (FLN) device that contains the point and type of
input or output device represented by the point.

LPS
Liters per Second.

loopout
The output of the control loop expressed as a percentage.

MMI
Man Machine Interface. Terminal and its interface program that allows you to communicate
with a field panel or equipment controller.

override switch
Button on a room temperature sensor that an occupant can press to change the status of a
room from unoccupied to occupied (or from night to day) for a predetermined time.

32 Siemens Building Technologies, Inc.


Glossary

PID
Proportional, Integral, Derivative.

pressure dependent
Variable Air Volume (VAV) room temperature control system in which the temperature
directly drives the damper.

RTS
Room Temperature Sensor.

setpoint
Virtual point that stores a point value such as a temperature setting. Points that monitor
inputs, such as temperature, report actual values.

SI units
Systeme International d'Unites. The international metric system.

slave mode
Default application that displays when power is first applied to a Terminal Equipment
Controller. No control action is initiated in the slave mode.

slope
Factor that converts analog values (used by the controller) to a form which the user can
understand (engineering units).

stand-alone control
Type of control offered by a controller that is providing independent DDC control to a space.

Terminal Equipment Controller


Siemens Building Technologies, Inc. product family of equipment controllers (one is the Unit
Conditioner Controller — Electronic Output) that house the applications software used to
control terminal units, such as heat pumps, VAV terminal boxes, fan coil units, unit
ventilators, etc.

unbundle
Term used to describe the entering of a point that resides in a controllers database into the
field panel's database so that it can be monitored and controlled from the field panel.

VAV
Variable air volume. Ventilation system that changes the amount of air supplied to and
exhausted from the rooms served.

Siemens Building Technologies, Inc. 33


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

34 Siemens Building Technologies, Inc.


Index
actuators.............................................................5 auxiliary points ................................................. 16
damper actuator .........................................3, 7 AVS (see Air Velocity Sensor) ......................... 31
valve actuator ...........................................3, 24 Basic Sanity Test ............................................... 4
AI (see analog input) ........................................31 calibration........................................................... 7
airflow ...............................................................31 centralized control............................................ 31
algorithm...........................................................31 CFM (see cubic feet per minute) ..................... 31
analog input (Glossary) ....................................31 control loop ...................................................... 31
application 2040/2140 control loops
control drawing ...............................................9 cooling loop .................................................... 7
overview .........................................................9 flow loop ......................................................... 7
application 2041/2141 heating loop.................................................... 7
control drawing .............................................10 temperature loop ............................................ 7
overview .......................................................10 control temperature setpoints ............................ 7
application 2050/2150 controller
control drawing .............................................11 Terminal Equipment Controller ...................... 1
fan operation.............................................8, 12 Unit Conditioner Controller............................. 1
overview .......................................................11 day/night mode .................................................. 7
application 2051/2151 DDC (see Direct Digital Control)...................... 31
control drawing .............................................12 DI (see digital inputs) ....................................... 32
13 direct digital control (DDC)............................. 1, 7
overview .......................................................12 Direct Digital Control (DDC)............................... 1
application 2052/2152 DO (see digital outputs) ................................... 32
control drawing .............................................13 electric reheat .................................................... 8
13 English units..................................................... 32
overview .......................................................13 equipment controller ........................................ 32
application 2053/2153 fail-safe operation .............................................. 7
control drawing .............................................14 Fan Operation .............................................. 8, 13
14 field panel..1, 3, 4, 16, 17, 19, 20, 21, 22, 23, 24,
overview .......................................................14 25, 26, 27, 28, 29, 31, 32, 33
application 2054/2154 FLN .................................................................. 32
control drawing .............................................14 heating and cooling switchover.......................... 8
14 hot water reheat ................................................. 8
overview .......................................................14 intercept ........................................................... 32
application 2090/2188 LED Indicators ................................................... 4
auxiliary points..............................................16 light emitting diode (LED) indicators .................. 4
overview .......................................................16 loopout ............................................................. 32
point extension .............................................16 LPS (see Liters per Second)............................ 32
applications MMI (see Man-Machine Interface)................... 32
basic operation ...............................................7 night mode override switch ................................ 7
calibration .......................................................7 override switch ................................................. 32
control loops ...................................................7 PID ................................................................... 33
control temperature setpoints.........................7 point database ................................................. 19
electric reheat .................................................8 applications list ....................................... 19, 31
fail-safe operation ...........................................7 intercept.................................................. 19, 31
heating and cooling switchover ......................8 point addresses ...................................... 19, 31
hot water reheat....................................1, 8, 10 point descriptors ..................................... 19, 31
night mode override switch.............................7 slope....................................................... 19, 31
secure mode operation...................................8 point extension................................................. 16
sequencing logic.............................................7 pressure dependent..................................... 7, 33

Siemens Building Technologies, Inc. 35


APOGEE Unit Conditioner Controller—Electronic Output Owner’s Manual

room temperature sensor...................................2 standard...................................................... 1


RTS ..................................................................33 calibration ....................................................... 7
secure mode applications ..................................1 hardware inputs
secure mode operation ......................................8 analog ......................................................... 2
sequencing logic ................................................7 digital .......................................................... 2
setpoint.............................................................33 hardware outputs
SI units .............................................................33 analog ......................................................... 2
slave mode .......................................................33 digital .......................................................... 2
slope.................................................................33 ordering notes ................................................ 1
stand-alone ..................................................1, 33 product overview ............................................ 1
stand-alone control...........................................33 related equipment .......................................... 5
standard applications .........................................1 sequencing logic ............................................ 7
temperature sensors valve
duct temperature sensor.................................5 2-position heating ......................................... 22
room temperature sensor ...............................5 Variable Air Volume (VAV) ................................ 7
Terminal Equipment Controller ........................33 VAV (see Variable Air Volume)........................ 33
unbundle...........................................................33 wall switch.......................................................... 2
Unit Conditioner Controller wiring
applications communication wiring..................................... 3
secure mode ...............................................1 power wiring ................................................... 3

36 Siemens Building Technologies, Inc.


PXC Modular Series Owner's
Manual

125-3582(CA)

01/26/2011 125-3582, Rev. 2


Copyright Notice

Copyright Notice

Notice
Document information is subject to change without notice by Siemens Industry, Inc.
Companies, names, and various data used in examples are fictitious unless otherwise
noted. No part of this document may be reproduced or transmitted in any form or by
any means, electronic or mechanical, for any purpose, without the express written
permission of Siemens Industry, Inc.

Warning
This equipment generates, uses, and can radiate radio frequency energy. If equipment
is not installed and used in accordance with the instructions manual, it may cause in-
terference to radio communications. Equipment has been tested and found to comply
within the limits for a Class B digital device pursuant to Part 15 of the FCC rules. These
limits are designed to provide reasonable protection against such interference when
operated in a commercial environment. Operation of this equipment in a residential
area is likely to cause interference. Residential area equipment users are required to
take whatever measures necessary to correct the interference at their own expense.

Service Statement
Control devices are combined to make a system. Each control device is mechanical in
nature and all mechanical components must be regularly serviced to optimize their op-
eration. Siemens Industry, Inc. branch offices and authorized distributors offer Tech-
nical Support Programs that will ensure continuous, trouble-free system performance.
For further information, contact your nearest Siemens Industry, Inc. representative.
Copyright 2011 by Siemens Industry, Inc.

FCC Regulations
The manual for an intentional or unintentional radiator shall caution the user that
changes or modifications not expressly approved by the party responsible could void
the user’s authority to operate the equipment.
For a Class B digital device or peripheral, the instructions furnished the user shall
include the following or similar statement, placed in a prominent location in the text of
the manual:
NOTE: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not in-
stalled and used in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference will not occur
in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following
measures:

2
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Copyright Notice

 Reorient or relocate the receiving antenna.


 Increase the separation between the equipment and receiver.
 Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
 Consult the dealer or an experienced radio/TV technician for help.

To the Reader
Your feedback is important to us. If you have comments about this manual, please
submit them to: mailto:Sbt_technical.editor.us.sbt@siemens.com

Credits
APOGEE, APOGEE GO, InfoCenter Administrator, InfoCenter Report Manager,
InfoCenter Server, InfoCenter Suite, Insight, Staefa, and TALON are registered
trademarks of Siemens Industry, Inc.
Other product or company names mentioned herein may be the trademarks of their
respective owners.
Printed in USA

3
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Table of Contents

How to Use This Manual ........................................................................................ 7


Chapter 1—Introduction ....................................................................................... 10
Modular Product Overview ....................................................................................... 10
Ordering Information ................................................................................. 10
Compatibility with the APOGEE Automation System ............................................... 12
BACnet Protocol Compatibility .................................................................. 12
TCP/IP Protocol Compatibility................................................................... 13
Principles of Field Panel Operation .......................................................................... 14
Gathering and Processing Field Inputs ..................................................... 15
Executing Control Programs ..................................................................... 15
System Program ....................................................................................... 16
License Manager ...................................................................................... 16
APOGEE Automation Networking ............................................................................ 17
Management Level Network ..................................................................... 17
Automation Level Network ........................................................................ 17
Field Level Network .................................................................................. 24
Chapter 2—Hardware Features ........................................................................... 25
PXC Modular Product Diagram ................................................................................ 25
Expansion Module Product Diagram ........................................................................ 27
Memory..................................................................................................................... 27
Flash Read-Only Memory (Flash ROM) ................................................... 27
Random Access Memory (RAM) .............................................................. 29
Communication Connections ................................................................................... 29
HMI and Tool Ports ................................................................................... 30
10B/100B Ethernet Port ............................................................................ 31
RS-485 Port .............................................................................................. 31
Expansion Module Overview .................................................................... 32
TX-I/O Island Bus ...................................................................................... 33
Modular Series Smoke Control Application Requirements ...................................... 33
Example ALN Configuration for Smoke Control Applications ................... 35
PXM10S/T Product Overview and Description ........................................................ 36
Product Features ...................................................................................... 36
Requirements ............................................................................................ 37
Application Menus ..................................................................................... 37
Operator Display Layout ........................................................................... 38
Operator Display Menu Tree..................................................................... 39
Main Menu Structure ................................................................................. 39
Login and Logoff ....................................................................................... 40
Viewing, Commanding, and Releasing Points .......................................... 46
Configuring Point Monitor ......................................................................... 51

5
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Configuring Settings .................................................................................. 55
TX-I/O Product Range Overview .............................................................................. 59
TX-I/O Module Overview ........................................................................... 59
TX-I/O Power Supply and Bus Modules ................................................... 63
PX Series Enclosures and Service Boxes................................................................ 66
PX Series Service Box Features ............................................................... 66
Product Numbers ...................................................................................... 68
PX Series Enclosure Specifications .......................................................... 69
PX Series Service Box Specifications ....................................................... 70
PX Series Enclosure Placement ............................................................... 70
Chapter 3—Applications .......................................................................................73
Operator Interface .................................................................................................... 73
Field Panel GO .......................................................................................... 73
Powers Process Control Language (PPCL) Control Program and Point Database 74
Control Programs ...................................................................................... 74
Point Database .......................................................................................... 74
Applications .............................................................................................................. 75
Adaptive Control ........................................................................................ 75
Alarm Management ................................................................................... 75
Daylight Saving Time ................................................................................ 76
Equipment Scheduling .............................................................................. 76
Loop/Loop Tuning ..................................................................................... 76
Start-Stop Time Optimization (SSTO) ....................................................... 76
Time and Calendar .................................................................................... 76
Trend Data Collection ............................................................................... 76
User Access and Privileges ...................................................................... 77
Customized Applications .......................................................................................... 77
Chapter 4—Troubleshooting .................................................................................79
Service Information................................................................................................... 79
Electrostatic Discharge ............................................................................. 80
Error Status Messages.............................................................................. 80
Ordering Replacement Parts .................................................................... 80
Replacing the Batteries ............................................................................. 80
Reinstalling the Mounting Tabs ................................................................. 81
Troubleshooting Modular Field Panels ..................................................................... 82
BATT LOW LED ........................................................................................ 82
RUN LED .................................................................................................. 83
TX and RX LEDs ....................................................................................... 83
Communication ......................................................................................... 83
Display....................................................................................................... 83
Errors......................................................................................................... 84
Troubleshooting the TX-I/O Island Bus .................................................................... 84
Glossary ...............................................................................................................86
Index ....................................................................................................................90

6
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
How to Use This Manual

How to Use This Manual


About This Manual
This manual is written for the owner and user of the PXC Modular Series. It is designed
to help you become familiar with the PXC Modular and its applications.
This section covers manual organization, document conventions and symbols used in
the manual, how to access help, related publications, and any other information that
will help you use this manual.

Document Organization
This manual contains the following chapters:
 Chapter 1—Introduction, describes each section in this manual and presents an
overview of PXC Modular operation.
 Chapter 2—Hardware Features, describes the PXC Modular hardware components
and their functions.
 Chapter 3—Applications, describes the operating system and applications
available with the PXC Modular.
 Chapter 4—Troubleshooting, describes basic corrective measures you should take
if you encounter a problem when using a PXC Modular.

NOTE:
The troubleshooting section is not meant to be a full diagnostic guide, but is designed
to help you address basic troubleshooting issues. If you encounter a problem not
covered in this section or require further assistance, consult your Siemens Industry
representative.

 A Glossary describes the terms and acronyms used in this manual.


 An Index is provided to assist you in finding information presented in this manual.

Prerequisites
In addition to reading this owner's manual, you should also become familiar with the
following technical documentation. Each document has been written to help you get
the most out of your PXC Modular Series hardware.
These manuals, along with information about other Siemens Industry products,
technical training classes, and services can be obtained from your local Siemens
Industry representative.
 Powers Process Control Language (PPCL) User's Manual (125-1896). This manual
describes Powers Process Control Language (PPCL), the language used to write
the control programs for the PXC Modular.
 APOGEE P2 ALN Field Panel User's Manual or APOGEE BACnet ALN Field Panel
User's Manual (125-3019 or 125-3020). This manual describes the operator
interface program used to communicate with APOGEE field panels. It contains
information on defining the PXC Modular database, including slopes and
intercepts.

7
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
How to Use This Manual

For Smoke Control Applications


Smoke Control Systems Application and Engineering Manual (125-1806). This manual
is a comprehensive reference on smoke control applications for APOGEE equipment.
It contains all of the various agency requirements and recommended practices of
organizations that are widely-recognized in composing standards and testing
equipment involved in life safety applications.

When Using Insight Software


Insight 3.x Documentation. To view Insight 3.x documentation, see the Insight Online
Documentation window, which you can access from the Insight Main Menu or the
Insight program group.

Document Conventions
The following table lists conventions to help you use this manual in a quick and
efficient manner.

Convention Examples

Numbered Lists (1, 2, 3…) indicate a 1. Turn OFF power to the field panel.
procedure with sequential steps. 2. Turn ON power to the field panel.
3. Contact the local Siemens Industry
representative.

Conditions that must be completed or ⊳Composer software is properly installed.


met before beginning a task are ⊳A Valid license is available.
designated with a ⊳. 1. Select Start > Programs > Siemens > GMS >
Intermediate results (what will happen Composer.
following the execution of a step), are ⇨The Project Management window displays.
designated with a ⇨. 2. Open an existing project or create a new one.
Results, which inform the user that a task ⇨The project window displays.
was completed successfully, are
designated with a ⇨.

Actions that should be performed are Type F for Field panels.


specified in boldface font. Click OK to save changes and close the dialog box.

Error and system messages are The message Report Definition


displayed in Courier New font. successfully renamed displays in the status
bar.

New terms appearing for the first time are The field panel continuously executes a user-
italicized. defined set of instructions called the control
program.

This symbol signifies Notes. Notes provide


additional information or helpful hints.

Cross references to other information are For more information on creating flowcharts, see
indicated with an arrow and the page Flowcharts [→92].

8
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
How to Use This Manual

Convention Examples

number, enclosed in brackets: [→92]

Safety Symbols
The following table lists the safety symbols used in this manual to draw attention to
important information.
Symbol Meaning Description

NOTICE CAUTION Equipment damage may occur if a procedure or instruction is not


followed as specified. (For online documentation, the NOTICE displays
in white with a blue background.)

CAUTION Minor or moderate injury may occur if a procedure or instruction is not


followed as specified.

WARNING Personal injury or property damage may occur if a procedure or


instruction is not followed as specified.

DANGER Electric shock, death, or severe property damage may occur if a


procedure or instruction is not followed as specified.

Getting Help
For more information about APOGEE products, contact your local Siemens Industry
representative.

9
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Modular Product Overview

Chapter 1—Introduction
Chapter 1 provides an introduction to the PXC Modular Series and how it is integrated
with the APOGEE Automation System. The following topics are discussed:
 PXC Modular Series Product Overview
 Compatibility with the APOGEE Automation System
– BACnet Protocol Compatibility
– TCP/IP Protocol Compatibility
 Principles of PXC Modular Operation
– Gathering and Processing Field Inputs
– Executing Control Programs
– System Program
 APOGEE Automation Networking
– Management Level Network
– Automation Level Network
– Field Level Network

Modular Product Overview


The PXC Modular is an integral part of the APOGEE® Automation System. It is a high
performance, modular Direct Digital Control (DDC) supervisory field panel.
The field panel operates stand-alone or networked to perform complex control,
monitoring, and energy management functions without relying on a higher level
processor.
 Up to 100 PXC Modular field panels communicate on a peer-to-peer network.
 With the addition of TX-I/O modules and a TX-I/O Power Supply on a self-forming
bus, the PXC Modular can directly control up to 500 points.

See the APOGEE Wiring Guidelines for Field Panels and Equipment Controllers
(125-3002) for information on setting up this configuration.

 With the addition of an Expansion Module, the PXC Modular also provides central
monitoring and control for distributed wireless or wired Field Level Network (FLN)
devices.

Ordering Information
Product Number Description

PXC00-E96.A PXC Modular, BACnet/IP or MS/TP ALN, P1 or MS/TP FLN. PXX-485.3 is also required as the connection
to the FLN devices.

PXC00-PE96.A PXC Modular, Ethernet/IP or RS-485 ALN, P1 FLN. PXX-485.3 is also required as the connection to the
FLN devices.

10
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Modular Product Overview

Product Number Description

PXC100-E96.A PXC Modular, BACnet/IP or MS/TP ALN, P1 or MS/TP FLN, self-forming TX-I/O Island Bus. PXX-485.3 is
also required as the connection to the FLN devices.

PXC100-PE96.A PXC Modular, Ethernet/IP or RS-485 ALN, P1 FLN, self-forming TX-I/O Island Bus. PXX-485.3 is also
required as the connection to the FLN devices.

PXX-485.3 Provides FLN support for the PXC Modular. Includes three RS-485 P1 FLN connections or one MS/TP
FLN connection; maximum of 96 devices supported.

Optional Licenses
Product Number Description

PXF-TXIO.A License to enable the Island Bus on PXC00-E96.A and PXC00-PE96.A.

LSM-FPGO License to enable Field Panel GO on the PXC-36

LSM-VAEM License to enable Virtual AEM support when the P2 ALN is connected to RS-485

LSM-FPWEB License to enable BACnet Web Server (PXC-36) or Web Services (PXC-16/24)

Product Number Description

PXF-TXIO.A License to enable the Island Bus on PXC00-E96.A and PXC00-PE96.A.

LSM-FPWEB License to enable BACnet Web Server (PXC-36) or Web Services (PXC-16/24)

TX-I/O I/O Modules


Product Number Description

TXM1.8D TX-I/O Module, 8 DI points

TXM1.16D TX-I/O Module, 16 DI points

TXM1.8U TX-I/O Module, 8 Universal points

TXM1.8U-ML TX-I/O Module, 8 Universal points with LOID

TXM1.8X TX-I/O Module, 8 Super Universal points

TXM1.8X-ML TX-I/O Module, 8 Super Universal points with LOID

TXM1.6R TX-I/O Module, 6 DO with Relay points

TXM1.6R-M TX-I/O Module, 6 DO with Relay points with manual override

TX-I/O Power Supply and Bus Modules


Product Number Description

TXS1.12F4 TX-I/O Power Supply, 1.2A, 4A Fuse

TXS1.EF4 TX-I/O Bus Connection Module, 4A Fuse

11
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Compatibility with the APOGEE Automation System

TXA1.IBE TXIO Island Bus Expansion module with RS-485 connection.

TXB1.P1 TX-I/O Bus Interface Module, P1

Accessories
Product Number Description

TXA1.K12 One set of address keys, numbers 1-12.

TXA1.K24 One set of address keys, numbers 1-24.

TXA1.K-48 One set of address keys, numbers 25-48.

TXA1.K-72 One set of address keys, numbers 49-72.

TXA1.LLT-P100 Labels for TX-I/O, 100 sheets/pack, letter format.

TXA1.LH Replacement label holders.

Compatibility with the APOGEE Automation System


The PXC Modular Series is fully compatible with, and will communicate with, all the
APOGEE or pre-APOGEE products in your facility.
For more information on compatibility of products, contact your Siemens Industry
representative.

CAUTION
When working on a network with multiple firmware revisions, always connect to the
operator interface at the field panel with the newest firmware revision.
Otherwise, you will not be able to view features in newer firmware revisions, or you
may coldstart the field panel.

BACnet Protocol Compatibility


APOGEE BACnet is compatible with the BACnet/IP protocol.

CAUTION
When sharing data values from APOGEE P2 (proprietary) field panels to BACnet
devices, the Cross-Trunk Service does not support requests originating from BACnet
devices to access points (objects) that reside in APOGEE P2 field panels.
If you plan to share data values from APOGEE P2 field panels with BACnet devices
(field panels), you must do one of the following:
● Install and enable the Insight BACnet Server Option.
● Use PPCL in the APOGEE P2 field panels to command values in the BACnet
devices through the Insight Cross-Trunk service.

12
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Compatibility with the APOGEE Automation System

APOGEE P2 and BACnet Product Features Order of Implementation


The APOGEE field panel firmware supports the BACnet protocol as follows:
 If both the BACnet and APOGEE protocols have a function, the BACnet function is
implemented.
 If APOGEE provides a function that the BACnet protocol does not support, the
APOGEE function is retained.
This approach to BACnet implementation retains the APOGEE feature set while
providing compatibility with standard BACnet/IP protocol.

TCP/IP Protocol Compatibility


PXC Modular Series controllers with BACnet/IP or Ethernet TCP/IP (P2) ALN provide
the following:
 100% compatibility with the TCP/IP protocol suite.
 Support of Dynamic Host Configuration Protocol (DHCP) and Domain Name
Servers (DNS).
 Support and auto detection of 10Base-T and 100Base-TX Ethernet.

Required IP Addresses
APOGEE BACnet/IP or Ethernet TCP/IP (P2) ALN uses:
 One IP address per device (field panel or Insight workstation).
 One additional shared IP address per ALN for the multicast group (when using
multicast optimization).

Device Registration
Devices register with the DHCP server and Domain Name Server, if either is present.

Address Assignment
IP addresses are dynamically assigned by the DHCP server.
If an address changes or is not recognized, the field panel firmware lets you release
the dynamically assigned IP address and then reconnect the field panel to the DHCP
server, accepting a new IP address assignment in the process.
If there is no DHCP server at the site, you must manually assign static IP addresses as
part of the startup system configuration.

Physical Addressing
Each device on the BACnet/IP or Ethernet TCP/IP (P2) ALN has a hard-wired MAC
address, which is printed on the product label.

Port Numbers
The default TCP/IP port number for APOGEE BACnet/IP or Ethernet TCP/IP (P2) ALN
communications is 5033. You can change the TCP/IP port number if necessary.

13
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Principles of Field Panel Operation

NOTE:
All devices on the network must use the same TCP/IP port number.

The default TCP/IP port number for Virtual AEM communications is 3001.
You must specify a UDP port number when using multicast optimization. The default
UDP port number is 8.

Network Bandwidth
BACnet/IP or Ethernet TCP/IP (P2) ALN does not add significantly to your network
overhead. Burst conditions for this product occur during:
 Database downloading after coldstart.
 Database uploading.
 Trend data uploading.
 Burst of alarms or COVs.

Data Exchange
BACnet/IP or Ethernet TCP/IP (P2) ALN sends and receives APOGEE data in TCP/IP
packets.
BACnet/IP or Ethernet TCP/IP (P2) ALN synchronizes global data between all devices.
Each device runs a global data replication engine that communicates with peer devices
to:
 Exchange new and changed global data.
 Resolve conflicts when data does not match.

Device Naming Conventions


Field panel DNS node names are limited to 30 characters and cannot contain spaces.

Network Security
BACnet/IP or Ethernet TCP/IP (P2) ALN uses your intranet security within the firewall
and a username/password combination to restrict access outside the firewall. You can
use VLAN to improve internal security.

Principles of Field Panel Operation


The PXC Modular Series gathers information about the environment of your facility, as
well as the equipment it monitors and controls. The PXC Modular receives updated
information, stores information, executes control programs, handles operator
commands and requests, and makes control management decisions. At the same
time, the PXC Modular also translates decisions into actions and allows the operator to
observe those actions. The operator can also override and modify the decisions made
by the PXC Modular.

14
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Principles of Field Panel Operation

Gathering and Processing Field Inputs


The PXC Modular samples the information at all field inputs, or points, approximately
once each second, and stores numerical representations of the sampled values.
Under certain conditions, some points require additional handling. The PXC Modular
initiates required actions after these points are checked against previously-entered
configuration data.

Example
A log entry might be required in a point history file every 20 samples, or notification of
an alarm condition could be sent to the operator as a point crossed the alarm
threshold.

Executing Control Programs


The PXC Modular continuously executes a user-defined set of instructions called the
control program. This program uses the most recent point values and the most recent
clock time. The control program does the following:
 Evaluates control strategies.
 Uses an internal calendar and time clock for time-based functions.
 Updates point values and commands field points according to the program results.
 Sends messages or reports to proper terminal locations as needed.

Example
During occupied hours (7:00 A.M. through 5:00 P.M.) a fan:
 Turns ON if the room temperature rises above 80°F (27°C).
 Turns OFF when the temperature drops below 73°F (23°C).
Between 5:00 P.M. and 7:00 A.M. the fan turns OFF regardless of the room
temperature.
If the temperature rises to 85°F (29°C) at any time, the PXC Modular sends an alarm
message to an alarm printer.
These specifications can be met by:
1. Connecting a room temperature sensor/transmitter and fan starter output to the
PXC Modular.
2. Defining the room temperature sensor with a high alarm limit of 85°F (29°C) and
the fan points in the PXC Modular database.
3. Writing a short control program that defines your control strategy.
4. Enabling the execution for that portion of the control program.
To perform this control strategy, the PXC Modular:
 Continuously executes the control program.
 Samples a current or voltage signal representing the room temperature and
updates the value associated with that temperature in its memory.

15
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
Principles of Field Panel Operation

– If the temperature rises to 85°F (29°C), then the PXC Modular sends an alarm
message to the printer.
 Checks the current time once per second.
– Between 5:00 P.M. and 7:00 A.M., the fan remains OFF.
– Between 7:00 A.M. and 5:00 P.M., the control program checks the current
value of the temperature and sends the appropriate ON or OFF command to
the fan starter.
If the ON command is issued, the PXC Modular updates the value of the starter point
in its memory to reflect the current state of the fan.

System Program
The PXC Modular contains a non-volatile system program called firmware, which can
be upgraded in the field. The firmware is stored in Flash ROM memory, which keeps it
virtually immune to all forms of power fluctuations or failure, including battery failure.
For more information on Flash ROM memory, see Memory [➙ 27].
General functionality of the firmware includes:
 Executing control programs.
 Communicating between other field panels and the Insight workstation.
 Monitoring points.
 Managing point-related information.
 Keeping track of real time (both clock and calendar time).
 Executing self-test and error detection in the PXC Modular.

License Manager
License Manager adds applications or functionality to a field panel without the need to
replace the hardware or perform a firmware flash. Field panels with Firmware Revision
2.8.2/3.0.1 or later support the License Management attribute.
Contact your Siemens Industry representative for more information on applications and
functionality that can be activated through License Manager.

License Manager Definitions


 A feature is an application or additional functionality that can be added to a field
panel without the need to replace the hardware. Some features require a firmware
flash.
 A license is the code provided by Siemens Industry to unlock a feature.
 The ID_STRING is a unique identifier that distinguishes an individual piece of
hardware. It is composed of the panel's part number, revision, year and week of
manufacture, and serial number. Therefore, a license for one field panel will not
work on another field panel.

16
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

How does License Manager Work?


Field panels can either be ordered with licensed features and functionality pre-loaded,
for example, FLN or TX-I/O island bus support, or upgraded to add special features, for
example, integration drivers, Field Panel GO, and Virtual AEM.

NOTE:
The installation of some features and licenses require that the field panel be
coldstarted, while others do not. For example, Field Panel GO requires the creation of
Web server folders and therefore requires that the field panel be coldstarted.
However, TX-I/O module installation does not.

Any or all of the licensed features can be activated at any time using licenses acquired
from Siemens.
When the field panel is powered, the firmware reviews the inventory of installed
features, comparing that list to the License Vault, where all installed licenses are
stored. Every feature with a corresponding license is initiated and run. Because
licenses are loaded into non-volatile memory, powering down the field panel will not
erase them.

APOGEE Automation Networking


The following levels of networking provide varying levels of system integration in the
APOGEE Automation System.
 Management Level Network (MLN)
 Automation Level Network (ALN)
 Remote Automation Level Network
 Field Level Network (FLN)
These systems also use a number of network protocols that add functionality or
provide support for third-party devices.

Management Level Network


The Management Level Network (MLN) is the communications connection between
individual Insight workstations. It allows multiple Insight users to access the entire
APOGEE Automation System.
 An MLN is a TCP/IP Server-client network, and usually resides on the corporate
LAN.
 APOGEE Automation Systems without an Insight workstation do not have a
Management Level Network.

Automation Level Network


The APOGEE Automation Level Network (ALN) provides field panel-to-field panel and
Insight workstation-to-field panel communication. The ALN types are:
 P2 RS-485 ALN

17
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

 Ethernet TCP/IP ALN


 Remote ALN (Auto-dial and AEM)
 BACnet/IP ALN
 BACnet Master-Slave/Token Passing (MS/TP) ALN

Simultaneous ALN Access


More than one operator or field panel can access the network at one time. For
example, as one operator accesses the system, another operator can access the
system at another terminal (or from a remote site using a modem). This ensures that
field panels can send alarm information to the alarm printer even as an operator
accesses other information.

How Information Moves Through the Network


When an operator issues a command over the ALN network through a field panel, that
field panel validates the command, determines where to send it, and then passes the
command to the destination over the network.
Example
In the figure Commanding Over an Automation Level Network, the operator at the
Insight workstation, located in the lower level of the building, issues a command to
control the main air-handling unit (AHU) of the building. This command is sent by the
communication network to the field panel located on the top floor.

Figure. Commanding Over an Automation Level Network.

18
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

RS-485 P2 Automation Level Network


The RS-485 ALN is a proprietary token-passing network that communicates over RS-
485 cabling. It is Protocol 3 (P3) at and above 38,400 bps, and Protocol 2 (P2) below
38,400 bps.
 An Insight workstation is optional with this ALN.
 Up to 100 field panels (99 with an Insight workstation) can be connected and can
communicate by means of an RS-485 peer-to-peer network.
 Information can be sent and retrieved across the RS-485 ALN from any connected
field panel.

Media
The RS-485 ALN can communicate over one or more of the following:
 Physical wire (RS-485 cabling)
 Dedicated telephone lines
 Leased-line modems
 Line drivers
 Trunk Isolator Extenders (TIE)
 Fiber Optic Interfaces
The trunk system provides connections within buildings or between buildings for
multiple field panels and operator workstations.
The following figure shows a possible implementation of an RS-485 ALN network.

19
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

MLN, RS-485 ALN, and P1 FLN network example.

Ethernet TCP/IP Automation Level Network


The Ethernet Automation Level Network (EALN) uses TCP/IP-based communication
over a customers Ethernet cabling and IP network to reduce overall system and
maintenance costs. Otherwise, system operation is identical to RS-485 ALN
installations.
 An Insight workstation is optional with this ALN.
 When an Insight workstation is used, multiple Insight workstations can be defined
on the MLN.
 A maximum of 1000 Ethernet field panels can be defined for each Insight
workstation on the MLN.
 Each Insight workstation can host up to 64 EALNs.
 The Insight workstation counts as a node on every EALN to which it is connected.
Information can be sent and retrieved across the EALN from any Ethernet capable field
panel. The following figure shows a possible implementation of EALN over a corporate
IP network. In this example, the MBCs contain Power Open Processors with Ethernet
ALN.

20
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

MLN, Ethernet ALN, and P1 FLN network example.

21
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

Remote Automation Level Network (Single Field Panel


Remote Sites)
One PXC Modular can act as a stand-alone field panel. A stand-alone field panel is
generally used in remote sites where only one field panel is needed to control the
equipment for that site. Communications with the remote site are achieved by using
modems or the Virtual APOGEE Ethernet Microserver (AEM).
The remote site PXC Modular can initiate a telephone call to a device such as a
personal computer running Insight software, a dumb terminal, or a printer. Once the
remote site connects to the device, an alarm or other user-defined event is issued.
When the remote site no longer requires the connection to the device, the remote site
disconnects. The remote site can also receive telephone calls from a device running
Insight software to allow for centralized access of a local network's database.
The Virtual APOGEE Ethernet Microserver (AEM) allows an Automation Level Network
(ALN) to be connected directly to an Ethernet network at all times (versus a modem,
which connects when necessary). The ALN can consist of a single remote field panel
or a maximum of 32 field panels.
For local access, operators can communicate with the remote site by physically
connecting to the field panel via an operator's terminal. When an operator issues a
command, the field panel validates the command and sends it to the appropriate
device.
For more information about remote site field panels, contact your Siemens Industry
representative.

BACnet/IP Automation Level Network


BACnet field panels communicate over a customer's Ethernet cabling and IP network
using the ASHRAE Building Automation and Control Networking (BACnet) protocol.
 One Insight workstation can administer up to 64 Ethernet-based BACnet/IP ALNs.
 Up to 100 BACnet/IP or Ethernet TCP/IP (P2) field panels can reside on a
BACnet/IP network (1000 maximum per Insight workstation).
 Because they use different networking protocols, APOGEE P2 Ethernet TCP/IP
and BACnet/IP field panels cannot communicate directly with each other, even on
the same physical network.
The following figure shows a possible implementation of APOGEE P2 Ethernet ALN
and BACnet/IP ALN over a corporate IP network.

22
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

BACnet MS/TP Automation Level Network


BACnet field panels communicate over a customer’s Ethernet cabling and IP network
using the ASHRAE Building Automation and Control Networking (BACnet) MS/TP
protocol.
 One Insight workstation can administer up to 64 Ethernet based MS/TP ALNs.
 Up to 10 BACnet MS/TP ALN field panels can reside on an MS/TP network
segment (1000 maximum per Insight workstation). Network segments must be
physically separated.
 BACnet devices (field panels or Insight workstations) can be set up as one of the
following:
– A standard BACnet MS/TP device
– A BACnet Broadcast Management Device (BBMD)
– A foreign device

23
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 1—Introduction
APOGEE Automation Networking

Field Level Network


The APOGEE Field Level Network (FLN) is a data communications network that
passes information between an FLN device or devices and an Automation Level
Network (ALN) device, usually within one building. FLNs consist of devices that
communicate using RS-485 P1 or MS/TP.
 P1 devices can include Terminal Equipment Controllers (TEC), Fume Hood
Controllers (FHC) and other vendor equipment, such as ABB Speed Drives, which
contain Protocol 1.
 Selected models of APOGEE field panels can communicate with other vendor
protocols on the FLN, such as McQuay, Lumisys, EST IRC-3, and Allen Bradley.
Contact your Siemens Industry representative for information on devices that can
communicate with other vendor protocols.

24
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXC Modular Product Diagram

Chapter 2—Hardware Features


Chapter 2 describes the PXC Modular Series components and functions, as well as the
enclosure used for the PXC field panel series. The following topics are discussed:
 Product Diagrams
 Backup Batteries
 Memory
 Communication Connections
 PXC Modular Series Specifications
 Modular Series Smoke Control Application Requirements
 TX-I/O Product Range
 PX Series Enclosures and Service Boxes

PXC Modular Product Diagram

Modular Series Features, Symbols, and Status LEDs.


Label LED, Symbol, Status Indication
or Feature

1 24V~ - Supply voltage, 24 Vac input.

2 ⊥ - System neutral.

3 - Functional earth ground.

4 - USB Host port. (Ancillary smoke control applications only).

25
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXC Modular Product Diagram

Modular Series Features, Symbols, and Status LEDs.


Label LED, Symbol, Status Indication
or Feature

5 S-+ - RS-485 P2 or BACnet MS/TP Automation Level Network (ALN) port.

6 - SDIO (Secure Digital Input/Output) card slot.

7 - BACnet/IP or Ethernet TCP/IP (P2) Automation Level Network (ALN) port.

8 RUN (green) ON Normal operation. 24 Vac power is ON and the application firmware has booted.

OFF Error.
- 24 Vac input is not present.
- Power is ON, but the application firmware has not booted.

FLT (red) (for - -


future use)

BAT (red) ON Error. Backup battery is low. Replace the battery.

OFF Normal operation.

COM (yellow) ON Linked to Ethernet hub.


(Ethernet only)
OFF No link to Ethernet hub.

Flashing Linked to Ethernet hub and communicating.

TX (yellow) and Flashing Normal operation. Transmitting (TX) or receiving (RX) over the RS-485 ALN trunk.
RX (yellow)
OFF or Error. No device, no connection, or bad connection.
(RS-485 only)
Flashing

9 Tool/HMI - Human-Machine Interface port (RJ-45, service only).

10 AA alkaline - SDRAM backup battery. See BAT LED in this table for related indication.
battery

11 Coin cell - Real Time Clock backup battery.


battery

12 FW (for future - Firmware reset button.


use)

13 Reset - Hardware reset button. Coldstarts the PXC Modular.

14 - USB Device port. For non-smoke control applications only.

15 Expansion port - Connection for an RS-485 Expansion Module or future expansion devices.

16 TX-I/O bus - Connection for a TX-I/O Power Supply or Bus Connection Module, which powers
connector TX-I/O Modules.
(male)

26
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Expansion Module Product Diagram

Expansion Module Product Diagram

LED, Symbol, or Feature Status Indication

1 S-+ -- RS-485 P1 or MS/TP Field Level Network (FLN) ports.

2 Expansion connector -- Connection for future expansion devices.

3 RUN (green) ON Normal operation. 24 Vac power is ON and the module firmware
has booted.

OFF Error.
 24 Vac input is not present.
 Power is ON, but the module firmware has not booted.

TX (yellow) and RX Flashing Normal operation. Transmitting (TX) or receiving (RX) over the RS-
(yellow) 485 ALN trunk.

OFF or ON solid Error. No device, no connection, or bad connection.

4 PXC Modular Expansion -- PXC Modular connection for an RS-485 Expansion Module or
port future expansion devices.

5 Expansion connector -- Connection to the PXC Modular.

Memory
The APOGEE firmware (program), its point database, PPCL program, trend data, and
other information reside in the field panel memory. Memory consists of two areas:
Flash Read-Only Memory (Flash ROM) and Random Access Memory (RAM).

Flash Read-Only Memory (Flash ROM)


Flash Read-Only Memory (Flash ROM) is the non-volatile, permanent memory of the
PXC Modular, which stores the operating system, the APOGEE firmware, and the
language files. A limited amount of secondary storage is provided in Electrically
Erasable Programmable Read-Only Memory (EEPROM) for the field panel address or
name, communication speeds, and other set-up parameters. In the event of a power

27
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Memory

surge, a power loss, or failure of the battery backup, the Flash ROM and EEPROM
contents stay intact.
PXC Modular Flash ROM size cannot be upgraded in the field.

Compressed ROM
The PXC Modular has a large amount of high performance RAM. To allow for future
features and to provide high system performance, the APOGEE firmware is stored in
ROM in a compressed state; it is de-compressed into RAM on system power-up. As a
result, the entire onboard RAM is not available for the point database, the PPCL
program, and trend data.

Auto-Restore and Database Backup to Flash


APOGEE Firmware Revision 2.8.4/3.1 and later supports Auto-Restore and Database
Backup to Flash.
 Database Backup to Flash allows the user to manually save a copy of the database
in flash memory of the controller.
 The field panel may also be configured to automatically restore the database from
flash memory after a coldstart.
– When auto-restore is enabled, a coldstart does not result in the same downtime
as with earlier revisions of APOGEE Firmware. Because there is no waiting on
a full download from the backup system, the database is restored from flash so
quickly that it seems as though the field panel never coldstarted.
– Database restoration from flash is disabled by default.
– When P1 Mode is selected for the PXC Compact, database restoration from
flash is automatically enabled and 128K of memory is reserved for ISB files.
For procedures on using Auto-Restore and Database Backup to Flash, see the
APOGEE P2 ALN Field Panel User's Manual or APOGEE BACnet ALN Field Panel
User's Manual (125-3019 or 125-3020).

Auto Save
This feature allows the database to be backed up automatically whenever database is
changed, instead of being an operator selected function. It does not provide any
safeguard and or protection against power loss while the process is underway.
However, this feature sends messages to HMI that the auto save operation is in
progress or finished.
The feature may be turned on or off using a prompt similar to the existing Autorestore
prompt. See the APOGEE BACnet ALN Field Panel User's Manual (125-3020) for
more information.

File System Operations


File System Operations provide many features and works on three drives of a field
panel.
The following is a list of supported features: :

28
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Communication Connections

 List Drives — list the drives on the field panel where A: is the ram drive, B: is the
USB drive if attached, IFD: is the internal Flash Drive.
 Set_drive — identifies the drive that you desire to perform other functions on.
 listDirectory — lists the Files and folders contained on the selected drive.
 Change_dir — changes the current directory to allow you to view the contents of
subfolders on the drive.
 File_ops — opens up the file control menu which allows you to copy, rename,
delete and move files in the panel. These functions work on the drive that was
selected by the Set_drive function.
 File_ops/Copy_file — allows you to copy files within a drive or to another drive.
 File_ops/Rename_file — allows you to rename a file.
 File_ops/Move_file — allows you to move a file within a drive or to another drive.
 File_ops/Delete_file — allows you to delete a file.

USB Media Support


 Support for USB mass storage devices (Memory sticks or USB hard drives).
 Backup of database, storage for graphics, Web Server upgrades

Random Access Memory (RAM)


Synchronous Dynamic Random Access Memory (SDRAM) is the working memory of
the PXC Modular. When the PXC Modular has booted and is operating normally, the
APOGEE firmware, the PPCL control program, the point database, and trend data
have been transferred from Flash ROM. Information stored in RAM, such as the point
database or PPCL, may be viewed, modified, deleted, activated, or deactivated from
an operator terminal by any high-level authorized user. In the event of a power loss,
the contents of RAM are kept intact by a backup battery.
PXC Modular RAM size cannot be upgraded in the field.
The program length, number of database points, and number of trend entries is limited
only by available memory.

Communication Connections
The PXC Modular Series operates on the Automation Level Network (ALN) or the Field
Level Network (FLN).
 When connected to the ALN, the PXC Modular uses a logical point firmware
database to communicate directly with PXC Compacts, MBCs, RBCs, MECs,
SCUs, and other nodes on the network.
 When connected to the MS/TP FLN, the PXC Modular operates as a third-party
BACnet device.
The PXC Modular provides the following communication connections:
 HMI and Tools
 Network

29
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Communication Connections

– 10B/100B Ethernet port


– RS-485 port
– USB Host port
 PXC Modular Expansion Module
 TX-I/O Bus
The following connections and features are available when communicating on a
BACnet/IP Automation Level Network:
 Ethernet port
 RS-485 Port
 USB Host port
 Web Server support: Web-based Graphical User Interface (GUI) compatible with
BACnet® networks. Ideal for small or remote facilities to monitor and control the
Building Automation System.
The following connections and features are available when communicating on an
Ethernet TCP/IP Automation Level Network:
 Ethernet port
 USB Host port
 Field Panel GO, a Web-based graphical user interface for the APOGEE System.
Field Panel GO is suited for sites with up to six field panels on the Ethernet ALN.
(Additional license required.)
The PXC Modular hardware can be changed between RS-485 P2 and Ethernet ALN
through the HMI. The factory default is Ethernet ALN.

NOTE:
Changing the ALN type coldstarts the field panel.

NOTE:
In Ethernet ALN mode, RS-485 P2 parameters are displayed and may be entered as
a selection. However, when in RS-485 P2 ALN mode, Ethernet ALN parameters are
not an available selection.

HMI and Tool Ports


 The HMI port provides a connection to a laptop computer for local operation and
engineering.
 The USB Device port supports a generic serial interface for an HMI or Tool
connection.

Human-Machine Interface (HMI)/Tool Port


The Human-Machine Interface (HMI)/Tool port provides RS-232 compliant
communications through a quick-connect RJ-45 jack. The HMI port supports the
following functionality:

30
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Communication Connections

 Connecting a machine interface device, such as an operator terminal or a text-


based operator terminal, to the PXC Modular.
 Executing firmware flash upgrades.
 1200 bps to 115.2 Kbps communication is supported.

NOTE:
The communication speed of the port must match the communication speed of the
device connected to it.

USB Device Port


The USB Device port supports a generic serial interface for an HMI or Tool device. The
USB Device port does not support firmware flash upgrades.

10B/100B Ethernet Port


The 10B/100B Ethernet port provides a path for commands and information
transmitted between field panels inside a firewall. This port provides both full- and half-
duplex 10Base-T or 100Base-TX compliant communications over a BACnet/IP or
Ethernet TCP/IP (P2) Automation Level Network (ALN). The highest possible
communication speed is automatically detected and selected.

RS-485 Port
The RS-485 port provides a path for commands and information transmitted between
field panels. This port provides communications over a RS-485 P2 or BACnet MS/TP
Automation Level Network (ALN). The communication speed is set during startup.
The RS-485 port provides half-duplex, asynchronous serial RS-485 communications
over shielded twisted pair cable. The RS-485 connector is labeled + – to indicate the
positive and negative connections. is a reference pin.
The following features are available when communicating on an RS-485 Automation
Level Network:
 RS-485 port
 Virtual AEM
Without additional hardware, the Virtual AEM connects an RS-485 APOGEE
Automation Level Network (ALN) or individual RS-485 field panels to a P2 Ethernet
network.
 An additional license is required.
 FLN support is not available when a Virtual AEM license is installed.

FLN Support
The Siemens Industry Field Level Network (FLN) can consist of devices that
communicate over an RS-485 connection using either MS/TP or Protocol 1 (P1).
 BACnet/IP ALN networks support application-specific control devices that
communicate using MS/TP or P1.

31
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Communication Connections

 Ethernet TCP/IP and RS-485 ALN networks only support application-specific


control devices that communicate using P1.

PXC Modular Series FLN Support.


ALN Protocol FLN Protocol Firmware Revision Number of FLN Drop Number Range
Supported Devices1

BACnet/IP MS/TP or P1 3.1 and later Up to 96 devices per 0 to 254


(RS-485) FLN connection

Ethernet TCP/IP or P1 (RS-485) 2.8.5 and later Up to 96 devices per 0 to 254


RS-485 FLN connection

2.8.4 and earlier 32 devices per FLN 0 to 31 if networked


connection 0 to 99 if stand-alone

1 Each field panel supports a total of 96 FLN devices. With Firmware Revisions 2.8.5 and later, the devices may be grouped in
any combination on the FLN ports as long as the total number of FLN devices on the field panel does not exceed 96.

Expansion Module Overview


The Expansion Module provides the hardware connection for Field Level Network
(FLN) devices including:
 Siemens Industry FLN
 Communications Drivers to Non-Siemens Networks
 Wireless P1 FLN

Siemens Industry FLN


Using the Triple RS-485 Expansion Module, the PXC Modular supports up to three RS-
485 networks of P1 Field Level Network devices, or one RS-485 network of BACnet
MS/TP devices.

Communication Drivers to Non-Siemens Networks


As an option, the PXC Modular can communicate to related building system
controllers, such as boilers, chillers, rooftop units, Programmable Logic Controllers
(PLCs), power meters, lighting panels, fire alarm and life safety systems, and access
control systems.

Wireless P1 FLN
Wireless P1 FLN replaces the traditional FLN cabling with wireless communication
links that form a wireless mesh network. The Wireless FLN is enabled through the PXC
Modular HMI.

NOTE:
A P1 FLN license must be installed in order to use Wireless FLN.

32
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Modular Series Smoke Control Application Requirements

TX-I/O Island Bus


The PXC-36 offers the flexibility of expanding the total point count through a self-
forming island bus. With the addition of TX-I/O modules and a TX-I/O Power Supply,
up to 32 points (or four TX-I/O modules) can be supported.
An additional license may be required to enable the Island Bus.

Modular Series Smoke Control Application


Requirements
 The controller must be located at the bottom of the enclosure.
 The controller may be oriented either horizontally or vertically. See the following
figures.
For Ethernet communications, the UL Listed surge protector (Ditek model DTK-
MRJ45C5E) is required for BACnet/IP or Ethernet TCP/IP (P2) networks. The surge
protector must be located in the same enclosure as the controller.

Modem Requirements
 The UL864 Listed surge protector (538-600) is required.
 Devices connected between the USB port and the UL Listed surge protector must
be located within the same room.
 A USB-to-RS-232 adaptor may be needed for UL Listed modems or UL Listed
printers that are not configured for USB communication.
 The modem may be located inside the PX Series enclosure.

33
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Modular Series Smoke Control Application Requirements

34
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
Modular Series Smoke Control Application Requirements

Example ALN Configuration for Smoke Control Applications


The RS-485 ALN does not have the same restrictions as the Ethernet ALN for smoke
control. Namely, Ethernet requires UL listed switches and routers.
The following figure displays a possible ALN configuration for smoke control.

Example ALN Configuration for Smoke Control.

35
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

PXM10S/T Product Overview and Description


PXM10S and PXM10T are optional controller mounted Operator Display modules that
provide a password protected user interface. This interface allows you to interact with
the existing field panel database and its immediate sub-networked (FLN) devices.

NOTE:
All unacknowledged alarms are viewable even if you are not logged into the module.

Product Description
The PXM10S/T modules are available as an upgrade for use with all Siemens
Compact and Modular Series field panels to provide additional local operator
capabilities. The PXM10S and PXM10T modules are field mounted and replace the
field panel covers.
There are three dedicated buttons, ALARM, INFO, ESC and one push DIAL. These
buttons, the push dial, and LCD display screen allow for interactive feedback at the
field panel controller.
The PXM10S/T modules supports all the languages loaded in the host field panel. The
language displayed on the LCD after user login is determined by the user account
language setting.
There are two versions of the modules as follows:
 PXM10S has all available options, including point monitor and optional blue
backlight.
 PXM10T does not include the Point Monitor or the optional blue backlight color.
Language selection and user account timeout settings for the PXM10S or PXM10T
module must be configured using an operator workstation or HyperTerminal at the field
panels HMI when creating an ALN user account.

NOTE:
For more information on creating and configuring user accounts, see the 125-3019 or
125-3020.

Product Features
The PXM10S and PXM10T modules provide the following features:
 Plug and Play - Upon connection to the host field panel, the device is recognized
and fully functional
 User-friendly navigation and menu structure
 Push DIAL for easy operation
 Alarm button with red LED indicator for local operator alarm annunciations
 INFO button provides one touch access to detailed system information for points
and alarms
 Manual and/or automatic login option for enhanced security or easy access

36
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

 View controller information and status, view and acknowledge alarms and
command/override local points value
 Hot Swappable – The module can be installed or removed without powering down
the controller and interrupting facility operations
 Point Monitor – Can customize a group of points to continuously display and
refresh with updated values (PXM10S only)
 Multi-language (Chinese, (Traditional and Simplified) French, and Korean) support

Communication Connections
A field panel fully powered and running Firmware Revision 3.2.2 and later recognizes
the PXM10S and PXM10T modules within approximately 5 seconds of connection.
Prior to that, the Operator Display is not operational.
If a field panel is coldstarted or it’s the first time the panel is powered up, it takes
approximately 15 to 30 seconds after connection before the PXM10S and PXM10T
module is operational.

Requirements

System Requirements
The PXM10S and PXM10T modules can be used with Compact platforms (PXC-36,
PXC-24, and PXC-16) as well as the Siemens PXC Modular field panels.
 All hardware must be installed.
 Power must be available to all devices.
 System components must be installed, running, and checked out by an appropriate
system representative.

Hardware Platform
The PXM10T and PXM10S modules can be used on all Siemens Compact and
Modular series controllers.

Firmware Platform
The PXM10T and PXM10S modules are compatible with all Siemens Compact and
Modular series controllers using Firmware Revision 3.2.2 or later.

Application Menus
The following application menus are provided with the PXM10S and PXM10T modules.
 Login
 Alarms
 Points (Command and Release)
 Point Monitor
 Logoff

37
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

 Settings

NOTE:
You must have sufficient operator access permissions to the Alarms, Points, and
Point Monitor applications to fully use all features and corresponding submenus. For
example, Edit/Configure access permission is required to add, delete, or reconfigure
a point.

Operator Display Layout

Display screen – Displays splash screen with either PXM10S or PXM10T module,
device Firmware Revision, field panel Firmware Revision number, and Cimetrics
BACstac revision number.

Splash screen

NOTE:
If text information is too long for Display screen, the text scrolls across the screen,
from the left to right, in a marquee style.

NOTE:
The list of objects (once they are created) that display for the Alarms, Points, and
Point Monitor menus are static, however, the point information (current value, status,
priority, etc.) is dynamic.

38
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Navigation Push DIAL – Rotate clockwise or counter clockwise to highlight menu


options (up or down). Press DIAL to enter a menu, OK your selection, go to next page
or edit a value. Rotate DIAL to change a value. Pressing DIAL is equivalent to
selecting OK.
ESC button – Press once to return to previous menu/page or backspace during
text/value editing.
INFO button – Press once to return to the window containing all available information
about the selected line, navigate to the next higher menu level, or close the alarm
window.

Alarm Window
There are two ways to view alarms, both of which display the alarm list with the point
system name and status:
 Alarm button. Provides direct access to the list of unacknowledged alarms.
 Alarm menu. Displays any point in alarm, regardless if it has been acknowledged
or not and provides two generic filters:
– All Alarms filter allows you to view all acknowledged and unacknowledged
alarms in the system
– Unacknowledged Alarms filters all alarms and lists only unacknowledged
alarms in local system
Pressing the INFO button for alarms displays:

INFO of unacknowledged alarm

Press ESC to close alarm window without affecting the alarm.

Operator Display Menu Tree

Main Menu Structure


All menu screen captures in this manual reflect the PXM10S module. Not all menu
options/features shown are available with the PXM10T module.

NOTE:
A solid DOWN arrow in the top right corner of the display screen indicates more menu
options are available and a solid UP arrow indicates more items are available after
the last highlighted item.

39
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Main menu

Alarms - Allows you to view and acknowledge alarms. However, you must be logged
in with sufficient permissions (at least Command or Edit/Configure level access) to
acknowledge an alarm.
Points - Allows you to view, command, and release the host field panel’s onboard
points and sub network points (FLN devices). To command and release points, you
need Command or Edit/Configure level access permissions.
Point Monitor - Displays a submenu, which allows an operator to configure and display
a custom grouping of point and their values. The values are refreshed every four
seconds. To configure points, you need Edit/Configure level access permissions.
LogOff - Displays screen for confirming logoff.
Settings - Displays a submenu and screens that allow you to customize the LCD’s
display settings.

Login and Logoff


You must have at least Read only level access permission to login to the PXM10S or
PXM10T module. If you log in and you have no access level permissions, the system
will immediately log you off the module.
If there are too many failed login attempts, you are locked out of the module. You must
use the HMI to unlock any user accounts. Also, you can only change your password for
the PXM10S or PXM10T modules from the HMI.

Logging In

Automatic Login
The PXM10S or PXM10T automatic login feature must be configured using the host
field panel’s HMI port. Only one user account can be flagged as the automatic login
account.

NOTE:
Default user account login information for PXM10S or PXM10T is on a per ALN
account basis.

If your network contains an assortment of field panels with Firmware Revisions earlier
than 3.2.2, the AutoLogin account is not replicated or passed onto other field panels.
For more information about workstation user accounts, see the Insight Online Help
system.

40
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Configuring AutoLogin at the HMI with HyperTerminal


Complete the following steps to configure an automatic login using HyperTerminal at
the host field panel’s HMI.
You must be logged into the field panel with an account that has Edit level access
permission to the users access group.
To configure automatic login, complete the following steps:

HMI S, U, A, E, A (System, Users, Accounts, Edit, Add)

Prompt/Field Option/Entry Description

User initials Type the new user’s initials.

Account name Type the account name.

Password Type a password for the user.

Verify password Retype the password.

System, User namespace S View System point names.

U View User point names. (default setting)

Access group(s) All groups (default setting)

A single access group Valid value 1 through 30.

Multiple access groups Valid values 1 through 30 separated by commas,


or use two periods to indicate a range (for
example, 1..4,7,9,12..20).

Privilege Point N (No_access)


R (Read_only)
C (Command)
E (Edit) (default setting)

Alarm N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

Trend N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

Application N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

PPCL N (No_access)

41
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

R (Read_only)
C (Command)
E (Edit) (default setting)

FLN devices N (No_access)


R (Read_only)
C (Command)
E (Edit) (default setting)

Equipment Scheduler N (No_access)


R (Read_only)
C (Command)
E (Edit) (default setting)

System N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

Diagnostics N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

Users N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

Hardware N (No_access)
R (Read_only)
C (Command)
E (Edit) (default setting)

Language ID Language Default

Particular language Language ID, ? displays all available languages.


NOTE: You can also enter nothing, to display all
available languages.

Time format (HH:MM:SS) Default

Particular format Time format; ? displays all available formats.


NOTE: You can also enter nothing, to display all
available Time formats.

Date format (MM/DD/YYYY) Default

Particular format Date format; ? displays all available formats.


NOTE: You can also enter nothing, to display all
available Date formats.

42
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

AutoLogoff enabled (Y/N) Y Enable automatic logoff.

AutoLogoff delay 1 to 1440 minutes

N Disable automatic logoff.

Password Expire Limit 0 to 365 days

Use for PXM10Tiny AutoLogin (Y/N) Y Enable automatic login.

N Disable automatic login.

Example
>User initials : tiny
>Account name : PXM10TINY---------------------
---
>Password : ???------------
>Verify password : ???------------
>System, User namespace : U
>Access group(s) : 1..30-------------------------
----------
>Point privilege - No_access, Read_only, Command, Edit: E
>Alarm privilege - No_access, Read_only, Command, Edit: E
>Trend privilege - No_access, Read_only, Command, Edit: E
>Application privilege - No_access, Read_only, Command, Edit: E
>PPCL privilege - No_access, Read_only, Command, Edit: E
>FLN devices privilege - No_access, Read_only, Command, Edit: E
>Equipment Scheduler privilege - No_access, Read_only, Command,
Edit: E
>System privilege - No_access, Read_only, Command, Edit: E
>Diagnostics privilege - No_access, Read_only, Command, Edit: E
>Users privilege - No_access, Read_only, Command, Edit: E
>Hardware privilege - No_access, Read_only, Command, Edit: E
>Language ID : 0409
>Time format : HH:MM:SS---
>Date format : MM/DD/YYYY-
>AutoLogoff enabled (Y/N) : Y
>AutoLogoff delay : 5---
>Password Expire Limit : 30-
>Use for PXM10Tiny AutoLogin (Y/N): Y
User account <tiny> added

NOTE:
For more information on creating and configuring user accounts, see the 125-3019 or
125-3020.

Do the following to automatically log in to the PXM10S or PXM10T module.

43
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Automatic Login submenu

Menu/Submenu Step Description

Splash screen/logo Press DIAL.

Rotate DIAL to highlight Login menu displays.


Automatic Login.

Login Press DIAL/OK to select System logs you into the Main menu of the module.
Automatic Login.

Main menu

Manual Login
Do the following to manually log in to the PXM10S or PXM10T module. The default
language for manual login is U.S. English.

Manual Login submenu

Menu/Submenu Step Description

Splash screen/logo Press DIAL.

Rotate DIAL to highlight Login menu displays.


Manual Login.

Login Press DIAL/OK to select Manual Login menu displays.


Manual Login.

44
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Menu/Submenu Step Description

Manual Login USR **** Enter your user name (up to 4 characters) and
PWD *************** password (3 to 15 characters).
A one character username is allowed.
NOTE: You can only use capital letters A through Z
for user name and passwords.

For USR, rotate DIAL to


highlight each character.

Press DIAL/OK to select NOTE: If you make a mistake selecting a character,


each character. Repeat press ESC to return to the previous character.
until you enter the complete
user name.

Press DIAL/OK twice to


move to the PWD fields.

For PWD, rotate DIAL


highlight each character.

Press DIAL/OK to select a NOTE: If you need to return to the previous editable
character. Repeat until you field, for example from PWD fields back to USR
enter the complete fields, press ESC. To proceed to the next field, press
password. DIAL/OK.

Press DIAL/OK to confirm System logs you into the Main menu of the module.
USR and PWD.

Manual Login screen

Logging Off
There are three ways to log off.
 Automatic logoff – Occurs when the module interface has been idle for the amount
of time defined in the user account settings. The timer feature is configured when a
user account is created at the field panel.
 Manual logoff – Select Logoff on the screen – Prompts you to confirm logoff.
 Press ESC on the Main menu screen – Prompts you to confirm logoff.

45
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

NOTE:
When you log off the module, the screen may go blank for approximately two
seconds.

Do the following to manually log off the PXM10S or PXM10T module.

Logoff menu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Logoff.

Press DIAL/OK to and Confirms Logoff submenu displays.


select Logoff.

Confirm Logoff Rotate DIAL to highlight


Are you sure? Yes or No.

Press DIAL/OK to make Confirms logoff and returns to splash screen.


selection. NOTE: If you press ESC, you are prompted with the
same Confirm Logoff screen.

Confirm Logoff submenu

Viewing, Commanding, and Releasing Points

Viewing Points
All points displayed on the screen are listed alphabetically, by system name.

46
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

NOTE:
Only four lines (excluding the title) of points are listed at a time for the English and
French language.
Only three lines (excluding the title) of points are listed for the Chinese and Korean
language.

Do the following to view and scroll to the next series of points in the field panel.

Points

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Points.

Press DIAL/OK to select Displays the Points menu.


Points.

Points Press DIAL/OK to highlight


desired point.

Press DIAL/OK to select


point.

Rotate DIAL to highlight the Refreshes the screen and displays the previous
last point (bottom of screens last highlighted point, as well as the next
screen), and then rotate series of points.
DIAL once more.

Repeat steps until you The number of points you can enter is dependent on
reach the end of the point the number of points stored at the host’s field panel
list. database, and sub network devices
connected/configured to the host’s field panel you
are connected to.

Press ESC. Returns you the Points menu.

Press INFO. Displays detailed point information of selected point.

47
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Scrolling the list of points


The point name is displayed in the left column and values in the right column. For
TECs, the prefix is the TEC name; and the exposed point in the Points menu is the
DAY.NGT subpoint. To see a complete list of the devices subpoints, highlight the
DAY.NGT point, and then press DIAL/OK.

TEC subpoints menu with list of device subpoints

NOTE:
Based on FLN speed and network traffic, there may be a delay in displaying a full
point database.

Commanding Points
Do the following to change the point value and command the points in the field panel.
These steps also apply to commanding TEC subpoints.

Point Action Command submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Points.

Press DIAL/OK to select Displays the Points menu.


Points.

Points Press DIAL/OK to highlight Displays the Point Action submenu.


desired point.

48
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Menu/Submenu Step Description

Point Action Rotate DIAL to highlight


Command.

Press DIAL/OK to select Displays the point name in title. Lists the selected
Command. point’s current value, edit (highlighted) and priority
fields.

[selected point name] With Edit field highlighted, Changes the specified point value.
rotate DIAL to each
numeric character and
decimal, and press
DIAL/OK after each
numeric increment,
including decimal
character, until you enter
the new value.

Press DIAL/OK. Confirms the point value change and moves to the
Priorit field.

With Priorit field Confirms the point priority change and returns you to
highlighted, repeat steps to the Points menu.
change priority of selected
point.

Press ESC. Returns you to the previous menu without changing


the point value or priority.

Command Point value submenu

Edit Command Point value submenu

Releasing Points
Do the following to change a point priority and release a point.

49
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Point Action Release Priority submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Points.

Press DIAL/OK to select Displays the Points menu.


Points.

Points Rotate DIAL to highlight


desired point.

Press DIAL/OK to select Displays the Point Action submenu.


point.

Point Action Rotate DIAL to highlight


Release Priority.

Press DIAL/OK to select NOTE: BACnet point priorities cannot be


Release Priority. commanded lower than a priority value of 8.

Rotate DIAL to change the


numeric value of the point
priority.

Press DIAL/OK to edit point


priority.

Rotate DIAL to change


point priority value.

Press DIAL/OK to confirm Releases BACnet point priority.


change.

Press ESC. Returns you to the previous menu without changing


the point priority.

Release Priority value submenu

50
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Configuring Point Monitor

NOTE:
This application and its sub-features are only available with the PXM10S module.

The Point Monitor allows you to select the points you frequently need to monitor and
allows quick access to view a point status. This concept is similar to a Favorites list.
The maximum number of points listed and stored in Point Monitor is 10. You cannot
add more points to the Point Monitor once you reach the maximum number.
Reset/clear the Point Monitor of stored points and then add the desired set of 10 or
fewer points you want to monitor.

NOTE:
Depending on user access rights, previously added points (by other users) to the
Point Monitor may not be visible. In this situation you can’t see or add any points in
Point Monitor. If this happens, you must first reset the Point Monitor to purge the old
information. This affects all users. While Point Monitor information can’t be retrieved,
the field panel database is not affected.

Configuring Points for Point Monitor


Do the following to configure the host field panel’s points for monitoring in Point
Monitor after logging in.

Point Monitor

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Point Monitor.

Press DIAL/OK to select Displays the Point Monitor menu.


Point Monitor.

Point Monitor Rotate DIAL to highlight Displays all available points at the field panel.
Configure.

Press DIAL/OK to select


Configure.

Edit Pt Monitor Rotate DIAL to highlight Displays black background, allowing you to edit field.
desired point.

51
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Menu/Submenu Step Description

Press DIAL/OK to select


point.

Press DIAL/OK to select Y Y=Yes; point is monitored.


or N. N=No; point is not monitored. (This is the default
setting.)

Press DIAL/OK to select Y


or N.

Press ESC. Returns you to the Monitor menu.

Configure submenu

Edit Point Monitor submenu

Do the following to configure bundled points in Point Monitor.

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Point Monitor.

Press DIAL/OK to select Displays the Point Monitor menu.


Point Monitor.

Point Monitor Rotate DIAL/OK to highlight Displays all available points at the field panel.
Configure.

Press DIAL/OK to select


Configure.

Edit Pt Monitor Rotate DIAL to select Displays all available points and subpoints at the
desired point. field panel.

Subpoints Rotate DIAL to select Displays a list of subpoints associated with the
subpoint. selected point.

52
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Menu/Submenu Step Description

Press DIAL/OK to select Y Y=Yes; point is monitored.


or N. N=No; point is not monitored. (This is the default
setting.)

Press ESC. Returns you to the Point Monitor menu.

Resetting Point Monitor


Do the following to reset points in Point Monitor.

Reset submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Point Monitor.

Press DIAL/OK to select Displays the Point Monitor menu.


Point Monitor.

Point Monitor Rotate DIAL to highlight


Reset.

Press DIAL/OK to select Displays the Remove Monitor.


Reset.

Remove Monitor Rotate DIAL to highlight


point.

Press DIAL/OK to make


select point.

Remove Monitor Rotate DIAL to highlight Confirms you want to remove a point(s) from being
Are you sure? Yes or No. monitored.

Press DIAL/OK to make


selection.

Press ESC. Returns you to the Monitor menu.

53
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Remove Monitor submenu

Displaying Monitored Points


Automatic logoff occurs after a predetermined amount of inactivity; however, the Point
Monitor continues to display points, and refreshes the Display screen every four
seconds.
You can scroll the Point Monitor list like you would the point list, however no function
keys such as INFO, ESC, Alarm, etc. are enabled. If you press any of the key
functions, the login splash screen prompts you to login.
Do the following to display monitored points.

Display submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Point Monitor.

Press DIAL/OK to select Displays the Point Monitor menu.


Point Monitor.

Point Monitor Rotate DIAL to highlight


Display.

Press DIAL/OK to select Displays the Display submenu.


Display.

Display Displays the monitored points; one point and its


value per line. Up to 10 points can be added the
Point Monitor list.

Press ESC. Returns you to the Monitor menu.

54
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Configuring Settings

Brightness
Do the following to modify the Brightness feature.

Settings menu

Adjust Brightness submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Settings.

Press DIAL/OK to select. Displays the Settings menu.

Settings Press DIAL/OK to highlight


Brightness.

Press DIAL/OK to select Displays the Brightness menu.


Brightness.

Brightness Rotate DIAL to highlight


Adjust Brightness.

Press DIAL/OK to select


Adjust Brightness.

Rotate DIAL to select a Valid brightness values are 0 through 100.


value.

Press DIAL/OK to make Applies the value and returns you to the previous
selection. menu.

Press ESC. Returns you to the Settings menu without applying


the new value.

55
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Brightness submenu

Color

NOTE:
The Color feature is available only for the PXM10S module.

Do the following to modify the Color feature.

Adjust Color submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Settings.

Press DIAL/OK to select. Displays the Settings menu.

Settings Press DIAL/OK to highlight Displays the Color submenu.


and select Color.

Color Rotate DIAL to highlights


and select Adjust Color.

Rotate DIAL to toggle Displays the backlight color you choose.


between Blue and White
color.

Press DIAL/OK to select. Applies the value and returns you to the previous
menu.

Press ESC. Returns you to the Settings menu without applying


the new color.

56
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Color submenu

Contrast
Do the following to modify the Contrast feature.

Adjust Contrast submenu

Menu/Submenu Step Description

Main Rotate DIAL to select


Settings.

Press DIAL/OK to select. Displays the Settings menu.

Settings Press DIAL/OK to select Displays the Contrast submenu.


Contrast.

Contrast Rotate DIAL to highlight


and select Adjust Contrast.

Rotate DIAL to select a Valid Contrast values are 0 through 100.


value.

Press DIAL/OK to select. Applies the value and returns you to the previous
menu.

Press ESC. Returns you to the Settings menu without applying


the new value.

Contrast submenu

57
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PXM10S/T Product Overview and Description

Timeout
The backlight of the PXM10S and PXM10T modules automatically turns off the
backlight on the Display screen after a predetermined amount of inactivity. However,
the moment you press any key, the backlight turns on again. If Point Monitor was
active on the screen during this time, the point list is saved, even if you are logged off.
Do the following to modify the Timeout feature.

Adjust Timeout submenu

Menu/Submenu Step Description

Main Rotate DIAL to highlight


Settings.

Press DIAL/OK to select. Settings menu displays.

Settings Press DIAL/OK to highlight Timeout submenu displays.


and select Timeout.

Timeout Rotate DIAL to highlight


and select Adjust Timeout.

Rotate DIAL to select a Valid Timeout values are 0 through 240 seconds.
value.

Press DIAL/OK to select. Applies the value and returns you to the previous
menu.

Press ESC. Returns you to the Settings menu without applying


the new value.

Timeout submenu

58
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

TX-I/O Product Range Overview


TX-I/O™ is a range of I/O modules, with associated power and communication
modules, for use within the APOGEE System. The I/O modules communicate between
the PXC Modular or the PXC-36 and the related devices in the building services plant.
The TX-I/O product range includes the following:
 Eight types of I/O modules, which act as signal converters.
 TX-I/O Power Supply for the TX-I/O modules.
 TX-I/O Bus Connection Module, which bridges communication and power from one
DIN rail to another.
 TX-I/O Island Bus Expansion (IBE) module, which increases the distance between
the primary field panel and expansion field panels on the island bus.
 P1 Bus Interface Module (BIM), which connects TX-I/O modules to the P1 FLN.
The P1 BIM provides power for TX-I/O modules, but it does not contain
applications or perform control; the control database for the TX-I/O points resides
in a field panel.

TX-I/O Module Overview


TX-I/O Modules are modular expansion I/O consisting of an electronics module and a
terminal base; they receive power from a TX-I/O Power Supply, Bus Connection
Module, or P1 BIM.
 The electronics module performs A/D or D/A conversion, signal processing, point
monitoring, and command output.
 The terminal base provides for termination of field wiring and connection of the self-
forming TX-I/O island bus.
All TX-I/O modules provide the following features:
 DIN rail mounting.
 High density point count (compared to physical dimensions).
 Hardware addressed with address keys.
The design of the TX-I/O Modules provides optimum diagnostics and results in a more
efficient installation and maintenance workflow.
 Field wiring may be terminated prior to installation of electronics.
 Connected peripheral devices can be measured without affecting or being affected
by the I/O module.
 Hot-swappable electronic components allow powered electronics to be
disconnected and replaced without removing terminal wiring or disturbing the self-
forming bus.

59
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

TX-I/O Module Product Diagram

TX-I/O Module Symbols and Status LEDs


LED, Symbol, or Feature LED or Symbol Indication

1 Address key and module status - Module status as a whole (as opposed to the I/O points).
LED (green)
ON Normal operation. 24 Vac (supply voltage) input present;
fuse is intact.

OFF Error.
- No 24 Vac (supply voltage) input.
- Fuse is blown.

Flashing or pulsing - Fault indication


- No address key
- Remote override

2 I/O point numbers - -

3 Terminal number - -

4 Test terminal -

5 Connection terminals -

6 - System neutral.

- Configurable point.

- Output (arrow pointing OUT from center of module).

60
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

TX-I/O Module Symbols and Status LEDs


LED, Symbol, or Feature LED or Symbol Indication

- Input (arrow pointing IN toward center module).

- 24 Vdc output (field supply).

- 24 Vac output (field supply).

7 Override status LEDs (yellow) ON Manual operation; a local override is active.

OFF No voltage or manual operation off.

Flashing or pulsing - Override action


- Remote override
- Output: Local override is off, operation is not possible.
- Input: Operation is not possible.

8 LCD signal display - Only on a TX-I/O modules with –ML suffix.

9 Local override switch - Only on a TX-I/O with –M or –ML suffix.

10 I/O status LEDs (green) - Status of the inputs and outputs (peripheral devices). LEDs
are labeled with the I/O point number.

ON Binary value indication.

OFF No voltage or binary value indication.

Flashing or pulsing - Fault indication


- Activity of field devices
- Module unconfigured, no address key
- Analog value indication

TX-I/O Module LCD Symbol Chart


The TX-I/O module LCD displays a symbol to indicate each point type and its current
value.

TX-I/O Module LCD Display for Errors and Reminders


(Displays in LCD Top Row)

Value above range limit

Value below range limit

Open circuit

Short circuit

Point type invalid for use with manual override

61
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

TX-I/O Module LCD Display for Errors and Reminders


(Displays in LCD Top Row)

No sensor (current)

No output signal

24 Vdc supply < 22 Vdc

Inactive point

Invalid value

No voltage

Unconfigured point

TX-I/O LCD Display by Point Type.


Point Type Normal Operation
(Displays in LCD Bottom Row) (Displays in LCD Top Row)

Analog Input, Current Low or high value

Analog Input, Temperature


Resistance

Analog Input, Voltage Low or high value

Analog Output, Low or high value


Current

Analog Output, Low or high value


Voltage

Digital Input, Counter Step indicator

Digital Input, N/C


Inactive Active
Contact

Digital Input, N/O


Inactive Active
Contact

Address Keys
The P1 Bus Interface Module (BIM) and I/O modules are addressed using a TX-I/O
address key.

62
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

TX-I/O Module Keys.

The keys are available in sets of 24, up to a maximum value of 72 (2 sets of 12, 1-24,
25-48, and 49-72).
 The I/O module address is mechanically encoded in the address key.
– Without an address key, the module is inactive.
– With an address key inserted, the module has full functionality.
 Based on the address, the PXC Modular, PXC-36, or P1 BIM configures the I/O
module, indicates which field devices are connected to this module, and which
function is required for the field devices.
When replacing the plug-in I/O module, the address key must first be swiveled
outward. This switches the load off but values remain saved in the PXC Modular, PXC-
36, or P1 BIM. The key remains plugged into the terminal base so that the PXC
Modular, PXC-36, or P1 BIM can communicate the required function to the new I/O
module.

Reset Key
The reset key sets the module back to the factory settings (default function on each of
the I/O points):
 The reset key is inserted in place of the address key and then swiveled out again.
 The module indicates the reset by briefly lighting all its I/O status LEDs.
 Note that a reset is only possible when the module is supplied with 24 Vdc.

TX-I/O Power Supply and Bus Modules


The TX-I/O™ Power Supply and Bus Modules provide power, communications, and
expansion options for the TX-I/O Island Bus.

Power and Communication Modules


The TX-I/O Power Supply and Bus Connection Module provide the following functions
for the island bus:

63
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

Function
Product TX-I/O Bus Communication 24 Vdc power 24 Vac power

TX-I/O Power Supply Signal pass-thru Output 28.8 W  NEC Class 2 Output , 96 VA
(TXS1.12F4) (1.2A at 24 Vdc) max., fused at 4A
 Class 1 Power Limited Input,
150 VA max.

Bus Connection Module  Signal pass-thru Pass-thru  NEC Class 2 Output, 96 VA


(TXS1.EF4)  Allows for external max., fused at 4A
connection of I/O  Class 1 Power Limited Input, 96
signals. VA max.

The P1 Bus Interface Module (BIM) provides the following functions for the island bus:

Function
Product TX-I/O Bus Communication 24 Vdc power 24 Vac power

P1 Bus Interface Module Protocol translation 14.4 W (0.6A at  NEC Class 2 Output, 96 VA
(TXB1.P1) 24 Vdc) max., fused at 4A
 Class 1 Power Limited Input,
125 VA max.

Island Bus Expansion Module


The Island Bus Expansion (IBE) module provides the following functions for the island
bus:

Product TX-I/O Bus Communication Function

Island Bus Expansion  Signal pass-thru of Increases the distance between the primary field panel
Module (TXA1.IBE) Communication Data and expansion field panels on the island bus
(CD)
 Allows for external
connection of the I/O
signals
 RS-485 interface

TX-I/O Power Supply Overview


The TX-I/O Power Supply bridges communication and power from one DIN rail to
another and generates 28.8 W (1.2A at 24 Vdc) to power TX-I/O modules and
peripheral devices.
 An LED provides an indication of 24 Vdc on the TX-I/O bus.
 Up to 4 TX-I/O Power Supplies can be operated in parallel, with a maximum of two
per DIN rail.
 It can be located within a row of TX-I/O modules or at the beginning of a new DIN
rail.
The TX-I/O Power Supply performs the following functions:

64
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
TX-I/O Product Range Overview

 Transfers 24 Vac at 4A to power TX-I/O modules and peripheral devices.


 Provides an input point for 24 Vac to power additional peripheral devices.
– Isolates the 24 Vac peripheral device supply in case of overload or short-circuit.
– The replaceable AC fuse can be accessed from an installed module.
– Indicates the AC fuse status with an LED for easy diagnostics.
 Routes the bus signal between DIN rails (+24 Vdc Communication Supply (CS)
and Communication Data (CD) signals).

Supply Terminal Connections


 24 Vac supply terminals are fused (replaceable) for Class 2 (24 Vac at 50/60 Hz)
through the TX-I/O Power Supply.
 24 Vdc supply terminals are connected in the I/O module, not in the terminal base.
24 Vdc is supplied and overload protected in the TX-I/O Power Supply.

Bus Connection Module Overview


The Bus Connection Module bridges communication and power from one DIN rail to
another. It provides the bus signal, module supply voltage, and field device supply
voltage to TX-I/O Modules on an additional DIN rail.
The Bus Connection Module performs the following functions:
 Passes 24 Vac at 4A to power TX-I/O modules and peripheral devices.
 Provides an input point for 24 Vac to power additional peripheral devices.
– Isolates the 24 Vac peripheral device supply in case of overload or short-circuit.
– The replaceable AC fuse can be accessed from an installed module.
– Indicates the AC fuse status with an LED for easy diagnostics.
 Routes the bus signal between DIN rails (+24 Vdc Communication Supply (CS)
and Communication Data (CD) signals).

Supply Terminal Connections


 24 Vdc is supplied to terminals one and four (CS) and to both ends of the TX-I/O
bus connector for distribution to connected TX-I/O modules and external devices.
 24 Vac is passed through an internal fuse from terminals three and four (system
neutral) to the male TX-I/O bus connector.
 External devices draw power from the 24 Vdc, 24 Vac, and system neutral
terminals on the TX-I/O modules.
 24 Vdc supply terminals are connected in the I/O module, not in the terminal base.
24 Vdc is current-limited in the Bus Connection Module.

Island Bus Expansion Module Overview


The TX-I/O Island Bus Expansion (IBE) module increases the distance between the
primary field panel and expansion field panels on the island bus. Up to 4 expansion
enclosures may be connected to the primary enclosure using IBEs, for a maximum of
five IBEs on the island bus.

65
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

 Each IBE supports two segments of up to 200 ft (61 m) each.


 All expansion field panels must be connected to the same building approved earth
ground as the primary field panel.
 Each IBE must be installed on the male bus connector of the TX-I/O Power Supply
or a Bus Connection Module which is connected to a TX-I/O Power Supply.
 An LED provides an indication of island bus communication.
 A programming tool is not required.
For information on expanding an island bus with the IBE, contact your local Siemens
Industry representative.

PX Series Enclosures and Service Boxes


PX Series enclosures house both electronic and pneumatic components. The
enclosures include a perforated backplane for mounting PXC Series field panels or
other electronic or pneumatic components.
General features of the enclosures includes:
 Availability in three sizes to match installation needs: 18-, 19-, and 34-inch.
 Sturdy construction, which accommodates secure conduit fittings and protects
components against incidental contact and falling dirt.
 UL Smoke Control listed for indoor use (19- and 34-inch enclosures only).
 Multiple knockouts along the top and bottom.
 Perforated backplane, which extends wall-to-wall for mounting of additional
equipment.
 Spacious interior for easy routing and termination of wiring.
The 18-inch enclosure is a pull-box type utility cabinet for low cost installations. It is
equipped with the following:
 Factory-installed 16” × 12” perforated panel
 DIN rail and wire tie bar kit
The 19- or 34-inch PX series enclosures are equipped with the following:
 Factory-installed backplane assembly, which includes wire tie down rails and DIN
rails
 Label pouch
 Hinged door and key lock
 Conduit knockouts and venting

PX Series Service Box Features


The PX Series Service Box Assemblies transform either 115 Vac or 230 Vac to 24 Vac
sized for either 192 VA or 384 VA.
 The 192 VA service boxes mount directly inside a 19- or 34-inch PX Series
Enclosure.
 The 384 VA service boxes provide additional power for larger systems and mount
only in the 34-inch PX Series Enclosure.

66
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

The service boxes provide protection against electrical transients and are Smoke
Control and Energy Management listed when installed according to the Service Box
Assemblies Installation Instructions (553-131).
The service box assemblies consist of the following:
 Chassis for mounting inside enclosure.
 ON/OFF circuit breaker for transformer.
 Two Class 1 power limited 24 Vac outputs, which include one terminal for earth
ground for use inside enclosure only.
 One Class 2 output with circuit breaker to distribute up to 96 VA for use outside the
enclosure.
 Wire cover for field connections.
 Duplex Service Outlet (115 Vac models only).
 Optional sidewall kits PXA-SW192VA and PXA-SW384VA may be used for
installation in third-party enclosures, such as motor control cabinets.

PX Series Service Box (115V), 34-inch enclosure.

67
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

PX Series Service Box (115V), 19-inch enclosure.

PX Series Service Box Connectors.

 Each Service Box distributes the total 24 Vac power provided to the plug-in
terminations on the left side.
– Two Class 1 power-limited terminations distribute up to the total power to
controllers and power supplies inside the same enclosure.
– Earth ground is provided on the CTLR termination.
– One Class 2 termination distributes up to 96 VA to auxiliary devices outside of
the enclosure.
 Each 115VAC Service Box has a duplex outlet on the front to power accessory
devices such as modems and Portable Operator’s Terminals.

Product Numbers

68
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

Product Number Description

PXA-SB115V192VA PX Series Service Box—115V, 24 Vac, 50/60 Hz, 192 VA

PXA-SB115V384VA PX Series Service Box—115V, 24 Vac, 50/60 Hz, 384 VA

PXA-SB230V192VA PX Series Service Box—230V, 24 Vac, 50/60 Hz, 192 VA

PXA-SB230V384VA PX Series Service Box—230V, 24 Vac, 50/60 Hz, 384 VA

PXA-ENC18 18" Enclosure (Utility Cabinet) (UL Listed NEMA Type 1 Enclosure)

PXA-ENC19 19” Enclosure (UL Listed NEMA Type 1 Enclosure)

PXA-ENC34 34” Enclosure (UL Listed NEMA Type 1 Enclosure)

PX Series Enclosure Specifications

PX Series 18" Enclosure Specifications


Dimensions (H × W × D)

PXA-ENC18 18" × 14" × 6"


(457.2 mm × 355.6 mm × 152.4 mm)
UL Listed NEMA Type 1 Enclosure, Pull-box style

Operating Environment

Ambient operating environment +32°F to +122°F (0°C to +50°C), 93% rh (Non-condensing)

Mounting Surface Building wall or structural member (Do not mount on HVAC components or any
other vibrating surface)

Agency Listings

Agency Compliance UL 508A (acceptable for UL 916 applications)


FCC Compliance

PX Series 19" and 34" Enclosure Specifications


Dimensions (H × W × D)

PXA-ENC19 19" × 22" × 5.75"


(482.6 mm × 558.8 mm × 146.05 mm)
UL Listed NEMA Type 1 Enclosure, Hinged Door with lock

PXA-ENC34 34" × 22" × 5.75"


(863.6 mm × 558.8 mm × 146.05 mm)
UL Listed NEMA Type 1 Enclosure, Hinged Door with lock

Operating Environment

Ambient operating environment +32°F to +122°F (0°C to +50°C), 93% rh (Non-condensing)

69
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

Mounting Surface Building wall or structural member (Do not mount on HVAC components or any
other vibrating surface.)

Agency Listings

UL UL 864 UUKL Smoke Control Equipment


ULC-C100 UUKL7
UL 916 PAZX
UL 508A

Agency Compliance FCC Compliance


Australian EMC Framework - with metal enclosure, maximum opening size is 34"
European EMC Directive (CE) - with metal enclosure, maximum opening size is 34"
European Low Voltage Directive (LVD)

PX Series Service Box Specifications


Power Requirements for 115 Vac PXA-SB115V192VA
Service Boxes Input: 115 Vac +/- 15%, 50/60Hz +/- 5%, 220VA maximum, 2A CB
Output: 24Vac +/- 20%, 50/60Hz +/- 5%, 192VA maximum
PXA-SB115V384VA
Input: 115 Vac +/- 15%, 50/60Hz +/- 5%, 440VA maximum, 4A CB
Output: 24Vac +/- 20%, 50/60Hz +/- 5%, 384VA maximum

115 Vac models also have a duplex outlet, which is protected by Mains 20A or 15A
CB for use internal to enclosure to power laptop and peripheral devices.

Power Requirements for 230 Vac PXA-SB230V192VA


Service Boxes Input: 230Vac +/- 15%, 50/60Hz +/- 5%, 220VA maximum, 1A CB
Output: 24Vac +/- 20%, 50/60Hz +/- 5%, 192VA maximum
PXA-SB230V384VA
Input: 230 Vac +/- 15%, 50/60Hz +/- 5%, 440VA maximum, 2A CB
Output: 24Vac +/- 20%, 50/60Hz +/- 5%, 384VA maximum

Service Box Output Jacks One 3-terminal and one 2-terminal NEC Class 1 output jack
for use internal to enclosure to power system components.

One 2-terminal NEC Class 2 output jack with 4A CB


for use external to enclosure to power actuators.

PX Series Enclosure Placement

70
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

CAUTION
Do not mount the enclosure on ductwork, HVAC components, or any other vibrating
surface.
● Mount the enclosure at least 12 feet (3.7 m) away from devices that can generate
Radio Frequency Interference (RFI), such as Electro-pneumatic devices (EPs),
relays, and walkie-talkies.
● Mount the enclosure at least 5 feet (1.5 m) away from 100 kVa or larger motors
and variable frequency drives (VFD).

CAUTION
If the enclosure is mounted under a wire trough or any other obstruction, provide a
minimum vertical clearance of 2 inches (50.8 mm) to allow for installation and removal
of the enclosure door.

71
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 2—Hardware Features
PX Series Enclosures and Service Boxes

 Space between door panel and opening obstruction must be at least 11 inches
(279.4 mm) to allow for door removal at 40 degrees, or 28 inches (711 mm) with a
cabinet mounting at least 19 inches (483 mm) from the left side wall to allow door
to completely open at 135 degrees.
 5 inches (127 mm) minimum horizontal distance between the enclosure and any
obstruction to the left and right.
 7 inches (178 mm) minimum depth out from the wall on the left (hinged) side for
door clearance.

72
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 3—Applications
Operator Interface

Chapter 3—Applications
Chapter 3 describes the program and applications provided with or available for the
PXC PXC Modular Series. The following topics are discussed in this chapter:
 Operator Interface
– Field Panel GO
 Powers Process Control Language (PPCL) Point Database and Control Program
– Control Programs
– Point Database
 Applications
 Customized Applications

Operator Interface
An operator issues commands or requests to the PXC Modular using an operator
terminal and the operator interface. The operator interface is the software that allows
the operator to communicate interactively with the PXC Modular Series. The operator
interface does the following:
 Interprets and processes commands entered from operator terminals.
 Formats and sends all output directed to the operator.
 Provides levels of operator access that control an operator’s authority to perform
certain functions.
The operator interface is described in detail in the APOGEE P2 ALN Field Panel User's
Manual or APOGEE BACnet ALN Field Panel User's Manual (125-3019 or 125-3020).
This manual is designed to help you become familiar with and use the operator
interface. It describes the functions necessary for everyday operation of your system,
plus the higher-level functions for commanding, displaying, editing, scheduling,
networking, alarm management, and others.

Field Panel GO
The Field Panel GO license provides a Web-based user interface for your APOGEE®
Building Automation System. It is an ideal solution for small or remote facilities with
field panels on an Ethernet TCP/IP Automation Level Network (ALN).
A Field Panel GO Web server-enabled controller can accommodate an unlimited
number of user accounts, with up to two concurrent operator sessions. And each user
account can be defined with customized levels of access and privileges to the system.
Field Panel GO encompasses the following operator applications:
 Alarm Status and acknowledgement
 Graphical Monitoring and Control
 Point Commander
 Schedule Overrides
 Status Reporting

73
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 3—Applications
Powers Process Control Language (PPCL) Control Program and Point Database

 Historical Data Reporting


 Setup and Customization
Contact your local Siemens Industry representative for more information on Field Panel
GO.

Powers Process Control Language (PPCL) Control


Program and Point Database
The control programs and point database are stored in RAM. This information can also
be saved or loaded into the PXC Modular using APOGEE Datamate software or Insight
software.

Control Programs
The control programs define all user-defined control logic, calculations, applications,
and so on for the PXC Modular. PPCL is written in an English-based programming
language called Powers Process Control Language (PPCL). It is a powerful
programming language developed specifically for controlling Heating, Ventilating, and
Air Conditioning (HVAC) equipment. Multiple PPCL programs can be run
simultaneously to provide instructions for the PXC Modular to operate equipment,
control system loads, and optimize the system operation.
For a complete description of PPCL and how to use it, see the APOGEE Powers
Process Control Language (PPCL) User's Manual (125-1896). This manual is available
from your local Siemens Industry representative.

Point Database
The PXC Modular Series has the basic capabilities required to control and monitor a
facility. However, the operator (or the installer) must program specific instructions into
the PXC Modular and create databases that are customized for your particular facility.
The databases contain information, such as point names, addresses, schedules, and
alarm information for the equipment being supervised by the PXC Modular.
The PXC Modular uses information from the point database to define each point so
that the firmware and the software know how to evaluate or command the point.
Among the items kept in the point database are the following:
 Location, or address of field inputs/outputs
 Logical point names and descriptions of points
 Point type
 Alarm information
 Current value of a point
 Information to convert analog signals to engineering units (slope and intercept
constants)
The point database is described in detail in the APOGEE P2 ALN Field Panel User's
Manual or APOGEE BACnet ALN Field Panel User's Manual (125-3019 or 125-3020).

74
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 3—Applications
Applications

Applications
Applications are an important part of the energy management capabilities of your
system. The applications that you can incorporate into the operation of your system
include:
 Adaptive Control
 Alarm Management
 Daylight Saving Time
 Equipment Scheduling
 Loop/Loop Tuning
 Start/Stop Time Optimization (SSTO)
 Time and Calendar (schedules, Daylight Saving Time)
 Trend Data Collection
 User Access and Privileges

Adaptive Control
Adaptive control is a closed loop control algorithm that auto-adjusts to compensate for
mechanical system/load/seasonal changes. It is designed to eliminate the
compromises of traditional Proportional, Integral, Derivative (PID) control. When
compared to traditional PID control, adaptive control provides more efficient, robust,
fast, and stable control. Adaptive control achieves superior performance in a dynamic,
non-linear system in terms of response time and holding steady state, while minimizing
error, oscillations, and actuator repositioning.

Alarm Management
An alarm is a status that indicates whether a point value or state is above or below a
defined value. Alarm management is the strategy used to define, route, acknowledge,
and resolve those alarms.
Points are defined as alarmable for the following reasons:
 To prevent critical problems. Points that affect human safety or can cause a severe
problem in building operation should be defined as alarmable. For example, an
alarm that notifies you that the temperature of a heating coil is too low and action
must be taken before it freezes.
 To notify you when equipment is not functioning properly. Sometimes problems
may occur and go unnoticed. Alarming is a useful tool to identify equipment that is
not working properly and to prevent other devices from becoming damaged.
 To announce scheduled maintenance. For example, an alarm can notify you when
it is time to change air filters.

75
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 3—Applications
Applications

Daylight Saving Time


The Daylight Saving Time (DST) functionality adjusts the system time to match the
daylight saving time change-over. If your area uses daylight saving time, this feature
offers a convenient method to automatically adjust the system clock.

Equipment Scheduling
Equipment Scheduling is designed to provide 365-day, time-based control of a space
in a facility. The basic design of this application begins with a definition of the space,
called a zone. The state of the zone dictates how the field panel controls the points
associated to that space. The state of the zone is known as the mode (in this
document it is referred to as the current mode value of the zone).

Loop/Loop Tuning
The loop application is the PPCL Proportional, Integral, Derivative (PID) control loop
algorithm. The loop tuning application evaluates and calculates gains and sample
times for existing LOOP statements in PPCL. This feature calculates appropriate
Proportional, Integral and Derivative (PID) gains and sample time for a selected control
loop, based on specific building and control information defined in the LOOP
statement. When complete, you decide how to apply the newly calculated variables.

Start-Stop Time Optimization (SSTO)


Start/Stop Time Optimization (SSTO) is an optional, self-adjusting routine that affects
the start and stop times of various occupancy modes. SSTO can help conserve energy
by starting a heating or cooling process, prior to occupancy, as late as possible. SSTO
can also stop heating or cooling a zone as early as possible, prior to vacancy.
For example, a meeting in August occurs at 1:00 P.M. and lasts until 4:00 P.M. Based
on the information provided in SSTO parameters, the equipment scheduling application
calculates the latest possible time cooling can start and still reach the cooling setpoint.
Also, calculations are made to determine the earliest time cooling can stop without
affecting comfort limits.

Time and Calendar


Calendar dates (in the form of day shifts and replacement days) are entries used to
supplement the Equipment Scheduling application.
Time functions compensate for Daylight Savings Time (DST) and provide time-based
control for building equipment.

Trend Data Collection


Trending is a function that records point data over time. Trend data is either collected
when the current point value changes by a specified amount (the trend COV limit), or
point values are recorded after the system waits a specific amount of time and then the
process is repeated.

76
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 3—Applications
Customized Applications

Trend data can be uploaded from the field panel to the Insight workstation for storage
and reporting, and the data can be converted to several spreadsheet formats for
further analysis and reporting.

User Access and Privileges


A user issues commands or requests to the PXC Modular Series using an operator
terminal and the operator interface program that resides in the PXC Modular Series.
The operations that a particular user can perform depend on the access level assigned
to each field panel function in their user account.
User accounts are used to manage access and security for field panels on a specified
Automation Level Network (ALN). By creating individual accounts, a system
administrator can control each user’s access to objects and functions residing in field
panels on a specified ALN.
Specifically, a system administrator can perform the following tasks:
 Define the users that can access an ALN
 Assign access to access groups
 Assign privileges to field panel functions residing on an ALN

Controlling User Access to Field Panel Functions


The following four access levels can be assigned to any field panel function for any
user.
 No Access – Users cannot see the function.
 Read Only – Users can only view the value or status of objects.
 Command – Users can command or display the value or status of objects.
 Edit – Users can add, delete, command, modify, and view objects.

Example
If a user has a Command access level for the Point Editing function, then only the
functionality required to command a point is available to them. They do not see or have
access to the prompts required to add, modify, or delete a point definition.
For more information on user accounts and privileges, see the APOGEE P2 ALN Field
Panel User's Manual or APOGEE BACnet ALN Field Panel User's Manual (125-3019
or 125-3020).

Customized Applications
Some PXC Modular Series applications are created in the Powers Process Control
Language (PPCL). These applications use PPCL statements and additional hardware
to perform customized operations or functions in your system. Examples of
applications created in PPCL include:
 Duty Cycling
 Enthalpy and Dry Bulb Economizer Control
 Peak Demand Limiting (PDL)

77
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 3—Applications
Customized Applications

Information on how to customize these applications for your facility is included in the
APOGEE Powers Process Control Language (PPCL) User's Manual (125-1896) and
the APOGEE P2 ALN Field Panel User's Manual or APOGEE BACnet ALN Field Panel
User's Manual (125-3019 or 125-3020). These manuals are available from your
Siemens Industry representative.

78
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Service Information

Chapter 4—Troubleshooting
NOTE:
The following information is for qualified service personnel only.

Chapter 4 describes corrective measures you can take if you encounter a problem with
a PXC Modular Series controller. If you encounter a symptom or a problem not
covered in this manual, contact your Siemens Industry representative. The following
topics are discussed in this chapter:
 Service Information
– Electrostatic Discharge Requirements
– Error Status Messages
– Ordering Replacement Parts
– Replacing the Batteries
– Reinstalling the Mounting Tabs
 Troubleshooting the PXC Modular and TX-I/O Island Bus

Service Information
This section describes corrective measures you can take if you encounter a problem
with a PXC Modular Series controller.
If you encounter a symptom or a problem not covered in this manual, contact your
Siemens Industry representative.

NOTE:
When removing power to a controller to perform maintenance or service, make sure
that the person in charge of the facility is aware of this and that appropriate steps are
taken to keep the building in control.

NOTE:
When troubleshooting, record the problem and what actions were performed
immediately before the problem occurred. Being able to describe the problem in detail
is important should you need assistance from your local Siemens Industry
representative.

To view the status of the PXC Modular and to call up reports for troubleshooting, you
can use an operator's terminal and the operator interface or an Insight workstation. For
more information, see the following documentation:
 APOGEE P2 ALN Field Panel User's Manual or APOGEE BACnet ALN Field Panel
User's Manual (125-3019 or 125-3020).
 Insight Revision 3.x Documentation. To view this documentation, see the Insight
Online Documentation window, which you can access from the Insight Main Menu
or the Insight program group.

79
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Service Information

It is good practice to back up the PXC Modular database routinely and whenever
changes are made to the database or new equipment is added.
While performing the troubleshooting procedures outlined in this manual, you may wish
to refer to the APOGEE Wiring Guidelines for Field Panels and Equipment Controllers
(125-3002).

Electrostatic Discharge
An electrostatic discharge (ESD) wrist strap is generally not required when installing or
servicing a PXC Modular. However, if the field panel is installed in a very dry
environment where a high static discharge is likely, an ESD wrist strap is
recommended.

Error Status Messages


For error status message descriptions, see the APOGEE P2 ALN Field Panel User's
Manual or APOGEE BACnet ALN Field Panel User's Manual (125-3019 or 125-3020).

Ordering Replacement Parts


If a PXC Modular Series is not operating correctly, it should be replaced.

Replacing the Batteries

CAUTION
AC power must be ON during battery replacement. Otherwise, data loss will occur.

NOTE:
The battery is taped in the tray to secure it during shipping. The tape does not need to
be replaced.

1. Pull the release tab on the curved side of the battery compartment cover.
2. Remove the battery compartment cover.
3. Remove the failed battery, and place a fresh battery in the tray with the positive (+)
and negative (-) ends properly aligned.
- For the AA battery, make sure the positive (+) and negative (-) ends are
properly aligned.
- For the coin cell battery, make sure the positive (+) side is facing up.
4. Replace the battery compartment cover.

NOTE:
The LOW BATT LED remains ON if an alkaline battery is used in Compact models
with extended temperature range operation.

80
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Service Information

Replacing the AA Battery.

Reinstalling the Mounting Tabs


Do the following to reinstall a DIN mounting tab:
1. Place the wire spring clip into the pocket in the channel for the mounting tab.
2. Make sure the mounting tab is face down.
3. Working from the center (inside) of the base, slide the mounting tab into the
channel. (See the following figure.)

NOTE:
The end with the screw hole slides into the channel first.

81
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Troubleshooting Modular Field Panels

Reinstalling a DIN Mounting Tab.

Troubleshooting Modular Field Panels


Find the symptom below that best describes the problem and perform the corrective
action that follows.
If the problem persists or other symptoms are present, contact your Siemens Industry
representative.

CAUTION
Before performing any RS-485 Expansion Module troubleshooting procedures,
complete a successful check-out of the PXC Modular.

BATT LOW LED

The BATT LOW LED is on or the battery low warning is displayed at the
operator's terminal.

CAUTION
If you do not have a current backup, save the database before continuing.

1. Check that the mylar insert was removed from the AA (LR6) battery holder.
2. Check for polarity (+ to +) and (- to -).
3. Check that the battery is properly seated in the battery holder.
4. Replace the battery.

82
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Troubleshooting Modular Field Panels

RUN LED

The RUN LED is on solid.


 The RUN LED is steadily lit during normal operation to indicate that 24 Vac power
is ON and the application firmware has booted.

The RUN LED is off.


1. Verify that power is connected.
2. Check the service box and transformer ON switches.
3. If power is ON, verify that the application firmware has booted.
4. Measure voltage on 24V~ and (Terminals 1 and 2).

The RS-485 Expansion Module RUN LED is off.


1. Check that the Expansion Module is properly seated on the DIN rail.
2. Verify the connection between the RS-485 Expansion Module and the PXC
Modular.

TX and RX LEDs

Communication

Points cannot be read or commanded from the operator's terminal.


1. Verify that failed points have been properly addressed.
2. Verify the status of the points at the operator's terminal. Verify that points are not
under Operator priority.

No communication over the FLN trunk.


1. Verify the FLN address and communication speed.
2. Verify the FLN trunk is connected to the correct FLN port.

Display

NOTE:
In USE FW REV TABLE ALN mode, RS-485 parameters are displayed and may be
entered as a selection. However, when in RS-485 ALN mode, USE FW REV TABLE
ALN parameters are not an available selection.

83
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Troubleshooting the TX-I/O Island Bus

PXC Modular defaults to Ethernet ALN but continues to display


parameters for RS-485 P2 ALN.
1. Generate the Field Panel Configuration report by entering the following at the HMI:
S, H, F, D (System, Hardware, Fieldpanels, Display).
2. Verify the field panel settings on the Field Panel Configuration report (such as the
ALN baud rate for P2 ALN or an IP address for Ethernet TCP/IP ALN).
3. Verify the current ALN type on the Field Panel Configuration report.

NOTE:
Changing the ALN type coldstarts the field panel.

4. If needed, change the ALN type by entering the following at the HMI: S, H, F, C, E,
M (System, Hardware, Fieldpanels, Config, nEttype, Modify). (S, H, F, C, S, T for
Firmware Revision 2.8.3 and earlier.)

Errors

PXC Modular program and database are not down-line loading properly.
 Verify that the Insight software is at least Revision 3.8.1 (P2) or 3.9.1 (BACnet).

Troubleshooting the TX-I/O Island Bus


The 24 Vac LED on the TX-I/O Power Supply or the P1 Bus Interface
Module (BIM) is OFF.
1. Check for 24 Vac input.
2. Replace the fuse (4A, 5 × 20 mm, 250V, medium-acting, ceramic fuse).

All points on the TX-I/O island bus are failed.


 Verify all three signals, System Neutral ( ), Communication Data (CD), and
Communication Supply (CS) are connected throughout the entire TX-I/O island
bus.

The I/O module status LED (under the address key) is flashing or the I/O
point status LED is flashing on an open point. All points are operating
normally.

84
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Chapter 4—Troubleshooting
Troubleshooting the TX-I/O Island Bus

CAUTION
The TX-I/O™ island bus must extend from the male bus connector of the TX-I/O
Power Supply or Bus Connection Module.
• The TX-I/O Power Supply and Bus Connection Module only supply 24 Vac to I/O
modules on the male bus connector.
• I/O modules on the female bus connector of the TX-I/O Power Supply or Bus
Connection Module do not receive power and have a fault condition.

A point is failed or the point type displayed does not correspond to the
point type defined in the database.
1. Using the job drawing or TX-I/O Island Bus layout sheet, verify that the address
keys are in the correct module.
2. Reset the module to factory settings.
- Verify that the module is supplied with 24 Vdc.
- Remove keys that are in the wrong module.
- Insert and then remove the reset key.
- Cycle power to the module.
- Insert the correct address key.

A current point on a Super Universal Module is failed.


 Verify that the sensor supply wire is connected to the DC terminal (3, 11, 20, or
28).

85
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Glossary

Glossary
The glossary contains terms and acronyms that are used in this manual.

1
100Base-TX: Fast Ethernet network implementation. 100Base-TX stands for 10Mbps
baseband twisted-pair cable. The “X” stands for 100Base-X, the IEEE identifier for the
media system used by 100Base-TX.
10Base-T: Ethernet network implementation. 10Base-T stands for 10Mbps baseband
twisted-pair cable.

A
Adaptive Control: Closed loop control algorithm that auto-adjusts to compensate for
mechanical system/load/seasonal changes.
AEM/AEM100/AEM200: Devices that allow APOGEE field panel networks to
communicate with the Insight workstation across an Ethernet network. The APOGEE
Ethernet Microserver (AEM) operates on a 10Base-Tconnection, but can also be
routed across low speed networks (for example, across Frame Relay). The AEM100
supports auto-sensing 10Base-T and 100Base-TX Ethernet communication. The
AEM200 adds a second serial port, allowing MMI access without disconnecting from
the Insight network.
alarm priority: Ranking of a point alarm.
Automation Level Network (ALN) Devices: Extends Protocol 2 networks, leased line
Modem, TI-2, Fiber Optic TIs, and TIE.
analog input-electric: Analog input point that receives either a current, voltage, or
resistance input signal.
analog output-pneumatic: Analog output point that outputs a pneumatic signal.
AO-V point: Physical analog output point that generates a voltage signal.
Automation Level Network (ALN): The level in the communication hierarchy that
consists of automation stations, automation devices, Application-Specific Controllers
(ASCs), etc.

B
BACnet: A data communication protocol for Building Automation and Control Networks,
ANSI/ASHRAE Standard 135-2004. BACnet allows devices from multiple
manufacturers to work together on a network.
BACnet Broadcast Message Device (BBMD): BBMDs pass BACnet Broadcast
Messages to other BBMDs on the network, allowing these messages to reach BACnet
devices on the other side of a subnet router.
BACnet Encoded Name: A numeric representation of an object name that exceeds the
APOGEE standard of 30 alphanumeric characters or less per name.
BACnet/IP: BACnet over IP protocol.
BBMD: See BACnet Broadcast Message Device.

86
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Glossary

broadcast: Destination IP address that represents all interfaces on all hosts. Usually,
this is restricted to all hosts on the local subnet.

C
command priority: Ranking of a point command.
current value: Last commanded or sensed value of a logical point.

D
Device ID: Uniquely identifies a device object on the BACnet Inter network.
Device Instance Number: A number assigned to a BACnet device (for example, a
BACnet field panel) that uniquely identifies it on the BACnet/IP network.
Device port: A USB Device port supports a generic serial interface for an HMI or Tool
connection.
Device Specific Name: A textual representation of a BACnet object name that meets
the APOGEE naming standard of 30 alphanumeric characters or less.
digitized value: Integer value used by the field panel to determine the logical value,
state, and condition of logical points.
Domain Name Server (DNS): Common method of assigning computer names in UNIX-
based networks. A DNS server maintains a list of host names and IP addresses,
allowing computers that query them to find remote computers by specifying host
names rather than IP addresses. DNS is a distributed database; therefore, DNS
servers can be configured to use a sequence of name servers, based on the domain in
the name being looked for.
Dynamic Host Configuration Protocol (DHCP): Protocol used for automatic TCP/IP
configuration of nodes across a network. DHCP dynamically assigns addresses to
nodes and allows for central administration of addresses.
dynamic point information: Information stored in the point database that may change
during system operation and is not part of the data entered when defining points.

E
enclosure: Metal case that houses the field panel components.
English units: The foot-pound-second system of units for weights and measurements.
enhanced alarming: Application that allows floating alarms and alarm segregation.
Ethernet ready: Any device that communicates over Ethernet cabling. For example,
both Ethernet ALN and BACnet/IP field panels are Ethernet ready, even though they
use different communication protocols.

F
Field Level Network (FLN): A data communications link that passes information
between an FLN device and an Automation Level Network (ALN) device. Terminal
Equipment Controllers (TEC) are examples of FLN devices.

87
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Glossary

H
HAND-OFF-AUTO (HOA) switches: Manually operated control switches located on the
face of HOA-equipped controllers that enable digital output points to be manually
placed into HAND (ON), OFF, or AUTO control. Analog outputs can be placed into
AUTO or multiple manual control positions.
Host port: A USB Host port provides support for USB modems and line printers.
Human-Machine Interface (HMI) port: Interfaces of various hardware and/or software
units allowing the operator to transfer information to a technical system and/or receive
information from the same.

I
Instance ID: The identifying number for objects (for example, points) within a BACnet
device. Instance IDs can be assigned manually or automatically within the range set for
the host device.
Internet Protocol (IP): A connection-less protocol that allows a packet to travel across
multiple networks on its way to its destination. IP is the network layer of TCP/IP suite.
Intrinsic Alarming: BACnet alarming that incorporates alarm destinations (via
Notification Classes) within a single alarm message.

M
multicast: Destination IP address that represents one or more interfaces. IP datagrams
sent to a multicast address will be sent to all hosts participating in this multicast group.

N
notification class: Notification Class supports enable/disable based on the day of week
and time of day and the alarm priority for all points associated with it.

P
Plain Old Telephone Service (POTS): Acronym for the standard telephone service that
is used in most homes. Communication speed is generally restricted to 52K bps.
point condition: State of a point such as normal, alarm, alarm-by-command, failed,
operator disabled, or proofing.

R
Read Only Memory (ROM): Non-volatile, permanent, but field-programmable memory
that stores the operating system of the field panel. ROM stays intact even in the event
of a power surge, a power loss, or failure of the battery backup.
Remote Automation Level Network (ALN): Automation Level Network (ALN) hosted by
a remote field panel. The ALN is only seen at the remote site and at a centrally located
Insight workstation.
remote field panel: Field panel not directly connected to the Insight ALN. Remote field
panels connect over the telephone lines using a dial-up modem, or over an Ethernet
network using an AEM/AEM100/AEM200.

88
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Glossary

S
service box: Component that receives the line power and converts it to 24 Vac for the
field panel.

T
telnet: Program that runs on top of TCP/IP, it is the Internet standard protocol for
remote login.
text-based terminal: Operator terminal that displays and accepts text only.
To-Fault: A BACnet event indicating that the BACnet object (point) has transitioned to
the Fault state from some other state for the recipient or device. A BACnet object
mayor may not require acknowledgement of this event by a user.
To-Normal: A BACnet event indicating that the BACnet object (point) has transitioned
to the Normal state from some other state for the recipient or device. A BACnet object
mayor may not require acknowledgement of this event by a user.
To-OffNormal: A BACnet event indicating that the BACnet object (point) has
transitioned to the OffNormal state from some other state for the recipient or device.
OffNormal states in BACnet are: OffNormal, high-limit, low-limit, and life-safety-alarm.
A BACnet object may or may not require acknowledgement of this event by a user.
tombstone: Remnant or memento of a deleted record that is retained for a finite
amount of time in a node’s replication database. Tombstones are used to keep track of
locally deleted records that must be deleted from replication partners during future
global data replication sessions.
totalized value: Sum of information (in hours or minutes) about logical points such as
run time, total volume, and degree days.
Transmission Control Protocol/Internet Protocol (TCP/IP): Protocol suite developed by
the U.S. Department of Defense to link dissimilar computers across different kinds of
networks. TCP/IP is the transport protocol employed by the Internet and is commonly
used on Ethernet networks.

U
unbundle: Describes the action of entering a point that resides in an equipment
controller's database into the field panel's database so that it can be monitored and
controlled from the field panel.
Unicast: Destination IP address that represents a single interface to a single system. IP
datagrams sent to a unicast address are sent to a single interface on a single IP host.
User Datagram Protocol (UDP): TCP/IP protocol that provides simple datagram
services. UDP is a connection-less mode protocol that is layered on top of IP. UDP
does not guarantee delivery and is not used for applications that require
acknowledgements or re-transmission.

V
Virtual AEM: Without additional hardware, the Virtual AEM connects an RS-485
APOGEE Automation Level Network or individual field panels to a P2 Ethernet
network. (Additional license required.)

89
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Index

Index
Numerics B
10B/100B Ethernet port, 31 backup batteries
replacing, 80
A BACnet
Adaptive Control, 75 product features order of implementation, 13
alarm management, 75 BACnet MS/TP ALN
APOGEE automation networking number of field panels supported, 23
Ethernet TCP/IP ALN, 20 BACnet protocol, 12
Field Level Network (FLN), 24 BACnet/IP ALN
P2 Ethernet and BACnet/IP ALN over an IP network, number of field panels supported, 22
22 bus connection module, 63
remote ALN, 22
RS-485 P2 ALN, 19 C
Virtual AEM, 22 calendar dates, 76
APOGEE automation networking:Automation Level communication ports
Network (ALN), 17
10B/100B Ethernet, 31
APOGEE Ethernet Microserver (AEM), 14
HMI and Tool, 30
applications
compatibility
Adaptive Control, 75
BACnet product features order of implementation, 13
alarm management, 75
BACnet protocol, 12
calendar dates, 76
sharing APOGEE P2 values with BACnet devices, 12
customized applications, 77
TCP/IP protocol, 13
Daylight Saving Time (DST), 76
customized applications, 77
Equipment Scheduling, 76
loop/loop tuning, 76
D
Start-Stop Time Optimization (SSTO), 76
Database Backup to Flash, 28
time functions, 76
Daylight Saving Time (DST), 76
trend data collection, 76
DHCP server, 13, 13
user access and privileges, 77
DNS node name format, 14
Automation Level Network (ALN), 17
Domain Name Server, 13
10B/100B Ethernet port, 31
BACnet MS/TP ALN, 23
E
BACnet/IP, 22
electrostatic discharge (ESD), 80
HMI and Tool ports, 30
Equipment Scheduling, 76
simultaneous ALN access, 18
Auto-Restore of database, 28

90
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Index

Ethernet TCP/IP ALN S


number of field panels supported, 20 service information, 79
electrostatic discharge (ESD), 80
F reinstalling the mounting tabs, 81
Field Level Network (FLN), 24
replacing the batteries, 80
Flash Read-Only Memory (Flash ROM), 27
Start-Stop Time Optimization (SSTO), 76

H T
Human-Machine Interface (HMI)/Tool port, 30
TCP/IP protocol
address assignment, 13
I compatibility, 13
IP addresses, 13
default TCP/IP port number, 13
assignment, 13
default UDP port number, 14
island bus expansion (IBE) module, 63
device registration, 13
DNS node name format, 14
L network bandwidth, 14
loop/loop tuning, 76
network security, 14
required IP addresses, 13
M
Virtual AEM, 14
Management Level Network (MLN), 17
time functions, 76
memory
trend data collection, 76
compressed ROM, 28
troubleshooting
Flash Read-Only Memory (ROM), 27
24 Vac LED, 84
Random Access Memory (RAM), 29
BATT LOW LED, 82
I/O module status LED, 84
O
RUN LED, 83, 83, 83
operator interface, 73
TX-I/O product range, 59
TX-I/O Product Range
P
power and bus modules, 63
P1 bus interface module (BIM), 63
TX-I/O island bus, 33
power supply module, 63
Powers Process Control Language (PPCL), 74
U
UDP port number, 14
R
USB Device port, 31
Random Access Memory (RAM), 29
user access and privileges, 77
remote ALN
user accounts, 77
number of field panels supported, 22
RS-485 P2 ALN
number of field panels supported, 19

91
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Index

V
Virtual AEM, 22
default TCP/IP port number, 14

92
Siemens Industry, Inc. 125-3582(CA)
01/26/2011
Issued by © 2011 Copyright Siemens Switzerland Ltd
Siemens Industry, Inc. Technical specifications and availability subject to change without notice.
Building Technologies Division
1000 Deerfield Pkwy
Buffalo Grove IL 60089
Tel. +1 847-215-1000

Document-ID 125-3582(CA) 125-3582 PXC Modular Series Owner's Manual


Edition 01/26/2011

You might also like