Technical Information
WirelessHART Fieldgate SWG70
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications
with a control function.
WirelessHART Fieldgate The WirelessHART Fieldgate SWG70 acts as an interface between the WirelessHART network and a
SWG70 system that has an Ethernet or RS-485 connection.
Fieldgate is designed for installation in hazardous areas Zone 2. You can mount the antenna directly
on the Fieldgate or remotely depending on the requirements of the application.
System design The WirelessHART Fieldgate stores information received from the WirelessHART Adapter SWA70
or other WirelessHART field devices in a buffer which can be accessed by a host application via an
Ethernet or RS-485 connection. The figure shows a Fieldgate operating in a typical meshed Wire-
lessHART network architecture.
Ethernet 2
4 3
4
4
4
2
WirelessHART Fieldgate SWG70
Input
Communication interface WirelessHART communication interface (IEC 62591)
Input variables • Process variables according to HART standard are sent to the network by the field devices in the
burst mode.
• Up to 250 WirelessHART-based devices can be connected.
Output
Overview of versions and All Fieldgate SWG70 versions feature an Ethernet interface and a serial interface. Depending on the
protocols device version, this interface can support different protocols.
Fieldgate Interface Protocol
SWG70 version MODBUS EtherNet/IP HART-IP AMS
SWG70-xx-1 Ethernet X – X X
Modbus Serial (RS-485) X – X –
SWG70-xx-2 Ethernet X – X X
MODBUS + OPC 1) Serial (RS-485) X – X –
SWG70-xx-3 Ethernet – X X X
EtherNet/IP Serial (RS-485) – – X –
1) For OPC, there is an OPC DA server. The software is included in the scope of delivery and must be installed on
a Windows PC.
Transmission rate 100 Mbit/s (max. cable length 100 m at 25 °C ambient temperature)
3
WirelessHART Fieldgate SWG70
Transmission rate 100 Mbit/s (max. cable length 100 m at 25 °C ambient temperature)
Transmission rate Hardware or software configurable between 1200 Bit/s to 115200 Bit/s
Maximum bus length 1200 m (1230 yds), depending upon cable and transmission rate
Power supply
Power supply 20 VDC to 30 VDC SELV / PELV
Power <5 W
Connection facilities • Two 2-port terminal blocks, 2nd port for redundant power supply
• Screw terminals: 0.2 mm2 to 4 mm2 for solid wire, 0.2 mm2 to 2.5 mm2 for stranded wires
4
WirelessHART Fieldgate SWG70
Operating conditions
Application range The Fieldgate SWG70 serves as a gateway for WirelessHART networks.
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications
with a control function.
Installation conditions
Installation instructions Location: Avoid mounting the WirelessHART Fieldgate near a pipe or high-voltage equipment
wherever possible.
Where possible, the WirelessHART Fieldgate should be in radio contact with at least
20 % of all wireless field devices or adapters.
Under typical conditions, the maximum spacing is 250 m outdoors and 50 m indoors.
Installation: A remote antenna can be mounted outside a cabinet.
Orientation: With vertical antenna.
Protection If there is a risk of lightning, install suitable antenna accessories. See “Accessories” on
against page 7.
lightning: Connect the protective ground to the protective ground connection of the Fieldgate
housing. The minimum cross-section of the protective ground is 2.5 mm2.
Hazardous Fieldgates with the appropriate certification (see ordering information) can be
area: mounted in Zone 2.
The housing cover can be removed in Zone 2 to view the LEDs. It is not permitted to
operate any switches in an explosive atmosphere.
Environment
Ambient temperature range –20 °C to +60 °C (–4 °F to 140 °F)
5
WirelessHART Fieldgate SWG70
Mechanical Construction
Overall dimensions
52 (2.05)
85 (3.35)
150 (5.91)
150 (5.91)
57 (2.24)
115 (4.53)
115 (4.53)
From center
to center
240 - 250
(9.45 - 9.84)
10 (0.39)
20 (0.79)
20 (0.79)
52 (2.05) 228 (8.98)
85 (3.35) 257 (10.12)
Degree of protection IP 66 / IP 67
Operation
Configuration • Web browser via Ethernet
• FieldCare via Ethernet (HART IP CommDTM) or RS-485 (serial CommDTM)
Operating elements • 2x Pushbuttons within housing for selecting operating mode during local configuration
• 5x LEDs within housing for indicating current operating mode during local configuration
• 1x 8-position DIP switch for HART device address (1 to 4),
baudrate of RS485 interface (5 to 6), terminating resistor (7) and security mode (8)
hardware settings can be overwritten by software settings.
6
WirelessHART Fieldgate SWG70
Diagnosis • Display of wireless field device list with process values of selected field device
• Display of wireless field device list with burst message identification of selected field device
• Network monitoring of wireless communication events
• Diagnostic function
Accessories
Antenna accessories Note the following when selecting accessories for the antenna:
• The Ex approval for Fieldgate SWG70 is only valid for the 2 dBi antenna supplied.
• The antenna must comply with the rules for the usage of 2.4 GHz equipment that apply in the
country of installation. In case of doubt, please contact a regional expert for radio approvals.
• The gain is calculated from the difference in the antenna gain and the losses of the individual
components such as the cables and surge arrester. The gain may not exceed the 2 dBi limit.
• The WirelessHART range of the Fieldgate SWG70 depends on the coaxial cable used (attenuation)
between the Fieldgate and the antenna.
2
1
3 4 3