1 2 3 4 5 6 7 8 9 10

REV. No.

C01

CONTROL VALVE (OR GENERIC) SYMBOLS PRIMARY ELEMENT SYMBOLS (FLOW) GENERAL INSTRUMENTS GENERAL NOTES
CONTROL VALVE ACTUATOR SYMBOLS 1 2
SHT. No.

1. FOR GENERAL NOTES REFER TO DRAWING KZ01-PR-PID-53-00010.


001

GATE ORIFICE PLATE & FLANGES


DIAPHRAGM SHARED DISPLAY
FO SHARED CONTROL COMPUTER
3-WAY M
PACKAGE
SYSTEMS AND DISCRETE
A LOCATION / ACCESSIBILTY BASIC PROCESS SAFETY
MOTOR CONTROL INSTRUMENTED PLC
SOFTWARE A
SYSTEM (PAS) SYSTEM (SIS)
4-WAY RESTRICTION ORIFICE
LOCATED IN FIELD. U
CYLINDER / PISTON NOT PANEL, CABINET, OR CONSOLE MOUNTED.
ANGLE ORIFICE PLATE & QK CHANGE FITTING VISIBLE AT FIELD LOCATION. C
KZ01-PR-PID-53-00011

NORMALLY OPERATOR ACCESSIBLE. P NOTES


GLOBE M MAGNETIC
BALL FLOAT 1 FLOW ASSUMED LEFT TO RIGHT AS SHOWN.
LOCATED IN OR ON FRONT OF CENTRAL OR MAIN PANEL OR CONSOLE. U
3-WAY GLOBE NOZZLE VISIBLE ON FRONT OF PANEL OR ON VIDEO DISPLAY. C
DWG. No.

NORMALLY OPERATOR ACCESSIBLE AT PANEL FRONT OR CONSOLE. P 2


CAPACITANCE SENSOR MULTIPLE LOCATIONS OF THE SAME TYPE CAN BE DISTINGUISHED BY ADDING A
TEXT LABEL OR NOTE.
ANGLE GLOBE VORTEX
LOCATED IN REAR OF CENTRAL OR MAIN PANEL. U 3 ALL FIELD TRANSMITTERS WILL BE SUPPLIED WITH AN INTERNAL LOCAL INDICATOR
B BALL PRESS-BALANCED DIAPHRAGM FORWARD REVERSE PITOT TUBE
LOCATED IN CABINET BEHIND PANEL.
C UNLESS OTHERWISE STATED. B
NOT VISIBLE ON FRONT OF PANEL OR ON VIDEO DISPLAY.
NOT NORMALLY OPERATOR ACCESSIBLE AT PANEL OR CONSOLE. P 4 * REPRESENTS PARAMETERS LIKE FLOW (F), TEMPERATURE (T), LEVEL (L),
3-WAY BALL SINGLE PORT PITOT TUBE PRESSURE (P) ETC.
HANDWHEEL USED
WITH ANY ACTUATOR LOCATED IN OR ON FRONT OF SECONDARY OR LOCAL PANEL. U 5 CONTROL VALVES OF SIZE 8" AND BELOW SHALL BE OF MINIMUM 300# RATING.
GENERIC ROTARY (1/4 TURN) AVERAGING PITOT TUBE VISIBLE ON FRONT OF PANEL OR ON VIDEO DISPLAY. C
NORMALLY OPERATOR ACCESSIBLE AT PANEL FRONT. P
DISPLACEMENT FLOAT
BUTTERFLY WEIR
LOCATED IN REAR OF SECONDARY OR LOCAL PANEL. U
E/H
LOCATED IN FIELD CABINET. C
DIAPHRAGM SEGMENTAL WEDGE NOT VISIBLE ON FRONT OF PANEL OR ON VIDEO DISPLAY.
ELECTRO-HYDRAULIC P
NOT NORMALLY OPERATOR ACCESSIBLE AT PANEL OR CONSOLE.
G
SOLENOID 0000 SIGHT GLASS
C MANUAL C
3-WAY SOLENOID FE
0000 VARIABLE AREA (ROTAMETER)
PADDLE WHEEL FINAL CONTROL ELEMENTS INSTRUMENT FUNCTION SYMBOLS
4-WAY SOLENOID
E
VARIABLE AREA WITH UPSTREAM VALVE FINAL CONTROL ELEMENTS INCLUDE, BUT ARE NOT LIMITED TO, CONTROL VALVES, SOLENOID VALVES,
ANGLE SOLENOID P
PILOT LOUVERS, DAMPERS, MOTORS, VARIABLE SPEED DRIVES AND MACHINE COMPONENTS.
SUMMING X MULTIPLYING
STRAIGHTENING VANES
CONTROL VALVES ARE GENERALLY PNEUMATICALLY OPERATED AND FURNISHED WITH POSITIONERS
THAT MAY: DIVIDING DIFFERENCE
KNIFE S
A) BE ACTUATED BY A PNEUMATIC OR AN ELECTRONIC SIGNAL
SINGLE SOLENOID VENTURI
B) NOT BE SHOWN IF ALL CONTROL VALVES ARE FURNISHED WITH POSITIONERS.
d/dt DERIVATIVE HIGH SELECT
MULTIVANE 1 DAMP/LOUV CV TURBINE OR PROPELLER
D D
SQ RT LOW SELECT
S POS DISPLACEMENT
R SINGLE SOLENOID
MULTIVANE 2 DAMP/LOUV CV WITH REMOTE RESET
HIGH LIMIT X/X CONVERSION INPUT/OUTPUT
FLUME
PLUG CONTROL VALVES WITH PNEUMATIC, ELECTRONIC OR FIELDBUS SIGNAL:
LOW LIMIT X/X = A ANALOG
S ULTRASONIC TYPICAL INSTALLATION 5 SHOWN ON P&ID B BINARY
3-WAY PLUG R
SINGLE SOLENOID D DIGITAL
WITH MANUAL RESET n AVERAGING E VOLTAGE (EMF)
TARGET F FIELDBUS
PNEUMATIC SIGNAL: 4
n H HYDRAULIC
4-WAY PLUG *VJN X EXPONENTIAL
I CURRENT

4
CORIOLIS +

O ELECTROMAG-
*V BIAS NETIC, SONIC
E *V 4 E
SINGLE VANE DAMP/LOUV CV + P PNEUMATIC
+
R RESISTANCE
f(x)
UNSPECIFIED FUNCTION
SLIDE
f(x)
USER DEFINED
3-WAY SLIDE
PRESSURE RELIEF DEVICES
SELF ACTUATED DEVICES
RUPTURE DISC OR SAFETY HEAD FOR
ELECTRONIC SIGNAL: I/P
PRESSURE RELIEF (EXPLOSION PANEL) *VJN 4

4
SIGNAL LINES +

RUPTURE DISC OR SAFETY HEAD FOR PRESSURE REDUCING REGULATOR


CONNECTION TO PROCESS VACUUM RELIEF (EXPLOSION PANEL) *V (SELF CONTAINED)
4
PNEUMATIC SIGNAL
MISCELLANEOUS *V
+
+

F 4P6 RELIEF VALVE & CONNECTION SIZE F


ELECTRICAL/ELECTRONIC SIGNAL R LOCAL RESET PSET= 5000.00 kPa-g PRESSURE SET POINT
BACK PRESSURE REGULATOR
CAPILLARY TUBING VSET= 40.0 kPa-g VACUUM SET POINT
(SELF CONTAINED)
HYDRAULIC SIGNAL POSITIONER
PRESSURE RELIEF OR SAFETY VALVE C01 15/07/2015 APPROVED FOR CONSTRUCTION NP RB/KP/KK TAM/IDD
MECHANICAL LINK
DCS SOFTWARE LINK / SIS-PAS B01 27/03/2015 APPROVED FOR DESIGN AL RB/KP/KK TAM/IDD
CHEMICAL SEAL / DIAPHRAGM PRESSURE REDUCING REGULATOR
COMMUNICATION VACUUM RELIEF VALVE F/P WITH EXTERNAL TAP A02 27/10/2014 ISSUED FOR HAZOP NP KP/KK IDD
FF COMMUNICATION LINK FIELDBUS SIGNAL: 4
*VJN A01 12/09/2014 ISSUED FOR REVIEW AL SKG//KK TAM/IDD
(E.g. DCS TO FIELDBUS DEVICES.)

4
PILOT LIGHT OR PRESSURE AND VACUUM RELIEF VALVE REV DATE DESCRIPTION ORIG CHK'D APP'D
LINK TO/FROM DIFFERENT GAUGE GLASS ILLUMINATOR OR CONSERVATION VENT *V
SYSTEMS. (E.g. UCP TO PAS, *V 4 +
BACK PRESSURE REGULATOR
MCC TO PAS.) + WITH EXTERNAL TAP
S P
G SOLENOID VALVE - 3-WAY PILOT OPERATED RELIEF VALVE G
ELECTROMAGNETIC, SONIC WITH REMOTE SENSOR
SIGNAL OR FIBRE OPTIC CABLE
S DIFFERENTIAL PRESSURE REDUCING
SOLENOID VALVE 4-WAY SINGLE
VALVE FAILURE REGULATOR CLIENT: BP EXPLORATION (EPSILON) LIMITED
TYPICAL CONTROL VALVE WITH POSITIONER AND SOLENOID
CENTRAL PROCESSING FACILITY (CPF) - KHAZZAN PROJECT
PRESSURE REDUCING REGULATOR
I UNDEFINED INTERLOCK LOGIC
WITH INTERNAL RELIEF VALVE Y CONTRACT NO. : CO-BPXO-12-0376 ORIGINAL DWG SIZE : A1
FAIL ACTION TEMPERATURE REGULATOR
FC +
PETROFAC JOB NO. : JI-2024 SECURITY CLASS. : PROJECT INTERNAL
FILLED SYSTEM TYPE
PSET= 500.00 kPa-g PRESSURE SET POINT S TITLE:
FO - FAIL OPEN S SEQUENCE INTERFACE POINT VSET= 90.0 kPa-g VACUUM SET POINT I/P
FC - FAIL CLOSED S PIPING AND INSTRUMENT DIAGRAM - GEN1 - SYSTEM 0000
*VJN
FI - FAIL INDETERMINATE
FL - FAIL LOCKED LAST POSITION PRESS/VAC RELIEF MANHOLE COVER 4 LEGEND SHEET
4
KZ01-PR-PID-53-00011.pid

FLO - FAIL LOCKED VALVE OPENS ON DUAL FUNCTIONS OR INSTRUMENTS 3-WAY TEMPERATURE REGULATOR
H
DECREASING CONTROL *V FILLED SYSTEM TYPE
INSTRUMENT SYMBOLS GENERAL H
SHARING COMMON HOUSING
FLC - FAIL LOCKED VALVE CLOSES ON +

*V
DECREASING CONTROL +

C INSTRUMENT WITH SCALE DRAWING No. SHEET No. REVISION


TIGHT SHUT-OFF (ON/OFF VALVES)
LONG TAG NUMBER
DEFAULT IS CLASS V. NONE KZ01-PR-PID-53-00011 001 C01
4

IF DIFFERENT, INDICATE WITH A NOTE.


CAD Filename: KZ01-PR-PID-53-00011-001-C01.pid
1 2 3 4 5 6 7 8 9 10