Fcu Control Diagram: Sequence of Operation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

2-WAY ELECTRIC

MODULATING CONTROL
DAISY CHAIN TO
VALVE PROVIDED BY
BMS FRONT END
MSCC (TYP. CHW & HHW)

HHWR CHWR

DISCHARGE TEMPERATURE SENSOR

FILTER
SUPPLY
FAN

T
HHWS CHWS OCCUPANCY SENSOR
NOTE 4 OS
PRIMARY ROOM MOUNTED
DRAIN PAN THERMOSTAT PROVIDED
FCU DIGITAL
HIGH LEVEL POWER, SEE CONTROLLER PROVIDED T BY MSCC.
SENSOR ELECTRICAL BY MSCC. PROVIDE WITH
SEQUENCE OF OPERATION: TEMPERATURE
READOUT, SET POINT
A. The Fan Coil Unit is controlled by a unit mounted controller
provided by Mechanical Systems Controls Contractor (MSCC). ADJUST AND
UNOCCUPIED
B. On a call for cooling, the thermostat signals for the heating control OVERRIDE BUTTON.
valve to modulate toward the closed position. On a further call for
cooling, the thermostat signals for the fan to speed up from its
minimum setting to its maximum setting, via the fan's ECM motor. NOTES:
Upon a further call for cooling, this cooling coil control valve shall
1. The Mechanical Systems Control Contractor (MSCC) shall be
be modulated open.
responsible for the selection of, providing & installing all DDC
C. On a call for heating, the thermostat signals the cooling coil controllers & control devices to accomplish the sequence of
control valve to close. A further call for heating shall slow the fan operation specified herein. All products, manufacturers & installation
to its minimum airflow setting. On a further call for heating, the requirements shall conform to Masterspec 230905 - "Mechanical
thermostat signals the heating coil valve to modulate toward the Systems Controls".
full open position.
2. The MSCC shall provide & install all DDC & related wiring, conduit
D. When not scheduled, assume minimum airflow setpoint of 30% of & j-hook hanging systems. See Masterspec 230905 - "Mechanical
scheduled maximum airflow. Systems Controls" for raceway/conduit, cabling and labeling
E. In the unoccupied mode the unit cycles on and off and sequences requirements.
heating and cooling as noted above to maintain temperature 3. MSCC shall integrate unit controls back to the UMHHC unified front
end (i.e. Desigo) per standards outlined in Masterspec 230905 -
Note To Editor: For work in MED INN, delete the above paragraph "Mechanical Systems Controls" All front end graphics, point
'E' & associated occupancy sensor in diagram and use the below mapping, alarm & trend management shall be the responsibility of
paragraph 'E': the systems integrator contracted by Systems Monitoring.

E. In the unoccupied mode the unit cycles on and off and sequences Note To Editor: Select below if appropriate:
heating and cooling as noted to maintain unoccupied setpoint 4. FCU control enclosure, pre-wired by FCU manufacturer, on 36" long
temperatures. whip, as part of UL/ETI labeled assembly. Field mount enclosure to
Occupied: Monday - Friday 7:00am to 6:00pm achieve minimum 36" long working clearance at access to
enclosure controller & electrical connections
Unoccupied: Monday - Friday 6:01pm to 6:59am, Saturday
and Sunday
F. If the drain pan alarm is initiated, the unit stops and an alarm is
sent to the BMS. The unit automatically resets when the drain pan
is cleared of water.
G. Minimum points to BMS include: Room Setpoint (adjustable),
Room Temperature (with high/low temperature alarm), Discharge
Air Temperature, General FCU Alarm & Drain Pan Alarm.

- FCU CONTROL DIAGRAM


-
0 NOT TO SCALE

2101 Commonwealth, Suite B


Ann Arbor, MI 48105
FAX: (734) 763-0417
www.med.umich.edu/facilities/plan
FILE: D230905H-10.dwg FAN COIL UNIT
ISSUE: August 2015 CONTROL DIAGRAM