Unit Iii Overvoltages
Unit Iii Overvoltages
Unit Iii Overvoltages
Fig.3.1: Strength of direct lightning strikes and minimum arcing strengths as a function of
network voltage level
For networks with a voltage less than 400 kV, all direct lightning strikes result in arcing
and an earth fault. It is estimated that only 3% of overvoltages exceed 70 kV and have an
origin in direct lightning strikes. Moreover, as a result of attenuation of the voltage wave
throughout its propagation along the line, maximum overvoltages at the entrance of a
substation or building are estimated at 150 kV in MV systems.
ii. Indirect Lightning Strikes:
When indirect strokes fall on a support or just next to a line, high overvoltages are then
generated in the network. Indirect strokes are more frequent than direct ones and are proven
to be also almost as dangerous.
If lightning hits the pylon or the earth cable, the current flowing off causes an increase in
metal frame potential with respect to earth. The corresponding overvoltage U is
i L di
U R
2 2 dt
where R is the earth connection steep wave resistance and L is the inductance of the pylon
and/or the earthing conductor.
When this voltage reaches the value of arcing voltage of an insulator, an arcing return
occurs between the metal structure and one or more of the conductors. When the voltage is
greater than 150 kV, this arcing return is unlikely to happen. The quality of pylon earth
connections plays an important role: from 750 kV upwards, there is virtually no risk of arcing
return, thus justifying the installation of earth cables on EHV lines. In networks below 90 kV,
these cables provide efficient protection if the pylon earth connection is excellent.
If lightning hits just near the line, the energy flowing off to the ground causes a very rapid
variation in the electromagnetic field which induces waves on the line that are similar in
shape and amplitude to those generated by a direct stroke. They are mainly characterized by
their very steep front and their very fast damping.
When the voltage wave resulting from a lightning stroke passes through an MV/LV
transformer, transmission mainly occurs by capacitive coupling.
The amplitude of the overvoltage thus transmitted, observed on the secondary winding on
the LV side, is less than 10% of its value on the MV side (generally less than 70 kV).
Therefore, on LV lines, induced overvoltages are generally less than 7 kV.
2. Write a brief notes on capacitance switching.
One of the more common causes of electrical transients is switching of capacitor banks in
power systems. Electrical utilities switch capacitor banks during peak load hours to offset the
lagging kVAR demand of the load. The leading kVARs drawn by the capacitor banks offset
the lagging kVAR demand of the load, reducing the net kVA load on the circuit. Switching of
capacitor banks is accompanied by a surge of current which is initially limited by the
characteristic impedance of the power system and resistance of the line.
Fig.3.2.Capacitor Switching
Principles of Protection
1. Preventive protection:
• To limit internal or lightning impulse overvoltages (overhead protection cable, neutral
earthing, regulators, protection relays, switching-impulselimiting circuit-breaker);
2. Repressive protection:
• For draining the overvoltage to earth using special equipments (dischargers, surge
arresters).
The fundamental principles of overvoltage protection of electrical equipment are:
i. To limit the voltage for sensitive insulation.
ii. To reduce, or prevent, surge current from flowing between grounds.
iii. To drain the surge current away from the load.
iv. To bond the ground and equipment.
v. To create a low-pass filter using limiting and blocking principles.
Insulation Coordination
Three basic elements to insulation coordination, which are:
Determining the overvoltage stresses from the system.
Knowing the strength of the insulation of specific equipment in the substation.
Selecting surge arrester ratings and locations, or other mitigation equipment or
operating restrictions, to ensure that the system-imposed overvoltages do not
exceed the insulation strength of the equipment, including an appropriate
protective margin.
Protection level is determined by three factors:
Installation;
Environment;
Equipment used.
Final objective of insulation coordination is to ensure safe and optimized distribution of
electric power, which means the best possible economic balance between the various costs,
namely:
Insulation;
Protective devices;
Failures (operating loss and repairs) weighted with their probabilities.
Clearance:
i. Gas clearance: Shortest path between two conductive parts (air, SF6, etc.)
ii. Creepage distance: Shortest path between two conductors following the outer
surface of a solid insulator.
Insulation Deterioration depends
Environmental conditions (humidity, pollution, UV radiation);
Age (deterioration of the material);
Permanent electrical stresses (local value of the electric field).
Gas Clearance depends
Air pressure with altitude;
Device filling pressure.
Voltage Withstand
Power Frequency Withstand: Voltage withstand monitored through the standard one-
minute dielectric tests is generally sufficient.
Switching Impulse Voltage Withstand:
Characterized with the following properties:
Non-linear relation with voltage;
Unbalance, variation according to wave polarity;
Passage through a minimum curve value of the withstand voltage as a function
of front time;
Dispersion withstand must be expressed in statistical terms.
Standard tests of a wave of front time 250 ms and half-amplitude time 2500 ms
Lightning Overvoltage Withstand:
Positive and Negative Polarities – 1.2/50μS
Two formulas can be used to evaluate withstand to a 1.2/50 μS positive-polarity
impulse of an air gap for HV and MV networks:
where V50 is the voltage for which the breakdown probability is 50 %; and
where V0 is the withstand voltage and d is clearance in meters (V50 and V0 are in MV).
A lot of experimental studies have provided tools to evaluate the relation between
clearance and withstand voltage, taking into account a variety of factors such as front and tail
times, environmental pollution and insulator type.
7. Discuss in detail about Cable protection. (08)
Main source of outages in underground distribution is cable failures.
As a cable ages, the insulation becomes progressively weaker and a moderate transient
overvoltage causes breakdown and failure.
The life of the cable may be increased for few years by arrester protection than cable
replacement.
Depending on voltage class, the cable may have been installed with only one arrester at
the riser pole or both a riserpole arrester and an open-point arrester.
Fig.3.6. Cable Protection
To provide additional protection, utilities may choose from a number of options:
1. Add an open-point arrester, if one does not exist.
2. Add a third arrester on the next-to-last transformer.
3. Add arresters at every transformer.
4. Add special low-discharge voltage arresters.
5. Inject an insulation-restoring fluid into the cable.
6. Employ a scout arrester scheme on the primary
The cable life is an exponential function of the number of impulses of a certain magnitude
that it receives. The damage to the cable is related by,
D=NVc
where, D - Constant, representing damage to the cable
N - Number of impulses
V - Magnitude of impulses
c - Empirical constant ranging from 10 to 15
Therefore, anything that will decrease the magnitude of the impulses only slightly has the
potential to extend cable life a great deal.
8. Explain about the low impedance power conditioners.
Low-impedance power conditioners (LIPCs) are used primarily to interface with the
switch-mode power supplies found in electronic equipment. LIPCs differ from isolation
transformers in that these conditioners have much lower impedance and have a filter as part
of their design (Fig. 3. ).
TVSS have more surge-limiting elements than an arrester, which most commonly consists
solely of MOV blocks.
An arrester may have more energy-handling capability.
Different modes of operation, crowbar and clamping.
Crowbar devices are normally open devices that conduct current during overvoltage
transients. Once the device conducts, the line voltage will drop to nearly zero due to the short
circuit imposed across the line. These devices are usually manufactured with a gap filled with
air or a special gas. The gap arcs over when a sufficiently high overvoltage transient appears.
Once the gap arcs over, usually power frequency current, or “follow current,” will continue to
flow in the gap until the next current zero. Thus, these devices have the disadvantage that the
power frequency voltage drops to zero or to a very low value for at least one-half cycle. This
will cause some loads to drop offline unnecessarily.
Clamping devices for ac circuits are commonly nonlinear resistors (varistors) that conduct
very low amounts of current until an overvoltage occurs. Then they start to conduct heavily,
and their impedance drops rapidly with increasing voltage. These devices effectively conduct
increasing amounts of current (and energy) to limit the voltage rise of a surge. They have an
advantage over gap-type devices in that the voltage is not reduced below the conduction level
when they begin to conduct the surge current. Zener diodes are also used in this application.
MOV arresters have two important ratings. The first is maximum continuous operating
voltage (MCOV), which must be higher than the line voltage and will often be at least 125
percent of the system nominal voltage. The second rating is the energy dissipation rating (in
joules). MOVs are available in a wide range of energy ratings.
10. Write notes on protection against overvoltage using isolation transformer. (8)
Fig.3.8.a. Isolation Transformer