Chapter 1 Introduction To Power System Protection
Chapter 1 Introduction To Power System Protection
PROTECTION
PE 422
COURSE CONTENTS
Introduction
Review of Background Material
Relaying Instrumentation
Protection fundamentals
Protective relaying application
Stability
Reclosing and load shedding
Fundamentals of Automation
INTRODUCTION
A protection scheme in a power system is designed to
continuously monitor the power system to ensure maximum
continuity of electrical supply with minimum damage to life,
equipment, and property.
For the design of protection schemes it is necessary to know:
1. Fault characteristics of different elements of a power system.
2. Tripping characteristics of different protective relays
A good protective scheme can be designed by obtaining the
closest match between tripping and fault characteristics.
Design has to ensure that relays will detect undesirable conditions
and then trip to disconnect the affected area, but remain restrained
at all other times
Dependence of Modern Society on Electric supply
Domestic usage
Industrial
Commercial
Railway networks, telecommunication systems
Hospitals, banks, post offices
No power system can be designed in such a way
that it would never fail.
Faults and abnormal operating conditions
1. Shunt Faults (short circuits)
When the path of the load current is cut short due to insulation
damage then it is called short circuit.
Insulation may be damaged due to no. of reasons:
a. Aging
b. Temperature
c. Hail, snow, rain
d. Chemical pollution
e. Foreign objects
f. Other causes
ingle Line to Ground Fault due to flash over of Insulator String
These faults are due to flash over of spark gap across the string
insulators.
Short circuit may be
Temporary, permanent (dead short circuit), partial short circuit.
Mostly these are Temporary faults and supply is restored
after deionized of spark path
Reclosures are used for internal re-energization
(for low voltage system i.e. distribution system 3 attempts
are allowed after which breaker is locked out) Whereas for
high voltage levels where the damage due to short circuit may
be very large only one reclosure attempt is allowed.
A fault which bypasses the entire load current through itself is
called a metallic fault. Such faults gives very low or
practically zero fault resistance.
In partial short circuits, fault resistance can be modelled as a
non-zero and in parallel with the intended path of the current.
Mostly fault resistance is the resistance of that arc produced
as a result of flashover. Arc resistance has a non linear
behavior in nature.
Arc resistance according to Warrington model:
.
R𝑎𝑟𝑐 = 8750 (𝑆 + 3𝑢𝑡)/𝐼1 4
sensitivity
selectivity and
Speed
Evolution of Power Systems
a) Isolated (Radial) simple
b) Interconnected (Network) complicated
Isolated Power System:
Single source of supply
Simple
no stability problem
1. Sensitivity
The protective system must be alive to the presence of the
smallest fault current. The smaller the fault current it can
detect, the more sensitive it is.
2. Selectivity
In detecting the fault and isolating the faulty element, the
protective system must be very selective. Ideally, the
protective system should isolate faulty element, thus causing
minimum disruption to the system.
3. Speed
The longer the fault persists on the system, the larger is the
damage to the system and higher is the possibility that the
system will lose stability. Thus, it helps a lot if the entire
process of fault detection and removal of the faulty part is
accomplished in as short a time as feasible. Therefore, the
speed of the protection is very important. It must, however, be
mentioned that speed and accuracy bear an inverse
relationship! The high-speed systems tend to be less accurate.
This is for the simple reason that the high speed system has
lesser amount of information at its disposal than a slow-speed
system.
4. Reliability and Dependability
When conductors passing through a CT are not centered in the circular (or
oval) opening, slight inaccuracies may occur.
Current transformers used in metering equipment for three-phase 400
ampere electricity supply
Shapes and sizes can vary depending on the end user or switchgear
manufacture.
Burden
Rating factor
Load
Temperature and
Physical configuration.
The voltage transformer steps down the high voltage of the line to a
level safe enough for the relaying system and personnel to handle.
provide a ring of security around each and every element of the power system.
If there is any fault within this ring, the relays associated with it must trip all the
allied circuit breakers so as to remove the faulty element from the rest of the power
system. This 'ring of security' is called the zone of protection.
Faults occurred within the zone are known as internal faults and those outside are
called external faults
The farthest point from the , relay location, which is still inside the zone, is called the
reach point. The distance between the relay location and the reach point is termed the
reach of the relay.
Figure Zone of protection external fault/internal fault
Zones of Protection
if the fault takes place in the overlapped portion, more than the minimum
number of circuit breakers will trip, causing a major dislocation to the
system. Each of the zones may be implemented using a different relaying
principle. All the zones, in practice, may not be as well marked out as they
are shown in the figure and may contract or expand depending upon the
various system conditions
Figure Various zone of Protection
Primary and Back-up Protection
Each element requires a different protection due to their unique set of faults
and abnormal conditions.
Various Principles of Power System
Protection
Fault current sudden built up under fault conditions, thus over current relay is the
most natural principal of relaying.
However, fault current magnitude is a function of type of fault and the source
impedance. The source impedance, which depends upon the number of generating
units that are in service at a given time, keeps changing from time to time. Therefore,
the reach as well as the operating time of over-current relaying keep changing from
fault to fault, and time to time.
Another natural and appealing principle is the differential protection. It is based on
the premise that the current entering a protected section must be equal to that leaving
it. Any discrepancy between the two indicates the presence of a fault. However, it is
impractical to apply this principle to a transmission line because the ends are far apart
and it is not easy to compare information at the two ends.
To get over the above problem, a distance relay compares voltage
with current at the same end. This, in effect, measures the impedance
between the relay location and the fault point. Since impedance of a
transmission line can be considered to be directly proportional to the
distance along the line, this type of relaying is known as distance
relaying.