Catalogue Simosec New en PDF
Catalogue Simosec New en PDF
Catalogue Simosec New en PDF
siemens.com/SIMOSEC
Application
Typical uses
R-HA40-111.tif
R-HA41-115.tif
Example
Transfer switchgear with
integrated low-voltage niche
R-HA40-112.tif
R-HA41-135.tif
Product Range
Product range overview, options for panels 14 – 15
Medium-Voltage Switchgear Product range overview, equipment features 16 – 17
Panels 18 – 22
Catalog HA 41.43 · 2018
Design
Invalid: Catalog HA 41.43 · 2017 Panel design 23 – 24
Operation (examples) 25
siemens.com/medium-voltage-switchgear
Components
siemens.com/SIMOSEC Three-position switch-disconnector 26
Operating mechanisms, equipment 27 – 28
Vacuum circuit-breaker, busbars 29 – 32
Cable connection 33 – 34
Cable cross-sections, HV HRC fuse assembly 35 – 40
Instrument transformers 41 – 43
Indicating and measuring equipment 44 – 53
Protection systems 54
Low-voltage compartment 55
Low-voltage niche 56
Dimensions
Switchgear installation 57 – 59
Panels 60 – 65
Floor openings and fixing points 66 – 68
Installation
Shipping data, transport 69 – 71
Standards
Standards, specifications, guidelines 72 – 75
Reavailability
• Three-position switch-disconnector with gas-insulated,
maintenance-free quenching principle
• Metallic partition between busbar compartment,
s witching devices and cable compartment
• Separate pressure relief for each compartment
• C able testing without the need to isolate the busbar
• Mounting location of three-phase current transformer
for selective disconnection of circuit-breaker feeders.
*) For standards, see page 72
Electrical features
• Rated voltages up to 24 kV
• Rated short-time withstand current up to 25 kA
• Rated normal current of feeders
–– Up to 800 A, e.g. for ring-main, metering panels
–– Up to 1250 A, for circuit-breaker panels
–– Up to 1250 A, for bus sectionalizer panels
• Rated normal current of busbar up to 1250 A.
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) T he rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC 62271‑1/VDE 0671‑1)
1) D epending on HV HRC fuse-link (depending on the let-through current of the HV HRC fuse-link),
earthing switch at the feeder: see page 11
3) On request: Panel types K and K1, each with make-proof earthing switch
4) Busbar
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC 62271‑1/VDE 0671‑1)
2) With vacuum circuit-breaker in gas-filled switching-device vessel (maintenance-free under normal ambient conditions according to IEC 62271‑1)
) 1250 A in preparation
• possible
– not possible
Three-position switch-disconnector
Rated insulation level Rated voltage Ur kV 7.2 12 17.5 24
Rated short-duration power-frequency withstand voltage Ud
– phase-to-phase, phase-to-earth, open contact gap kV 20 28, 42 *) 38 50
– across the isolating distance kV 23 32, 48 *) 45 60
Rated lightning impulse withstand voltage Up
– phase-to-phase, phase-to-earth, open contact gap kV 60 75 95 125
– across the isolating distance kV 70 85 110 145
Rated frequency fr Hz 50 / 60
Rated normal Standard: A 630
current Ir**) Option: A 800
50 Hz Rated short-time for rated duration of short-circuit t k = 1 s, 2 *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit t k = 3 s (4 s *)) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit making current Ima up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz Rated short-time for rated duration of short-circuit t k = 1 s, 2 *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit t k = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit making current Ima up to kA 55 65 55 65 55 65 42 52 65
Switching capacity for general-purpose switches according to IEC / EN 62271-103
Test duty TDload Rated mainly active 100 operations Iload [I1] *) A 630
load-breaking current Iload 20 operations 0.05 Iload [I1] A 31.5
Test duty TDloop Rated closed-loop breaking current Iloop [I2a]
A 630
Test duty TDcc Rated cable-charging breaking current Icc [I4a]
A 68
Test duty TDlc Rated line-charging breaking current Ilc [I4b]
A 68
Test duty TDma Rated short-circuit making current Ima 50 Hz up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz up to kA 55 65 55 65 55 65 42 52 65
Test duty TDef1 Rated earth-fault breaking current Ief1 [I6a]
A 200
Test duty TDef2 Rated cable-charging breaking current and line-charging breaking
current under earth-fault conditions Ief2 A 115
Number of mechanical operating cycles / M-classification n 1000 / M1; 2000 *) / M1
Number of electrical operating cycles with I load / Classification n 100 / E3
Number of short-circuit making operations with Ima n 5 5 5 5 5 5 5 5 5
Classification E3 E3 E3 E3 E3 E3 E3 E3 E3
C-classification for general-purpose switch (no restrikes, TD: Icc, Ilc) C2 C2 C2 C2 C2 C2 C2 C2 C2
Classification for disconnectors according to IEC / EN 62271-102 / VDE 0671‑102
Number of mechanical operating cycles n 1000 (2000 *))
M-classification M0 (M1 *))
Technical data and switching capacity for earthing switch according to IEC / EN 62271-102 / VDE 0671‑102
Rated short-time withstand current Ik 50 Hz up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima 50 Hz up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-time withstand current Ik 60 Hz up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima 60 Hz up to kA 55 65 55 65 55 65 42 52 65
Number of mechanical operating cycles / M-classification n 1000 / M0
Number of short-circuit making operations with Ima n 5 5 5 5 5 5 5 5 5 / 2 2)
Classification E2 E2 E2 E2 E2 E2 E2 E2 E2/E1 2)
Switch-disconnector / fuse combination according to IEC/EN 62271-105/VDE 0671‑105
Rated voltage Ur kV 7.2 12 17.5 24
Rated normal current Ir **) A 200 1)
Rated transfer current Itransfer A 1750 1750 1500 1400
Maximum transformer rating kVA 800 1600 1600 2500
Switching capacity for make-proof earthing switch, arranged on feeder side, downstream from HV HRC fuse, for typical: T, T1, M(VT-F)
Rated short-time withstand current t k = 1 s kA 2
Rated short-circuit making current Ima 50 Hz kA 5
60 Hz kA 5.2
Number of short-circuit making operations with Ima / E-classification n 5 / E2 5 / E2 5 / E2 5 / E2
Number of mechanical operating cycles / M-classification n 1000 / M0
For footnotes, see page 10
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC 62271‑1/VDE 0671‑1)
Vacuum circuit-breaker
Switching capacity according to IEC / EN 62271-100 / VDE 0671‑100
Type CB-f 1) 4), combined with three-position disconnector, in gas-insulated switching-device vessel 4)
Type CB-r / SION L (3AE6) 1)
Rated voltage Ur kV 7.2 12 17.5 24
Rated normal current Ir **) CB-f, CB-r (SION L)A 630
for circuit-breaker type A on request: 800
CB-r (SION L)A 1250
Rated frequency fr Hz 50 / 60
50 Hz Rated short-time for rated duration of short-circuit t k = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit t k = 3 s (4 s *) )) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit breaking current Isc up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz Rated short-time for rated duration of short-circuit t k = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit t k = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit breaking current Isc up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima up to kA 55 65 55 65 55 65 42 52 65
Classification and number of operating cycles for circuit-breaker according to IEC / EN 62271-100 / VDE 0671‑100
Circuit-breaker: CB-f NAR 3)
Mechanical Number of operating cycles 2000
Class M1
Electrical Number of operating cycles with Ir: 2000 Class E2
Breaking of capacitive currents Class C1
Number of short-circuit breaking operations with Iscn 20
Class S1
Rated operating sequence CB-f NAR O – 3 min – CO – 3 min – CO
Circuit-breaker: CB-f AR 1); CB-r AR 1) 3)
Mechanical Number of operating cyclesn 10 000
Class M2
Electrical Number of operating cycles with Ir: 10,000 Class E2
Breaking of capacitive currents Class C2
Number of short-circuit breaking operations with Isc for CB-f ARn 30 or 50
Number of short-circuit breaking operations with Isc for CB-r ARn 30
Class S2
Rated operating sequence CB-f O – 0.3 s – CO – 3 min – CO
CB-f O – 0.3 s – CO – 30 s – CO
CB-r (SION L) O – 0.3 s – CO – 15 s – CO
Classification for disconnector according to IEC / EN 62271-102 / VDE 0671‑102 (for panel types L, L1, ...)
Number of mechanical operating cyclesn 1000 (2000 *))
M-classification M0 (M1 *))
Classification for earthing switch according to IEC / EN 62271-102 / VDE 0671‑102 (for panel types L, L1, ...)
Number of mechanical operating cycles / M-classificationn 1000 / M0
Number of short-circuit making operations with Iman 5 5 5 5 5 5 5 5 5
Classification E2 E2 E2 E2 E2 E2 E2 E2 E2
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (acc. to IEC 62271‑1/ VDE 0671‑1)
) Only for CB-f
1) Definition of the different types of vacuum circuit-breakers (= VCB): VCB version: without AR 3) with AR 3)
Panel VCB type Vacuum circuit-breaker – Design: CB-...NAR CB-...AR
type
L, L1 CB-f fixed-mounted in gas-insulated switching-device vessel, combined with three-position CB-f NAR CB-f AR
disconnector
L1(r), L2(r) CB-r (SION L) air-insulated, removable, separate three-position disconnector CB-r AR
3) AR = Automatic reclosing; NAR = Non-automatic reclosing
4) VCB in switching-device vessel (maintenance-free under normal ambient conditions according to IEC 62271‑1)
R-HA41-116a.tif
Column No.
Ring-main panel, type R
Cable Ring-main panel 1) R 375 630 A, 800 A
feeder
panels R1 500 630 A, 800 A
Transformer panel 1) T 375 200 A
T1 500 200 A
Cable panel K 375 630 A
K1 500 630 A, 1250 A
l Available
Optionally available
– Not applicable
y)
or
eg
)
ble
at
ca
yc
d
uit
(3 r
tin
ble
A)
on
M
ca
ec
e4
2 nd
vic
yp
er
of
VT
VT
.t
fs
.g
ad
in
in
so
(e
res
res
te
CT
ns
os
CT
t-
t-
as
as
(L
pe
ri
T
sin
e
c
c
eC
s te
-ty
ry
ag
as
as
re
go
r re
olt
as
ble
ble
st-
le)
le)
ble
te
ph
dv
ea
ca
ca
-po
-po
ca
ca
ca
e-
te
rg
as
as
2 nd
(2
(1
3 rd
re
Ra
Su
LS
Th
CT
CT
VT
VT
1 2 3 4 5 6 7 8 9 10 Panel type
l – l – – (up to 17.5 kV) – (up to 17.5 kV) 24 kV R
LSC 2
l l l – – 24 kV R1
– – l – – – – – 24 kV T
LSC 2
– – l – – – – – 24 kV T1
– – l (up to 17.5 kV) – (up to 17.5 kV) 24 kV K
LSC 1
– l l – 24 kV K1
l l l 24 kV L
LSC 2
l l l 24 kV L1
l l l – 24 kV L1(r)
LSC 2
l l l 24 kV L2(r)
l l l – LSC 2 24 kV D1 )
– – – – – LSC 2 24 kV R(T)
– – – – – LSC 2 24 kV R1(T)
l l – – – – – LSC 2 24 kV L(T)
l l – – – – – LSC 2 24 kV L1(T)
l l – – – – – 24 kV L1(r, T)
LSC 2
l l – – – – – 24 kV L2(r, T)
– – – – – LSC 2 24 kV D1(T)
– l – – – – 24 kV M
– l – 24 kV M(-K)
– l – – – – LSC 1 24 kV M(-B)
– l – 24 kV M(-BK)
– l – 24 kV M(KK)
– – – – – – 17.5 kV M(VT)
– – – – – – 24 kV M1(VT)
LSC 2
– – – – – – 17.5 kV M(VT-F)
– – – – – – 24 kV M1(VT-F)
– – – – – – LSC 1 24 kV H
– – – – – LSC 1 24 kV H1
– – – – – – – – LSC 2 24 kV E
) In preparation
1) Panel type:
Metal-clad
2) T
ype designation
of vacuum
circuit-breaker
R-HA41-118a.tif
Column No.
Ring-main panel 1) as feeder R 375
Cable panel R1 500
type K as transfer R(T) 375
R1(T) 500
Transformer panel 1) as feeder T 375
T1 500
Cable panel as feeder K 375
K1 500
Circuit-breaker panel 1) as feeder L 500
with CB type “CB-f” 2) L1 750
as transfer L(T) 500
L1(T) 750
Circuit-breaker panel 1) as feeder L1(r) 750
with CB type 3AE 2) L2(r) 875
as transfer L1(r, T) 750
L2(r, T) 875
R-HA41-119a.tif
2)
l Basic equipment
h)
1)
itc
tch
Additional equipment
sw
wi
h
)
itc
)7
i ng
ns
(option), further
)2
sw
th
itio
h1
additional equipment
er
) i ng
ar
h
os
itc
ov
re
itc
tch th
-p
on request
sw
tc
)
(o
sw
)7
wi ear
ree
)
)2
er
2)
en
2
on
ing
h1
th
– Not available
)
1)
ak
er
1)
gs f
r tm
o
F
iti
ak
ro
re
t ch
of
tch
r th
OF
itc
h
os
er
rth e-p
b
e
pa
itc
m
”/“
it-
br
wi
sw
wi
ea
k
-p
m
ea
s
sw
ak
it-
cu
ON
i
ns
i
s
ee
an
or
o
on
br
nd m
ion
cu
cir
c
)2
ing
hr
itio
ch
y“
2)
nt
it-
-p al
iti
e
r a and
cir
h1
e
rt
sit
1)
me
m
c
e
rg
rc u
r th
os
ab
m en
os
ee ri
e
r tm
fo
uu
o
m
e
c
hr ct
h
c
p
-p
c
cto h
uu e
ea
pla
en
ing
itc
e-
uu
c
r
ne itc
or
a c et w
n /
r t ele
ac
ee
ve
w
pa
re
d-
sw
at
of
on sw
tio
rat
ac
r
s
nv
hr
in
er
co
to
om
h
e
dv lb
re
dic
on
rv
ot
rt
rt
ov
ec
pe
ica
ed
ion
r
isc n
ei
2) ed n
s to
al)
nt
an ne
p
lc
iti
-d itio
tio em
fo
fo
nn
rc
ro
e-
o
k
as
e
ind
i
n
sit
s
ina
) pa
oc
f
r tm
ak
r
ism
ice
wi ea osi
i
o
m
ism
to
tch os
co
to
ica or r
m
(fo
n
-p
po
rl
l
m
nis
h1 r
m
re
ult
mo
wi e-p
er
n s ith h p
rv
en
ps
itc ake
5)
an
e
pa
ee
ve
an
ind ) f
e-
r
r
t
se
h
r
-se
ed
to
fa
te
ha
m
r tm
fo
r, s re
ch
on
hr
m
itio B w itc
e
co
or
ice NO
h
s w - b re
lea
nt
et
ica
h-
hr
cla
n
at
h
ec
ec
as
or
co
rt
me
w
ut
i
cto r t
red
k
e
nt
t
pa
rt
er
r v (1
tch
re
y -f
ow
m
m
ind
-p f VC r s
r
ac
ipm
fo
k-o
he
ion it
le
ble
ea
ne fo
e
op
o
m
ing
s i t i rc u
wi
- s e ch
ree o fo
nt
br
m
ad
ing
ing
ab
wi
ef
ut
nd
nic
loc
on tch
co
ed
or
ca
qu
-
t
g(
hu
or it
th SED” vice
rat
.t.
es
re
k-o
c
le
r 4)
r
vic
i
at
at
po c
y -f sw
pa
w
rg
isc wi
uit
ge
ye
ed
r
ab
tin
ing
c
s
e- in
ot
pe
al
fo
er
er
g
loc
de
ha
m
LO de
ve
as
as
rd ys
os
lt a
lt a
nt
i rc
sc
nic
ad g
em
ea
ar
op
op
tio
lo
re k
th
ck
co
re a l i n
gc
co
th rl o c
ing
ou
se
se
(fo iliar
“C ng
ing
nd
vo
vo
t-c
lh
il a
ua
ha
rlo
ar
l-r
ec
or
or
ble
lea
lea
rin
or
em
i
w-
w-
co
ne
-e
n
or
ck
ca
ck
n
os
sp
ec
te
ra
ot
ot
te
Sig
Ma
Flo
Au
De
Ca
Sh
Sp
Re
Re
Se
Lo
Lo
Lo
Lo
Lo
Pa
In
C-
Pr
In
In
Cl
M
M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Panel type
l
1)
l – l l – l – – – – – –
R
R1
l l – l – l – – – – – – – – –
R(T)
–
R1(T)
8) T
l l – l l l – l l – – – –
T1
K
– – l l l – – – – – – – – – – – – – –
K1
2) L
l l – l l l l – – –
L1
2) L(T)
l l – – l l l – – – – – –
L1(T)
l
2)
l – l l l l – – 6)
L1(r)
L2(r)
l
2)
l – – l l l – – – – –
L1(r, T)
L2(r, T)
M
– – l – l – – – – – – – – – – – – – – – –
M(-B)
M(-K)
– – l l l – – – – – – – – – – – – – – –
M(-BK)
– – l l l – – – – – – – – – – – – – – – M(KK)
1)
l l – – l – l – – – – – – – – – M(VT)
1)
l l – – l – l – – – – – – – – – M1(VT)
1)
l l – – l – l – – – – – – – – M(VT-F)
1)
l l – – l – l – – – – – – – – M1(VT-F)
– – l – l – – – – – – – – – – – – – – – – – H
– – l – l – – – – – – – – – – – – – – – – – H1
l l – l l – l – – – – – – D1 )
l l – – l – l – – – – – – – – – D1(T) )
l – l – l – l – – – – – – – – – – – E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Panel type
) In preparation 5) N
ot to be applied for versions with separate feeder earthing switch in
1) Three-position switch as three-position switch-disconnector panel types L1(r), L2(r)
2) Three-position switch as three-position disconnector 6) Inspection window is a standard equipment in panel types L1(r), L2(r)
4) In special cases, deeper floor cover for panels with cable feeder for versions with separate earthing switch at the cable feeder
required. Design of floor cover: Depending of direction of 7) Or for earthing switch in panel type E
pressure relief 8) For panel type T with a rated voltage of 24 kV:
Deeper cable fixing located underneath the panel
Option Option
Option Three-position
switch-disconnector
Option *) Option*)
Make-proof
earthing switch
Option *) or*)
Type R Type K
375 mm wide 375 mm wide Capacitive voltage
detecting system
Option Option
Fixed earthing point
Option
Cable-type current
transformer, e.g.
4MC703 . . .
Option
or or or or
Three-phase
current transformer
or or 4MC63 . . .
Type R1 Type K1
500 mm wide 500 mm wide
Voltage transformer,
Ring-main panel e.g. 4MR, 1-pole,
Busbar earthing panel cast-resin insulated
as transfer panel for attachment to
panel
types M, M(-K), H types L1(r, T)
2nd cable
(no scope of supply)
Option Option
Option
Surge arrester
*) Option: Up to Ur=17.5 kV
Option Option
L1, R) as well as on
the panel combina-
tion [e.g. R(T)]
Option
Discharge switch
Option Option
Option
HV HRC fuse
Capacitive voltage
Option detecting system
On request:
Three-phase
current transformer
4MC63 . . .
Cable
(not included in the
scope of supply)
2nd cable
(not included in the
scope of supply)
Surge arrester
*) On request
) In preparation
Scheme 1
Scheme 2
Scheme 3
Scheme 4
Option Option
Capacitive voltage
Standard:
detecting system
For transfer
to the right
Type M 750 mm wide
Panel design Fixed earthing point
Billing metering panels 630 A, 800 A, 1250 A
of M(K)
for cable connection Standard
M
Block-type current
transformer 4MA,
cast-resin insulated
Option or or or
Transfer
panel
Option Option Option
Voltage transformer,
Option
e.g. 4MR, 1-pole,
Scheme 1
Scheme 2
Scheme 3
or or or
Option
Scheme 2
Scheme 3
Scheme 4
scope of supply)
Option Option or
Surge arrester
Option
Type M(-BK) 750 mm wide
Billing metering panels 630 A, 800 A, 1250 A Panel design
of M(-B)
for busbar connection
or or or
Individual metering
Option Option
Option
Scheme 1
Scheme 2
Scheme 3
Scheme 4
Option Option
2) P1and P2 are terminal
designations of the
Type M(-B) 750 mm wide
current transformer
Three-position
switch-disconnector
Option Option
Fixed earthing point
HV HRC fuse
Option Option
Voltage transformer,
e.g. 4MR, 1-pole,
cast-resin insulated
Type M(VT-F) Type M1(VT-F)
375 mm wide 500 mm wide
Scheme 3
Scheme 4
Scheme 1
transformer 4MA,
cast-resin insulated
Option Option
Option
Voltage transformer,
or or or e.g. 4MR, 1-pole,
Schemes 1 to 4 depend on: cast-resin insulated
– Rated voltage U r
– P anel combinations (TC-xx)
Type H, 630 A, 800 A, 1250 A with the adjacent panel
375 mm wide types
Scheme 3
Scheme 4
Scheme 1
Option Option
Option
or or or
Option
the rated voltage and
or
Option
Option Option Option Option
With vacuum
circuit-breaker, Vacuum circuit-
fixed-mounted breaker (type 3AE6
Option or With vacuum Option or or (CB-r) removable)
circuit-breaker,
Type L
type 3AE6, removable
500 mm wide **)
Type L1(r), 630 A Make-proof
750 mm wide earthing switch
Option
Type L2(r), 1250 A
875 mm wide
Capacitive voltage
detecting system
Option
Option Option
Type L1(r, T), 630 A
Voltage transformer,
750 mm wide
e.g. 4MR, 1-pole,
Option Type L2(r, T), 1250 A cast-resin insulated
875 mm wide
Option Cable
(no scope of supply)
**) Standard: Feeder earthing via the
vacuum circuit-breaker type 3AE6
Option Option
With vacuum circuit-breaker, (with interlocks, without earthing switch)
2nd cable
fixed-mounted (no scope of supply)
**)
Type L1(T) Panel combinations Design Rated current
750 mm wide L1(r, T) + H1 Standard 630 A
L1(r, T) + R1(T) Standard 630 A Surge arrester
Type L(T):
500 mm wide L2(r, T) + D1(T) Standard 1250 A 2) P1and P2 are terminal
L2(r, T) + H1 Standard 1250 A designations of the
current transformer
Vacuum circuit-breaker:
Circuit-breaker panel (with vacuum circuit-breaker type CB-f NAR) 41 Vacuum circuit-breaker, (VCB) fixed-mounted
42 Operating mechanism box
43 Manual operation for “spring charging”
– for closing with manual operating mechanism
– for emergency operation with motor operating
mechanism
44 Mechanical “OFF” pushbutton
45 Mechanical “ON” pushbutton
(not supplied with spring-operated mechanism)
46 “Spring charged” indicator
47 Operations counter (option for
VCB type: CB-f NAR)
48 Position indicator
49 Option: Three-phase current transformer 4MC63
50 Option: Overcurrent-time protection relay
(type 7SR45 or similar)
51 Option: Multifunction protection relay
SIPROTEC 5 7SJ82
52 Cable-type current transformer
53 Niche applicable for control cables and /
or bus wires
54 Option: Additional earthing busbar
for switching-device vessel
55 Metallic partition of busbar compartment
Control board
Front of ring-main feeder, type R
The control boards are function-related. They integrate
operation, mimic diagram and position indication. Further-
more, the respective indicating, measuring and monitoring
equipment as well as locking devices and control elements
(e.g. local-remote switch) are arranged there according to
the panel type and version. The ready-for-service indicator
and rating plates are also located at the operating front.
Operation is identical for transformer and circuit-breaker
feeders. First, the operating mechanism must be charged;
then, closing / opening is done through separate pushbut-
tons. The condition of the energy store is indicated.
All actuating openings are functionally interlocked against
each other, and are optionally lockable. The operating Panel width: 375 mm
lever carries two plug inserts, separately for the discon- Front of transformer feeder, type T
necting and earthing function.
Operation of Operating levers
three-position switch
R-HA40-114a.tif
1 Manual operation of load-break function (R, T) or disconnecting
function (L)
2 Locking function (option for ring-main feeders)
3 Manual operation of earthing function
4 Panel designation label
5 Position indicator for switch-disconnector
Features
• Switch positions: Three-position switch-disconnector
CLOSED – OPEN – EARTHED
• Switching functions as general-purpose
switch-disconnector (class E3) according to
– IEC / EN 62271-103 / VDE 0671-103 *)
– IEC / EN 62271-102 / VDE 0671-102 *)
• Designed as a three-position switch with the functions
– Switch-disconnector and
– Make-proof earthing switch
R-HA41-132a.tif
• Operation via rotary bushing welded gas-tight into the
front of the switching-device vessel
• Climate-independent contact in the gas-filled
switching-device vessel
• Maintenance-free according to IEC / EN 62271-1 /
VDE 0671-1
Busbar
• Individual secondary equipment
CLOSED
• No cross insulation between phases.
OPEN
Mode of operation
The operating shaft forms one unit together with the three
contact blades. Due to the arrangement of the fixed con-
tacts (earth – busbar), it is not necessary to interlock the
CLOSE and EARTHING functions. EARTHED
Moving contact
Closing operation
OPEN / CLOSE CLOSE OPEN
Opening operation
During the opening operation, the arc is caused to rotate
by the arc-suppression system. This rotation movement
prevents the development of a fixed root.
The isolating distance in gas established after breaking OPEN / EARTH OPEN EARTH
fulfills the conditions applicable to isolating distances in
accordance with
– IEC / EN 62271-102 / VDE 0671-102 *)
and
– IEC / EN 62271-1 / VDE 0671-1 *).
Due to the arc rotation caused by the arc-suppression
system, both load currents and minor no-load currents are
Switch positions: CLOSED OPEN Feeder EARTHED
safely interrupted.
Earthing operation as
three-position
The EARTHING operation is implemented by changing from
switch-
the “OPEN” to the “EARTHED” position. disconnector
up to 630 A
as
three-position
disconnector
up to 1250 A
Spring-operated / stored-energy mechanism
The switching movements are performed independently
of the operating speed.
During the charging process, the closing and opening
springs are charged. This ensures that the switch-discon-
nector / fuse combination can switch off all types of faults
reliably even during closing.
Closing and opening is done via pushbuttons, and is there-
fore identical with the operation of circuit-breaker operat-
ing mechanisms.
An energy store is available for tripping by means of an Shunt release (option)
operating HV HRC fuse or via a shunt release (f-release). (f-release)
After tripping, a red bar appears on the position indicator. Spring-operated / stored-energy mechanisms can be equipped
with a shunt release. Remote electrical tripping of the three-
position switch-disconnector is possible via the magnet coil of
the shunt release, e.g. transformer overtemperature tripping.
To avoid thermal overloading of the shunt release in the
event of a continuous signal that may be applied, the shunt
release is switched off via an auxiliary switch which is me-
chanically coupled with the three-position switch-
Assignment of operating mechanism type disconnector.
of three-position switch to panel types
Panel type R, L, D1, L(r) E T, M(VT-F), M(VT)
Function Switch-disconnector (R) Earthing switch Switch-disconnector (T, T1) Earthing switch
Disconnector (L, D) Disconnector [M(VT), M(VT-F)]
Disconnector [L1(r), L2(r)]
Type of operating Spring-operated Spring-operated Stored-energy Spring-operated
mechanism
Operation Manual Manual Manual Manual
Motor (option) Motor (option)
Legend
D = Disconnector feeder
E = Earthing panel
L = Circuit-breaker feeder
R = Ring-main feeder
T = Transformer feeder
M(VT), M(VT-F) = Busbar voltage metering panel
*) FNN: Forum network technology / network operation of the VDE (FNN)
R-HA41-124a.tif
60 9 7
110 5 4
240 2.5 2 Panel type R:
Operating mechanism for three-position switch, and
Rated switching capacity low-voltage niche with terminals and MCB's (options)
Rated insulation level 250 V AC / DC
Insulation group C according to VDE 0110
Continuous current 10 A
Making capacity 50 A
R-HA41-144b tif
Abbreviations:
NO = Normally open contact
NC = Normally closed contact Panel type L:
Motor operating mechanism for three-position switch,
**) Depending on the secondary equipment of the three-position
and circuit-breaker type “CB-f NAR“
switch
C.t.-operated release
tacts return to the open position and remain there even Position switch
if the closing command is sustained. This means that the Mechanical interlocking
*) A R = Automatic reclosing
NAR = Non automatic reclosing
Rated short-circuit breaking current 20 kA Rated short-circuit breaking current 25 kA
Rated short-circuit breaking current 20 kA Rated short-circuit breaking current 25 kA
2 000
1 000
500
200
100
90
50
30
20 6
10
0.5 1 2 5 10 16 25 kA 50 *)
A R = Automatic reclosing
NAR = Non automatic reclosing
Busbars
• Safe-to-touch due to metallic enclosure Busbars
• Metal-clad busbar compartment 1 Busbar
• Three-pole design, bolted from panel to panel 2 Bushing-
• Easy switchgear extension 1 type insu-
lator for
• Made of copper: Round E-Cu. busbar
R-HA41-125a.tif
2
1 Busbar
2 Bushing-
1 type insu-
lator for
busbar
R-HA41-140.tif
General features
Cable connection (examples)
• Connecting lugs for sealing
L1 L2 L3 L1 L2 L3
ends arranged one behind the
other
• Uniform cable connection
height for the respective panel
types
• With cable bracket,
5
e.g. type C40 according to 1
4
DIN EN 50024 2
3
• Access to the cable compart-
ment only if feeder has been
isolated and earthed.
R-HA41-126a.tif
R-HA41-127a.tif
Special features
– In cable panels (type K)
Ring-main panel type R Cable compartment with
– In ring-main panels (type R) Cable compartment as delivered cable sealing ends (options: A, B, C 1)
– In circuit-breaker panels (type L) and D 1), see below)
• For thermoplastic-insulated
cables L1 L2 L3 L1 L2 L3
• For paper-insulated mass-
impregnated cables with
adapter systems
• For connection cross-sections
up to 300 mm2
• Cable routing downwards.
– In transformer panels (type T)
• For thermoplastic-insulated
cables 7
6
• For connection cross-sections 8
R-HA41-129a.tif
R-HA41-128a.tif
Cable sealing end, e.g. for panel types R..., K…, D…, M(-K), M(-BK), L… and T...2) Connection height **)
(for connection heights of cables, see opposite dimension drawings) of cables above
Make Type Cross-section in mm2 floor or above
lower edge of panel:
Single-core thermoplastic-insulated cables for ≤ 12 kV (6 / 10 kV); acc. to IEC standard 2)
Euromold AIN 10, AFN 10 25–300 (500 *)
AIS, AIP 150–300; 50–300
12 MONOi 25–300 (500 *)
ITK-212 •) 50–300 (400 *)
Prysmian Kabel und Systeme ELTI mb-1C-12 35–240
ELTI-1C-12 25–300
TE Connectivity IXSU-F 16–300 (500 *)
MVTI-31xx- 25–240 (300 *)
EPKT 16–300
Lovink-Enertech IAEM 10 25–300
IAES 10 25–300 (500 *) Panel type R ...
3M 92-EB 6x-1 35–300 (400 *)
Südkabel SEHDI 10.2 35–300 (500 *)
nkt cables TI 12 25–240
TO 12 25–300 (500 *)
Three-core thermoplastic-insulated cables for ≤ 12 kV (6 / 10 kV); acc. to IEC standard 2)
Euromold AIN 10, AFN 10 •) 25–300 (500 *)
12 MONOi 35–300 (500 *)
Prysmian Kabel und Systeme ELTI-3C-12 25–300 Panel type L ...
TE Connectivity IXSU-F33xx 16–300 (500 *)
Lovink-Enertech IAES 10 25–300
GHKI 16–300 (400 *)
Single-core thermoplastic-insulated cables for > 12 kV to ≤ 24 kV (12 / 20 kV) •) 2)
Euromold AIN 20, AFN 20 25–300 (630 *)
AIS, AIP 70–300; 25–300
24 MONOi 25–300 (500 *)
36 MSC 3) 95–300 (500 *) Panel type T ...
36 MSC (Option 4)) 95–300 (500 *) Dimension a
ITK-224 25–240 ~ 384 mm:
Prysmian Kabel und Systeme ELTI mb-1C-24 35–240 For fuses with e = 442 mm
ELTI-1C-24 25–300 (standard for 24 kV)
TE Connectivity IXSU-F 25–300 (500 *) ~ 534 mm:
MVTI-51xx- 25–300 For fuses with e = 292 mm
EPKT 16–300 (500 *)
Note:
Lovink-Enertech IAEM 20 25–300
Depending on make and
IAES 20 25–300 (500 *)
type, the termination of
3M 93-EB 6x-1 50–300 (400 *) the cable sealing end
Südkabel SEHDI 20.2 35–300 (500 *) (= shield earth) for the 3-core
SEI 24 25–240 thermoplastic-insulated cable
nkt cables TI 24 25–240 and the fitted cable clamp
TO 24 25–300 (500 *) (option) may be located
Three-core thermoplastic-insulated cables for > 12 kV to ≤ 24 kV (12 / 20 kV) •) 2) underneath the panel in the
Euromold 24 MONOi 35–300 (500 *) cable basement. This must be
taken into account in panels
AFN 20, AIN 20 35–300
with floor cover (option).
Lovink-Enertech GHKI 25–300 (500 *)
TE Connectivity on request IXSU-F53xx on request
Cable cross-sections
Panel type Panel width Version Connected cables Transformer combination in the connection
x connection cross-section compartment
number x mm2
for rated voltage Current transformer
12 kV 17.5 kV 24 kV 4MC70 4MA 4MR
Standard 1 x 300 1 x 300 1 x 300
K 375
On request 2 x 300 2 x 300 2 x 300
Standard 1 x 300 1 x 300 1 x 300
K1 500
Option 2 x 400 2 x 300 2 x 300
Standard 1 x 300 1 x 300 1 x 300
R 375
On request 2 x 300 2 x 300 2 x 300
Standard 1 x 300 1 x 300 1 x 300
R1, D1 500
Option 2 x 300 2 x 300 2 x 300
Standard 1 x 300 1 x 300 1 x 300
L 500
Option 2 x 240 2 x 240 2 x 240 – –
Standard 1 x 300 1 x 300 1 x 300
L1 750
Option 2 x 300 2 x 300 2 x 300
M(-K), Standard 1 x 400 1 x 300 1 x 300
750
M(-BK) Option 3 x 400 3 x 300 3 x 300
Standard 1 x 400 1 x 300 1 x 300
M(KK) 750
Option 2 x 300 2 x 300 2 x 300
Standard 1 x 300 1 x 300 1 x 300 –
L1(r) 750
Option 2 x 300 2 x 300 2 x 300 –
Standard 2 × 300 2 × 300 2 × 300
L2(r) 875
Option 3 × 300 3 × 300 3 × 300
possible – not possible
Cable fixing: Depending on the cable type (1-core cable, 3-core cable) or the associated panel type )
and its components, the cable may also be fixed in the cable basement (for local installation):
1-core cable 3-core cable
Max. dimensions Cable version
Hcc in mm 1-core 3-core
Standard 435 425
Option: 469 459
cable clamp
(= Option)
H cc = Available height for cable
connection: From the
Optionally, a deep floor cover is also possible: mounted cable clamp 5)
• Requirements according IEC 62271‑105 fulfilled as
“OPEN” indication
HV alternating current switch-fuse combination
• Selection of HV HRC fuses for transformers
• Fuse replacement possible only when feeder is earthed
• Option: Shunt release on operating mechanism of Control board of a transformer feeder
three-position switch-disconnector
1 HV HRC fuse
• Option: “Tripped indication” of three-position switch-
(not included
disconnector in transformer feeder (transformer switch) in the scope of
for remote electrical indication with one normally-open supply)
contact (1 NO). 2 Earthing switch
1 for cable
Mode of operation connection
“HV HRC fuse tripped” 3 Cover for bolted
cable lug con-
Following the tripping of an HV HRC fuse-link, the 2 nection (e.g. for
mechanism for charging the spring must be set to the rated voltage
“OPEN” position. 3 Ur = 24 kV)
Subsequently, earthing can be implemented by means of 4 Cable sealing end
the three-position switch-disconnector and e.g. the fuse (not included
can be replaced. in the scope of
4
supply)
Replacement of HV HRC fuse-links (without any tools)
• Isolating and earthing of the transformer feeder R-HA41-129a.tif
Features
• According to IEC 61869‑2 / Three-phase current transformer 4MC63 ... installed on
DIN EN 61869-2 *) bushing-type insulators
• D esigned as a three-pole
R-HA41-142.tif
R-HA41-044.eps
ring-core current trans-
former
• Free of dielectrically
stressed cast-resin parts
(due to design)
• Insulation class E
• Inductive type
• Climate-independent Technical data Three-phase current transformer 4MC63 60 (standard type) 1)
• Secondary connection by for IN ≤150 A for IN ≤ 400 A for IN ≤ 1000 A
means of a terminal strip for ID = 630 A for ID = 630 A for ID = 1250 A
in the panel.
Primary data
Installation
Highest voltage 0.72 kV 0.72 kV 0.72 kV
• Arranged outside the for equipment Um
switching-device vessel on Rated current INA 150 100 75 50 400 300 200 1000 750 600 500
the bushings Rated short-duration 3 kV 3 kV 3 kV
• Factory-assembled power-frequency
withstand voltage
• Mounting location:
(winding test)
–– For circuit-breaker panels
Rated short-time 25 kA / 1 s, 2 s 1) 25 kA / 1 s, 2 s 1) 25 kA / 1 s, 2 s 1)
type L...
thermal current Ith or 20 kA / 3 s or 20 kA / 3 s or 20 kA / 3 s
–– For bus sectionalizer
Rated continuous 630 A 630 A 1250 A
panels type L(T)
thermal current ID
–– Option: On request for
Transient overload 1.5 x ID / 1 h 2 x ID / 0.5 h 1.5 x ID / 1 h
ring-main-panels type R... current
Rated dynamic 2.5 x Ith 2.5 x Ith unlimited
Other designs
current Idyn
(option)
For protection equipment
Secondary data
based on the current-trans-
Rated current A 1 0.67 0.5 0.33 1 0.75 0.5 1 0.75 0.6 0.5
former operation principle:
RatingVA 5 3.33 2.5 1.67 5 3.75 2.5 5 3.75 3 2.5
Three-phase current trans-
Rated current (option) 5A 5A 5A
former type 4MC63 60 for
• Protection relay 7SR45 Current at ID 4.2 A 1.575 A 1.25 A
(7SJ46) as definite-time Protec- Class 10 P 10 P 10 P
tion Overcurrent 10 10 10
overcurrent protection
core factor
• D efinite-time overcurrent
protection relay, make 1) Other values on request, e.g. as additional type 4MC63 63 (complementary types)
Woodward / SEG, type
WIP-1.
Three-phase current
transformer 4MC63 64 for
• D efinite-time overcurrent
protection relay, make
Woodward / SEG, type WIC.
Features
• According to IEC 61869‑2 / Cable-type current transformer Cable-type current
DIN EN 61869-2 *) 4MC70 33, 4 overall heights transformer 4MC70 31
• D esigned as a single-pole
ring-core current trans-
R-HA41-024a eps
R-HA41-025 eps
former
H
• Climate-independent
H
• Free of dielectrically
stressed cast-resin parts
(due to design) On request:
• Insulation class E Cable-type current transformer
• Inductive type
R-HA41-027.eps
• Secondary connection by
means of a terminal strip
inside the panel. B
Application
• For circuit-breaker panels
type L... Technical data Cable-type current Cable-type current
transformer 4MC70 33 transformer 4MC70 31
• For ring-main panels
type R... Primary data
• For transformer panels Highest voltage 0.72 kV 0.72 kV
type T... for equipment Um
Rated current IN 20 A to 600 A 50 A to 600 A
Installation Rated short-duration 3 kV 3 kV
• C able-type current trans- power-frequency withstand
voltage (winding test)
former 4MC70 33 for
panel types: R..., K..., L... Rated short-time up to 25 kA / 1 s or 25 kA / 3 s 25 kA / 1 s,
thermal current Ith or 20 kA / 3 s or 14.5 kA / 3 s
• C able-type current trans- Rated continuous 1.0 x IN 1.0 x IN
former 4MC70 31: E.g. for thermal current ID option: 1.2 x IN option: 1.2 x IN
panel types R..., K... Transient overload current 1.5 x ID / 1 h 1.5 x ID / 1 h
and T... or 2 x ID / 0.5 h or 2 x ID / 0.5 h
• Arranged on the cable at Rated dynamic current Idyn 2.5 x Ith 2.5 x Ith
the panel connection
• For shielded cables Secondary data
• Transformers mounted on Rated current 1 A or 5 A 1 A or 5 A
a supporting plate at our Measuring Class 0.2 0.5 1 1
core
factory; final assembly on Overcurrent factor without FS5 FS10 FS5 (option: FS10)
the cables on site. Rating 2.5 VA to 30 VA 2.5 VA to 10 VA
Protection Class 10 P 5P –
core Overcurrent factor 10 10 –
Rating 2.5 VA to 10 VA –
Option: Secondary tap 1 : 2 (e.g. 150 A – 300 A) 1:2
Dimensions
Overall height H 2) mm 65 1) 110 1) 170 1) 285 1) 89
Outside diameter 150 mm 85 mm x 114 mm
Inside diameter 55 mm 40 mm
*) For standards, see page 72 For cable diameter 50 mm 36 mm
1) Depending on the core data
2) Available installation space for Other values on request
cable-type current transform-
ers inside the panels depends
on make, type and cross-sec-
tion of sealing end.
Example: Panel type R or K:
Installation space
approx. 285 mm
Features Application
Current transformer 4MA7 • For panel types:
• According to IEC 61869‑2 / DIN EN 61869-2 *) –– Metering panel type M...as billing metering panel
• Dimensions according to DIN 42600-8 (750 mm wide)
• D esigned as a single-pole indoor block-type current –– Metering panel / bus riser panel type H and H1
transformer –– Busbar voltage transformer panel types M(VT), M(VT-F), L …
• Cast-resin insulated • For mounting at the feeder.
• Insulation class E
• Secondary connection by means of screw-type terminals.
R-HA41-030a eps
R-HA41-029a eps
Voltage transformer 4MR
• According to IEC 61869‑3 / DIN EN 61869-3 *)
• Dimensions according to DIN 42600-9 (small model)
• Designed as an indoor voltage transformer:
–– Type 4MR, single-pole
–– Option: Type 4MR, two-pole
• Cast-resin insulated
• Insulation class E
• Secondary connection by means of screw-type terminals. Current transformer 4MA7, Voltage transformer 4MR14,
single-pole single-pole
Technical data
Current transformer 4MA7, single-pole (other values on request)
Primary data
Highest voltage for equipment UmkV 3.6 7.2 12 12 17.5 24
Rated short-duration power-frequency withstand voltage UdkV 10 20 28 42 38 50
Rated lightning impulse withstand voltage UpkV 20 60 75 75 95 125
Rated current INA 20 to 1200
Rated short-time thermal current IthkA up to 20 kA / 3 s, or up to 25 kA / 1 s
Rated continuous thermal current ID up to 1.0 × In (option: 1.2 × In)
Rated dynamic current Idyn max. 2.5 × Ith
Secondary data
Rated current A 1 or 5
Measuring core Class 0.2 0.5 1
Overcurrent factor without FS5 FS10
Rating VA 2.5 to 30
Protection core Class 5 P or 10 P
Overcurrent factor 10
Rating VA 2.5 to 30
Ready-for-service indicator
Features Gas monitoring
• Self-monitoring; easy to read
• Independent of temperature and pressure variations
• Independent of the site altitude
• Only responds to changes in gas density
• Option: Alarm switch “1 NO” for remote electrical indication.
Mode of operation 1 Green indication:
Ready for service
For the ready-for-service indicator, a gas-tight measure-
(red indication:
ment box is installed inside the switching-device vessel.
Not ready for service)
A coupling magnet, which is fitted to the bottom end of
the measurement box, transmits its position to an outside
armature through the non-magnetizable stainless-steel
switching-device vessel. This armature moves the ready-
for-service indicator of the switchgear.
While changes in the gas density during the loss of
gas, which are decisive for the dielectric strength, are
displayed, temperature-dependent changes in the gas
pressure are not. The gas in the measurement box has the
same temperature as that in the switching-device vessel. Stainless-steel vessel Ready-for-service
The temperature effect is compensated via the same filled with SF6 gas indicator
pressure change in both gas volumes.
Ready-for-service indicator
Principle of operation 2 Measurement box
of gas monitoring with 3 Magnetic coupling
ready-for-service indicator
R-HA41-122b.tif
R-HA41-EARTH-ZERO.psd
be equipped with short-circuit or earth-fault indicators in
different designs. The equipment features are shown in the
table on page 46.
Short-circuit and earth-fault indicators reduce the
downtimes of a power system by delimiting the fault
locations in medium-voltage systems.
R-HA40-146.tif
EARTH ZERO
R-HA41-ALPHA-E.psd
Ring-main unit
Short-circuit indicator has picked up
Short-circuit indicator has not picked up
Response of protection device with tripping
ALPHA E
Short-circuit/earth-fault indicators can be used in all kinds of
power systems. In impedance-earthed and solidly earthed
systems, as well as in isolated and compensated (resonant-
R-HA41-SIGMA-2.psd
ComPass Bs 2.0
Short-circuit /
ComPass A 2.0
ComPass B 2.0
EarthZeroFlag
SIGMA F+E 2.0
earth-fault indicators
SIGMA D++
Earth Zero-
SIGMA 2.0
SIGMA D+
from Horstmann
ALPHA M
SIGMA D
Function ALPHA E
Short circuit / earth fault / / / / / / / / / / –/
Direction indication – – – – – –
Monitoring: U, I, f, P, Q, S, E,
– – – – – – – –
cos ϕ, load flow direction
Control of a CB or SD – – – – – – – – – –
Logic – – – – – – – – – –
Applicable for the following neutral treatments
Impedance earthed
Solidly earthed
Isolated –
Compensated –
Short-circuit pickup values
400, 600, 200, 300, 400, 600, DIP: 200, 300, 400, 600, 800,
I>> Short-circuit current 800, 800, 1000, 2000 A, 2000 A, self-adjustment 20 – 2000 A –
1000 A self-adjustment Software (SW): 50 – 2000 A
40, 80, 200, DIP: 40, 80 ms,
tI>> Pickup delay 100 ms 40, 80 ms 40 ms – 60 s –
300 ms Software (SW): 40 ms – 60 s
Reset
Manually / from remote / – (M)
/ / / / / / / / / / –
/ (E)
Auto. time reset (E)
Current/voltage recovery – – – / – / / / / – / / –/
Test
Manually / from remote / – / / / / / / / / –
Communication
Relay contact 1 1 2 3 4 4 4 4 4 4 1
Maintained / passing contact adjustable adjustable adjustable adjustable adjustable
RS485 / MODBUS-RTU – – – – – – – –
USB connection – – – –
Parameterizing
Manually / from remote / – / – / – / – / – / – / – / / / / –
Supply
Lithium cell, ≥ 20 years (E) /Capacitor (AC/DC)
Current-transformer operated (not IET>) – – –
External auxiliary voltage 24 – 230 V
24 V AC, 24 – 230 V
24 – 230 V AC / DC AC / DC 24 – 230 V
– – 24 – 60 V DC AC / DC –
(only AC / DC versions) (SIGMA F+E3 AC / DC
(possible) (for IET>)
2.0 optional)
Binary inputs
Number 2 2 2 2 2 2 2 2 2 6 –
Number of phase current / summation current sensors
Short circuit / earth fault 3/0 3/0 3/0 3/0 3/0
3/0 or 3/1 for
3/0 or 3/1 3/0
3/0 (opt. 3/1
0/1
IET> or 2/1)
Voltage coupling
Capacitive – – – – – –
Resistive – – – – – – – – –
R-HA41-IKI-20.tif
be equipped with short-circuit or earth-fault indicators in
different designs. The equipment features are shown in
the table on page 48.
The three most common types of faults in medium-voltage
systems are earth faults in cables and switchgear, faults and
overloads of distribution transformers, as well as short
circuits in cables and switchgear. For fast fault location and
minimization of downtimes, electronic fault indicators are IKI-20
used:
• Selective fault detection, and thus minimization of
downtimes
• Reliable fault detection through electronic measured-
R-HA41-IKI-20CPULS.tif
value acquisition
• Remote indication of fault events and measured values.
1. Short-circuit and short-circuit-to-earth indicator IKI-20
– Universally adjustable
– Current-transformer supported battery version or
auxiliary voltage versions available
– Extended commissioning and testing functions.
IKI-20CPULS
2. Short-circuit and earth-fault indicator IKI-20PULS
– Short-circuit detection same as IKI-20
– Earth-fault detection via pulse location in compensated
systems.
R-HA41-IKI-22.tif
IKI-10-light-P
IKI-20CPULS
50_2F_EW_
50_1F_EW_
IKI-20PULS
IKI-50_2F
IKI-50_1F
Short-circuit /
IKI-20U
IKI-20C
IKI-20B
IKI-20T
IKI-22
PULS
PULS
IKI-
IKI-
earth-fault indicators
from Kries
Function
Short-circuit indication
Earth-fault indication
Short-circuit-to-earth
indication 5)
Direction indication
Solid
Isolated
Compensated
Pickup current
Short-circuit current 400, 600, 100, 200, 300, 400,
100, 200, 400, 600, 800,
800, 1000 600, 800, 1000, 2000 A 100 ... 1000 A (steps of 100 A)
1000, 2000 A
A
Earth-fault current Transient fault detection 4 ... 30 A (steps of 1 A)
Short-circuit-to-earth 20, 40,
40, 80, 100, 150 A 40, 80, 100, 200 A 40 ... 200 A (steps of 10 A)
current 5) 60, 80 A
Pulse location
Pickup time
Short-circuit current 60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 – 1600 ms
Short-circuit-to-earth 70,
60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 – 1600 ms
current 5) 250 ms
Earth-fault current Pulse Pulse
Transient fault detection 400 – 3000 ms
location location
Reset
Manual
Automatic
From remote
Remote indication
Passing contact adjustable adjustable
Maintained contact adjustable adjustable
Interface
RS485 / MODBUS
IEC 60870‑5-104 (option)
Power supply
Lithium battery
R-HA41-SICAM-FCM.tif
Earth-fault indication
Earth-fault function
(impedance-earthed system)
Indication of direction,
–
short-circuit/earth-fault
Undervoltage and overvoltage
– SICAM FCM
indication
Applicable for the following neutral earthing options
Impedance
Solid 1. SICAM FCM
Isolated The short-circuit and earth-fault indicator SICAM FCM
Compensated (Feeder Condition Monitor) with direction indication
Pickup current enables fast and precise fault location, thus reducing
Type 1: 200 – 1200 A, the downtimes in the power system. The possibility to
50 … 2000 A
Short-circuit current
(steps of 1 A)
type 2: 200 – 800 A determine and telecommunicate the values U, I, f, P, Q, S,
(in 7 steps each) E, cos ϕ and load flow direction supports efficient opera-
Type 1: 10 – 100 A, tional management and network planning.
1 … 1000 A
Earth-fault current type 2: 40 – 300 A
(steps of 1 A)
(in 7 steps each)
• Usable in earthed, isolated and resonance-earthed systems
Pulse location – –
Pickup time • Directional short-circuit and earth-fault detection
40 ms • Selective fault information with direction indication as a
Short-circuit current < 500 ms adjustable
< t < 60 s basis for “self-healing” applications
40 ms
Earth-fault current < 500 ms adjustable • Usable with current and voltage sensors according to
< t < 60 s
IEC 60044 for precise measurement without calibration
Reset
and adjustment to the primary values
Manual
Automatic • Alternatively usable with an integrated capacitive voltage
From remote detecting system
Remote indication • Flexible earth-current detection as from 0.4 A
Passing contact adjustable – • Integrated MODBUS-RTU interface:
Maintained contact adjustable 2 binary outputs
• Remote parameterization via SICAM A8000 and MODBUS
Interface
RS485 / MODBUS –
• Self-test function of the communication connection.
Power supply 2. SICAM FPI (Fault Passage Indicator)
Lithium battery
• Detection of short circuits and earth faults
External auxiliary voltage –
Current inputs
• Indication of phase and earth faults via 4 separate LEDs
Phase current 3 (2) 1) 3 optical • Enhanced diagnostics, self and sensor cable diagnostics
Summation current 0 (1) 1) 1 optical is supported
Voltage inputs • Configurable binary outputs, for remote indication to
Via resistor divider 3 – SCADA via RTU for faults and for diagnostics.
Via integrated capacitive
3 –
voltage indicator (optional)
Relay outputs
Potential-free 2 2) 2
R-HA41-SICAM-FPI.psd
Binary inputs
Number 1 –
SICAM FPI
R-HA41-IKI-30.tif
• Tripping of the circuit-breaker in case of overload
(delayed)
• Tripping of the circuit-breaker when the short-circuit
current arises.
R-HA40-103 psd
in indicator Plug-in
• LRM detecting systems with integrated voltage
indicator
indicator type VOIS+, VOIS R+,
CAPDIS-S1+, CAPDIS-S2+, WEGA 1.2 C, per phase at
the panel front
WEGA 2.2 C or WEGA 3.
Plug-in voltage indicator
• Verification of safe isolation from
supply phase by phase
• Indicator suitable for continuous operation
R-HA41-VOIS tif
• Measuring system and voltage indicator
can be tested, repeat test according to
local specifications and standards
• Voltage indicator flashes if high voltage
is present.
Integrated voltage indicator
VOIS+, VOIS R+
VOIS+, VOIS R+
• Without auxiliary power
• Display indication “A1” to “A3”
CAPDIS S2+: The red and green LEDs show the
(see legend) state of the relay contacts
• Repeat test according to local
R-HA41-CAPDIS-S1.tif
WEGA 3
• Display indication “A1” to “A5”
Symbols shown
R-HA41-WEGA-3.tif
• Integrated repeat test of the
interface (self-monitoring) WEGA 3 WEGA 1.2 C WEGA 2.2 C
• With integrated 3-phase LRM
test socket for phase com-
parison.
interface (self-monitoring)
• With integrated function test
(without auxiliary power) by
pressing the “Display Test”
button
• With integrated 3-phase LRM Integrated voltage indicator
WEGA 1.2 C
test socket for phase com-
parison.
R-HA41-WEGA-2-2-C.tif
Verification of correct
terminal-phase connections Phase comparison test units according to IEC 61243-5 or VDE 0682-415
• Verification of correct terminal-
R-HA41-EPV.eps
R-HA41-ORION-3-1.tif
phase connections possible by
means of a phase comparison
test unit (can be ordered
separately)
• Safe-to-touch handling of
the phase comparison test unit
by inserting it into the capaci-
tive taps (socket pairs) of the
switchgear.
R-HA41-ORION-M-1.tif
R-HA41-201 tif
– Cable-type current transformer (standard)
– Three-phase current transformer as option for SIMOSEC
switchgear panels type L .....
Mounting location Reyrolle 7SR45
• In 350 mm high low-voltage compartment (option) of the
circuit-breaker feeder, or in the low-voltage niche.
R-HA41-058b tif
• Installation on the panel: 3 2 LCD
Possible per feeder 4
3 Navigation keys
• Customer-specific equipment 4 Function keys
For accommodation of protection, control, measuring On circuit-breaker panel type L, L1, …
and metering equipment for additional low-voltage equipment
• O verall height depends on the panel-specific
configuration of primary and secondary equipment
• D oor with hinge on the left
(standard for heights of 350 and 550 mm) Low-voltage compartment (example 750 x 350 mm)
Option: Door with hinge on the right.
R-HA41-040a tif
Low-voltage cables
• Control cables of the panel to the low-voltage compart-
ment via multi-pole, coded module plug connectors
• Option: Plug-in bus wires from panel to panel inside the
low-voltage niche, or optionally in the separate wiring
duct on the panel.
Switchgear height
1750 mm
mounting frame), e.g.
– Type 7SR45, 7SR10:
For type L and L1
– Make Woodward / SEG,
type WIC1: For type L and L1 In circuit-breaker panel In circuit-breaker panel
On request: type L (500 mm) (with CB-f NAR*)) type L1 (750 mm)
– 7SJ80
– Make Woodward / SEG,
WIP-1 Protection relay as option:
12
• For bus wires and / or control 1 Protection relay type 7SR45
cables; niche open at the side 2 On request: Protection relay type
to the adjacent panel 7SJ80 in LV niche
3 Protection relay make 1, 3
• Safe-to-touch, separated from
Woodward (SEG), type WIC 11
high-voltage part of the panel
4 On request:
• Degree of protection IP3X Multifunction protection relay
(standard). SIPROTEC 4 type 7SJ61 on swing-out
frame
R-HA41-143b tif
Option: as door
8 Option: Local-remote switch for
three-position switch-disconnector
9 Option: Momentary-contact rotary
In circuit-breaker panel
control switch ON-OFF for motor
type L (500 mm)
operating mechanism of the
three-position switch-disconnector
10 Panel front
11 Low-voltage niche open
12 Option:
Installed equipment
In metering panel
type M (750 mm)
(low-voltage niche open)
*)
A R = Automatic reclosing
NAR = Non automatic reclosing
arrangement).
Room dimensions
See opposite dimension
drawings.
Door dimensions
The door dimensions depend
on the
–– Number of panels in a
transport unit
–– D esign with or without
low-voltage compartment.
Switchgear fastening
• For floor openings and fixing
points of the switchgear, see Wall-standing arrangement (side view) Free-standing arrangement (side view)
pages 66 to 68
• Foundations:
–– Steel girder construction
–– Steel-reinforced concrete.
Panel dimensions
See pages 60 to 65
Weight
The weight of a panel d
epends
on the extent to which it is
equipped (e.g. with motor
operating mechanism, volt-
age transformer). For details,
please refer to page 69.
Wall- – – 1750 ≥ 2400
standing
Free- – – ) 1750 ≥ 2400
standing
Free- IAC A FLR 2100 ≥ 2400
l
standing 16 kA, 1 s
IAC A FLR l 2100 ≥ 2400
21 kA, 1 s
16 End wall
17 Depth of pressure relief duct
18 Option: Pressure relief duct for each panel,
for wall-standing or free-standing arrangement
19 Option: Front cover (panel without low-voltage compartment)
20.1 Option: Low-voltage compartment: 350 mm high
20.2 Option: Low-voltage compartment: 550 mm high
21.1 End wall: 1750 mm high
21.2 End wall: 2100 mm high
(standard for IAC design, ) Option: Rear pressure relief duct
option without IAC = 2100 mm high) l As standard
Compartment Dimensions for: in mm
“Available mounting depth approx.
for low-voltage equipment”
LV niche – with front cover a1 201
LV niche – with door a2 246
(option)
LV compartment (option) a3 443
*)
Option: Low-voltage compartment or front cover
available in two heights: 350 mm or 550 mm
1)
Option: Pressure relief duct
Position of cables ) x1 ) x2 )
*)
P anel depth depends on panel type and panel design:
– Low-voltage niche with door (= option) (instead of screwed front cover): 1041 mm
– L ow-voltage niche with door: 1041 mm
**) In addition, a low-voltage compartment can be selected optionally. The switchgear height is changed respectively
Ring-main panels
Type R Type R1 Type R1(T)
Ring-main panel Ring-main panel
type R(T) type R(T)
for panel combinations, for panel combinations,
as left-hand transfer as right-hand transfer
panel type R(T) panel type R(T)
(placed on the left side of (placed on the right
panel combination) side of panel combina-
tion)
Type R(T) Type R(T)
Transformer panels
*) Option:
Low-voltage compartment
** For panel design with 4MA
block-type current transformer,
the cable connection height is
reduced
1) Location of voltage transformer
in left-hand panel
Panel type T:
2) Dimension a
~ 384 mm: for fuses with e = 442 mm
~ 534 mm: for fuses with e = 292 mm
panel
Cable panels
Type K Type K1
Type D1 Type D1(T)
Disconnector panel type D1 for cable connection Disconnector panel type D1(T)
for panel combinations [e. g. metering panel type M or L1(T)]
*) Option:
Low-voltage compartment
**) For panel design with 4MA
Circuit-breaker
panel 630 A
Type L (500 mm) Type L(T)
as transfer panel to the right
Circuit-breaker
panel 630 A, 1250 A
Type L1 (750 mm) Type L1(T)
as transfer panel to the right
*) Option:
Low-voltage compartment
**) For panel design with 4MA
block-type current transformer,
the cable connection height is
Position of L1, L2 and L3: See page 59 reduced
Dimensions x1 and x2: See pages 59 and 66 ) Option: Protection relay
M
M(-K)
Type M Type M(-K)
Metering panel type M (standard) Metering panel type M(-K) (for cable connection)
M(-B)
M(-BK) M(-BK)
Type M(-BK)
Type M(-B)
Ur Dimensions in mm
x1 x2 *) Option:
Low-voltage compartment
Up to 17.5 kV 187 210 **) The cable connection height
24 kV 215 250 depends on the rated voltage,
the transformer design and the
Dimensions x1 and x2 for cable connection: See pages 66 and 67 number of cable connections
Metering panel
and / or
Bus riser panel bus riser panel
Ur Dimensions in mm
x1
Up to 17.5 kV 187
24 kV 187
Ur Dimensions
in mm
x1 x2
Up to 17.5 kV 187 210
24 kV 215 250
*) Option:
Low-
voltage
compart
ment
2) Earthing of
the feeder
via the
vacuum
circuit-
breaker
Option:
Inspection
window
Dimensions
x1, x2 and c2
for cable con-
nection:
Circuit-breaker panels 630 A
Type L1(r) Type L1(r) Type L1(r, T) 2) See pages 66
as transfer panel and 67
Circuit-breaker panels 1250 A
Type L2(r) Type L2(r) Type L2(r, T) 2)
as transfer panel
Panel Rated normal Total width Serial Panel Rated normal Total width Serial
combination *) current of TC of TC no. combination *) current of TC of TC no.
(in mm) of TC (in mm) of TC
R(T) - H 630 A, 800 A 750 TC-1 L1(T) - M 630 A 1500 TC-23
H - R(T) 630 A 750 TC-2 L1(T) - M(-K) 630 A 1500 TC-25
R(T) - R(T) 630 A, 800 A 750 TC-3 L1(T) - R(T) 630 A 1125 TC-27
R(T) - M 630 A, 800 A 1125 TC-4 D1(T) - H 1250 A 875 TC-45
R(T) - M(-K) 630 A, 800 A 1125 TC-6 L1(r,T) - H1 630 A 1250 TC-61
L(T) - H 630 A 875 TC-11 L1(r,T) - R1(T) 630 A 1250 TC-62
L(T) - M 630 A 1250 TC-13 L2(r,T) - H1 1250 A 1375 TC-63
L(T) - M(-K) 630 A 1250 TC-15 L2(r,T) - D1(T) 1250 A 1375 TC-64
L(T) - R(T) 630 A 875 TC-17 R(TM) - L(TM) 630 A 1500 TC-57
L1(T) - H 630 A 1125 TC-21 R(TM) - L1(TM) 630 A 1750 TC-58
*) C
urrent and voltage transformer installation in the “TC”: Depending on the type of “TC” and the rated voltage (not possible everywhere)
TC = Typical combination
For Dimensions in mm
panel type x1 x1 x2 c1
T 187 187 210 210 187.5 187.5
Position of cables 1)
For Dimensions in mm
panel type x1 x1 x2 c1
T1 187 187 210 210 187.5 187.5
L 187 187 210 210 187.5 187.5
Position of cables 1)
1 187 215 210 250 235 335
L1 with CTs,
VTs 2 187 215 210 250 235 335
1 Wall distance (see page 59) 4 Position of the led-in cables for the feeder 1)
2 Fixing frame (base) of an individual panel or panel block 5 Fixing points
3 Floor opening for high-voltage cables and, where applicable, 6 Floor opening if required for panels without cable connection
control cables 7 Option: Pressure relief duct
Note: 1) The position of the cables in the panel depends on the additional
Connection of double cables: Depending on the panel type and version built-in panel components, e.g. current and voltage transformers.
of the sealing end, the cable distance is approx. 110 mm. Therefore, the dimensions x1, x2, c1, c2 may be different.
Position of cables 1)
panel type Number x1 x1 x2 c1 c1
of cables
For Dimensions in mm
Position of cables 1)
For Dimensions in mm
3 187 235 210 230 377 377
1 Wall distance (see page 59) 4 Position of the led-in cables for the feeder 1)
2 Fixing frame (base) of an individual panel or panel block 5 Fixing points
3 Floor opening for high-voltage cables and, where applicable, 6 Floor opening if required for panels without cable connection
control cables 7 Option: Pressure relief duct
Note: 1) The position of the cables in the panel depends on the additional
Connection of double cables: Depending on the panel type and version built-in panel components, e.g. current and voltage transformers.
of the sealing end, the cable distance is approx. 110 mm, or 100 mm. Therefore, the dimensions x1, x2, c1, c2 may be different.
For For
panel type: panel type:
R(T) R1(T), E1
M(VT), M1(VT),
M(VT-F) M1(VT-F)
H, E L(T)
D1(T)
H1
For panel width 750 mm For panel width L1(r, T), width 750 mm
For For
panel type: panel type:
L1(r, T)
L1(T)
M, M(-B)
For
panel type:
L2(r, T)
1 Wall distance (see page 59) 4 Position of the led-in cables for the feeder 1)
2 Fixing frame (base) of an individual panel or panel block 5 Fixing points
3 Floor opening for high-voltage cables and, where applicable, 6 Floor opening if required for panels without cable connection
control cables 7 Option: Pressure relief duct
Note: 1) The position of the cables in the panel depends on the additional
Connection of double cables: Depending on the panel type and version built-in panel components, e.g. current and voltage transformers.
of the sealing end, the cable distance is approx. 110 mm. Therefore, the dimensions x1, x2, c1, c2 may be different.
Individual panels or Panel type Panel or panel Transport unit “TU” (including packing) for standard panels
combinations thereof for combination (without / with pressure relief duct, option)
standard switchgear
Width Net Width Height H ) Depth Volume Gross
B1 weight 1) B2 of “TU” T2 weight 1)4)
mm approx. kg m m m m3 approx. kg
without / with without / with without / with without / with
LV C*) / LV C*) LV C*) /LV C*) LV C*) / LV C*) LV C*) / LV C*)
*) L ow-voltage compartment, 350 mm high, weight 1) The net weight and the gross weight depend on the extent to which
approx. 60 kg depending on the panel type and on the the panel is equipped (e.g. current transformers, motor operating
extent to which it is equipped, or optionally 550 mm mechanisms) and are therefore given as mean value
high 3) P anel types including CTs and VTs: Weight per CT or VT as cast-resin
) O ther heights “H“ of “TU“ possible (depending on the design: Approx. 20 kg (example: 3 CTs and 3 VTs approx.
equipment of the panel type and the packing type) additionally 120 kg per panel)
) Depending on the delivering factory 4) Add additional weight for pressure relief duct (according to table values)
Individual panels or Panel type Panel or panel Transport unit “TU” (including packing) for standard panels
combinations thereof for combination (without / with pressure relief duct, option)
standard switchgear
Width Net Width Height H ) Depth Volume Gross
B1 weight 1) B2 of “TU“ T2 weight 1)
mm approx. kg m m m m3 approx. kg
without / with without / with without / with without / with
LV C*) / LV C*) LV C*) / LV C*) LV C*) / LV C*) LV C*) / LV C*)
For individual panel
For combinations of different individual panels
*) L ow-voltage compartment, 350 mm high, weight approx. 60 kg 1) The net weight and the gross weight depend on the extent to
depending on the panel type and on the extent to which it is which the panel is equipped (e.g. current transformers, motor
equipped, or optionally 550 mm high operating mechanisms) and are therefore given as mean value
** Packing weight 2)
Sum of the net weights of individual panels
*** On request: Max. panel width “B3“ ≤ 1125 mm (e.g. for 3 x 375 mm)
Δ) O ther heights “H“ of “TU“ possible (depending on the equipment of
the panel type and the packing type)
) Depending on the delivering factory (CN, PT)
Overseas Type: Seaworthy crate (standard)
by seafreight Welded PE protective foil, with closed wooden crate, Pallet
with desiccant bag
Type: Open for container Crane transport with pallet
PE protective foil pulled over the switchgear,
with wooden base
Overseas Type: Open
by airfreight PE protective foil pulled over the switchgear,
with wooden base and lattice or cardboard cover
Transport
SIMOSEC switchgear is completely delivered in transport
units. Please observe the following:
Transport with lifting truck
• Transport facilities on site
with or without pallet
• Transport dimensions and weights
• Size of door openings in building
• Switchgear with low-voltage compartment: Please
Standards
SIMOSEC switchgear complies with the relevant standards and
specifications applicable at the time of type tests.
In accordance with the harmonization agreement reached by
the countries of the European Union, their national
specifications conform to the IEC standard.
Insulating gas Specification for sulfur hexafluoride (SF6) IEC 60376 VDE 0373‑1 EN 60376 –
SF6
HA40-2037c en eps
m=1
PM IEC / EN 60529:
Metallic partition according to IEC 62271‑200 (3.109.1). Type of protection Degree of protection
Metallic partitions between open, accessible compart- Standard: IP 2 X
ments and live parts.
The SIMOSEC switchgear is suitable for application in Protection against solid foreign objects
indoor installations under normal operating conditions as Protected against solid foreign objects of 12.5 mm diameter
defined in the standard IEC 62271‑1. and greater (the object probe, sphere of 12.5 mm diameter,
shall not fully penetrate)
Protection against solid foreign objects,
electric shock and water
Protection against access to hazardous parts
SIMOSEC switchgear fulfills according to the standards *)
Protected against access to hazardous parts with a finger
IEC 62271‑1 EN 62271-1 VDE 0671‑1 (the jointed test finger of 12 mm diameter, 80 mm length,
IEC 62271‑200 EN 62271-200 VDE 0671‑200 shall have adequate clearance from hazardous parts)
IEC 60529 EN 60529 VDE 0470‑1
IEC 62262 EN 50102 VDE 0470‑100 Protection against water
No definition
the following degrees of protection
Option: IP 3 X
(for explanations, see opposite table):
Degree of protection “IP” Type of protection
Protection against solid foreign objects
IP2X (standard) for switchgear enclosure
Protected against solid foreign objects of 2.5 mm diameter and
IP3X (option) for switchgear enclosure
greater (the object probe, sphere of 2.5 mm diameter, shall not
(optional)
penetrate at all)
IP3XD (option on request) for switchgear enclosure
(on request)
Protection against access to hazardous parts
IP65 for parts of the primary circuit of
Protected against access to hazardous parts with a tool
switching-device vessels under
(the access probe of 2.5 mm diameter shall not penetrate)
high voltage
IP 6 5
2018