A Series of Heat Transfer Experiments For The Mechanical Engineering Technology Student
A Series of Heat Transfer Experiments For The Mechanical Engineering Technology Student
A Series of Heat Transfer Experiments For The Mechanical Engineering Technology Student
W.R. Kaminski
Professor and Coordinator
Mechanical Engineering Technology
Central Washington University
Ellensburg, WA 98926
Abstract
A series of five heat transfer experiments that are used to teach the laboratory component for
a Mechanical Engineering Technology (MET) heat transfer course at Central Washington University
(CWU) are presented in this paper. The experiments have been found to be very useful in bridging
the gap between theory and hands-on experience. The experiments that will be described in this
paper are referred to as: (1) Transient Lumped Mass Heat Transfer, (2) Pin Fin Characterization, (3)
Contact Resistance Measurement, (4) Electrically Heated Tube Forced Convection, and (5) Free
Convection From a Vertical Heated Surface.
These experiments have all been built by MET students at a relatively low cost and fully
tested over the last several years. Design details and approximate costs are presented in the paper
so that others may benefit from our experiences. The paper contains a set of test data from each
experiment so that the reader may judge the effectiveness of the experiment. All of the experiments
utilize state-of-the-art instrumentation and data systems, most of which have been donated by local
industry. The students extensively utilize computers for data storage and processing using spread
sheets.
The experience gained at CWU in the use of these experiments has been very positive in
terms of comments and performance by our students, many of which are non-traditional. Heat
transfer at the Engineering Technology level can be difficult to teach, which makes a well thought
out set of laboratory experiments crucial to the successful learning of the subject.
Nomenclature
2
A cross-sectional area, in
2
As surface area, in
Bi Biot Number
o
C specific heat, BTU/lbm- F
2
D flow passage diameter, in
2 o
h convective heat transfer coefficient, BTU/sec-in - F
2 o
hc contact resistance coefficient, BTU/sec-in - F
o
k thermal conductivity, BTU/sec-in- F
o
kf thermal conductivity evaluated at the film temperature, BTU/sec-in- F
Page 3.44.1
Introduction
The students normally work in groups of two or three, depending upon the complexity of the
experiment. This pooling of energy and knowledge is beneficial to the student. As in industry, the
team approach is utilized so the student gets accustomed to collective working and thinking. Each
experiment is concluded with a complete lab report which states objectives; lists equipment used;
shows a schematic of the experiment, and contains data tables, sample calculations, conclusions,
and recommendations. The recommendations are passed on to the next class who then act on the
recommendations.
This paper describes a series of five heat transfer laboratory experiments that the student
performs, which supports the course syllabus.
The purpose of this experiment is to demonstrate unsteady heat transfer to a lumped mass
utilizing simple geometries. Both experimental and analytical approaches are explored. Two masses
are used, one an aluminum cube and the other a brass cylinder as shown in Figure 1. Dimensional
data are included in Figure 1. Two different thermocouples, K and J types are used so that the
student can experience this variation. The thermocouple junction is located at the center of the
o
masses and held in place by using high temperature (500 F) epoxy.
Page 3.44.2
Aluminum: Brass:
S = 0.750 i n D = 0.750 in
3 3
V = 0.422 in V = 0.361 in
2 2
As = 3.357 in A, = 2.807 in
The experimental apparatus includes a boiling water and ice water baths, instrumented
masses, boiling and ice water thermocouples, and a data logger such as a Fluke Hydra Data
Acquisition Unit (Model 2629 A) that we use or alternatively, a strip chart recorder. The mass, a cube
or cylinder, is stabilized at room temperature. The room, boiling water bath and ice water bath
temperatures are continuously recorded. The mass is then immersed into the boiling water and left
there so that the mass’s temperature can be recorded as a function of time. After the mass has
stabilized in the boiling water, the cube is immersed into the ice water and a measurement of the
temperature response of the mass is made. The data is plotted and an analysis is performed to
determine the time constant and heat transfer coefficient. Knowledge of the time constant enables
an analytical curve of mass temperature versus time to be drawn and compared to the measured
temperature response.
Prior to any transient analysis, the Biot Number using equation (1), must be calculated. If Bi
< 0.1, then the simple lumped mass analysis applies and equations (2) and (3) are valid.
Page 3.44.3
COOLING
The measured and calculated curves are much more in agreement for the case of heating rather than
for cooling. The magnitude of the convective heat transfer coefficients is high which suggests very
strong convection or possibly moderate boiling. The data for the brass cylinder was qualitatively
similar to the data for the aluminum cube.
If a thermocouple readout and strip chart recorder are available, the cost of duplicating this
experiment is approximately $50.
Time(Seconds)
Page 3.44.4
Figure 3, Comparison of thermal response for heating and cooling of an aluminum cube.
Lab 2. Pin Fin Characterization
Heat transfer from heat exchanger surfaces can be effectively augmented by using fins. Many
industrial applications abound. Although the pin fin is not as routinely used as other fin geometries,
it does represent a simple configuration to analyze.
The objective of this experiment is to develop an understanding of the thermal performance of a pin
tin by performing an experimental and analytical study of several pin fin geometries. Figure 4 shows
three fin configurations that were built and tested. Each fin was made from 1050-O aluminum stock
and instrumented with 5 thermocouples starting with a base thermocouple and progressing outward
toward the tip with the last thermocouple 0.200 in. from the tip.
0.06
As shown in Figure 5, the fins were installed just inside of the exit plane of a 3 in. x 4 in. wind
tunnel that was constructed of sheet metal by the students. The wind tunnel was driven by a scrapped-
out 1/4 hp fan. The flow was straightened by utilizing a rectangular bundle of plastic drinking straws
Page 3.44.5
positioned at the midpoint of the duct. Heat was supplied to the fin base by an electric heater which
was insulated from the environment to reduce the heat loss. The 5 “K’ type thermocouples were
connected to a Fluke Hydra data logger for data acquisition and recording.
The average velocity of the wind tunnel was measured by a Davis Instruments, Turbo Meter, wind
speed indicator. These measurements were also verified by traversing a pitot tube across the exit plane
of the wind tunnel.
The lengthwise variation in fin temperature is shown in figure 6 for the circular, rectangular,
and triangular pin fins. Data from the circular and rectangular pin fins indicates only minor
differences in temperature profiles. However, the triangular pin fin reaches a much lower
temperature at the fin tip. This fact is borne out by data presented in Table 1. The actual and
theoretical efficiencies indicate that the triangular shaped fin is much more efficient than the circular
or rectangular fins. The least efficient fin is the rectangular fin. Qualitatively, the actual and
theoretical fin efficiencies are similar. The actual fin efficiency was calculated by ratioing the actual
fin heat transfer to the maximum heat transfer’. The actual fin heat transfer was determined by
calculating the temperature gradient between the fin base thermocouple and the first thermocouple
just past the base and using the Fourier Law of conduction. The maximum heat transfer was
calculated using Newton’s equation for cooling by convection. A convective heat transfer coefficient
2
was calculated from measured air velocities using a correlation presented by Holman for circular
and non circular cylinders in cross flow. In this analysis it was assumed that the entire fin was
operating at the fin base temperature. Theoretical efficiencies were calculated using charts
3
presented by Cengel .
Page 3.44.6
If two solids, each having plane flat surfaces, are brought in contact with each other by
pressing one surface against the other, the actual direct contact between the two surfaces takes
place at only a limited number of spots. Since the surfaces are not perfectly smooth, there are
pockets or voids present. The voids are filled with the fluid of the surroundings which is usually
air. The heat flowing across the interface takes place by conduction through the fluid in the voids
as well as through those areas that have metal-to-metal contact. Since the thermal conductivity
through the void fluid is less than through the metal, the void fluid acts as a resistance to the heat
flow. The resistance is confined to a very thin layer between the surfaces, thus it is called
thermal contact resistance. Experiments have shown that there exists a steep drop in
temperature across the interface. The magnitude of this thermal resistance depends upon the
surface roughness, type of materials, interface pressure, interface temperature level, and type of
fluid filling the void.
Data from the thermocouples shown in Figure 7 was collected by the Fluke Hydra and
down loaded into a PC spreadsheet (Microsoft Excel). The measured temperatures are shown
graphically in Figure 8. This experiment offers many interesting analyses to be performed. If
one uses the temperature gradient between thermocouple 1 and 3 in conjunction with the Fourier
Page 3.44.7
Law for conduction (equation 7), then a good estimate of heat flux q/A is obtained.
1” DIA. x 6” ALUMINUM TEST RODS
THERMOCOUPLE - 3 PER CYLI
1/4” HOSE MOUNTS
shown in Table 2.
Figure 8. Results from a typical thermal contact resistance experiment.
Interface q/A hc 2 o
2 o
Type (BTU/sec-in ) ( F) (BTU/sec-in - F)
-4
Rough 0.0171 66 3.64x10
-4
Rough/Grease 0.0210 24 4.29x10
-3
Smooth 0.0594 19 2.97x10
The heat transfer behavior of a fluid in forced convection flow can be characterized by
its ability to transfer heat between itself and a solid surface, across a temperature difference. The
conventional relationship used to express heat transfer rate per unit surface area as a function of
the convective heat transfer coefficient and the wall to fluid temperature difference is given by
equation (9). The magnitude of the convective heat transfer coefficient, as defined in equation
(9), is primarily controlled by velocity, properties of the fluid, and geometry of the flow passage.
q w A s = h ( T w - TF ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ( 9 )
compared to that of the tube material. If the heated tube is thermally insulated over its external
surface, nearly all of the heat generated is absorbed by the fluid flowing within the tube. Thus,
measuring the power dissipation provides a direct determination of the total heat flow to the
fluid, as well as the heat flux distribution over the inner surfaces of the tube. Thermocouples
attached to the outer surface of the tube measure temperatures that are readily related to the wall
temperature at the inner surface. Measurement of the inlet fluid temperature, pressure, mass
flowrate, and electrical power dissipated are used to calculate the fluid bulk temperature along
the length of the heated tube and the corresponding convective heat transfer coefficient.
Figure 9 shows a drawing of the electrically heated tube. The tube is made from 316
stainless steel and is 0.250 in. outside diameter with a 0.035 in. wall thickness having a
-6
resistance of 28.3x10 Ohm-inches. Two copper buss bars are clamped to either end of the tube.
HOLD DOW
STRIP
THERMOCOUPLE JUNCTION-SPOT
WELDED OR HIGH TEMPERATURE
EPOXIED
Four 0.062 in. “K” type thermocouples are attached to the outer surface of the tube, and are
spaced at equal distances apart. The tube cross-sectioned view shows how a typical
thermocouple is attached to the tube. The thermocouples can either be spot welded or high
temperature (500 “F) epoxied to the tube. A thin piece of shim stock provides strain relief for the
o
thermocouple which is wrapped 180 around the tube. The assembly is completed when
Page 3.44.10
compression fittings are attached to the ends of the tube and the tube is insulated with fiberglass.
A typical arrangement for the electrically heated tube experiment is shown in figure 10.
Standard pressure gages are used to measure P,, P,, and P,. Closed junction thermocouple
probes are used to measure inlet and outlet temperatures. Electrical power from an AC arc
welder is determined by measuring current and voltage. It should be emphasized that an AC
power source is preferred over a DC source primarily because the thermocouples may be
directly attached to the tube wall. If a DC source was used then the thermocouples would have
to be electrically insulated from the tube surface otherwise each thermocouple would have a
DC voltage proportional to the distance from the ground potential buss bar. There are other
secondary reasons for this choice.
Typical results of an experiment performed with air flowing through the electrically
o
heat tube apparatus is described here. The inlet conditions were kept constant at 75 F, a
POWER SUPPLY
(AC ARC WELDER)
pressure of 94 psia and an air flow rate of 0.045 lb m/min. The Reynolds Number was turbulent
for this experiment and calculated to range from approximately 4046 to 5128 depending upon
power level and location within the tube. The electrical power was varied from 0 to 51.5 Watts
with an electrical to thermal conversion efficiency of 81.5%. This efficiency is lower than a
desired 90% or better. Figure 11 is a typical plot of the wall and fluid bulk temperature
distribution with distance in the flow direction for the 51.5 Watt test point. The plotted points
refer to the thermocouple measurements for wall temperature whereas, the fluid temperatures
are calculated from know inlet and exit temperature measurements and the fact that electrical
heating produces a constant heat flow with length. The fact that the fluid and wall temperatures
vary linearly with distance in the flow direction with a constant temperature difference is an
indication of constant heat flux heating.
transfer to the student It should be noted that a liquid such as water could also be tested. In
Figure 11. Measured fluid and wall temperatures for heated tube experiment
this case, a short section of non-conducting tubing should be used at the inlet to isolate the
electrically heated tube from the remainder of the fluid system.
This experiment could be duplicated for about $800 including the purchase of a small
arc welding machine.
0.8
h=0.023(Re f) (Prf)kf(l/D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (10)
small, many devices depend largely on this mode of heat transfer for cooling such as electrical
furnaces, electrical transmission lines, transformers, and some electronic components.
Position measurements normal to the hot plate are read accurately using a micrometer. The
thermal boundary was determined by measuring the temperature of the air surrounding the hot
0.060 K TYPE
plate. The thermocouple probe was translated horizontally, starting at the hot plate and
progressively moving outwardly normal to the plate. The edge of the thermal boundary layer
o
was defined as the location where the air temperature was within 2 F of the undisturbed air.
The temperatures were recorded by a Fluke Thermocouple Thermometer.
The metal wall temperature was measured by two independent techniques. Initially, the
entire hot surface was thermally mapped by measuring the surface temperature with an infrared
thermometer for three levels of hot plate settings. A Kane-May Infratrace 1500 infrared
thermometer was used. The second technique involved using the thermocouple probe to
touch a desired spot on the hot plate surface. This technique was less accurate than using
the infrared thermometer probe due to conduction heat losses to the probe body. Alternatively
Page 3.44.13
the Infratrace 1500 integrated temperatures over a spot of approximately 0.5 in. in diameter.
0.5
Figure 14. Temperature profile normal to hot plate at centerline, 3.5 inches from bottom edge
7
convection about a vertical, heated plate’, a length Grashof Number of 4.420x10 was
calculated resulting in length Nussult Number of 43.89 and a predicted heat transfer
2 o
coefficient of 1.57 Btu/hr-ft - F. The measured and predicted heat transfer coefficients are
Page 3.44.14
close enough to give the student an appreciation for the mechanisms and theory involved in
natural convection.
The experiments described in this paper were found to be both challenging and
interesting to the students based on comments and student course reviews. The experiments
were found to significantly contribute to the understanding heat transfer and supported the
basic framework of the Mechanical Engineering Technology curriculum.
Acknowledgments
The author wishes to thank all of the Mechanical Engineering Technology students, past
and present, at Central Washington University for their enthusiastic participation in the heat
transfer experiments described in this paper.
References
1. Cengel, Younis, A., Heat Transfer, A Practical Approach, 1st ed., pp 177- 184 WCB/McGraw Hill,
Boston, MA, 1998.
2. Holman, J. P., Heat Transfer, 8th ed., pp 302-307, McGraw Hill Companies, Inc., New York, NY,
1997.
3. Cengel, Younis, A., Heat Transfer. A Practical Approach, 1st ed., p 185, WCB/McGraw Hill, Boston,
MA, 1998.
4. Holman, J. P., Heat Transfer, 8th ed., pp 56-59, McGraw Hill Companies, Inc., New York, NY,
1997.
5. Holman, J. P., Heat Transfer, 8th ed., pp 336-346, McGraw Hill Companies, Inc., New York, NY,
1997.
Page 3.44.15