So-54sr 101 Rek
So-54sr 101 Rek
So-54sr 101 Rek
control buttons
LED signalization of
device operation status
touch screen
14
218
analog inputs
power supply
www.mikronika.pl
Application
The SO-54SR-1xx-REK controller installed in a control unit.
AR automation switch
Features
Protection functions
No. ABBREVIATION NAME SYMBOL ANSI CODE
Automation functions
No. ABBREVIATION NAME
1 AR Automatic Reclosing
2 IFPT Instantaneous Fault Protection Tripping
3 I2H Interlock from magnetic current basing on 2nd harmonic
www.mikronika.pl
Telemetry functions
ELEMENTS SENT TO A DISPATCH CENTRE COMMANDS REALIZED FROM A DISPATCH CENTRE
binary signals from objects with read precision 1 ms circuit breaker control ON/OFF
values of phase currents changes of protection setting banks
values of phase and/or interphase voltages protections and automation enabling/disabling
value of 3I0 current triggering reset
active and reactive power, network frequency object state checking
Recording functions
< event log
< multi-channel disturbance recorder, which enables recording oscillograms of measured and calculated values
as well as binary events and saving in COMTRADE files
Data from the recorder and the event log is available from the dispatcher panel, pConfig configuration software and
SCADA dispatch system. It may be also automatically transmitted to a central disturbance server.
Communication
For communication with the controller, in the standard version, external communication modules are applied,
equipped with a GRPS/UMTS/LTE-APN radio connection, supporting DNP 3.0 protocols through TCP/IP or UDP and
PN-EN 60870-5-104. Communication modules are able to connect to an external TETRA terminal.
Other communication protocols may be also applied, e.g. PN-EN 60870-5-101, PN-EN 60870-5-103, Modbus, etc.,
using serial connections. The device may be also applied as a component of a distributed substation telemetry
system based on the PN-EN 61850 communication standard.
Measurements
The controller is manufactured in versions designed for measuring currents from xxx/1A, xxx/5A current transform-
ers and Rogowski coils. According to the needs, phase and interphase voltages may be measured from outputs of
voltage transformers or capacitor (reactance) dividers.
Technical data
PARAMETER VALUE
supply voltage 24V AC/DC
maximal power consumption 14W
current input constant capacity 2x In
current input thermal capacity 50 x In in time 1s
current input dynamic capacity 2,5 x 50 x In in time t<150ms
current module starting value errors <2,5%
voltage module starting value errors <2,5%
time meter starting value errors <0,1%
Specification of versions
PARAMETER SO-54SR-101-REK SO-54SR-111-REK SO-54SR-131-REK SO-54SR-141-REK
WE-A 3x 4 WE-U; Uwe=5V RMS 3x WE-I CR, 6x WE-U DP 4x WE-I PP, 6x WE-U DP 4x WE-I PP, 4x WE-U PN
WE-B 2x 8 WE-B; 24V DC 2x 8 WE-B; 24V DC 2x 8 WE-B; 24V DC 2x 8 WE-B; 24V DC
WY-B 4x WY-B; 0,25A/220V DC 4x WY-B; 0,25A/220V DC 4x WY-B; 0,25A/220V DC 4x WY-B; 0,25A/220V DC
DK/F/SO54SR/EN/1216/1.4