Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Medium Voltage Solid State OEM Soft Starter: Installation & Operation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88

2.3 - 7.

2kV

Medium Voltage
Solid State OEM Soft Starter

INSTALLATION & OPERATION


MANUAL

D – REVIEWED FOR INFORMATION ONLY ®

Authorization to proceed does not relieve Contractor/Supplier of its responsibility


or liability under the Contract and or Purchase Order.
By Alejandro Soto O. (alejandro.soto@fluor.com) at 6:34 pm, 03 Jul 2012

DEH41021
00011601MN
-1-
2.3 - 7.2kV
1.1 Overview
2.3 - 7.2kV
Chapter 1: Introduction ...................................................................................................... 1
Medium Voltage Solid 1.2 Specifications
State Soft Starters 1.3 Design Features
2.3 - 7.2KV 1.4 Theory of Operation
1.5 General Protection
1.6 Thermal Overload Protection
Installation & 1.7 Firing Circuit
Operation Manual 1.8 Electronics

Chapter 2: Connections ...................................................................................................... 9


2.1 Warnings
2.2 Control Connections
2.3 Reference Section with RTD, Power, Communications and CPU board drawings

Chapter 3: Start-Up .......................................................................................................... 17


3.1 Introduction
3.2 Acceleration Adjustments
3.3 Deceleration Adjustments
3.4 Sequence of Normal Operation
3.5 Emergency Bypass Operation

Chapter 4: User Interface and Menu Navigation ............................................................. 21


4.1 Keypad/Operator Interface
4.2 Menu Navigation

Chapter 5: Setpoint Programming .................................................................................. 24


5 .1 Setpoints Page List
5.2 Setpoint Menu
SP.1 Basic Configuration ................................................................................................ 34
SP.2 Starter Configuration ............................................................................................... 35
SP.3 Phase & Ground Settings ....................................................................................... 38
SP.4 Relay Assignment ................................................................................................... 41
SP.5 Relay Configuration ............................................................................................... 43
SP.6 I/O Configuration .................................................................................................... 44
SP.7 Custom Acceleration Curve ................................................................................... 47
SP.8 Overload Curve Configuration ............................................................................... 50
SP.9 RTD Option Configuration ...................................................................................... 51
SP.10 Set Password ....................................................................................................... 53
SP.11 Communications .................................................................................................... 54
SP.12 System Setpoints .................................................................................................. 55
SP.13 Calibration & Service ............................................................................................ 57

Chapter 6: Metering Pages .............................................................................................. 58


6 .1 Metering Page List & Menu

Chapter 7: Maintenance and Troubleshooting ................................................................ 68


7.1 Failure Analysis
7.2 Typical Block Diagram
7.3 Overload Curve Definition
7.4 TCB Diagram
7.5 Typical Wiring Diagram
7.6 Spare Parts List
7.7 Instructions for Stack Replacement
7.8 Instructions for Low Voltage Test
2.3 - 7.2kV

Reference chart
Table or Page Table or Page
Section Section
Drawing Number Drawing Number
1.2 Specifications 1-3 5.2 Overcurrent Trip Delay Graph 39
Setpoint Page 4 Displays - Relay
1.3 Unit PIV Ratings 3 5.2 41
Assignment
Setpoint Page 5 Displays - Relay
1.8 Keypad Operator Interface 8 5.2 43
Configuration
Setpoint Page 6 Displays - User I/O
2.2 TCB Diagram 10 5.2 44 - 46
Configuration
Setpoint Page 7 Displays - Custom
2.2 TB1 10 5.2 47 - 49
Acceleration Curve
Setpoint Page 8 Displays - Overload
2.2 TB2 10 5.2 50
Curve Configuration
Setpoint Page 9 Displays - RTD Option
2.2 TB3 11 5.2 51
Configuration
Setpoint Page 10 Displays - Set
2.2 TB4 11 5.2 53
Password
Setpoint Page 11 Displays -
2.2 Jumper Selections 12 5.2 54
Communications
Setpoint Page 12 Displays - System
2.2 Switch Positions 12 5.2 55
Setpoints
Setpoint Page 13 Displays - Calibration
2.3 Optional RTD Board 13 5.2 57
& Service
2.3 Communications Board 14 6.1 Metering Page List 58 - 59
Communications Board Connections:
2.3 14 6.2 Metering Menu 60
RS485 and RS422
Metering Page 1 Displays - Metering
2.3 Power Board 15 6.2 61
Data

2.3 Power Board Connections 15 6.2 Metering Page 2 Displays - Metering 62

2.3 CPU Board Connections 16 6.2 Metering Page 3 Displays - RTD Values 63

3.2 Acceleration Adjustments 17 6.2 Metering Page 4 Displays - Status 64

Metering Page 5 Displays - Event


3.3 Coasting Stop 18 6.2 65
Recorder
3.3 Accel and Decel Modes 18 6.2 Metering Page 6 Displays - Last Trip 66
3.4 Sequence of Operations 19 6.2 Metering Page 7 Displays - Statistics 67
4.1 Keypad Operator Interface 21 7.1 Troubleshooting Charts 68 - 70
4.1 Programming the Operator Interface 21 7.1 SCR Testing Procedure 70
4.2 Menu Navigation 22 7.2 Typical Block Diagram 71
4.2 Changing Setpoints Example 23 7.3 Overload Curve Definition 72
5.1 Setpoints Page List 24 - 32 7.4 TCB Diagram 73
5.2 Setpoint Menu 33 7.5 Typical Wiring Diagram 74
Setpoint Page 1 Displays - Basic
5.2 34 7.6 Spare Parts List Charts 76 - 77
Configuration
5.2 Overload Class Trip Curves 34 7.6 PCB Mounting Order 77
Setpoint Page 2 Displays - Starter
5.2 35 7.7 Stack replacement and PCB mounting 78
Configuration
5.2 Jog/Voltage Ramp 36 7.7 Connections for Low Voltage 82
Setpoint Page 3 Displays - Phase &
5.2 38 - 39 7.8 Waveform Diagram 84
Ground Settings
2.3 - 7.2kV

Chapter 1 - Introduction
This chapter is an introduction to the reduced voltage solid state starter for
medium voltage AC motors. It describes the basic configuration, operation and
unit features. It is highly recommended that new users read this section
thoroughly to gain a basic understanding of the starter system before attempting
to start up a unit.

1.1 Overview
The standard soft starter panel is an SCR-based motor controller designed for
the starting, protection and control of AC medium voltage motors. It contains
the SCR stack assemblies, fiber optic connections and low voltage control
circuitry ready to be interfaced with an enclosure and the necessary equip-
ment to create a complete Class E2 medium voltage motor soft starter.

1.2 Specifications

125% - Continuous
Unit Overload Capacity 500% - 60 seconds
(Percent of motor FLA) 600% - 30 seconds
1 Cycle: up to 14 x FLA (internally protected by the programmable short circuit)

Frequency 50 or 60Hz, +2Hz hardware selectable


Power Circuit 6 SCRs, 12 SCRs or 18 SCRs (model dependent)
SCR Peak Inverse
6500V - 21000V (model dependent see Table 1)
Voltage Ratings
Phase Insensitivity User selectable phase sequence detection
Transient Voltage Protection RC snubber dv/dt networks (one per SCR module)
Enclosed units: 0° to 40°C (32° to 104°F) (optional - 20° to 50° C with heaters)
5 - 95% relative humidity
Ambient Condition Design
0 - 3300 ft. (1000m) above sea level without derating
(Ratings for ambient conditions external to unit)
Control 2 or 3 wire 120VAC (customer supplied)
Multiple: Form C (contacts), rated 4 Amps, 250VAC max.
Auxiliary Contacts 8 Relays (4 programmable) - Form C contact
Fault Indicator: Form C contact
BIL Rating 2300V - 7200V 60kV
Approvals UL Recognized, Canadian UL Recognized

-1-
2.3 - 7.2kV
1.2 Specifications (continued)

Advanced Motor Protection

Two Stage Electronic Starting: Programmable for Class 5 through 30


Overload Curves Run: Programmable for Class 5 through 30 when "At-Speed" is detected.
Overload Reset Manual (default) or automatic
Overload circuit retains thermal condition of the motor regardless of control
Retentive Thermal Memory
power status. Unit uses real time clock to adjust for off time.
Overload will not reset until thermal capacity available in the motor is enough for
Dynamic Reset Capacity a successful restart. Starter learns and retains this information by monitoring
previous successful starts.

Phase Current Imbalance Imbalance Trip Level: 5 - 30% current difference between any two phases
Protection Imbalance Trip Delay: 1 - 20 seconds
Trip Level: 100 - 300% of motor FLA
Over Current Protection
Trip Delay: 1 - 20 seconds
Under Current Trip Level: 10 - 90 % of motor FLA
Load Loss Trip Protection
Under Current Trip Delay: 1 - 60 seconds
Coast Down (Back Spin)
Coast Down Time Range: 1 - 60 minutes
Lockout Timer
Range: 1 - 6 successful starts per hour
Starts-per-hour Lockout Timer
Time between starts: 1 - 60 minutes between start attempts
Programmable Outputs
Type / Rating Form C (DPDT), Rated 4 amps 240 VAC max, (960 VA)
Run Indication Programmable
At Speed Indication Programmable
Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Acceleration Adjustments
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 600% (VR or CR)
4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Settings Dual Ramp Control: Ramp 1 = Default
Ramp 2 = selectable via dry contact input

Begin Decel Level: 0 - 100% of line voltage


Deceleration Adjustments Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Jog Settings Voltage Jog: 5 - 75%
Kick Voltage: 10 - 100%
Kick Start Settings
Kick Time: 0.1 - 2 seconds
Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload,
Fault Display
Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Lockout Display Coast Down Time, Starts Per Hour, Time Between Starts, and Any Lockout
Event History

Data includes cause of event, time, date, voltage, power factor and current for
Up to 60 Events
each phase and ground fault current at time of event

-2-
2.3 - 7.2kV

1.2 Specifications (continued)


Metering Functions
Motor Load Percent of FLA
Current Data A, B, C Phase Current, Avg Current, Ground Fault (option)
Thermal Data Remaining thermal register; thermal capacity to start
Avg Start Time, Avg Start Current, Measured Capacity to start, time since last
Start Data
start
RTD Data (Option) Temperature readings from up to 12 RTDs (up to 6 stator RTDs)
Voltage Metering kW, kVAR, PF, kWH
Serial Communications
Protocol Modbus RTU
Signal RS-485, RS-422 or RS232
Network Up to 247 devices per mode
Functionality Full operation, status view, and programming via communications port
Operator Interface
LCD Readout Alpha numeric LCD display
Keypad 8 function keys with tactile feedback
Status Indicators 12 LEDs include Power, Run, Alarm, Trip, Aux Relays
Up to 1000 circuit-feet from chassis (use twisted, shielded wire &
Remote Mount Capability
power source)
Clock and Memory
Operating Memory SRAM loaded from EEPROM at initialization
Factory Default Storage Flash EPROM, field replaceable
Customer Settings and Status Non-volatile EEPROM, no battery backup necessary
Real Time Clock Lithium ion battery for clock memory only

1.3 Design Features


The standard soft start panel has the following features: 200 & 400 Ampere Units
Total
Series
• SCR Power Modules: For each phase, the SCRs are Voltage Number PIV Rating
Pairs
matched devices arranged in inverse parallel pairs and in of SCRs
series strings as indicated in the chart to facilitate sufficient 2300 V 0 6 6500 V
Peak Inverse Voltage ratings for the applicable supply 3300 / 4160 V 2 12 13000 V
voltage. 6000 - 7200 V 3 18 19500 V

600 Ampere Units


• RC Snubber Networks: provide Transient Voltage Protec-
tion for SCR Power Modules in each phase to avoid dv/dt Total
Series
damage. Voltage Number PIV Rating
Pairs
of SCRs
2300 V 2 12 7000 V
• Firing Circuit: The SCRs are gated (turned on) using a
3300 / 4160 V 4 24 14000 V
Sustained Pulse Firing Circuit. This circuitry is amplified and
6000 - 7200 V 6 36 21000 V
isolated from the control voltage by means of fiber optics and
ring transformers.
Unit PIV Ratings
Table 1

1.4 Theory of Operation


The power of the soft starter is in the CPU, a microprocessor based protection and
control system for the motor and starter assembly. The CPU uses Phase Angle
Firing of the SCRs to apply a reduced voltage to the motor, and then slowly and
gently increases torque through control of the voltage and current until the motor
accelerates to full speed. This starting method lowers the starting current of the
motor, reducing electrical stresses on the power system and motor. It also reduces
peak starting torque stresses on both the motor and load mechanical components,
promoting longer service life and less downtime.
-3-
2.3 - 7.2kV

Acceleration: The soft starter comes standard with several methods of


accelerating the motor so that it can be programmed to match almost any
industrial AC motor application.

The factory default setting applies a Voltage Ramp with Current Limit as this
has been proven the most reliable starting method for the vast majority of
applications. Using this starting method, the Initial Torque setting applies just
enough voltage to the motor to cause the motor shaft to begin turning. This
voltage is then gradually increased over time (as per the Ramp Time setting)
until one of three things occur: the motor accelerates to full speed, the Ramp
Time expires or a Current Limit setting is reached.

If the motor accelerates to full speed before the ramp time setting has ex-
pired, an automatic Anti-Oscillation feature will override the remaining ramp
time and full voltage will be applied. This will prevent any surging or pulsation
in the motor torque, which might otherwise occur due to the load not being
fully coupled to the motor when operating at reduced voltage and torque
levels.

If the motor has not reached full speed at the end of the ramp time setting, the
current limit setting will proportionally control the maximum output torque.
Feedback sensors in the soft starter provide protection from a stall condition,
an overload condition or excessive acceleration time.

The Current Limit feature is provided to accommodate installations where


there is limited power available (for example, on-site generator power or utility
lines with limited capacity). The torque is increased until the motor current
reaches the pre-set Current Limit point and it is then held at that level. Current
Limit overrides the ramp time setting so if the motor has not accelerated to full
speed under the Current Limit setting, the current remains limited for as long
as it takes the motor to accelerate to full speed.

When the motor reaches full speed and the current drops to running levels,
the soft starter detects an At-Speed condition and closes the Bypass Contac-
tor. The Bypass Contactor serves to shunt power around the SCR stack
assemblies to prevent heat build-up in the starter enclosure due to the slight
voltage drop across the SCRs. At this point, the soft starter has the motor
operating at full voltage, just as any other starter would.

Other starting methods available to the soft starter are:

· Current Ramp: uses a closed current feedback PID loop to provide a linear
torque increase up to a Maximum Current level.

· Constant Current: current is immediately increased to the Current Limit point


and held there until the motor reaches full speed.

· Custom Curve: gives the user the ability to plot torque and time points on a
graph. The soft starter will then accelerate the motor following these points.

· Tachometer Input: uses 4-20mA monitoring signal from the motor or load
shaft.

Deceleration: the soft starter provides the user with the option of having the
load coast to a stop or of controlling the deceleration by slowly reducing the
voltage to the motor upon initiating a stop command. The Decel feature is the
opposite of DC injection braking in that the motor will actually take longer to
come to a stop than if allowed to coast to a stop. The most common applica-
tion for the Decel feature is pumping applications where a controlled stop
prevents water hammer and mechanical damage to the system.
-4-
2.3 - 7.2kV

1.5 General Protection


Operation of the soft starter can be divided into 4 modes: Ready, Start, Run and
Stop. The CPU provides motor and load protection in all four modes. Additional
details on each protection feature can be found in later chapters.

Ready Mode: In this mode, control and line power are applied and the starter
is ready for a start command. Protection during this mode includes the
monitoring of current for leakage through multiple shorted SCRs or welded
contacts on the Bypass Contactor. Other protection features in effect are:

· Starter SCR Temperature


· Shorted SCR
· Blown Fuse Indication
· Phase Reversal (if enabled)
· Line Frequency Trip Window
· External Input Faults

Note: The “Programming Mode” can only be entered from the Ready Mode.
During programming, all protection features and start command are disabled.

Start Mode: These additional protection functions are enabled when the soft
starter receives a valid Start command:

· Phase Reversal (if enabled)


· Start Curve
· Acceleration Timer
· Phase Imbalance
· Short Circuit / Load Pre-check
· Ground Fault (Optional)
· External Input Faults
· Accumulated Starting FLA Units
· Overload Protection
· Thermal Capacity

Note: Shorted SCR and Shunt Trip protection are not in effect once the soft
starter goes into the Start Mode.

Run Mode: The soft starter enters the Run Mode when it reaches full output
voltage and the motor current drops below the FLA setting (motor nameplate
FLA times the service factor) for a pre-determined period of time. During the
Run Mode these additional protection features are enabled:

· Running Overload Curve


· Phase Loss
· Under Current / Load Loss
· Over Current / Electronic Shear Pin (Jam protection)
· External Input Faults

Stop Mode: Once a Stop command has been given, the unit protection
features change depending on which Stop Mode is selected.

· Decel Mode: retains all protection features of the Run Mode. At the end of
Decel, the motor will be stopped and the protection features change as
indicated below.
· Coast-To-Stop Mode: power is immediately removed from the motor and the
soft starter returns to the Ready Mode.
· Coast-Down / Back Spin Timer
· Starts-per-Hour
· Time Between Starts
· External Input Faults
-5-
2.3 - 7.2kV

1.6 Thermal Overload Protection


The soft starter plays an important role in the protection of your motor in that it
monitors the motor for excessive thermal conditions due to starting, running or
even ambient conditions. The soft starter has a Dynamic Thermal Register system
in the CPU that provides a mathematical representation of the thermal state of the
motor. This thermal state information is kept in memory and is monitored for
excesses in both value and rate of change. Input is derived from current
imbalances and (optional) RTD measurements making it dynamic to all processes
involving the motor. The soft starter monitors these conditions separately during
Start and Run modes to provide proper thermal overload protection at all times.

Start Mode overload protection is selectable using one of three methods:

· Basic Protection: I2t data is accumulated and plotted based on an Overload


Curve selected in programming. This is programmed per NEMA Class 5-30
standard curves and is based on the Locked Rotor Current (from the motor
nameplate) as programmed into the soft starter.

· Measured Start Capacity: the user enters a measured amount of thermal


capacity from a pre-selected successful start as a setpoint to the Thermal
Register for the soft starter to follow.

· Learned Curve Protection: the user sets the soft starter to the “LEARN” mode
and starts the motor under normal starting conditions. The CPU then samples
and records 100 data points during the start curve, analyzes them and creates
a graphical representation in memory. The soft starter is then switched to Curve
Follow protection mode and monitors motor performance against this curve.
This feature is especially useful in initial commissioning tests to record a base
line performance sample (in this case, it is not necessarily used for motor
protection).

Run Mode overload protection is initiated when the soft starter determines
that the motor is At-Speed. Overload Protection is initiated when the motor
RMS current rises above a “pick-up point” (as determined by the motor
nameplate FLA and service factor). Run mode protection is provided by the CPU
monitoring the Dynamic Thermal Register. Data for the Dynamic Thermal
Register is accumulated from I2t calculations and motor cooling rates. A trip
occurs when the register reaches 100% as determined by the selected
Overload Protection Curve (NEMA Class 5-30 standard curves) and is based
on the programmed Locked Rotor Current indicated on the motor nameplate.
The Dynamic Thermal Register is altered, or “biased”, by the following condi-
tions:

· Current Imbalance: will bias the register higher to account for additional
motor heating during a current imbalance condition.

· Normal Cooling: provided when the motor current drops below the pick-up
point or the motor is off line. The cooling rate is lower for motors that are off-
line (such as after a trip) since cooling fans are also inoperative.

· RTD Input: (requires the optional RTD monitor card): will bias the register in
either direction based on real-time input of the motor, bearing and even
ambient temperature conditions.

· Dynamic Reset is another feature that adds reliability and consistency to


the performance of the soft starter. If a motor overload condition occurs and
the soft starter trips, it cannot be reset until sufficient cool down time has
elapsed. The cool down time is biased by RTD measurements when they are
used. Otherwise, the cool down time is determined by the thermal state of
the motor when the starter tripped.
-6-
2.3 - 7.2kV

· Retentive Memory provides continuous overload protection and real time


reset even if power is lost. Upon restoration of power, the soft starter will
read the Real Time Clock and adjust the thermal register to display what
would be the true (or real) elapsed time.

· Learned Reset Capacity is a feature that is unique to the soft starter. By


sampling the amount of thermal capacity used in the previous three starts,
the soft starter will not allow a reset until a sufficient amount of thermal
capacity has been regained in the motor. This prevents nuisance tripping and
insures that unsuccessful start attempts where current is not present (which
would otherwise use up the starts-per-hour capacity of the motor) are not
counted.

1.7 Firing Circuit


The SCR gate firing circuit is critical to performance and stability of the system.
The soft starter firing circuit includes several unique features which enhance the
ruggedness, noise immunity and flexibility for maximized performance. This
performance is attained without the need for reactors or field installed devices used
in other systems, regardless of conditions (line impedance, short circuit capacity or
switching transients). These features include:

Auto Synchronizing of the gate timing pulses matches each phase firing
angle to their respective phases. The soft starter actively tracks minor shifts
in the line frequency, avoiding nuisance tripping that may happen with
conventional gate firing systems. This is especially useful on portable or
backup generator supplies, allowing the soft starter to be used confidently in
applications that have unstable power.

Sustained Pulse firing keeps the firing signal active for 270 electrical degrees,
ensuring that the DC gate pulse causes the SCR to fire even if line noise is
present at a critical moment. This provides the soft starter with superior
noise immunity and protects against misfiring, enhancing the system reliability.

Closed Loop Firing Control is a method of balancing the SCR firing pattern
based on the desired output. The CPU uses feedback signals from both the
output current and voltage providing smooth output and preventing imbalances
during ramping which prevents unnecessary motor heating.

Transformer Isolation of the firing signals prevents interference from line


noise and EMI/RFI signals that may be present. Specially designed 120V
3 phase isolation transformers provide potential measurement, firing board
power and gate power systems while being isolated from the line voltage.
High isolation Ring Transformers are used to step this down to 28VAC for the
Sustained Pulse firing circuit, providing further isolation for the SCR gates.

Fiber Optic Isolation is provided for all signal interfaces between the
Medium Voltage and Low Voltage systems. Even the current signals from
CTs are converted to fiber optic signals for maximum isolation and safety.

1.8 Electronics
The soft starter electronics systems are divided into two categories, Low Voltage
and Medium Voltage, based solely on where they are located in the starter
structure.

Low Voltage electronics include the Keypad Operator Interface, the CPU and
Main Power PC boards are located in an isolated Low Voltage Compartment
of the enclosure.

-7-
2.3 - 7.2kV

· Keypad Operator Interface: a 2 line x 20 character LCD display with


backlighting for low ambient conditions. The display read-out is in truncated
English and can show multiple data points in each screen. Also included are
12 LED indicators, which include Power, Run, Alarm, Trip and the status of
the 8 Aux. Relays. It communicates to the CPU via a serial link and, if
necessary, can be remotely mounted up to a circuit distance of 1000’ from
the soft starter.

· CPU Board: where the microprocessor and communications co-processor


reside. It is attached to the main power board, and communicates to it and the
Keypad Operator Interface via serial links. The CPU determines operating
functions, stores user programming and acts upon feedback signals for faults,
metering and historical data. This board also contains the flash EEPROM
and SRAM memory, as well as the Analog I/O and terminations.

· Main Power Board: is also referred to as the Firing Board. It contains the Keypad Operator Interface
Digital I/O relays and interfaces to the TCB board (see below) for user inter-
face. It also controls the sequencing of the Isolation and Bypass contactors
with the SCR firing. This board generates all firing signals for the SCR stacks
and receives feedback signals from fiber optic transmitters. It converts analog
levels to digital signals for the CPU. These firing pulses are via fiber optic
signals to isolate them from the Medium Voltage environment.

Control Electronics are located in the medium voltage and low voltage sections
of the soft starter. The main line power must be disconnected before these
electronics can be accessed.

· TCB (Terminal and Control Board): is the user connection interface board. It
is located in the Medium Voltage section in order to satisfy UL termination
requirements, but does not actually connect directly to the medium voltage
components other than the contactor coils. This board contains the user
terminal blocks, output relays (duplicated), inputs and control power connec-
tions. It also contains additional timed relays for interfacing with Power
Factor Correction contactors (if used) and other external devices. Please
note Power Factor Capacitor warnings in Section 2.1.

· Gate Drive Boards: located directly on the SCR stacks. These boards
communicate to the Main Power board via fiber optic cables. They amplify
the gate pulse signals with power from the Ring Transformers to create the
Sustained Pulse Firing of the SCRs. There is one Gate Drive board for each
pair of SCRs in each stack.

· Temp / CT Boards are attached to the Gate Drive boards on the SCR
stacks and provide the heat sink temperature and current signals back to the
Main Power Board via fiber optic cables.

· MOV Boards are attached to standoffs mounted on the SCR heat sinks and
are mounted directly below the Gate Drive boards. The MOV boards are used
to protect the gate/cathode section of the SCRs.

· DV/DT Boards are also attached to standoffs mounted on the SCR heat
sinks and are mounted below the MOV boards. The DV/DT boards are used
to reduce voltage transients across the stack assemblies.

-8-
2.3 - 7.2kV

Chapter 2 - Connections
2.1 Warnings:

DANGER
HAZARDOUS VOLTAGE
Disconnect all power supplying this equipment prior
to working on it.

Failure to follow this instruction will result in death


or serious injury.

! WARNING
SAFETY HAZARD
Do not bypass electrical or mechanical interlocks.

Failure to follow this instruction will cause severe


equipment damage, serious injury or death.

Note: Power Factor Capacitors


• Do not install PF capacitors on the load side of the soft
starter.
• If PF capacitors are installed on the line side of the soft
starter either locate the capacitors as far as possible from
the main contactor or use a separate contactor to switch the
capacitors.

! CAUTION
SCR DAMAGE
Do not connect (PFC) capacitors to the load side of
the unit.

Doing so will cause DI/DT damage to the SCRs when


energized.

-9-
2.3 - 7.2kV
Customer Provided
Momentary or Maintained
Start / Stop Switching
Maintained
2.2 Control Connections - TCB (Terminal and Control Board)
START
For a larger view of this picture, see page 73.
Fuses STOP
Momentary
2.2.1 TCB Board F1: Control Fuses for TB1 1 - 9
Part #ACG1A250VAC or equivalent
The TCB board provides interconnections F2: Contactor and relay output fuses
Part #ACG4A250VAC or equivalent
between the main power and CPU boards and F3: TB2 Pin #6
Part #ACG4A250VAC or equivalent

the customer’s control logic connections. It is


a 120 VAC control board with several auxiliary TB9
Aux Start
dry control contacts, built-in time delay circuits

TB2
MB
MVC3 - TCB Output
and emergency bypass functions. It also 120 VAC
Neutral
controls the sequence of the inline isolation
and bypass contactor and provides provisions TB1
T1
for shutdown interlocks. (see section 2.2.2)
Optional
Interlocks
2.2.2 Description of Terminal Connections
TB1 120 VAC
Source

F1

HEATSINK
#1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12
NC C NC C NC C NO AC C NO NC F2
FACTORY WIRED
AC INTER INTER MB DO NOT USE
SOURCE LOCK LOCK STOP START NEUT TB2 F3

Start/Stop Control TB2 Emergency Bypass


Figure 2-1 AUX Contacts

Emergency Bypass/
Start/Stop Control - Terminal Block 1 (TB1) : TB6
Full Voltage Start
• Positions 2-3 and 4-5 have factory jumpers
installed and can be removed for customer’s
DCU CONNECTIONS ONLY

normally closed, dry, shutdown contacts (See


Fig 2-1 above).

FAULT
• Positions 6-7-8 are for either two wire or three-
TB3
wire start/stop logic. Two wire is connected to
positions 6 and 8 with a N.O. dry, maintained

LOCK OUT
start/stop contact. Three wire control connects
to 6 with 7 as the stop push-button, and the
start push-button is connected to 7 and 8. FACTORY WIRED
DO NOT USE
• Positions 10-11-12 are a dry Form C contact. TB7
The contact is an immediate start/stop
contact.
P.F.C. CAP

TB2
TB4

TB8
TIME DELAY

#1 #2 #3 #4 #5 #6 #7 #8 #9 #10
NO O C NO NC S N C NO NC
EMER BYP INTER CUST. POWER DELAYED
SWITCH LOCK OUTPUT START

Emergency Bypass Control


Figure 2-2
TB5
Emergency Bypass Control - Terminal Block 2
(TB2): Figure 2-3
• Positions 1 and 2 are for an emergency
bypass contact. If a dry contact closes
position 1 and 2, this causes the CPU to be
CAUTION
shut off so there is no display. Then when a OVERLOAD PROTECTION LOSS
start is initiated, it pulls in the inline isolation When operating the unit in Emergency Bypass Mode,
contactor which starts the motor across the there is no electronic overload protection.
line. See section 3.5 for more details. External overload protection must be provided for
continued safe operation.

- 10 -
2.3 - 7.2kV

• Positions 3-4-5 are a Form C contact. This is a dry contact that is


initiated by the emergency contact being closed. It provides indication of
the emergency bypass mode.
• Positions 6 and 7 are a customer connection for control power. Position 6
is the 120 VAC supply (400 VA) and position 7 is the return.
• Positions 8-9-10 are a Form C contact. The dry contact is a delayed
start/stop contact. The amount of delay is determined by X1, X2 and SW3
(see “Switch Positions” and “Jumper Selection” on the next page). Note:
Additional Time Delay to SP2 of the CPU programming.

Fault - Terminal Block 3 (TB3): TB3


• Positions 1-2-3 and 4-5-6 are sets of Form C contacts. These are
dry contacts that operate when a blown fuse indication is given or
disconnect is open. #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12
• Positions 7-8-9 and 10-11-12 are sets of Form C contacts. These are C NO NC C NO NC C NO NC C NO NC

fault contacts that change state if any fault condition occurs.


Lockout/Fault Contacts
Figure 2-4
Optional Relay - Terminal 4 (TB4):
• Positions 1-2-3 and 4-5-6 are sets of Form C contacts. These are
auxiliary time delay contacts that will change state (after a delay)
when the Start contact is initiated. X3, X4 and SW4 determine the
amount of delay. (See switch position and Jumper selection on the
following page)
• Positions 7-8-9 and 10-11-12 are sets of Form C contacts. These are
power factor correction capacitor (PFC) contacts to pull in an isolation
contactor for the power factor correction capacitors (if required by the
application). These will change state when the At Speed contact is Time Delay/PFC Cap Contacts
Figure 2-5
initiated. X5, X6 and SW5 determine the amount of delay. (See “Switch
Positions” and “Jumper Selection” on the following page). Note: This delay
is in addition to SP2 of the CPU programming.

Terminal 5 Block (TB5):


RS-485 connections: software required (if wiring distance is >25 ft then
make use of termination resistors as needed). Minimum 22 gauge twisted
pair wiring.

Terminal Block 6 (TB6):


(Factory wired) Main power board connections 1-12

Terminal Block 7 (TB7):


(Factory wired) Main power board connections 13-24

Terminal Block 8 (TB8):


• Positions 1 and 2 accept dry, normally closed contacts from blown fuse
indicators and/or disconnect interlock contact.
• Positions 3 and 4 accept dry, normally closed contacts from an external
overload protection device (required if emergency bypass is used).
• Positions 5 and 6 accept dry, normally closed contact from the bypass
contactor for an At Speed indication. (Factory wired)
• Positions 7 and 8 are wired to the coil of the bypass contactor and
energizes and de-energizes the contactor. (Factory wired)
• Positions 9 and 10 are wired to the coil of the inline isolation contactor
and energizes and de-energizes the contactor.
Note: All customer contacts are 960VA, 120VAC (Max) rated dry contacts.

- 11 -
2.3 - 7.2kV

LEDs provided on the TCB board:


• -12 VDC power supply
• +12 VDC power supply
• Start = start is initiated to TCB board
• Fault = any fault has occurred
• Fuse Blown = disconnect open or blown fuse has activated
• PFC On = Power Factor Correction Capacitor contacts have energized
• Timed Out = Auxiliary time delay contacts have energized

Jumper Selection
For the following, please refer to Figure 2-6

Start Delay
This is a selectable delay period between the initiation of the start command
and when the CPU actually receives the start signal. Selecting Jumper X1 or X2
determines the method by which this delay (in cycles or seconds) is calcu-
lated. See below for instructions on setting delay time.
• X1 = (DLY-C) Start time delay in cycles
Jumper Selection on TCB Board
• X2 = (DLY-S) Start time delay in seconds (Factory setting) Figure 2-6

Auxiliary (Start) Delay (from the time the start is initiated to when contacts
change state). Selecting jumper X3 or X4 determines the method by which this
delay is calculated (cycles or seconds). See below for instructions on setting
delay time.
• X3 = (AUX-C) Auxiliary time delay in cycles
• X4 = (AUX-S) Auxiliary time delay in seconds (Factory setting)

Power Factor Correction (PFC) Capacitor Contactor Delay (From the time
the bypass closes to when contacts change state). Jumper selection deter-
mines the method by which this delay is calculated. See below for instruction
on setting delay time.
• X5 = (PFC-C) Time delay in cycles
• X6 = (PFC-S) Time delay in seconds (Factory setting)

Switch Positions
Please refer to Figure 2-7.
• SW1 = On = Dual Adjustment
OFF = Disabled
• SW2*= Not used
Switches SW3, SW4 and SW5 are 7 position dip switches that use
binary code to count up to 127 seconds/cycles (see “Jumper Selection”
Figure 2-7
above).
• SW3 = Start Delay; 7 position dip switch uses binary count up to 127 Example:
seconds/cycles. (See jumper selection above.) Factory setting: 1 second Switch settings are cumulative.
Setting dip switch positions 1, 2,
• SW4** = Auxiliary (Start) Delay 7 position dip switch uses binary count
and 3 to “on” = 1+2+4 = 7 seconds
up to 127 seconds/cycles. (See jumper selection above.) Factory setting:
total time. Note: This example
1 second
applies to SW3, SW4 & SW5.
• SW5** = PFC time delay; 7 position dip switch uses binary count up to
127 seconds/cycles. (See jumper selection above) Factory setting: 1
second.
*Note: This switch interacts with the CPU programming when the Decel func-
tion is enabled.
**Note: These times are in addition to SP2 in the CPU setpoints.

- 12 -
2.3 - 7.2kV

2.3 Reference Section - THIS SECTION IS FOR REFERENCE ONLY.


NO FIELD WIRING/CONNECTIONS ARE REQUIRED.

2.3a Optional RTD Board

RTD1 RTD2 RTD3 RTD4 RTD5 RTD6 RTD7 RTD8 RTD9 RTD10 RTD11 RTD12
Compensation
Shield
Power
Signal

RTD
Typical RTD
Installation

- 13 -
2.3 - 7.2kV

2.3 Reference Section - THIS SECTION IS FOR REFERENCE ONLY.


NO FIELD WIRING/CONNECTIONS ARE REQUIRED.

2.3b Communications Board

REAR
VIEW

(RS485) (RS422)

Note: Remove for last unit in modbus string

2.3c Communications Board Connections


TB1
TB2

RS485 Connections RS422 Connections


(Customer Connections) (Factory Only)

- 14 -
2.3 - 7.2kV

2.3 Reference Section - THIS SECTION IS FOR REFERENCE ONLY.


NO FIELD WIRING/CONNECTIONS ARE REQUIRED.
2.3d Power Board
Board
Ground Test Points
19 1 7 1 7 1 19 1

20 2 J3 20 J6 2
J5 J4

AI

AT

BI

BT

CI

CT

3
GF

1
J1

C2 C1

7
7, A - Phase
B2 B1

4, B - Phase
A2 A1

1, C - Phase

1
J2
31

J8
J7
J2

6
1
F1

TB1 TB2
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
TB3

2.3e Power Board Connections


TB3 TB3
Two-Wire Three-Wire
Connection Connection

TB1 TB2
Factory use only. Do not reprogram. Refer to Setpoint Page 5 for programming information

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C. C N.O. N.C.
AUX1 AUX2 AUX3 AUX4 AUX5 AUX6 AUX7 AUX8
(TRIP) (ALARM) (RUN) (AT SPEED) Relay Relay Relay Relay
Relay Relay Relay Relay

(Max Relay Contact Rating is 240 VAC, 4A, 960VA)

- 15 -
2.3 - 7.2kV
2.3 Reference Section - THIS SECTION IS FOR REFERENCE ONLY.
NO FIELD WIRING/CONNECTIONS ARE REQUIRED.

2.3f CPU Board Connections

1 2

19 20

1 2

19 20

Contact factory for remote


reset connections Factory wired. Do not change
Analog Output #1

Analog Output #2

Program Enable

UV-P Rotation
Input

Thermostat
Tach Input

Dual Ramp
4 - 20 mA

4 - 20 mA

TCB Fault

TB1 TB2 TB3

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

+ - + - + - + - + - + - + -
+ -
Note: Install program jumper to enable
setpoint programming. Jumper must be
removed after programming or for
prolonged storage to preserve settings.

- 16 -
2.3 - 7.2kV
Chapter 3 - Start-up
3.1 Introduction
It is best to operate the motor at its full load starting condition to achieve the
proper time, torque and ramp settings. Initial settings are set to accommodate
most motor conditions. TRY INITIAL SETTINGS FIRST. See Section 5.1.2
Starter Configuration (Setpoint Page 2) to make any adjustments.

3.2 Acceleration Adjustments


The unit is set at the factory with typical starting characteristics that perform
well in most applications. When the system is ready to start, try the initial
unit settings. If the motor does not come up to speed, increase the current
limit setting. If the motor does not start to turn as soon as desired, raise the
starting voltage adjustment. Adjustment description and procedures are
described as follows. See Setpoint 5.1.2 Starter Configuration (Setpoint Page
2) for additional Accel settings:

3.2.1 Starting Voltage


Factory Setting = 20% of line voltage
Range = 0% - 100% of line voltage
Starting voltage adjustment changes the initial starting voltage level
to the motor.

3.2.2 Ramp Time


Factory Setting = 10 sec.
Range = 0 - 120 sec.
Ramp time adjustment changes the amount of time it takes to
reach the current limit point or full voltage if the current limit point
was not reached.
Note: Refer to your motor manual for the maximum number of starts per
hour allowed by the manufacturer and do not exceed the recom-
mended number.

3.2.3 Current Limit


Factory Setting = 350% of motor FLA
Range = 200% - 600% of motor FLA
The current limit adjustment is factory set for 350% of the motor FLA. The
range of adjustment is 200% to 600%. The main function of current limit
is to cap the peak current. It may also be used to extend the ramping
time if required. The interaction between the voltage ramp and the current
limit will allow the soft start to ramp the motor until the maximum current
is reached and the current limit will hold the current at that level. The
current limit must be set high enough to allow the motor to reach full
speed. The factory setting of 350% is a good starting point. Do not set
the current limit too low on variable starting loads. This could
cause the motor to stall and eventually trip the overload protection.
Note: If the motor does stall, refer to the motor manufacturer’s motor data for
the proper cooling time.

3.3 Deceleration Adjustments (Pump Control)


Decel extends the stopping time on loads that would otherwise stop too
quickly if allowed to coast to a stop. Decel control provides smooth decelera-
tion until the load comes to a stop. Three adjustments optimize the decelera-
tion curve to meet the most demanding requirements. The unit is shipped from
the factory with the decel feature disabled.

- 17 -
2.3 - 7.2kV

Deceleration Applications
The unit is shipped from the factory with the decel feature
disabled. Apply power and adjust the soft start before enabling or
modifying the deceleration adjustments. Both acceleration and decel-
eration adjustments should be made under normal load conditions.

The deceleration feature provides a slow decrease in the output


voltage, accomplishing a gentle decrease in motor torque during the
stopping mode. This is the OPPOSITE OF BRAKING in that it will take
longer to come to a stop than if the starter were just turned off. The
primary use of this function is to reduce the sudden changes in
pressure that are associated with “Water Hammer” and slamming of
check valves with centrifugal pumps. Decel control in pump applica-
tions is often referred to as Pump Control.

In a pump system, liquid is being pushed uphill. The force exerted by


gravity on the column of liquid as it goes uphill is called the “Head
Pressure” in the system. The pump is sized to provide enough Output
Pressure to overcome the Head Pressure and move the fluid up the
pipe. When the pump is turned off, the Output Pressure rapidly drops
to zero and the Head Pressure takes over to send the fluid back down
the hill. A “Check Valve” is used somewhere in the system to prevent
this (if necessary) by only allowing the liquid to flow in one direction.
The kinetic energy in that moving fluid is suddenly trapped when the
valve slams closed. Since fluids can’t compress, that energy is
transformed into a “Shock Wave” that travels through the piping
system looking for an outlet in which it dissipates. The sound of that
shock wave is referred to as “Water Hammer”. The energy in that
shock wave can be extremely damaging to pipes, fittings, flanges,
seals and mounting systems.

By using the Soft Stop/Deceleration feature of the starter, the pump


output torque is gradually and gently reduced, which slowly reduces
the pressure in the pipe. When the Output Pressure is just slightly
lower than the Head Pressure, the flow slowly reverses and closes the
Check Valve. By this time there is very little energy left in the moving
fluid and the Shock Wave is avoided. When the output voltage to the motor is
low enough to no longer be needed, the soft starter will end the Decel cycle
and turn itself off.

Another common application for decel control is on material handling convey-


ors as a means to prevent sudden stops that may cause products to fall over
or to bump into one another. In overhead crane applications, soft stopping of
the Bridge or Trolley can prevent loads from beginning to over swing on
sudden stops.

- 18 -
2.3 - 7.2kV

3.3.1 Start Deceleration Voltage


Factory Setting = 60% of line voltage
Range = 0% - 100% of line voltage
The step down voltage adjustment eliminates the dead band in the
deceleration mode that is experienced while the voltage drops to a level
where the motor deceleration is responsive to decreased voltage. This
feature allows for an instantaneous drop in voltage when deceleration is
initiated.

3.3.2 Stop Deceleration Voltage


Factory Setting = 20% of line voltage
Range = 0% - 100% of line voltage
The stop voltage level setpoint is where the deceleration voltage drops
to zero.

3.3.3 Deceleration Time


Factory Setting = 5 sec.
Range = 0 - 60 sec.
The deceleration ramp time adjusts the time it takes to reach the stop
voltage level set point. The unit should be restarted and stopped to verify
that the desired deceleration time has been achieved.

Note: Do not exceed the motor manufacturer’s recommended number of starts per
hour. When calculating the number of starts per hour, a decel curve should be
counted as a start curve. For example, recommended number of starts per
hour = 6, allowable starts with decel cycle per hour = 3.

3.4 Sequence of Normal Operation


• Apply control power and check that the “Power” LED comes on. (Display 1)
• Apply three phase power to the unit. The motor should run only when the
start command is applied. MOTOR STOPPED
Display 1
• Apply the start command. (Display 2). The RUN LED will be lit. (Display READY TO START
3). The AUX3 LEDs will be lit. If the motor does not enter run mode in the
MOTOR STARTING
set time (Acceleration time limit, see SP8.2), a trip will occur. Display 2 00 X FLA
• When the motor reaches full speed, the “AUX4” LED (At Speed) will be lit.
• The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has Display 3 OVERLOAD ALARM
TIME TO TRIP: XXX SECS.
energized. IA, IB, IC will display the current setting for Phase A, Phase B,
and Phase C and the G/F indicates ground fault. (Display 4).
Display 4 IA: _ _ _ IB: _ _ _
• If the motor decelerates, or stops, during the acceleration period, hit the IC: _ _ _ G/F: _ _ _
stop button immediately and open the disconnect line. If the unit does not
follow this operational sequence, please refer to the Troubleshooting
Chapter.

It is best to operate the motor at its full load starting condition to achieve the
proper time, torque and ramp settings. Initial settings are set to accommodate
most motor conditions. TRY INITIAL SETTINGS FIRST. See Section 5.1.1
(Setpoint Page 2) to make any adjustments.
• Initial Voltage
• Soft Start Curve
• Current Limit
• Acceleration Time

If decel is enabled, the following parameters for Deceleration Time, Start Decel
Voltage (see SP2, page 35) and Stop Decel Voltage must also be pro-
grammed.

- 19 -
2.3 - 7.2kV

3.5 Emergency Bypass Operation

! DANGER
HAZARDOUS OPERATION
Do not operate the Bypass Contactor with medium
voltage power applied to the unit.

Failure to follow this instruction will cause the motor


to start unexpectedly.

• Remove input power (using line start section and lock out disconnect).
• Close the emergency bypass contact.
• Re-close disconnect on line start panel.
• Bi-metallic overload protection is required (customer supplied if factory
emergency overload protection option has not been included.)

Note: In the emergency bypass mode, there is no overload protection unless a


separate (optional or customer supplier) thermal overload relay is installed.

The line start panel is operable as a normal across-the-line starter. When


power is applied, the bypass contactor is energized, tying the input
terminals directly to its output terminals. When the “ON/OFF” contact is
closed, the main contactor is energized and the motor line starts. When
the “ON/OFF” contact is opened, the motor is disconnected from the line
via the main in-line vacuum contactor.

- 20 -
2.3 - 7.2kV

Chapter 4 - User Interface & Menu Navigation


This chapter explains the keypad operator interface, the LCD descriptions and the
programming features

4.1 Keypad/Operator Interface


The user keypad/ keypad operator interface consists of:
• 2 row by 20 characters Liquid Crystal Display (LCD)
• 12 LEDs
• 8 pushbuttons

Note: The controller is menu driven and there are three levels of programming.
The programming for two of these levels is password protected. Level two
requires a three digit password and level three requires a four digit password.

Toggle between the menu selection for metering and


MENU
setpoint pages.

RESET Will clear the trip indicator and release the trip relay.

In the edit mode, press the ENTER pushbutton so the Keypad Operator Interface
unit will accept the new programming information.
ENTER When not in the edit mode, the ENTER pushbutton will
toggle through the event indicator list (such as alarms
or trips)

Provides general help information about a specific


HELP
setpoint or action.
Will scroll up through the setpoint and metering menu
page. It will scroll to the top of the setpoint page or a
Button UP ARROW section. In edit mode it will increase a setpoint in an
incremental step or toggle through the available
options in the setpoint.

In the main menu the RIGHT ARROW button provides


access to the setpoint page. For setpoint pages with
RIGHT ARROW multiple columns, the RIGHT ARROW will scroll the
setpoint page to the right. When in edit mode it will
shift one character to the right.

Will scroll down through the setpoint pages and down


through the setpoints. In edit mode, it will decrement
DOWN ARROW
through values and toggle available options in the
setpoint.

Will move to the left through setpoint pages with


LEFT ARROW multiple columns. When in edit mode it will become the
backspace key and will shift one character to the left.

Power Indicates control power is present


Run Indicates unit/motor is running
Lights in conjunction with AUX 2 to indicate event or
Alarm
LED warn of possible critical condition.
Lights in conjunction with AUX 1 to indicate a critical
Trip
condition has occurred.
AUX 1-8 Auxilary relays
Note: The directional arrow buttons require careful operation. In edit mode, if
the buttons are held for a long period, the scrolling speed will increase.

- 21 -
2.3 - 7.2kV

4.2 Menu Navigation


Notes:
1. The MENU keys allow you to toggle the screens between the Setpoint Menu and
MENU the Metering Menu. Simply use the arrow keys to get to the different screens
(1) within each menu.
Example: To access Setpoint Page 3: PHASE & GROUND SETTINGS, press
the MENU key once and the DOWN ARROW two times.
PAGE 1 BASIC 2. Levels 1, 2 and 3 indicate password protection levels for these setpoint pages.
CONFIGURATION

LEVEL 1
PAGE 2 STARTER
CONFIGURATION

PAGE 3 PHASE &


GROUND SETTINGS

PAGE 4 RELAY
ASSIGNMENT

LEVEL 2

PAGE 5 RELAY
CONFIGURATION

PAGE 6 USER I/O


CONFIGURATION

PAGE 7 CUSTOM
ACCELERATION CURVE

PAGE 8 OVERLOAD
CURVE CONFIGURATION

PAGE 9 RTD
CONFIGURATION

LEVEL 3
PAGE 10 SECURITY
SET PASSWORD

PAGE 11
COMMUNICATIONS

PAGE 12 SYSTEM
SETPOINTS

FACTORY PAGE 13 CALIBRATION


LEVEL & SERVICE

- 22 -
2.3 - 7.2kV

4.2.1 Password Access


Screens in Level 1 of the setpoint menu can be changed without password
access because they list basic motor information. Screens in Levels 2 and 3
require passwords because they provide more in-depth protection and
control of the soft starter unit. The password in Levels 2 and 3 can be
changed by the user.

Note: Setpoints can only be changed when the motor is in Stop/


Ready Mode! The unit will not allow a start if it is still in the
Edit Mode. When the unit is in the Edit Mode, an asterisk is
displayed in the top right corner of the display.

4.2.2 Changing Setpoints


Example 1: Changing Motor FLA
A. Press MENU button to display Setpoint Page 1, Basic Configuration
B. Press the RIGHT ARROW you will view the screen Motor Full Load
Amps.
C. Press the ENTER button for edit mode. Note the asterisk (*) in the top
right corner of the LCD screen that indicates Edit Mode.
D. To change the value, select the UP ARROW or DOWN ARROW.
E. To accept the new value, press the ENTER button. The unit will accept
the changes and will leave the edit mode. Note the * is no longer in the
top right corner of the LCD Display.

MENU

PAGE 1 BASIC MOTOR FULL LOAD AMPS


CONFIGURATION : 140 AMPS

ENTER

MOTOR FULL LOAD AMP*


2x : 142 AMPS

ENTER

MOTOR FULL LOAD AMP


: 142 AMPS

- 23 -
2.3 - 7.2kV
Chapter 5 - Setpoint Programming
The controller has thirteen programmable setpoint pages which define the motor
data, ramp curves, protection, I/O configuration and communications. In Section
5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages
are illustrated and defined for easy navigation and programming. Note: Setpoints
can only be changed when the starter is in the Ready Mode. Also the soft start will
not start when it is in programming mode.

5.1 Setpoints Page List


These charts list the Setpoint Page, the programmable functions and the section.

5.1.1 Basic Configuration (Setpoint Page1)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
50 - 100% of Unit Max Current Rating
Motor Full Load Amps (FLA) Model dependent SP1.1
No Passowrd Required

(Model and Service Factor dependent)


Basic Configuration

Service Factor 1.15 1.00 – 1.3 SP1.2


Level 1
Page 1

Overload Class 10 O/L Class 5-30 SP1.3


NEMA Design B A-F SP1.4
Insulation Class B A, B, C, E, F, H, K, N, S SP1.5
Line Voltage 4160 100 to 7200V SP1.6
Line Frequency 60 50 or 60 HZ SP1.7

5.1.2 Starter Configuration (Setpoint Page 2)


Setpoint Security Factory Setting
Description Range Section
Page Level Default

Jog, Start Ramp 1, Start Ramp 2, Custom


Start Control Mode Start Ramp 1 SP2.1
Accel Curve, Start Disabled, Dual Ramp

Jog Voltage Off 5-75%, Off SP2.2


Start Ramp #1 Type Voltage Current, Voltage, Off
Initial Voltage #1 20% 0-100%
Ramp Time #1 10 sec 0-120 sec
Current Limit #1 350% FLA 200-600 % SP2.3
Initial Current #1 200% FLA 0-300%
Ramp Time #1 10 sec 0-120 sec
Maximum Current #1 350% FLA 200-600 %
No Passowrd Required

Start Ramp #2 Type Off Current, Voltage, Off


Starter Configuration

Initial Voltage #2 60% 0-100 %


Ramp Time #2 10 sec 0-120 sec
Level 1
Page 2

Current Limit #2 350 % FLA 200-600 % SP2.4


Initial Current #2 200% FLA 0-600 %
Ramp Time #2 10 sec 0-120 sec
Maximum Current #2 350% FLA 200-600 %
Kick Start Type Off Voltage or Off
Kick Start Voltage 65% 10-100 % SP2.5
Kick Start Time 0.50 sec 0.10-2.00
Deceleration Disabled Enabled or Disabled
Start Deceleration Voltage 60% 0-100 %
SP2.6
Stop Deceleration Voltage 30% 0-59 %
Deceleration Time 5 sec 1-60 sec
Timed Output Time Off 1-1000 sec, Off SP2.7
Run Delay Time 1 Sec 1-30 sec, Off SP2.8
At Speed Delay Time 1 Sec 1-30 sec, Off SP2.9
- 24 -
2.3 - 7.2kV

5.1.3 Phase and Ground Settings (Setpoint Page 3)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Imbalance Alarm Level 15% FLA 5-30 %, Off
SP3.1
Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec
Imbalance Trip Level 20% 5-30 %, Off
SP3.2
Imbalance Trip Delay 2.0 sec 1.0-20.0 sec
Undercurrent Alarm Level Off 10-90 %, Off
SP3.3
Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec
Overcurrent Alarm Level Off 100-300 %, Off
SP3.4
Overcurrent Alarm Delay 2.0 sec 1.0-20.0 sec
Overcurrent Trip Level Off 100-300 %, Off
SP3.5
Overcurrent Trip Delay 2.0 sec 1.0-20.0 sec
Phase Loss Trip Disabled Enabled or Disabled
SP3.6
Phase Loss Trip Delay 0.1 sec 0-20.0 sec
Phase Rotation Detection Enabled Enabled Only
SP3.7
Phase Rotation ABC ABC
*Ground Fault Alarm Level Off 5-90 %, Off
SP3.8
*Ground Fault Alarm Delay 0.1 sec 0.1-20.0 sec
*Ground Fault Loset Trip Level Off 5-90 %, Off
SP3.9
*Ground Fault Loset Trip Delay 0.5 sec 0.1-20 sec
Phase and Ground Settings

*Ground Fault Hiset Trip Level Off 5-90 %, Off


SP3.10
Password Protection

*Ground Fault Hiset Trip Delay 0.008 sec 0.008-0.250 sec


Overvoltage Alarm Level Off 5 -30%, Off
Level 2
Page 3

SP3.11
Overvoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Overvoltage Trip Level Off 5-30%, Off
SP3.12
Overvoltage Trip Delay 2.0 sec 1.0-30.0 sec
Undervoltage Alarm Level Off 5-30%, Off
SP3.13
Undervoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Undervoltage Trip Level Off 5-30%, Off
SP3.14
Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec
Line Frequency Trip Window Disabled 0-6 Hz, Disabled
SP3.15
Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec
P/F Lead P/F Alarm Off 0.1-1.00, Off
SP3.16
P/F Lead Alarm Delay 1.0 sec 1-120 sec
P/F Lead P/F Trip Off .01-1.00, Off
SP3.17
P/F Lead Trip Delay 1.0 sec 1-120 sec
P/F Lag P/F Alarm Off .01-1.00, Off
SP3.18
P/F Lag Alarm Delay 1.0 sec 1-120 sec
P/F Lag P/F Trip Off .01-1.00, Off
SP3.19
P/F Lag Trip Delay 1.0 sec 1-120 sec
Power Demand Period 10 min 1 - 60 min
KW Demand Alarm Pickup Off KW Off, 1-100000
KVA Demand Alarm Pickup Off KVA Off, 1-100000 SP3.20
KVAR Demand Alarm Pickup Off KVAR Off, 1-100000
Amps Demand Alarm Pickup Off Amps Off, 1-100000
* Ground fault option must be installed

- 25 -
2.3 - 7.2kV

5.1.4 Relay Assignments (Setpoint Page 4)


Setpoint Security Factory Setting
Description Range
Page Level 1st 2nd 3rd
O/L Trip Trip Only None None
I/B Trip Trip None None
S/C Trip Trip Only None None
Overcurrent Trip Trip None None
Stator RTD Trip Trip None None
Bearing RTD Trip Trip None None
*G/F Hi Set Trip Trip None None
*G/F Lo Set Trip Trip None None
Phase Loss Trip Trip None None
Accel. Time Trip Trip Only None None
Start Curve Trip Trip Only None None
Over Frequency Trip Trip None None
Under Frequency Trip Trip None None
I*I*T Start Curve Trip None None
Learned Start Curve Trip None None
Phase Reversal Trip None None
Overvoltage Trip Trip None None
Undervoltage Trip Trip None None None
Power Factor Trip Trip None None Trip(AUX1)
Tach Accel Trip None None None Alarm(AUX2)
Password Protection

Inhibits Trip Trip None None AUX3


Relay Assignments

TCB Fault Trip None None AUX4


External Input #2 None None None AUX5-8
Level 2
Page 4

Dual Ramp None None None Only Available in 8 Relay


Thermostat Trip None None System
O/L Warning Alarm None None Notes:
Overcurrent Alarm Alarm None None AUX1 to AUX4 are for Factory
Use only. Do not change!
SCR Fail Shunt Alarm None None None
Only AUX 5 - 8 are used in the
*Ground Fault Alarm Alarm None None
2nd & 3rd relay assignments.
Under Current Alarm None None None
Motor Running AUX3 None None
I/B Alarm Alarm None None
Stator RTD Alarm None None None
Non-Stator RTD Alarm None None None
RTD Failure Alarm None None None
Self Test Fail Trip None None
Thermal Register Alarm None None
U/V Alarm Alarm None None
O/V Alarm Alarm None None
Power Factor Alarm None None None
KW Demand Alarm None None None
KVA Demand Alarm None None None
KVAR Demand Alarm None None None
Amps Demand Alarm None None None
Timed Output None None None
Run Delay Time None None None
At Speed AUX4 None None

*Ground fault option must be installed.

- 26 -
2.3 - 7.2kV

5.1.5 Relay Configuration (Setpoint Page 5)

Setpoint Security Factory Setting


Description Range Section
Page Level Default
Trip (AUX1) Fail-Safe No Yes or No SP5.1
Trip (AUX1) Relay Latched Yes Yes or No SP5.2
Alarm (AUX2) Fail-Safe No Yes or No SP5.1
Alarm (AUX2) Relay Latched No Yes or No SP5.2
AUX3 Relay Fail-Safe No Yes or No SP5.1
AUX3 Relay Latched No Yes or No SP5.2
Password Protection
Relay Configuration

AUX4 Relay Fail-Safe No Yes or No SP5.1


Level 2
Page 5

AUX4 Relay Latched No Yes or No SP5.2


AUX5 Relay Fail-Safe No Yes or No SP5.1
AUX5 Relay Latched No Yes or No SP5.2
AUX6 Relay Fail-Safe No Yes or No SP5.1
AUX6 Relay Latched No Yes or No SP5.2
AUX7 Relay Fail-Safe No Yes or No SP5.1
AUX7 Relay Latched No Yes or No SP5.2
AUX8 Relay Fail-Safe No Yes or No SP5.1
AUX8 Relay Latched No Yes or No SP5.2

- 27 -
2.3 - 7.2kV

5.1.6 User I/O Configuration (Setpoint Page 6)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Tachometer Scale Selection Disabled Enabled or Disabled
Manual Tach Scale 4.0 mA: 0 RPM 0 - 3600 SP6.1
Manual Tach Scale 20.0 mA: 2000 RPM 0 - 3600
Tach Accel Trip Mode Select Disabled Underspeed, Overspeed or Disabled
Tach Ramp Time 20 sec 1 - 120
Tach Underspeed Trip PT 1650 RPM 0-3600 SP6.2
Tach Overspeed Trip PT 1850 RPM 0 - 3600
Tach Accel Trip Delay 1 sec 1 - 60
Off, RPM 0-3600, Hottest Non-Stator RTD
0-200°C, Hottest Stator RTD
Analog Output #1 RMS Current
0 - 200°C, RMS Current 0 - 7500 A, %
Motor Load 0 - 600 %. SP6.3

Analog Output #1 4mA: 0 0-65535


Analog Output #1 20mA: 250 0-65535
Analog Output #2 % Motor Load Same As Analog Input #1
User I/O Configuration

Passowrd Protection

Analog Output #2 4mA: 0 0-1000% SP6.4


Analog Output #2 20mA: 1000 0-1000%
Page 6

Lavel 2

User Programmable External


Inputs
TCB Fault Enabled Enabled or Disabled
Name Ext. Input #1 TCB Fault User Defined, up to 15 Characters
External Input #1 Type NO Normally Open or Closed
External Input #1 Time Delay 1 sec 0-60 sec
External Input #2 Disabled Enabled or Disabled
Name Ext. Input #2 User Defined, up to 15 Characters
External Input #2 Type NO Normally Open or Closed
SP6.5
External Input #2 Time Delay 0 sec 0-60 sec
Second Ramp Dual Ramp Enabled or Disabled or Dual Ramp
Name Ext. Input #3 Second Ramp User Defined, up to 15 Characters
Second Ramp Type NO Normally Open or Closed
Second Ramp Time Delay 0 sec 0-60 sec
Thermostat Enabled Enabled or Disabled
Name Ext. Input #4 Thermostat User Defined, up to 15 Characters
Thermostat Type NC Normally Open or Closed
Thermostat Time Delay 1 sec 0-60 sec

- 28 -
2.3 - 7.2kV

5.1.7 Custom Acceleration Curve (Setpoint Page 7)


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Custom Accel Curve Disabled Disabled, Curve A, B, or C
Custom Curve A
Curve A Voltage Level 1 25% 0-100%
Curve A Ramp Time 1 2 sec 1-60 sec
Curve A Voltage Level 2 30% 0-100%
Curve A Ramp Time 2 2 sec 1-60 sec
Curve A Voltage Level 3 37% 0-100%
Curve A Ramp Time 3 2 sec 1-60 sec
Custom Acceleration Curve

Curve A Voltage Level 4 45% 0-100%


Password Protection

Curve A Ramp Time 4 2 sec 1-60 sec


Curve A Voltage Level 5 55% 0-100%
Level 3
Page 7

Curve A Ramp Time 5 2 sec 1-60 sec SP7.1


Curve A Voltage Level 6 67% 0-100%
Curve A Ramp Time 6 2 sec 1-60 sec
Curve A Voltage Level 7 82% 0-100%
Curve A Ramp Time 7 2 sec 1-60 sec
Curve A Voltage Level 8 100% 0-100%
Curve A Ramp Time 8 2 sec 1-60 sec
Curve A Current Limit 350% FLA 200-600%
Same Programmable Data Points and Ranges
Custom Curve B
as Custom Curve A

Same Programmable Data Points and Ranges


Custom Curve C
as Custom Curve A

5.1.8 Overload Curve Configuration (Setpoint Page 8)

Setpoint Security Factory Setting


Description Range Section
Page Level Default
Basic Run Overload Curve
Run Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
SP8.1
Run Locked Rotor Current 600% FLA 400-800%
Coast Down Timer Disabled 1-60 Min, Disabled
Overload Curve Configuration

Basic Start Overload Curve


Password Protection

Start Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
Start Locked Rotor Current 600% FLA 400-800%
Level 3
Page 8

SP8.2
Acceleration Time Limit 30 sec 1-300 sec, Disabled
Number of Starts Per Hour Disabled 1-6, Disabled
Time Between Starts Time 15 Min 1-60 Min, Disabled
Area Under Curve Protection Disabled Enabled or Disabled
SP8.3
Max I*I*T Start 368 FLA 1-2500 FLA*FLA*sec
Current Over Curve Disabled Disabled, Learn, Enabled
Learned Start Curve Bias 10% 5-40% SP8.4
Time for Sampling 30 sec 1-300 sec

- 29 -
2.3 - 7.2kV

5.1.9 RTD Option Configuration (Setpoint Page 9)

Setpoint Security Factory Setting


Description Range Section
Page Level Default

Use NEMA Temp for RTD Values Disabled Enabled or Disabled SP9.1

# of RTD Used for Stator 4 0-6 SP9.2


RTD Voting Disabled Enabled or Disabled SP9.3
120 OHM NI, 100 OHM NI, 100 OHM PT, 10
Stator Phase A1 Type Off
OHM CU
RTD #1 Description Stator A1 User defined, Up to 15 Characters
Stator Phase A1 Alarm Level Off 0-240C (32-464F), Off
Stator Phase A1 Trip Level Off 0-240C (32-464F), Off
Stator Phase A2 Type Off Same as Stator Phase A1
RTD #2 Description Stator A2 User defined, Up to 15 Characters
Stator Phase A2 Alarm Off 0-240C (32-464F), Off
Stator Phase A2 Trip Level Off 0-240C (32-464F), Off
Stator Phase B1 Type Off Same as Stator Phase A1
RTD #3 Description Stator B1 User defined, Up to 15 Characters
Stator Phase B1 Alarm Level Off 0-240C (32-464F), Off
Stator Phase B1 Trip Level Off 0-240C (32-464F), Off
Stator Phase B2 Type Off Same as Stator Phase A1
Password Protection

RTD #4 Description Stator B2 User defined, Up to 15 Characters


RTD Configuration

Stator Phase B2 Alarm Level Off 0-240C (32-464F), Off


Level 3
Page 9

Stator Phase B2 Trip Level Off 0-240C (32-464F), Off


Stator Phase C1 Type Off Same as Stator Phase A1
RTD #5 Description Stator C1 User defined, Up to 15 Characters SP9.4
Stator Phase C1 Alarm Level Off 0-240C (32-464F), Off
Stator Phase C1 Trip Level Off 0-240C (32-464F), Off
Stator Phase C2 Type Off Same as Stator Phase A1
RTD #6 Description Stator C2 User defined, Up to 15 Characters
Stator Phase C2 Alarm Level Off 0-240C (32-464F), Off
Stator Phase C2 Trip Level Off 0-240C (32-464F), Off
End Bearing Type Off Same as Stator A1
RTD #7 Description End Bearing User defined, Up to 15 Characters
End Bearing Alarm Level Off 0-240C (32-464F), Off
End Bearing Trip Level Off 0-240C (32-464F), Off
Shaft Bearing Type Off Same as Stator Phase A1
RTD #8 Description Shaft Bearing User defined, Up to 15 Characters
Shaft Bearing Alarm Level Off 0-240C (32-464F), Off
Shaft Bearing Trip Level Off 0-240C (32-464F), Off
RTD #9 Type Off Same as Stator Phase A1
RTD #9 Description User defined User defined, Up to 15 Characters
RTD #9 Alarm Level Off 0-240C (32-464F), Off
RTD #9 Trip Level Off 0-240C (32-464F), Off

- 30 -
2.3 - 7.2kV

5.1.9 RTD Option Configuration Page 9 Cont’d

Setpoint Security Factory Setting


Description Range Section
Page Level Default
RTD #10 Type Off Same as Stator Phase A1
RTD #10 Description User defined User defined, Up to 15 Characters
RTD #10 Alarm Level Off 0-240C (32-464F), Off
RTD #10 Trip Level Off 0-240C (32-464F), Off
Password Protection
RTD Configuration

RTD #11 Type Off Same as Stator Phase A1


Level 3
Page 9

RTD #11 Description User defined User defined, Up to 15 Characters


SP9.4
RTD #11 Alarm Level Off 0-240C (32-464F), Off
RTD #11 Trip Level Off 0-240C (32-464F), Off
RTD #12 Type Off Same as Stator Phase A1
RTD #12 Description User defined User defined, Up to 15 Characters
RTD #12 Alarm Level Off 0-240C (32-464F), Off
RTD #12 Trip Level Off 0-240C (32-464F), Off

5.1.10 Security Set Password Page 10


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Level
Page

Set Level 2 Password 100 000 – 999 Three Digits SP10.1


10

Set Level 3 Password 1000 0000 – 9999 Four Digits SP10.2

5.1.11 Communications Page 11


Setpoint Security Factory Setting
Description Range Section
Page Level Default
Set Front Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.1
Password Protection
Communiications

Set Modbus Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.2
Page 11

Modbus Address Number 247 1 – 247 SP11.3


Level 3

Set Access Code 1 1 – 999 SP11.4


Set Link Baud Rate 38.4 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.5

Remote Start/Stop Disabled Enabled or Disabled SP11.6

- 31 -
2.3 - 7.2kV

5.1.12 System (Setpoint Page 12)

Setpoint Security Factory Setting


Description Range Section
Page Level Default
Default Display Screen
Metering Data Page # 1 Enter Metering Page (1-4)
Enter Metering Screen
Page 1(1-10) SP12.1
Metering Data Screen # 1 Page 2 (1-11)
Page 3 (1 - 29)
Page 4 (1 - 6)
Alarms
RTD Failure Alarm Disabled Enabled or Disabled
SP12.2
Thermal Register Alarm 90% Off, 40-95%
Thermal Alarm Delay 10 sec 1-20 sec
Password Protection

Thermal Register Setup Info


System Setpoints

Cold Stall Time O/L Class O/L Class (5-30) or 4-40 second time delay
Page 12

Level 3

Hot Stall Time ½ O/L Class ½ O/L Class, 4-40 sec


Stopped Cool Down Time 30 Min 10-300 Min
Runing Cool Down Time 15 Min 10-300 Min
Relay Measured Cool Rates Disabled Enabled or Disabled
Thermal Register Minimum 15% 10-50% SP12.3
Motor Design Ambient Temp 40C 10-90C

Motor Design Run Temperature 80% Max 50-100% of Motor Stator Max Temp

Motor Stator Max Temp INS CLS INS CLS, 10-240 C


I/B Input to Thermal Register Enabled Enabled Only
Use Calculated K or Assign 7 1-50, On

Press Enter to Clr Thermal Register SP12.4

5.1.13 Calibration and Service (Setpoint Page 13)

Setpoint Security Factory Setting


Description Range Section
Page Level Default
Set Date and Time FACTORY SET;
(DDMMYY:HHMM) ##/##/## ##:##
FACTORY USE ONLY
Calibration & Service

FACTORY SET;
Enter Date (DDMMYYYY) D=1-31, M=1-12, Y=1970-2069 SP13.1
##/##/####
Page 13

FACTORY SET;
Enter Time (HH:MM) H=00-23, M=0-59
##:##
Model # FACTORY SET;
Display Only, Cannot be changed SP13.2
Firmware REV. # ###### ######
Press Enter to Access Factory
Available to Qualified Factory Personnel SP13.3
Settings

- 32 -
2.3 - 7.2kV

5.2 Setpoint Menu


Note:
1. Push MENU key to toggle the screens between Setpoint Menu and Metering
MENU Menu.
(1) 2. Follow the arrow keys to get to different screens.
Example: For Page 3 PHASE & GROUND SETTINGS, press the MENU key and
the DOWN ARROW two times.
PAGE 1 BASIC
CONFIGURATION

LEVEL 1
PAGE 2 STARTER
CONFIGURATION

PAGE 3 PHASE &


GROUND SETTINGS

PAGE 4 RELAY
ASSIGNMENT

LEVEL 2

PAGE 5 RELAY
CONFIGURATION

PAGE 6 USER I/O


CONFIGURATION

PAGE 7 CUSTOM
ACCELERATION CURVE

PAGE 8 OVERLOAD
CURVE CONFIGURATION

PAGE 9 RTD
CONFIGURATION

LEVEL 3
PAGE 10 SECURITY
SET PASSWORD

PAGE 11
COMMUNICATIONS

PAGE 12 SYSTEM
SETPOINTS

FACTORY PAGE 13 CALIBRATION


LEVEL & SERVICE

- 33 -
2.3 - 7.2kV

SP.1 Basic Configuration (Setpoint Page 1)


In Setpoint Page 1, the controller is looking for the following
basic nameplate data of the motor.
MENU

SP1.1 Motor Full Load Amps (FLA): Allows the user to PAGE 1 BASIC MOTOR FULL LOAD AMPS
enter the motor’s FLA rating. Range of adjustment is CONFIGURATION : 200 AMPS
50 - 100% (less programmed service factor). Range: 50 - 100% of Unit
MAX CURRENT AMPS
Increments of 1
SP1.2 Service Factor: Sets the pickup point on the overload
SERVICE FACTOR
curve as defined by the programmed motor full load : 1.15 X FLA
current. Ex: If the motor FLA is 100 and the service Range: 1.00 - 1.3
factor is 1.15, the controller overload pickup point will Increments of 0.01
be 115 Amps.
OVERLOAD
CLASS: 10
SP1.3 Overload Class: Choose the motor protection Range: 5 - 30
overload class, range from 5-30. Increments of 5
Ex: Overload Class 10 will trip in 10 seconds at six
times FLA. NEMA
DESIGN: B
Range: A - F

INSULATION
CLASS: B
Range: A - S

LINE VOLTAGE
INPUT: 4160 VOLTS
Range: 100 - 7200

LINE FREQUENCY
HZ: 60
Range: 50 or 60

SP1.4 NEMA design: The motor design maximum allowed slip (Select
from Class A through F).

SP1.5 Insulation Class: The motor insulation temperature class (Select


A, B, C, E, F, G, H, K, N or S).

SP1.6 Line Voltage Input: Applied Voltage

SP1.7 Line Frequency: The user may choose either 50 Hz or 60 Hz.

- 34 -
2.3 - 7.2kV

SP.2 Starter Configuration (Setpoint Page 2)

MENU
(Hit DOWN ARROW one time)

PAGE 2 STARTER START CONTROL MODE


CONFIGURATION : START RAMP 1
JOG, START RAMP 1,
START RAMP 2, DUAL
RAMP, CUSTOM ACCEL
CURVE,START DISABLED
If If
VOLTAGE CURRENT
JOG VOLTAGE selected selected
: OFF these these
screens screens
Range: 5 - 75% or Off will appear. will appear.
Increments 5

START RAMP #1 TYPE INITIAL VOLTAGE INITIAL CURRENT


: VOLTAGE #1: 20% #1: 200% FLA
Options:Voltage, Current Range: 0 - 100% Range: 0 - 300%
or Off Increments of 1 Increments of 1

RAMP TIME RAMP TIME


#1: 10 SEC. #1: 10 SEC.
Range: 0 - 120 SEC. Range: 0 - 120 SEC
Increments of 1 Increments of 1

CURRENT LIMIT MAXIMUM CURRENT


#1: 350% FLA #1: 350% FLA
Range: 200 - 600% Range: 200-600%
Increments of 10 Increments of 10

If If
START RAMP #2 TYPE VOLTAGE CURRENT
: OFF selected INITIAL VOLTAGE selected INITIAL CURRENT
these these
#2: 60% #2: 200% FLA
Options: Voltage, Current screens screens
or Off will appear. Range: 0 - 100% will appear. Range: 0 - 300%
Increments of 1 Increments of 1

RAMP TIME RAMP TIME


#2: 10 SEC. #2: 10 SEC.
Range: 0 - 120 SEC. Range: 0 - 120 SEC
Increments of 1 Increments of 1

CURRENT LIMIT MAXIMUM CURRENT


#2: 350% FLA #2: 350% FLA
Range: 200 - 600% Range: 200-600%
Increments of 10 Increments of 10

KICK START KICK START VOLTAGE


TYPE: OFF : 65%
Range: Voltage or Off Range: 10 - 100%
Increments of 5

DECELERATION KICK START TIME


: DISABLED : 0.50 SEC.
Range: Enabled or Disabled Range: 0.10 - 2.00
Increments of 0.10

START DECELERATION
TIMED OUTPUT VOLTAGE: 60%
TIME: OFF
Range: 0 - 100%
Range: 1 - 1000 sec, OFF Increments of 1
Increments of 1

RUN DELAY STOP DECELERATION


TIME: 1 SEC. VOLTAGE: 30%
Range: 0 - 30 sec, OFF Range: 0 - 59%
Increments of 1 Increments of 1

AT SPEED DELAY DECELERATION


TIME: 1 SEC. TIME: 5 SEC.
Range: 0 - 30 sec, OFF Range: 1 - 60
Increments of 1 Increments of 1

- 35 -
2.3 - 7.2kV
SP.2 Starter Configuration (Setpoint Page 2) • Voltage Ramping with Current Limit is the
Provides multiple choices for starting ramps that can be most used curve and is similar to voltage
selected for particular loads and applications. ramping. However, it adds an adjustable
maximum current output. Voltage is increased
SP2.1 Start Control Mode: Dual Ramp, Custom gradually until the setting of the Maximum
Accel Curve, Jog Voltage, Start Ramp 1, Start Current Limit setpoint is reached. The voltage is
Ramp 2. held at this level until the motor accelerates to
• Dual Ramp: The dual ramp mode works in full speed. This may be necessary in
conjunction with External Input #3. This allows applications where the electrical power is
the user to switch between the two start ramps limited. Typical applications include portable or
without having to reconfigure the start mode. emergency generator supplies, utility power
(For details on configuring External Input #3 for near the end of a transmission line and utility
DUAL RAMP see Setpoint Page 6.) starting power demand restrictions. Note: Using
• Custom Accel Curve: Allows the user to Current Limit will override the Ramp Time setting
custom design the acceleration start curve to if necessary, so use this feature when
the application. (See setpoint page 7 for acceleration time is not critical. To achieve
configuration setup.) Note: If Custom Accel Voltage Ramping with Current Limit, select
Curve has not been enabled in setpoint page 7, VOLTAGE for the START RAMP #1 setpoint and
it will ignore the start control mode and read this set CURRENT LIMIT#1 setpoint to a desired
setpoint as disabled. lower setting, as determined by your application
• Tach Ramp: See setpoint page 6 for requirements.
configuration setup of tachometer input.
(Pending) Start Ramp 1 Type: Current
• Current Ramping (Closed Loop Torque
SP2.2 Jog Voltage: The voltage level necessary to Ramping) is used for smooth linear acceleration
cause the motor to slowly rotate. of output torque. This ramp is only used on
some conveyor systems (long haul or down hill).
SP2.3 Start Ramp 1 Type: The ramp type can be For other applications, use Voltage Ramp or a
setup for either Voltage or Current. If Voltage is custom accel curve (see page 47). Output
selected, initial voltage, ramp time and current voltage is constantly updated to provide the
limit are adjustable. If Current is selected, initial linear current ramp, and therefore the available
current, ramp time and maximum current are torque is maximized at any given speed. This is
adjustable. for applications where rapid changes in torque
Start Ramp 1 Type: Voltage may result in load damage or equipment
• Voltage Ramping is the most reliable starting changes. Typical applications include overland
method, because the starter will eventually conveyors if belt stretching occurs; fans and
reach an output voltage high enough to draw full mixers if blade warping is a problem; and
current and develop full torque. This method is material handling systems if stacked products
useful for applications fall over or break. This feature can be used with
where the load or without the Maximum Current Limit setting.
conditions change To achieve Current Ramping select CURRENT
frequently and where for START RAMP #1 TYPE setpoint and the
different levels of MAXIMUM CURRENT #1 setpoint to the desired
torque are required. level.
Typical applications
include material • Current Limit Only: (Current Step) start uses
handling conveyors, the Current Limit feature exclusively. This
positive displacement method of starting eliminates the soft start
pumps and drum voltage/current ramp and instead, maximizes
mixers. the effective application of motor torque within
Voltage is increased the limits of the motor. In this mode, setpoint
from a starting point (Initial Torque) to full voltage RAMP TIME #1 is set to zero (0), so the output
over an adjustable period of time (Ramp Time). current jumps to the current limit setting
To achieve Voltage Ramping, select VOLTAGE immediately. Typically used in with a limited
for the START RAMP #1 TYPE setpoint and set power supply, when starting a difficult load such
CURRENT LIMIT#1 setpoint to 600% (the as a centrifuge or deep well pump, when the
maximum setting). Since this is essentially motor capacity is barely adequate (stall
Locked Rotor Current on most motors, there is condition or overloading occurs) or if other
little or no Current Limit effect on the Ramp starting modes fail. Since ramp times are set to
profile. zero (0), START RAMP #1 TYPE is set to either
VOLTAGE or CURRENT.
- 36 -
2.3 - 7.2kV

• Initial Torque (Initial Voltage #1 or Initial SP2.4 Start Ramp 2: The same options and screen
Current #1): Sets the initial start point of either setups as Start Ramp 1. Note: CUSTOM
the Voltage Ramp or the Current Ramp. Every ACCEL CURVE overrides the voltage or current
load requires some amount of torque to start start in Ramps 1 and 2 when selected to be the
from a standstill. It is inefficient to begin ramping start control mode.
the motor from zero every time, since between
zero and the WK2 break-away torque level, no SP2.5 Kick Start: Used as an initial energy burst in
work is being performed. The initial torque level applications with high friction loads.
should be set to provide enough torque to start
rotating the motor shaft, enabling a soft start • Kick Start Voltage: The initial voltage (as a
and preventing torque shock damage. Setting percent of full voltage value) that is needed to
this start point too high will not damage the start the motor. (i.e., Breakaway or Initial
starter, but may reduce or eliminate the soft Torque.)
start effect.
• Kick Start Time: The time the initial torque
• Ramp Time #1: Sets the maximum allowable boost is applied.
time for ramping the initial voltage or current
(torque) setting to either of the following: SP2.6 Deceleration: Allows the motor to gradually
1) the Current Limit setting when the motor is come to a soft stop.
still accelerating, or
2) full output voltage if the Current Limit is set to • Start Deceleration Voltage: The first part of
maximum. the deceleration ramp. The soft starter initially
Increasing the ramp time softens the start drops to this voltage level upon receiving a
process by gradually increasing the voltage or STOP command. (Represented as a percent of
current. Ideally, the ramp time should be set for voltage value.)
the longest amount of time the application will
allow (without stalling the motor). Some • Stop Deceleration Voltage: The drop-off point
applications require a short ramp time due to of the deceleration ramp. (Percent of voltage
the mechanics of the system. (i.e, centrifugal value.)
pumps, because pump problems can occur due
to insufficient torque). • Deceleration Time: Decel ramp time.

• Current Limit: Sets the maximum motor SP2.7 Timed Output: Used with an AUX 5-8 relay.
current the starter will allow during Ramping. As When enabled, and upon a start command, it
the motor begins to ramp, the Current Limit waits until the programmed time plus the run
feature sets a ceiling at which the current draw delayed time has expired. The relay energizes
is held. Current Limit remains in effect until the and remains so until a stop command is
following occurs: received. It de-energizes upon receiving a stop
1) the motor reaches full speed (detected by the command.
At-Speed detection circuit) or
2) the Overload Protection trips on Motor SP2.8 Run Delay Time: Can be used with an AUX 5-
Thermal Overload. 8 relay. The delay timer begins upon receipt of
Once the motor reaches full speed, the Current the start command. The relay will then drop out
Limit feature becomes inactive. when the time has expired.

In the Voltage Ramp Profile, the voltage output SP2.9 At Speed Delay Time: Used with an AUX 4
is increased until it reaches the Current Limit. relay, it waits until after the motor reaches the
Ramp time is the maximum amount of time it end of ramp and the programmed delay time has
takes for the voltage to increase until the expired. The relay energizes until a stop
Current Limit setting takes over. With some load command has been received.
conditions, the Current Limit is reached before
the Ramp Time expires.

The Current Ramp profile varies the output


voltage to provide a linear increase in current up
to the Maximum Current setpoint value. A
closed loop feedback of motor current maintains
the Current Ramp profile.

- 37 -
2.3 - 7.2kV
SP.3 Phase & Ground Settings
(Setpoint Page 3) MENU
(Security Level: 2) (Hit DOWN ARROW two times)

PAGE 3 PHASE & IMBALANCE ALARM IMBALANCE ALARM


GROUND SETTINGS LEVEL: 15% FLA DELAY: 1.5 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 20.0 SEC.
Increments of 1 Increments of 0.1

IMBALANCE TRIP IMBALANCE TRIP


LEVEL: 20%FLA DELAY: 2.0 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 20.0 SEC.
Increments of 1 Increments of 0.1
Note: Proper phase sequence must be observed when
UNDERCURRENT ALARM UNDERCURRENT ALARM
connecting the input power. For example, phase LEVEL: OFF DELAY: 2.0 SEC.
A must lead phase B, which in turn must lead Range: 10 - 90%, OFF Range: 1.0 - 60.0 SEC.
Increments of 1 Increments of 0.1
phase C by 120° respectively. If the phase
rotation is not correct, a fault light and the LCD OVERCURRENT ALARM OVERCURRENT ALARM
display will indicate the problem. LEVEL: OFF DELAY: 2.0 SEC.
Range: 100 - 300%, OFF Range: 1.0 - 20.0 SEC., OFF
Increments of 1 Increments of 0.1
SP3.1 Imbalance Alarm Level: This is an advance
warning of a phase imbalance problem. The OVERCURRENT TRIP OVERCURRENT TRIP
LEVEL: OFF DELAY: 2.0 SEC.
problem may not be a fault in the motor, but
Range: 100 - 300%, OFF Range: 1.0 - 20.0 SEC.
merely caused by imbalanced voltages. Increments of 1 Increments of 0.1

PHASE LOSS TRIP PHASE LOSS TRIP


• Imbalance Alarm Delay: The amount of time : DISABLED DELAY: 0.1 SEC.
the imbalance condition must exist before an Options: Enabled or Disabled Range: 0 - 20.0 SEC.
Increments of 0.1
alarm occurs.
PHASE ROTATION PHASE ROTATION
SP3.2 Imbalance Trip Level: This will trip the motor DETECTION: ENABLED : ABC
on excessive phase imbalance. The trip level
should be programmed to a higher value than the
alarm level.
* GROUND FAULT ALARM GROUND FAULT ALARM
LEVEL: OFF DELAY: 0.1 SEC.
• Imbalance Trip Delay: The amount of time the
Range: 5 - 90%, OFF Range: 0.1 - 20.0 SEC.
imbalance condition must exist before a trip will Increments of 1 Increments of 0.1
occur.
* GROUND FAULT LOSET GROUND FAULT LOSET
TRIP LEVEL: OFF TRIP DELAY: 0.5 SEC
SP3.3 Undercurrent Alarm Level: Typically used to Range: 5 - 90%, OFF Range: 0.1 - 20.0 SEC., OFF
warn of possible load loss, a coupling breaking or Increments of 1 Increments of 0.1
other mechanical problems.
GROUND FAULT HISET GROUND FAULT HISET
* TRIP LEVEL: OFF TRIP DELAY: 0.008 SEC.
• Undercurrent Alarm Delay: The amount of time Range: 5 - 90%, OFF Range: 0.008 - 0.250 SEC.
the undercurrent condition must exist before an Increments of 1 Increments of 0.002

alarm will occur. OVERVOLTAGE ALARM OVERVOLTAGE ALARM


LEVEL: OFF DELAY: 1.0 SEC.
SP3.4 Overcurrent Alarm Level: Typically used to Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
Increments of 1 Increments of 0.1
indicate when the motor is overloaded. This
feature can be used to either stop the feed to the OVERVOLTAGE TRIP OVERVOLTAGE TRIP
LEVEL: OFF DELAY: 2.0 SEC.
equipment or warn operators of an overload Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
condition. Increments of 1 Increments of 0.1

UNDERVOLTAGE ALARM UNDERVOLTAGE ALARM


• Overcurrent Alarm Delay: The amount of time LEVEL: OFF DELAY: 1.0 SEC.
the overcurrent condition must exist before an Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
Increments of 1 Increments of 0.1
alarm will occur.
UNDERVOLTAGE TRIP UNDERVOLTAGE TRIP
LEVEL: OFF DELAY: 2.0 SEC.
Range: 5 - 30%, OFF Range: 1.0 - 30.0 SEC.
Increments of 1 Increments of 0.1

LINE FREQUENCY TRIP LINE FREQUENCY TRIP


WINDOW: DISABLED DELAY: 1.0 SEC.
Range: 0 - 6, Disabled Range: 1.0 - 20.0 SEC.
Increments of 1 Increments of 0.1

- 38 -
2.3 - 7.2kV

SP.3 Phase & Ground Settings (Setpoint Page 3)


MENU
(Hit DOWN ARROW two times)

PAGE 3 PHASE & POWER FACTOR LEAD P/F LEAD ALARM


GROUND SETTINGS P/F ALARM: OFF DELAY: 1 SEC.
Range: .01 - 1.00, OFF Range: 1 - 120 SEC
Increments of .01 Increments of 1

POWER FACTOR LEAD P/F LEAD TRIP


P/F TRIP: OFF DELAY: 1.0 SEC.
Range: .01 - 1.00, OFF Range: 1 - 120 SEC.
SP3.5 Overcurrent Trip Level: Typically used to Increments of .01 Increments of 1
indicate the motor is severely overloaded and at
POWER FACTOR LAG P/F LAG ALARM
which point a trip occurs. P/F ALARM: OFF DELAY: 1.0 SEC.
Range: .01 - 1.00, OFF Range: 1 - 120 SEC.
Increments of .01 Increments of 1
• Overcurrent
Trip Delay: The POWER FACTOR LAG P/F LAG TRIP
amount of time P/F TRIP: OFF DELAY: 1.0 SEC.
Range: .01 - 1.00, OFF Range: 1 - 120 SEC.
the overcurrent Increments of .01 Increments of 1
condition must
POWER DEMAND
exist before a trip PERIOD: 10 MINUTES
will occur. Range: 1 - 60 Minutes
Increments of 1

SP3.6 Phase Loss Trip: When enabled, the


KW DEMAND ALARM
soft starter will trip the motor off-line upon a loss PICKUP: OFF KW
of phase power. Range: OFF, 1 - 100000
Increments of 1

• Phase Loss Trip Delay: The amount of time the KVA DEMAND ALARM
phase loss condition must exist before a trip will PICKUP: OFF KVA
Range: OFF, 1 - 100000
occur. Increments of 1

SP3.7 Phase Rotation Detection: The soft starter is KVAR DEMAND ALARM
continuously monitoring the phase rotation. Upon PICKUP: OFF KVAR
a start command, a trip will occur if it detects a Range: OFF, 1 - 100000
Increments of 1
change in the phase rotation.
AMPS DEMAND ALARM
• Phase Rotation: Must be ABC only. This PICKUP: OFF AMPS
setpoint monitors the wiring to ensure that the Range: OFF, 1 - 100000
Increments of 1
phase rotation is correct. To view the present
phase rotation, go to Metering Page1, screen SP3.10 * Ground Fault Hiset Trip Level: Used to trip
number 4 on page 61. the motor (within milliseconds) upon detecting a
high level of ground current leakage. This
SP3.8 * Ground Fault Alarm: Typically used to warn of setpoint is intended to detect low impedance
low level ground current leakage faults.

• * Ground Fault Alarm Delay: The amount of • *Ground Fault Hiset Trip Delay: The amount of
time that the ground fault condition must exist time that the ground fault condition must exist
before an alarm will occur. before a trip will occur.

SP3.9 * Ground Fault Loset Trip Level: Typically SP3.11 Overvoltage Alarm Level: Typically used to
used to trip the motor on a low level of ground indicate when the line voltage is too high. This is
current leakage. This setpoint is intended to an alarm level.
detect high impedance faults.
• Overvoltage Alarm Delay: The amount of time
• * Ground Fault Loset Trip Delay: The amount that the overvoltage condition must exist before a
of time that the ground fault condition must exist trip will occur.
before a trip will occur.

*Ground Fault Option must be installed


- 39 -
2.3 - 7.2kV

SP3.12 Overvoltage Trip Level: Typically used to SP3.18 Power Factor Lag Alarm: Typically used to
indicate that the line voltage is too high and at indicate a lagging power factor.
which point a trip occurs
• Power Factor Lag Alarm Delay: The amount
• Overvoltage Trip Delay: The amount of time of time that the power factor lagging condition
that the overvoltage condition must exist before a must exist beyond the window before a trip will
trip will occur. occur.

SP3.13 Undervoltage Alarm Level: Typically used to SP3.19 Power Factor Lag Trip: The acceptable
indicate when the line voltage is too low. This is amount of power factor lag before a trip is
an alarm level. generated.

• Undervoltage Alarm Delay: The amount of • Power Factor Lag Delay: The amount of time
time that the overvoltage condition must exist that the power factor lag condition must exist
before a trip will occur. beyond the window before a trip will occur.

SP3.14 Undervoltage Trip Level: Typically used to SP3.20 Power Demand Period: The controller
indicate that the line voltage is too low and at measures the demand of the motor for several
which point a trip occurs parameters (current, kW, kVAR, kVA). The
demand values of motors assists in energy
• Undervoltage Trip Delay: The amount of time management programs where processes may
that the undervoltage condition must exist before be altered or scheduled to reduce overall
a trip will occur. demand. Demand is calculated by a
programmed amount of time where current, kW,
SP3.15 Line Frequency Trip Window: The acceptable kVAR and kVA samples are taken and then
amount of drift above or below the line frequency averaged and stored to assess demand.
(in Hz) before a trip is generated.

• Line Frequency Trip Delay: The amount of


time that the frequency drift condition must exist
beyond the window before a trip will occur.

SP3.16 Power Factor Lead Alarm: Typically used to


indicate a leading power factor.

• Power Factor Lead Alarm Delay: The amount


of time that the power factor lead condition must
exist beyond the window before a trip will occur.

SP3.17 Power Factor Lead Trip: The acceptable


amount of power factor lead before a trip is
generated.

• Power Factor Lead Delay: The amount of time


that the power factor lead condition must exist
beyond the window before a trip will occur.

- 40 -
2.3 - 7.2kV
SP.4 Relay Assignment (Setpoint Page 4)
PHASE REVERSAL I/B ALARM
MENU 1ST: TRIP 1ST: ALARM

(Hit DOWN ARROW three times)

OVERVOLTAGE TRIP STATOR RTD ALARM


PAGE 4 RELAY O/L TRIP 1ST: TRIP 1ST: NONE
ASSIGNMENT 1ST: TRIP ONLY
Range: TRIP (AUX1),
ALARM (AUX2), AUX3,
AUX4
UNDERVOLTAGE TRIP NON-STATOR RTD ALARM
1ST: TRIP 1ST: NONE
I/B TRIP
1ST: TRIP

POWER FACTOR TRIP RTD FAILURE ALARM


1ST: TRIP 1ST: NONE
S/C TRIP
1ST: TRIP ONLY

TACH ACCEL TRIP


SELF-TEST FAIL
1ST: NONE
1ST: TRIP
OVERCURRENT TRIP
1ST: TRIP

INHIBITS TRIP
1ST: TRIP THERMAL REGISTER
STATOR RTD TRIP 1ST: ALARM
1ST: TRIP

TCB FAULT
1ST: TRIP U/V ALARM
NON-STATOR RTD TRIP 1ST: ALARM
1ST: TRIP

EXTERNAL INPUT #2
1ST: NONE O/V ALARM
G/F HI SET TRIP 1ST: ALARM
1ST: TRIP

DUAL RAMP
1ST: NONE POWER FACTOR ALARM
G/F LO SET TRIP 1ST: NONE
1ST: TRIP

THERMOSTAT
1ST: TRIP KW DEMAND ALARM
PHASE LOSS TRIP 1ST: NONE
1ST: TRIP

O/L WARNING
1ST: ALARM KVA DEMAND ALARM
ACCEL. TIME TRIP 1ST: NONE
1ST: TRIP ONLY

OVERCURRENT ALARM
1ST: ALARM
KVAR DEMAND ALARM
START CURVE TRIP
1ST: NONE
1ST: TRIP ONLY

SCR FAIL SHUNT ALARM


1ST: NONE
AMPS DEMAND ALARM
OVER FREQUENCY TRIP 1ST: NONE
1ST: TRIP

GROUND FAULT ALARM


1ST: ALARM
TIMED OUTPUT
UNDER FREQUENCY TRIP 1ST: NONE
1ST: TRIP

UNDERCURRENT ALARM
1ST: NONE
RUN DELAY TIME
I*I*T START CURVE 1ST: NONE
1ST: TRIP

MOTOR RUNNING
LEARNED START CURVE 1ST: AUX3 AT SPEED
1ST: TRIP 1ST: AUX4

- 41 -
2.3 - 7.2kV

SP.4 Relay Assignment (Setpoint Page 4)


(Security Level: 2)

All of the protection functions of the MVC Plus are user programmable to
an output relay. The factory will ship with all tripping functions assigned
to TRIP (AUX1) relay, and all alarm functions to ALARM (AUX2) relay.
Note: AUX1 - 4 are Factory Set and should not be changed.

SP4.1 The following is a list of all the user programmable functions.

Note: The 1st Relay Assignments are factory defaults and should not be changed.

FUNCTIONS RELAY ASSIGNMENTS


1st 2nd 3rd
IMBALANCE TRIP TRIP (AUX1) NONE NONE
SHORT CIRCUIT TRIP TRIP (AUX1) NONE NONE
OVERCURRENT TRIP TRIP (AUX1) NONE NONE
STATOR RTD TRIP TRIP (AUX1) NONE NONE
NON-STATOR RTD TRIP TRIP (AUX1) NONE NONE
GROUND FAULT HI SET TRIP* TRIP (AUX1) NONE NONE
GROUND FAULT LO SET TRIP* TRIP (AUX1) NONE NONE
PHASE LOSS TRIP TRIP (AUX1) NONE NONE
OVER FREQUENCY TRIP TRIP (AUX1) NONE NONE
UNDER FREQUENCY TRIP TRIP (AUX1) NONE NONE
I*I*T START CURVE TRIP (AUX1) NONE NONE
LEARNED START CURVE TRIP (AUX1) NONE NONE
PHASE REVERSAL TRIP (AUX1) NONE NONE
OVERVOLTAGE TRIP TRIP (AUX1) NONE NONE
UNDERVOLTAGE TRIP TRIP (AUX1) NONE NONE
POWER FACTOR TRIP TRIP (AUX1) NONE NONE
TACH ACCEL TRIP NONE NONE NONE
INHIBITS TRIP TRIP (AUX1) NONE NONE
TCB FAULT TRIP (AUX1) NONE NONE
EXTERNAL INPUT 2 NONE NONE NONE
DUAL RAMP NONE NONE NONE
THERMOSTAT TRIP (AUX1) NONE NONE
OVERLOAD WARNING ALARM (AUX2) NONE NONE
OVERCURRENT ALARM ALARM (AUX2) NONE NONE
SCR FAIL SHUNT ALARM ALARM (AUX2) NONE NONE
GROUND FAULT ALARM* ALARM (AUX2) NONE NONE
UNDERCURRENT ALARM NONE NONE NONE
MOTOR RUNNING AUX3 NONE NONE
IMBALANCE ALARM ALARM (AUX2) NONE NONE
STATOR RTD ALARM NONE NONE NONE
NON-STATOR RTD ALARM NONE NONE NONE
RTD FAILURE ALARM NONE NONE NONE
SELF TEST FAIL TRIP (AUX1) NONE NONE
THERMAL REGISTER ALARM (AUX2) NONE NONE
U/V ALARM ALARM (AUX2) NONE NONE
O/V ALARM ALARM (AUX2) NONE NONE
POWER FACTOR ALARM NONE NONE NONE
KW DEMAND ALARM NONE NONE NONE
KVA DEMAND ALARM NONE NONE NONE
KVAR DEMAND ALARM NONE NONE NONE
AMPS DEMAND ALARM NONE NONE NONE
TIMED OUTPUT NONE NONE NONE
RUN DELAY TIME NONE NONE NONE
AT SPEED AUX4 NONE NONE
*Ground fault option must be installed
- 42 -
2.3 - 7.2kV

SP.5 Relay Configuration (Setpoint Page 5)


(Security Level: 2)
MENU
In Setpoint Page 5 the user
(Hit DOWN ARROW four times)
can configure the four output
relays as either fail-safe or
PAGE 5 RELAY TRIP (AUX1) RELAY TRIP (AUX1) RELAY
non fail-safe and latching or CONFIGURATION FAIL-SAFE: NO LATCHED: YES
non-latching.
Options: Yes or No

SP5.1 When a relay has been configured


ALARM (AUX2) RELAY ALARM (AUX2) RELAY
as fail-safe and power is applied, FAIL-SAFE: NO LATCHED: NO
the relay will be energized. The
relay will then de-energize when
an event occurs or if the power AUX 3 RELAY AUX3 RELAY
fails. Note: The relays in the FAIL-SAFE: NO LATCHED: NO
controller will not prevent a start
sequence unless they are wired in
as interlocks. If power is lost, the AUX4 RELAY AUX4 RELAY
motor power is also lost. FAIL-SAFE: NO LATCHED: NO

SP5.2 A relay configured as non-latching


will reset itself when the cause of AUX5 RELAY AUX5 RELAY
the trip event is not continuous. FAIL-SAFE: NO LATCHED: NO
The TRIP (AUX1) relay should
always be programmed for
latching, because this trip should AUX6 RELAY AUX6 RELAY
require a visual inspection of the FAIL-SAFE: NO LATCHED: NO
motor and starter before issuing a
manual reset to release the relay
after a trip has been stored.
AUX7 RELAY AUX7 RELAY
FAIL-SAFE: NO LATCHED: NO

AUX8 RELAY AUX8 RELAY


FAIL-SAFE: NO LATCHED: NO

- 43 -
2.3 - 7.2kV

SP.6 User I/O Configuration (Setpoint Page 6)


(Security Level: 2)

MENU
(Hit DOWN ARROW five times)

ENABLED
PAGE 6 USER I/O TACHOMETER SCALE MANUAL TACH SCALE
CONFIGURATION SELECTION: DISABLED 4.0 mA: 0 RPM
Options: ENABLED or Range: 0-3600
DISABLED Increments of 5

MANUAL TACH SCALE


20.0 mA: 2000 RPM
Range: 0-3600
Increments of 5
TACH ACCEL TRIP MODE
SELECT: DISABLED
TACH RAMP TIME
: 20 SEC
Range: 1 - 120 SEC.,
Disabled
Increments of 1

TACH UNDERSPEED TRIP


PT: 1650 RPM
Range: 0 - 3600
Increments of 5

TACH OVERSPEED TRIP


PT: 1850 RPM
Range: 0 - 3600
Increments of 5

TACH ACCEL TRIP


DELAY: 1 SEC
Options: UNDERSPEED,
OVERSPEED or DISABLED Range: 1 - 60
Increments of 1

ANALOG OUTPUT #1 ANALOG OUTPUT #1 ANALOG OUTPUT #1


:RMS CURRENT 4ma: 0 20mA: 250
Range: Range: 0-65535 Range: 0-65535
Analog Output Range Increments of 1 Increments of 1
RPM 0 - 3600
Hottest Bearing 0 - 200°C
Hottest Stator RTD 0 - 200°C
RMS Current 0 - 6500A
% Motor Load 0 - 1000%
KW 0-30000 KW
OFF
Increments of 1

ANALOG OUTPUT #2 ANALOG OUTPUT #2 ANALOG OUTPUT #2


:% MOTOR LOAD 4mA: 0 20mA: 1000
Range: See Analog Output #1 Range: 0-1000% Range: 0-1000%
Increments of 1 Increments of 1 Increments of 1

USER PROGRAMMABLE
EXTERNAL INPUTS

Continued...

- 44 -
2.3 - 7.2kV

SP.6 User I/O Configuration (Setpoint Page 6)


(Security Level: 2)
The controller can be configured to accept a tachometer
feedback signal through the 4-20mA input and has two
options available for scaling the tachometer input.

SP6.1 The first screen of setpoint page 6 is SP6.3 The controller provides two 4-20mA analog
TACHOMETER SCALE SELECTION. When this outputs. Each analog output is independent of
is set to ENABLED, the user will need to input the other and can be assigned to monitor
the tachometer scale of the 4-20mA input range. different functions. The available output ranges
are RPM, Hottest Non-Stator (Bearing) RTD,
• Manual Tach Scale 4.0 mA: The unit is Hottest Stator RTD, RMS current, or % Motor
looking for an RPM value to assign to the lowest Load.
point on the scale. This value should represent
the motor at zero speed. • Analog Output #1 – Select a function from the
available five options to be transmitted from the
• Manual Tach Scale 20.0 mA: The unit is 4-20mA output. Note: If selecting RPM, the
looking for an RPM value to assign to the Tachometer feedback input signal must be
highest point on the scale. This value should present in order for the controller to give proper
represent the motor at full speed. output. If selecting RTD, the RTD option must
be installed and an RTD input signal must be
SP6.2 Tach Accel Trip Mode Select: When enabled, present for a proper output to be given from the
the underspeed or overspeed must be selected analog output.
for the Tach Accel Trip. If underspeed is • Analog Output #1 (4 mA): Enter a value that
selected, only the Tach Underspeed Trip Point the 4mA level will represent for the selected
will be used. If overspeed is selected only the function; typically this value should be 0.
Tach Overspeed Trip Point will be used. • Analog Output #1 (20 mA): Enter a value that
the 20mA level will represent for the selected
• Tach Ramp Time: This is the duration of time function.
before the tachometer begins to sample.
SP6.4 Analog Output #2 – All of the setpoints and
• Tach Underspeed Trip: The minimum value of setup screens for Analog Output #2 are the
motor RPM which must be achieved before the same as those for Analog Output #1.
Tach Ramp Time sample is taken.

• Tach Overspeed Trip: The maximum motor


RPM allowed when the Tach Ramp Time sample
is taken.

• Tach Accel Trip Delay: The duration of time


that the Tach Accel trip condition must persist
before a trip is generated.

- 45 -
2.3 - 7.2kV

SP.6 User I/O Configuration (Setpoint Page 6)


(Security Level: 2)
USER TCB FAULT NAME EXT. INPUT #1 TCB FAULT TCB FAULT
PROGRAMMABLE SELECT: ENABLED TCB FAULT TYPE: NORMALLY OPEN TIME DELAY: 1 SEC.
EXTERNAL Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC
INPUTS Normally Closed Increments of 1
(Continued)

EXTERNAL INPUT #2 NAME EXT INPUT #2 EXTERNAL INPUT #2 EXTERNAL INPUT #2


SELECT: DISABLED TYPE: NORMALLY OPEN TIME DELAY: 0 SEC.
Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC.
Normally Closed Increments of 1

SECOND RAMP NAME EXT INPUT #3 SECOND RAMP SECOND RAMP


SELECT: DUAL RAMP SECOND RAMP TYPE: NORMALLY OPEN TIME DELAY: 0 SEC.
Options: Enabled, Disabled or See text for directions Options: Normally Open or Range: 0 - 60 SEC
Dual Ramp Normally Closed Increments of 1

THERMOSTAT NAME EXT INPUT #4 THERMOSTAT THERMOSTAT


SELECT: ENABLED THERMOSTAT TYPE: NORMALLY CLOSED TIME DELAY: 1 SEC.
Options: Enabled or Disabled See text for directions Options: Normally Open or Range: 0 - 60 SEC.
Normally Closed Increments of 1

SP6.5 User Programmable External Inputs: The


controller provides up to 4 digital external inputs
which are individually programmable. A
description name can be assigned to each
individual input for easy identification.

• External Input #1: Factory programmed for • External Input #3: The setup screens and
TCB Fault. setpoints for External Input #3 includes the
option of being configured for Dual Ramp. In
• External Input #2: If used, this setpoint must Dual Ramp mode, the initial contact setting is
be enabled. the same as the START RAMP #1. Upon a
change in input contact state, the controller will
• Name Ext. Input #2: The user can assign a switch over to START RAMP #2 and use that
description name to the input to easily identify setting for start control mode. Note: The start
the cause of external trip or alarm. Up to 15 RAMP types should only be switched while the
characters including spaces can be used to motor is stopped. In Setpoint Page 4 Relay
assign the name. Assignments, do not assign any output relay to
this function. The controller will ship with
• External Input #2 Type: The external input can External input #3 programmed for dual ramp. If it
be set as either a normally open or normally is not needed, disable the dual ramp.
closed contact.
• External Input #4 – These input screens are for
• External Input #2 Time Delay: Upon a change the thermostat input and can be enabled or
in contact setting, the unit will wait the disabled. Note: It is recommended that this
programmed amount of time before generating function remain enabled. If the thermostat
an output. If no delay is needed, then input 0 indicates an over temperature condition, the
seconds. The controller will post an event upon controller will trip the motor.
seeing a change in state.

- 46 -
2.3 - 7.2kV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)
MENU
(Hit DOWN ARROW six times)

PAGE 7 CUSTOM CUSTOM ACCEL CURVE


ACCELERATION CURVE : DISABLED
Range: DISABLED,
CURVE A, B or C
SP7.1 Setpoint Page 7 allows the user to custom CURVE A VOLTAGE
CUSTOM CURVE A LEVEL 1: 25%
design the acceleration curve (start curve) to the
Range: 0 - 100%
specific application. The user can custom Increments of 1
design up to three different curves in the
CURVE A RAMP
controller. Only one curve can be active TIME 1: 2 SEC
(enabled) at a time. Each of the three curves Range: 1 - 60 SEC
allow for eight voltage plotting points, with Increments of 1

corresponding ramp times and a current limit CURVE A VOLTAGE


setting. LEVEL 2: 30%
Range: 0 - 100%
Note: Each successive voltage level must be Increments of 1
programmed to a voltage level equal to or CURVE A RAMP
greater than the previous level. All eight levels of TIME 2: 2 SEC.
voltages must be programmed and the eighth Range: 1 - 60 SEC
Increments of 1
level has been preset at 100%.
CURVE A VOLTAGE
LEVEL 3: 37%
• If Custom Accel Curve has been set to curve A,
Range: 0 - 100%
B or C on this page, the controller will override Increments of 1
the Start Control Mode selected in Setpoint
Page 2, (even if Start Control Mode in Setpoint CURVE A RAMP
TIME 3: 2 SEC.
Page 2 has not been set to Custom Accel
Range: 1 - 60 SEC
Curve). Increments of 1
Note: Setpoint Page 7 has a security level 3
CURVE A VOLTAGE
requirement. LEVEL 4: 45%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 4: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE A VOLTAGE
LEVEL 5: 55%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE A VOLTAGE
LEVEL 6: 67%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE A VOLTAGE
LEVEL 7: 82%
Range: 0 - 100%
Increments of 1

CURVE A RAMP
TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

- 47 -
2.3 - 7.2kV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)

CURVE A VOLTAGE CURVE B VOLTAGE


CUSTOM CURVE A LEVEL 8: 100% CUSTOM CURVE B LEVEL 7: 82%
Range: 0 - 100% Range: 0 - 100%
Increments of 1 Increments of 1

CURVE A RAMP CURVE B RAMP


TIME 8: 2 SEC TIME 7: 2 SEC.
Range: 1 - 60 SEC Range: 1 - 60 SEC
Increments of 1 Increments of 1

CURVE A CURRENT
LIMIT: 350% FLA CURVE B VOLTAGE
LEVEL 8: 100%
Range: 200 - 600%
Increments of 10 Range: 0 - 100%
Increments of 1

CURVE B RAMP
CURVE B VOLTAGE TIME 8: 2 SEC
CUSTOM CURVE B LEVEL 1: 25%
Range: 1 - 60 SEC
Range: 0 - 100% Increments of 1
Increments of 1
CURVE B CURRENT
CURVE B RAMP LIMIT: 350% FLA
TIME 1: 2 SEC.
Range: 200 - 600%
Range: 1 - 60 SEC Increments of 10
Increments of 1

CURVE B VOLTAGE
LEVEL 2: 30% CUSTOM CURVE C CURVE C VOLTAGE
Range: 0 - 100% LEVEL 1: 25%
Increments of 1 Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 2: 2 SEC. CURVE C RAMP
Range: 1 - 60 SEC TIME 1: 2 SEC.
Increments of 1 Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 3: 37% CURVE C VOLTAGE
Range: 0 - 100% LEVEL 2: 30%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 3: 2 SEC. CURVE C RAMP
Range: 1 - 60 SEC TIME 2: 2 SEC.
Increments of 1
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 4: 45% CURVE C VOLTAGE
Range: 0 - 100% LEVEL 3: 37%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 4: 2 SEC.
CURVE C RAMP
Range: 1 - 60 SEC TIME 3: 2 SEC.
Increments of 1
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 5: 55%
CURVE C VOLTAGE
Range: 0 - 100% LEVEL 4: 45%
Increments of 1
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 5: 2 SEC.
CURVE C RAMP
Range: 1 - 60 SEC
Increments of 1 TIME 4: 2 SEC.
Range:1 - 60 SEC
Increments of 1
CURVE B VOLTAGE
LEVEL 6: 67%
CURVE C VOLTAGE
Range: 0 - 100%
Increments of 1 LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE B RAMP
TIME 6: 2 SEC.
Range: 1 - 60 SEC CURVE C RAMP
Increments of 1 TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

- 48 -
2.3 - 7.2kV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)

SP7.1 Setpoint Page 7 allows the user to custom


design the acceleration curve (start curve) to the CUSTOM CURVE C CURVE C VOLTAGE
LEVEL 6: 67%
specific application. The user can custom Range: 0 - 100%
design up to three different curves in the Increments of 1
controller. Only one curve can be active
(enabled) at a time. Each of the three curves CURVE C RAMP
has eight voltage levels, with corresponding TIME 6: 2 SEC.
Range: 1 - 60 SEC
ramp times and a current limit setting. Increments of 1
Note: Each successive voltage level must be
programmed to a voltage level equal to or CURVE C VOLTAGE
greater than the previous level. All eight levels of LEVEL 7: 82%
voltages must be programmed and the eighth Range: 0 - 100%
Increments of 1
level has been preset at 100%.
CURVE C RAMP
• If Custom Accel Curve has been set to curve A, TIME 7: 2 SEC.
B or C on this page, the controller will override Range: 1 - 60 SEC
Increments of 1
the Start Control Mode selected in Setpoint
Page 2, (even if Start Control Mode in Setpoint
CURVE C VOLTAGE
Page 2 has not been set to Custom Accel LEVEL 8: 100%
Curve). Range: 0 - 100%
Note: Setpoint Page 7 has a security level 3 Increments of 1
requirement.
CURVE C RAMP
TIME 8: 2 SEC.
Range: 1 - 60 SEC
Increments of 1

CURVE C CURRENT
LIMIT: 350% FLA
Range: 200 - 600%
Increments of 10

- 49 -
2.3 - 7.2kV
SP.8 Overload Curve Configuration (Setpoint Page 8)
(Security Level: 3)
MENU
(Hit DOWN ARROW seven times)

PAGE 8 OVERLOAD BASIC RUN RUN CURVE LOCKED RUN LOCKED ROTOR
CURVE CONFIGURATION OVERLOAD CURVE ROTOR TIME: O/L CLASS CURRENT: 600% FLA
Range: 1 - 30 SEC, O/L CLASS Range: 400 - 800%
Increments of 1
Configures the unit’s start and run
protection mode. The unit has COAST DOWN TIMER
TIME: DISABLED
independent start and run curve
Range:1 - 60 MIN, DISABLED
protection and the settings can be Increments of 1
based on the OL Class or set by the BASIC START START CURVE LOCKED START LOCKED ROTOR
motor’s locked rotor current and time. OVERLOAD CURVE ROTOR TIME: O/L CLASS CURRENT: 600% FLA
Range:1 - 30 SEC, O/L CLASS Range: 400 - 800%
Increments of 1 Increments of 10
SP8.1 Basic Run Overload Curve
• Run Curve Locked Rotor ACCELERATION TIME
Time: Set the locked rotor LIMIT: 30 SEC
time to the OL Class default Range:1 - 300 SEC, DISABLED
Increments of 1
chosen in Setpoint Page 1 or
set the time in seconds. This NUMBER OF STARTS PER
is the time the locked rotor HOUR: DISABLED
condition exists before a trip Range: 1 - 6, DISABLED
Increments of 1
occurs.
• Run Locked Rotor Current: TIME BETWEEN STARTS
The current the motor draws TIME: 15 MIN
with full voltage on the Range:1 - 60 MIN, DISABLED
Increments of 1
windings and no rotor
movement (as a percent of AREA UNDER CURVE MAX I*I*T START
PROTECTION: DISABLED : 368 FLA*FLA*SEC
motor FLA). Refer to the
Range: ENABLED or DISABLED Range:1 - 2500, FLA*Time (Sec)
nameplate data or contact the Increments of 1
motor manufacturer.
• Coast Down Timer: If CURRENT OVER LEARNED START CURVE TIME FOR SAMPLING
enabled, this prevents the CURVE: DISABLED BIAS: 10% : 30 SEC
Options: DISABLED, LEARN Range: 5 - 40% Range: 1 - 300 SEC
motor from restarting for the or ENABLED Increments of 1 Increments of 1
programmed amount of time,
after a stop command is given.

SP8.2 Basic Start Overload Curve


• Number of Starts per hour: If enabled, this
• Start Curve Locked Rotor Time: The locked
limits the maximum number of starts permitted
rotor time can be set to the OL Class default
per hour. This setpoint allows a maximum of 6
chosen in Setpoint Page 1 or to a specific time.
starts per hour. Contact motor manufacturer.
The overload condition must exist for the
• Time Between Starts: If enabled, the controller
programmed amount of time before a trip
prevents another start attempt until the
occurs.
programmed time has expired.
• Start Locked Rotor Current: The current the
motor draws with full voltage on the windings
and no motor movement (as a percent of motor
FLA). Refer to the motor nameplate data or
contact the motor manufacturer.
• Acceleration Time Limit: If the motor does not
enter run mode (reach at speed) within the
preset time, the unit trips on acceleration time
limit.

- 50 -
2.3 - 7.2kV
SP.9 RTD Option Configuration (Setpoint Page 9)
(Security Level: 3)
Please note, this is supplied as an option.
Contact factory for more information.
MENU Optional
(Hit DOWN ARROW eight times)
Ranges:
* 120 OHM NICKEL (NI)
PAGE 9 RTD USE NEMA TEMP FOR 100 OHM NICKEL (NI)
CONFIGURATION RTD VALUES: DISABLED 10 OHM COPPER (CU)
100 OHM PLATINUM (PT)
Options: ENABLED OR OFF
DISABLED
** OFF or 0 - 240C (32-464F) Example: ### C = ### F
# OF RTD’S USED FOR Increments of 1
STATOR: 4
*** STATOR A1, STATOR A2, STATOR B1, STATOR B2, STATOR C1, STATOR C2,
Range: 0 - 6 FRONT BEARING, BACK BEARING, BEARING BOX, AMBIENT, NONE
Increments of 1

RTD VOTING
: DISABLED
Options: ENABLED or
DISABLED

STATOR PHASE A1 TYPE RTD # 1 DESCRIPTION STATOR PHASE A1 ALARM STATOR PHASE A1 TRIP
: OFF STATOR PHASE A1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE A2 TYPE RTD # 2 DESCRIPTION STATOR PHASE A2 ALARM STATOR PHASE A2 TRIP
: OFF STATOR PHASE A2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE B1 TYPE RTD # 3 DESCRIPTION STATOR PHASE B1 ALARM STATOR PHASE B1 TRIP
: OFF STATOR PHASE B1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE B2 TYPE RTD # 4 DESCRIPTION STATOR PHASE B2 ALARM STATOR PHASE B2 TRIP
: OFF STATOR PHASE B2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

STATOR PHASE C1 TYPE RTD # 5 DESCRIPTION STATOR PHASE C1 ALARM STATOR PHASE C1 TRIP
: OFF STATOR PHASE C1 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: *** Range: ***

STATOR PHASE C2 TYPE RTD # 6 DESCRIPTION STATOR PHASE C2 ALARM STATOR PHASE C2 TRIP
: OFF STATOR PHASE C2 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

END BEARING TYPE RTD #7 DESCRIPTION END BEARING ALARM END BEARING TRIP
: OFF END BEARING LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

SHAFT BEARING TYPE RTD # 8 DESCRIPTION SHAFT BEARING ALARM SHAFT BEARING TRIP
: OFF SHAFT BEARING LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

RTD # 9 TYPE RTD # 9 DESCRIPTION RTD # 9 ALARM RTD # 9 TRIP


: OFF RTD # 9 LEVEL: OFF LEVEL: OFF
Range:* Range: *** Range: ** Range: **

RTD # 10 TYPE RTD # 10 DESCRIPTION RTD # 10 ALARM RTD # 10 TRIP


: OFF RTD # 10 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

RTD # 11 TYPE RTD # 11 DESCRIPTION RTD # 11 ALARM RTD # 11 TRIP


: OFF RTD #11 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

RTD # 12 TYPE RTD # 12 DESCRIPTION RTD # 12 ALARM RTD # 12 TRIP


: OFF RTD # 12 LEVEL: OFF LEVEL: OFF
Range: * Range: *** Range: ** Range: **

- 51 -
2.3 - 7.2kV

SP.9 RTD Option Configuration (Setpoint Page 9)


(Security Level: 3)
The controller is available with an optional RTD card that
provides 12 programmable RTDs which are individually
programmable for type. The available types are 100 ohm
platinum, 100 ohm nickel, 120 ohm nickel and 10 ohm
copper. Each RTD can be identified with a description name
of up to 15 characters (including spacing). Also, each
individual RTD has it own alarm and trip level.

SP9.1 Use NEMA Temp for RTD Value: When this


setpoint is enabled, the controller will use the NEMA
design insulation class to limit the maximum allowed
range of the alarm and trip level. The maximum
allowed temperature range is 240° C or (464°F).

SP9.2 # Of RTD’S Used for Stator: Up to six RTDs can be


assigned to monitor the stator of the motor.

SP9.3 RTD Voting: When this is enabled, the controller


will not post a trip until 2 RTD’s have exceeded the
trip level. This prevents nuisance RTD tripping.

SP9.4 Each of the 12 RTDs is configured in the following


manner. The first column is the RTD type, the
second column is the RTD description, the third
column is the alarm level, and the fourth column is
the trip level.
The first six RTDs have been pre-programmed with a
description name for the STATOR, with two RTDs per
phase. RTDs #1 & #2 have been named STATOR
PHASE A1 and A2 respectively. RTDs #3&4 are
named STATOR PHASE B1 and B2, RTDs #5&6 are
named STATOR PHASE C1 and C2. If other
description names are required, press the right arrow
button from the RTD Type screen to go the RTD
description screen. If no alarm or trip level is
required these setpoints can be turned off.

- 52 -
2.3 - 7.2kV

SP.10 Set Password (Setpoint Page 10)


(Security Level: 3) MENU
The controller has three levels of user programmable (Hit DOWN ARROW nine times)
setpoint screens. Level one setpoints do not require a
password because the data contained in level one is PAGE 10 SECURITY SET LEVEL 2
basic nameplate data and starter control. Level two SET PASSWORD PASSWORD: 100

setpoint screens require a three-digit password to Range: 000 - 999


configure the protection schemes. Level three setpoint
screens require a four-digit password to access the full SET LEVEL 3
PASSWORD: 1000
range of protection and starter schemes.
Range: 0000 - 9999

SP10.1 Set Level 2 Password: This level uses a 3-digit


password. The default level 2 password is 100.

SP10.2 Set Level 3 Password: Level three uses a 4-


digit password. The default level 3 password is
1000.

- 53 -
2.3 - 7.2kV

SP.11 Communications (Setpoint Page 11) MENU


(Security Level: 3) (Hit DOWN ARROW ten times)
SP11.1 Set Front Baud Rate: Configures the RS232
communications baud rate. PAGE 11 SET FRONT BAUD
COMMUNICATIONS RATE: 9.6 KB/SEC
SP11.2 Set Modbus Baud Rate: Configures the Range: 2.4, 4.8, 9.6, 19.2
modbus communications baud rate. 38.4 KB/SEC

SET MODBUS BAUD


SP11.3 Modbus Address Number: Assigns a Modbus RATE: 9.6 KB/SEC
address to the controller relay. Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC

SP11.4 Set Access Code: Assigns an access code to MODBUS ADDRESS


the Modbus addressing. Typically not used. NUMBER: 247
Range: 1 - 247
Increments of 1
SP11.5 Set Link Baud Rate: Configures the RS422
communications baud rate between the keypad SET ACCESS CODE
CODE: 1
operator and the CPU board. (For applications Range: 1 - 999
with remote keypad only.) Increments of 1

SET LINK BAUD


SP11.6 Remote Start/Stop: Allows the RS485 Modbus RATE: 38.4 KB/SEC
communications to start and stop the motor. Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
Contact factory for details.
REMOTE START/STOP:
DISABLED
Option: Enabled or Disabled

- 54 -
2.3 - 7.2kV
SP.12 System Setpoints (Setpoint Page 12)
(Security Level: 3)
MENU
(Hit DOWN ARROW eleven times)

PAGE 12 SYSTEM DEFAULT DISPLAY METERING DATA METERING DATA


SETPOINTS SCREEN PAGE #: 1 SCREEN #: 1
Enter Metering Page (1 - 4) Enter Metering
Number for display Screen Number for display

ALARMS RTD FAILURE ALARM


ALARM: DISABLED
Enabled or Disabled

THERMAL REGISTER THERMAL ALARM


ALARM: 90% DELAY: 10 SEC.
Range: Off, 40 - 95% Range: 1 - 20 SEC.
Increments of 1 Increments of 1

COLD STALL TIME


THERMAL REGISTER : O/L CLASS
SETUP INFORMATION
Range: O/L CLASS,
4 - 40 SEC
Increments of 1
HOT STALL TIME
: 1/2 O/L CLASS
Range: 1/2 O/L CLASS,
4 - 40 SEC
Increments of 1
STOPPED COOL DOWN
TIME: 30 MIN
Range: 10 - 300 MIN
Increments of 1

RUNNING COOL DOWN


TIME: 15 MIN
Range: 10 - 300 MIN
Increments of 1

RELAY MEASURED COOL


RATES: DISABLED
Range: ENABLED or
DISABLED

THERMAL REGISTER
MINIMUM: 15%
Range: 10 - 50%, OFF
Increments of 1

MOTOR DESIGN AMBIENT


TEMPERATURE: 40 C
Range: 10 - 90 C
Increments of 1

MOTOR DESIGN RUN


TEMPERATURE: 80% MAX
Range: 50 - 100% of Motor
Stator Max Temp.
Increments of 1%

MOTOR STATOR MAX


TEMPERATURE: INS CLS
Range: Insulation Class
10 - 240 C
Increments of 1

I/B INPUT TO THERMAL


REGISTER: ENABLED
Options: ENABLED or
DISABLED

USE CALCULATED K OR
ASSIGN: 7
Range: 1 - 50, ON

PRESS ENTER TO CLR


THERMAL REGISTER
- 55 -
2.3 - 7.2kV

SP.12 System Setpoints (Setpoint Page 12)


(Security Level: 3)
SP12.1 Default Display Screen: This setpoint group
allows the user to choose the default screen the • Thermal Register Minimum: Sets the value in
controller displays while the motor is running. the thermal register which represents a motor
Select the metering page number (1-3), then running at the nameplate current (with no
select the metering screen number. The range overheating or negative sequence currents
varies depending on the selected page. To present).
display a default screen, program the following • Motor Design Ambient Temperature: Use the
two setpoints: data from the motor manufacturer’s
• Metering Data Page#: Range is Page 1 - 3. specifications. When RTD option is supplied,
• Metering Data Screen#: If Page 1 is selected this setpoint will be the base point for the RTD
as the default page, then Screens 1- 10 are biasing of the Thermal Register.
available. If Page 2 Screens 1-29 are available. • Motor Design Run Temperature: Use the data
If Page 3 is selected then Screens 1-6 are from the motor manufacturer’s specifications.
available. (See Metering Menu, MP.1, for screen This setpoint defines the operating temperature
number assignment.) rise of the motor at full load amps or 100% load.
• Motor Stator Max Temperature: This
SP12.2 Alarms: Configures the RTD failure alarm (when represents the maximum temperature the stator
RTD option is included) and the thermal register insulation will withstand. The user may choose
alarm. to use the temperature setting of the insulation
• RTD Failure Alarm: If enabled, and an RTD class (selected in Setpoint Page 1) or enter a
shorts or open, an alarm occurs. (Only if RTD specific maximum temperature. This value
option is installed). should not exceed the stator’s insulation
• Thermal Register Alarm: Sets a level in the temperature. This maximum temperature
thermal register to generate an alarm when the represents 100% thermal capacity.
Thermal Register Capacity Used has exceeded • U/B Input to Thermal Register: When enabled
this level. it allows the controller to use the line current
• Thermal Alarm Delay: The amount of time imbalance information to bias the Thermal
that the Thermal Register Used must exceed Register.
the setpoint before an alarm condition will occur. • User Calculated K or Assign: When the
setpoint is set to ON the controller will calculate
SP12.3 Thermal Register Setup Information: This the k constant factor for biasing the thermal
setpoint group will configure the thermal register register, or the user may choose to assign the k
and indicate to the controller which inputs to value.
use when thermal modeling.
• Cold Stall Time: Enter the time from the motor SP12.4 Press Enter to CLR Thermal Register: Allows
manufacturer’s specification sheet or use the the level three password user to clear the
time defined by the OL Class. This setpoint is thermal register for emergency restarts.
used to define the thermal capacity of the motor.
• Hot Stall Time: Enter the amount of time
specified by the motor manufacturer or use half
of the time defined by the OL Class.
• Stopped Cool Down Time: The time the motor
requires to cool down after it has stopped. Use
only the data provided by the motor
manufacturer. This setpoint is used to configure
the cooling rate of the thermal register.
• Running Cool Down Time: The amount of
time the motor requires for cooling down while
running. Use only the data provided by the
motor manufacturer.
• Relay Measured Cool Rates: When the RTD
option is supplied, the controller can be
configured to use the measured cool rates from
the RTDs instead of the programmed settings.
This setpoint should only be enabled when the
RTD option is present.

- 56 -
2.3 - 7.2kV

SP.13 Calibration & Service (Setpoint Page 13)


(Security Level: Factory Use Only)

MENU
(Hit DOWN ARROW twelve times)

PAGE 13 CALIBRATION SET DATE AND TIME ENTER DATE (DDMMYYYY) ENTER TIME (hh:mm)
& SERVICE ##/##/## ##:## :##/##/#### :##:##
Range: D = 1 - 31, M = 1-12, Range: H = 00 - 23, M = 0 - 59
Y = 1970 - 2069 Increments of 1
Increments of 1
MODEL #: ######
FIRMWARE REV. #: ######

PRESS ENTER TO ACCESS


FACTORY SETTINGS

SP.13 Calibration & Service (Setpoint Page 13)


Certain screens are displayed for user information only,
such as: Current date and time, Model number and
Firmware revision number. Setpoint changes in this page
will only be accessible to factory personnel.
SP13.1 Set Date and Time: Displays the date and time.
• Enter Date (DDMMYYYY): Allows the factory
personnel to program the date for the controller in
the format shown.
• Enter Time (hh:mm): Allows the factory personnel
to program the time for the controller.

SP13.2 Model & Firmware #: Displays the model number


and firmware revision in the controller.

SP13.3 Press Enter to Access Factory Settings: Available


to qualified personnel.

- 57 -
2.3 - 7.2kV

Chapter 6 - Metering Pages


The unit offers performance metering which gives the user the ability to view
information about the motor and the soft starter.

6.1 Metering Page List


The following charts list each Metering Page and the functions within that page.
The applicable section of the manual is also referenced.

6.1.1 Metering Menu & Data (Metering Page 1)


Metering
Description of Display Screen
Page
Phase A, B, C and Ground Fault (Option) 1
Average current of the % of imbalance and the motor's RPM 2
Metering Menu & Data

Motor load as a percentage of motor FLA 3


Line frequency and present phase sequence 4
Page 1

Percentage of remaining Thermal Register 5


Thermal capacity required to start the motor 6
Average time required to start 7
Average current during start 8
2
Measured I T required to start the motor 9
Amount of time required to start the motor during the last successful start 10

6.1.2 Metering (Metering Page 2)


Metering
Description of Display Screen
Page
Phase A, B, C currents and Power Factor 1
Phase A, B, C currents and Ground Fault (Option) 2
Displays kW and kVA 3
Displays kVAR and Power Factor 4
Displays Peak ON and kW Demand 5
Metering
Page 2

Displays Peak ON and kVA Demand 6


Displays Peak ON and kVAR Demand 7
Displays Peak ON and Amps Demand 8
Clears Demand values 9
Displays Megawatt hours used 10
Press enter to clear statistics on MWH values 11

6.1.3 RTD Option Values (Metering Page 3)


Metering
Description of Display Screen
Page
Hottest stator RTD (#1 - 6) 1
Hottest non-stator RTD (#7 - 12) 2
Temperature of start phase A1 in °C and °F 3
RTD Values
Page 3

Maximum temperature for RTD #1 4


Same as Screens 3 - 4 for RTDs #2 - 12 5 - 26
Clear the maximum temperature register (Level 3 password required) 27
Measured running thermal stabilization time of motor (in minutes) 28
Measured stopped cooling time (to ambient) of motor (in minutes) 29

- 58 -
2.3 - 7.2kV
6.1.4 Status (Metering Page 4)
Metering
Description of Display Screen
Page
Current status 1
Amount of time remaining before an overload trip occurs 2
Page 4
Status
Amount of time remaining from a thermal inhibit signal 3
Coast down time remaining 4
Amount of time remaining before a start command can be given 5
Excessive number of starts per hour 6

6.1.5 Event Recorder (Metering Page 5)


Metering
Description of Display Screen
Page
Recorder

Displays the event with date and time (Up to 60 events) 1


Page 5
Event

Displays Phase A, B, C current values, Ground Fault (Option) at time of trip 1A


Displays Vab, Vbc, Vca and Power Factor at time of trip 1B

6.1.6 Last Trip (Metering Page 6)


Metering
Description of Display Screen
Page
Cause of last trip 1
Measured phase current 2
Last Trip
Page 6

Measured voltage and power factor 3


Imbalance percentage, the frequency and the kW 4
Hottest stator RTD temperature 5
Hottest non-stator RTD temperature 6

6.1.7 Statistics (Metering Page 7)


Metering
Description of Display Screen
Page
Accumulated total running hours 1
Clear the total running hour count 2
Total number of trips 3
Number of start and run overload trips since the last statistical data
4
clearing
Number of frequency trips and imbalance trips 5
Overcurrent trips 6
Stator and non-stator RTD trips 7
Ground fault hiset and loset trips 8
Acceleration time trips 9
Start under curve trips 10
Start over curve trips 11
Statistics
Page 7

2
I T start curve trips 12
Learned start curve trips 13
Fail shunt trip trips 14
Phase loss trip trips 15
Tach accel trip trips 16
Undervoltage and Overvoltage trips 17
Power Factor trips 18
Phase reversal trips 19
Exp Inp #1 20
Exp Inp #2 21
Exp Inp #3 22
Exp Inp #4 23
Press enter to clear statistics 24
- 59 -
2.3 - 7.2kV

6.2 Metering Menu


Push MENU key to toggle the screens between Setpoint Menu and Metering
Menu and follow the arrow keys to get to different screens.

MENU

METERING PAGE 1
CURRENT METERED DATA

METERING PAGE 2
VOLTAGE & POWER DATA

METERING PAGE 3
RTD VALUES

METERING PAGE 4
STATUS

METERING PAGE 5
EVENT RECORDER

METERING PAGE 6
LAST TRIP

METERING PAGE 7
STATISTICS

- 60 -
2.3 - 7.2kV

MP.1 Metering Data (Metering Page 1)


Displays the basic current metering data: MENU
Screen 1: Phase A, B, C and ground fault (option)
current.

METERING PAGE 1 IA: ###### IB: ######


Screen 2: Displays the average current, percent of CURRENT METERED DATA IC: ###### G/F: #####
Screen 1
imbalance and the motor’s RPM (available
with tachometer input)
I (AVG): ####
Screen 3: Displays the motor load in percent of motor Screen 2
I/B: ## % RPM: ####
FLA.

Screen 4: Displays the line frequency and the present


Phase Order. MOTOR LOAD % OF FLA
Screen 3
FLA: ### %

Screen 5: Displays the percent of the remaining


thermal register. In order for the motor to
successfully start, the percentage must be LINE FREQUENCY:: ##.##
Screen 4
greater than the thermal capacity required PHASE ORDER: ###
for a successful start.

Screen 6: Displays the thermal capacity required to THERMAL REGISTER


successfully start the motor. Screen 5
REMAINING: ### %

Screen 7: Displays the average time required to start.


THERMAL CAPACITY
Screen 8: Displays the average current during start. TO START: ### %
Screen 6

Screen 9: Displays the measured I2T required to start


the motor.
AVERAGE START TIME
Screen 7
TIME: ##.# SECS
Screen 10: Displays the amount of time required to
start the motor during the last successful
start.
AVG START CURENT
Screen 8
: ###### AMPS

I*I*T TO START
Screen 9
I*I*T: #######

LAST START
Screen 10
TIME: ##.# SEC

- 61 -
2.3 - 7.2kV

MENU
MP.2 Metering (Metering Page 2)
Screen 1
Displays the statistical voltage metering informa-
METERING PAGE 2 Vab: ### Vbc: ###
tion. VOLTAGE & POWER DATA Vca: ### P/F: ## #.##

Screen 1: Displays Phase A, B, C and Power Factor. Screen 2


IA: ##### IB: #####
Note: P/F: N/A Motor stopped IC: ##### G/F:###.#
P/F: LG #.## (Lagging)
P/F: LD #.## (Leading) Screen 3
kW: #####
Screen 2: Displays Phase A, B, C and Ground Fault kVA: #####
Current.
Screen 4
kVAR: #####
Screen 3: Displays kW and kVA. P/F: ## #.##

Screen 4: Displays kVAR and Power Factor. Screen 5


PEAK ON: ##/## ##:##
kW: #####
Screen 5: Displays Peak On and kW demand.
Screen 6
Screen 6: Displays Peak On and kVA demand. PEAK ON: ##/## ##:##
kVA: #####
Screen 7: Displays Peak On and kVAR demand.
Note: P/F: N/A Motor stopped Screen 7
PEAK ON: ##/## ##:##
P/F: LG #.## (Lagging)
kVAR: #####
P/F: LD #.## (Leading)
Screen 8
Screen 8: Displays Peak On and Amps demand. PEAK ON: ##/## ##:##
AMPS: #####
Screen 9: Clears Demand Values.
Screen 9
PRESS ENTER TO CLEAR
Screen 10: Displays the Megawatthours used. DEMAND VALUES

Screen 11: Press Enter to clear statistics on MWH Screen 10


values. MWH USED
: #####

Screen 11
PRESS ENTER TO CLEAR
MWH VALUES

- 62 -
2.3 - 7.2kV
METERING PAGE 3 HOTTEST STATOR
RTD VALUES RTD#: # @ ### C

MP.3 RTD Values (Metering Page 3) Screen 2


Displays the RTD information (when RTD option is HOTTEST NON-STATOR
RTD#: # @ ### C
supplied)
Screen 3 Screen 4
Screen 1: Displays the hottest stator RTD (#1 - 6 STATOR PHASE A1 MAX TEMP SINCE
depending upon number of RTDs used for RTD #1: ### C = ### F CLEAR RTD #1: ### C
stator).
Screen 5 Screen 6
Screen 2: Displays the hottest non-stator RTD (#7-12 STATOR PHASE A2 MAX TEMP SINCE
if #1-6 is used for stator). RTD #2: ### C = ### F CLEAR RTD #2: ### C

Screen 3: Displays the temperature of stator phase A1 Screen 7 Screen 8


in °C and °F. STATOR PHASE B1 MAX TEMP SINCE
RTD #3: ### C = ### F CLEAR RTD #3: ### C

Screen 4: Displays the maximum temperature for RTD Screen 9 Screen 10


#1 since the last command to clear the STATOR PHASE B2 MAX TEMP SINCE
thermal register. RTD #4: ### C = ### F CLEAR RTD #4: ### C

Screen 5 - 26: Same as Screens 3 - 4 for RTDs #2 - Screen 11 Screen 12


#12 STATOR PHASE C1 MAX TEMP SINCE
RTD #5: ### C = ### F CLEAR RTD #5: ### C
Screen 27: Allows the user to clear the maximum
temperature register upon entering the Screen 13 Screen 14
setpoint level 3 password. STATOR PHASE C2 MAX TEMP SINCE
RTD #6: ### C = ### F CLEAR RTD #6: ### C

Screen 28: Displays the measured run cool time in Screen 15 Screen 16
minutes. END BEARING MAX TEMP SINCE
RTD #7: ### C = ### F CLEAR RTD #7: ### C
Screen 29: Displays the measured stopped cool time in
minutes. Screen 17 Screen 18
SHAFT BEARING MAX TEMP SINCE
RTD #8: ### C = ### F CLEAR RTD #8: ### C

Screen 19 Screen 20
RTD #9 MAX TEMP SINCE
RTD #9: ### C = ### F CLEAR RTD #9: ### C

Screen 21 Screen 22
RTD #10 MAX TEMP SINCE
RTD #10: ### C = ### F CLEAR RTD #10: ### C

Screen 23 Screen 24
RTD #11 MAX TEMP SINCE
RTD #11: ### C = ### F CLEAR RTD #11: ### C

Screen 25 Screen 26
RTD #12 MAX TEMP SINCE
RTD #12: ### C = ### F CLEAR RTD #12: ### C

Screen 27
PRESS ENTER TO
CLEAR MAX TEMP REGS

Screen 28
MEASURED RUN COOL
TIME: ### MIN

Screen 29
MEASURED STOPPED
COOL TIME: ### MIN

- 63 -
2.3 - 7.2kV

MP.4 Status (Metering Page 4)


Displays the present status of the soft start.
MENU
Screen 1: Displays the present state of the unit as
follows: Screen 1 (See note at left)
METERING PAGE 4
(CURRENT STATUS)
STATUS

Screen 2
Screen 1 Note: O/L TRIP LEFT TO
TRIP: ###### SEC
CURRENT STATUS Screens include:
1. MOTOR STOPPED
Screen 3
READY TO START
THERM INH TIME LEFT
2. MOTOR STARTING : #### MIN
MULT. OF FLA
Screen 4
3. MOTOR RUNNING
COAST DOWN TIMER
AT ###.## X FLA TIME LEFT: #:## MIN
4. LAST TRIP CAUSE
NONE (or trip cause) Screen 5
TIME BETWEEN STARTS
5. PROGRAMMING TIME: #:## MIN
SETPOINTS
6. MOTOR STATUS Screen 6
UNKNOWN STATE ### (displays relay state upon error) STARTS PER HOUR TIME
## ## ## ## ## ## ##

Screen 2: Displays the amount of time remaining


before an overload trip will occur.

Screen 3: Displays the amount of time remaining from


a thermal inhibit. The inhibit time comes
from the amount of thermal register
remaining versus the amount of thermal
capacity required to start.

Screen 4: Displays the coast down time remaining


(Backspin time). The time remaining
depends upon the user setting in Setpoint
Page 8, Coast Down Time.

Screen 5: Displays the amount of time remaining


before a start command can be given.

Screen 6: If the number of starts per hour has


exceeded the setting.

- 64 -
2.3 - 7.2kV

MP.5 Event Recorder - 60 Events (Metering Page 5)

MENU
Screen 1 Screen 1a Screen 1b
METERING PAGE 5 :<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
Event Recorder (60 event) 1st :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event

:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
2nd :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event

:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
59th :##/##/## ##:##
Event
IC: ###### G/F: #### Vca: ###### P/F: ####

:<cause of event> IA: ###### IB: ###### Vab: ###### Vbc: ######
60th :##/##/## ##:## IC: ###### G/F: #### Vca: ###### P/F: ####
Event

All events will be viewed from oldest event in buffer to most recent event.

The events are listed from oldest to most recent.

Screen 1: Displays the event (i.e., Imbalance Trip) with the


date and time it occurred.

Screen 1a: Displays the current at Phase A, B, C and the


ground fault at the time of the trip.

Screen 1b: Displays the Vab, Vbc, Vca and power factor at
the time of trip.

- 65 -
2.3 - 7.2kV

MP.6 Last Trip (Metering Page 6) MENU


Displays the information regarding the last trip.
Screen 1
Screen 1: Displays the cause of the last trip. METERING PAGE 6 (cause of trip)
LAST TRIP (value at time of trip)

Screen 2: Displays the measured phase current at the


Screen 2
time of the trip.
Ia: #### Ib: ####
Ic: #### G/F: ####.#
Screen 3: Displays the Vab, Vbc, Vca and power
factor at the time of trip. Screen 3
Vab: ###### Vca: ######
Vca: ###### P/F: ######
Screen 4: Displays the imbalance percentage, the
frequency and the kW at the time of the trip.
Screen 4
I/B: ## % Hz: ##.#
Screen 5: Displays the hottest stator RTD temperature KW: ########
(when RTD option present) at time of the
trip. Screen 5
HOTTEST STATOR
RTD# # @ ### C
Screen 6: Displays the hottest non-stator RTD
temperature (when RTD option present) at Screen 6
the time of the trip. HOTTEST NON-STATOR
RTD# # @ ### C

- 66 -
2.3 - 7.2kV

MENU
Screen 1
METERING PAGE 7 MWH TOTAL
STATISTICS : ###

Screen 2 Screen 3
MP.7 Statistics (Metering Page 7) RUNNING HOURS TOTAL PRESS ENTER TO
CLEAR RUN HOURS
TIME: ## ## HOURS
Displays the statistical trip information.
Screen 1: Displays the total of megawatt hours. Screen 4
Screen 2: Displays the accumulated total running TOTAL TRIPS: ###
hours. S/C TRIPS: ###

Screen 3: Clears the total running hour count. Screen 5 Screen 18


Screen 4: Displays the total number of trips since the START O/L TRIPS: ### U/V TRIPS: ###
last clearing the statistical data and the total RUN O/L TRIPS: ### O/V TRIPS: ###
number of short circuit trips.
Screen 6 Screen 19
Screen 5: Displays the numbers of start overload and FREQUENCY TRIPS: ###
POWER FACTOR
run overload trips since the last clearing of I/B TRIPS: ### TRIPS: ###
the statistical data.
Screen 6: Displays the number of frequency trips and Screen 7
OVERCURRENT Screen 20
Imbalance trips. TRIPS: ### PHASE REVERSAL
Screen 7: Displays the number of overcurrent trips TRIPS: ###
Screen 8: Displays the number of Stator and non-Stator Screen 8
RTD Trips STATOR TRIPS: ### Screen 21
NON-STATOR TRIPS: ### EXP INP #1: ###
Screen 9: Displays the number of Ground Fault Hi and
Lo Set trips Screen 9
Screen 10: Displays the number of acceleration time G/F HISET TRIPS: ###
Screen 22
trips. G/F LOSET TRIPS: ###
EXP INP #2: ###
Screen 11: Displays the number of start under curve Screen 10
trips ACCELERATION TIME
Screen 23
Screen 12: Displays the number start over curve trips TRIPS: ###
EXP INP #3: ###
Screen 13: Displays the number of I2T start curve trips
Screen 11
Screen 14: Displays the number of learned start curve START UNDER CURVE
Screen 24
trips. TRIPS: ###
EXP INP #4: ###
Screen 15: Displays the number of fail shunt trips.
Screen 12
Screen 16: Displays the number of phase loss trips.
START OVER CURVE
Screen 17: Displays the number of tachometer Screen 25
TRIPS: ###
PRESS ENTER TO
acceleration trips. CLEAR STATISTICS
Screen 18: Displays the number of undervoltage and Screen 13 LEVEL 2 Password required
overvoltage trips. I*I*T START CURVE
TRIPS: ###
Screen 19: Displays the number of power factor trips.
Screen 20: Displays the number of phase reversal trips. Screen 14
Screen 21: Displays the number of external input #1 LEARNED START CURVE
TRIPS: ###
trips.
Screen 22: Displays the number of external input #2 Screen 15
trips. FAIL SHUNT TRIP
Screen 23: Displays the number of external input #3 TRIPS: ###

trips.
Screen 16
Screen 24: Displays the number of external input #4 PHASE LOSS TRIP
trips. TRIPS: ###
Screen 25: Requires a Security Level 2 password to
clear the statistics. Screen 17
TACH ACCEL TRIP
TRIPS: ###

- 67 -
2.3 - 7.2kV
Chapter 7 - Maintenance and Troubleshooting
The soft starter is designed to be a maintenance-free product. However, as with all electronic equipment, the unit
should be checked periodically for dirt, moisture or industrial contaminants. These can cause high voltage arc-over,
carbon tracking or prevent proper cooling of the SCR heat sinks. All bolts should be checked annually for proper
tightness using an accurate torque wrench. According to the manufacturer’s manual, check the contactor for air gap
spacing of the vacuum bottles.

Note: If the unit is installed in a contaminated environment and forced air cooling is used, blower filters must be
checked and cleaned regularly to insure proper air flow and cooling of the enclosure.

7.1 - Failure Analysis


When a fault occurs, the LCD will display the fault error and the listed LED and AUX Relay will be lit. Please clear
all faults before attempting to restart the unit. Note: If the problem persists after the required programming changes
have been made, and all corrective actions have been taken, please contact the factory for assistance.
Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
One of the main Short circuit between the
fuses blows or Locate and remove short
inputs
circuit breaker
opens when the TCB FAULT TRIP Trip AUX1
Remove power and test SCR(s). Refer to
power is applied
Faulty SCRs Section 7.1.1 for the SCR testing
or disconnect is procedure
open
Short circuit or ground fault
Locate and remove short or ground
in motor/cabling
Phase Loss Repair cause of phase loss
Branch circuit protection Verify correct sizing of branch circuit
Short Circuit Trip SHORT CIRCUIT TRIP Trip AUX1 not correctly sized protection

Remove power and replace main circuit


Faulty main circuit board
board.
Remove power and test SCR(s). Refer to
Faulty SCRs Section 7.1.1 for the SCR testing
procedure
Single phase incoming
Correct problem with incoming power
power
SINGLE PHASE TRIP
Single Phase Trip (Check LCD display for Trip AUX1
Remove power and test SCR(s). Refer to
possible fault indicators) Faulty SCRs Section 7.1.1 for the SCR testing
procedure

If fans have power, remove power and


Fan(s) not functioning
replace fan(s). If fans do not have power,
(If supplied)
find cause of power loss and repair.

Remove power and clean heatsink with


Heatsink coated with dirt high pressure air (80 - 100 psi max clean
and dry air)

Thermostat trips EXTERNAL TRIP ON Verify that running current does not
Trip AUX1 Overcurrent on unit
during run THERMOSTAT exceed unit rating

Environment temperature
over 122° F (ambient
Place unit in environment temperature
temperature for chassis
less than 122°F for panel version or less
units) or over 104°F
than 104°F for enclosed version.
(ambient temperature for
enclosed version

Bypass failed to close Check bypass contactor and wiring

- 68 -
2.3 - 7.2kV

Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
Loss of 1 or more phases
of power from utility or Check power source
Phase Loss PHASE LOSS Trip AUX1
generated power

Blown power fuses Check for short circuits


Check motor nameplate versus
Improper programming
programmed parameters
Overload OVERLOAD TRIP Trip AUX1
Possible load damage or
Check motor currents
jammed load

Improper setting for motor


Verify current limit setting
Stall prevention ACCEL TIME TRIP Trip AUX1 load condition

Damaged load Check for load failure

Improper programming Check setpoint settings


Wrong position of
Check disconnect or open breaker
disconnected breaker
Under Voltage
UNDER VOLTAGE TRIP Trip AUX1 Main contactor failed to
Trip Check internal connections
close

Reduce current limit setting, saturation or


Transformer too small
sagging power supply transformer

Under Current Improper programming Check setpoint settings


UNDER CURRENT TRIP Trip AUX1
Trip
Unloaded motor Check load

Failed CPU or Main Firing


Contact factory
Self-test Failure SELF-TEST FAILURE Trip AUX1 Board
Vibration Check internal wiring connections
Troubleshoot and repair generator
Contact utilities company
Line Frequency OVER OR UNDER Generator Power Problem
Trip AUX1 Main board failure
Trip FREQUENCY TRIP or grid change
Three phase power removed from Main
Board
Improper programming Check program setpoints

Any wire going to ground


GROUND FAULT Check with meggar or Hi-pot motor leads
Any Ground Fault (I.e. stator ground, motor
HI-SET OR LO-SET Trip AUX1 and motor
Trip ground, soft start ground)

High vibration or loose


Check internal connections
connections

Warning: This is a serious fault condition. Ensure that the fault


condition is cleared on the load before attempting to restart the
motor.
Motor stopped
Check for fault indication Trip AUX1
during run
Load shorted/ grounded/
Remove power and repair.
faulted
Faulty main circuit board Replace the main circuit board

Control circuit Remove power, locate and remove this


Short in control circuit
fuses blow after short
None None None
control power is
Apply the correct voltage to the control
applied. Wrong control voltage
circuit

- 69 -
2.3 - 7.2kV

Aux
Problem CPU LCD Display LED Possible Cause Solutions
Relay
No control voltage applied Apply control voltage to TB1 pins 1 and 6
to control board on the power board

Control power transformer Remove power and replace the power


failure or CPT fuse failure transformer or the CPT fuse

Start circuit wired Remove power and correct the start


incorrectly circuit wiring

Any fault indication No start command Apply the start command


Motor will not start Trip AUX1
message No 3 phase line voltage Apply 3 phase line voltage to the unit

Remove power and test SCR(s). Refer to


Shorted SCR in starter Section 7.1.1 for the SCR testing
procedure

Remove power and repair the control


Faulty control logic
logic.

Failure of main circuit


Replace the main circuit board
board

Check the motor and the motor


Faulty motor
connections

Remove power and perform the SCR


Motor vibrates/ Faulty SCRs
Trip AUX1 device checks
Motor growls
while starting or IMBALANCE TRIP Remove power and test SCR(s). Refer to
extremely IMBALANCE ALARM Faulty gate/cathode on
Section 7.1.1 for the SCR testing
unbalanced motor SCRs
procedure
currents run mode
Faulty main circuit board Replace the main circuit board
Faulty motor/wiring Troubleshoot and repair/replace wiring
Alarm AUX2
Faulty main circuit board Replace the main circuit board

7.1.1 - SCR Testing Procedure


Perform the SCR Heat Sink Ohm test on each Stack Assembly.

Test Ohm Meter Reading Result


From Position A to Greater than 10K Ohm Pass
Position B Less than 10K Ohm Fail
C From Position B to Greater than 10K Ohm Pass
Position C Less than 10K Ohm Fail
Pass (Typical 8 to
8 to 100 Ohms
Gate to Cathode for 20 Ohms)
B each SCR Less than 10 or greater
Fail
than 100 Ohms
A

Gate Drive Note: Allow 15 minutes after shutdown for DV/DT network to discharge
Board
DC voltage.

- 70 -
2.3 - 7.2kV

7.2 - Typical Block Diagram

Voltage L1 L2 L3
Transformer

Ring
Transformer

Temp/ CT

1
Fiber Optics CT

Board
4 3

1
2
CT
4
3

1
CT
4

2
A B C

Gate Drive Boards


CPU

DV/DT Boards
MOV Boards
Digital
Main Fiber Optics
Controller SCR Assembly
Firing Board

Control Board
Customer Connections T1 T2 T3

- 71 -
2.3 - 7.2kV

7.3 - Overload Curve Definition

- 72 -
2.3 - 7.2kV

7.4 - TCB Diagram


Customer Provided

Momentary or Maintained
Start / Stop Switching

Momentary
TB9
Aux Start

TB2
MB
MVC3 - TCB Output
120 VAC
STOP
Maintained

Neutral

TB1
T1

Optional START
Interlocks

120 VAC
Source

F1

HEATSINK
F2
FACTORY WIRED
DO NOT USE
F3

TB2 Emergency Bypass


AUX Contacts

TB6 Emergency Bypass/


Full Voltage Start

Fuses
DCU CONNECTIONS ONLY

F1: Control Fuses for TB1 1 - 9


FAULT

Part #ACG1A250VAC or equivalent


F2: Contactor and relay output fuses
Part #ACG4A250VAC or equivalent
TB3 F3: TB2 Pin #6
Part #ACG4A250VAC or equivalent
LOCK OUT

FACTORY WIRED
DO NOT USE
TB7
P.F.C. CAP

TB4

TB8
TIME DELAY

TB5

- 73 -
2.3 - 7.2kV
7.5 - Typical Wiring Diagram

Customer
Provided

Customer
Provided

- 74 -
2.3 - 7.2kV

May be mounted
elsewhere

- 75 -
2.3 - 7.2kV
7.6 - Spare Parts List

Unit Voltage Quantity


Description Part Number
and Amp Rating Req./Unit
Current
Call Factory Specify model number 3
Transformer
MVC3-STK23200 2300V, 200A 3
MVC3-STK23400 2300V, 400A 3
MVC3-STK23600 2300V, 600A 3
Heatsink
MVC3-STK41200 3300/4160V, 200A 3
Assembly with
MVC3-STK41400 3300/4160V, 400A 3
Boards
MVC3-STK41600 3300/4160V, 600A 3
(1 Phase)
MVC3-STK72200 6000 - 7200V, 200A 3
MVC3-STK72400 6000 - 7200V, 400A 3
MVC3-STK72600 6000 - 7200V, 600A 3
25-0200-6500-23 2300V, 200A 3
25-0400-6500-23 2300V, 400A 3
25-0600-3500-23 2300V, 600A 3
SCR(s) Clamped 25-0200-6500-41 3300/4160V, 200A 3
in Heat Sink 25-0400-6500-41 3300/4160V, 400A 3
Alone 25-0600-3500-41 3300/4160V, 600A 3
25-0200-6500-72 6000 - 7200V, 200A 3
25-0400-6500-72 6000 - 7200V, 400A 3
25-0600-3500-72 6000 - 7200V, 600A 3
10-0090 2300V, 200A & 400A 3
10-0090 2300V, 600A 6
Gate Drive 10-0090 3300/4160V, 200A & 400A 6
Transfomer 10-0090 3300/4160V, 600A 12
10-0090 6000 - 7200V, 200A & 400A 9
10-0090 6000 - 7200V, 600A 12

Voltage Contact
Contact Factory Contact Factory
Transfomers Factory

Control Power Contact


Contact Factory Contact Factory
Transfomers Factory

Temperature &
MVC3-Temp/CT-PS All models 3
Current Board

- 76 -
2.3 - 7.2kV

Unit Voltage Quantity


Description Part Number
and Amp Rating Req./Unit
MVC3-GD 2300V, 200A & 400A 3
MVC3-GD 2300V, 600A 6
Gate Drive MVC3-GD 3300/4160 V, 200A & 400A 6
Boards MVC3-GD 3300/4160 V, 600A 12
MVC3-GD 6000 - 7200V, 200A & 400A 15
MVC3-GD 6000 - 7200V, 600A 18
MVC2-MOV 2300V, 200A & 400A 3
MVC2-MOV 2300V, 600A 6
MVC2-MOV 3300/4160 V, 200A & 400A 6
MOV Board
MVC2-MOV 3300/4160 V, 600A 12
MVC2-MOV 6000 - 7200V, 200A & 400A 15
MVC2-MOV 6000 - 7200V, 600A 18
MVC2-Dv/Dt 2300V, 200A & 400A 3
MVC2-Dv/Dt 2300V, 600A 6
MVC2-Dv/Dt 3300/4160 V, 200A & 400A 6
Dv/Dt Board
MVC2-Dv/Dt 3300/4160 V, 600A 12
MVC2-Dv/Dt 6000 - 7200V, 200A & 400A 15
MVC2-Dv/Dt 6000 - 7200V, 600A 18
Main Firing
MVC3-MB-MTR All models 1
Board

Digital Controller MVC3-CPU-MTR All models 1

Control Board MVC3-TCB All models 1

Medium Voltage Contact


Contact Factory Specify model number
Fuses Factory

Communications
DSS1000-COM All models 1
Board

RTD Board DSS1000-RTD Option 1

Ground Fault Board MVC3-GFCT Option 1

Ground Fault CT 11-0029B Option 1

PCB Mounting Order

DVDT MOV Gate Drive


Board Board Board

Temp CT
Board

- 77 -
2.3 - 7.2kV

7.7 - Instructions for Stack Replacement


For Reference Only

TEMP / CT Board

Gate Drive Board

MOV Board

DV/DT Board

PCB Mounting Order

DVDT MOV Gate Drive


Board Board Board

Temp CT
Board

- 78 -
2.3 - 7.2kV

7.7 - Instructions for Stack Replacement

Note: All power sources must be removed and a waiting period of at least
15 minutes must be observed before initiating any repairs to the
unit(s) because DC voltage may still be present immediately after
turning off power to the unit.
Note: It is good practice to disassemble and reassemble one stack at a
time so you can have an assembled and wired stack in the unit as a
reference.
Note: It is recommended that the order include the SCR with the heatsink
assembly at a minimum. Only an experienced technician should
attempt to replace the SCRs.

Tools:
• Phillips screwdriver
• 3/8” 12 point socket set
• 2 9/16” wrenches
• ½” wrench
• AC/DC Multimeter
• Manual (refer to drawings in this section)

Procedure:
1. Verify that no DC or AC voltage is present on any of the power compo-
nents.
2. Disconnect all four wires connected to TB1 positions 1-3 on the tem-
perature CT board.
3. Disconnect the 4 red transformer wires on each of the gate drive
boards. These would be TB1, positions 3 and 5 for each gate drive
board. Typically, the 2300V unit will have only 4 wires per phase to
disconnect, a 4160V unit will have 8 wires per phase and a 6000 -
7200V unit will have 12 wires per phase (Note: the 7200V/600 amp unit
will also have 24 wires.)
4. Use the 9/16 wrench and carefully unbolt all of the line and load power
connections attached to the heat sinks. Note: If the unit is a 6000 -
7200V, remove the power strap connecting one side of the stack to the
stack directly below it.
5. Before removing the fiber optic wiring, make a note of the label on the
fiber cable to ensure they are placed exactly in the same socket they
were removed from. Now remove all fiber optic connectors on the stack.
Gently push on the connector tab and pull with a gentle left-to-right
motion on the connector in the direction away from the fiber optic
device. Two connectors will be found per gate drive board and one
duplex connector will be found on the small Temp/CT board on top.
Caution: Do not touch the tip of the connectors or contaminate the
connection sockets with any dust or foreign material.
6. Remove the wires from the Temp/CT board terminal block (3 screws)
7. Use a 9/16” socket with a 6” extension to remove the lower bolt that
routes through the front face of the heat sink and into the isolation
standoff mounted to the white panel. Then carefully hold the heat sink in
place with one hand and remove the top bolt from the heat sink.
8. Ensure the fiber optic connectors and all wires are positioned out of the
way, and then the heat sink can be gently removed from the unit.
- 79 -
2.3 - 7.2kV

SCR Replacement:
1. Remove white jumper wires on the gate drive board and make a note of
their placement.
2. Remove both 7/16 bolts and single 10 - 32 screw at the top of gate
drive board and lift off the board.
3. To remove the MOV board, remove the SCR gate/cathode leads (thin
red and white wires) and the white jumper wires attached to them.
Make a note as to how they were connected. Unbolt the ½” fasteners
as well.
4. At this point, all boards should now be removed from the aluminum heat
sink assembly.
5. Make a note (or drawing) of how each of the SCRs are oriented within
the heat sink. If factory supplied replacement SCRs and heatsinks are
used, the following steps are not required.
6. Loosen and carefully remove the ½” feed-through bolt and two black
springs that hold the assembly together and turn it on its side.
7. Remove the two (2) SCRS in the top layer, making certain to note that
the SCRs are not facing the same direction.
8. Remove the two (2) SCRs in the bottom layer, also making certain to
note that the SCRs are not facing the same direction.
9. Clean the heat sink surface area thoroughly and reapply some thermal
heat sink grease sparingly to the SCRs mating surfaces.
10. Please note that replacement SCRs are in matched sets of four and as
such, please try to keep the matched sets within the same phase.
11. Now, take any two SCRs from a set and place them on the heat sink in
the same direction as the old SCRs were, ensuring that the dimple in the
center of the SCR is properly placed onto the center pin of the heat sink
assembly. Place the next level of heat sink bar on the mounted SCRs.
Note: There is a difference in the heat sink bars. The center bar has
more holes drilled in it for mounting the circuit boards on it.
12. Now replace the other two (2) SCRs by repeating steps 10 and 11.
13. Next, carefully sandwich the SCRs and turn the stack over so the heat
sink bars are vertical and run the center bolt through the springs and
hand tighten the nut on the center bolt assembly.
14. Then make approximately 3 and ½ full revolutions on the nut to create
the appropriate amount of compression force. You can tell if there is
enough compression force applied to the heat sink by the fact that the
force needed to turn the nut will suddenly increase.
15. Finally, reinstall all boards in the same manner in which they were
removed.
16 Refer to drawing PCB mounting order drawings for disassembling and
reassembling the stack assembly.

Reinstallation:
1. Hold the rebuilt or new stack assembly in the vertical position with the
Temp/CT board on top (only the top stack assembly will have this board in
a multi-stack phase) and place the stack on the positioning studs that
protrude from the isolation standoffs.
2. While pressing on the stack to hold it on the positioning studs, place the
feed-through bolt through the heat sink and finger-tighten the top bolt.
Then repeat the process with the bottom feed-through bolt to ensure the
stack is held against the isolation standoffs.
3. After verifying no wires or fibers have been pinched between the stack
assembly and isolation standoffs, tighten the top bolt completely, then
repeat the process for the bottom bolt. Now the stack assembly should be
held firmly in place.
4. Using the 9/16” wrench reinstall the line and load power cables and
tighten.

- 80 -
2.3 - 7.2kV

5. If needed, refer to the appropriate drawing to reconnect red transformer


wires on each gate drive board. As an example, for the 4160V stack,
reattach TB4-1 to X3, TB4-3 to X4, TB1-3 to X2 and TB1-1 to X1. Verify
all X(#) wires are reconnected to their original position on the gate drive
boards. Otherwise the SCRs will misfire.
6. Reconnect thermostat wires on TB1 positions 2 and 3 of the Temp/CT
board.
7. Reconnect the main CT black wire to TB1-1. Then feed the white wire
through the board mounted CT and connect to TB1-1 on the Temp/CT
board. Please note that one each of the thick white wires from the encap-
sulated CT must be connected with the Main CTs wiring.
8. Ensure the same fiber optic routing is used as before. If the fiber optic
wiring is positioned close to a heat source, (such as the 25-watt resistors
on the gate drive board) melting or distortion of the plastic fiber may
occur. Minimum distance is a ½ inch with a minimum bend radius of 2
inches. All gate drive boards require 2 single connectors per board and
the Temp/CT connector is a duplex piece with a mating tab that faces
away from the stack. If the tab is broken off, refer to an adjacent stack’s
labels to see how the labels should be positioned when installing a
duplex connector with a broken tab. Again, caution should be taken not
to touch the fiber connector end or force it in with the tab facing down.

- 81 -
2.3 - 7.2kV

7.8 - Instructions for Low Voltage Test

Tools:
• Phillips screwdriver
• Medium voltage fuse pullers if available
• Two control power transformer (Test PT) 500 VA minimum
• 120 VAC control power (Test plug)
• Low voltage motor strapped for the proper voltage (typically 5 HP or less)
• Oscilloscope if available
• Wire jumper
• Test switch (single pole i.e. - light switch)
• Manual (reference drawing above)
480 or 240 VAC 3 Phase Supply
Construct an open delta low A B C
voltage source for powering Ensure proper
the MVC for low voltage testing phase sequence
HAZARDOUS VOLTAGE
(Minimum of 500VA each) H2 H1 H1 H2
Remove all medium voltage fuses to
prevent back-feeding transformers. PTs
Failure to follow this instruction will X1
result in death or serious injury. X1
X2 X2
A B C
Low Voltage Panel
TB1 Terminal 1 TB1 Terminal 3 TB1 Terminal 5
Procedure:
120 VAC 3 Phase Output
1. Verify that no DC or AC voltage
Connect to MVC3-MB (Main Firing Board)
is present on any of the power
Caution: Remove the three phase transformer PT fuses and CPT fuses
components. on panel to prevent backfeed to the Medium Voltage
2. Verify setup of control power
transformers for the proper
voltage. If using 480 VAC or 240 VAC 3 phase verify transformers are
strapped for that voltage. See above drawing. Configure as an open
delta for 3 phase as shown in drawing.
3. Verify medium voltage disconnect is open and pull medium voltage
fuses including VT and CPT fuses.
4. Connect 3 phase power 480 or 240 VAC to the down stream side of
the fuses. Do not connect to disconnect side of fuses. The size of the
small test motor will dictate the current drawn and minimum cable size
for connection. Also, connect the Primaries of the TEST PT in the
proper phase sequence of A-B-C.
5. Disconnect medium voltage motor.
6. Connect low voltage motor. (Typically 5 HP or less)
7. Connect a wire jumper between TB8 pins 1 and 2 on the TCB (control
board) to bypass fuse blown and open disconnect fault. The TCB is
located in the medium voltage compartment.
8. Install a switch on TB1 pins 1 and 8 on the TCB (control board) to
bypass all interlocks (Interlock Switch).

- 82 -
2.3 - 7.2kV

9. Verify or wire a 120 VAC plug to the TEST plug supplied by the factory.
(Line start packages only)
10. Remove both control power fuses on the medium voltage CPT (single
phase control power transformer)
11. Remove 3 fuses from the medium voltage potential transformer (PT)
12. Verify the 120-volt test switch is in the “NORMAL” position. (Line
start package only)
13. Connect test power to test plug connector and place the 120-volt test
switch to the “TEST” position.
14. The keypad should be energized with the “Power LED,” Stop LED
15. Close the temporary Start switch, which is connected to the control
board.
16. The Main Vacuum contactor should close and the keypad should trip
on “Under Voltage” Open temporary Interlock switch and reset CPU
fault.
17. Connect the Secondary of the TEST PT to Panel TB1 positions 1 -
phase A, position 3- phase B, and position 5 - phase C on the main
firing board (MVC3-MB). It is physically located behind the low voltage
compartment door. (Screw terminal block)
18. Verify all connections are good and then energize the low voltage of
either 480 or 240 volt, three phases.
19. Use the multimeter on the AC scale and verify 3 phase 120 VAC
(phase to phase) at TB1 pins 1, 3 and 5 of the main firing board.
20. If all 120 VAC 3 phase is present then de-energize low voltage of
480 or 240 VAC.
21. Re-energize the low voltage of 480 or 240 VAC.
22. Now all test voltages should be present 480 or 240 VAC and three
phase 120 VAC (TEST PT) and 120 VAC single phase for control
power.
23. Close the temporary Start switch and the test motor should spin up
smoothly.
24. Use the Multimeter on the AC scale and check (phase to phase)
voltages on T1, T2 and T3 motor leads. The voltages should be
balanced.
25. If the motor doesn’t spin up smoothly the soft starter is malfunctioning.
Proceed to step 27 for troubleshooting.
26. If the motor starts and runs smoothly then repeat this procedure in
reverse to remove all test connections and reinstall all fuses.

- 83 -
2.3 - 7.2kV

Low Voltage Troubleshooting:


Tools: Ungrounded Oscilloscope
27. Open test switch and stop motor.
28. Change Setpoint Page 5 AUX4 is set at non-fail safe. Change it to fail safe.
29. Observe bypass contactor closes immediately.
30. Place the Oscilloscope on the 2msec time scale and 1 v per
division.
31. Connect the Oscilloscope probe to the Gate and Cathode of the SCRs.
32. The gate and cathode leads are the white wires on the gate drive board in the medium voltage cabinet. See
drawing below.
33. If waveform is inverted, swap Oscilloscope connections for proper polarity. Close the temporary Start switch and
allow the test motor to reach full speed.
34. Then verify all gating signals to each SCR (two gating signals on every gate drive board). See drawing below for
correct waveform.
35. Once the bad signal(s) are found; write down the location and call the factory for further guidance.

Waveform is
the gating signal as
measured with an
ungrounded oscilloscope
at the gate to cathode
of the SCR. The
waveform should be 1.7
to 2msec off time and
approximately 1.5 to
3 Vdc. This signal is only
present at full conduction
or the motor is at speed.
Each SCR gating signal
should be checked
in accordance with the
low voltage test procedure.

- 84 -

You might also like