Powerline Dpa 40 Iec: Technical Data Sheet
Powerline Dpa 40 Iec: Technical Data Sheet
Powerline Dpa 40 Iec: Technical Data Sheet
PowerLine DPA
Document information
Project name : Merah Expansion
UPS model : PowerLine DPA 40 IEC
TAG number :
Date of issue : 08.11.2016
Document number : 4NWD003314
Document name : TDS_ABB_PWL_DPA_40_IEC
Revision : 0
Revision history
10 Options ........................................................................................................................ 12
11 Heat dissipation with nonlinear load ............................................................................ 13
12 Installation planning – UPS positioning ....................................................................... 14
13 Operational Parameters .............................................................................................. 14
14 Annex .......................................................................................................................... 15
14.1 Single Line Diagram ..................................................................................................................... 15
Contact us ........................................................................................................................... 16
1 System description
The PowerLine DPA is a three-phase uninterruptible power system (UPS). It is a true on-line double
conversion UPS providing quality power for sensitive equipment in industrial environments. Its modular
design consists of:
1.1 Identification
Type Nominal power Input Voltage / Output Voltage - Configuration*
rating [kW]
PowerLine 40 400 / 400 - Redundant
DPA
* S = Single, R= Redundant
PowerLine DPA
Panel Thickness
Side and rear 20/10mm
Door 20/10mm
Finishing galvanized and painted
Weight of UPS system kg 1305
3 Environmental characteristics
The following data declarations are valid for PowerLine DPA
PowerLine DPA
AC power system IT
Input frequency Hz 50 Hz
-30/+40 %
Frequency tolerance -
Total harmonic distortion (THDi) % 4
0.99 @ 100% load
Input power factor -
Inrush current without input
A < 100% of rated current
transformer
Inrush current with input/bypass
<10 x In of rated current
transformer
Rated short-time withstand 10 for 1.5 seconds
kA
current (Icw)
Current (r.m.s), rated (with battery 66.2264611955629
A
charged and input 400/230V)
5 Bypass characteristics
Rated power kW 40
Input frequency Hz
Frequency tolerance % -4/+4 %, -2/+2 % (selectable)
Nominal output current A 61.9762015564994
6 Battery characteristics
12
Max battery charger power capability kW
4) Alarm indication Shows the present faults in the system. The LED is
activated as long as the alarm is present
Options
No
System Cold start
Yes
Magnetics (Alu) Input Transformer
Yes
Bypass Transformer
Yes
Output Transformer
No
Mechanics Dust Filter
No
Top cable entry
Yes
Lifting eyes
Yes
Anti-condensation heater
Yes
Conformal coating
Control & No
SNMP interface
monitoring
Yes
Modbus TCP/IP
No
Modbus RS-485
No
Synchronization kit
Yes
Battery Temperature sensor
11 Heat dissipation with nonlinear load
PowerLine DPA
The minimum clearances as described below that are needed to allow proper airflow to the UPS system,
and to allow proper service and maintenance, should be respected.
PowerLine DPA
A Back clearance 10 mm
13 Operational Parameters
Languages in Display ............................ : EN
14 Annex
14.1 Single Line Diagram