With or without terminals

D 9025
1.5-2.5 mm², Cu 3~

Replaced by DK 0202 G, DK 0402 G (larger enclosure) from 31.12.2017


with terminals
5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
included cable entry: 4 ESM 20,
sealing range Ø 6-13 mm
for normal environment and protected outdoor
colour: grey, RAL 7035

rated insulation voltage Ui = 690 V a.c./d.c.


tightening torque for terminal 1.2 Nm
material PS (Polystyrene)
degree of protection IP 55 (ESM)
degree of protection (see cable entry systems LES) IP 65
width 88 mm
height 88 mm
depth 53 mm
weight 0,14 kg
in accordance with IEC 60670-22

Drawings

Dimension drawing

Page 1 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: December 11. 2020
With or without terminals

D 9025
1.5-2.5 mm², Cu 3~

Detail mass

Box walls

Operating and ambient conditions


Application area Suitable for indoor installation and outdoor installation, protected
against weather influences
Resistant to occasional cleaning procedures (direct jet) Resistant to occasional cleaning procedures (direct jet) with high-
pressure cleaner without additives, water pressure: max. 100 bar,
water temperature: max. 80° C, distance => 0,15 m, in accordance
with the requirements IP 69, enclosure and cable glands at least
IP 65
Ambient temperature Average value over 24 hours + 35 °C
Maximum value + 40 °C
Minimum value - 25 °C
Relative humidity 50% at 40° C
short-time
100% at 25° C
Fire protection in the event of internal faults Demands placed on electrical devices from standards and laws
Minimum requirements
- Glow wire test in accordance with IEC 60695-2-11:
- 650°C for boxes and cable glands
- 850°C for parts of insulating material necessary to retain current
carrying parts in position
Burning behaviour Glow wire test IEC 60695-2-11: 750 °C
UL Subject 94: V-2
flame-retardant
self-extinguishing
Degree of protection against mechanical load IK07 (2 Joule)
Toxic behaviour halogen-free
Page 2 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: December 11. 2020
With or without terminals

D 9025
1.5-2.5 mm², Cu 3~

silicone-free
"halogen-free" in accordance with the examination of the cables
and insulated wires - corrosiveness of fumes - as per IEC 60754-2
Note: For material properties see technical data.