Test Device: Excitation Curve
Test Device: Excitation Curve
Test Device: Excitation Curve
Overall assessement OK
Asset
Ipn 400.0 A Object Location
Isn 1.0 A Manufacturer RITZ Company SEC
Rated burden 15.0 VA /0.80 Type ASS17.5.05 Country KSA
Operating burden 15.0 VA /0.80 Serial number 19/80345925 Station MOBILE SS
Standard IEC 61869-2 Core 1 Feeder H03
Application Protection Tap 1 Phase R
Class 5P Optional IEC-ID
Frequency 60.0 Hz Comment
Rct max 1.759 Ω ?
ALF 20.0
Ts
Burden
Burden cos φ: Z
V-meas I-meas
Excitation
Ls 0.002849 H Lm 49.70279 H Results at rated burden (15.00 VA) Results at operating burden (15.00 VA)
Kr 91.45 % ALF > 26.36 ALFi 25.49 ALF > 26.36 ALFi 25.49
Standard IEC 61869-2 εci (@ ALF=20) 0.534 % εci (@ ALF=20) 0.534 %
V-kn 334.27 V I-kn 0.0219 A Ts 3.612 s Ts 3.612 s
Ratio
Turns ratio 397.4568 Results at rated burden (15.00 VA) Results at operating burden (15.00 VA)
εt -0.6358 % Ratio 400.0 : 1.0047 Ratio 400.0 : 1.0047
Polarity OK ε 0.4740 % ∆φ 1.36 min ε 0.4740 % ∆φ 1.36 min
εc 0.4757 % εc 0.4757 %
Residual magnetism
Residual flux
Residual magnetism
Excitation curve
450.00
400.00
350.00
300.00
Voltage [V]
250.00 X1-X2
200.00
150.00
100.00
50.00
0.00
0.00 0.500 1.00 1.50 2.00 2.50 3.00 3.50
Ie [A]
1/2
Current ratio error in % at % of rated current at rated burden (15.00 VA)
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
15/0.8 -0.1307 0.2171 0.3079 0.3783 0.4423 0.4740 0.4810 0.4979
7.5/0.8 0.1475 0.3573 0.4227 0.4686 0.5138 0.5370 0.5420 0.5531
3.75/1 0.5308 0.5285 0.5468 0.5629 0.5802 0.5908 0.5931 0.5989
1.875/1 0.5857 0.5633 0.5724 0.5844 0.5964 0.6042 0.6061 0.6104
20.0000
3.75 VA
0.0000
-20.0000 1.88 VA
-40.0000
Limits
-60.0000
-80.0000
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
2/2