b Phase 87g 2nd Core With Acceptable Criteria
b Phase 87g 2nd Core With Acceptable Criteria
b Phase 87g 2nd Core With Acceptable Criteria
Overall assessement OK
Asset
Ipn 14000.0 A Object Location
Isn 5.0 A Manufacturer WESTINGHOUSE Company ALFANAR
Rated burden 30.0 VA /0.80 ? Type BUSHING TYPE CT Country KSA
Operating burden 30.0 VA /0.80 ? Serial number NA Station GHAZLAN PP
Standard IEC 60044-1 Core CORE 87G 2ND Feeder UNIT 4
Application Protection Tap 1S1-1S2 Phase B
Class 5P Optional IEC-ID
Frequency 60.0 Hz Comment
Rct max PHASE SIDE CT B PHASE
ALF 50.0 ?
Ts
Secondary winding resistance ACCEPTABLE CRITERIA: NEED FACTORY REPORT RESULTS TO COMPARE Primary winding resistance
R-meas (25.0 °C) 2.175 Ω R-meas (25.0 °C)+Rlead 2.175 Ω R-meas
R-ref (75.0 °C) 2.594 Ω R-ref (75.0 °C)+Rlead 2.594 Ω R-ref
Burden
Burden cos φ: Z
V-meas I-meas
Excitation ACCEPTABLE CRITERIA:- ACCORDING TO IEC 60044-1 CALCULATIONS Ie MUST BE LESS THAN 130ma AT KNEEPOINT VOLTAGE
Ls 0.009355 H Lm 60.567885 H Results at rated burden (30.00 VA) Results at operating burden (30.00 VA)
Kr 88.44 % ALF > 54.67 ALFi > 54.60 ALF > 54.67 ALFi > 54.60
Standard IEC 60044-1 εci (@ ALF=50) 0.048 % εci (@ ALF=50) 0.048 %
V-kn 759.714 V I-kn 0.0435 A Ts 17.042 s Ts 17.042 s
Ratio ACCEPTABLE CRITERIA:- ACCORDING TO IEC 60044-1 ERROR % MUST BE BETWEEN -1% TO +1% & PHASE ERROR BETWEEN -60MIN TO +60MIN FOR 5P CLASS
Turns ratio 2799.2043 Results at rated burden (30.00 VA) Results at operating burden (30.00 VA)
εt -0.0284 % Ratio 14000.0 : 4.9984 Ratio 14000.0 : 4.9984
Polarity OK ε -0.0312 % ∆φ 1.28 min ε -0.0312 % ∆φ 1.28 min
εc 0.0485 % εc 0.0485 %
Residual magnetism
Residual flux
Residual magnetism
Excitation
10000.00
1000.00
X1_X2_1
100.00
Terminal voltage
10.00
1.00
0.010
0.000 0.001 0.010 0.100 1.00 10.00
RMS current
1/2
Current ratio error in % at % of rated current
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
0.6
0.4
Current ratio error [%]
7.500 VA
0.2
0
-0.2 3.750 VA
-0.4
-0.6 Limits
-0.8
-1
-1.2 Limits
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
40
Phase [min]
20 7.500 VA
0
3.750 VA
-20
-40 Limits
-60
-80 Limits
2/2