Overview of Distribution System
Overview of Distribution System
Overview of Distribution System
need for a primary distribution system to supply a few large loads such as industrial
loads in the area at high voltage. The sub-transmission substation steps down the
transmission voltage to primary distribution levels. The distribution transformers are
located at the distribution substation to change the primary distribution voltage to the
secondary distribution voltage. The distribution substations are the feeding points for
the secondary distribution system.
The distributions are run from the distribution substations or feeding points.
These are conductors which are tapped to supply the various loads of the consumers by
service mains [81Pab].
Sub-transmission
Distribution
Substation
Primary
Feeder
Distribution
Transformer
Secondaries
Consumers’ Service
No DC System AC System
1. It requires only two conductors.
It requires, at least, two wires for the
However, if earth is used as the
single phase system, and three wires for
return conductor, only one
three phase system. However, the three
conductor is sufficient; thus, much
phase transmission is economical.
copper can be saved.
2. Problems of inductance,
capacitance, surges, etc., are It has all these problems.
eliminated in this system.
8
3.
It has no skin effect. It has skin effect.
(continued)
4. The DC system has no corona loss The AC system suffers from corona
and has, therefore, no radio losses which produce radio interference.
interference.
5. Voltage regulation in the DC system Voltage regulation in the AC system is
is better. poor.
6. In the DC system, high voltage In the AC system, with transformers,
cannot be made available as high can get any voltage (high or low).
voltage generation is quite However, the generation voltage is
uneconomical. 11kV
7. The DC switch gear/substation The AC switch gear/substation is easy
needs more maintenance. to maintain.
Radial system
Transmission
Substation
Circuit Breaker
Substation Bus
Circuit Breaker
Load
Primary Feeder
Fuse
Distribution
Transformer
Distribution
Load
Source
Parallel
or Loop
Circuit
Ring
Loop
Load Load
Sub-transmission Sub-transmission
Substation Substation
Substation
Substation
Load Load
11
Arrestors, grounding methods, spacing of wires and insulation levels to be used for the
lines should be properly chosen.
2.7.1. Primary Distribution
The primary distribution would be the circuits supplying power at high voltage
to large consumes such as industrial consumers and to distribution substation. The
voltages are 33kV, 11kV, 6.6kV, and 3.3kV. The three-phase, three wire system is
adopted for primary distribution.
The advantages of the three phase, four wire systems are at a time, one gets two
voltages, 400V and 230V the three phase supply is given to factories, whereas, the
single phase supply is given to houses for light and fan loads.
2.7.4. Secondary Distribution Design
The link between the primary distribution and secondary distribution is a series
of substations suitable located to step-down the voltage of the primary distribution
system to the secondary distribution voltage. The following points have to be
considered.
Choice of voltage
Conductor size
Types of secondary distribution
radial system
loop radial or low voltage secondary network
wrapping of tinned copper conductors which act as the ground. The cable is pulled
through underground concrete duct of simply buried along with active cables to
provide alternate service in case of a fault.
The 24.9 kV aerial lines are supported on wooden poles. The latter also carry
the LV circuits and telephone cable. The 24.9 kV lines are tapped at various points so
supply 3-phase and single phase power to residences, commercial establishments and
recreation centers.
For nearby areas the 24.9 kV line voltages is regulated within acceptable limits
by the tap-changing transformers at the substation. In more remote distinct, special
measures have to be taken to keep the voltage reasonably stable which changing load.
Thus self-regulating autotransformers are often installed.
breakers of fuses are used on the secondary side. The primary high-voltage terminal is,
however protected by a cutout in order to prevent excessive damage to equipment in
case of a fault.
2.9. Development of a Distribution Plan
When designing and developing the distribution plan for a particular area, the
following main points should be considered;
Service conditions are load tabbed serve, density of customers, length of lines
and points of supply.
Electrical designs are transformers and accessories, protection of electrical
system and operation of the system.
Mechanical designs are poles and spans, hardware and guying, wires and
clearances and installation of transformers and substations.
Cost per kilometer of distribution lines and cost per consumer.
Distributors are conductors that are tapped for supplying loads to consumers.
The main requirement of these conductors is to supply power to consumers at the rated
voltage within the permissible voltage variation. The voltage at the last consumer
connected across the distributors should not fall below the minimum prescribed value.
The distributors are fed from the feeding points or substations. The types of
load on the distributors are concentrated loads at various points of tapping of the
service mains. If the loads are uniformly distributed such as street lighting loads of
equal sizes at equal distances, they may be represented as uniformly distributed load
per unit length of the distributor.
In practice, it may be that the loads are both concentrated at various points as
well as uniformly distributed. The voltage drops that occur due to such loads can be
worked out and the voltage at the terminals of the last consumer can be found out.
Shunt capacitors.
Automatic voltage boosters are less expensive than induction regulators and are
important in improving the service in low-density areas, particularly on long, rural
lines.
Automatic tap changing on-load is also used with large distribution
transformers and power transformers in substations to control the voltage on a bus or
feeder.
For satisfactory operation, operation of regulators on distribution circuit must
be coordinated with the system design and the regulator setting may be determined to
give the best results.
The distribution system may be designed with the following limitations:
8% voltage drop is allowed between the primary of the first transformer and
end of the secondary of last transformer with maximum load on the circuit and
the maximum load on the last transformers and secondary.
Regulators are set up to provide a voltage, at the primary of the first
transformer of about 4 % more than the normal voltage.
When automatic control is used for the distribution system, the contact making
voltmeters are set to the value of the standard voltage to be maintained.
Shunt capacitors can be used on the distribution system to improve the voltage
regulation of the system. The shunt capacitors, it connected to utilization equipment
and switched on in accordance with the load, reduce the voltage drop in the
distribution system and thus help in obtaining the better voltage regulation.
Shunt capacitors installed on a distribution system reduce the current, improve
the voltage regulation and reduce energy loses in every part of the system between
capacitors and generators [74Dep].
Ground fault relaying is simple. The earth fault may be utilized to operate
protective relays to isolate the fault.
Persistent arcing grounds can be eliminated by employing protective gears.
The methods of neutral grounding are solid earthing and resistance earthing.
Earth resistance usually will be high where the gravel, sand or stone content in
the soil is high with a low content of clay or loam. Resistance will be lowest with a
high content of clay or loam in the soil and little or no sand, gravel, or stone [74Dep].
Transmission
Generating Lines Substation
Plants Load
Select
Switches
Distribution Substation
Voltage
Load Select Regulato Back- Sub-
r up Transmission
Line Lines
22
Step-up Transformer
Power
Transformer
Generation Transmission
Voltage System Sub-Transmission
Regulato System
r
(b)
Power Distribution Network
To Another
Distribution
Substation
Primary Feeder
Low Voltage Low Voltage
(a)
Secondary Main
Customer Loads
(c)
Figure 2.6. Simplified Block Diagram of Basic Utility Power Distribution [75Ste]
(a) Overall Network
(b) System Terminology
(c) Distribution between Primary and Secondary System
The secondary system originates at the distribution transformer and ends at the
consumer loads. This is referred to as secondary banking. If an even higher service
reliability factor is required the secondary mains in area can be connected in a mesh or
a network, similar to the networking of the primary.
Fuses and circuit breakers are included at a number of points in the distribution
system to minimize fault-caused interruptions of service. Ground-fault interrupters
(GFIs) are also included at various points in the system to open the circuit if excessive
ground currents begin to flow on the monitored line.
Depending on the geographic location, varying levels of lightning protection
are included as part of the AC power system design. Most service drop transformers
have integral lightning arresters. In areas of severe lightning, a ground wire is strung
between the top insulators of each pole, diverting the lightning to the ground wire, and
away from the hot leads [75Ste].
Substation
Distributor
Distributor
Distributor