Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 61

ULCF3000 INSTALLATION Manual

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY


The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s
(“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales
office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE
SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE
ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY
ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or
other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to
damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the
use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the
information, recommendations and descriptions contained herein. The information contained in this manual is subject to
change without notice.

2 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


ULCF3000 INSTALLATION
Manual

Contents
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1. Fire alarm system limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2. Installation precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3. Product descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4. Product features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5. Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.6. Controls and indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6.1. Touch screen user button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6.2. LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.7. Panel controls and indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.8. Fitting printer paper role. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2 INSTALLATION GUIDELINES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 essential please read before proceeding!. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2 Agency requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3 Calculating current draw and standby battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4 Calculating maximum current draw and battery backup
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4.1 Detector technical characteristics UL approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4.1.1 calibrated detector sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4.2 UL Approved audio visual devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.4.3 Examples of battery calculations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.4.4 Maximum number of devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.4.5 Wiring requirement for SLC circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1 Mounting the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2 Earth cable on ULCF3000RM (does not apply to ULCF3000) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.3 Installing cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.4 Connecting the AC Power and earth connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5 Battery Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.6 Output (NAC) Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.6.1 Class B Style Y NAC wiring using main board (Horns only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.6.2 Class B Style Y NAC Wiring using wheelock DS 12/24 (Horns & Strobes) . . . . . . . . . . . . . . . . . . . . . . . . 22
3.7 SLC Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.8 Supervisory signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Addressable devices can be programmed for supervisory signals. This input on a latching mode and
requires a manual reset to restore their normal state provided the condition is cleared.Panel Relay Outputs. . . 23
Panel relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

4 NETWORKING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.1 Battery maintenance installation cautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

5 TECHNICAL SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6 COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.1 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.2 Panel programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3 PC Commissioning software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.1 Device input programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

ULCF3000 INSTALLATION MANUAL 3


ULCF3000 INSTALLATION
Manual

6.3.2 Isolate Zone / Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error! Bookmark not defined.

7 PANEL CONTROLS & INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30


7.1 Touch screen display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.2 Panel operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.3 Public access level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.4 Evacuate (Access level 2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5 Silence alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.6 Acknowledge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.7 Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.8 Pre-alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.9 Disabled devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.10 Troubles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.11 Enable/disable (Others menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.12 Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.13 Lamp test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.14 Weekly test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.15 Viewing events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.16 Check auto config. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.17 Test device (Access level 3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.18 Test zone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.19 Sounder level test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.20 Global flashing LED on/off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
7.21 One man walk test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.22 Commission: Load CDR from Laptop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7.23 Commission: Download CDR to Laptop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.24 Commission: Auto learn. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.25 Erase log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.26 Change date/time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.27 Change text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.28 Change zone text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.29 Change panel text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
7.30 Configure zones. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.31 Change user code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.32 Add zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.33 Delete zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.34 Add device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.35 Delete device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.36 Configure heat detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.37 Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.38 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

8 BATTERY DISPOSAL INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59


9 COMPATIBILITY TABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

4 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


ULCF3000 INSTALLATION
Manual

NNote: For maintenance recommendations refer


to the NFPA 72 National Fire Alarm Code, 2007.
NNote: Software release:
DTS Micro: 3.03.50.xx
Loop: 3.2.4.xx
NNote: Install in accordance to NFPA 70, 72 (2007).
The ULCF3000 is suitable as a Local signaling unit.
All circuits inherently power limited except
AC wiring and battery cabling.

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING


JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the
product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming
features or options must be limited to specific values or not used at all as
indicated below.
Program feature Permitted in UL Possible Settings permitted
or option 864? (Y/N) settings in UL 864
Enable All / N Enable All / Enable All
Disable All Disable All

ULCF3000 INSTALLATION MANUAL 5


Introduction

Introduction Smoke detectors cannot be expected to provide adequate


warning of fires caused by arson, children playing with
1.1. Fire alarm system limitations matches (especially in bedrooms), smoking in bed,
and violent explosions (caused by escaping gas,
An automatic fire alarm system – in general is made up improper storage of flammable materials, etc.).
of smoke detectors, heat detectors, manual pull stations,
Call points, audible warning devices, and fire alarm control Heat detectors do not sense particles of combustion and
panels with remote notification capability, which can alarm only when heat on their sensors increases at
supply early warning of a developing fire. Such a system, a preset rate or reaches a predetermined level.
on the other hand, is unable to assure protection against Rate-of-rise heat detectors may be subject to reduced
property damage or loss of life resulting from a fire. sensitivity overtime. For this reason, the rate-of-rise
feature of each detector should be tested at least once
The Manufacturer recommends that smoke and /or heat per year by a qualified fire protection expert.
detectors must be positioned throughout a protected Heat detectors are designed to protect property, not life.
premise following the recommendations of the current
edition of the National Fire Protection Association IMPORTANT
Standard 72 (NFPA72), manufacturer’s recommendations,
State and local codes, and the recommendations Smoke detectors must be installed in the same room as
contained in the Guide for Proper Use of System Smoke the control panel and in rooms used by the system for the
Detectors, which is made available at no charge to all connection of alarm transmission wiring, communications,
installing dealers. A study by the Federal Emergency signaling, and/or power. If detectors are not located,
Management Agency (an agency of the United States a developing fire may damage the alarm system,
government) indicated that smoke detectors may not go crippling its ability to report a fire.
off in as many as 35%of all fires. While fire alarm systems
are intended to provide early warning against fire, Audible warning devices such as bells may not alert
they cannot promise warning or protection against fire. people if these devices are located on the other side of
A fire alarm system may not provide timely or sufficient closed or partly open doors or are located on another floor
notice, or might not function, for a diversity of reasons. of a building. Any warning device may fail to alert people
with a disability or those who have recently consumed
Smoke detectors may not sense fire where smoke cannot drugs, alcohol or medication.
reach the detectors such as in chimneys, in or behind
walls, on roofs, or on the other side of closed doors Please note that:
Smoke detectors also may not sense afire on another Strobes can, under certain circumstances, cause seizures
level or floor of a building. A second-floor detector, for in people with conditions such as epilepsy.
example, may not sense a first-floor or basement fire.
Studies have shown that certain people, even when they
Particles of combustion or “smoke” from a developing hear a fire alarm signal, do not respond or comprehend
fire may not reach the sensing chambers of smoke the meaning of the signal. It is the property owner’s
detectors because:- responsibility to conduct fire drills and other training
•• Barriers such as closed or partially closed doors, walls, exercise to make people aware of fire alarm signals and
or chimneysmay inhibit particle or smoke flow. instruct them on the proper reaction to alarm signals.
•• Smoke particles may become “cold,” stratify, In rare instances, the sounding of a warning device can
and not reach the ca lingor upper walls where cause temporary or permanent hearing loss.
detectors are located. A fire alarm system will not operate without any electrical
•• Smoke particles may be blown away from detectors power If AC power fails, the system will operate from
by air outlets. standby batteries only for a specified time and only
if the batteries have been properly maintained and
•• Smoke particles may be drawn into air returns before replaced regularly.
reaching thedetector.
Equipment used in the system may not be technically
The amount of “smoke” present may be insufficient compatible with the control. It is essential to use only
to alarm the smoke detectors. Smoke detectors are equipment listed for service with your control panel
designed to alarm at various levels of smoke density. Telephone lines needed to transmit alarm signals from
If such density levels are not created by a developing fire a premise to a central monitoring station may be out of
at the location of detectors, the detectors will service or temporarily disabled. For added protection
not go into alarm. against telephone line failure, backup radio transmission
systems are recommended.
Smoke detectors, even when working property,
have sensing limitations. Detectors that have photo The most common cause of fire alarm malfunction is
electronic sensing chambers tend to detect smoldering insufficient maintenance. To keep the entire fire alarm
fires better than flaming fires, which have little visible system in excellent working order, ongoing maintenance
smoke. Detectors that have ionizing-type sensing is required as the manufacturer’s recommendations, and
chambers tend to detect fast – flaming fires better than UL and NFPA standards. At a minimum, the requirements
smoldering fires. Because fires develop in different ways of NFPA 70, 72 shall be followed. Environments with
and are often unpredictable in their growth, both type of large amounts of dust, dirt or high air velocity require
detector is necessarily best and a given type of detector more frequent maintenance. A maintenance agreement
may not provide adequate warning of a fire. should be arranged through the local manufacturer’s
representative. Maintenance should be scheduled

6 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


Introduction

monthly or as required by National and /or local fire codes not interfere with battery, transformer, and printed circuit
and should be performed by authorized professional board location.
fire alarm installers only. Adequate written records of all
inspections should be kept. Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
1.2. Installation precautions terminal contact pressure and difficulty with screw
terminal removal.
WARNING This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
Several different sources of power can be connected handling any circuits so that static charges are removed
to the fire alarm control panel. Disconnect all sources from the body. Use static-suppressive packaging to
of power before servicing the Control unit and protect electronic assemblies removed from the unit.
associated equipment may be damaged by removing
and/or inserting cards, modules or interconnecting Follow the instructions in the installation, operating,
cables while the unit is energized. Do not attempt to and programming manuals. These instructions must
install, service, or operate this unit until this manual be followed to avoid damage to the control panel and
is read and understood fully. associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
CAUTION 1.3. Product descriptions
System Reacceptance Test after Software Changes.
The ULCF3000 provides all of the sophisticated features
To ensure proper system operation, this product must
required of a leading edge analog fire system along with
be tested in accordance with NFPA 70, 72 after any
the simple operation and neat installation demanded by
programming operation or change in site -specific
both installers and building users.
software. Re-acceptance testing is required after any
change, addition or deletion of system components, The panel can be flush or surface mounted and the
or after any modification, repair or adjustment to system generously sized metal back box allows ample facilities for
hardware or wiring. All components, circuits, system rear or top cable entries.
operations, or software functions known to be affected
by a change must be 100% tested. A comprehensive range of ancillary devices is available
to operate with ULCF3000, including Optical, Ionization,
In addition, to ensure that other operations are not photo-thermal and heat detectors.
inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, Each of the ULCF3000 system components has been
up to a maximum of 50 devices, must also be tested and specifically designed to operate as part of a ULCF3000
proper system operation verified. system, this provides an assurance that the panel,
the detectors, the interfaces and the ancillaries are all fully
This system meets NFPA requirements for indoor dry compatible with one another and that the full range of
operation at 0-49° C/32-120° F and at a relative humidity system functionality is supported by each device.
of 93 ±2% RH (non-condensing) at 32 ±2° C/ 90 ±3° F.
However, the useful life of the system’s standby batteries Fire alarm control panel models:
and the electronic components may be adversely affected ULCF30002G, ULCF30004G, ULCF30002GP,
by extreme temperature ranges and humidity. Therefore, ULCF30004GP, ULCF30002GNC, ULCF30004GNC,
it is recommended that this system and all peripherals ULCF30002GPNC, ULCF30004GPNC, ULCF30002GRM,
be installed in an environment with a nominal room ULCF30004GRM, ULCF30002GPRM, ULCF30004GPRM,
temperature of 15-27°C/60-80° F. ULCF30002GNCRM, ULCF30004GNCRM,
Verify that wire sizes are adequate for all initiating and ULCF30002GPNCRM, ULCF30004GPNCRM,
indicating device loops. Refer to manual Specifications ULCFR3000L2, ULCFR3000L4, ULCFR3000L2NC,
section for maximum allowable I.R. drop from the ULCFR3000L4NC.
specified device voltage. Designation system:
Like all solid state electronic devices, this system may The prefix “ULCF3000” is for a stand-alone panel.
operate erratically or can be damaged when subjected The prefix “ULCF3000” is for rack-mount panels that
to lightning-induced transients. Although no system are networked within the rack. The various control unit
is completely immune from lightning transients and models differ in the following manner:
interferences, proper grounding will reduce susceptibility.
Overhead or out-side aerial wiring is not recommended, 2G or L2 2-Loop panel
due to an increased susceptibility to nearby lightning 4G or L4 4-Loop panel
strikes. Consult with the Technical Services Department
GP 2-Loop panel c/w integral printer
if any problems are anticipated or encountered.
4GP 4-Loop panel c/w integral printer
Disconnect AC power and batteries prior to removing
2GNC or L2NC 2-Loop panel c/w network card
or inserting circuit boards. Failure to do so can
damage circuits. 4GNC or L4NC 4-Loop panel c/w network card
2GPNC 2-Loop panel c/w integral printer, network card
Remove all electronic assemblies prior to any drilling,
4GPNC 4-Loop panel c/w integral printer, network card
filing, reaming, or punching of the enclosure.
When possible, make all cable entries from the sides Model numbers followed by suffix “RM” have a Red
or rear. Before making modifications, verify that they will Metal enclosure backbox and cover.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 7


Introduction

1.4. Product features SLC Circuits (see fig.1)


•• The Panel has the following features: Communication Loop TB6, 7, 8, 9
Addressable Loops = Max 4
•• 120mm x 90mm Touchscreen Display Maximum Length, see Table 9
•• 2 or 4 SLC loops. Maximum Loop Current is 500ma (Short Circuit) or
200 ma (nominal)
•• Real time clock. Maximum Loop Resistance is 50 Ohms
Supervised and power limited Operation:
•• Event History Buffer (9,999 events) with Date/Time
Class A, Style 6 Supervised for:
stamp. Events canbe displayed on Touchscreen.
Ground faults impedance value 0Ω
•• 4 Notification appliance circuits (NAC’s) outputs.
When Installing SLC wiring in conduit, each loop must be
•• 3 programmable general purpose relays. installed in separate conduit.
•• Walk Test Facility The total number of addresses per loop is 200;
this includes detectors, call points and all other
•• Switchable 2 amp power supply 120/240 VAC 60 Hz. addressable items and call points. When designing
•• Dedicated alarm and trouble relays. systems it’s recommended that allowances are made for
future expansion, Short circuit isolators are incorporated
•• Housed in a 50cm W x 4 cm H x 20 D metal cabinet. into every Menvier loop device, including Smoke
detectors, heat detectors, sounders, manual pulls
•• Cabinet supports two 12V, 7Ah backup batteries.
and interfaces. Therefore, no further fault protection
•• Short circuit isolators incorporated into each loop. is required, in the event of a single fault; none of the
devices connected to the loop will fail to operate as the
•• Spur tolerant soft addressing fault will be isolated by the two adjacent devices.
•• Large multifunction touch screen Spur connected devices downstream of a cable fault will
cease to function.
•• Up to 200 addresses per loop
Notification appliance (see fig.1)
•• Fully monitored network cable up to 126 panels.
TB11, TB12, TB13, TB14, (Horns)
•• Optional integral printer +Out1, Minus1, +Out2, Minus2 (Strobes/Horns)
•• Alarm Verification 4 NACs Regulated Outputs (750mA each) for Horns only
•• PAS (Positive Alarm Sequence) using the main board (PCBA2314) or two (2) NACs for
strobes/horns using Wheelock DSM 12/24 (0.5Amp total
•• Pre-Signal per Point (NFPA 70, 72 compliant) for either one NAC or shared between both NAC1, NAC2)
•• Remote Alarm Silence, Reset , Disablement and When the product is powered by 240V, the maximum
Drill via addressablemodules current of 3.0 A is shared between the circuits on the
main board. (cont’d)
•• User Programmable password
When the product is powered by 120V, the maximum
•• Fully programmable from keypad or Local PC current of 2.25 A is shared between the circuits on the
•• Upload and Download facility main board.
•• Facility to download Logo When determining the Notification signaling scheme,
a panel may only provide power for either Horns from the
•• Autolearn Feature main board, or Horns/Strobes from the Wheelock synch
•• Battery Charger with Temperature Compensation module model DSM 12/24, but not both!

•• Detector sensitivity Supervised for:


Ground faults impedance value 0’Ω Regulated
1.5. Specifications NAC Specification
AC Power Four programmable outputs are Notification Appliance
Circuit (NAC). The NAC provide the following
(see fig.1) programmable modes:
120 VAC 60 Hz or 240 VAC 60Hz, 2.0 Amps (L hot, N Steady – 24 VDC at alarm condition
Neutral) Supervised
Pulsing – 24 VDC at alarm condition
Battery (Lead acid only) J5 (see fig.1)
Synchronization
Maximum Charging Circuit: Normal- 27.6VDC @ 1.0amp
The Control panel battery charge capacity is 2 X 12 AH. Cooper Wheelock DSM-12/24 R is for
Wire batteries in series to produce a 24 Volt equivalent. 11 Exceeder strobes (15cd). This module can
Do not parallel batteries to increase the Amp Hour rating. also synchronize horns.
It is recommended that the batteries are
Power limited circuitry and supervised Operation: Style Y
replaced every 5 years
(Class B) Nominal Operating Voltage =24 VDC
End of line Resistor = 6K8 1/5W 1% (part number

8 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


Introduction

ULEOR6K8) Refer to device compatible document listed


in table 2.
AC trouble outputs relay TB15
Contact rating: 1.0 amp @30VDC (resistive) form C relays

Alarm/Trouble output relay YPCB2294 TB1


Contact rating: 1.0 amp @30VDC (resistive) form C relays

Trouble output
12V NS, 30mA;
0V Trouble
Power Limited
Limited to same room installation
Special Application – Recorded range of compatibility:
13.7Vdc – 1.8Vdc

Network SLC
5V dc rated voltage; 100mA maximum current Maximum
Line Impedance 50Ω Power Limited

Table 1. 
Primary Operating Supply 120/240 V, 60 Hz, 2.0 A
Supervised
Secondary Operating 24 V dc nominal battery voltage
Supply 1.0A maximum battery charge current
0.1 Battery derating factor
12 Ah maximum battery capacity
Supervised
Notification Appliance 24 V dc nominal output voltage
Circuits, 0.75 A maximum output current
(Class B) - Style Y 50 ohms maximum line impedance
Sounder Group 1 sounder 1,
Sounder Group 1 sounder 2, When the product is powered by 240Vac, the
Sounder Group 2 sounder 1, maximum current of 3.0 A is shared between
Sounder Group 2 sounder 2; these circuits.

When the product is powered by 120Vac, the


maximum current of 2.25 A is shared between
these circuits.

Supervised, Power limited, Regulated


Notification Appliance 24 V dc nominal output voltage
Circuits, 0.5 A maximum output current
(Class B) - Style Y 50 ohms maximum line impedance
SYNC MODULE
NAC1, NAC2 The maximum current of 0.5 A is shared
between these circuits.

Supervised, Power limited,


Regulated
Alarm, Trouble Contacts. 30 V dc, 1 A, Unity power factor
Relay Expansion, Fig. 7 30 V dc, 1 A, Unity power factor
For connection to Power limited sources only
Aux Relay (AC Trouble) 30 V dc, 1 A, Unity power factor
Contacts For connection to Power limited sources only
Trouble Output (TB2, RL1) 12V NS, 30mA;
Trouble: 0V
Power Limited
Limited to same room installation
Special Application: Recorded range of
compatibility: 13.7Vdc – 1.8Vdc
Signaling Line Circuit 24 V dc rated voltage;
Style [6] Class [A]– 500 mA maximum current
(Addressable Loop) Maximum Line Impedance 50Ω
[Supervised, Power limited]
Network SLC 5V dc rated voltage; 100mA maximum current
Maximum Line Impedance 50Ω
Power Limited
Limited to Same-enclosure Installations

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 9


Introduction

Figure 1.  Typical wiring diagram

10 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


Introduction

Figure 2.  For further details on each device,


see the respective Installation Instructions.
Typical wiring diagram

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 11


Introduction

1.6. Controls and indication on the backup battery, the disabling of a notification
appliance, the ground faults, or short or open circuits.
1.6.1.Touch screen user button The alarm panel’s sounder will activate* if a trouble
condition exists. In a trouble condition, the panel displays
Acknowledge
the zone or devices causing the condition. When the
This function, also abbreviated to “ACK”, is used to situation causing the trouble condition is rectified and the
acknowledge an abnormal situation such as an alarm or panel is reset, the General trouble indicator goes out and
trouble condition. The acknowledge function tells the the trouble relay will return to its normal state.
panel that building personnel or emergency responders
System trouble LED (Yellow LED)
are aware of the alarm, trouble, or supervisory condition.
Acknowledging the alarm or trouble condition also Indicator is lit to indicate system malfunction or system
normally silences the panel’s own sounder. has been rebooted
Alarm silence Power trouble LED (Yellow LED)
Also known as “audible silence”. Depending on the Indicator is lit and the panel internal sounder will
configuration of the alarm system, this function will either activate*, when there is no power being provided to the
silence the system’s notification appliances completely, system from the Building’s electrical system or from the
or will silence only the audible alarm, with strobe lights battery backup .The touch screen display will display the
continuing to flash. Audible silence allows for easier cause of the trouble (AC trouble or Battery trouble).
communication amongst emergency responders while
responding to an alarm. This can also be used during If the trouble is due to the AC power input, the AC trouble
construction as a means of a preliminary test, relay will operate after a programmed delay set by the
before the final full test. user. The delay can be set at 0, 60, 120 or 180 minutes.
If the trouble condition is due to battery malfunction or
Reset battery being disconnected from the panel, the trouble
relay will also activate. When the trouble recondition has
This resets the panel after an alarm condition. All initiating
been restored the panel has been manually reset, the
devices are reset, and the panel is cleared of any alarm
LED and trouble relays will return to their normal state.
conditions. If an initiating device is still in alarm after the
system is reset, such as a smoke detector continuing to NAC trouble LED (Yellow LED)
sense smoke, or a manual pull station still in an activated
position, another alarm will be initiated. Indicator is lit, the internal sounder* and the trouble relay
also activates, it means that a trouble condition exists
Evacuate/Drill on the panel NAC circuits. This trouble condition is often
activated by a short or open of the NAC circuits. The
This will operate all the notifications appliances as well as
trouble relay also activates during this condition.
audible alarms as well as Panel’s own sounder.
When the situation causing the trouble condition
1.6.2.LED Indicators is rectified and the panel is reset, the NAC trouble
Power on LED (Green LED) indicator goes out and the trouble relay will return to
its normal state.
Indicator is lit, power is being provided to the system
from building’s electrical supply and or from the battery Silenced LED (Yellow LED)
backup. If this indicator is lit without any other indicators This signal indicates that the system has been silenced.
also lit, then the system is in a normal condition. All notification appliances have been silenced.
If no LED’s are lit, then there is no power source
feeding the panel System test LED (Yellow LED)
General alarm LED (Red LED) When the system is under a test condition such as
“walk test”, the system test led will be illuminated.
This indicator is lit when an alarm condition exists This led is off when the system is restore to
in the system, initiated by smoke detectors, heat its normal condition
detectors, sprinkler flow switches, manual pull stations,
manual call points, or otherwise. Along with the indicator Alarm silenced (Yellow LED)
on the panel, notification appliances, such as horns and
strobes, are also activated, signaling a need to evacuate Pre signal LED (Yellow LED)
to building occupants. In an alarm condition, the fire alarm LED is lit when the pre-signal feature
panel indicates where the alarm originated. The alarm has been implemented.
panel can be reset once the device which initiated the
alarm is reset, such as returning the handle of a manual Ground trouble
pull station to its normal position. When the panel detects a ground Fault condition which
General trouble (Yellow LED) indicates a short between any line extending from the
panel and the Earth Ground circuits, the Ground trouble
When held steady or flashing, it means that a trouble LED will be illuminated and the trouble relay will also
condition exists on the panel. Trouble conditions are activate during a trouble condition.
often activated by a contaminated smoke detector or an
electrical problem within the system. Trouble conditions When the trouble condition has been restored and the
are also activated by a zone being disabled (disconnected panel has been manually reset, the LED and trouble relay
from the system), a circuit being disabled, low power will return to their normal state.

12 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


Introduction

*Local piezo sounder


A piezo sounder provides separate and distinct sounds for
alarm, trouble andsupervisory conditions as follows:
•• Alarm - on steady
•• Trouble - pulse 1 second on and 1 second off
•• Supervisory - pulse ½ second on and ½ second off

1.7. Panel controls and indicators


1. System LED’s
2. Zonal LED’s
3. Touch screen display
4. Printer access door
5. Slot for optional printer

Figure 3. 
ULLCDF63000000
U

Power General General System Power NAC System Alarm Ground PRE-
ON ALARM TROUBLE TROUBLE TROUBLE TROUBLE SUPERVISORY TEST SILENCED TROUBLE SIGNAL

LED Name Function Action


1 Power On Shows Panel is On Check Indicator is Illuminated
2 General Alarm Indicators Panel has Detected a Fire Implement Fire Action Procedure
3 General Trouble Monitors Devices for Troubles e.g. Smoke detectors/Sounders Report to System Supervisor
4 System Trouble Monitors Fire Panel for Troubles Report Fault to Service Dept
5 Power Trouble Monitor Internal Battery Charger Report Fault to Service Dept
6 NAC Trouble Monitors NAC Circuits/Indicates Disablement of this Output Report Fault to Service Dept
7 Supervisory Part of the System has been Disabled Report to System Supervisor
8 System Test Indicates when System is under test Check with System Supervisor
9 Alarm Silenced Indicates panel has been silenced Implement Fire Action Procedure
10 Ground Trouble Display Activation (If Option Fitted) Check with System Supervisor
11 Pre-Signal Delays on Outputs Active Check with System Supervisor

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 13


Introduction

Figure 4.  1.8. Fitting printer paper role


1. Log book storage
Open the printer access door on the right hand side of the
2. Insert supervisor key here panel using the key provided. Drop the paper roll into the
3. Printer paper holder and feed paper into the printer. The printer
will then automatically pull the paper through if the panel
4. Paper roll storage is powered up. Tear off the excess paper them close and
secure the printer access door.
Please note for paper feed to operate correctly, paper end
must be straight.

Figure 5. 

1. Optional hinged cover


2. Scroll up
3. Acknowledge
4. Scroll down

14 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


2 Installation guidelines

2 Installation guidelines The ULCF3000 range of conventional fire alarm control


panels are designed in accordance UL864 9th Fire
2.1 Essential please read before proceeding! Detection and Fire Alarm systems Control and Indicating
Equipment.
The equipment described in this manual is listed by UL
Underwriters Laboratories, for use in fire alarm signaling 2.3 Calculating current draw and standby battery
systems, only when installed in accordance with this
manual and the latest National Fire Protection Association This section is to determine the current draw and standby
Standards NFPA 72; the National Electrical Code (NFPA battery needs for your installation.
70); the Life Safety Code (NFPA 101); and/or the local Maximum Battery Standby Load
authority having jurisdiction (AHJ).
It is recommended to use the battery Yuasa Battery
It is possible to apply system components incorrectly or (www.yuasabatteries.com). The required nominal batteries
arrange system components and installation wiring so capacity as versus standby current system is shown in
that required life safety functions are NOT performed. the table bellow (1-1).
As a result, lives may be lost.
Make sure that for the system configuration the standby
To minimize this possibility: is not more than 0.41 A for 12 Ah battery.
DO NOT deviate from any installation instructions
contained in this manual. Table 2. 
DO NOT assume any installation details not shown Battery Capacity, Ah Size , mm Maximum permissible System
in this manual. Model Standby current during
L W H 24 h
DO NOT alter any mechanical or electrical features of
the equipment supplied NP12-12 12 151 99 101 0.4100

BE FAMILIAR with the building code, fire prevention code,


and/or requirements of the Authority Having Jurisdiction 2.4 Calculating maximum current draw and
(AHJ) in the locale of the installation. battery backup requirements
This section will assist you in determining the maximum
CAUTION system current draw and standby battery needs for your
installation. Follow the steps below to determine the
Under normal and fault conditions, AC line voltages may current draw and standby battery requirements.
be present on any terminal. Touching any component
could be hazardous and result in loss of life. A short circuit Total standby and alarm current is determined by
can result in arcing that could cause molten metal injuries multiplying the quantity of items by its current draw.
to testing personal. To quickly determine maximum system current draw,
perform the following computations:
To minimize this possibility, only qualified electrical
technicians familiar with electrical hazards should perform Fill in the quantities of conventional detectors,
these checkout procedures. Safety glasses should be addressable detectors and devices.
worn by such personnel, and instruments used for voltage
Fill in the quantities and current draw of the Notification
measurement should be designed for the purpose and
Appliances or auxiliary-powered devices for each output
should be in good mechanical and working order.
from the manual for each specific device.
If there is application or installation information that is not
Fill in the total quantities of detectors and modules. The
clear or not covered in this manual, please contact us at:
detectors and modules total alarm current is determinate
Menvier Technical Support at +44 (0)1302 321541
by estimation method, under the hypothesis that 5% LED
2.2 Agency requirements will be ON.
The PANEL is listed by UL Underwriters Laboratories The required battery capacity is determined
to UL 864 9th edition as a FACP control unit for use in according to equation:
NFPA 72 systems. Cb >= (Isb* Tsb + Ia*Ta)*1.1
Requirements for All Installations
Where:
General requirements are described in this section. When Cb required battery capacity, Ah
installing an individual device, refer to the specific section
Isb standby current, A
of the manual for additional requirements.
Tsb supervisory time, 24hours
•• All field wiring must be installed in accordance with
Ia alarm current, A
NFPA 70 NationalElectric Code.
Ta alarm time, 5 min (0.0833 hours)
•• Use UL listed smoke detectors and notification 1.1 safety factor.
appliances compatiblewith the PANEL from those
specified in the Appendix to this manual. Make sure the total alarm current you calculated
•• A full system checkout must be performed every time (including current for the panel itself) does not exceed 4.0
the panel isprogrammed. Amps. This is the maximum alarm current allowable.
The calculation example is shown in the table 8.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 15


2 Installation guidelines

2.4.1 Detector technical characteristics UL approved


Table 3. 
Detector Head ULCAP320 ULCAPT340 UCAH330

Base WBA or UCAB300 WBA or UCAB300 WBA or UCAB300


Working Voltage 18-30Vdc 18-30Vdc 18-30Vdc
Voltage Waveform Filtered dc +/- 1v Filtered dc +/- 1v Filtered dc +/- 1v
max ripple @120Hz max ripple @120Hz max ripple @120Hz
Standby Current (Average) 220 uA 220 uA 220uA
Alarm Current (max) 5 mA 5 mA 5 mA
Relay Current (max) N/A N/A N/A
Start-up Time 2 seconds 2 seconds 2 seconds
Sensitivity 2.55+/- 0.33%/ft 2.55+/- 0.33%/ft N/A
Sensitivity use checker Use No-Climb Use No-Climb Use No-Climb
TRUTEST TRUTEST TRUTEST
UL Listing 77TL UL Listing 77TL UL Listing 77TL
Heat Element rating N/A 135ºF 135ºFROR
+Fixed + Fixed
*135ºF Fixed
Reset Time (max) 2 seconds 2 seconds 2 seconds
Heat Detector N/A 50ft 50ft
(heat alone operation)
Ambient Temperature 32-100ºF 32-100ºF 32-100ºF
32-50ºF (194ºF
Mounting Position Ceiling in open areas Ceiling in open areas Ceiling in open areas
Compatibility Identifier W002 W002 W002

2.4.1.1 Calibrated detector sensitivity


Table 3
Part Code Type Normal Pre-Alarm Alarm Trouble

ULCAP320 Optical 10 – 49 50 – 59 60 – 255 0 – 10


(Nominal 20)
ULCAPT340 Optical Heat 10 – 49 50 – 59 60 – 255 0 – 10
(Nominal 20)

Normalized smoke detector value versus %/Ft:


Table 4. 
Normalised Smoke detector response ULMAP320 & ULMAPT340

20 0%/Ft
50 1.91%/Ft
60 2.55%/Ft

16 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


2 Installation guidelines

2.4.2 UL Approved audio visual devices


Table 5.  Notification appliances
Horn strobe ratings per UL 1971 & UL 464 at 24 Vdc
UL Max Current* at 99 dB(A)
24 Vdc 12 Vdc
Mode Regulated 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Voltage
Range Vdc
HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159
HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125

Horn strobe ratings per UL 1971 & UL 464 at 24 Vdc


UL Max Current* at 95 dB(A)
24 Vdc 12 Vdc
Mode Regulated 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Voltage
Range Vdc
HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153
HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122

Horn strobe ratings per UL 1971 & UL 464 at 24 Vdc


UL Max Current* at 90 dB(A)
24 Vdc 12 Vdc
Mode Regulated 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Voltage
Range Vdc
HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120

Table 6.  Product codes

Part Code Description

HSR Wall mounted horn strobe


HSWC Ceiling mounted horn strobe
HNR Wall mounted horn
HNWC Ceiling mounted horn
STR Wall mounted sync strobe
STWC Ceiling mounted sync strobe
RSSWP-2475-FR Weatherproof wall mounted sync strobe
RSSWP-2475C-FW Weatherproof ceiling mounted sync strobe

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 17


2 Installation guidelines

Table 7.  Examples of battery calculations


QUANTITY QUANTITY STAND-BY MAXIMUM TOTAL TOTAL
OF DEVICE/ OF DEVICE/ CURRENT ALARM STAND-BY ALARM
MODULE MODULE (Amps) CURRENT CURRENT CURRENT
IN ALARM (Amps) (Amps) (Amps)
CONDITION
MAXIMUM
SYSTEM COMPONENTS

Main System on Standby (Loop + Mother Board + 1 0.23 0.23


Display + Network Card)
Panel in Alarm (As above + Synch Module+ 0.27 0.27
Relay Board+ Zonal Led’s)

Loop 1
Photoelectric smoke sensor ULCAP320 100 5 0.00022 0.005 0.022 0.025
Multi-mode heat sensor UCAH330 50 0 0.00022 0.005 0.011 0
Photo-thermal smoke sensor ULCAPT340 50 0 0.00022 0.005 0.011 0
Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0
Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0
3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0
Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0
Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0
Loop-mounted repeater ULCF3000PR 0 0 0.00031 0.00035 0 0
4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0
Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0
120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0
Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

Loop 2
Photoelectric smoke sensor ULCAP320 100 5 0.00022 0.005 0.022 0.025
Multi-mode heat sensor UCAH330 50 0 0.00022 0.005 0.011 0
Photo-thermal smoke sensor ULCAPT340 50 0 0.00022 0.005 0.011 0
Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0
Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0
3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0
Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0
Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0
Loop-mounted repeater ULCF3000PR 0 0 0.00031 0.00035 0 0
4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0
Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0
120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0
Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

Loop 3
Photoelectric smoke sensor ULCAP320 100 5 0.00022 0.005 0.022 0.025
Multi-mode heat sensor UCAH330 50 0 0.00022 0.005 0.011 0
Photo-thermal smoke sensor ULCAPT340 50 0 0.00022 0.005 0.011 0
Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0
Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0
3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0
Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0
Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0
Loop-mounted repeater ULCF3000PR 0 0 0.00031 0.00035 0 0
4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0
Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0
120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0
Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

18 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


2 Installation guidelines

Loop 4
Photoelectric smoke sensor ULCAP320 100 5 0.00022 0.005 0.022 0.025
Multi-mode heat sensor UCAH330 50 0 0.00022 0.005 0.011 0
Photo-thermal smoke sensor ULCAPT340 50 0 0.00022 0.005 0.011 0
Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0
Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0
3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0
Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0
Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0
Loop-mounted repeater ULCF3000PR 0 0 0.00031 0.00035 0 0
4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0
Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0
120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0
Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

AC Trouble Relay (0.025 Quiescent) 1 0 0 0 0


Trouble relay coil current (0.025 Quiescent) 1 0 0 0 0
0

Alarm Trouble 1 0 0.025 0 0.025


LON Card 0 0.035 0.035 0 0
Network-mounted repeater ULCFTR3000 0 0

NOTIFICATION APPLIANCES
NAC # 1 1 0.75 0 0.75
NAC # 2 1 0.75 0 0.75
NAC # 3 1 0.75 0 0.75
NAC # 4 1 0.75 0 0.75
A)Supervisory (Standby) Current, (A) 0.406 0.28936 3.39 0.406 3.395
B)Supervisory Time(24 hours) 24
C)Supervisory requirements(A*B) 9.744
D)Alarm Current 3.395
E)Alarm time hours (5min=0.0833,10min=0.167) 0.0833
F)Alarm Requirement 0.2828035
G)Battery backup (C+F) 10.026804
H)10% Safety Factor (=G*.1) 1.0026804
I)Battery Requirement with 10% safety factor(=G+H) 11.029484
REQUIRED BATTERY SIZE Ah 12

Table 8.  Examples of battery calculations Table 9. 

2.4.3 Maximum number of devices Wire Gauge 22AWG 18AWG 16AWG 14AWG

The maximum number of Menvier addressable devices mm2 .34 1.0 1.5 2.5
per SLC circuit is 200. The Menvier Panel can support Maximum 1500 feet 3900 feet 6200 feet 10,000 feet
up to 4 SCL circuit, a total of 800 addressable devices. Distance

2.4.4 Wiring requirement for SLC circuits


Must meet the National Electric Code 760-51
requirements for power limited fire protective
signaling cables.
Maximum wiring resistance is 50 ohms and maximum
loop length depends on the wire gauge as per below.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 19


3 Installation

3 Installation 2. Mount the enclosure in a clean, dry, vibration-free area


where extremetemperatures are not encountered.
Read all the installation instructions before commencing The location should be readilyaccessible with sufficient
with the installation. The installation of this panel must be room for easy installation and maintenance.
carried out by a suitably qualified /trained person. 3. Locate the top of the cabinet approximately 5 feet
With the hinge mounting on the left, determine the (1.5 m) above the floor.
number of conductors required for the devices to 4. Mount by using the two mounting holes located in
be installed. Sufficient knockouts are provided for the upper back of thecabinet. After the panel has been
wiring convenience. properly located using the mountingholes, the panel
Select the appropriate knockout(s) and pull the conductors can be secured.
into the box. All wiring should be in accordance with the 5. Complete all conduit connections to the cabinet.
National and/or Local codes for fire alarm systems. Use the knockoutsprovided in the top and the sides.
6. 6.Wire must NOT enter the bottom of the cabinet,
3.1 Mounting the enclosure since this area is intendedfor batteries only.
The ULCF3000 and ULCF3000RM can be flush mounted
or surface mounted. The electronic components within the fire panel are Static
Sensitive. Do not touch the electronics directly.
Install the Enclosure as follows:

1. Carefully unpack the system components and inspect


for any damage dueto shipping.

Figure 6.  Panel mounting dimensions

132 mm 400 mm
309 mm
227mm
364 mm

472 mm

20 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


3 Installation

3.2 Earth cable on ULCF3000RM Cable anchorage


(does not apply to ULCF3000) The mains cable must be fixed securely with a 20mm
Care must be taken to ensure that the earth connection cable gland. Remove a suitably located knockout feed
between the back box and the front cover of the on the cable through the gland and bolt the gland to the
ULCF3000RM is connected each time the cover is ULCF3000 and ULCF3000RM backbox as shown.
removed and refitted. Ensure that there is a serrated Secure the cable to the side of the box using the cable
washer fitted between the earth terminal and the nut on clip provided.
both ends of the cable. Connect wiring from AC mains to J2 on the PCBA2147
being careful to observe proper connections in the figure
below.
Figure 7.  Earth strap
NNote: Apply the AC Power BEFORE connecting the
batteries to the Panel!
NNote: Apply AC power to panel after the system is
completely installed and visually checked.

Figure 8.  AC power entry

Live(Hot) L
3.3 Installing cabling
Neutral N
Once the backbox is mounted the next stage is to install
the power and loop cables and fit the glands. Earth
3.4 Connecting the AC Power and earth
connection
WARNING
To reduce the risk of electrical shock, make sure that
all power has been turned off or disconnected prior to
attempting to connect power to the Power Supply.
NNote: Make sure that AC main circuit breaker is off
before wiring any connection between mains and
control panel
The primary power needed for the Menvier Fire Alarm
Control Panel is 120VAC 60hz or 240VAC 60Hz.

1. 1.Enter Power Cable into Cabinet knock out hole.


2. 2.Attach the brown (live) wire from the source to
terminal “Line” (USA usecolor black wire).
3. 3.Attach the blue (neutral) wire from the source to the
“Neutral” terminal (USAuse color white wire).
4. 4.Attach the ground wire from the source to the “GD”
terminal block (USA usecolor green wire).

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 21


3 Installation

3.5 Battery installation 3.6.1 Class B Style Y NAC wiring using main
The batteries are placed at the bottom of the enclosure by board (Horns only)
removing the four nuts holding the battery plate.
The ULCF3000 is fully protected if the batteries are Figure 10. 
connected in the opposite direction the battery fault
yellow led will show steady in such a condition. When 6K8
green battery LED is in a steady condition to shows that Resistor
the battery connection is normal. + + + +

Figure 9.  Battery connection + + + +

Red wire
Black wire
Interconnecting
Cable

12V Battery

12V Battery 3.6.2 Class B Style Y NAC Wiring using


Wheelock DS 12/24 (Horns & Strobes)

Figure 11. 
WARNING ULEOR6K8
Before connecting the battery to the fire alarm panel. Resistor
Ensure the interconnecting cable between the batteries is
not connected. Do not connect this cable until the system + +
is fully installed. Supervised Power
Limited

3.6 Output (NAC) installation + +


The Panel is equipped with 4 regulated Class B
Style Y NAC (Notification Appliance Circuits). At 240Vac
input, use 4 horns 0.75A each for 3A total . At 120Vac
input, use 3 horns, 0.75A each for 2.25A total. At either
240Vac or 120Vac, use 2 NACS for strobe synchronisation
using Wheelock DS 12/24 with 2 regulated outputs
at 0.25A each or 0.5A total.
Use UL listed notification appliances only
(see table 2). These appliances capable of producing MINUS OUT MINUS OUT
the American National Standards Institute’s ANSI S3.41 2 2 1 1
audible emergency evacuation signal pattern, and are
synchronized on a system basis. These devices can be
silenced system or globally.

22 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


3 Installation

3.7 SLC Installation


Four SLC loop Class A Style 6 are provided on the
Menvier Fire Alarm Panel main board. These SLC groups
provide communication to addressable detectors,
monitors, indication devices and control modules.

Figure 12.  SLC Instillation


LED remote indicator CIR301

Class A
connection returns back to loop A- A+

Maximum of 200 addressable devices per SLC circuit


(see fig. 2)

3.8 Supervisory signal


Addressable devices can be programmed for supervisory
signals. This input on a latching mode and requires a
manual reset to restore their normal state provided the
condition is cleared.
Panel relay outputs
The panel has 3 Form C relays 30V 1A (resistive) Alarm,
Trouble, and AC Trouble.
The AC Trouble relay can be programmed as per
NFPA 72 requirements.
These three out puts can be used to connect to a
central station using Firewatch 411UD Digital Alarm
Communicator Transmitter.
Technical specifications
Contact rating

Figure 13 . Panel relay Nuopuos


1A @ 30VDC (PF=1)

AC
Trouble
Alarm
AUX Relay

Trouble
Fault
Sounder

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 23


4 Networking

4 Networking This can either be connected in a loop of an individual


panel or it can be connected to the network.
This operation is only UL approved while connected in
the same enclosure (rack) since the Network Card cannot The recommended network cable for the network
detect Ground Faults. connection between panels is an enhanced Firetuf cable
Manufactured by Draka cables (part number 910234.)
Only the Network Repeater while in passive mode and
only able to silence it’s own audible device (piezo buzzer) Screen continuity must be maintained throughout the
may be networked. entire network circuit including at each junction point.
The screen should only be earthed at the connection point
Up to 126 ULCF3000 and ULCF3000RM panels or passive provided at the first panel and not at any other point.
repeaters can be networked together to The screen or drain wire of the network cable should not
operate as a single networked system. To achieve this be considered as a safety earth and therefore should not
each panel must be fitted with a network card be connected to terminals marked with the earth symbol,
(supplied at additional cost.) except at the panel, and should not be insulated with
green and yellow sleeving
When operating as a networked system all fire and
fault event information is displayed at every panel, Where the network cable passes between buildings,
silencing and resetting of alarms can also be carried screen continuity should not be maintained from building
out from any panel on a networked system if panels are to building. A booster device must however be used
suitably configured. irrespective of cable length and should be fitted at a
suitable point in the link between buildings. The cable
Networked panels are connected using a loop topology screen should be connected to the earth of one panel
as illustrated. in each building.
Networked panels can be used as active repeaters;
alternatively a low cost passive repeater is available.

Figure 14 . NeowNrk example

NET1 NET2

NET1 NET2

24 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


5 Technical specification

4.1 Battery maintenance installation cautions 5 Technical specification


Initial preparation before installation:-
Power Supply
(Approved UL 864 9th
Verify no abnormalities on battery case Edition) Mains
(like crack or leakage)
Nominal Voltage : 120 Vac
Free air space must be provided between each Nominal Current : 240 Vac
Maximum Current : 75mA
battery. Recommended minimum space is 5~10mm Input Fuse R1 : 1.5A
(0.02~0.04 inches). : NTC SG39 Imax 4Amp
Set the batteries firmly in the equipment. Otherwise, Output Voltage including tolerances : 26V = 18.5 to 29.5Volts
batteries may be damaged, or connection conductivity : 26V RAW = 18.5 to 29.5Volts
: 5Volt Output = 4.6V to 5.5V
may be decreased due to shock. When batteries are used
in vibration conditions, they shall be mounted in upright Ripple Voltages 26V = 800mV
26V RAW = 800mV
position and with proper cushion for protecting vibration. 5Volt Output = 430mV
Avoid mixed usage of batteries differing in capacity, Maximum Loadings 26V O/P = 0.98A I max b
manufacturer, storage or charge/discharge conditions. 26V RAW O/P = 1.7A I max b
5V = 0.5A
Batteries may be damaged after cycles due to difference
in electrical characteristics. Standby Current : 26V = 280mA I max a
(4 Loops Loaded) : 26V RAW = 150mA I max a
Regular check and replace precautions : 26V = 280mA I max
: 26V RAW = 150mA I max
Measure the total voltage of the batteries during float : 5V = 43mA
charge to see whether there is any abnormal deviation
and investigate the situation. ULCF3000 and ULCF3000RM is protected by an internal
thermal device, this requires no maintenance.
TRANSPORTATION PRECAUTIONS
I max a, I max b & I min = Current as specified in UL 864
Handle the batteries carefully to avoid injuries. 9th Edition
Avoid moisture or rain on the batteries and cartons.
Transport the batteries in the upright position and avoid Batteries
abnormally strong shock / vibration.
Number of Batteries :2
Do not lift a battery by its terminal. Otherwise, internal Manufacturer: :YUASA NP12-12
Capacity : 12 Ah
construction may be damaged and leakage may occur. Battery Fuse : 6.3A Anti-Surge (F4)
Maximum battery current : 3.5 Amps
Other precautions Standby current (mA) :175 (4 loops), 125 (2 loops)
Maximum Charging Current to
Clean battery with wet soft cloth. Never apply oil, the Batteries : 0.970amp
polyvinyl chloride or organic solvents (like gasoline and Float Voltage : 27.4 Volts
paint thinner) to the battery. Otherwise, battery cover may Final Voltage : 20.4Volts
be cracked / deform and acid leakage will result. Charging Characteristics : Constant Voltage with 0.970A limit
with temperature Compensation
Do not disassemble the battery. Otherwise, sulphuric acid Maximum current drawn from the : 3.5Amps
will flow out. batteries when the mains is not
available
If sulphuric acid deposit on to skin or cloth,
wash immediately with water. If splashed into eyes, Deep Discharge Protection : 20.6 Volts
Battery Internal Impedance Fault : >0.5 ohms
wash with a large amount of water and consult medical
physician immediately.
Avoid dusting by cloth duster or dry cloth (particularly
chemical textile), as they will generate static electricity CAUTION
which is dangerous.
Risk of explosion if battery is replaced by an incorrect
Wash your hands after handling battery. type. Dispose of the used batteries according to the
Do not short the battery terminals. instructions.

Never dispose battery into fire.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 25


5 Technical specification

Outputs
NAC circuits

Number of sounder circuits :4


Total sounder Load : 0.75 Amp max per sounder or 1.5 Amp max per sounder with
Wheelock DSM 12/24 (2 circuits)
Sounder Circuit Fuses (F1/2/3/4) : 1.6 Amp (Quick Blow)
End of line resistor : ULEOLR6K8

AC Trouble, alarm trouble, trouble outputs

The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load : 30 Volts 1 Amp Resistive
AC Trouble Relay: Fused (PTC) : 1.1 Amp

Printer (Optional)

Type : High speed thermal


Number of Characters per Line : 40
Type of paper : 58mm x 46mm Thermal Roll
Replacement paper roll order code : ADF6PRINTERPAPER

Mechanical specification

Weight including batteries : 18Kg


Weight excluding batteries : 9Kg
Dimensions (Standard batteries) : 495mm(L) x 395mm(H) x 180mm(D)
Type of Material (backbox) : Mild Steel (Power Coated)
Type of Material (Fascia) : PC/ABS
Flammability Rating : UL 94 5VA
Total Number of knockouts : 51
Diameter of Knock out : 20mm
Anti-Tamper Cover ( Optional)
Material used : Poly Carbonate
Flammability Rating : UL 94 5VA

Terminal blocks: do not use excessive force


when tightening the screws.

26 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


6 Commissioning

6 Commissioning Loop checking with a multimeter


Before connecting and powering up the panel please The first quick test that should be done on all the loops is
ensure you read and understand the manual. to check the continuity of the loops using a multimeter.

The following is a summary of the minimum steps to start The resistance should be measured start positive to end
the Menvier ULCF3000 Fire Alarm Panel. positive, start negative to end negative, and positive to
negative at the start and end of each loop.
1. Read Manual The resistance along the positive line should be less than
2. Ensure all cables are fault free (no ground, Open or 50 ohms. The resistance across the negative line should
short circuit faults) and follow the procedure below. be 2k5 ohms for each device on the loop, e.g. 20 devices
should measure 50k ohms.

Figure 15 . CNmmissiNning prNcedure The resistance across the loop positive to negative will be
in the Mohm region.
Check the loops with a multimeter Ensure the screen is continuous around the loop;
this reading should be approx 10 ohms.
 The screen should not be bonded to building earth.
Auto Learn the panel
Test the loops with the multimeter set to AC volts – this
 is to check that there is no induced voltage which could
be caused by the cables being run too closely to a high
Load to a PC (optional) voltage source.

 This will show if anything drastic is wrong with the loop


devices wired in backwards breaks etc. If there is a short
Download from a PC at the end or start of the loop this will need to be fixed
before powering the panel.
 Auto-learn function (see page 46)
Check auto Config This is accessed through the engineer level access code.
 When the panel is auto-learned all the devices address
information is set up from address 1 upwards from the
Run Intermittent Fault search start of each loop, previous addressing is lost. Once the
panel has finished the auto-learn it will reset itself. After
 this is done reset the panel using the touch screen.

Test the device Check auto config.


This function has two purposes, the first is to check that
when a database has been downloaded the transmitted
data matches the device data on the loop and then it
highlights any anomalies as device unknown or device
type mismatches.
The second is to pinpoint any o/c or s/c faults on the loop.
The panel achieves this by electronically disconnecting the
return legs and interrogates the devices on the loop. If
there is a break the panel will go to fault stating the first
device it cannot see beyond the break. This same function
also pinpoints short circuits in the same way, creating a
fault beyond the point where an isolator has opened.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 27


6 Commissioning

6.1 Configuration Up/downloading using PC software (see page 45)


Detector LED flashing The PC Software enables the panel to upload all the
address, location text, any comments and programming
The ULCF3000 and ULCF3000RM detector flashing of inputs and outputs to be downloaded back to panel.
function is used to allow a visual inspection and This will speed up commissioning.
confirmation that the fire panel is in communication with
the installed system devices. This facility can be accessed
via the engineering menu and can be switched on or off
at any time as required.
ULC F300 0

6.2 Panel programming purpose of notifying key personnel who then have the
option of initiating a general alarm. All NAC’s circuits,
Positive alarm sequence and Auxiliary outputs can be pre-programmed with a delay
of up to 10 minutes using Menvier Site Installer software
The positive alarm sequence will program a delay to the
by using a double knock global or zone feature.
NAC’s, Alarm relay and Auxiliary for a period of
15 seconds, if the alarm is acknowledge, it will silence During this condition, the Pre-signal will be lit.
the piezo sounder and start a timer which prevents
activation of these outputs for an additional time duration Alarm verification features
which can be user programmed for up three minutes. The panel is equipped with the Alarm verification features
After the programmed delay, all the outputs will activate used to reduce unwanted false alarm wherein a typical
if the source of the alarm is not cleared. If the alarm is smoke detector report alarm condition for minimum
not acknowledged or reset during the first time delay of period of time in order to accept a valid alarm condition.
15 seconds, all the appropriate outputs will be activated. This period can be programmed to 15s, 30s or 60s.
Note: If a second alarm occurs during either time delays, During the minimum 60-second alarm confirmation period
the alarm will proceed immediately causing activation of following the retard-reset-restart period, re-actuation of
the appropriate output zones. the same detector that initiated the alarm verification
Pre-signal: An arrangement where the operation of an cycle, actuation of another smoke detector on the same
automatic detector or initial operation of manual station circuit (zone), or an alarm from another zone shall result
actuates only on selected devices or devices for the immediately in an alarm signal from the control unit.

Figure 16 . Alarm verificaoiNn oiming diagram

Retard-Reset-Restart Period -
Maximum 60 Seconds
No Alarm at Control Unit No Alarm at Control Unit

t=0 seconds t=n seconds

28 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


6 Commissioning

6.3 PC Commissioning Software


6.3.1 Device input programming

Normal Standby  Default setting

Alarm  Panel reports fire from device.


Trouble  Panel reports fire from device.
Reset  Panel resets.
NAC Silence  Silence all currently active sounders.
Supervisory  Panel reports supervisory from device.
Drill  Panel manually set into alarm.

NAC Programming
Pre-Signal
The output of a device when triggered can be delayed up
to 10minutes - based on a user defined value in minutes.
This programming option is enabled when a value other
than zero is entered inside the ‘Delay’ window.

Every panel must be configured with the pre-programmed


delay Double Knock per Zone is required for outputs to
operate pre signal.
Double Knock feature will override:
•• Pre programmed delays
•• Alarm Verification
•• Positive Alarm Sequencing

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 29


7 Panel controls & indicators

7 Panel controls & indicators The Touch Screen is a multi-function display consisting
320x240 dots featuring high intensity backlighting.
7.1 Touch screen display In normal operation, the display indicates as above with
the backlighting off.
During an event on the system the display shows the
Access
FIRST EVENT and LAST EVENT plus other events as
Code
space allows.
The last 2 lines are normally used to display the total
number of events, but they are also used for scrolling
fire conditions, faults, pre alarms or disabled devices
independently or for displaying a reduced menu when
in fire condition.
When an event occurs the Touch Screen backlighting
comes on unless there is a mains power supply fault.
Use the Touch Screen to scroll through all active events
on the system by using the SCROLL UP and SCROLL
DOWN buttons (available at access level)

1. You can display the contents of the log and also view
details of any Alarms, Troubles, pre-alarms, faults or
disablements. When displaying the system menu on
the Touch Screen, the last 5 lines of the display are
shown in reverse text.

7.2 Panel operation Access


Code
ULCF3000 and ULCF3000RM are operated via a backlit
touch screen. The default fire screen is shown below.
From this screen all the panels’ functions can be
operated. The first time you touch the screen the backlight
will illuminate the panel.

Pressing a field will highlight it and forward to the next


screen as shown below.

Access Access
Code Code

30 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.3 Public access level 1


Public access level does not require an access code and
allows anybody to review the functions outlined below

Access
Code

Access Access
Code Code

Access Access
Code Code

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 31


7 Panel controls & indicators

7.4 Evacuate (Access level 2) 7.5 Silence alarms


To activate the touch screen, touch the top left corner To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter supervisor mode touch the supervisor button and enter
the passcode. the passcode.
Enter the Supervisor Mode Passcode and select Enter the Supervisor Mode Passcode and select
“Evacuate” on the menu at the top of the screen. “Silence Alarms” button as the top of the screen.

Select “Yes” to evacuate the building. Select “yes” to silence Alarm.

32 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.6 Acknowledge
To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the passcode.
Enter the Supervisor Mode and Select “acknowledge”
from the Top Menu.

7.7 Reset
Enter the Supervisor Mode and Select “Reset” from the
top Menu. Select “Yes” to reset the panel.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 33


7 Panel controls & indicators

7.8 Pre-alarms 7.10 Troubles


Enter the Supervisor Mode and Select “Pre-Alarms” tab. Enter Supervisor Mode Passcode and select “Troubles” tab

A pre-alarm is shown when a detector appears to register


heat or smoke but in a quantity that is insufficient to 7.11 Enable/disable (Others menu)
warrant an alarm.
To activate the touch screen, touch the top left corner
Pre-alarm may indicate a buildup of dirt in a smoke of the screen until the screen illuminates. To enter the
detector which can be interpreted by the detector as supervisor mode touch the supervisor button and enter
smoke presence. the passcode.
Enter the Supervisor Mode passcode and select the
7.9 Disabled devices “Others” tab.
Enter the Supervisor mode and Select the “Disabled” tab.

The individual buttons show which devices and the


number of devices which have been disabled. Press one
of the buttons to display detailed information for
a particular category.

34 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

The Enable/Disable
feature allows the
operator to disable part
or a whole system by
the sub menus shown
on the left.

The “Disable All” feature is not permitted


in UL864 9th Edition

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 35


7 Panel controls & indicators

7.12 Print 7.13 Lamp test


To activate the touch screen, touch the top left corner To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter supervisor mode touch the supervisor button and enter
the passcode. the passcode.
Enter the Supervisor Mode and Select the “Others” Tab. Enter the Supervisor Mode and Select the “Others” Tab.
Press “Print” Press “Lamp Test”

Select the Information you wish to print from


the Buttons Listed

36 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.14 Weekly test


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the passcode. Select the others tab as shown below.
Press Weekly test.

Weekly test is now in progress.

The panel will automatically return to the system healthy


screen once the weekly test has been completed.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 37


7 Panel controls & indicators

7.15 Viewing events


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the passcode.
Enter the Supervisor Mode Passcode. Select the
“Others” tab and press View Log.

Use the scroll bar to view the list of up to 9999 events

The ULCF3000 and ULCF3000RM event log stores up


to 9999 events including, Alarms, Troubles, resets and
address changes. Once the maximum 9999 events
have been reached ULCF3000 and ULCF3000RM will
automatically overwrite the oldest event every time a new
event is stored. The event log can only be reset by an
approved service engineer.

38 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.16 Check auto config


To activate the touch screen, touch the top left corner Tab. Press Check Auto Config. This feature will scan the
of the screen until the screen illuminates. To enter the loop and pinpoint the exact location of any break in the
supervisor mode touch the supervisor button and enter loop wiring and will also identify any changes in the loop
the passcode. configuration (e.g. New devices added or changed
Enter the Supervisor Mode and Select the “Others” device types).

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 39


7 Panel controls & indicators

Replace device enables an existing device to be replaced


with a new device without losing the existing text and
sounder programming.
Replace a single device then use the replace device menu
to allocate an existing address to the new device.

40 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.17 Test device (Access level 3)


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
service mode touch the supervisor button and enter
supervisor passcode.

Touch row to select device to test.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 41


7 Panel controls & indicators

7.18 Test zone


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode, Select “Test” and on the Screen
Shown Below Press “Test Zone”

42 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.19 Sounder level test mode


Enter the Service Mode and Select Test. From the Test
Menu Select “Sounder Level Test Mode”

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 43


7 Panel controls & indicators

7.20 Global flashing LED on/off


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode and Select test.

If global LED flashing is


set to on, all device
LED’s will pulse
intermittently to confirm
correct communication.

Select “Global Flashing


LED On/Off” from the
Test Menu Screen.
Test Device

Test Zone

Sound Level Test Mode

Global Flashing LED On/Off

One Man Walk Test

44 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.21 One man walk test


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode and Select Test.

Select “One Man


Walk Test” from the
Test Menu Screen.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 45


7 Panel controls & indicators

7.22 Commission: Load CDR from laptop


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode and Select Commission.

Select “Load CDR


from Laptop” from the
Commission Menu”

After pressing “Yes” click


commission on the PC
download software.

Important:

Do not click commission


before pressing “Yes” on
the “Load CDR” screen.

46 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.23 Commission: Download CDR to laptop


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode and Select Commission.

Select “Download
CDR from Laptop”
from the Commission
Menu Screen.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 47


7 Panel controls & indicators

7.24 Commission: Auto learn


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode and Select Commission.

Select “Auto Learn”


from the Configure
Menu Screen.

Important:

Activating autolearn
will erase all existing
programming, text
and configuration
data.

48 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.25 Erase log


To activate the touch screen, touch the top left corner
of the screen until the screen illuminates. To enter the
supervisor mode touch the supervisor button and enter
the service passcode.
Enter the Service Mode and Select Commission.

Select “Erase Log


and Reset” from
the Configure
Menu Screen.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 49


7 Panel controls & indicators

7.26 Change date/time


Enter the Service Mode and Select Configure. Select Set the Time Using the Buttons Shown Below.
Change Date/Time.

7.27 Change Text


Enter the Service Mode and Select Configure. Select Set the Time Using the Buttons Shown Below.
“Change Text”

Select the Address you wish to change and edit using the
keyboard

50 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.28 Change zone text


Enter the Service Mode and Select Configure.
Select “Change Text”

Select the zone you wish to Change and


Edit Using the Keyboard

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 51


7 Panel controls & indicators

7.29 Change panel text


Enter the Service Mode and Select Configure.
Select “Change Text”

Press “Change
Zone Text

52 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.30 Configure zones


Enter the Service Mode and Select Configure.
Select “Configure Zones”

Select Zone into which


device will be added

Touch the dash to


move the device into
the selected zone.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 53


7 Panel controls & indicators

7.31 Change user code


Enter the Service Mode and Select Configure. Select
“Change User Code”

54 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.32 Add zone 7.33 Delete zone


Enter the Service Mode and Select Configure. Select “Add Enter the Service Mode and Select Configure, select
Zone” “Add/Delete” then “Delete Zone

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 55


7 Panel controls & indicators

7.34 Add device 7.35 Delete device


Enter the Service Mode and Select Configure, select Enter the Service Mode and Select Configure, select
“Add/Delete” then “Add Device” “Add/Delete” then “Delete Device”

Select a Loop Select a


to Add a New Device to
Device Delete

Confirm Confirm or
New Cancel
Device Deletion
and Loop

56 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


7 Panel controls & indicators

7.36 Configure heat detectors 7.37 Network


Enter the Service Mode and Select Configure. Select Enter the Service Mode and Select Configure. Select
“Configure Heat Detectors” “Network”, this menu defines whether messages are
broadcast across the network or remain local.

Select a
Device to
Configure

Select appropriate detector class

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 57


7 Panel controls & indicators

7.38 Password protection

The Menvier ULCF3000 and ULCF3000RM system


has password protection which restricts access to the
DISABLE Menu and to TEST/COMMISSIONING MODE.
The password is a four digit code and the default number
is 2214 for access level two and 143243 for access level
three. The password entry screen is accessed via the
supervisor mode button. Press supervisor mode and
the password entry screen will be displayed, type in the
passcode and press Ok. If the wrong password is entered
three times further access to the system is denied.

58 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


8 Battery disposal instructions

8 Battery disposal instructions


Although batteries contain lead and small amounts of
antimony and arsenic, they are safe if handled according
to the accompanying guide. The battery cells must not
be dismantled as this involves several hazards, which are
best handled under controlled conditions, using special-
ised equipment. No attempt should be made to repair any
batteries; they should be treated as disposable when they
have outlived their use.
Batteries must be disposed of in accordance with current
waste disposal and pollution legislation and in particular;
The Environment Protection Act 1990, Special Waste
Regulation 1996. It is recommended that the following
authorities are contacted before any attempt is made to
dispose of batteries; Environment Agency Local office,
Local Authority Environmental Health or Waste Handling
department.

ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com 59


9 Compatibility List

Name of panel Model number of device Description File number

ULCF30002G, ULCAPT340, UCAPT340 Analog Photoelectric Smoke, S35885


ULCF30004G, Complimentary Fixed Temperature
ULCF30002GP, Heat Detector
ULCF30004GP,
ULCF30002GNC, UCPT-2W Conventional Photoelectric Smoke, S35885
ULCF30004GNC, Complementary Fixed Temperature
ULCF30002GPNC, Heat Detector
ULCF30004GPNC, ULCAH330 Analog Fixed Temperature S35887
ULCF30002GRM, Heat Detector
ULCF30004GRM,
ULCF30002GPRM, UCHR-2W, UCHRI-2W, Conventional Combination Electronic S35887
ULCF30004GPRM, Fixed Temperature And Rate-Of-Rise
ULCF30002GNCRM, Heat Detector
ULCF30004GNCRM, UCHT-2W, UCHTI-2W Conventional Electronic Fixed S35887
ULCF30002GPNCRM, Temperature Heat Detector
ULCF30004GPNCRM,
ULR3000L2, ULR3000L4, ULCAP320 & UCAP320 Analog Photoelectric Smoke Detector S24205
ULR3000L2NC & CIR301 Remote Indicator S35888
ULR3000L4NC
ULCMIO353 230v Relay I/O Unit S24988
ULCIO351 3 Channel I/O Unit S24988
ULCSC354 4 Way Sounder Controller S24988
ULCF3000PR Loop Repeater S24988
ULCTPR3000 Network Repeater S24988
ULCSUM355 Shop Unit Monitor S24988
ULMCIM-C Single Input Module S24988
ULMCOM-S Single Output Module S24988
ULCSI350 Spur Isolator Unit S24988
ULCZMU352 Zone Monitor Unit S24988
ULMCIM Input Module S24988
ULMIU872 Mini Zone Monitor Module S24988
ULMCOM Output Module S24988
UMPS-1-0 & UMPS-200, For Addressable Pull Stations S25161
outdoor use when used with
Model SGB32C back box.

Name of panel Model number of device Description File number

ULCF30002G, ULFX340 Analog Photoelectric Smoke, S35885


ULCF30004G, Complimentary Fixed Temperature
ULCF30002GNC, Heat Detector
ULCF30004GNC,
ULCF30002GP, UCPT-2W Conventional Photoelectric Smoke, S35885
ULCF30004GP, Complementary Fixed Temperature
ULCF30002GPNC, Heat Detector
ULCF30004GPNC, ULFX330 Analog Fixed Temperature S35887
ULCF30002RM, Heat Detector

60 ULCF3000 INSTALLATION MANUAL PR209-171-505-13 February 2018 www.eaton.com


ULCF30004RM, UCHR-2W, UCHRI- 2W Conventional Combination Electronic S35887
ULCF30002NCRM, Fixed Temperature And Rate-Of-Rise
ULCF30004NCRM, Heat Detector
ULCF30002PRM,
ULCF30004PRM, UCHT-2W, UCHTI-2W Conventional Electronic Fixed S35887
ULCF30002PNCRM Temperature Heat Detector
ULCF30004PNCRM ULMAP320 Analog Photoelectric Smoke Detector S24205
ULCFR3000L2,
ULCFR3000L4, DIR301 Remote Indicator S35888
ULCFR3000L2NC, ULCMIO353 230v Relay I/O Unit S24988
ULCFR3000L4NC.
ULCIO351 3 Channel I/O Unit S24988
ULCSC354 4 Way Sounder Controller S24988
ULCF3000PR, ULCF3000PR Loop Repeater S24988
ULCTPR6000 Network Repeater S24988
ULCSUM355 Shop Unit Monitor S24988
ULMCIM-C Single Input Module S24988
ULMCOM-S Single Output Module S24988
ULCSI350 Spur Isolator Unit S24988
ULCZMU352 Zone Monitor Unit S24988
ULMCIM Input Module S24988
ULMIU872 Mini Zone Monitor Module S24988
ULMCOM Output Module S24988
UMPS-100 & UMPS-200, For Addressable Pull Stations S25161
outdoor use when used with
Model SGB32C back box.

Name of panel Model number of device Description File number

ULCF30002G, ULFX60004G, ULFX340 Analog Photoelectric Smoke, S35885


ULCF30002GNC, Complimentary Fixed Temperature
ULCF30004GNC, Heat Detector
ULCF30002GP,
ULCF30004GP, UCPT-2W Conventional Photoelectric Smoke, S35885
ULCF30002GPNC, Complementary Fixed Temperature
ULCF30004GPNC, Heat Detector
ULCF30002RM, ULCF330 Analog Fixed Temperature Heat S35887
ULCF30004RM, Detector
ULCF30002NCRM,
ULCF30004NCRM, UCHR-2W, UCHRI- 2W Conventional Combination Electronic S35887
ULCF30002PRM, Fixed Temperature And Rate-Of-Rise
ULCF30004PRM, Heat Detector
ULCF30002PNCRM, UCHT-2W, UCHTI-2W Conventional Electronic Fixed S35887
ULCF30004PNCRM, Temperature Heat Detector
ULCFR3000L2,
ULCFR3000L4, ULMAP320 Analog Photoelectric Smoke Detector S24205
ULCFR3000L2NC, DIR301 Remote Indicator S35888
ULCFR3000L4NC.
ULCMIO353 230v Relay I/O Unit S24988
ULCIO351 Channel I/O Unit S24988
ULCSC354 4 Way Sounder Controller S24988
ULCF3000PR, ULCF3000PR Loop Repeater S24988
ULCTPR6000 Network Repeater S24988
ULCSUM355 Shop Unit Monitor S24988
ULMCIM-C Single Input Module S24988
ULMCOM-S Single Output Module S24988
ULCSI350 Spur Isolator Unit S24988
ULCZMU352 Zone Monitor Unit S24988
ULMCIM Input Module S24988
ULMIU872 Mini Zone Monitor Module S24988
ULMCOM Output Module S24988
UMPS-100 & UMPS-200, For Addressable Pull Stations S25161
outdoor use when used with
Model SGB32C back box.

EaoNn
EMEA Headquarters
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu

© 2018 Eaton
All Rights Reserved Eaton is a registered trademark.
Publication No. PR209-171-505-13 /
25-14533-M All trademarks are property
CSSC-935 February 2018 of their respective owners.

You might also like