Capacitor Placement in Unbalanced Power Systems: January 2002
Capacitor Placement in Unbalanced Power Systems: January 2002
Capacitor Placement in Unbalanced Power Systems: January 2002
net/publication/228887896
CITATIONS READS
17 213
3 authors:
A. Abur
Northeastern University
276 PUBLICATIONS 8,885 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Energies' Special Issue: Distributed Energy Storage Devices in Smart Grids View project
All content following this page was uploaded by Guido Carpinelli on 29 May 2014.
Abstract – This paper presents a capacitor placement unwanted harmonics in the systems. Harmonics are
method for three phase unbalanced power systems. The known to cause overvoltages under certain network
method aims to minimize not only the power losses and configurations involving shunt capacitors. This issue is
capacitor costs, but also the distortions due to harmonics raised and a solution is proposed for minimizing har-
present in the power system. The proposed method is
capable of accomplishing this objective for both balanced
monic overvoltages in [6]. A practical method that
and unbalanced operating conditions. One of the objec- avoids convergence problems and incorporates discrete
tives of this paper is to demonstrate the significant differ- nature of capacitor banks along with the voltage distor-
ences in the results of capacitor placement studies when tions due to the installed capacitors, is developed and
unbalanced systems are approximated by their positive presented in [7]. This method is based on the balanced
sequence single phase equivalents. Furthermore, the ef- three phase operation and therefore analyzes the posi-
fects of taking harmonic distortions into account during tive sequence network only.
the capacitor placement procedure are also demonstrated.
Numerical examples on a distribution test power system In this paper, the work reported in [7] will be ex-
are provided to illustrate the method.
tended to the more general case of the three phase un-
Keywords: Optimization, capacitor placement, loss balanced operation. Several distribution feeders are
minimization, harmonic distortion, unbalanced opera- known to have line sections carrying a mixture of sin-
tion, distribution systems. gle, double or three phase loads. Such systems as well
as those having full three phase but unbalanced loads
can be studied using the presented method in this paper.
In addition to the cost of losses and capacitor installa-
tions, it is possible to associate a cost with the harmonic
distortions as discussed in [8-9]. Hence, the problem is
1 INTRODUCTION
formulated in such a way that both network losses and
Power distribution systems contain shunt capacitors harmonics are minimized along with the cost of capaci-
at various strategic locations in order to maintain a tors placed for this purpose.
desired voltage profile, correct power factor and reduce
power losses along feeders. When dealing with a large The paper is organized such that the problem de-
scale distribution system containing several feeders and scription is presented first. This is followed by the
their laterals, deciding on the best locations and sizes of sections describing the details of the three phase power
these capacitors becomes a complicated optimization flow and linear harmonic analysis modules, which make
problem. In addition to the scale of the problem, there up the main computational engines of the overall algo-
are other issues such as the discrete nature of capacitor rithm. Simulation results obtained using the developed
sizes, operational limits on voltages and feeder load- program and a test system will be presented next. Con-
ings, that need to be addressed. Effective solution algo- clusions and suggestions on future work will be pre-
rithms for balanced distribution feeders have been de- sented in the final section.
veloped [1,2]. These solutions mainly utilize the posi-
tive sequence network model and the associated power
2 DESCRIPTION OF THE PROBLEM
flows in formulating the problem. Hence, the results do
not directly apply for systems containing feeders with The objective of the presented method is to deter-
missing phases, unevenly loaded feeders or shunt ca- mine the best locations and sizes of shunt capacitors for
pacitors on single or double phase feeders. Three phase each phase, so that the total cost of the capacitors, of the
unbalanced distribution systems are later studied in total power losses of the network and the harmonic
[3,4] where simulated annealing and genetic algorithms distortion of the network are minimized. This objective
are respectively used to solve this more complicated should be met subject to the network three-phase power
problem. A simplified formulation and the MINOS flow equations as well as the limits on the bus voltage
optimization package are used to solve the same prob- and current magnitudes, harmonic indices (HI) and the
lem in [5]. Recently, distribution systems are populated total number of capacitor units to be installed. Hence, it
with nonlinear loads or control devices that generate
14th PSCC, Sevilla, 24-28 June 2002 Session 03, Paper 2, Page 2
can be formulated as the following optimization prob- rent injections. Details of this computation are dis-
lem: cussed in a later section.
heat pumps and non-specific sources such as PCs, TVs, function of capacitor bank additions. The objective
etc. The load data reported in [11] are reduced by 50%, functions are normalized to make the comparison easy.
since the voltage distortions are found to exceed the It should be noted that in the case without THD term the
IEEE-519 recommended limits [12] before the place- placement procedure is terminated at the fifth step due
ment of any capacitors. to a constraint violation. The violated constraint is the
Unit capacitors available at any bus are assumed to value of the fundamental voltage at bus #675, which
come in discrete sizes of 50 kVAR. The unit cost of exceeds the specified limit of 1.05 p.u., when an addi-
capacitors are reported in [13] while the unit cost of tional unit capacitor is attempted to be placed after the
energy are reported in [14]. fourth step.
The constraint limits are assumed as 105% for the Note that, in Fig.3, the solid lines represent the varia-
voltages at fundamental, 3% for the single voltage har- tion of the objective function J until the optimal solution
monics and 5% for the total harmonic distortion. is reached. The dashed lines indicate how J would have
Several cases are simulated. The following results varied, had the optimization procedure not been termi-
will be presented as representative cases. nated. In the top curve, the procedure terminates be-
cause the minimum is reached. In the bottom curve, it
4.1 Case 1 is terminated by the constraint violation after step 4 and
no other solution yielding a lower J within the con-
In this case the sensitivity of capacitor placement to straints can be found at the fifth step.
the objective function structure is investigated. The
objective function is first considered as the sum of the 4.2 Case 2
losses and the capacitor costs only. The harmonic costs
are then introduced into the objective function, to ob- In this case the sensitivity of the capacitor placement
serve the significance of this consideration in the out- procedure to the specified constraints is considered.
come of the optimization process. In order to simplify Initially, constraints identical to those used in Case 1,
the analysis, the harmonic index is assumed to be sim- are considered. These limits are subsequently relaxed
ply the total harmonic distortion and its associated cost (110% for the voltages at fundamental, 5% for the sin-
is evaluated so as to have the same cost of losses and gle voltage harmonics and 8% for the total harmonic
distortion), in order to observe their significance on the
650
Table 1:Capacitor Placement Results of Case 1
J [p.u.]
1.05
652 680
Figure 2: Network Diagram for the 13-bus test system
1
0.95
harmonics in the system without capacitors.
The locations and sizes of the capacitors that yield 0.9
the minimum objective function in both cases are listed
in Table 1. As evident from the table, two unit capaci- 0.85 + J includes THD term
tor banks are located at the most distant three phase load o J excludes THD term
bus (note that bus #680 is unloaded) and two other unit
0 1 2 3 4 5 6 7
banks are located at a single phase bus. On the other
hand, the capacitor banks at the single phase bus are no Number of capacitors bank
longer allocated when the objective function takes into
Figure 3: Variation of objective functions versus number of
account the THD cost.
capacitors bank
Fig. 3 shows the variation of the two objective func-
tions one with and one without the THD cost term, as
14th PSCC, Sevilla, 24-28 June 2002 Session 03, Paper 2, Page 5
Table 2: Capacitor Placement Results of Case 2
Bus code 675 611 645 646
Phase code 1 2 3 1 2 3 1 2 3 1 2 3
Without THD cost 2x50 2x50 2x50 2x50 1x50 1x50
(kVAr)
With THD cost 2x50 2x50 2x50
(kVAr)
Without THD cost 2x150 1x150 2x150 1x150 1x150 1x150 1x150
(kVAr)
With THD cost 2x150 1x150 2x150 1x150 1x150 1x150 1x150
(kVAr)
outcome of the optimization process. The locations A comparison of the results shown in Tables 1 and 3
and sizes of the capacitors that yield the minimum ob- implies that in the case of the balanced system a much
jective function in case of relaxed limits are listed in larger number of capacitors are required to achieve the
Table 2. minimum J. This is due to both the reduced level of
It follows from the analysis of the results in Tables 1 voltage harmonics and the larger amount of total reac-
and 2 without THD cost that the same capacitor banks tive load in the balanced system.
are located in the three phase bus #675; two more banks
are located at the single phase busses #645 and #646.
When the objective function takes into account the 5 CONCLUSIONS
THD cost, none of the capacitor banks in single phase
busses are allocated. This paper presents a capacitor placement procedure
for three phase unbalanced power systems. The pro-
4.3 Case 3 posed procedure not only accounts for system losses
and capacitor costs, but also for harmonic distortion of
In the absence of a three phase capacitor placement bus voltages and the effects of unbalanced operation.
program such as the one described here, an approximate The recent proliferation of nonlinear loads in distribu-
solution may be attempted by using a single phase pro- tion systems makes the issue of harmonic pollution an
gram that works for balanced systems. This means that important one to be considered in any of the distribution
all unbalanced loads and structurally non-symmetric automation functions such as capacitor sizing and loca-
lines will be replaced by balanced components and tion. This paper presents a simple yet effective solution
hence the solution will be different. This case investi- to the problem. Numerical examples demonstrating the
gates the errors involved in such an approximation. effectiveness of the procedure under both balanced and
The case compares the capacitor placement results of unbalanced operating conditions are provided.
Case 1 with that of a fully balanced version of the same Future work will involve more realistic representa-
system. Thus, the procedure of Section 3 is applied to a tion of the harmonic cost in the objective function.
balanced system which is created by approximating the
unbalanced system of Case 1 by a balanced version. REFERENCES
This is accomplished by balancing all the lines (all lines
are assumed three phase and structurally symmetric)
[1] M. Baran, F.F. Wu, “Optimal Capacitor Placement
and loads (all loads are assumed three phase balanced
on Radial Distribution systems”, IEEE Trans. on
loads) of the unbalanced system. Moreover, harmonics
Power Delivery, Vol.4, No.1, Jan. 1989, pp.725-
of order 5, 7, 11 and 13 only have been taken into ac-
734.
count with consequent reduction of harmonic distortion
levels. [2] J. J. Grainger, and S. H. Lee, “Optimum Size and
The locations and sizes of the capacitors (all 150 Location of Shunt Capacitors for Reduction of
kVAR three phase banks) that yield the minimum ob- Losses on Distribution Feeders”, IEEE Trans. on
jective function for this fully balanced case are listed in PAS, Vol.100, Mar.1981, pp.1105-1118.
Table 3. Results shown in the table indicate that in both [3] H-D. Chiang, J-C. Wang, J. Tong and G. Darling,
cases capacitor banks are located in the same three “Optimal Capacitor Placement, Replacement and
phase buses #675, #611, #692, #671, #652, #645, #646. Control in Large-Scale Unbalanced Distribution
14th PSCC, Sevilla, 24-28 June 2002 Session 03, Paper 2, Page 6
Systems: System Modeling and A New Formula- [10] IEEE Task Force on Harmonics Modeling and
tion”, IEEE Trans. on Power Systems, Vol.10, Simulation, “Modeling and Simulation of the
No.1, February 1995, pp.356-362. Propagation of Harmonics in Electric Power Net-
[4] C.S. Chen, C.T. Hsu and Y.H. Yan, “Optimal Dis- works – Part I: Concepts, Models and Simulation
tribution Feeder Capacitor Placement Considering Techniques”, IEEE Trans. on Power Delivery, Vol.
Mutual Coupling Effect of Conductors”, IEEE 11, No. 1, 1996, pp. 452-465
Trans. on Power Delivery, Vol.10, No.2, April [11] IEEE Task Force on Harmonics Modeling and
1995, pp.987-994. Simulation, “Modeling and Simulation of the
[5] K.N. Miu, H-D. Chiang and G. Darling, “Capacitor Propagation of Harmonics in Electric Power Net-
Placement, Replacement and Control in Large- works – Part II: Sample Systems and Examples”,
Scale Distribution Systems by a GA-Based Two- IEEE Trans. on Power Delivery, Vol. 11, No. 1,
Stage Algorithm”, IEEE Trans. on Power Systems, 1996, pp. 466-474
Vol.12, No.3, August 1997, pp.1160-1166. [12] IEEE Recommended Practices and Requirements
[6] Y. Baghzouz, S. Ertem, “Shunt Capacitor Sizing for Harmonic Control in Electrical Power Systems,
for Radial Distribution Feeders with Distorted Sub- IEEE Std 519-1992, IEEE, New York, NY, April
station Voltages”, IEEE Trans. on Power Delivery, 1993.
Vol.5, April 1990, pp.650-657. [13] A.E. Emanuel, C. Kawann, “Passive Shunt Har-
[7] Bei Gou and A. Abur, “Optimal Capacitor Place- monic Filters for Low and Medium Voltage: A Cost
ment for Improving Power Quality”, Paper SM 011. Comparison Study”, IEEE Trans. on Power Sys-
Proceedings of IEEE/PES Summer Meeting, July tems, Vol. 11, No. 4, 1996, pp. 1825-1831
18-22, 1999, Edmonton, Canada. [14] T.T. Chang, H. Chang, “Application of Differential
[8] P. Caramia, G. Carpinelli, E. Di Vito, A. Losi and Evolution to Passive Shunt Harmonic Filter Plan-
P. Verde, “Probabilistic Evaluation of the Eco- ning”, 8th IEEE ICHQP, Athens (Greece), 1998, pp.
nomical Damage due to the Harmonic Losses in In- 149-153
dustrial Energy Systems”, IEEE Trans. on Power
Delivery, Vol.11, No.2, 1996, pp.1021-1031.
[9] P. Caramia, G. Carpinelli, A. Russo, P. Varilone, P.
Verde: “An Integrated Probabilistic Harmonic In-
dex”, IEEE PES 2002 Winter Meeting, New York
(USA), 27-31 January 2002