Guide To Decoupling of Electrical Equipment On Cathodically Protected Structures
Guide To Decoupling of Electrical Equipment On Cathodically Protected Structures
Guide To Decoupling of Electrical Equipment On Cathodically Protected Structures
PROBLEM
Cathodic protection (CP) is most easily achieved when the protected structure is electrically isolated from other structures and
from grounding systems. This results in lower current requirements from CP sources, such as rectifiers or galvanic anodes,
and generally allows the user to achieve the required voltage criteria for protection against corrosion, per National Association
of Corrosion Engineers (NACE) guidelines. However, many cathodically protected structures, such as pipelines and tanks, are
inadvertently bonded to other structures and grounding systems, where CP personnel can easily detect that an electrical short
exists but can have great difficulty in remediating this connection. Figure 1 shows the typical scenario at a block valve site,
where CP is bonded to the grounding system. It is often possible for personnel to specifically identify the bond that shorts the
CP system, but they may be unsure of solutions, especially when the short is an electrical grounding conductor that relates to
codes and safety.
Even though grounding conductors are identified as the cause of the undesired CP short, these cannot be removed for
convenience. Electrical bonding and grounding conductors are needed to conduct AC fault current and prevent over-voltage
conditions, and must be left in place. National electrical codes require equipment grounding conductors to be 1) permanent
and continuous, 2) rated to handle the anticipated AC fault current from the source, and 3) of low impedance to allow AC fault
current to flow, permitting a clearing device (circuit breaker or fuse) to clear the fault. These define what is an “effective ground-
fault current path” for safety, per the electrical codes. To remove the offending conductor for convenience on the CP system is
to allow an unacceptable shock hazard at the site during any over-voltage condition.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Examples of required electrical grounding codes include the US National Electrical Code, NFPA 70, in section 250.4(A)(5),
and the Canadian Electrical code, CSA C22.1, Safety Standard for Electrical Installations, in section 10-500. Other national
authorities have similar requirements for safety, describing product requirements, installation materials, and practices.
SOLUTION
While equipment grounding conductors are required, there are solutions that address the conflict with CP. Decoupling devices,
or “decouplers,” are solid-state devices that block cathodic protection current but meet safety grounding codes, if the device is
independently certified for this use. Decouplers perform a valuable role in making the grounding conductor appear unchanged
from an AC current perspective, and allowing all safety functions of the electrical code to be employed, all while blocking CP
current. When installed in series in the equipment grounding conductor, CP compliance can be achieved, as well as preserving
the needed safety aspects. Figure 2 illustrates how the typical installation locates the decoupler between the electrical
equipment on the cathodically protected tank or pipeline and the electrical supply panel that feeds it.
Installation Allowed
Why is a decoupler allowed in an electrical installation, and how does it comply with the electrical codes? If a decoupler
has been independently tested and certified as meeting the requirements of an effective ground-fault current path, then
it has similar characteristics to the grounding conductor that it has been placed in, and will not compromise that path.
While a mechanical switch or a fusible device could never be placed in series in a grounding conductor and meet the code
requirements, a certified decoupler can comply. This is explicitly authorized, for example, in US National Electrical Code section
250.6(E) and in Canadian Electrical Code section 10-806(1). For this reason, Dairyland decouplers carry certification marks
on the nameplate, traceable to public certification documents showing compliance to the effective ground-fault current path
requirements. Decouplers by Dairyland also have additional certifications, such as allowance for use in hazardous locations,
which has relevance to this application, as discussed later in this document.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Grounding Conductors versus Neutrals
Certified Dairyland decouplers can be used in series in equipment grounding conductors, which should not be confused with
a neutral, which is a grounded conductor. The neutral is a load current-carrying conductor that is grounded at one point in the
facility, while a grounding conductor is a non-load current-carrying conductor that performs a safety bonding function. Dairyland
decouplers are certified for use in bonding and grounding conductors, not neutrals, and solving any CP short in a facility using
a decoupler can be accomplished in the bonding and grounding system, without need for placement in a neutral. Customer
confusion about neutrals usually comes the fact that the neutral that is bonded to the facility grounding system also has a
connection to the power utility grounding system at the transformer, and CP current can often be found flowing to the power
utility system via the neutral. However, the best solution for simple facilities involves decoupling CP shorts by placement of the
decoupler in grounding conductors closer to the point of the bond (near the pipeline or tank). Decoupling an entire facility with
CP from the power utility can also be accomplished, when dealing with more complex sites with multiple connections between
structures and ground, however that is addressed in other Dairyland documents.
Alternative Approaches
Decoupling grounding conductors that affect CP systems can be straightforward and inexpensive, accomplished by a facility
electrician. There are other approaches can accomplish the same end result, however these usually involve greater effort and
expense. Some have used electrically isolated joints on either side of a piece of electrical equipment that contains a grounding
conductor, to separate that section from the cathodically protected pipeline. If done during the original installation, this can
be done inexpensively, however a decoupler should still be used for over-voltage protection of the joint isolation system – an
application described in other Dairyland documents. For existing pipelines without such isolation joints, field installation of joints
is generally prohibitively expensive and requires a pipeline outage. Decoupling via the grounding conductor therefore becomes
much more attractive and requires no pipeline outage.
There are several typical types of facility construction that provide a continuous metallic path between a cathodically protected
structure and a grounding system. The following sections will deal with several common situations, and describe customer-
installed arrangements for mitigation of excessive CP current drain.
Warning: This application guide attempts to provide users with additional information for addressing CP problems in facilities via
decoupling, but does not cover all electrical requirements, hazards, practices, or other requirements applicable to the sites and
installations described herein. The user is responsible for the final application and suitability of the guidance in this document.
Note: Users may be familiar with Dairyland disconnect switches used in series with decouplers, typically associated with AC
mitigation applications, which can safely isolate the decoupler. Any such switch may not be used in series with a code-covered
grounding conductor, as this would be a violation of code, potentially leaving the grounding system in an “open” state. This loss
of the grounding system would result in an unsafe condition during AC fault, lightning, or other over-voltage conditions.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Outer Jacket
Inner Jacket
Phases &
Neutral Armor Filler Insulated
Conductors
Figure 3: Typical metallic conduit with grounding conductor Figure 4: Typical teck (armored) cable construction
Note that an additional facility feature also commonly bonds between the pipeline and grounding system – a signal cable
supporting a transmitter, with a metallic sheath and grounding conductor. If the sheath and ground are bonded at the transmitter
to the pipeline, this path has the same effect upon CP as does the motor ground and conduit. Likewise, measurement tubing and
other continuous metallic systems can bypass to the intended isolation. All of these issues are addressed later in this document.
A decoupler, connected in series with the grounding conductor, can block CP current while preserving the AC continuity of the
grounding system. This needs to be done at a location where the conduit can also be most easily altered to create an open
point. The decoupler will then be connected in series with the grounding conductor, and can also be connected across the open
point in the conduit, keeping the system AC continuous. The teck cable sheath is most typically altered at an end of the cable,
where it meets a panel or equipment.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Options for addressing conduit or teck sheaths with electrical isolation include:
– Installation of a non-conductive enclosure into the conduit (applies to conduit or teck cable)
– Applying an electrically isolated fitting where the conduit/sheath meets the supply panel or the pipeline equipment
(applies to conduit or teck cable)
– Replacing a section of the metal conduit with PVC (applies to conduit only)
Each of the above methods addresses the problem of continuous metallic conduit or sheath shorting out the CP system by
locating an electrical isolation system at a chosen point along the run. When using a non-conductive enclosure the decoupler
is located inside, while the use of an electrically isolated fitting or PVC section must still allow the internal grounding conductor
to exit at some point and connect through the decoupler. For this reason, the decoupler may be located separately from the
isolation point. Each of these cases are described in more detail below.
Each of the above points need to be considered during review of every proposed installation in order to avoid excessive effort
to test and electrically isolate the conduit or sheath, or to avoid a future bypass of the decoupler.
Access point: Best access to the conduit or sheath typically occurs at the beginning or end of the run on an above grade
exposure. Where this metallic system terminates at the panel or cathodically protected equipment, it is easy to install an
electrically isolated fitting or alter the system to include a non-metallic enclosure.
Length of run from CP system to the point of isolation: The conduit or sheath is still part of the CP system as it travels
back from the cathodically protected structure, up to the point of isolation. If that conduit or sheath segment contacts another
grounded object, any decoupling attempt will be already bypassed. Generally, minimizing the conduit length by moving the
point of decoupling toward the cathodically protected structure also limits the chance of a bypass. However, this also may
affect the hazardous location classification of the isolation point, which is addressed below.
Hazardous locations: The selected decoupler must be rated and certified as meeting the hazardous location criteria of the
intended point of isolation. For a Division 2 or Zone 2 site classification, the decoupler must be similarly rated and certified.
Likewise, a Division 1 or Zone 1 site requires a decoupler with this rating. An electrical supply panel resides in an ordinary, or
non-hazardous, area, while the conduit run may pass through Div 2/Zone 2 and/or a Div 1/Zone 1 areas, requiring an increasing
decoupler cost if located in a Div 1/Zone 1 area. Dairyland decouplers rated Div 2/Zone 2 also address ordinary locations.
Number of circuits to decouple: Multiple circuit grounding conductors can be decoupled with a single decoupler, if certain
conditions exist. First, consider if the grounding conductors come from CP systems that would be affected if solidly bonded
together at a decoupler. If CP would be affected, then one decoupler should be used for each circuit grounding conductor.
Additionally, consider if it is reasonable to wire one decoupler to multiple grounding conductors, or if this effort would require
excessive cable length and installation just to avoid the additional cost of a decoupler.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Dairyland offers nonconductive enclosures to house decouplers for this application, with backplates predrilled for various
Dairyland decoupler models. Additional unused backplate area allows for the installation of other customer equipment, such as
monitoring devices. See the Dairyland website for various ENCL accessory enclosures.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Non-metallic conduit and electrically isolated conduit fittings
Another approach for addressing continuous metallic conduit is to replace a segment at one end with a nonconducting conduit
material, such as PVC. Electrically isolated conduit fittings can also mate to a panel but provide a nonconducting mount. In either
of these cases, the equipment grounding conductor inside of the conduit must first enter an electrical panel, then exit appropriately
in order to connect to one decoupler terminal, and finally a new segment of insulated grounding conductor would be added from
the other decoupler terminal to the panel grounding bus (if at the panel end) or the equipment grounding point (if at the electrical
equipment on the cathodically protected structure). Alternatively, a sealed conduit T fitting can allow the grounding conductor to
exit the conduit, connect to the adjacent decoupler, and then continue down the conduit. See figures 8-11.
Signals
See Figures 12, 13
Power
See Figures 9-11
Grounding Bus in
Electrical Panel to
Decoupler Positive
Grounding Conductor
From Cathodically
Protected Equipment to
Decoupler Negative
Figure 9: PVC conduit as method of isolation
To Decoupler
To Decoupler
Isolated Conduit Fitting
Separating Metal Conduit Sealed Conduit Tee
from Panel
Figure 10: Alternative -Electrically isolated conduit fitting as method of isolation Figure 11: Alternative - Electrically isolated conduit tee as method of isolation
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Possible bypasses around the decoupler
Various metallic connections in a facility can bypass a decoupler that has been properly installed in an equipment grounding
conductor. Some of these include:
– Signal cable shields and grounding conductors
– Measurement tubing
– Shorted isolators in piping or tubing, or non-isolated piping in contact with grounded objects
– Equipment supports
– Other safety bonds or grounds, such as to nearby structures or grounding grids
Each of these will be addressed briefly, but clearly there are many different arrangements and conditions possible from one facility
to the next, and these points should cause the user to more fully examine and test for possible bypasses to the intended isolation.
Insulated Signal
Conductors
Grounding/Bonding
Conductor
Grounded Signal
Equipment
To Electrical Panel
Grounding Bus.
Open Point
in Shield
Grounding Conductor
Decoupler Enclosure
From Cathodically
Signal Cable Protected Equipment to
* Also Isolate Any Signal Ground From Field by
with Shield* Decoupler Negative
Connecting to Decoupler Negative Wire
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
Measurement tubing
Pipeline pressure measurement or equipment control tubing often bridges between cathodically protected and unprotected
structures, affecting CP levels. The solution for such tubing is to install an appropriate electrically isolated fitting or union into
the path to isolate CP, as in Fig 14. This may be required in multiple parallel tubing runs, as demonstrated in Fig 15. If all sets
of tubing come from the same CP structure, then one decoupler can connect across the isolated fittings, with jumpers across
common sides to connect all into the protection scheme. If any existing isolated fittings in tubing are not presently protected,
those isolation points should have overvoltage protection via a decoupler in order to prevent arcing and product ignition, as
these are often overlooked in overvoltage protection arrangements. Dairyland manufactures tubing clamp kits to allow for
attachment to the tubing on either side of the isolated fitting.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17
CP POTENTIAL READINGS AND CLEARING ELECTRICAL SHORTS
If cathodic protection readings are unacceptable following decoupling of grounding conductors, there may be various shorts
to ground still in existence. These can be challenging to trace, but typical culprits include failed shorted electrical isolation kits
(due to previous overvoltage events), piping that has never been isolated properly, pipe supports, and various wired bonds to
fences, grounding grids, or other equipment. In each of these cases, testing can typically show CP current flow or electrical
continuity, or visual examination may reveal non-isolated points. When the final shorted connection is cleared, CP potentials
should immediately improve.
Warning: Any action regarding the clearing of electrical shorts should also closely consider if those points can support voltage
during steady-state or abnormal conditions. Such points may require an overvoltage protection device, such as a decoupler,
in order to properly reference structures to ground for safety. If steady-state induced AC voltage is present on pipelines,
separating metallic connections may result in arcing, which should not be performed in a classified hazardous location.
Personnel protection from shock hazards should always be utilized when investigating and testing structures for continuity or
isolation. Decouplers provide both AC continuity and DC isolation as well as over-voltage protection, however disconnection
from the system may result in an arc and a sudden voltage increase on the structure, if such structure is exposed to induced
AC voltage. Users should carefully evaluate facility condition, electrical exposures, and other hazards, and involve appropriate
personnel during investigation and remediation.
SUMMARY
Electrical continuity between cathodically protected structures and other unrelated structures or grounding systems can affect
cathodic protection, but can usually be addressed by the proper application of isolation techniques and use of decouplers. If
questions remain after reviewing the above guidance, please contact Dairyland technical support staff for assistance.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Electrical Equipment Guide: 2019.04.17