GE Consumer & Industrial

Power Protection

Record Plus
Moulded Case Circuit Breakers
Selective & Current Limiting

GE imagination at work
Record Plus

The breaker

Order codes A

Trip units B

Components & Accessories C

Technical data D

Application guide E

Wiring diagrams F

Dimensions G

Numerical Index X
Record Plus

Circuit Breaker type FD160 FD63/160 FE160


Denomination N H C E S N H L N H L
EN 60947-2 standard
Poles Number of 1 3,4 2(1),3,4 3,4
Rated insulation voltage Ui (Volts) 750 500 750 750 750 750
Rated impulse withstand voltage Uimp [Kilovolt] 3 6 8 8 8 8
Technical data

Rated operational voltage Ue Volts AC 240 500 690 690 690 690
Volts DC 250 - - 500 500 500

Line protection device


Category of use A A A A
Suitable for use as a isolator Positive ON & OFF yes yes yes yes
Rated current Ith = Ie A at 40°C 63 or 160 63 or 160 63 or 160 160
Ultimate breaking capacity Icu [kA] 230/240V AC 25 50 25 40 50 85 100 200 85 100 200
400/415V AC - - 18 25 36 50 80 150 50 80 150
440V AC - - 12 14 25 30 65 130(4) 42 65 130
500V AC - - 10 12 18 22 36 50(4) 30 50 100
690V AC - - - 4.5 6 8 10 12 10 22 75
250V DC Single pole - 50 - - 25 40 65 100 50 85 100
500V DC Two pole - - - - 25 40 65(2) 100(2) 50 85(2) 100(2)
Service breaking capacity Ics (%Icu) ≤ 500V 100% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100%
690V AC - - - 75% 75% 50% 50% 35% 100% 75% 25%
Single phase breaking capacity IIT [kA] 230V AC 25 50 16 25 30 50 80 150 50 80 150
400/415V AC - - - 4.5 6 8 10 12 15 22 36
Endurance (CO operations) Mechanical 10000 10000 25000 40000
Electrical at In 5000 5000 10000 20000
Electrical at In/2 10000 10000 20000 30000
Endurance (On-Tripped operations) Mechanical 4000 4000 10000 16000
Trip Units Interchangeable no no no yes
Thermal magnetic line LTM LTM
Thermal magnetic generator GTM GTM
Thermal magnetic selective LTMD LTMD
TM
Magnetic only Mag Break Mag BreakTM
Electronic selective SMR1
Electronic enhanced
Circuit Breaker type and denomination FD160Y FD 63Y FD160Y FE160Y
EN 60947-3 standard
Non Automatic breaker (Switch)
Rated current In (class AC23) 220V AC to 690V AC 160 63 160 160
Rated making capacity Icm (kA peak) 2.8 1.7 2.8 4.9
Short-term withstand current Icw [kA] Icw eff. 1 second 2 1.2 2 3
Icw eff. 3 seconds 2 1.2 2 3
Circuit Breaker type FD63/160 FE160
Denomination N H L N H L
EN 60947-4 standard
Use in motor circuits
Rated current Ith A at 65°C FD50-50 FD160-100 150
Endurance (CO operations) Mechanical 25000 40000
Electrical at In class AC23 10000 20000
Operations per hour 120 120
Protection Short-circuit only (sep. overload device) Mag BreakTM Mag BreakTM
Overload class 10 and short-circuit SMR1
Max In (A) class 10 FD63-50 FD160-100 150
Max In (A) class 30 FD63-50 FD160-80 150
Earth fault unit (differential) Optional FDQ type Optional FEQ type
Circuit Breaker / Switch type FD63/160 all types FE160 all types
NEMA AB1 standard
3ph. interruption ratings [kA] 240V AC - - - - 50 65 100 - 100 150 200
480V AC - - - - 25 36 50 - 50 65 130
600V AC - - - - 6 8 10 - 25 36 42
Installation
Mounting On symmetrical DIN Rail yes yes yes no
Fixed yes yes yes yes
Plug in no yes yes yes
Draw out no no no yes
Connection Front yes yes yes yes
Rear no no yes yes
Dimensions [w x h x d] mm 3 pole, fixed front connection 27 x 130 x 85 81 x 130 x 85 81 x 130 x 85 105 x 170 x 95
4 pole, fixed front connection for single pole 108 x 130 x 85 108 x 130 x 85 140 x 170 x 95
Weights [kg] 3 pole, fixed front connection 0.4 0.9 0.9 1.5
4 pole, fixed front connection for single pole 1.3 1.3 2.0
(1) N type only. (3) Use 2 poles.
(2) Use 3 poles. (4) 160A rating only; derate to 65kA at 440V and 36kA at 500V.
22
Record Plus

FE250 FG400 FG630 FK800 FK1250 FK1600


V N H L N H L N H L N H L N H L N H

Performance figures
3,4 3,4 3,4 3,4 3,4 3,4
690 750 750 750 1000 1000 1000
8 8 8 8 8 8 8
500 690 690 690 690 690 690
440 500 - - 500 500 500

A B(5) B(5) B B B
yes yes yes yes yes yes
250 400 630 800 1250 1600
65 85 100 200 85 100 200 85 100 200 85 100 170 85 100 170 85 100
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
25 42 65 130 42 65 130 42 65 130 42 65 80 42 65 80 42 65
18 30 50 100 30 50 100 30 50 100 36 42 50 36 42 50 36 42
- 10 15 22 10 22 75(7) 10 22 40(7) 20 25 30 20 25 30 20 25
25 50 85 100 50(3) 60(3) 80(3) 50(3) 60(3) 80(3) - -
- 50 85(2) 100(2) 36(2) 50(2) 60(2) 36(2) 50(2) 60(2) - -
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 50% 100% 75% 50% 100% 75%
- 100% 75% 50% 100% 45% 25% 100% 45% 25% 100% 75% 50% 100% 75% 50% 100% 75%
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
- 10 15 22 10 (6) (6) 10 (6) (6) 20 25 30 20 25 30 20 25
10000 25000 20000 20000 10000 10000 10000
5000 10000 7500 5000 4000 3000 2000
10000 20000 15000 10000 8000 6000 4000
4000 10000 8000 8000 4000 3000 2000
no yes yes yes no no no
LTM LTM LTM
GTM
LTMD
Mag BreakTM Mag BreakTM
SMR1 SMR1 SMR1e
SMR2 SMR 1s & g
FE250Y FG400Y FG630Y FK800Y FK1250Y FK1600Y

250 400 630 800 1250 1600


6.4 8.5 11.3 14.1 21.2 28.3
4 5 6.5 10 15 20
4 5 6.5 10 15 20
FE250 FG400 FG630 FK800 FK1250 FK1600
N H L N H L N H L N H L N H L N H

225 350 500 720 1000


25000 20000 20000 10000 10000
10000 7500 5000 4000 3000
120 120 60 60 60
Mag BreakTM Mag BreakTM Mag BreakTM Mag BreakTM Mag BreakTM
SMR1 SMR1 or SMR2 SMR1 or SMR2
225 350 500 720 1000
225 350 500 720 1000
Optional FEQ type Optional FGQ type Optional FGQ type
FE250 all types FG400 all types FG630 all types FK800 all types FK1250 all types FK1600 all types

65 100 150 200 100 150 200 100 150 200 85 - - 85 - - 85 -


36 50 65 130 50 65 130 50 65 130 42 - - 42 - - 42 -
22 25 36 42 25 36 42 25 36 42 25 - - 25 - - 25 -

no no no no no no
yes yes yes yes yes yes
yes yes yes no no no
yes yes yes yes yes yes
yes yes yes yes yes yes
yes yes yes yes yes yes
105 x 170 x 95 140 x 265 x 115 140 x 265 x 115 210 x 320 x 160 210 x 320 x 160 210 x 320 x 160
140 x 170 x 95 185 x 265 x 115 185 x 265 x 115 280 x 320 x 160 280 x 320 x 160 280 x 320 x 160
1.6 4.5 4.5 12.2 18.0 18.0
2.1 6.0 6.0 15.1 23.4 23.4
(5) 350 and 500A executions only (7) On use of FG400 and FG630L type at 690V, one
(6) Please contact us. long and widened terminal shield is required.
33
Record Plus

Breaker type

Insulation
voltage
FE250 Product
description

Breaker frame
rating enclosed

Breaking
capacity Connection
(IEC values) torques
6 digit
reference plus
trip unit rating
Serial number 200A
Catalogue
Standards number

Certification
Record Plus

The Record PlusTM line of circuit breakers has been Meeting the international standards. The requirements
designed to comply with the following standards: are met of BS, VDE, UTE, KEMA, CEI. Record Plus breakers
EN 60947 Low-voltage switchgear and controlgear have been tested in acordance with the NEMA standards
EN 60947-1: General rules
EN 60947-2: Circuit-breakers For the Record Plus product certificates are
EN 60947-3: Switches, disconnectors, switch- available from the following regulatory bodies:
disconnectors and fuse-combination units Germanische Lloyds - RINA
EN 60947-4-1: Contactors and motor-starters Lloyds Register of Shipping - CCC (China)
Section One: Electromechanical contactors and Further tests are being undertaken to meet the
motorstarters requirements of the following regulatory bodies:
EN 60947-5-1: Control circuit devices and switching Bureau Veritas - Det Norske Veritas
elements
Section One: Electromechanical control circuit devices Please contact us to check the availability of individual
The compliance has been verified by two testing authorities: certificates.
LOVAG and KEMA (appropriate certificates are available
on request)

4
Record Plus

A new line of breakers


designed for global applications

Contents

A complete line of selective


& current limiting breakers

Protection with flexible &


interchangeable trip units

Common accessories
safe & easy to mount

Wide range of electrical &


mechanical operators

Versatile installation
options

A full solution for


low voltage distribution

55
Record Plus

The Record PlusTM family of circuit breakers has been developed as a line of aesthetically and
technically coordinated protection devices for low voltage distribution and control applications.
The circuit breakers are available in four sizes, each of which is tailored to the individual requirements
associated with its application.
The line offers a current range running from 3A to 1600A in single, 3 and 4 pole ratings. Numerous
versions as fixed, plug in and draw out are available and the line is completed with a full range of
accessories.

FD63/160 FE160 and FE250


Rated at 160A, the FD63/160 frame size is Rated at 160 and 250A, the FE frame sizes
designed for use in both a DIN-rail are designed for side-by-side mounting with
Record Plus

environment with modular equipment and in FD63/160 types in panels. FE sizes are
industrial applications. It is supplied with equipped with an easily accessible busbar
IPXXB terminals suitable for direct connection connection and can also be supplied with
of one or two conductors totalling up to 95 cable lugs for use with copper or aluminum
mm2 and is available as a thermal-magnetic conductors. The design allows the use of
breaker, a moulded case switch, and as a interchangeable thermal-magnetic,
magnetic-only motor circuit protector. magnetic-only, and electronic trip units.
The FD63/160 bridges the gap between
residential miniature circuit breakers and
industrial moulded case circuit breakers.

6
Record Plus

A complete line of
selective & current limiting breakers
FG400 and FG 630 FK 800, 1250 and 1600
Rated at 400 and 630A, the FG frame size Rated at 800,1250 and 1600A, the FK frame
includes all of the advanced features of the sizes are designed for use with the FG400
FD and FE frame sizes. and 630 frame sizes. The design uses
The FG connection area features easy-to- electronic trips units available in a number of
access busbar connections. Cable lugs for performance ranges and allowing a wide
use with single or multiple copper or variety of setting options and groundfault
aluminum conductors are optionally protection. If needed thermal-magnetic and
available. The breaker is designed for use magnetic only trip units are also available.
with interchangeable electronic units that The FK connection area features easy-to-
can be easily adapted to multiple levels of access busbar connections or cable lugs for
protection. use with single or multiple copper or
aluminum conductors.

77
Record Plus

Record PlusTM circuit breakers are designed to protect, isolate and switch circuits in low voltage
distribution networks. Circuit protection is provided by a combination of the devices unique current
limiting properties and integrated protection devices commonly referred to as trip units.

The trip units are designed to protect circuits and/or the equipment connected to these circuits and
exist as electromechanical or electronic devices. Numerous electromechanical types are available as
thermal magnetic devices with overload and short-circuit protection or magnetic-only types providing
short-circuit protection. Electronic devices offering wide setting ranges and a more sophisticated level of
protection are available in several versions. Each trip unit has a setting area finished with a sealable
transparant trip unit door.

Electromechanical devices Electronic devices SMR1


Record Plus

Devices available in a current range of 16 to The Record PlusTM FE, FG and FK sizes can be
1250A(1) as single, two, three or four pole equipped with rigorously designed and tested
devices. The electromechanical trip units exist interchangeable electronic trip units available
as thermal magnetic, magnetic-only and in three and four pole units in currents
generator protection models. The high- ranging from 25 to 1600A.
performance thermal magnetic trip units
exist as selective and non-selective versions The SMR1 and SMR2 types offer ajustable
and are equipped with a fault indicator that overload and selective short-circuit protection.
distinguishes between overload and short- The SMR1 range is designed for simplicity
circuit events in accordance with HD 384. and includes numerous exciting features
This patented safety feature allows users to such as an overload signalling option, a built-
reduce downtime by resetting the breaker in temperature sensor and rating plugs
directly after an overload event. suitable for both line and motor protection.

(1) For 400 and 630A types, please contact us.

8
Record Plus

Protection with
flexible & interchangeable
trip units
Personnel protection
A line of three and four pole add-on residual
current devices are available as side or
bottom mounted units with ratings up to
630A and sensitivities of 30mA to 10A.
The devices slide on to the breaker easily and
are fixed by simply tightening the main
electrical connections. Designed to meet the
latest standards, they each have a
mechanical and electrical test option and
share a common cut out.
A de-electric disconnect plug unit and setting
areas with transparent, tamper-free cover
are standard for the whole line.
For ratings above 630A, seperate sensors
and relays are available, or an integrated
ground fault protection can be used.

Electronic devices SMR2


The SMR2 has been designed to provide a
flexible solution for all protection scenarios.
The device is available in two versions, each
allowing the user to conveniently tailor his
protection to meet individual circuit
requirements.
The available options include adjustable
overload pickup values, overload trip time
characteristics, short time pickup circuit
values, short time delay circuit trip times and
energy values.
The trip unit can be equipped with a ground
fault protection and is also available with a
load shedding option.

9
Record Plus

Common accessories
safe & easy to mount

Safe and easy to mount


The internal accessories are designed for safe and
easy mounting. The breaker trips upon cover removal
and remains tripped until the cover is replaced. Cover
removal provides access to a specifically designed,
isolated compartment into which the accessories can
Record Plus

be mounted easily and safely in conveniently marked


areas.
The advanced design includes routing channels for
external wiring that allows access to internal
terminals, making it easier to connect accessories.
Particular attention has been paid to the design of
these terminals that allow the connection of wiring
from 0.5 to 2.5 mm2.

Common and adaptable


The same internal accessories are used in the
FD, FE and FG frame sizes. The mounting
system and wiring access methodology
remains the same: simple and effective.
The FK frame has equivalent accessories and
the same connection options.
For plug-in and draw-out breakers 6, 8 and
10 pole plug/socket combinations are
available. These are equipped with wiring that
can be led through specific openings in the
breaker rear.

10
Record Plus

Mounting Wiring
Internal accessories can be easily External wiring is routed through the
clicked into conveniently marked areas top or the side of the breaker lid
in the isolated compartment. through break out openings.
Clearly marked indication of the The wiring can then be connected to
accessory position and a mechanical the accessory terminals. These cage
interchange prevention system assure terminals allow for cross sections from
an error-proof and solid mounting of 0.75 to 2.5 mm2 and even allow the
the accessory. connection of two wires.
All contact points are coded in
accordance with the EN 60947
standard thus allowing for universal
wiring diagrams.

Auxiliary and Bell Alarm contacts


The internal accessories are common to Record PlusTM FD, FE and FG circuit
breakers. They offer a unique, patented, auxiliary contact block with normally
open and normally closed contacts which are suitable for use in high current
and high fidelity applications. A selective Bell Alarm contact featuring
complementary contacts is also available.

Releases
The shunt and undervoltage releases are a totally new design combining the
best in electromechanical and electronic engineering. Most releases are
common for AC and DC voltages and are available in a wide voltage range.
They combine low power consumption, a kiss-free, lock-out design and the
ease of use common to all Record PlusTM internal accessories.

11
Record Plus

Wide range of
electrical & mechanical operators
Record Plus

Easy-to-mount rotary handles


Fitted onto the breaker front the device allows the vertical handle
movement to be changed into a rotary operation with the OFF
position at 3 o’clock and the OFF position at 6 o’clock. An accurate
position indication of the three breaker positions ON-OFF and
TRIPPED is provided by a totally new internal design that also
allows the user to install one or two early closing and late opening
contact blocks which are the same as the standard internal
accessory types.
Can be turned 90°
to allow horizontal mounting
of breaker.

Easy to install
The handles are available as a breaker mounted device, a type
that can be mounted through a door or a panel and a version
where the operator is mounted on the door or panel front.
The door and/or panel mounted units are equipped with
(bypassable) interlocks to prevent the door from opening or the
panel being removed whilst the breaker is ON. The door/panel
mounted operators use a drilling common across the line.
Each breaker size and breaking capacity rating has its own
escutcheon and handle that can be equipped with padlocks
and/or a keylock.

12
Record Plus

Safe to operate
Locking/Interlocking devices
To allow users to safely work on the installations or installation segments
protected by the Record PlusTM moulded case circuit breakers it is
possible to padlock the devices in their OFF position. A padlocking facility
can be attached to the breaker front allowing the breaker to be equipped
with up to three padlocks of 5 to 8 mm.
A second type (depicted in the photo) is only firmly attached to the
breaker when it is padlocked and can be removed for use on another
breaker when not in use. Key locking devices allow the creation of
multiple key interlocking configurations. A walking beam system is
available for interlocking two or three breakers. The system can be
upgraded to a fully automatic power transfer system.

Easy to operate
Electrical operators
Front mounted devices that allow electrical
operation of the breaker on which the device
is mounted. Common to all electrical
operators is a closing speed lower than
80 milliseconds, the same three wire
electrical scheme and a clear and accurate
ON, OFF and TRIPPED indication in the
devices front face. Each device has two
operational positions electrical or manual
and can be padlocked or
key-locked in OFF position. Easy connection
is achieved by locating the terminals in the
immediate vicinity of those of the internal
accessories and by using terminals with a
connection capacity of
0.5 to 2.5 mm2.

13
Record Plus

Versatile installation options

Standard connection options


The breakers are equipped with front access terminals
designed to allow the user to quickly and easily connect
standard conductors. The FD63/160 frame has box clamps
suited for one or two cable cores or busbars while the FE, FG
and FK frame sizes are configured to allow for easy busbar
connection.
Record Plus

Configurable connection options


A wide range of alternatives are available in kit form with
rear and angular connectors, spreaders, customised ring ter-
minal connectors and extenders. Single and multiple box
clamps can be directly fitted to the breaker terminals or in
combination with extenders and spreaders. This flexibility
allows the user to adapt Record PlusTM circuit breakers to
almost all standard connection configurations while at the
same time allowing for the use of over-dimensioned and/or
multiple conductors.

Terminal shields
Each breaker can be fitted with tamper resistant, short or
long, terminal shields that allow a IP30 finishing of the
product. Backplates and phase separators complete this line
and consistently enable the user to connect the products in
a safe manner. Specific applications, extra accessories are
available for some breaker sizes like the FD160 with its IPXXB
terminal covers and the FG frame with its widened long
terminal shield.

14
Record Plus
Plug-in systems
Plug-in mounting systems are available for current ratings through
630A in both kit and assembled options. The plug-in system
consists of a single-piece moulded base in an IPXXB configuration.
The mounting system features a safety interlock which ensures
that the breaker is mechanically tripped before it is fully withdrawn
or re-inserted in the ON position.
An optional set of plug-in terminal block(s) are available
for use with internal accessory connections. Plug-in
mounting bases are normally supplied with exactly the
same front access terminal configuration as the standard
fixed breaker. This allows the use of the
same wide range of connection accessories that are
available in kit form on the fixed version. These includs
rear and angular connectors, spreaders, customised ring
terminal connectors and extenders. Internal accessories
can be easily clicked into conveniently marked areas in
the isolated compartment. Clearly marked indication of
the accessory position and a mechanical interchange
prevention system assures an error-proof and solid
mounting of the accessory.

Draw-out system
Simple, hand-operated draw-out mechanisms are available for
breakers up to 1600A. The draw-out system enables Record PlusTM
breakers to be configured as fully isolated devices with three
positions: Inserted, Test & Isolated, Remove
The system makes use of the plug-in base and offers all the
advantages of these IPXXB devices such as the safety
interlock system which makes sure that the breaker is
mechanically tripped before it is fully withdrawn or
re-inserted in the "on" position.
They also allow the use of the same optional set of plug-in terminal
block(s) for use with internal accessory connections and are
normally supplied with exactly the same front access terminal
configuration as the standard fixed breaker.
External wiring is routed through the top or the side of the breaker
lid through break out openings. All contact points are coded in
accordance with the EN 60947 standard thus allowing for universal
wiring diagrams.

Connectivity
The installation of a breaker is much easier and more cost effective
when the mounting and connecting of the breaker can be reduced
to a few simple, automateable tasks. Based on these principles
GE Power Controls have devised a unique system
that allows the user to mount and connect the
breaker before installation.
An adaptor plate, specifically designed for the
Record PlusTM breaker line and incorporating all the
connection hardware, is fitted to the breaker using
5 to 6 simple screws. Once mounted the adaptor is
then simply plugged onto a three or four pole busbar
system already installed in the equipment.

15
Record Plus
Using world class design and development
tools like Six Sigma, Computer Simulation
and Lean Manufacturing, Record PlusTM is
intended to meet and exceed the most
stringent quality and safety standards.
At GE we are proud to offer a product that
will offer years of reliable and dependable
protection.
GE Power Controls’ name is synonymous
with a broad range of products designed to
meet our customer’s changing and
competitive environment. Our drive to
exceed our customer’s expectations is the
Record Plus

foundation for continual renewal of our


commitment to provide innovative low
voltage solutions.
The new ElfaPlus, Record PlusTM, M-Pact and
Surion breaker and starter lines offer a full
line of hi-performance protection devices.
The four lines are designed to be
aesthetically and technically compatible and
suited for a wide range of applications.
They provide a fully co-ordinated approach
to circuit and device protection for domestic,
commercial or industrial usage.
GE Power Controls' new lines meet the latest
technical standards and regulations and
have been certified by authorities as Lovag,
the KEMA and Lloyd’s. The components in
these lines have been designed to be an
integral part of a solution. A complete low
voltage distribution and control range
including components, accessories and the
distribution and controls equipment they
go into.

16
Record Plus

Full solution for


low voltage distribution

Application Software
The new HD 384 and R064-03 stan-
dards require that the design of a low
voltage distribution system includes
the determination of all perspective
short-circuit and fault currents levels.
GE Power Controls have developed a
windows based software package to
do this: Procera Plus offers a multi
standard and multi lingual software
package to accompany our new
product line.

Implementation Software
Two ranges of software are designed
to allow a user to select the correct
protection devices, the associated
components needed to install it,
and a distribution system in which
they can be installed.
The software can be linked with
Procera and automatically produces
drawings and ordering details.

17
17
Record Plus
Record Plus

18
Record Plus

A.2 How to order a standard breaker

A.4 FD frame

A.5 Complete circuit breakers

A.8 Accessories

A.12 FE frame

A.13 Complete circuit breakers FE160 & FE250


The breaker
A.18 Breaker in components

A.20 Accessories
Order codes A

A.24 FG frame
Trip units B
A.25 Complete circuit breakers FG400 & FG630

A.29 Breaker in components


Components & Accessories C
A.31 Accessories

A.34 FK frame Technical data D


A.35 Complete circuit breakers FK800, FK1250 & FK1600

A.42 Connectivity, 60mm busbar system Application guide E


A.44 Changeover devices

A.45 Electrical and mechanical interlocks Wiring diagrams F


A.47 Changeover devices

A.48 Residual current devices with seperate sensor Dimensions G

Numerical Index X

A.1
Record Plus
How to order a standard breaker
To determine the basic breaker, the required current rating, the
short circuit breaking capacity and the number of switched and
protected poles must be defined. This information can be found on
page 2 and 3 of this catalogue and is repeated in short-form within
the ordering code part of each breaker size.

After selecting the basic device the circuit protection element or trip
unit needs to be defined. These are available in numerous types,
each of which is described briefly in the ordering code part of each
breaker size, whilst a full functional description can be found in the
relative section B of this catalogue.

With the above mentioned information the correct code for the
required moulded case circuit breaker can be found in the order
Order codes

code pages. Here the selected product is a version suited for fixed
mounting and front access connection.

Internal accessories
Common internal acessories are available from the FD63/160 frame
size till the FG400/630 frame size. Taking into account
the maximum breaker content the ordering procedure just requires
a correct code selection.
The FK800, 1250 and 1600 types have equivalent accesories.

Operators
The breakers are normally supplied with an elongated toggle
operator. Other operators, as rotary handles and electrical
A operators, can be ordered seperately.

Residual Current devices (RCD)


Available as add-on devices for side mounting (FD63/160) or
B mounting below the trip unit area of the breaker (FD63/160,
FE 160/250 and FG400/630). For breakers large than 630A seperate
RCD relays and sensors are available.
On the FK800, FK1250 and FK1600 an integrated ground
C fault device can be used.

Breakers in Plug-in or Draw-out version


D A breaker in fixed rating can easily be converted to a breaker in
plug-in or draw-out rating. The plug-in device is supplied in two
parts, one set for mounting on the breaker and one multipole base.
The draw-out unit is ordered as one complete conversion kit for the
E required breaker. On ordering plug-in or draw-out breakers with
accessories, please take into account that the auxiliary wiring also
needs to be executed as such (6, 8 or 10 pole socket system
F required).

Connection options
If the standard connection options do not meet the
G requirements a wide variety of others is available.
The connection options are supplied in kit form for mounting
on one side (load or line) of a breaker and can be used for the fixed,
plug-in or draw-out version of the breaker.
X
Installation accessories
Additional requirements, as to the protection degree of the
connection area, the locking or padlocking of the breaker and
finishing of cut-outs for operators can be met by the use of these
parts.

A.2
Record Plus

Order codes
A

A.3
Record Plus
FD frame

Breaking capacities

2, 3 and 4 pole types Single pole types

Icu 400/415V AC Icu 230/240V AC


in kA eff. in kA eff.
Type C E S N H L N H
FD63 18 25 36 50 80 150
FD160 18 25 36 50 80 150 25 50

Protection
Order codes

Trip Rated LTM LTMD GTM Mag Trip Rated LTM


Unit Current BreakTM Unit Current
(A) (A)

3 N,H
7 N,H
12.5 N,H
LTM 16 C,E S,N,H 16 N,H
Line thermal magnetic protection FD63 20 C,E S,N,H N,H,L 20 N,H
LTMD (2,3 & 25 C,E S,N,H,L N,H 25 N,H
4 pole) 30 N,H,L FD160
Selective thermal magnetic
32 C,E S,N,H,L N,H (single 32 N,H
protection 40 C,E S,N,H,L N,H pole) 40 N,H
GTM 50 C,E S,N,H,L N,H N,H,L 50 N,H
A Generator thermal magnetic 63 C,E S,N,H,L N,H 63 N,H
protection FD160 80 C,E S,N,H,L N,H N,H,L 80 N,H
Mag BreakTM (2,3 & 100 C,E S,N,H,L N,H N,H,L 100 N,H
4 pole) 125 C,E S,N,H,L N,H 125 N,H
B Magnetic Only protection
160 C,E S,N,H,L N,H 160 N,H
Y
Non Automatic or switch
Number of poles/ Number of poles/
(not mentioned in tables) protected poles protected
C (trips) poles (trips)

2 pole 2 trips N 1 pole 1 trip N,H


3 pole 3 trips C,E S,N,H,L N,H N,H,L
D 4 pole 3 trips N,H,L N,H N,H,L
4 pole 4 trips C,E S,N,H,L N,H

4 pole 3.5 trips N,H,L N,H


E (N=50%)(2)

Accessories
F O
1 Auxiliary contact left mounted
(NO or NC)
O
2 Auxiliary contact right mounted

G O
3
(NO or NC)
Bell Alarm trip unit (NO or NC)
O
4 Bell Alarm mechanism (CO)(1)
O
5 Shunt or Undervoltage release
X O
6 Operators
Rotary Handle
Electrical Operator
O
7 RCD, side or bottom mounted(1)
(Insert indicates Bell alarm contact
mounting)
O
8 Plug in system(1)

(1) Not applicable for some FDC and FDE types.


(2) Rated current ≥ 63A

A.4
Record Plus
FD63/160 - Complete circuit breaker
Line Thermal Magnetic LTM (fixed settings)
3 pole 3 trips 4 pole 4 trips(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no.


16 FDC35TE016ED 433907 FDC45TE016ED 433948
20 FDC35TE020ED 433911 FDC45TE020ED 433949
25 FDC35TE025ED 433914 FDC45TE025ED 433950
32 FDC35TE032ED 433918 FDC45TE032ED 433951
18 kA 40 FDC35TE040ED 436117 FDC45TE040ED 433952
FDC 50 FDC35TE050ED 436118 FDC45TE050ED 433953
63 FDC35TE063ED 436133 FDC45TE063ED 433954
80 FDC35TE080GD 436143 FDC45TE080GD 436145
100 FDC35TE100GD 436144 FDC45TE100GD 436146
125 FDC35TE125GD 433924 FDC45TE125GD 436147
160 FDC35TE160GD 433925 FDC45TE160GD 436148

One code covers: A standard, fixed front connection breaker with:


DIN-Rail mounting kit + Breaker finishing covers + Fixation hardware.

FD frame
16 FDE36TE016ED 433649 FDE46TE016ED 433697
20 FDE36TE020ED 433651 FDE46TE020ED 433699
25 FDE36TE025ED 433653 FDE46TE025ED 433701
32 FDE36TE032ED 433655 FDE46TE032ED 433703
40 FDE36TE040ED 433657 FDE46TE040ED 433705
25kA 50 FDE36TE050ED 433659 FDE46TE050ED 433707
FDE 63 FDE36TE063ED 433661 FDE46TE063ED 433709
80 FDE36TE080GD 433663 FDE46TE080GD 433711
100 FDE36TE100GD 433665 FDE46TE100GD 433713
125 FDE36TE125GD 433667 FDE46TE125GD 433715
160 FDE36TE160GD 433669 FDE46TE160GD 433717

One code covers: A standard, fixed front connection breaker with:


DIN-Rail mounting kit + Breaker finishing covers + Fixation hardware.

Selective Thermal Magnetic LTMD (settable thermals)


A
3 pole 3 trips 4 pole 4 trips(1)
16 FDS35TD016ED 430161 FDS45TD016ED 430224
20 FDS35TD020ED 430163 FDS45TD020ED 430226
25
32
FDS35TD025ED
FDS35TD032ED
430165
430167
FDS45TD025ED 430228
FDS45TD032ED 430230
B
36 kA 40 FDS35TD040ED 430169 FDS45TD040ED 430232
FDS 50 FDS35TD050ED 430178 FDS45TD050ED 430241
63 FDS35TD063ED 432952 FDS45TD063ED 432964
80
100
FDS35TD080GD
FDS35TD100GD
432955
432958
FDS45TD080GD 432967
FDS45TD100GD 432970
C
125 FDS35TD125GD 432961 FDS45TD125GD 432973
160 FDS35TD160GD 433602 FDS45TD160GD 433604

2 pole 2 trips
D
16 FDN66TD016ED 430143
20 FDN66TD020ED 430144
25 FDN66TD025ED 430145
32 FDN66TD032ED 430146 E
40 FDN66TD040ED 430147
50kA 50 FDN66TD050ED 430148
FDN 63 FDN66TD063ED 430149
80 FDN66TD080GD 430794
100 FDN66TD100GD 430797 F
125 FDN66TD125GD 430800
160 FDN66TD160GD 433599

One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware G
Line Thermal Magnetic LTM (fixed settings)
1 pole 1 trip(2) 1 pole 1 trip(2) X
16 FDN13TF016EF 433316 FDH13TF016EF 433246
20 FDN13TF020EF 433322 FDH13TF020EF 433255
240V 25 FDN13TF025EF 433328 240V FDH13TF025EF 433262
25kA 32 FDN13TF032EF 433334 50kA FDH13TF032EF 433268
FDN 40 FDN13TF040EF 433340 FDH FDH13TF040EF 433274
50 FDN13TF050EF 433346 FDH13TF050EF 433280
63 FDN13TF063EF 433352 FDH13TF063EF 433286
80 FDN13TF080GF 433519 FDH13TF080GF 433292
100 FDN13TF100GF 433522 FDH13TF100GF 433298
125 FDN13TF125GF 433525 FDH13TF125GF 433304
160 FDN13TF160GF 433527 FDH13TF160GF 433310

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Fixation hardware not suitable for mounting of one individual single pole breaker (see page A.10)

A.5
Record Plus
FD63/160 - Complete circuit breaker
Generator Thermal Magnetic GTM (settable thermals)
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
16 FDN36TD016ED 430100 FDN436TD016ED 430117 FDN46TD016ED 430131 - -
20 FDN36TD020ED 430101 FDN436TD020ED 430118 FDN46TD020ED 430132 - -
25 FDN36TD025ED 430102 FDN436TD025ED 430119 FDN46TD025ED 430133 - -
50kA 32 FDN36TD032ED 430103 FDN436TD032ED 430120 FDN46TD032ED 430134 - -
FDN 40 FDN36TD040ED 430104 FDN436TD040ED 430121 FDN46TD040ED 430135 - -
50 FDN36TD050ED 430105 FDN436TD050ED 430122 FDN46TD050ED 430136 - -
63 FDN36TD063ED 430106 FDN436TD063ED 430123 FDN46TD063ED 430137 FDN456TD063ED 430129
80 FDN36TD080GD 430630 FDN436TD080GD 430688 FDN46TD080GD 430752 FDN456TD080GD 430718
100 FDN36TD100GD 430633 FDN436TD100GD 430691 FDN46TD100GD 430755 FDN456TD100GD 430721
125 FDN36TD125GD 430636 FDN436TD125GD 430694 FDN46TD125GD 430758 FDN456TD125GD 430724
160 FDN36TD160GD 433572 FDN436TD160GD 433578 FDN46TD160GD 433590 FDN456TD160GD 433584

16 FDH36TD016ED 430020 FDH436TD016ED 430037 FDH46TD016ED 430051 - -


Order codes

20 FDH36TD020ED 430021 FDH436TD020ED 430038 FDH46TD020ED 430052 - -


25 FDH36TD025ED 430022 FDH436TD025ED 430039 FDH46TD025ED 430053 - -
32 FDH36TD032ED 430023 FDH436TD032ED 430040 FDH46TD032ED 430054 - -
80kA 40 FDH36TD040ED 430024 FDH436TD040ED 430041 FDH46TD040ED 430055 - -
FDH 50 FDH36TD050ED 430025 FDH436TD050ED 430042 FDH46TD050ED 430056 - -
63 FDH36TD063ED 430026 FDH436TD063ED 430043 FDH46TD063ED 430057 FDH456TD063ED 430049
80 FDH36TD080GD 430338 FDH436TD080GD 430396 FDH46TD080GD 430460 FDH456TD080GD 430426
100 FDH36TD100GD 430341 FDH436TD100GD 430399 FDH46TD100GD 430463 FDH456TD100GD 430429
125 FDH36TD125GD 430344 FDH436TD125GD 430402 FDH46TD125GD 430466 FDH456TD125GD 430432
160 FDH36TD160GD 435821 FDH436TD160GD 435827 FDH46TD160GD 435839 FDH456TD160GD 435833

25 FDL36TD025ED 430070 FDL436TD025ED 430082 FDL46TD025ED 430090 - -


32 FDL36TD032ED 430071 FDL436TD032ED 430083 FDL46TD032ED 430091 - -
40 FDL36TD040ED 430072 FDL436TD040ED 430084 FDL46TD040ED 430092 - -
50 FDL36TD050ED 430073 FDL436TD050ED 430085 FDL46TD050ED 430093 - -
150kA 63 FDL36TD063ED 430074 FDL436TD063ED 430086 FDL46TD063ED 430094 FDL456TD063ED 430087
FDL 80 FDL36TD080GD 430518 FDL436TD080GD 430557 FDL46TD080GD 430591 FDL456TD080GD 430568
A 100
125
FDL36TD100GD
FDL36TD125GD
430521
430524
FDL436TD100GD
FDL436TD125GD
430560
430563
FDL46TD100GD
FDL46TD125GD
430594
430597
FDL456TD100GD
FDL456TD125GD
430571
430574
160 FDL36TD160GD 435845 FDL436TD160GD 435848 FDL46TD160GD 435854 FDL456TD160GD 435851

One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
B Breaker finishing covers + Fixation hardware

Generator Thermal Magnetic GTM (settable thermals)

C 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
25 FDN36TG025ED 430107 FDN436TG025ED 430124 FDN46TG025ED 430138 - -
32 FDN36TG032ED 430108 FDN436TG032ED 430125 FDN46TG032ED 430139 - -
40 FDN36TG040ED 430109 FDN436TG040ED 430126 FDN46TG040ED 430140 - -
50 FDN36TG050ED 430110 FDN436TG050ED 430127 FDN46TG050ED 430141 - -
D 50 kA
FDN
63 FDN36TG063ED 430111 FDN436TG063ED 430128 FDN46TG063ED 430142 FDN456TG063ED 430130
80 FDN36TG080GD 430649 FDN436TG080GD 430707 FDN46TG080GD 430771 FDN456TG080GD 430729
100 FDN36TG100GD 430652 FDN436TG100GD 430710 FDN46TG100GD 430774 FDN456TG100GD 430732
125 FDN36TG125GD 430655 FDN436TG125GD 430713 FDN46TG125GD 430777 FDN456TG125GD 430735
160 FDN36TG160GD 433575 FDN436TG160GD 433581 FDN46TG160GD 433593 FDN456TG160GD 433587
E
25 FDH36TG025ED 430027 FDH436TG025ED 430044 FDH46TG025ED 430058 - -
32 FDH36TG032ED 430028 FDH436TG032ED 430045 FDH46TG032ED 430059 - -
40 FDH36TG040ED 430029 FDH436TG040ED 430046 FDH46TG040ED 430060 - -
F 50 FDH36TG050ED 430030 FDH436TG050ED 430047 FDH46TG050ED 430061 - -
63 FDH36TG063ED 430031 FDH436TG063ED 430048 FDH46TG063ED 430062 FDH456TG063ED 430050
80kA 80 FDH36TG080GD 430357 FDH436TG080GD 430415 FDH46TG080GD 430479 FDH456TG080GD 430437
FDH 100 FDH36TG100GD 430360 FDH436TG100GD 430418 FDH46TG100GD 430482 FDH456TG100GD 430440
125 FDH36TG125GD 430363 FDH436TG125GD 430421 FDH46TG125GD 430485 FDH456TG125GD 430443
G 160 FDH36TG160GD 435824 FDH436TG160GD 435830 FDH46TG160GD 435842 FDH456TG160GD 435836

One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware

X
(1) Neutral on the left. If neutral on the right is needed, please contact us.

A.6
Record Plus
FD63/160 - Complete circuit breaker
Motor Protection (Mag BreakTM) Magnetic Only Breakers
3 pole 4 pole(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
3 FDN36MC003ED 436409 FDN436MC003ED 436411
7 FDN36MC007ED 430095 FDN436MC007ED 430112
50kA 12.5 FDN36MC012ED 430096 FDN436MC012ED 430113
FDN 20 FDN36MC020ED 430097 FDN436MC020ED 430114
30 FDN36MC030ED 430098 FDN436MC030ED 430115
50 FDN36MC050ED 430099 FDN436MC050ED 430116
80 FDN36MC080GD 430610 FDN436MC080GD 430668
100 FDN36MC100GD 430613 FDN436MC100GD 430671

3 FDH36MC003ED 436396 FDH436MC003ED 436398


7 FDH36MC007ED 430015 FDH436MC007ED 430032
12.5 FDH36MC012ED 430016 FDH436MC012ED 430033
80kA 20 FDH36MC020ED 430017 FDH436MC020ED 430034

FD frame
FDH 30 FDH36MC030ED 430018 FDH436MC030ED 430035
50 FDH36MC050ED 430019 FDH436MC050ED 430036
80 FDH36MC080GD 430318 FDH436MC080GD 430376
100 FDH36MC100GD 430321 FDH436MC100GD 430379

20 FDL36MC020ED 430065 FDL436MC020ED 430077


30 FDL36MC030ED 430066 FDL436MC030ED 430078
150kA 50 FDL36MC050ED 430067 FDL436MC050ED 430079
FDL 80 FDL36MC080GD 430498 FDL436MC080GD 430537
100 FDL36MC100GD 430501 FDL436MC100GD 430540

One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware + IPXXB covers (Finger protection on connection clamps)
A
Complete Non-Automatic Circuit Breaker (Switch)
In (A) 3 pole 4 pole(1)
63 FDY306D063ED 430150 FDY406D063ED 430151
B
FDY 160 FDY306D160GD 430805 FDY406D160GD 430810

One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware C

(1) Neutral on the left. If neutral on the right is needed, please contact us.
D

A.7
Record Plus
FD - Internal accessories
Normally open Normally closed Changeover
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

Aux. switch right mounted FAS10R 430837 FAS01R 430831 - -


Aux. switch left mounted FAS10L 430834 FAS01L 430828 - -
Bell alarm trip unit FABAT10 430818 FABAT01 430815 - -
Bell alarm RCD device FABAT10 430818 FABAT01 430815 - -
Bell alarm mechanism(1) - - - - FDBAM11 430880

Shunt Undervoltage Delayed undervoltage


Releases
12V AC/DC FASHTB 430840 FAUVRB 440018
24V AC/DC FASHTD 430843 FAUVRD 430861 - -
48V AC/DC FASHTF 430846 FAUVRF 430864 - -
60V AC/DC FASHTH 435118 FAUVRH 435120 - -
110 AC/DC FASHTJ 430849 FAUVRJ 430867 - -
220/240V AC/DC FASHTN 430852 FAUVRN 430870 FAUVDN 430858
400/415V AC FASHTU 430855 FAUVR8 436472 - -
440/480V AC - - FAUVRU 430873 - -
Order codes

FD - Operators
Electrical operators 24V AC/DC FDEMFD 430926
48V AC/DC FDEMFF 430929
60V AC/DC FDEMFH 430932
110V AC/DC FDEMFJ 430935
220/250V AC/DC FDEMFN 430938
400/440V AC FDEMF8 430920

Keylock for operator Ronis(2) FD1BRE 430877


Keylock for operator Profalux(2) FD1BPE 430876

Rotary handle for use


Rotary handles Direct on device Panel or door mounted
through door or cover plate(3)
Grey FDNRF/5 436478 FDNRC/5 436474 - -
A Red
Grey + Early closing Aux. Switches 2xNO(4)
FDNRFV/5
-
436479
-
FDNRCV/5
FDNRY/5
436475
436487
-
-
-
-
Red + Early closing Aux. Switches 2xNO(4) - - FDNRYV/5 436488 - -

Grey - - - - FDNRD/5 436476


B Red
Grey + Early closing Aux. Switches 2xNO(4)
-
-
-
-
-
-
-
-
FDNRDV/5
FDNRZ/5
436477
436489
Red + Early closing Aux. Switches 2xNO(4) - - - - FDNRZV/5 436490
Accessories
C (a) Flex operator adaptor push to trip, set of 2 pcs. (a)
Extension shaft kit (max. 600 mm) (b)
FDNFT
FDNRE
430968
430986
Only for use with panel or door mounted type
Only for use with panel or door mounted type
Side-by-side installation adapter kit (c) FDNR4 430971 Not for use with panel or door mounted type

Ronis keylock 1104B nr. BC 1027(2) (d) FA1BR1 430088


D (c)
Ronis keylock 1104B nr. BC 1053(2)
(b) Ronis keylock 1104B nr. BC 2932(2)
(d)
(d)
FA1BR2
FA1BR3
430089
430504
Ronis keylock 1104B nr. BC 2911(2) (d) FA1BR4 430505
Ronis keylock 1104B nr. BC 2936(2) (d) FA1BR5 430506
(d)
Ronis keylock 1104B nr. BC 2940(2) (d) FA1BR6 430507
E Ronis lock with random key(2) (d) FA1BRH 430068
Profalux lock with random key(2) (e) FA1BPH 430813
(e)

F FD - Residual current devices


Standard 3 pole 4 pole
RCD side mounted(5)
Voltage 220/440V AC (a) FDQDS3M 431013 FDQDS4M 431022
Voltage 400/690V AC (a) FDQDS3H 433542 FDQDS4H 433548
G
(a) One code covers an RCD with: DIN-Rail mounting kit & multidirectional supply kit
Side connected only
Voltage 220/440V AC (b) FDQDI3M 433388 FDQDI4M 433397
X
One code covers an RCD with: DIN-Rail mounting kit and interconnection kit.
(b)

RCD bottom mounted(5) Voltage 220/440V AC FDQDB3M 433370 FDQDB4M 433379


(below trip unit area) Voltage 400/690V AC FDQDB3H 433364 FDQDB4H 433373
Normally open Normally closed
Bell Alarm RCD device FABAT10 430818 FABAT 01 430815

One code covers an RCD with: Sealable connection cover (cut-out adaptor FDUF)

(1) Not for all FDC and FDE types (4) On request 1xNO/1xNC is available.
(2) Key included (5) Not possible on FDC and FDE types with TF and TC trip unit.
(3) Add door flange FDFH to allow use of the door interlock options 100/200V AC rating available on request

A.8
Record Plus
FD - Plug-in system(1)
3 pole 4 pole
Main system
complete Cat. no. Ref. no. Cat. no. Ref. no.

Complete set for breaker FDDDF3 430893 FDDDF4 430896


Fixed part for breaker FDDFF3 430899 FDDFF4 430902
Mobile part for breaker FDDMP3 430905 FDDMP4 430908

Fixed part for breaker & RCD FDDFQ3 433489 FDDFQ4 433492
Mobile part for breaker & RCD FDDMP3 430905 FDDMP4 430908

Fixed Mobile Complete set: Fixed and mobile part with connection and fixation hardware
Fixed part: Fixed base with connection and fixation and hardware
Mobile part: Mechanism trip device, terminal shields and set of 3 or 4 pole plugs

Auxiliary disconnects Complete set 8 pole FAPFM 430824


secondary wiring(2) Fixed part 8 pole FAPF8 430823
Mobile part 8 pole FAPM8 430826

Plug and socket 10 pole FAPPS 430827

FD frame
Insertion prevention kit Insertion prevention kit
(of ….wrong A rating) FAPIP 430825

FD - Connections: Optional(4)
3 pole 4 pole
Extenders
Standard flat type (a) FDBES3 430887 FDBES4 430888
Heightened type (b) FDBEH3 430885 FDBEH4 430886
Twisted 90° (c) FDBEA3 430883 FDBEA4 430884
(a) (b) (c)

Spreader Pole spacing 35 mm FDBSS3 430891 FDBSS4 430892


A
flat

External Cable Cu/Al 95 mm2 (3) FDTCA1316 433400 FDTCA1416 433401


B
box clamps

Rear connections Set 3 pole (2 short, 1 long) FDBRC3 430889 - -


C
Set 4 pole (2 short, 2 long) - - FDBRC4 430890

Spares, set of 2 short types FDBRCS2 433358 - -


Spares, set of 2 long types FDBRCL2 433357 - - D

FD - Installation accessories
3 pole 4 pole E
Terminal shields
(with finishing covers) Long, set of 2 pcs. FDJL3 430951 FDJL4 430954

Short, set of 2 pcs. FDJS3 430960 FDJS4 430963


F

Specific to Phase separators, set of 12 pcs. FDJP 430957


connection area G
Backplate set of 2 pcs. (3 or 4 pole) FDJB 430945

Finger protection IPXXB (set of 12 pcs)(5) FDJK 430069

X
Covers Cutout adaptor, Breaker + Trip unit FDUF3 430830 FDUF4 430832

Cutout filler for cover plate (64 mm), FBF6 883970 - -


length of 1.2 m

(1) Plug-in system max. 125A. (4) Set for equipping the line OR load side of breaker.
(2) Only necessary when internal accessories or an electrical (5) Supplied with mag. break types.
operator are used.
(3) External box clamps are always delivered with standard extender

A.9
Record Plus
FD - Installation accessories (continued)
Padlocking devices for Cat. no. Ref. no. Cat. no. Ref. no.
toggle operator(1)
Padlocking removable FD1PR 430879

Padlocking fixed FD1PF 430878

Circuit indication/coding Set of 20 blank labels FAC 430821


Order codes

Heightning set for Length = (18 mod. of 18 mm) 354 mm FDKE 617947
Redline/ElfaPlus MCB's

Mounting kit for individual Set of 50 pcs. FDKM1 436720


single pole breaker

A Door Flanges
Breaker front face and RCD FDFF3
3 pole
430941 FDFF4
4 pole
430942
Rotary handle (through cover plate model) FDFH 430829 - -

Electrical operator FDFE 432010 - -


B
Spare parts DIN-rail adaptor kit(2) FDKD3 430966 FDKD4 430967

Finishing covers, set of 2 pcs.(2) FDUA3 431025 FDUA4 431026


C Spare toggle (set of 5 pieces) FDUT 433539 - -

D
(1) Padlocks not included
(2) Supplied with breakers, not with all FDC and FDE types
E

A.10
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FD frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.11
Record Plus
FE Frame

Breaking capacities
Icu 400/415V AC in kA eff.
Type V N H L
FE160 50 80 150
FE250 36 50 80 150

Protection

Trip Rated LTM LTMD GTM Mag SMR1


Unit Current (A) BreakTM
Order codes

3 N, H, L
7 N, H, L
12.5 N, H, L
20 N, H, L
25 N, H, L N, H, L
30 N, H, L
32 N, H, L
LTM
FE160 40 N, H, L
Line thermal magnetic protection 50 N, H, L N, H, L
LTMD 63 N, H, L N, H, L
Selective thermal magnetic 80 N, H, L N, H, L
protection 100 N, H, L N, H, L N, H, L N, H, L
GTM 125 N, H, L N, H, L N, H, L N, H, L N, H, L
A Generator thermal magnetic 160 N, H, L N, H, L N, H, L N, H, L N, H, L
125 N, H, L N, H, L
protection
FE250 160 V N, H, L N, H, L N, H, L N, H, L
Mag BreakTM 200 V N, H, L N, H, L N, H, L
B Magnetic Only protection 250 V N, H, L N, H, L N, H, L N, H, L
SMR1
Selective electronic trip unit
Number of poles/
Y protected poles
C Non Automatic or switch (trips)
(not mentioned in tables)
3 pole 3 trips V, N, H, L N, H, L N, H N, H, L N, H, L
4 pole 3 trips N, H, L N, H, L N, H N, H, L N, H, L
D 4 pole 4 trips V, N, H, L N, H, L N, H N, H, L
4 pole 3.5 trips N, H, L N, H, L N, H N, H, L
(N=50%)(1)
(1) Rated current ≥ 63A
E
Accessories (main types)
F O
1 Auxiliary contact left mounted
(NO or NC) 1 or 2pcs.
O
2 Auxiliary contact right mounted

G O
3
(NO or NC) 1 or 2pcs.
Bell Alarm thermal magnetic trip unit
(NO or NC)
O
3 a Bell Alarm electronic trip unit (NO or NC)
X O
4 Bell Alarm mechanism (NO or NC)
O
5 Shunt or Undervoltage release
O
5 a Actuator for electronic trip unit .
O
6 Operators
Rotary handle
Electrical operator
O
7 Bottom mounted RCD (below trip unit)
(Insert indicates Bell alarm contact mounting)
O
8 Plug-in or draw-out system

A.12
Record Plus
FE160 - Complete circuit breaker
Line Thermal Magnetic LTM (adjustable settings)
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

25 FEN36TA025JF 435103 FEN436TA025JF 435178 FEN46TA025JF 435214 - -


32 FEN36TA032JF 435106 FEN436TA032JF 435181 FEN46TA032JF 435217 - -
40 FEN36TA040JF 435109 FEN436TA040JF 435184 FEN46TA040JF 435220 - -
50 kA 50 FEN36TA050JF 435112 FEN436TA050JF 435187 FEN46TA050JF 435223 - -
FEN 63 FEN36TA063JF 435115 FEN436TA063JF 435190 FEN46TA063JF 435226 FEN456TA063JF 435202
80 FEN36TA080JF 431751 FEN436TA080JF 431838 FEN46TA080JF 431949 FEN456TA080JF 431886
100 FEN36TA100JF 431757 FEN436TA100JF 431844 FEN46TA100JF 431955 FEN456TA100JF 431892
125 FEN36TA125JF 431763 FEN436TA125JF 431850 FEN46TA125JF 431961 FEN456TA125JF 431898
160 FEN36TA160JF 431769 FEN436TA160JF 431856 FEN46TA160JF 431967 FEN456TA160JF 431904

25 FEH36TA025JF 434772 FEH436TA025JF 434847 FEH46TA025JF 434883 - -


32 FEH36TA032JF 434775 FEH436TA032JF 434850 FEH46TA032JF 434886 - -
40 FEH36TA040JF 434778 FEH436TA040JF 434853 FEH46TA040JF 434889 - -
80 kA 50 FEH36TA050JF 434781 FEH436TA050JF 434856 FEH46TA050JF 434892 - -
FEH 63 FEH36TA063JF 434784 FEH436TA063JF 434859 FEH46TA063JF 434895 FEH456TA063JF 434871
80 FEH36TA080JF 431165 FEH436TA080JF 431252 FEH46TA080JF 431363 FEH456TA080JF 431300

FE frame
100 FEH36TA100JF 431171 FEH436TA100JF 431258 FEH46TA100JF 431369 FEH456TA100JF 431306
125 FEH36TA125JF 431177 FEH436TA125JF 431264 FEH46TA125JF 431375 FEH456TA125JF 431312
160 FEH36TA160JF 431183 FEH436TA160JF 431270 FEH46TA160JF 431381 FEH456TA160JF 431318

25 FEL36TA025JF 434970 FEL436TA025JF 435013 FEL46TA025JF 435049 - -


32 FEL36TA032JF 434973 FEL436TA032JF 435016 FEL46TA032JF 435052 - -
40 FEL36TA040JF 434976 FEL436TA040JF 435019 FEL46TA040JF 435055 - -
50 FEL36TA050JF 434979 FEL436TA050JF 435022 FEL46TA050JF 435058 - -
150 kA 63 FEL36TA063JF 434982 FEL436TA063JF 435025 FEL46TA063JF 435061 FEL456TA063JF 435037
FEL 80 FEL36TA080JF 431458 FEL436TA080JF 431545 FEL46TA080JF 431656 FEL456TA080JF 431593
100 FEL36TA100JF 431464 FEL436TA100JF 431551 FEL46TA100JF 431662 FEL456TA100JF 431599
125 FEL36TA125JF 431470 FEL436TA125JF 431557 FEL46TA125JF 431668 FEL456TA125JF 431605
160 FEL36TA160JF 431476 FEL436TA160JF 431563 FEL46TA160JF 431674 FEL456TA160JF 431611

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware A
Selective Thermal Magnetic LTMD (adjustable settings)
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 100 FEN36TD100JF 432945 FEN436TD100JF 432994 FEN46TD100JF 433061 FEN456TD100JF 433028
B
FEN 125 FEN36TD125JF 432953 FEN436TD125JF 433001 FEN46TD125JF 433067 FEN456TD125JF 433034
160 FEN36TD160JF 432971 FEN436TD160JF 433007 FEN46TD160JF 433073 FEN456TD160JF 433040

80 kA 100 FEH36TD100JF 431007 FEH436TD100JF 432198 FEH46TD100JF 432287 FEH456TD100JF 432242


C
FEH 125 FEH36TD125JF 431021 FEH436TD125JF 432205 FEH46TD125JF 432296 FEH456TD125JF 432250
160 FEH36TD160JF 431965 FEH436TD160JF 432214 FEH46TD160JF 432303 FEH456TD160JF 432259

150 kA 100 FEL36TD100JF 432332 FEL436TD100JF 432374 FEL46TD100JF 432907 FEL456TD100JF 432699
D
FEL 125 FEL36TD125JF 432341 FEL436TD125JF 432573 FEL46TD125JF 432921 FEL456TD125JF 432747
160 FEL36TD160JF 432349 FEL436TD160JF 432585 FEL46TD160JF 432927 FEL456TD160JF 432834

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware E

F
Generator Thermal Magnetic GTM
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 100 FEN36TG100JF 435139 FEN436TG100JF 436014 FEN46TG100JF 435250 FEN456TG100JF 436020 G
FEN 125 FEN36TG125JF 435142 FEN436TG125JF 436015 FEN46TG125JF 435253 FEN456TG125JF 436021
160 FEN36TG160JF 435148 FEN436TG160JF 436016 FEN46TG160JF 435259 FEN456TG160JF 436022

80 kA 100 FEH36TG100JF 434808 FEH436TG100JF 435902 FEH46TG100JF 434919 FEH456TG100JF 436026 X


FEH 125 FEH36TG125JF 434811 FEH436TG125JF 435903 FEH46TG125JF 434922 FEH456TG125JF 436027
160 FEH36TG160JF 434817 FEH436TG160JF 435904 FEH46TG160JF 434928 FEH456TG160JF 436028

150 kA 100 FEL36TG100JF 435923 FEL436TG100JF 435944 FEL46TG100JF 435992 FEL456TG100JF 435962
FEL 125 FEL36TG125JF 435926 FEL436TG125JF 435947 FEL46TG125JF 435995 FEL456TG125JF 435965
160 FEL36TG160JF 435932 FEL436TG160JF 435950 FEL46TG160JF 436002 FEL456TG160JF 435968

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.

A.13
Record Plus
FE160 - Complete circuit breaker
Motor protection (Mag BreakTM) Magnetic Only Breaker(2)
3 pole 3 trips 4 pole 3 trips(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

3 FEN36MC003JF 436365 - -
7 FEN36MC007JF 435073 - -
50kA 12.5 FEN36MC012JF 435076 - -
FEN 20 FEN36MC020JF 435079 - -
30 FEN36MC030JF 435082 - -
50 FEN36MC050JF 435085 FEN436MC050JF 435160
80 FEN36MC080JF 435899 - -
100 FEN36MC100JF 435088 FEN436MC100JF 435163
125 FEN36MC125JF 436335 FEN436MC125JF 436356
160 FEN36MC160JF 435094 FEN436MC160JF 435169

3 FEH36MC003JF 436361 - -
7 FEH36MC007JF 434742 - -
Order codes

12.5 FEH36MC012JF 434745 - -


20 FEH36MC020JF 434748 - -
80kA 30 FEH36MC030JF 434751 - -
FEH 50 FEH36MC050JF 434754 FEH436MC050JF 434829
80 FEH36MC080JF 435893 - -
100 FEH36MC100JF 434757 FEH436MC100JF 434832
125 FEH36MC125JF 436327 FEH436MC125JF 436329
160 FEH36MC160JF 434763 FEH436MC160JF 434838

3 FEL36MC003JF 436363 - -
7 FEL36MC007JF 434940 - -
12.5 FEL36MC012JF 434943 - -
20 FEL36MC020JF 434946 - -
30 FEL36MC030JF 434949 - -
150kA 50 FEL36MC050JF 434952 FEL436MC050JF 434994
FEL 80 FEL36MC080JF 435896 - -
100 FEL36MC100JF 434955 FEL436MC100JF 434997
A 125
160
FEL36MC125JF
FEL36MC160JF
436331
434961
FEL436MC125JF
FEL436MC160JF
436333
435004

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

B Selective Electronic Trip Unit (SMR1) without Rating Plug


In (A) 3 pole 4 pole(1)
25 FEN36AA025JBF 435881 FEN46AA025JBF 435887
C 50 kA
FEN
63
125
FEN36AA063JEF
FEN36AA125JGF
435884
431698
FEN46AA063JEF
FEN46AA125JGF
435890
431787
160 FEN36AA160JJF 431703 FEN46AA160JJF 431790

D
25 FEH36AA025JBF 435857 FEH46AA025JBF 435863
63 FEH36AA063JEF 435860 FEH46AA063JEF 435866
80 kA 125 FEH36AA125JGF 431112 FEH46AA125JGF 431201
E FEH 160 FEH36AA160JJF 431117 FEH46AA160JJF 431204

F 25 FEL36AA025JBF 435869 FEL46AA025JBF 435875


63 FEL36AA063JEF 435872 FEL46AA063JEF 435878
125 FEL36AA125JGF 431405 FEL46AA125JGF 431494
150 kA 160 FEL36AA160JJF 431410 FEL46AA160JJF 431497
FEL
G One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

X Ir 0.625: 1xIn Adjustable Rating Plugs for Trip Units SMR1


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
25A 16 FERJ3B0016 432174 FERJ43B0016 432210 FERJ4B0016 432276 - -
25 FERJ3B0025 432177 FERJ43B0025 432213 FERJ4B0025 432279 - -

63A 40 FERJ3E0040 432180 FERJ43E0040 432216 FERJ4E0040 432282 - -


63 FERJ3E0063 432183 FERJ43E0063 432219 FERJ4E0063 432285 FERJ45E0063 432249

125A 80 FERJ3G0080 432186 FERJ43G0080 432222 FERJ4G0080 432288 FERJ45G0080 432252


125 FERJ3G0125 432192 FERJ43G0125 432228 FERJ4G0125 432294 FERJ45G0125 432258

160A 100 FERJ3J0100 432189 FERJ43J0100 432225 FERJ4J0100 432291 FERJ45J0100 432255
160 FERJ3J0160 432195 FERJ43J0160 432231 FERJ4J0160 432297 FERJ45J0160 432261

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) All 3 and 7Amp FE size magnetic only breaker types have a breaking capacity at 690 Volt of 10kA.
A.14
Record Plus
FE160 - Complete circuit breaker
Ir 0.4: 1xIn Switchable Rating Plugs for Trip Units SMR1
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

25A 25 FERS3B0025 432312 FERS43B0025 432330 FERS4B0025 432363 - -

63A 63 FERS3E0063 432315 FERS43E0063 432333 FERS4E0063 432366 FERS45E0063 432348

125A 125 FERS3G0125 432318 FERS43G0125 432336 FERS4G0125 432369 FERS45G0125 432351

160A 160 FERS3J0160 432321 FERS43J0160 432339 FERS4J0160 432372 FERS45J0160 432354

Selective Electronic Trip Unit (SMR1) with Switchable Rating Plug


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
125 FEN36SA125JGF 431724 FEN436SA125JGF 431811 FEN46SA125JGF 431922 FEN456SA125JGF 431871
160 FEN36SA160JJF 431727 FEN436SA160JJF 431814 FEN46SA160JJF 431925 FEN456SA160JJF 431874

50 kA
FEN

FE frame
125 FEH36SA125JGF 431138 FEH436SA125JGF 431225 FEH46SA125JGF 431336 FEH456SA125JGF 431285
160 FEH36SA160JJF 431141 FEH436SA160JJF 431228 FEH46SA160JJF 431339 FEH456SA160JJF 431288

80 kA
FEH

A
125 FEL36SA125JGF 431431 FEL436SA125JGF 431518 FEL46SA125JGF 431629 FEL456SA125JGF 431578
160 FEL36SA160JJF 431434 FEL436SA160JJF 431521 FEL46SA160JJF 431632 FEL456SA160JJF 431581

150 kA
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware B
FEL

Complete Non-Automatic Circuit Breaker (Switch) D


In (A) 3 pole 4 pole(1)
160 FEY306D160JF 431988 FEY406D160JF 431994

FEY One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware E

F
(1) Neutral on the left. If neutral on the right is needed, please contact us

A.15
Record Plus
FE250 - Complete circuit breaker
Line Thermal Magnetic LTM (adjustable settings)
3 pole 3 trips 4 pole 4 trips(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no.

125 FEV36TA125KF 432416 FEV46TA125KF 431082


36 kA 160 FEV36TA160KF 436798 FEV46TA160KF 436817
FEV 200 FEV36TA200KF 431058 FEV46TA200KF 431094
250 FEV36TA250KF 431061 FEV46TA250KF 431097

One code covers: A standard fixed front connection breaker + Fixation hardware

Selective Thermal Magnetic LTMD (adjustable settings)


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 125 FEN36TD125KF 432962 FEN436TD125KF 433004 FEN46TD125KF 433070 FEN456TD125KF 433037
FEN 160 FEN36TD160KF 432976 FEN436TD160KF 433010 FEN46TD160KF 433076 FEN456TD160KF 433043
200 FEN36TD200KF 432979 FEN436TD200KF 433013 FEN46TD200KF 433079 FEN456TD200KF 433046
Order codes

250 FEN36TD250KF 432982 FEN436TD250KF 433016 FEN46TD250KF 433082 FEN456TD250KF 433049

125 FEH36TD125KF 431393 FEH436TD125KF 432209 FEH46TD125KF 432300 FEH456TD125KF 432254


80 kA 160 FEH36TD160KF 431980 FEH436TD160KF 432218 FEH46TD160KF 432307 FEH456TD160KF 432263
FEH 200 FEH36TD200KF 432076 FEH436TD200KF 432223 FEH46TD200KF 432311 FEH456TD200KF 432266
250 FEH36TD250KF 432096 FEH436TD250KF 432227 FEH46TD250KF 432316 FEH456TD250KF 432269

125 FEL36TD125KF 432344 FEL436TD125KF 432576 FEL46TD125KF 432924 FEL456TD125KF 432780


160 FEL36TD160KF 432353 FEL436TD160KF 432588 FEL46TD160KF 432930 FEL456TD160KF 432843
150 kA 200 FEL36TD200KF 432357 FEL436TD200KF 432618 FEL46TD200KF 432933 FEL456TD200KF 432868
FEL 250 FEL36TD250KF 432361 FEL436TD250KF 432621 FEL46TD250KF 432936 FEL456TD250KF 432871

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

Generator Thermal Magnetic GTM


A In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50kA 160 FEN36TG160KF 435151 FEN436TG160KF 436017 FEN46TG160KF 435262 FEN456TG160KF 436023
FEN 200 FEN36TG200KF 435154 FEN436TG200KF 436018 FEN46TG200KF 435265 FEN456TG200KF 436024
250 FEN36TG250KF 435157 FEN436TG250KF 436019 FEN46TG250KF 435268 FEN456TG250KF 436025
B
160 FEH36TG160KF 434820 FEH436TG160KF 435905 FEH46TG160KF 434931 FEH456TG160KF 435908
80kA 200 FEH36TG200KF 434823 FEH436TG200KF 435906 FEH46TG200KF 434934 FEH456TG200KF 435909
C FEH 250 FEH36TG250KF 434826 FEH436TG250KF 435907 FEH46TG250KF 434937 FEH456TG250KF 435910

160 FEL36TG160KF 435935 FEL436TG160KF 435953 FEL46TG160KF 436005 FEL456TG160KF 435971


D 150kA
200
250
FEL36TG200KF
FEL36TG250KF
435938 FEL436TG200KF
435941 FEL436TG250KF
435956
435959
FEL46TG200KF
FEL46TG250KF
436008
436011
FEL456TG200KF 435974
FEL456TG250KF 435977
FEL
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

E
Motor protection (Mag BreakTM) Magnetic Only Breaker
In (A) 3 pole 3 trips 4 pole 3 trips(1)
F 50kA 160 FEN36MC160KF 435097 FEN436MC160KF 435172
FEN 200 FEN36MC200KF 436764 FEN436MC200KF 436765
250 FEN36MC250KF 435100 FEN436MC250KF 435175

G
160 FEH36MC160KF 434766 FEH436MC160KF 434841
80kA 200 FEH36MC200KF 436754 FEH436MC200KF 436755
FEH 250 FEH36MC250KF 434769 FEH436MC250KF 434844

X
160 FEL36MC160KF 434964 FEL436MC160KF 435007
200 FEL36MC200KF 436756 FEL436MC200KF 436763
150kA 250 FEL36MC250KF 434967 FEL436MC250KF 435010
FEL
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.

A.16
Record Plus
FE250 - Complete circuit breaker
Selective Electronic Trip Unit (SMR1) without Rating Plug
3 pole 4 pole(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50 kA
FEN 125 FEN36AA125KGF 431920 FEN46AA125KGF 431938
160 FEN36AA160KJF 431706 FEN46AA160KJF 431793
250 FEN36AA250KKF 431709 FEN46AA250KKF 431796

80 kA 125 FEH36AA125KGF 431116 FEH46AA125KGF 431824


FEH 160 FEH36AA160KJF 431120 FEH46AA160KJF 431207
250 FEH36AA250KKF 431123 FEH46AA250KKF 431210

125 FEL36AA125KGF 431836 FEL46AA125KGF 431890


150 kA 160 FEL36AA160KJF 431413 FEL46AA160KJF 431500
FEL 250 FEL36AA250KKF 431416 FEL46AA250KKF 431503

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

FE frame
Ir 0.625: 1xIn Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
125A 80 FERJ3G0080 432186 FERJ43G0080 432222 FERJ4G0080 432288 FERJ45G0080 432252
125 FERJ3G0125 432192 FERJ43G0125 432228 FERJ4G0125 432294 FERJ45G0125 432258

160A 100 FERJ3J0100 432189 FERJ43J0100 432225 FERJ4J0100 432291 FERJ45J0100 432255
160 FERJ3J0160 432195 FERJ43J0160 432231 FERJ4J0160 432297 FERJ45J0160 432261

250A 160 FERJ3K0160 432204 FERJ43K0160 432240 FERJ4K0160 432306 FERJ45K0160 432270
250 FERJ3K0250 432207 FERJ43K0250 432243 FERJ4K0250 432309 FERJ45K0250 432273

Ir 0.4: 1xIn Switchable Rating Plugs for Trip Units SMR1


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
125A 125 FERS3G0125 432318 FERS43G0125 432336 FERS4G0125 432369 FERS45G0125 432351
A
160A 160 FERS3J0160 432321 FERS43J0160 432339 FERS4J0160 432372 FERS45J0160 432354

250A 250 FERS3K0250 432327 FERS43K0250 432345 FERS4K0250 432378 FERS45K0250 432360 B
Selective Electronic Trip Unit (SMR1) with Switchable Rating Plug
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 160 FEN36SA160KJF 431730 FEN436SA160KJF 431817 FEN46SA160KJF 431928 FEN456SA160KJF 431877
C
FEN 250 FEN36SA250KKF 431733 FEN436SA250KKF 431820 FEN46SA250KKF 431931 FEN456SA250KKF 431880

D
160 FEH36SA160KJF 431144 FEH436SA160KJF 431231 FEH46SA160KJF 431342 FEH456SA160KJF 431291
250 FEH36SA250KKF 431147 FEH436SA250KKF 431234 FEH46SA250KKF 431345 FEH456SA250KKF 431294
80 kA
FEH E

160 FEL36SA160KJF 431437 FEL436SA160KJF 431524 FEL46SA160KJF 431635 FEL456SA160KJF 431584 F


250 FEL36SA250KKF 431440 FEL436SA250KKF 431527 FEL46SA250KKF 431638 FEL456SA250KKF 431587
150 kA
FEL One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

G
Complete Non-Automatic Circuit Breaker (Switch)
In (A) 3 pole 4 pole(1)
X
FEY 250 FEY306D250KF 431991 FEY406D250KF 431997

One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us

A.17
Record Plus
FE160 - Circuit breaker in components
Breaker frames: Without trip unit
3 pole 4 pole
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FEN
160 FEN306F160JF 431712 FEN406F160JF 431799

80kA
FEH 160 FEH306F160JF 431126 FEH406F160JF 431213

150kA 160 FEL306F160JF 431419 FEL406F160JF 431506


FEL
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

Trip units: Line Thermal Magnetic (adjustable settings)


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
Order codes

25 FETTA3J0025 432546 FETTA43J0025 432391 FETTA4J0025 432636 - -


32 FETTA3J0032 432549 FETTA43J0032 432394 FETTA4J0032 432639 - -
40 FETTA3J0040 432552 FETTA43J0040 432397 FETTA4J0040 432642 - -
LTM 50 FETTA3J0050 432555 FETTA43J0050 432400 FETTA4J0050 432645 - -
63 FETTA3J0063 432558 FETTA43J0063 432403 FETTA4J0063 432648 FETTA45J0063 432603
80 FETTA3J0080 432561 FETTA43J0080 432406 FETTA4J0080 432651 FETTA45J0080 432606
100 FETTA3J0100 432564 FETTA43J0100 432409 FETTA4J0100 432654 FETTA45J0100 432609
125 FETTA3J0125 432567 FETTA43J0125 432412 FETTA4J0125 432657 FETTA45J0125 432612
160 FETTA3J0160 432570 FETTA43J0160 432582 FETTA4J0160 432660 FETTA45J0160 432615

Trip units: Selective Thermal Magnetic (adjustable settings)


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
LTMD 100 FETTD3J0100 433159 FETTD43J0100 433201 FETTD4J0100 433269 FETTD45J0100 433231
125 FETTD3J0125 433164 FETTD43J0125 433204 FETTD4J0125 433272 FETTD45J0125 433234
160 FETTD3J0160 433168 FETTD43J0160 433207 FETTD4J0160 433275 FETTD45J0160 433239

A Trip units: Generator Thermal Magnetic


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
GTM 100 FETTG3J0100 433296 FETTG43J0100 433311 FETTG4J0100 433332 FETTG45J0100 433326
B 125
160
FETTG3J0125
FETTG3J0160
432693
432696
FETTG43J0125
FETTG43J0160
432717
432720
FETTG4J0125
FETTG4J0160
432774
432777
FETTG45J0125
FETTG45J0160
432741
432744

Trip units: Mag BreakTM, Magnetic only type for motor protection
C In (A) 3 pole 3 trips 4 pole 3 trips(1)
12.5 FETMC3J0012 432495 - -
20 FETMC3J0020 432498 - -
30 FETMC3J0030 434736 - -
D MC 50
80
FETMC3J0050
FETMC3J0080
432501
436078
FETMC43J0050
-
432528
-
100 FETMC3J0100 432504 FETMC43J0100 432531
125 FETMC3J0125 436358 FETMC43J0125 436359
160 FETMC3J0160 432510 FETMC43J0160 432537
E
Trip units: Selective Electronic type without Rating Plug
In (A) 3 pole 4 pole(1)
F 25 FETAA3J0025 432414 FETAA4J0025 432432
SMR1 63 FETAA3J0063 432417 FETAA4J0063 432435
125 FETAA3J0125 432420 FETAA4J0125 432438
160 FETAA3J0160 432423 FETAA4J0160 432441

G Trip units: Dummy for non Automatic Circuit Breaker (Switch)


In (A) 3 pole 4 pole(1)
Y 160 FETD30J0160 432480 FETD40J0160 432486
X
(1) Neutral on the left. If neutral on the right is needed, please contact us

A.18
Record Plus
FE250 - Circuit breaker in components
Breaker frames: Without trip unit
3 pole 4 pole
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FEN
250 FEN306F250KF 431715 FEN406F250KF 431802

80kA
FEH 250 FEH306F250KF 431129 FEH406F250KF 431216

150kA 250 FEL306F250KF 431422 FEL406F250KF 431509


FEL
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware

Trip units: Selective Thermal Magnetic (adjustable settings)


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
LTMD 125 FETTD3K0125 433182 FETTD43K0125 433216 FETTD4K0125 433284 FETTD45K0125 433252
160 FETTD3K0160 433186 FETTD43K0160 433219 FETTD4K0160 433287 FETTD45K0160 433257

FE frame
200 FETTD3K0200 433191 FETTD43K0200 433222 FETTD4K0200 433290 FETTD45K0200 433260
250 FETTD3K0250 433195 FETTD43K0250 433225 FETTD4K0250 433293 FETTD45K0250 433263

Trip units: Generator Thermal Magnetic


In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
GTM 160 FETTG3K0160 432705 FETTG43K0160 432729 FETTG4K0160 432786 FETTG45K0160 432753
200 FETTG3K0200 432708 FETTG43K0200 432732 FETTG4K0200 432789 FETTG45K0200 432756
250 FETTG3K0250 432711 FETTG43K0250 432735 FETTG4K0250 432792 FETTG45K0250 432759

Trip units: Mag BreakTM, Magnetic only type for motor protection
In (A) 3 pole 3 trips 4 pole 3 trips(1)
MC 160
200
FETMC3K0160
FETMC3K0200
432513
436778
FETMC43K0160
FETMC43K0200
432540
436779
A
250 FETMC3K0250 432516 FETMC43K0250 432543

Trip units: Selective Electronic type without Rating Plug B


In (A) 3 pole 4 pole(1)
SMR1 125 FETAA3K0125 432004 FETAA4K0125 432007
160 FETAA3K0160 432426 FETAA4K0160 432444
250 FETAA3K0250 432429 FETAA4K0250 432447 C
Trip units: Dummy for non Automatic Circuit Breaker (Switch)
In (A) 3 pole 4 pole(1)
Y 250 FETD30K0250 432483 FETD40K0250 432489
D

(1) Neutral on the left. If neutral on the right is needed, please contact us.
E

A.19
Record Plus
FE - Internal accessories
Normally open Normally closed
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

Aux. switch right mounted FAS10R 430837 FAS01R 430831


Aux. switch left mounted FAS10L 430834 FAS01L 430828
Bell alarm electronic trip unit FABAT10 430818 FABAT01 430815
Bell alarm thermal magnetic trip unit FEBAT10 430970 FEBAT01 430969
Bell alarm mechanism FABAM10 432003 FABAM01 432000
Bell alarm RCD device FABAT10 430818 FABAT01 430815

Shunt Undervoltage Delayed undervoltage


Releases
12V AC/DC FASHTB 430840 FAUVRB 440018 - -
24V AC/DC FASHTD 430843 FAUVRD 430861 - -
48V AC/DC FASHTF 430846 FAUVRF 430864 - -
60V AC/DC FASHTH 435118 FAUVRH 435120 - -
110 AC/DC FASHTJ 430849 FAUVRJ 430867 - -
220/240V AC/DC FASHTN 430852 FAUVRN 430870 FAUVDN 430858
400/415V AC FASHTU 430855 FAUVR8 436472 - -
Order codes

440/480V AC - - FAUVRU 430873 - -

FE - Operators
Electrical operators 24V AC/DC FEEMFD 432052
48V AC/DC FEEMFF 432055
60V AC/DC FEEMFH 432058
110/130V AC/DC FEEMFJ 432061
220/250V AC/DC FEEMFN 432064
400/440V AC FEEMF8 435812

Keylock for electr. operator Ronis(1) FE1BRE 432012


Keylock for electr. operator Profalux(1) FE1BPE 432011

Rotary handle through


Rotary handles Direct on device Panel or door mounted
door or cover plate(2)
A Grey FENRF/5 436495 FENRC/5 436491 - -
Red FENRFV/5 436496 FENRCV/5 436492 - -
Grey + Early closing Aux. Switches 2xNO(4) - - FENRY/5 436500 - -
Red + Early closing Aux. Switches 2xNO(4) - - FENRYV/5 436501 - -
B Grey - - - - FENRD/5 436493
Red - - - - FENRDV/5 436494
Grey + Early closing Aux. Switches 2xNO(4) - - - - FENRZ/5 436502
Red + Early closing Aux. Switches 2xNO(4) - - - - FENRZV/5 436503
C Accessories

Flex oper. adaptor push to trip, set of 2 pcs. (a) FENFT 433531 Only for use with panel or door mounted type

Extension shaft kit (max. 600 mm) (b) FDNRE 430986 Only for use with panel or door mounted type
D (a) (b)
Side-by-side installation adapter kit (c) FENR4 432099 Not for use with panel or door mounted type

Adaptor for drawout (d) FENRW 432120


(c) (d)
E Ronis keylock 1104B nr. BC 1027(1) (e) FA1BR1 430088
Ronis keylock 1104B nr. BC 1053(1) (e) FA1BR2 430089
Ronis keylock 1104B nr. BC 2932(1) (e) FA1BR3 430504
(e) Ronis keylock 1104B nr. BC 2911(1) (e) FA1BR4 430505
Ronis keylock 1104B nr. BC 2936(1) (e) FA1BR5 430506
F Ronis keylock 1104B nr. BC 2940(1) (e) FA1BR6 430507
Ronis lock with random key(1) (e) FA1BRH 430068
(f) Profalux lock with random key(1) (f) FA1BPH 430813

G FE - Residual current devices


3 pole 4 pole
RCD bottom mounted (4)
160A Voltage 220/440V AC FEQDB3MJ 432138 FEQDB4MJ 432150
X 160A Voltage 400/690V AC FEQDB3HJ 432132 FEQDB4HJ 432144

250A Voltage 220/440V AC FEQDB3MK 432141 FEQDB4MK 432153


250A Voltage 400/690V AC FEQDB3HK 432135 FEQDB4HK 432147

Normally open Normally closed

Bell Alarm RCD device FABAT10 430818 FABAT 01 430815

One code covers an RCD with: Fixation hardware + Sealable interconnection cover

(1) Key included


(2) Add door flange FDFH for door lock options
(3) On request 1xNO/1xNC is available.
(4) 100/200V AC execution available on request.

A.20
Record Plus
FE - Plug-in system
3 pole 4 pole
Main system
Cat. no. Ref. no. Cat. no. Ref. no.

Complete set for breaker FEDDF3 432034 FEDDF4 432037


Fixed part for breaker FEDFF3 432040 FEDFF4 432043
Mobile part for breaker FEDMP3 432046 FEDMP4 432049
Fixed part for breaker & RCD FEDFQ3 430987 FEDFQ4 431842
Mobile part for breaker & RCD FEDMP3 432046 FEDMP4 432049
Complete set: Fixed and mobile part with connection and fixation hardware
Fixed part: Fixed base with connection and fixation hardware
Mobile part: Mechanism trip device, terminal shields and set of plugs

Auxiliary disconnects Complete set 8pole FAPFM 430824


(Secondary wiring) Fixed part 8 pole FAPF8 430823
Mobile part 8 pole FAPM8 430826

Plug and socket 10 pole FAPPS 430827

Insertion prevention kit Insertion prevention kit FAPIP 430825

FE frame
(of ….wrong A rating)

Spares Set of nutplates and connection bolts FEJN3 436467 FEJN4 436468
(For connection of bases used as spare)

FE - Drawout system
Main system 3 pole 4 pole
Complete set FEWS3 432168 FEWS4 432171

One code covers the fixed and withdrawable part of the draw-out system, with plug-in base, mounting accessories and fixation hardware
A

B
Accessories (for auxiliary Keylock in draw-out position Ronis(1) (a) FE1BRW 432188
disconnects see plug-in system) Keylock in draw-out pos. Profalux(1) (b) FE1BPW 432184

Position indication contact NO FAS01D 436309


C
Position indication contact NC FAS10D 436310
(a) (b)

FE - Connections: Optional
D
3 pole 4 pole
Extenders(3)
Standard flat type (a) FEBES3 432026 FEBES4 432027
Heightened type (b) FEBEH3 432024 FEBEH4 432025 E
Twisted 90° (c) FEBEA3 432022 FEBEA4 432023
(a) (b) (c) (d) (e) Angled 45° (d) FEBE43 432018 FEBE44 432019
Angled 90° (e) FEBE93 432020 FEBE94 432021

F
Spreader flat(3) Pole spacing 45mm FEBSS3 432032 FEBSS4 432033

Rear connections Set 3 pole (2 short, 1 long) FEBRC3 432028 - -


(3) Set 4 pole (2 short, 2 long) - - FEBRC4 432029 G
Set 3 pole (3 short) FEBRCS3 432190 - -
Set 4 pole (4 short) - - FEBRCS4 432191

Internal box
2.5 - 95mm2 16 - 150mm2 X
clamps Box Clamp Cu/Al, set 3 pole FETCA1316 432156 FETCA1320 432157
(3) Box Clamp Cu/Al, set 4 pole FETCA1416 432158 FETCA1420 432159

70 - 185mm2
External
box clamps Box Clamp Cu/Al, set 3 pole(2) FETCA1323 432160
(3) Box Clamp Cu/Al, set 4 pole(2) FETCA1423 432161

6 copper cable cores


External 25mm2 or 35 mm2
connectors
(3) Set 3 pole FETCA630A 880954
Set 4 pole FETCA640A 880955

(1) Key included


(2) External box clamps are always delivered with standard extender
(3) Set for equipping the line OR load side of breaker. A.21
Record Plus
FE - Installation accessories
3 pole 4 pole
Terminal shields
(with finishing covers) Cat. no. Ref. no. Cat. no. Ref. no.

Long, set of 2 pcs. FEJL3 432079 FEJL4 432082

Short, set of 2 pcs. FEJS3 432088 FEJS4 432091

Specific to connection area Phase separators, set of 12 pcs FEJP 432085

Backplate set of 2 pcs (3 or 4 pole) FEJB 432073

Covers Cutout filler for cover plate (64 mm), FBF6 883970
length of 1.2 m
Order codes

Padlocking devices Padlocking removable (a) FD1PR 430879


for toggle operator(1)
Padlocking fixed (b) FE1PF 432017

(b)

(a)

Circuit indication/coding Set of 20 blank labels FAC 430821

A
3 pole 4 pole
Door flanges
B Breaker front face FEFF3 432067 FEFF4 432068

RCD unit front face for 3 and 4 pole FDFF3 430941


Front face toggle area FEFT 432071
Rotary handle (through cover plate model) FDFH 430829
C Motor operator FEFE 430943

3 pole 4 pole
D Spare parts
Finishing covers, set of 2 pcs.(2) FEUA3 432162 FEUA4 432163

Spare toggle (set of 5 pieces) FEUT 433540

F FE - Accessories electronic trip units


3 pole
(a)
Rating plug tool (a) FAR 433500

G Battery test device (b) FAT 431402

Longtime module (c) FAMLT1 433376


(b)

(c)

(1) Padlocks not included


(2) Supplied with breakers, not with FEV type.

A.22
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FE frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.23
Record Plus
FG Frame

Breaking capacities

Icu 400/415V AC in kA eff.


Type N H L
FG400 50 80 150
FG630 50 80 150

Protection

Trip Rated SMR1 SMR2 Mag


Unit Current (A) BreakTM
Order codes

A
250 N, H, L N, H, L N, H, L
FG400 350 N, H, L N, H, L N, H, L
400 N, H, L N, H, L -
400 N, H, L N, H, L -
FG630 500 N, H, L N, H, L N, H, L
630 N, H, L N, H, L -

LTM(1)
Line thermal magnetic protection
SMR1 Number of poles /
Selective electronic protection. protected poles (trips)
SMR2
3 pole 3 trips N, H, L N, H, L N, H, L
Modular electronic protection with
A enhanced functionality
4 pole 3 trips N, H, L N, H, L N, H, L
4 pole 4 trips N, H, L N, H, L
Mag BreakTM 4 pole 3.5 trips (N=50%) N, H, L N, H, L
Magnetic Only protection
B Y
Non Automatic or switch
(not mentioned in tables)

C
(1) Consult us for availability

E Accessories (main types)

F O
1 Auxiliary contact left mounted
(NO or NC) 1, 2 or 3pcs.
O
2 Auxiliary contact right mounted

G O
3
(NO or NC) 1 or 2pcs.
Bell Alarm thermal magnetic trip unit
(NO or NC)
O
3 a Bell Alarm electronic trip unit (NO or NC)
X O
4 Bell Alarm mechanism (NO or NC)
O
5 Shunt or Undervoltage release
O
5 a Actuator for electronic trip unit .
O
6 Operators
Rotary handle
Electrical operator
O
7 Bottom mounted RCD (below trip unit)
(Insert indicates Bell alarm contact mounting)
Bottom mounted version is also available. 6
O
8 Plug in or draw out system

A.24
Record Plus
FG400 - Complete circuit breaker
Selective Electronic Trip Unit (SMR1) without Rating Plug
3 pole 4 pole(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 250 FGN36AA250LKF 434248 FGN46AA250LKF 434253
400 FGN36AA400LLF 431455 FGN46AA400LLF 431536

250 FGH36AA250LKF 434232 FGH46AA250LKF 434237


400 FGH36AA400LLF 431032 FGH46AA400LLF 431106
80kA
FGH

250 FGL36AA250LKF 434240 FGL46AA250LKF 434245


400 FGL36AA400LLF 431246 FGL46AA400LLF 431330

FG frame
150kA
FGL
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRJ3LK0160 434337 FGRJ43LK0160 434345 FGRJ4LK0160 434361 FGRJ45LK0160 434353
250 FGRJ3LK0250 434341 FGRJ43LK0250 434349 FGRJ4LK0250 434365 FGRJ45LK0250 434357
400A 250 FGRJ3LL0250 435343 FGRJ43LL0250 435356 FGRJ4LL0250 435397 FGRJ45LL0250 435367
400 FGRJ3LL0400 433151 FGRJ43LL0400 433163 FGRJ4LL0400 433187 FGRJ45LL0400 433175

Type line/Motor
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
A
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 250 FGRS3LK0250 434303 FGRS43LK0250 434307 FGRS4LK0250 434315 FGRS45LK0250 434311
400A 400 FGRS3LL0400 435435 FGRS43LL0400 434516 FGRS4LL0400 434537 FGRS45LL0400 434525 B
Selective Electronic Trip Unit (SMR1) with switchable Rating Plug

50kA
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1) C
FGN 250 FGN36SA250LKF 434249 FGN436SA250LKF 434251 FGN46SA250LKF 434254 FGN456SA250LKF 434252
400 FGN36SA400LLF 434489 FGN436SA400LLF 435277 FGN46SA400LLF 435280 FGN456SA400LLF 434504

80kA 250 FGH36SA250LKF 434233 FGH436SA250LKF 434235 FGH46SA250LKF 434238 FGH456SA250LKF 434236
D
FGH 400 FGH36SA400LLF 434399 FGH436SA400LLF 434408 FGH46SA400LLF 434426 FGH456SA400LLF 434414

250 FGL36SA250LKF 434241 FGL436SA250LKF 434243 FGL46SA250LKF 434246 FGL456SA250LKF 434244 E


150kA 400 FGL36SA400LLF 434444 FGL436SA400LLF 434453 FGL46SA400LLF 434474 FGL456SA400LLF 434462
FGL
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator + Rating plug +
Breaker finishing covers + Fixation hardware
F
Selective Electronic Trip Unit (SMR1) with Rating Plug, without Overload (LT) protection
In (A) 3 pole 3 trips 4 pole 3 trips(1)
50kA
FGN 400 FGN36BM400LLF 434687 FGN436BM400LLF 434693 G
80kA
FGH 400 FGH36BM400LLF 434663 FGH436BM400LLF 434669

X
400 FGL36BM400LLF 434675 FGL436BM400LLF 434681
150kA
FGL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator + Rating plug +
Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for use with switchable rating plug only.

A.25
Record Plus
FG400 - Complete circuit breaker
Modular Electronic Trip Unit (SMR2) without Rating Plug
3 pole 4 pole(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 250 FGN36KA250LKF 434073 FGN46KA250LKF 436159
350(2) „ FGN36KA350LLF 434483 FGN46KA350LLF 434510
400 FGN36KA400LLF 436156 FGN46KA400LLF 436160

80kA 250 FGH36KA250LKF 436150 FGH46KA250LKF 434041


FGH 350(2) „ FGH36KA350LLF 434393 FGH46KA350LLF 434420
400 FGH36KA400LLF 436151 FGH46KA400LLF 434042

250 FGL36KA250LKF 434049 FGL46KA250LKF 436153


350(2) „
FGL36KA350LLF 434438 FGL46KA350LLF 434468
150kA 400 FGL36KA400LLF 434050 FGL46KA400LLF 436154
FGL
Order codes

One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Filller for extension module and battery socket + Breaker finishing covers + Fixation hardware

LT: Ir = 0.625-1 x In
LTD: Line & Motor; 8 options Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRL3LK0160 436162 FGRL43LK0160 434101 FGRL4LK0160 434109 FGRL45LK0160 434105
250 FGRL3LK0250 434098 FGRL43LK0250 436177 FGRL4LK0250 436181 FGRL45LK0250 434106
400A 250 FGRL3LL0250 435399 FGRL43LL0250 435410 FGRL4LL0250 435433 FGRL45LL0250 434495
400 FGRL3LL0400 434099 FGRL43LL0400 436178 FGRL4LL0400 434111 FGRL45LL0400 434107

350(2)
350(2) „ FGRL3LL0350 435400 FGRL43LL0350 435412 FGRL4LL0350 435302 FGRL45LL0350 435266

Modular Electronic Trip Unit (SMR2) with two adjustable Rating Plugs, setting 0.4 - 1 x In
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50kA
A FGN 400 FGN36VA400LLF 435140 FGN436VA400LLF 435152 FGN46VA400LLF 435170 FGN456VA400LLF 435164

80kA
FGH 400 FGH36VA400LLF 434953 FGH436VA400LLF 434960 FGH46VA400LLF 434983 FGH456VA400LLF 434971

B 400 FGL36VA400LLF 435065 FGL436VA400LLF 435077 FGL46VA400LLF 435128 FGL456VA400LLF 435095


150kA
FGL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator +Two rating plugs +
Filller for extension module and battery socket + Breaker finishing covers + Fixation hardware
C
Extension modules for the SMR2 Electronic trip unit Plug in types replacing the filler module (1 pc max.)

Ammeter with 4 digit LCD display FAMAM2 436183


D Groundfault alarm + Modbus communication (RTu)
Groundfault alarm + 2 channel load shedding device
FAMGAM2
FAMGAS2
436185
436186
Groundfault alarm + Fault type indicators FAMGAT2 436187
Groundfault protection + Modbus communication (RTu) FAMGFM2 436188
Groundfault protection + 2 channel load shedding device FAMGFS2 436189
E Groundfault protection + Fault type indicators FAMGFT2 436190
2 channel load shedding device + Modbus communication (RTu) FAMSM2 436192
2 channel load shedding device + Fault type indicators FAMST2 436197
Fault type indicators + Modbus communication (RTu) FAMMT2 436191
Spare filler module FAMB2 434448
F
One code covers: A plug in module and where needed connection hardware

Other Modules
G
External communication and contact module (4 contacts, 1A/400V)(3) FAMECM 434013

One code covers: Module and connection hardware

X Non-Automatic Circuit Breaker (Switch)


In (A) 3 pole 4 pole(1)

FGY 400 FGY306D400LF 431659 FGY406D400LF 431671

One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator +
Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for Motor Protection
(3) Is needed for Modbus communication (1 per breaker).

A.26
Record Plus
FG630 - Complete circuit breaker
Selective Electronic Trip Unit (SMR1) without Rating Plug
3 pole 4 pole(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 400 FGN36AA400NLF 434561 FGN46AA400NLF 434636
500(2) „ FGN36AA500NNF 434812 FGN46AA500NNF 434866
630 FGN36AA630NNF 431461 FGN46AA630NNF 431539

80kA 400 FGH36AA400NLF 433142 FGH46AA400NLF 434432


FGH 500(2) „ FGH36AA500NNF 434600 FGH46AA500NNF 434630
630 FGH36AA630NNF 431038 FGH46AA630NNF 431132

400 FGL36AA400NLF 434459 FGL46AA400NLF 434534


„
500(2) FGL36AA500NNF 434645 FGL46AA500NNF 434770
150kA 630 FGL36AA630NNF 431249 FGL46AA630NNF 431333
FGL
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

FG frame
Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRJ3NL0250 433148 FGRJ43NL0250 433160 FGRJ4NL0250 433184 FGRJ45NL0250 433172
400 FGRJ3NL0400 435182 FGRJ43NL0400 435188 FGRJ4NL0400 435200 FGRJ45NL0400 435194
630A 400 FGRJ3NN0400 433154 FGRJ43NN0400 433166 FGRJ4NN0400 433190 FGRJ45NN0400 433178
630 FGRJ3NN0630 433157 FGRJ43NN0630 433169 FGRJ4NN0630 433193 FGRJ45NN0630 433181

Type line/Motor
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 400 FGRS3NL0400 433235 FGRS43NL0400 433241 FGRS4NL0400 433253 FGRS45NL0400 433247
500(2)„ 500 FGRS3NN0500 434512 FGRS43NN0500 434521 FGRS4NN0500 434542 FGRS45NN0500 434530 A

Selective Electronic Trip Unit (SMR1) with switchable Rating Plug


B
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50kA
FGN 400 FGN36SA400NLF 431530 FGN436SA400NLF 431596 FGN46SA400NLF 431650 FGN456SA400NLF 431626
500 „ FGN36SA500NNF 434835 FGN436SA500NNF 434848 FGN46SA500NNF 434884 FGN456SA500NNF 434860 C
80kA 400 FGH36SA400NLF 431091 FGH436SA400NLF 431168 FGH46SA400NLF 431240 FGH456SA400NLF 431198
FGH 500 „ FGH36SA500NNF 434612 FGH436SA500NNF 434621 FGH46SA500NNF 434642 FGH456SA500NNF 434627
D
400 FGL36SA400NLF 431309 FGL436SA400NLF 431372 FGL46SA400NLF 431449 FGL456SA400NLF 431425
150kA 500 „ FGL36SA500NNF 434657 FGL436SA500NNF 434758 FGL46SA500NNF 434806 FGL456SA500NNF 434764
FGL
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator + E
Rating plug + Breaker finishing covers + Fixation hardware

Selective Electronic Trip Unit (SMR1) with Rating Plug, without Overload (LT) protection (Motor)
In (A) 3 pole 3 trips 4 pole 3 trips(1) F
50kA
FGN 500 FGN36BM500NNF 434690 FGN436BM500NNF 434696

80kA 500 FGH36BM500NNF 434666 FGH436BM500NNF 434672 G


FGH

500 FGL36BM500NNF 434678 FGL436BM500NNF 434684


150kA
FGL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator + X
Rating plug + Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for use with Switchable Rating Plug only.

A.27
Record Plus
FG630 - Complete circuit breaker
Modular Electronic Trip Unit (SMR2) without Rating Plug
3 pole 4 pole(1)

In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 400 FGN36KA400NLF 436157 FGN46KA400NLF 436161
500(2) „ FGN36KA500NNF 434824 FGN46KA500NNF 434872
630 FGN36KA630NNF 436158 FGN46KA630NNF 434092

80kA 400 FGH36KA400NLF 436152 FGH46KA400NLF 434043


FGH 500(2) „ FGH36KA500NNF 434606 FGH46KA500NNF 434633
630 FGH36KA630NNF 434028 FGH46KA630NNF 434044

400 FGL36KA400NLF 434051 FGL46KA400NLF 436155


„
500(2) FGL36KA500NNF 434651 FGL46KA500NNF 434782
150kA 630 FGL36KA630NNF 434052 FGL46KA630NNF 434068
FGL
Order codes

One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Filller for extension module and battery socket + Breaker finishing covers + Fixation hardware

LT: Ir = 0.625-1 x In
LTD: Line & Motor; 8 options Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRL3NL0250 435206 FGRL43NL0250 435218 FGRL4NL0250 435254 FGRL45NL0250 435230
400 FGRL3NL0400 435212 FGRL43NL0400 435224 FGRL4NL0400 435260 FGRL45NL0400 435236
630A 400 FGRL3NN0400 434471 FGRL43NN0400 435419 FGRL4NN0400 434501 FGRL45NN0400 434497
630 FGRL3NN0630 434100 FGRL43NN0630 436179 FGRL4NN0630 434112 FGRL45NN0630 436180

500(2)
500(2) „ FGRL3NN0500 434473 FGRL43NN0500 435427 FGRL4NN0500 435309 FGRL45NN0500 435272

Modular ElectronicTrip Unit (SMR2) with two Adjustable Rating Plugs, setting 0.4 - 1 x In
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50kA
A FGN 630 FGN36VA630NNF 435146 FGN436VA630NNF 435158 FGN46VA630NNF 435176 FGN456VA630NNF 435167

80kA
FGH 630 FGH36VA630NNF 434958 FGH436VA630NNF 434965 FGH46VA630NNF 435003 FGH456VA630NNF 434977

B 630 FGL36VA630NNF 435071 FGL436VA630NNF 435091 FGL46VA630NNF 435134 FGL456VA630NNF 435122


150kA
FGL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator + Two rating plugs +
Filller for extension module and battery socket + Breaker finishing covers + Fixation hardware
C
Extension modules for the SMR2 Electronic trip unit Plug in types replacing the filler module (1 pc max.)

Ammeter with 4 digit LCD display FAMAM2 436183


D Groundfault alarm + Modbus communication
Groundfault alarm + 2 channel load shedding device
FAMGAM2
FAMGAS2
436185
436186
Groundfault alarm + Fault type indicators FAMGAT2 436187
Groundfault protection + Modbus communication FAMGFM2 436188
Groundfault protection + 2 channel load shedding device FAMGFS2 436189
E Groundfault protection + Fault type indicators FAMGFT2 436190
2 channel load shedding device + Modbus communication FAMSM2 436192
2 channel load shedding device + Fault type indicators FAMST2 436197
Fault type indicators + Modbus communication FAMMT2 436191
Spare filler module FAMB2 434448
F
One code covers: A plug in module and where needed connection hardware

Other Modules
G
External communication and contact module (4 contacts, 1 A/400V)(3) FAMECM 434013

One code covers: Module and connection hardware

X Non-Automatic Circuit Breaker (Switch)


In (A) 3 pole 4 pole(1)
630 FGY306D630NF 431665 FGY406D630NF 431687
FGY
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator +
Breaker finishing covers + Fixation hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for Motor Protection.
(3) Is needed for Modbus communication (1 per breaker).

A.28
Record Plus
FG400 - Circuit breaker in components
Breaker frame without Trip Unit
3 pole 4 pole(1)
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FGN
250 FGN306F250LF 434247 FGN406F250LF 434250
400 FGN306F400LF 431473 FGN406F400LF 431548

80kA 250 FGH306F250LF 434231 FGH406F250LF 434234


FGH 400 FGH306F400LF 431050 FGH406F400LF 431150

250 FGL306F250LF 434239 FGL406F250LF 434242


150kA 400 FGL306F400LF 431261 FGL406F400LF 431351
FGL
One code covers: A standard fixed front connection breaker with current sensors + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Selective Electronic Trip Unit (SMR1) without Rating Plug

FG frame
3 pole 4 pole(1) Long time protection Adj. Ir= 0.4 - 1 x In
Two long time delay bands Line, no phase loss protection
250 FGTAA3L0250 434319 FGTAA4L0250 434323 (with choice of protection mode) Motor with phase loss protection
SMR1 400 FGTAA3L0400 431718 FGTAA4L0400 431742 Short time protection Adj. 2 - 13 x Ir (current dependant
delay) (2)
Instantaneous protection Fixed 14 x Is (2)

Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRJ3LK0160 434337 FGRJ43LK0160 434345 FGRJ4LK0160 434361 FGRJ45LK0160 434353
250 FGRJ3LK0250 434341 FGRJ43LK0250 434349 FGRJ4LK0250 434365 FGRJ45LK0250 434357
400A 250 FGRJ3LL0250 435343 FGRJ43LL0250 435356 FGRJ4LL0250 435397 FGRJ45LL0250 435367
400 FGRJ3LL0400 433151 FGRJ43LL0400 433163 FGRJ4LL0400 433187 FGRJ45LL0400 433175

Type line/Motor
A
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A
400
250
350
FGRS3LK0250
FGRS3LL0400
434303
435435
FGRS43LK0250
FGRS43LL0400
434307
434516
FGRS4LK0250
FGRS4LL0400
434315
434537
FGRS45LK0250
FGRS45LL0400
434311
434525
B

Modular Electronic Trip Unit (SMR2) without Rating Plug


C
In (A) 3 pole 4 pole(1) 4 for line, no phase loss protection Adj. Ir= 0.4 - 1 x In
Six long time delay bands 4 for line, no phase loss protection
SMR2 250 FGTKA3L0250 434201 FGTKA4L0250 434205
350(3)„
400(2)
FGTKA3L0350
FGTKA3L0400
434902
434202
FGTKA4L0350
FGTKA4L0400
434908
434261 Short time protection
2 for motor, with phase loss
protection(2) D
Adj. 1.5-12 x Ir(2)
Switchable to I2 t curve
Five short time delay bands From 40 to 410 milliseconds
Adj. 2-13 x Is(2)

LT: Ir = 0.625-1 x In
Instantaneous protection
E
LTD: Line & Motor; 8 options Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRL3LK0160 436162 FGRL43LK0160 434101 FGRL4LK0160 434109 FGRL45LK0160 434105 F
250 FGRL3LK0250 434098 FGRL43LK0250 436177 FGRL4LK0250 436181 FGRL45LK0250 434106
400A 250 FGRL3LL0250 435399 FGRL43LL0250 435410 FGRL4LL0250 435433 FGRL45LL0250 434495
400 FGRL3LL0400 434099 FGRL43LL0400 436178 FGRL4LL0400 434111 FGRL45LL0400 434107

350A(3)„ 350 FGRL3LL0350 435400 FGRL43LL0350 435412 FGRL4LL0350 435302 FGRL45LL0350 435266 G
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) 400A trip unit limited to 5 LTD band settings(SMR2), a maximum ST setting of 10 x Ir and a maximum instantaneous setting of 11 x Is.
(3) Specifically configured for Motor Protection X

A.29
Record Plus
FG630 - Circuit breaker in components
Breaker frame without Trip Unit
3 pole 4 pole(1)
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FGN
400 FGN306F400NF 431488 FGN406F400NF 431554
630 FGN306F630NF 431491 FGN406F630NF 431560

80kA 400 FGH306F400NF 431067 FGH406F400NF 431153


FGH 630 FGH306F630NF 431073 FGH406F630NF 431156

400 FGL306F400NF 431267 FGL406F400NF 431354


630 FGL306F630NF 431282 FGL406F630NF 431357
150kA
FGL One code covers: A standard fixed front connection breaker with current sensors + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Selective Electronic Trip Unit (SMR1) without Rating Plug


Order codes

Long time protection Adj. Ir= 0.4 - 1 x In


3 pole 4 pole(1)
Two long time delay bands Line, no phase loss protection
400 FGTAA3N0400 431721 FGTAA4N0400 431745 (with choice of protection mode) Motor with phase loss protection
SMR1 500(3) „ FGTAA3N0500 434893 FGTAA4N0500 434899 Short time protection Adj. 2 - 13 x Ir (current dependant
630 FGTAA3N0630 431736 FGTAA4N0630 431748 delay) (2)
Instantaneous protection Fixed 14 x Is (2)

Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRJ3NL0250 433148 FGRJ43NL0250 433160 FGRJ4NL0250 433184 FGRJ45NL0250 433172
400 FGRJ3NL0400 435182 FGRJ43NL0400 435188 FGRJ4NL0400 435200 FGRJ45NL0400 435194
630A 400 FGRJ3NN0400 433154 FGRJ43NN0400 433166 FGRJ4NN0400 433190 FGRJ45NN0400 433178
630 FGRJ3NN0630 433157 FGRJ43NN0630 433169 FGRJ4NN0630 433193 FGRJ45NN0630 433181

Type line/Motor
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
A In (A) 3 pole 3 trips 4 pole(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 400 FGRS3NL0400 433235 FGRS43NL0400 433241 FGRS4NL0400 433253 FGRS45NL0400 433247
500(3) „ 500 FGRS3NN0500 434512 FGRS43NN0500 434521 FGRS4NN0500 434542 FGRS45NN0500 434530

B
Modular Electronic Trip Unit (SMR2) without Rating Plug
3 pole 4 pole 3 trips(1) 4 for line, no phase loss protection Adj. Ir= 0.4 - 1 x In
Six long time delay bands 4 for line, no phase loss protection
C 400 FGTKA3N0400 434203 FGTKA4N0400 434263 2 for motor, with phase loss
protection(2)
SMR2 500(3) „ FGTKA3N0500 434905 FGTKA4N0500 434911 Short time protection Adj. 1.5-12 x Ir(2)
630(2) FGTKA3N0630 434204 FGTKA4N0630 434265 Switchable to I2 t curve
Five short time delay bands From 40 to 410 milliseconds
Instantaneous protection Adj. 2-13 x Is(2)
D LT: Ir = 0.625-1 x In
Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
LTD: Line & Motor; 8 options
In (A) 3 pole 3 trips 4 pole 4 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRL3NL0250 435206 FGRL43NL0250 435218 FGRL4NL0250 435254 FGRL45NL0250 435230
E 400 FGRL3NL0400 435212 FGRL43NL0400 435224 FGRL4NL0400 435260 FGRL45NL0400 435236
630A 400 FGRL3NN0400 434471 FGRL43NN0400 435419 FGRL4NN0400 434501 FGRL45NN0400 434497
630 FGRL3NN0630 434100 FGRL43NN0630 436179 FGRL4NN0630 434112 FGRL45NN0630 436180

F 500(3) „ 500 FGRL3NN0500 434473 FGRL43NN0500 435427 FGRL4NN0500 435309 FGRL45NN0500 435272

Extension modules for the SMR2 Electronic trip unit


G Plug in types replacing the filler module (1 pc max.)

Ammeter with 4 digit LCD display FAMAM2 436183


Groundfault alarm + Modbus communication FAMGAM2 436185
Groundfault alarm + 2 channel load shedding device FAMGAS2 436186
X Groundfault alarm + Fault type indicators FAMGAT2 436187
SMR2 Groundfault protection + Modbus communication FAMGFM2 436188
Groundfault protection + 2 channel load shedding device FAMGFS2 436189
Groundfault protection + Fault type indicators FAMGFT2 436190
2 channel load shedding device + Modbus communication FAMSM2 436192
2 channel load shedding device + Fault type indicators FAMST2 436197
Fault type indicators + Modbus communication FAMMT2 436191
Spare filler module FAMB2 434448
One code covers: A plug in module and where needed connection hardware

Other Modules

SMR2 External communication and contact module (4 contacts, 1A/400V)(4) FAMECM 434013
One code covers: Module and connection hardware

(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) 630A trip unit limited to 5 LTD band settings(SMR2), a maximum ST setting of 10 x Ir and a maximum instantaneous setting of 11 x Is.
A.30 (3)
(4)
Specifically configured for Motor Protection
Is needed for Modbus communication (1 per breaker).
Record Plus
FG - Internal accessories
Normally open Normally closed
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

Aux. switch right mounted FAS10R 430837 FAS01R 430831


Aux. switch left mounted FAS10L 430834 FAS01L 430828
Bell alarm electronic trip unit FABAT10 430818 FABAT01 430815
Bell alarm mechanism FABAM10 432003 FABAM01 432000
Bell alarm RCD device FABAT10 430818 FABAT01 430815

Shunt Undervoltage Delayed undervoltage


Releases
12V AC/DC FASHTB 430840 FAUVRB 440018 - -
24V AC/DC FASHTD 430843 FAUVRD 430861 - -
48V AC/DC FASHTF 430846 FAUVRF 430864 - -
60V AC/DC FASHTH 435118 FAUVRH 435120 - -
110 AC/DC FASHTJ 430849 FAUVRJ 430867 - -
220/240V AC/DC FASHTN 430852 FAUVRN 430870 FAUVDN 430858
400/415V AC FASHTU 430855 FAUVR8 436472 - -
440/480V AC - - FAUVRU 430873 - -

FG frame
FG - Operators
Electrical operators 24V AC/DC FGEMFD 432817
48V AC/DC FGEMFF 432820
60V AC/DC FGEMFH 432823
110/127V AC/DC FGEMFJ 432826
220/250V AC/DC FGEMFN 432829
400/440V AC FGEMF8 432811

Keylock for electr. operator Ronis(1) (a) FG1BRE 431404


Keylock for electr. operator Profalux(1) (b) FG1BPE 431403
(a) (b)
Rotary handle through
Rotary handles Direct on device Panel or door mounted
door or cover plate(2)
Grey
Red
FGNRF/5
FGNRFV/5
436509
436510
FGNRC/5
FGNRCV/5
436504
436505
-
-
-
-
A
Grey + Early closing Aux. Switches 2xNO(4) - - FGNRY/5 436513 - -
Red + Early closing Aux. Switches 2xNO(4) - - FGNRYV/5 436514 - -

Grey
Red
-
-
-
-
-
-
-
-
FGNRD/5
FGNRDV/5
436506
436507
B
Grey + Early closing Aux. Switches 2xNO(4) - - - - FGNRZ/5 436515
Red + Early closing Aux. Switches 2xNO(4) - - - - FGNRZV/5 436516

Accessories C
Flex operator adaptor push to trip (a) FGNFT 432867 Only for use with panel or door mounted type
(a) (b)
Extension shaft kit (max. 600 mm) (b) FGNRE 434735 Only for use with panel or door mounted type

Adaptor for drawout (c) FGNRW 433892


D
(c)
Ronis keylock 1104B nr. BC 1027(1) (d) FA1BR1 430088
Ronis keylock 1104B nr. BC 1053(1) (d) FA1BR2 430089
Ronis keylock 1104B nr. BC 2932(1) (d) FA1BR3 430504 E
(d) Ronis keylock 1104B nr. BC 2911(1) (d) FA1BR4 430505
Ronis keylock 1104B nr. BC 2936(1) (d) FA1BR5 430506
Ronis keylock 1104B nr. BC 2940(1) (d) FA1BR6 430507
Ronis lock with random key(1) (d) FA1BRH 430068
(e) Profalux lock with random key(1) (e) FA1BPH 430813 F

FG - Residual current devices G


(4) 3 pole 4 pole
RCD bottom mounted
400/630A Voltage 200/440V AC FGQDB3M 430860 FGQDB4M 430869
400/630A Voltage 400/690V AC FGQDB3H 430856 FGQDB4H 430865
X

Normally open Normally closed


Bell Alarm RCD device FABAT10 430818 FABAT 01 430815

One code covers an RCD with: Fixation hardware + Sealable interconnection cover

(1) Key included


(2) Add door flange FGFH for door lock options
(3) On request 1xNO/1xNC is available.
(4) 100/200V AC execution available on request.

A.31
Record Plus
FG - Plug-in system
3 pole 4 pole
Main system
Cat. no. Ref. no. Cat. no. Ref. no.

Complete set for breaker FGDDF3 430944 FGDDF4 431064


Fixed part for breaker FGDFF3 431983 FGDFF4 431986
Mobile part for breaker FGDMP3 432796 FGDMP4 432799

Complete set: Fixed and mobile part with connection and fixation hardware
Fixed part: Fixed base with connection and fixation and hardware
Mobile part: Mechanism trip device, terminal shields and set of 3 or 4 pole plugs

Auxiliary disconnects Complete set 8 pole FAPFM 430824


(Secondary wiring) Fixed part 8 pole FAPF8 430823
Mobile part 8 pole FAPM8 430826

Plug and socket 10 pole (side mounted) FAPPS 430827


Order codes

Insertion prevention kit Insertion prevention kit FAPIP 430825


(of ….wrong A rating)

Spares Set of nutplates and connection bolts FGJN3 436469 FGJN4 436470
(For connection of bases used as spare)

FG - Drawout system
Main system 3 pole 4 pole
Complete set FGWS3 432910 FGWS4 432913

One code covers the fixed and withdrawable part of the draw-out system, with plug-in base, mounting accessories and fixation hardware.

B
Accessories (for Keylock in draw-out position Ronis(1) (a) FG1BRW 433407
auxiliary disconnects Keylock in draw-out position Profalux(1) (b) FG1BPW 433406
see plug-in system)
C Position indication contact NO (c) FAS01D 436309
Position indication contact NC (c) FAS10D 436310

(a) (b) (c)


D
FG - Connections: optional
E Extenders(2)
3 pole 4 pole
Standard flat type (a) FGBES3 431696 FGBES4 431697
Heightened type (b) FGBEH3 431691 FGBEH4 431695
Twisted 90° c (c) FGBEA3 431686 FGBEA4 431690

F (a) (b) (c)

Spreader flat(2) Pole spacing 70mm FGBSS3 431981 FGBSS4 431982

Rear connections(2) Set 3 pole (2 short, 1 long) FGBRC3 431701 FGBRC4 431702
X Set 4 pole (2 short, 2 long)
Set 3 pole (3 short) FGBRCS3 432193 FGBRCS4 432194
Set 4 pole (4 short)

One cable 240 mm2 or Two cables


Internal box clamps(2) 1x300 mm2 & 1x240 mm2
two cables 95 mm2
Box Clamp Cu/Al, set 3 pole FGTCA1327 435107 FGTCA230B 433412
Box Clamp Cu/Al, set 4 pole FGTCA1427 435116 FGTCA240B 433413

(1) Key included


(2) Set for equipping the line OR load side of breaker.

A.32
Record Plus
FG - Installation accessories
3 pole 4 pole
Terminal shields
(with finishing covers) Cat. no. Ref. no. Cat. no. Ref. no.

Long and widened type for spreaders FGJW3 432861 FGJW4 432864
and 690V applications, set of 2 pcs

Medium, set of 2 pcs. FGJM3 432846 FGJM4 432849

Short, set of 2 pcs. FGJS3 432855 FGJS4 432858

Specific to connection area Phase separators, set of 12 pcs FGJP 432852


Backplate (3 or 4pole), set of 2 pcs. FGJB 432840

Padlocking devices Padlocking removable (a) FG1PR 431409


for toggle operator(1)
Padlocking fixed (b) FG1PF 431408

FG frame
(a)
(b)

Circuit indication / coding Set of 20 blank labels FAC 430821

3 pole
Door flanges
RCD unit front face for 3 and 4 pole FDFF3 430941
Front face toggle area FGFT 432836
Rotary handle (through cover plate model)
Motor operator
FGFH
FGFE
430545
430544
A

Spare parts
3 pole 4 pole B
Finishing covers, set of 2 pcs. FGUA3 432908 FGUA4 432909

Spare toggle (set of 5 pieces) FGUT 433541


C
FG - Accessories electronic trip units SMR1 and SMR2
3 pole D
(a) Rating plug tool (SMR1 & 2) (a) FAR 433500

Battery test device (SMR1 & 2) (b) FAT 431402

(b)
E
Long time module (SMR1 only) (c) FAMLT1 433376

(c) G
Ground Fault SMR2 Sensor 250A (d) FGGS0250 431870

Ground Fault SMR2 Sensor 400A (d) FGGS0400 432838


X
(d) Ground Fault SMR2 Sensor 630A (d) FGGS0630 432839

(1) Padlocks not included

A.33
Record Plus
FK Frame

Breaking capacities

Icu 400/415V AC in kA eff.


Type N H L
FK800 50 80 100
FK1250 50 80 100
FK1600 50 80

Protection

Trip Rated LTM Mag SMR1e(1) SMR1s(1) SMR1g(1)


Order codes

Unit Current BreakTM


(A)

FK800 630 N, H, L
800 N, H, L N, H, L N, H, L N, H N, H
FK1250 1000 N, H, L N, H, L N, H N, H
1250 N, H, L N, H, L N, H, L N, H N, H
FK1600 1600 N, H N, H N, H

LTM
Line thermal magnetic
protection Number of poles /
SMR1e protected poles (trips)
Selective electronic protection.
3 pole 3 trips N, H, L N, H, L N, H, L N, H N, H
SMR1s
A Selective electronic protection with
4 pole 3 trips N, H, L N, H, L N, H, L N, H N, H
4 pole 4 trips(1) N, H, L N, H N, H
enhanced functionality
SMR1g (1) Switchable, 0%, 50% or 100% neutral protection
B Selective electronic protection with
enhanced functionality and ground
fault
Mag BreakTM
C Magnetic only breaker for motor
protection
Y
Non Automatic or switch
D (not mentioned in tables)

E
Accessories (main types)
F O
1 A maximum of one Bell Alarm contact AND
3 aux. contacts (all of CO type)
O
2 Shunt or Undervoltage release

G O
3 Operators
Rotary handle
OR
Electrical operator
X O
4 Draw out system
O
5 Connectors for auxiliary wiring
O
6 RCD with separate sensor

A.34
Record Plus
FK800 - Complete circuit breaker
Selective Electronic Trip Unit type SMR1e

3 pole 3 trips 4 pole(1)


N selectable 0-50-100%

In (A) Cat. no. Ref. no. Cat. no. Ref. no.


50kA
FKN 800 FKN36NE800PPF 435393 FKN46NE800PPF 435447

80kA 800 FKH36NE800PPF 435285 FKH46NE800PPF 435339


FKH

800 FKL36NE800PPF 435390 FKL46NE800PPF 435282


100kA
FKL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Enhanced Selective Electronic Trip Unit type SMR1s

In (A) 3 pole 3 trips 4 pole(1)


50kA N selectable 0-50-100%

FK frame
FKN 800 FKN36NS800PPF 435429 FKN46NS800PPF 435483

800 FKH36NS800PPF 435321 FKH46NS800PPF 435375


80kA
FKH One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Enhanced Selective Electronic Trip Unit type SMR1g (= s + ground fault)

3 pole 3 trips 4 pole(1)


In (A)
50kA N selectable 0-50-100%
FKN 800 FKN36NG800PPF 435411 FKN46NG800PPF 435465

800 FKH36NG800PPF 435303 FKH46NG800PPF 435357


A
80kA
FKH One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
B
Line Thermal magnetic trip unit LTM (adjustable settings)
In (A) 3 pole 3 trips 4 pole 3 trips(2)
50kA
FKN 630
800
FKN36NT630PF
FKN36NT800PF
435444 FKN436NT630PF 435408
435336 FKN436NT800PF 435300
C
80kA
FKH 630 FKH36NT630PF 435426 FKH436NT630PF 435462
800 FKH36NT800PF 435318 FKH436NT800PF 435354 D
630 FKL36NT630PF 435480 FKL436NT630PF 435534
100kA 800 FKL36NT800PF 435372 FKL436NT800PF 435535
FKL E
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Motor Protection (Mag BreakTM) Magnetic Only Breaker F


In (A) 3 pole 3 trips 4 pole 3 trips(2)
50kA
FKN 800 FKN36NM800PF 435537 FKN436NM800PF 435541

80kA G
FKH 800 FKH36NM800PF 435538 FKH436NM800PF 435542

800 FKL36NM800PF 435539 FKL436NM800PF 435543


100kA X
FKL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

(1) Switchable 0%, 50% or 100% neutral protection, neutral on left.


(2) Neutral on left

A.35
Record Plus
FK1250 - Complete circuit breaker
Selective Electronic Trip Unit type SMR1e

3 pole 3 trips 4 pole(1)


N selectable 0-50-100%

In (A) Cat. no. Ref. no. Cat. no. Ref. no.


50kA 1000 FKN36NE100SQF 435396 FFKN46NE100SQF 435450
FKN 1250 FKN36NE125SSF 435384 FKN46NE125SSF 435438

80kA 1000 FKH36NE100SQF 435288 FKH46NE100SQF 435342


FKH 1250 FKH36NE125SSF 435276 FKH46NE125SSF 435330

100kA 1000 FKL36NE100SQF 435545 FKL46NE100SQF 435547


FKL 1250 FKL36NE125SSF 435546 FKL46NE125SSF 435549

One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
Order codes

Enhanced Selective Electronic Trip Unit type SMR1s

3 pole 3 trips 4 pole(1)


In (A)
N selectable 0-50-100%
50kA 1000 FKN36NS100SQF 435432 FKN46NS100SQF 435486
FKN 1250 FKN36NS125SSF 435420 FKN46NS125SSF 435474

80kA 1000 FKH36NS100SQF 435324 FKH46NS100SQF 435378


FKH 1250 FKH36NS125SSF 435312 FKH46NS125SSF 435366

One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Enhanced Selective Electronic Trip Unit type SMR1g (= s + ground fault)


A 3 pole 3 trips 4 pole(1)
In (A)
N selectable 0-50-100%
50kA 1000 FKN36NG100SQF 435414 FKN46NG100SQF 435468
FKN 1250 FKN36NG125SSF 435402 FKN46NG125SSF 435456
B
80kA 1000 FKH36NG100SQF 435306 FKH46NG100SQF 435360
FKH 1250 FKH36NG125SSF 435294 FKH46NG125SSF 435348

C One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Line Thermal magnetic trip unit LTM (adjustable settings)


D In (A) 3 pole 3 trips 4 pole 3 trips(2)
50kA 1000 FKN36NT100SF 435550 FKN436NT100SF 435562
FKN 1250 FKN36NT125SF 435551 FKN436NT125SF 435563

E
80kA 1000 FKH36NT100SF 435553 FKH436NT100SF 435565
FKH 1250 FKH36NT125SF 435554 FKH436NT125SF 435566

F 100kA 1000 FKL36NT100SF 435555 FKL436NT100SF 435567


FKL 1250 FKL36NT125SF 435557 FKL436NT125SF 435569

One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
G
Motor Protection (Mag BreakTM ) Magnetic Only Breaker
In (A) 3 pole 3 trips 4 pole 3 trips(2)
50kA
X FKN 1250 FKN36NM125SF 435558 FKN436NM125SF 435570

80kA
FKH 1250 FKH36NM125SF 435559 FKH436NM125SF 435571

100kA
1250 FKL36NM125SF 435561 FKL436NM125SF 435573
FKL
One code covers: A standard fixed front connection breaker + Assembled dummy trip unit + Toggle elongator +
Breaker finishing covers + Fixation hardware

(1) Switchable 0%, 50% or 100% neutral protection, neutral on left.


(2) Neutral on left

A.36
Record Plus
FK1600 - Complete circuit breaker
Selective Electronic Trip Unit type SMR1e

3 pole 3 trips 4 pole(1)


N selectable 0-50-100%

In (A) Cat. no. Ref. no. Cat. no. Ref. no.


50kA
FKN 1600 FKN36NE160TTF 435387 FKN46NE160TTF 435441

80kA 1600 FKH36NE160TTF 435279 FKH46NE160TTF 435333


FKH
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Enhanced Selective Electronic Trip Unit type SMR1s

3 pole 3 trips 4 pole(1)


In (A)
50kA N selectable 0-50-100%
FKN 1600 FKN36NS160TTF 435423 FKN46NS160TTF 435477

FK frame
80kA 1600 FKH36NS160TTF 435315 FKH46NS160TTF 435369
FKH
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware

Enhanced Selective Electronic Trip Unit type SMR1g (= s + ground fault)

3 pole 3 trips 4 pole(1)


In (A)
50kA N selectable 0-50-100%
FKN 1600 FKN36NG160TTF 435405 FKN46NG160TTF 435459

1600 FKH36NG160TTF 435297 FKH46NG160TTF 435351


80kA
FKH One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
A

FKY- Non-Automatic circuit breaker (Switch) B

In (A) 3 pole 4 pole(2)


800 FKY306DN800PF 435495 FKY406DN800PF 435504
C
1000 FKY306DN100SF 435381 FKY406DN100SF 435273
FKY 1250 FKY306DN125SF 435489 FKY406DN125SF 435498
1600 FKY306DN160TF 435492 FKY406DN160TF 435501

One code covers: A standard fixed front connection breaker + Assembled dummy trip unit + Toggle elongator +
D
Breaker finishing covers + Fixation hardware

E
(1) Switchable 0%, 50% or 100% neutral protection, neutral on left.
(2) Neutral on left

A.37
Record Plus
FK - Internal accessories
Changeover
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.

Aux. switch right mounted CO FNS11R 436401


Bell alarm contact right mounted CO FNBA11R 435761

Shunt Undervoltage Delayed undervoltage


Releases
24V AC/DC FNSHTD 435693 - - - -
24 V AC - - FNUVR1 435698 - -
24 V DC - - FNUVRD 435701 - -
48 V AC/DC FNSHTF 435694 - - - -
48V /DC - - FNUVRF 435702 - -
110/130V AC/DC FNSHTJ 435695 - - - -
230V AC - - FNUVR6 435699 - -
220/240V AC - 220/2450V DC FNSHTN 435696 - - - -
400V AC - - FNUVR8 435700 - -
380/440V AC/DC FNSHT8 435692 - - - -
Order codes

230V AC - - - - FNUVD6 435697

FK - Operators
Electrical operators 24V AC/DC FNEMFD 435683
48V AC/DC FNEMFF 435680
110V AC FNEMF3 435686
110V DC FNEMFJ 436457
230V AC FNEMF6 435689
(a) 250V DC FNEMFN 436456

Keylock for electr. operator Ronis(1) (a) FN1BRE 435679


Keylock for electr. operator Profalux(1) (b) FN1BPE 435678
(b)

A Rotary handles Direct on device


Rotary handle through Panel or door
door or cover plate(2) mounted
Grey FNNRF/5 436522 FNNRC/5 436517 - -
Red FNNRFV/5 436524 FNNRCV/5 436518 - -
B Grey + Early closing aux. switches 2xNO(3)
Red + Early closing aux. switches 2xNO(3)
-
-
-
-
FNNRY/5
FNNRYV/5
436527
436528
-
-
-
-

Grey - - - - FNNRD/5 436519


Red - - - - FNNRDV/5 436520
C Grey + Early closing aux. switches 2xNO(3)
Red + Early closing aux. switches 2xNO(3)
-
-
-
-
-
-
-
-
FNNRZ/5
FNNRZV/5
436530
436531

D Accessories
Extension shaft kit (max. 600 mm) (a) FNNRE 435738 Only for use with panel or door mounted type

(a) Flex operator adaptor push to trip (b) FGNFT 432867 Only for use with panel or door mounted type
E
(b) Adaptor for drawout (c) FNNRW 435745
(c)
Ronis keylock 1104B nr. BC 1027(1) (d) FA1BR1 430088
Ronis keylock 1104B nr. BC 1053(1) (d) FA1BR2 430089
F Ronis keylock 1104B nr. BC 2932(1) (d) FA1BR3 430504
(d) Ronis keylock 1104B nr. BC 2911(1) (d) FA1BR4 430505
Ronis keylock 1104B nr. BC 2936(1) (d) FA1BR5 430506
Ronis keylock 1104B nr. BC 2940(1) (d) FA1BR6 430507
Ronis lock with random key(1) (d) FA1BRH 430068
G (e) Profalux lock with random key(1) (e) FA1BPH 430813

(1) Key included


(2) Add door flange FGFH for door lock options
X (3) On request 1xNO/1xNC is available.

A.38
Record Plus
FK - Residual current devices
Relay IΔ n Operating Settable Nr. of Cat. no. Ref. no. Pack.
voltage delay modules
RD5 0.03 ... 1A 110V AC 0-1s 3 RD5 110 704175 1
0.03 ... 1A 220V AC 0-1s 3 RD5 220 704169 1
0.03 ... 1A 380V AC 0-1s 3 RD5 380 704176 1

RD6 0.2 ... 5A 110V AC 0.5 - 5 s 3 RD6 110 704178 1


0.2 ... 5A 220V AC 0.5 - 5 s Splittable
3 RD6 220Closed 704177 1
0.2 ... 5A 380V AC 0.5 - 5 s 3 RD6 380 704179 1

RD1D 0.01 ... 5A 110V AC 0-3s 3 RD1D 110 872225 1


0.01 ... 5A 220/230V AC 0-3s 3 RD1D 220 872224 1
0.01 ... 5A 380/400V AC 0-3s 3 RD1D 380 872226 1

Sensor Round Internal diameter Ø 35mm TT 35 560091 1


Round Internal diameter Ø 60mm TT 60 560092 1
Round Internal diameter Ø 80mm TT 80 560093 1
Round Internal diameter Ø 110mm TT110 560094 1
Round Internal diameter Ø 160mm TT160 560095 1
Round Internal diameter Ø 210mm TT 210 560096 1

FK frame
Round Internal diameter Ø 22mm Din Rail type TTD 22 560090 1
Round; splittable Internal diameter Ø 110mm TTO 110 560097 1
Round; splittable Internal diameter Ø 210mm TTO 210 560098 1

Rectangular opening70 x 175mm BTR 175 704154 1


Rectangular opening115 x 305mm BTR 305 704155 1
Rectangular opening130 x 350mm BTR 350 704156 1

FK - Drawout system
3 pole 4 pole
Main system
Model with front connection
Complete set for FK800 FNWS3WP 433434 FNWS4WP 436481
Complete set for FK1250 & FK1600 FNWS3WT 436482 FNWS4WT 433442

Model with rear connection


A
Complete set for FK800 FNWS3AP 433436 FNWS4AP 433440
Complete set for FK1250 & FK1600 FNWS3AT 435757 FNWS4AT 435759

One code covers the fixed and withdrawable part of the draw-out system, with plug-in base, mounting accessories and fixation hardware. B
Auxiliary Complete set 6 pole FNPFM 435758
disconnects
(Secondary
wiring)
C

Accessories Keylock in chasis pos. 1 Ronis 1104A(1) FN1BRW1 435575


Keylock in chasis pos. 2 Ronis 1104A(1) FN1BRW2 435577 D
Position indication contact CO FNS11L 435760

Doorflange specific for drawout type FNFW 435578


Keylock in doorflange pos. 1 Ronis 1104A(1) FN1BRY1 433415 E
Keylock in doorflange pos. 2 Ronis 1104A(1) FN1BRY2 435574

FK - Connections: optional F
3 pcs 4 pcs
Terminal
extenders(2) Flat FK800 - FK1250 FNBES3P 435706 FNBES4P 435707

Flat FK1250 -FK 1600 FNBES3R 433420 FNBES4R 433422 G


Terminal spreader flat(2) Flat FK800 - FK1250 FNBSS3P 435708 FNBSS4P 435711

Flat FK1250 -FK 1600 FNBSS3R 435710 FNBSS4R 435712 X

Rear connections(2) Set 3 pole (2 short, 1 long) FNBRC3 433423 - -


Set 4 pole (2 short, 2 long) - - FNBRC4 433425

Set 3 pole (3 short) FNBRCS3 433426 - -


Set 4 pole (4 short) - - FNBRCS4 433427

Internal box clamps(2) Box Clamp Cu/Al, for 3 x 70-240 sq.mm. FNTCA3327 436316 FNTCA3427 436651
Box Clamp Cu/Al, for 4 x 70-240 sq.mm. FNTCA4327 433438 FNTCA4427 433439

(1) Key included


(2) Set for equipping the line OR load side of breaker. A.39
Record Plus
FK - Installation Accessories
3 pole 4 pole
Terminal shields
(with finishing covers) Cat. no. Ref. no. Cat. no. Ref. no.

Long, set of 2 pcs. FNJL3 435716 FNJL4 435719

Specific to Phase separators, set of 12 pcs FNJP 435722


connection area

Padlocking devices Padlocking removable FN1PR 433417


Order codes

for toggle operator(1)

Circuit indication / coding Set of 20 blank labels FAC 430821

Door flanges Front face toggle area FNFT 435715


Rotary handle (through cover plate model) FNFH 435714
Motor operator FNFE 435713
Rotary handle through cover model on drawout breaker FNFHW 436590
A

B
Spare parts Finishing covers (set of 2 pieces) FNUA3 435762 FNUA4 435763

C Spare toggle (set of 5 pieces) FNUT 435764

D
FK - Accessories electronic trip units
E Battery test device (a) FNT 435704

Sensor 800A for Ground fault device (b) FNGS0800 433419


Sensor 1000A for Ground fault device (b) FNGS1000 433421
Sensor 1250A for Ground fault device (b) FNGS1250 435709
F Sensor 1600A for Ground fault device (b) FNGS1600 436471

G (a) (b)

(1) Padlocks not included

A.40
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FK frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D
D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.41
Record Plus
Connectivity

Record Plus TM Breaker types

Adaptor Breaker types


type
FBAD FDE FDS FDN FDH FDL
160A 160A 160A 160A 160A
FBAE FEV FEN FEH FEL
160/250A 160/250A 160/250A 160/250A

Icu (kA) at 400/415V AC


25 36 50 80 150
Order codes

Busbar types and Ratings

Busbar In in A Icw (kA) at 400/415V AC


1 second rating(1)
Standards Size

20 x 5 250A 16.7 to 19.9


EN 60439-1 20 x 10 450A 17.6 to 23.8
VDE 0660 Teil 500 30 x 5 400A 22.4 to 27.6
30 x 10 630A 23.3 to 30
A Short-circuit rating of the full system with mounted breakers =
The indicated breaking capacity (Icu) of Record PlusTM MCCB’s
(1) Depending on support spacing (see page C.16)
B

F O
1 Busbar support
O
2 Busbars (not part of offering)
O
3 Connection set

G O
4 Lateral connection set
O
5 Support cover
O
6 Adaptor FD
O
7 Adaptor FE
X O
8 Busbar covers
O
9 Trim/Cover plate filler

A.42
Record Plus
Connectivity system with 60mm spacing; three and four pole
Busbar supports
3 pole 4 pole

Cat. no. Ref. no. Cat. no. Ref. no.


Set of left and right FBB3S 433458 FBB4S 433464
Endplate covers, pair of FBB3E 433455 FBB4E 433461

Connections
Incoming from side Incoming from front
1 pole for lateral bar, flexible bar or cable connection FBTS1L12 433468 - -
Cu/Al 35-240 mm2 for busbar section 5 mm

Connectivity
1 pole for lateral bar, flexible bar or cable connection FBTS10L12 433474 - -
Cu/Al 35-300 mm2 for busbar section 10 mm
3 pole set for conductors 1.5 to 70mm2 - - FBTF3L12 433456
4 pole set for conductors 1.5 to 70mm2 - - FBTF4L12 433497

Adaptors
3 pole 4 pole
FD frame 160A FBAD3 433443 FBAD4 433446
FE frame 250A FBAE3 433449 FBAE4 433452

Installation
A
Busbar cover adjustable 3pole FBCI3 433377
Busbar cover adjustable 4pole FBCI4 433444
Filler for cover plate cut out of 64mm l=1.2m FBF6 883970 B

A.43
Record Plus
Changeover devices

Available short-circuit rating at 415V AC


in kA
Device Y N H L
FE 160 3 50 80 150
FE 250 4.5 50 80 150
FG 400 6 50 80 150
FG 630 8 50 80 150
FK 800 10 50 80 100
FK1250 15 50 80 100
FK1600 20 50 80
Order codes

Available trip units, number of poles and


trips (protected poles)

Device Y LTMD(1) GTM(1) SMR Mag


types Break
LTM
Line thermal magnetic protection
LTMD FE 160 Y N,H,L N,H N,H,L N,H,L
FE 250 Y N,H,L N,H N,H,L N,H,L
Selective thermal magnetic
FG 400 Y N,H,L N,H,L N,H,L
protection FG 630 Y N,H,L N,H,L
GTM
A Generator thermal magnetic protection
FK 800
FK1250
Y
Y
N,H,L
N,H,L
N,H,L
N,H,L
N,H,L
N,H,L
SMR types FK1600 Y N,H
Selective/Modular electronic trip units 3 pole 3 trips Y(2) N,H,L N,H N,H,L N,H,L
4 pole 4 trips Y(2) N,H,L N,H N,H,L
B Mag BreakTM
4 pole 3 trips N,H,L N,H N,H,L N,H,L
Magnetic Only protection 4 pole 3.5 trips (N=50%)(3) N,H,L N,H N,H,L
Y
(1) FG & FK type LTM only (2) 3 or 4 pole without trips (3) Rated current > 63 A
Non Automatic or switch
C (not mentioned in tables)

Available device
D combinations
Main device Secundary device
N R
E FE 160 10 - 160A FE 160 10 - 160A
FE 250 80 - 250A FE 250 80 - 250A

FG 400 100 - 400A FE 160 10 - 160A


FG 630 160 - 630A FE 250 80 - 250A
F
FG 400 100 - 400A FG 400 100 - 400A
FG 630 160 - 630A FG 630 160 - 630A

FK 800 320 - 800A FG 400 100 - 400A


G FG 1250 400 - 1250A FG 630 160 - 630A
FG 1600 640 - 1600A

FK 800 320 - 800A FK 800 320 - 800A


FG 1250 400 - 1250A FG 1250 400 - 1250A
X FG 1600 640 - 1600A FG 1600 640 - 1600A

O
1 Mechanical interlock for two breakers
O
2 Breaker mounting plates
O
3 Mechanical interlock with lock in rotary handles
O
4 Electrical interlock with UVR and SHT release
O
5 Controller for automatic changeover suitable for two breakers Technical features pg. C.18
O
6 Electrical operators

A.44
Record Plus
Changeover systems

Electrical interlocking of two breakers


System with early action contacts in rotary handle and coils in both breakers(1)
Main Secondary Required main components
Device Device Listed protection devices are breakers or
N (left) R (right) Can be combined with
switches
Option 1 or 2
order codes can be found on :

FK800/1600

FK800/1600
FG400/630

FG400/630
FE160/250

FE160/250
FE 160: page A.13 FE 250 : page A.16

Changeover devices
FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
FK1600: page A.37 Cat. no. Ref. no. Qty

Rotary handle, grey, through door or panel type FE FENRX/5 436499 2


with 1 NO and 1 NC contact
x • •x Shunt release in mains device F-- - -- -- 4---- 1
Undervoltage release in secondary device F-- - -- -- 4---- 1

Rotary handle, grey, through door or panel type FG FGNRX/5 436512 2


with 1 NO and 1 NC contact
x • •x Shunt release in mains device F-- - -- -- 4---- 1
Undervoltage release in secondary device F-- - -- -- 4---- 1

Rotary handle, grey, through door or panel type FG FGNRX/5 436512 1


with 1 NO and 1 NC contact
Rotary handle, grey, through door or panel type FE FENRX/5 436499 1
x • •x with 1 NO and 1 NC contact
Shunt release in mains device F-- - -- -- 4---- 1
Undervoltage release in secondary device F-- - -- -- 4---- 1

Rotary handle, grey, through door or panel type FK


with 1 NO and 1 NC contact
FNNRX/5 436526 2 A
x • •x Shunt release in mains device F-- - -- -- 4---- 1
Undervoltage release in secondary device F-- - -- -- 4---- 1

Rotary handle, grey, through door or panel type FK FNNRX/5 436526 1


B
with 1 NO and 1 NC contact
Rotary handle, grey, through door or panel type FG FGNRX/5 436512 1
x • •x with 1 NO and 1 NC contact
Shunt release in mains device
Undervoltage release in secondary device
F-- - -- --
F-- - -- --
4----
4----
1
1
C

(1) Also available for three breakers


D

Shunt release for breaker/switch E


FE & FG type FK type
24V AC/DC FASHTD 430843 FNSHTD 435693
110/130V AC/DC FASHTJ 430849 FNSHTJ 435695
220/240V AC 250V DC FASHTN 430852 FNSHTN 435696 F
Undervoltage release for breaker/switch
a FK type
FE & FG type G
24V AC/DC FAUVRD 430861 - -
24V AC - - FNUVR1 435698
24V DC - - FNUVRD 435701
110/130V AC/DC FAUVRJ 430867 FNUVRJ 437018 X
220/240V AC 250V DC FAUVRN 430870 - -
230V AC - - FNUVR6 435699

A.45
Record Plus
Mechanical interlocking of two breakers
System with walking beam
Main Secondary Required components
Device Device Listed protection devices are breakers or
N (left) R (right) switches Option 1
order codes can be found on :

FK800/1600

FK800/1600
FG400/630

FG400/630
FE160/250

FE160/250
FE 160: page A.13 FE 250 : page A.16
FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
Cat. no. Ref. no. Qty
FK1600: page A.37

Mechanical interlock 2 FE frame breakers FE1I2 437001 1


x • •x

Mechanical interlock 2 FG frame breakers FG1I2 437005 1


x • •x
Order codes

Mechanical interlock 1 FG & 1 FE frame breakers FG1I4 437009 1


x • •x

Mechanical interlock 2 FK frame breakers FN1I2F 433416 1


x • •x

Mechanical interlock 1 FK & 1 FG frame breaker FN1I4F 437016 1


x • •x

System with rotary handles, 1 key and two locks (Ronis 1104) (1)
Main Secondary Required components
Device Device Listed protection devices are breakers or
A N (left) R (right) switches
order codes can be found on :
Option 2
FK800/1600

FK800/1600
FG400/630

FG400/630
FE160/250

FE160/250

FE 160: page A.13 FE 250 : page A.16


FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
Cat. no. Ref. no. Qty
B FK1600: page A.37

Rotary handle, grey, through door or panel type FE FENRC 432102 2


x • •x Ronis keylock FA1BR -- 430 - - - 2

C Rotary handle, grey, through door or panel type FG FGNRC 432873 1


x • •x Ronis keylock FA1BR -- 430 - - - 2

D Rotary handle, grey, through door or panel type FE FENRC 432102 1


x • •x Rotary handle, grey, through door or panel type FG FGNRC 432873 1
Ronis keylock FA1BR -- 430 - - - 2

E x • •x Rotary handle, grey, through door or panel type FK FNNRC 435726 1


Ronis keylock FA1BR -- 430 - - - 2

Rotary handle, grey, through door or panel type FK FNNRC 435726 1


F x • •x Rotary handle, grey, through door or panel type FG FGNRC 432873 1
Ronis keylock FA1BR -- 430 - - - 2

X Keylocks type Ronis 1104 with key


Ronis keylock 1104B nr. BC 1027 FA1BR1 430088
One type only

Ronis keylock 1104B nr. BC 1053 FA1BR2 430089


Ronis keylock 1104B nr. BC 2932 FA1BR3 430504
Ronis keylock 1104B nr. BC 2911 FA1BR4 430505
Ronis keylock 1104B nr. BC 2936 FA1BR5 430506
Ronis keylock 1104B nr. BC 2940 FA1BR6 430507

A.46
Record Plus
Complete automatic changeover sets
Two power supplies, ONLY one of which is allowed to supply the network
Main Secondary Required main components
Device Device Listed protection devices are breakers or
N (left) R (right) switches
order codes can be found on :

FK800/1600

FK800/1600
FG400/630

FG400/630
FE160/250

FE160/250
FE 160: page A.13 FE 250 : page A.16
FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
Cat. no. Ref. no. Qty
FK1600: page A.37

System 110V 50/60Hz with all necessary breaker FEEO1J 437000 1

Option 1

Changeover devices
accessories for two FE frames - WITHOUT CONTROLLER
x • •x System 220V 50/60Hz with all necessary breaker FEEO1N 437003 1
accessories for two FE frames - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1

System 110V 50/60Hz with all necessary breaker FGEO2J 437004 1

Option 2
accessories for two FG frames - WITHOUT CONTROLLER
x • •x System 220V 50/60Hz with all necessary breaker FGEO2N 437007 1
accessories for two FG frames - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1

System 110V 50/60Hz with all necessary breaker FGEO3J 437008 1


Option 3

accessories for 1 FG + 1 FE frame - WITHOUT CONTROLLER


x • •x System 220V 50/60Hz with all necessary breaker FGEO3N 437010 1
accessories for 1 FG + 1 FE frame - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1

System 110V 50/60Hz with all necessary breaker FKEO4J 437011 1


Option 4

accessories for two FK frames - WITHOUT CONTROLLER


x • •x System 220V 50/60Hz with all necessary breaker FKEO4N 437014 1
accessories for two FK frames - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1
A
System 110V 50/60Hz with all necessary breaker FKEO5J 437015 1
Option 5

accessories for 1 FK + 1 FG frame - WITHOUT CONTROLLER


x • •x System 220V 50/60Hz with all necessary breaker FKEO5N 437017 1
accessories for 1 FK + 1 FG frame - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1
B

Allowed combinations OFF OFF


ON
OFF
OFF
ON
C

Required controller type E model(1)


Controller 110/127V 50/60 cycles FE-FG frame FAECA3 436453
D
Controller 110/127V 50/60 cycles combinations with FK frame FNECA3 436452
Controller 220/240V 50/60 cycles FE-FG frame FAECA6 872240
Controller 220/240V 50/60 cycles combinations with FK frame FNECA6 436451
Required controller type E Plus model(1) E
Controller 110/127V 50/60 cycles FE-FG frame FAECE3 872141
Controller 110/127V 50/60 cycles combinations with FK frame FNECE3 436450
Controller 220/240V 50/60 cycles FE-FG frame FAECE6 872140
Controller 220/240V 50/60 cycles combinations with FK frame FNECE6 436449 F
E model with voltage monitoring(1)
Add indicated code to controller cat nr. and add extra ref.nr. - - - - - M 872052

G
(1) This are the reference numbers for the controler in english version. For other languages, consult us.

A.47
Record Plus
Residual current devices with separate
sensors

RD5, RD6 and RD1D

Function
RCD Relay
The relay part of the RCD device is a DIN-rail mounted device containing
the electronics and the setting area. On receipt of a signal from the
sensor two contacts are operated.
Sensor
Placed around the phase and neutral current paths it detects the vectorial sum of
Order codes

the current in the circuit. When this sum is no longer zero, a signal is sent to the
connected RCD relay.
The connection between the relay and the sensor should be as short as possible,
the maximum circuit resistance may not exceed 30 Ohm.
If the lead length is longer than 5 meters and/or the sensitivity is adjusted to
values < 0.5A the use of screened cables and earthed screening is recommended.
The same recommendation applies in cases where the sensor is installed in an
Applications environment where strong magnetic fields occur.
For high nominal currents or high sensitivities the cables must be centered within
the sensor.
The use of an oversized sensor and/or reduced cable cross sections not centraly
passing within the sensor could result in inaccurate readings.

A
Characteristics

B RCD Relay
• Complies with EN 50082 & EN 60730
• For sinusoidal and pulsating earth leakages
• Test button and reset (memory clean) button
C • Permanent working signal (green) and tripping signal (red) by means of LED
• Adjustable time delay (except 30mA) by means of potentiometer
• Two output contacts, one potential free
• Automatic test feature of the combination relay/sensor is provided
D • On disconnection of the sensor, the relay trips
• Plug-in terminal block
• Width: 3 modules of 18 mm
E • For installation in modular enclosures, DIN-rail mounted
Sensor
• Accuracy: 3/10,000 of the phase current (TTO type 1/10,000)
• Frequency: from 4 to 400Hz
F • Sealable cover terminals
• For use with the relay types RD1D, RD5 and RD6 as described here.
Also applicable for use with the reconnection relay RRC1 and RRC2
(see seperate publications)
G
Dimensions pg G.33

RD5 RD6 RD1D


X Operating voltage
Power consumption
110; 220; 380/400V 50/60Hz ±15%
2.5VA
110; 220; 380/400V 50/60Hz ±15%
2.5VA
110; 220; 380/400V 50/60Hz ±15%
2.5VA
Sensitivity settings 0.03 ; 0.3 ; 0.5 ; 1A 0.2 ; 0.5 ; 2 ; 5A 0.01 - 5A in steps of 10mA
Setting method Dipswitches Dipswitches Digital with LCD display
Frequency 50/60Hz 50/60Hz 50/60Hz
Time delay adjustment (1) 0 - 1 second 0.5 - 5 seconds 0 - 3 seconds in steps of 50ms
Tripping time 30mA type 1x IdN<50ms - 5 x Idn<35ms 1x IdN<50ms - 5 x Idn<35ms 1x IdN<50ms - 5 x Idn<35ms
Tripping threshold 75% of set sensitivity value 75% of set sensitivity value 75% of set sensitivity value
Pre Alarm at 50% setting ---- ---- Contact settable at 50% Idn
Contact ratings 5A / 230V 5A / 230 5A / 230V
Operating temperature - 20 to + 50°C - 20 to + 50°C - 20 to + 50°C
Terminal capacity 2.5 mm2; plug in terminal box 2.5 mm2; plug in terminal box 2.5 mm2; plug in terminal box
(1) Time setting ALWAYS disabled when 30mA setting is chosen.

A.48
Record Plus
RD range differential relay
IΔn Operating Settable Nr. of Cat. no. Ref. no. Pack.
voltage delay modules
RD5 0.03 ... 1A 110V AC 0-1s 3 RD5 110 704175 1
0.03 ... 1A 220/230V AC 0-1s 3 RD5 220 704169 1
0.03 ... 1A 380/400V AC 0-1s 3 RD5 380 704176 1

RD6 0.2 ... 5A 110V AC 0.5 - 5 s 3 RD6 110 704178 1


0.2 ... 5A 220/230V AC 0.5 - 5 s 3 RD6 220 704177 1

Residual current devices


0.2 ... 5A 380/400V AC 0.5 - 5 s 3 RD6 380 704179 1

RD1D 0.01 ... 5A 110V AC 0-3s 3 RD1D 110 872225 1


0.01 ... 5A 220/230V AC 0-3s 3 RD1D 220 872224 1
0.01 ... 5A 380/400V AC 0-3s 3 RD1D 380 872226 1

Sensor
Closed model; internal diameter 22mm , suitable for DIN rail mounting TTD 22 560090 1
Closed model; internal diameter 35mm TT 35 560091 1
Closed model; internal diameter 60mm TT 60 560092 1
Closed model; internal diameter 80mm TT 80 560093 1
Closed model; internal diameter 110mm TT110 560094 1
Closed model; internal diameter 160mm TT160 560095 1
Closed model; internal diameter 210mm TT 210 560096 1

Open/splittable model; internal diameter 110 mm TTO 110 560097 1


Open/splittable model; internal diameter 210 mm TTO 210 560098 1

Closed rectangular model opening 75 x 105mm BTR 175 704154 1


Closed rectangular model opening 115 x 305mm BTR 305 704155 1
Closed rectangular model opening 130 x 350mm BTR 350 704156 1

Accessories
Through Panel/Door mounting kit for relay with DIN -rail, mounting RDFR 872227 1
A
hardware and doorflange.

C
Wiring Diagram

SHT UVR* F

*12 = SHT
13 = UVR

A.49
Just rel
Record Plus

Thermal magnetic & Magnetic only trip units

B.2 FD frame: LTM, LTMD, GTM, Mag BreakTM

B.6 FE frame: LTM, LTMD, GTM, Mag BreakTM

Electronic trip units

B.11 FE160 and FE250 breakers SMR1 types

B.14 FG400 and FG630 breakers SMR1 types

B.19 FG400 and FG630 breakers SMR2 types

B.20 FG400 and FG630 breakers SMR2 types - modules


The breaker
B.24 FK800, FK1250 and FK1600 breakers SMR1e, s, g types

B.28 Electronic trip units - Accessories


Order codes A
B.29 Trip units - overview
Trip units B

Components & Accessories C

Technical data D

Application guide E

Wiring diagrams F

Dimensions G

y on us
Numerical Index X

B.1
Record Plus
Thermal Magnetic Trip Units

FD frame

Record PlusTM circuit breakers are designed to isolate and The trip units have been designed with the user in mind.
switch low voltage distribution circuits and to protect the The trip unit ratings are always indicated in amperes.
conductors, equipment and devices included in these To prevent unauthorized manipulation of the breaker
circuits. settings each trip unit comes with a transparent ,
The FD frame size is designed to use electro-mechanical tamper-free (sealable) cover.
trip units. These are typical thermal magnetic devices All units come as 3 and 4 pole devices (2p on request)
which offer an overload (thermal) and short-circuit and are available in a number of application-defined
protection (magnetic). subvariants.
The breaker can also be equipped with a Mag BreakTM
magnetic-only trip unit that offers short-circuit
protection.
Trip units

The trip unit is an integrated part of the breaker and is Mag BreakTM (magnetic only)
not interchangeable. The following versions are (FD..MO sub type)
available: Available in the FD63/160N, H and L breaker types.
A trip unit designed to offer short-circuit protection
LTM (line protection thermal magnetic) only and specifically suited for motor protection in
(FD...TF sub type) coordination with a contactor and a thermal relay
Available in the Concise (FD63/160C) and Effective (EN 60947-4).
breaker type (FD63/160E). Has a settable magnetic threshold of 10 to 15 x In.
Has no thermal setting option and a magnetic release
A set at 10 x In.(1) Y (non automatic - switch disconnector)
Designed for the protection of generic loads. A device available in a 63A and 160A variant .
Has no protection elements.
LTM (line protection thermal magnetic) Designed as switch disconnector
B (FD..TC & TE sub type)
Available in the Concise (FD63/160C) and Effective
breaker type (FD63/160E).
C Has a thermal settingof 0.8 to 1 times and a magnetic
release set at 10(1) x the selected rating. Designed for
the protection of generic loads.

D LTMD ( line thermal magnetic, selective)


(FD..TD sub type)
Available in the FD63/160S, N, H and L breaker types.
A trip unit offering selectivity with downstream devices
E as the ElfaPlus MCBs and Surion motor starter. Has a
thermal setting of 0.8 to 1 times, and a magnetic
release set at 10(1) x the selected rating.
F Designed for the selective protection of generic loads.

GTM (generator thermal magnetic)


(FD..TG sub type)
G Available in the FD63/160N and H breaker types
Suitable for generator protection and / or long cable
runs where a low magnetic threshold is required. Has a
X thermal setting of 0.8 to 1 times, and a magnetic
release set at 4 or 5 times the selected rating.

(1) 160A type 8x

B.2
Record Plus
FD63/160 breakers - trip unit overview
FD frame Trip unit overview
In Thermal setting Ir Magnetic setting Im Neutral protection
Sub- pick-up band 1.05 ÷ 1.3 Ir pick-up band ± 20% Im
Type type Applicable for breaker types [A] min [A] max [A] fix [A] 4P4T 4P 3.5T 4P3T
16 16 160 =Ir
20 20 200 =Ir
25 25 250 =Ir
32 32 320 =Ir
LTM F.D C E 40 Ir = In 40 10 x In 400 =Ir
50 50 500 =Ir
63 63 630 =Ir
80 80 800 =Ir
100 100 1000 =Ir
125 125 1250 =Ir
160 160 8 x In 1280 =Ir
16 12.8 16 160 =Ir
20 16 20 200 =Ir
25 20 25 250 =Ir
32 25.6 32 320 =Ir
LTM C.D C E 40 Ir = 32 40 10 x In 400 =Ir
50 40 50 500 =Ir

FD frame
E.D. 0.8÷1In
63 50.4 63 630 =Ir
80 64 80 800 =Ir
100 80 100 1000 =Ir
125 100 125 1250 =Ir
160 128 160 8 x In 1280 =Ir
16 12.8 16 160 =Ir
20 16 20 200 =Ir
25 20 25 250 =Ir

not protected (1)


32 25.6 32 320 =Ir
40 Ir = 32 40 10 x In 400 =Ir
LTMD D.D S N H L 50 0.8÷1In 40 50 500 =Ir
63 50.4 63 630 =Ir =Ir/2(1)
80 64 80 800 =Ir =Ir/2(1)
100 80 100 1000 =Ir =Ir/2(1)
125 100 125 1250 =Ir =Ir/2(1)
160
25
128
20
160
25
8 x In 1280
125
=Ir
=Ir
=Ir/2(1) A
5 x In
32 25.6 32 160 =Ir

not protected
40 32 40 160 =Ir
50 40 50 200 =Ir
GTM G.D N H Ir = n
63
80
0.8÷1In 50.4
64
63
80 4 x In
252
320
=Ir
=Ir =Ir/2
B
100 80 100 400 =Ir =Ir/2
125 100 125 500 =Ir =Ir/2
160 128 160 640 =Ir =Ir/2
3
7
35
70
52.5
105
C
not protected
12.5 Adjust- 125 187.5
20 able 200 300
Mag. N H
30 10÷15In 300 450
BreakTM L No protection
50
80
500
800
750
1200
D
100 1000 1500
Y Y 63 No protection
160
E
(1) Not available in S type

n
G
Depicted is the LTMD type

B.3
Record Plus
Time Current Curves
FD frame

Breaker FD63 / LTM 16-63A Breaker FD160 / LTM 80, 100 & 125A
10000 10000
120 120
100 6000 100 6000
80 80
60 4000 60 4000 Set at 1 x In
50 Set at 0,8 x In Set at 1 x In 50 Set at 0,8 x In
40 40 Ir=80, 100 or 125A
30 2000 30 2000 Ir=64,80 or 100A
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40

20 20
Trip units

Minutes
Seconds

Minutes
Seconds
10 10
6 6
4 4

2 2

1 1
0,6 LTM type 0,6 LTM type
Trip Time

Trip Time
0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01

A 0,006
0,004
0,006
0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
B x Nominal Current In x Nominal Current In

C 10000
Breaker FD160 / LTM 160A
10000
Breaker FD63 / LTMD 16-32A

120 120
100 6000 100 6000
80 80
60 4000 Set at 1 x In 60 4000 Set at 1 x In
50 Set at 0,8 x In 50 Set at 0,8 x In
40 Ir=160A 40 Ir=16 or 20A
2000 2000
D 30
20
1000
Ir=128A 30
20
1000
Ir=12,5 or 16A

10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
E 2
100
2
100
1 60 1 60
40 40

20 20
Minutes
Seconds

Minutes
Seconds

F 10 10
6 6
4 4

2 2

G 1
0,6 LTM type
1
0,6 LTM type
Trip Time

Trip Time

0,4 0,4

0,2 0,2

X 0,1
0,06
0,1
0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006 0,006
0,004 0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In

Time current curves are depicted in cold state.


For the types with fixed thermal settings (FD..TF) the 'set at 1x in' curves appply

B.4
Record Plus
Time Current Curves

Breaker FD63 / LTMD-GTM 40, 50 & 63A Breaker FD160 / LTMD-GTM 80, 100 and 125A
10000 10000
120 120
100 6000 100 6000
80 80 Set at 0,8 x In Set at 1 x In
60 4000 Set at 1 x In 60 4000
50 Set at 0,8 x In 50 Ir=64,80 or 100A Ir=80, 100 or 125A
40 Ir=40, 50 or 63A 40
30 2000 Ir=32,40 or 50A 30 2000
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40

20 20
Minutes
Seconds

Minutes
Seconds

FD frame
10 10
6 6
4 4
GTM type
2 2 GTM type

1 1
0,6 LTMD type 0,6 LTMD type
Trip Time

Trip Time

0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In B

Breaker FD63 / Mag. Break 3, 7, 12.5, 20, 30 and 50A

10000
Breaker FD160 / LTMD-GTM 160A
10000
Breaker FD160 / Mag. Break 80 and 100A C
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80
60 4000 60 4000
50 Ir=128A Ir=160A 50
40 40
2000 2000
30
20
1000
30
20
1000 Thermal Withstand of Breaker
D
10 600 10 600 FD63 type
8 8 Max in Class 10 and 30
6 400 6 400
5 5 63 Amp
4 4
3 200 3 200
2
100
2
100 E
1 60 1 60
40 40 Thermal Withstand of Breaker
FD160 type
20 20 Max in Class 30 80 Amp
Minutes
Seconds

Minutes
Seconds

10 10 Max in Class 10 100 Amp F


6 6
4 4

2 GTM type 2 Set at 10 x In

1
0,6 LTMD type
1
0,6 Set at 15 x In
G
Trip Time

Trip Time

0,4 0,4

0,2 0,2

0,1
0,06
0,1
0,06
X
0,04 0,04

0,02 0,02

0,01 0,01
0,006 0,006
0,004 0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 67,2 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In

Time current curves are depicted in cold state.


For the types with fixed thermal settings (FD..TF) the 'set at 1x in' curves appply

B.5
Record Plus
Thermal Magnetic Trip Units

FE frame

The breaker is built up of a frame and an inter- overload fault and, in accordance with the HD 384
changeable trip unit . The interchangeability also includes standards to immediately reclose after an overload
the electronic trip unit and the non-automatic switch event . Each trip unit is equipped with an interchange
variant . The FE frame size trip units are designed to prevention interlock that does not allow one to
distinguish between an overload or short-circuit and are incorrectly place a 200 or 250A trip unit in a 160A frame
equipped with indicating flags. This patented GE system size.
saves down time by enabling the user to identify an

The following versions are available:

LTM (line thermal magnetic protection )


Trip units

(FE...TA sub type)


Available in the FE160N, H & L and the FE250V, N, H & L
breaker types.
Has a thermal setting of 0.8 to 1 and a magnetic
setting of 5 to 10 times the selected rating.
Designed for the for protection of generic loads.

LTMD (Selective thermal magnetic protection)


(FE...TD sub type)
Available in the FE160N, H & L and FE250N, H & L
breaker types.
A A trip unit that offers selectivity with downstream
devices as the Elfa Plus, FD63/160 range and the
Surion motor starter.
Designed for the protection fo generic loads.
B
GTM (generator thermal magnetic)
(FE...TG sub type)
C Available in the FE160N, H & L and FE250N, H & L
breaker types.
Has a thermal setting of 0.8 to 1and a magnetic setting
of 3 to 5 times the selected rating.
D Suitable for generator protection and / or long cable
runs where a low magnetic threshold is required.

Mag BreakTM (magnetic only)


E (FE...MO sub type)
Available in the FE160N, H & L FE250N, H & L breaker
types.
F A trip unit designed to offer short-circuit protection
only and specifically suited for motor protection in
coordination with a contactor and a thermal relay
(EN 60947-4).
G Has a settable magnetic threshold of 10 to 15 x In.

Y (non automatic - switch disconnector)


X A 'dummy 'trip unit available in a 160A and 250A
variant .
Has no protection elements.
Designed as switch disconnector.

B.6
Record Plus
FE160 and FE250 breakers - trip unit overview (electromechanical)
FE frame Electro-mechanical trip unit overview
In Thermal Ir Magnetic Im Neutral protection
Sub- pick-up band 1.05 ÷ 1.3 Ir pick-up band ± 20% Im
Type type Applicable for breaker types [A] min [A] max [A] min [A] max [A] 4P4T 4P 3.5T 4P3T
25 20 25 200 =Ir
32 26 32 256 =Ir

not protected
40 32 40 Fixed 320 =Ir
50 40 50 8 x In 400 =Ir
LTM A.E N H L 63 adjustable 50 63 504 =Ir =Ir/2
FE160
80 0.8÷1xIn 64 80 400 800 =Ir =Ir/2
100 80 100 adjustable 500 1000 =Ir =Ir/2
125 100 125 5÷10 In 625 1250 =Ir =Ir/2
160 128 160 800 1600 =Ir =Ir/2
100 80 100 500 1000 =Ir

not protected
FE160 125 adjustable 100 125 adjustable 625 1250 =Ir
LTMD D.E N H L 160 0.8÷1xIn 128 160 5÷10 In 800 1600 =Ir
125 100 125 625 1250 =Ir =Ir/2
FE250 160 adjustable 128 160 adjustable 800 1600 =Ir =Ir/2
200 0.8÷1xIn 160 200 5÷10 In 1000 2000 =Ir =Ir/2
250 200 250 1250 2500 =Ir =Ir/2
40 32 40 160 =Ir

FE frame
50 40 50 Fixed 200 =Ir
FE160 63 adjustable 50 63 4 x In 252 =Ir =Ir/2
100 0.8÷1xIn 80 100 400 =Ir =Ir/2
GTM G.E N H 125 100 125 375 625 =Ir =Ir/2
160 128 160 480 800 =Ir =Ir/2
125 100 125 adjustable 375 625 =Ir =Ir/2
160 adjustable 128 160 3-5 In 480 800 =Ir =Ir/2
FE250
200 0.8÷1xIn 160 n 200 600
o 1000 =Ir =Ir/2
250 200 250 750 1250 =Ir =Ir/2
3,5 24,5 52,5
7 adjustable 49 105
12,5 7÷15In 87,5 188
20 140 300

not protected
Mag. FE160 30 210 450
BreakTM N H L 50 500 750
80
100
No protection
adjustable
800
1000
1200
1500
A
125 10÷15In 1250 1875
160 1600 2400
FE250 160 1600 2400
200
250
2000
2500
3000
3750
B
FE160 160
Y Y No protection
FE250 250

C
n o

Depicted is the LTMD type


E

B.7
Record Plus
Time Current Curves
FE frame

Breaker FE160 / GTM-LTM 25-32A Breaker FE160 / GTM-LTM 40, 50 and 63A
10000 10000
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80 Set at 0,8 x In Set at 1 x In
60 4000 60 4000
50 Ir=20 or 25A Ir=25 or 32A 50 Ir=32, 40 or 50A Ir=40, 50 or 63A
40 40
30 2000 30 2000
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40

20 20
Trip units

Minutes
Minutes

Seconds
Seconds

10 10
6 6
4 4
GTM type GTM type
2 2

1 1
LTM type LTM type
0,6 0,6

Trip Time
Trip Time

0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01

A 0,006
0,004
0,006
0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.2 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
B x Nominal Current In x Nominal Current In

C 10000
Breaker FE160 / GTM-LTM 801), 100, 125 and 160A
1) 80A type not available in GTM version
10000
Breaker FE160 / LTMD 100, 125 and 160A

120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80 Set at 0,8 x In Set at 1 x In
60 4000 60 4000
50 Ir=64, 80, 100 or 128A Ir=80, 100, 125 or 160A 50 Ir=80, 100 or 128A Ir=100, 125 or 160A
40 40
2000 2000
D 30
20
1000
30
20
1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
E 2
100
2
100
1 60 1 60
40 40

20 20
Minutes

Minutes
Seconds

Seconds

F 10 10
6 6
4 4
GTM type
2 Adjustable 2

G 1
0,6
3-5 x In
1
0,6
LTMD type
Adjustable
Trip Time

Trip Time

0,4 0,4 5-10 x In


LTM type
0,2 Adjustable 0,2
5-10 x In
X 0,1
0,06
0,1
0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006 0,006
0,004 0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Nominal Current In x Nominal Current In

Time current curves are depicted in cold state.

B.8
Record Plus
Time Current Curves

Breaker FE250 / GTM 125, 160, 200 and 250A Breaker FE250 / LTMD 125, 160, 200 and 250A
10000 10000
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80 Set at 0,8 x In Set at 1 x In
60 4000 60 4000
50 Ir=128, 200 or 250A Ir=160, 200 or 250A 50 Ir=100, 125, Ir=125, 160, 200 or 250A
40 40 160 or 200A
30 2000 30 2000
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40

20 20
Minutes

Minutes
Seconds

Seconds

FE frame
10 10
6 6
4 4

2 2

1 GTM type 1 LTMD type


0,6 Adjustable 0,6 Adjustable
Trip Time

Trip Time

0,4 3-5 x In 0,4 5-10 x In

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In B

Breaker FE160 / Mag. Break 3, 5, 12.5, 20, 30, 50, 80, 100, 125 and 160A

10000
Breaker FE250 / Mag. Break 160, 200 and 250A C
120
100 6000
80
60 4000
50
40
2000
30
20
1000 Thermal Whitstand of Breaker D
FE160 type
10 600
8 Max in Class 10 and 30
6 400
5 150 Amp
4
3 200
2
100 E
1 60
40 Thermal Whitstand of Breaker
FE250 type
20 Max in Class 10 and 30
Minutes
Seconds

10 225 Amp
F
6
4

1
0,6
Set at 10 x In
G
Set at 15 x In
Trip Time

0,4

0,2

0,1
0,06
X
0,04

0,02

0,01
0,006
0,004

0,002

0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In

Time current curves are depicted in cold state.

B.9
Record Plus
Electronic Trip Units

SMR range

Electronic trip units that offer sophisticated protective circuits in mind and has been rigorously tested to cope
functions and wide setting bands are standard with harmonic currents, electromagnetic fields, inrush
protection devices for the FG400, FG630, FK800, FK1250 currents and spikes, thus preventing phenomanae as
and FK1600 frame sizes. The FE frame can be equipped incorrect current measurement and nuisance tripping.
with interchangeable trip units offering a choice of the The devices exist in a number of performance tiers, the
electronic or the electro-mechanical device. Each SMR1 device for the FE and FG frame sizes, the SMR 2 for
electronic device has been designed with the the FG frame size and the SMR1e, 1s and 1g types for
abnormalities of modern low voltage distribution the FK frame size.

SMR1 The SMR 1 uses rating plugs that allow


Trip units

The SMR1 trip unit type is available for all FE and FG the user flexibility to make a last minute
frame sizes. The device has two basic protective choice in the required current rating,
functions. The first is a Long Time or overload protected poles or protection band.
protection with two time bands designed to match These exist in two variants, adjustable
motor or cable characteristics and a user defineable and switchable. In order to prevent an
setting range. When set to motor protection mode a insertion of a rating plug into the
phase loss protection is initiated that will trip the incorrect trip unit (number of poles and
breaker when the difference in current between one current rating) a mechanical interlock
phase line and the average of all three phase drops and color coding system are present .
below 20% .
The second device, the Short Time protection, offers The device is supplied with an electronic actuator coil
A protection against short-circuits and is settable from that fits into a pocket in the breaker housing and is
2 to 13 (1) x the adjusted LT protection. then connected to the trip unit . Without mounted and
connected actuator coil the breaker will not function.
However, in order to verify a correct operation of the
B combination a simple test device is available to test the
assembly.
We strongly recommend the use of this test device.
C Adjustable rating plug
This easy-to-adjust trip unit is equipped with a LT Specifically designed for line protection with a
pre-alarm device made up of a LED indicator on the setting range of 0.625 to 1 x the plug rating over 16
D trip unit front face and an electronic contact . setpoints. The settings on the devices are in current
Before the breaker trip is initialized the LED will at first values and thus allow for ease of setting.
start to blink (at about 0.95 x Ir). When the current Each trip unit size can be
flowing through the breaker reaches about 1.05 x Ir equipped with one of two
E and a trip is imminent , the LED stops blinking, remains available adjustable rating
on and an electronic contact closes, this just before the plugs types. For 4 pole trip
circuit breaker trips and power is disconnected. This units the rating plugs exist
F electronic signal can be linked to an external LT in 3 and 4pole protected versions with a choice in
module that transforms the electronic signal into one neutral rating between 50 or 100% of the phase
that allows the operation of an external relay. value.
(The LT module is a modular DIN-rail device).
G Switchable rating plug
Allows for a choice of line or class 10 motor
All SMR 1 trip units have a built-in temperature sensor
protection(2). The device has two setting knobs: one
that trips the breaker at temperatures above 90°C. It
for the desired rating and band selection and one for
X thus prevents the breaker and electrical components in
its immediate vicinity from overheating.
the definite current setting.
The current setting is in multiples of the selected
rating and has a range of 0.4 to 1 x the trip unit size
Each SMR1 trip unit comes with a transparent , tamper-
over 32 setpoints. Each
free (sealable) cover, this to prevent unauthorized
trip unit size has one
manipulation of the breaker settings. In the FE frame
switchable rating plug. For
size they are supplied in a single housing including
4 pole trip units the rating
current sensors that can fully displace the alternative
plugs exist in 3 and 4 pole
electromechanical device while the FG type is supplied
protected versions with a choice in neutral rating
as an electronic pouch (current sensors supplied with
between 50 or 100% of the phase value.
the breaker).

(1) Some FG types have a smaller ST setting range.


(2) according to IEC EN 60947-4.1

B.10
Record Plus
FE160 and FE250 breakers
SMR1 types

Trip units are available in 10 different versions depending prevent incorrect combinations of electronic trip units and
on the frame rating and the network frequency. rating plugs. The 50/60Hz and 400Hz variants use the
FE 160 frame size 50/60 Hz 25, 63, 125 and 160A same rating plug. When NO rating plug is installed in the
FE250 frame size 50/60Hz 125, 160 and 250A breaker, all protective functions remain operational. This
400 cycle variants (available on request) at a reduced current rating. (15 -20 % of the chosen trip
FE160 - 125 and 160A, FE 250 - 250A unit rating).
The trip units must be equipped with a rating plug that For applications where a overload protection is NOT
establishes the rated current of the protective device and needed a version with disabled LT protection is available.
its setting. A colour code and a mechanical interlock

SMR1 - FE frame
FE 160 & FE 250 Breakers - Electronic Trip Unit Overview
FE frame Electronic trip unit overview
In* LT ST Neutral protection
pick-up band 1.05÷1.2 Ir pick-up band ± 20% Im
[A] Ir setting min [A] max [A] Im setting min [A] max [A] 4P4R 4P 3.5T 4P3R
16 10 16 20 208 =Ir
25 16 25 32 325 =Ir
40 0.625-1xIn 25 40 50 520 =Ir
63 16 steps 40 63 2-13xIr 79 819 =Ir =Ir/2
FE160 80 line 50 80 10 steps 101 1040 =Ir =Ir/2

not protected
SMR1 +
125 protection 80 125 160 1625 =Ir =Ir/2
adjustable N H L 100 63 100 126 1300 =Ir =Ir/2
rating plug
160 100 160 200 2080 =Ir =Ir/2
80 50 80 79 819 =Ir =Ir/2
125 0.625-1xIn 63 125 126 1625 =Ir =Ir/2
FE250 100 16 steps 80 100 2-13xIr 160 1300 =Ir =Ir/2
160 line 100 160 10 steps 200 2080 =Ir =Ir/2
160
250
protection 100
160
160
250
200
320
2080
3250
=Ir
=Ir
=Ir/2
=Ir/2
A
25 0.4-1xIn 10 25 20 325 =Ir

not protected
FE160 63 32 steps 25 63 2-13xIr 50 819 =Ir =Ir/2
SMR1 + N H L 125 line/mot. 50 125 10 steps 100 1625 =Ir =Ir/2
switchable
160
125
protection
0.4-1xIn 32
64
50
160
125
128
100
2080
1625
=Ir
=Ir
=Ir/2
=Ir/2
B
rating plug 2-13xIr
FE250 160 steps line/ n 64 o 160 10 steps 128 p 2080 =Ir =Ir/2
250 mot. prot. 100 250 200 3250 =Ir =Ir/2

* Colour code indicates which rating plug can be applied where On switching to Motor Protection a phase loss protection is initiated. C
Do not use for line protection.

n o p
Band timings 1.5 x Ir 7.2 x Ir 3 poli / 3 sganciatori
D
Line protection 65 - 95 sec 2.0 - 3.0 sec
Motor protection 200 - 300 sec 6.4 - 9.6 sec

E
How to set the device ST or Im setting
The defined rating plug defines the long time (LT) Is set in multiples of the LT current setting and has a
setting range and the manner of its adjustment . setting of 2 to 13 x this value with 10 setpoints. F
LT setting with adjustable rating plug Example
One knob with 16 positions allows the user a current A line protection device; required overload or LT setting
setting (Ir) between 0.625 and 1 times the chosen 120A, short-circuit or ST setting 8 x the G
rating. (values in A) LT setting.
SMR1 of 250A + switchable rating plug of 250A.
LT setting with switchable rating plug LT setting ..........knob 1 set to line and 160A
One knob to set the protection band (line class 5 or ........knob 2 set at 0.75 (0.75 x 160 = 120A)
X
motor class 10) and the rated current value ST setting..........knob 3 set a 8 x (= 8 x 120)
(2 current value settings of 0.625 and 1 x the trip unit SMR1 of 250A + adjustable rating plug of 160A.
rating) - in sketch trip unit rating 250A settings LT setting ..........knob 2 set at 120 (value on scale)
160A or 250A. ST setting..........knob 3 set at 8 x (= 8 x 120)
A second knob with 16 positions allows the user to set
the current (Ir in multipliers of chosen rating).
The combination of these two knobs allows a setting
range of 0.4 to 1 x the trip unit rating with
32 setpoints.

B.11
Record Plus
Time Current Curves
FE160 and FE250 breakers
SMR1 types

Breaker FE160 / SMR 1 / Sensor 25A Breaker FE160 / SMR 1 / Sensor 63A
10000 10000
120 120
100 6000 100 6000
80 Rating plug set at 1 x sensor rating 80 Rating plug set at 1 x sensor rating
60 4000 60 4000
50 (Ir=25A) 50 (Ir=63A)
40 40
30 2000 Motor protection mode. 30 2000 Motor protection mode.
20 Im set at 13 x Ir. 20 Im set at 13 x Ir.
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
(Ir= 25A). (Ir= 63A).
2 2
100 Line protection mode. 100 Line protection mode.
1 Im set at 6 x Ir. 1 Im set at 6 x Ir.
60 60
40 Rating plug set at
40 Rating plug set at
Class 10 Class 10
0.4 x sensor rating 0.4 x sensor rating
20 20
Trip units

Minutes

Minutes
Seconds

Seconds
(Ir=10A) (Ir=25A)
10 Line protection mode. 10 Line protection mode.
6 Im set at 13 x Ir. 6 Im set at 2 x Ir.
4 4

2 2

1 1
0,6 0,6
Trip Time

Trip Time
0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01

A 0,006
0,004
0,006
0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
B x Trip unit rating In x Trip unit rating In

C 10000
Breaker FE160 / SMR 1 / Sensor 125A
10000
Breaker FE160 / SMR 1 / Sensor 160A

120 120
100 6000 100 6000
80 Rating plug set at 1 x sensor rating 80 Rating plug set at 1 x sensor rating
60 4000 60 4000
50 (Ir=125A) 50 (Ir=160A)
40 40
2000 Motor protection mode. 2000 Motor protection mode.
D 30
20
1000
Im set at 13 x Ir.
30
20
1000
Im set at 13 x Ir.

10 600 10 600
8 8
6 400 6 400
5 5
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
E 2
100
(Ir= 125A).
Line protection mode.
Im set at 6 x Ir.
2
100
(Ir= 160A).
Line protection mode.
Im set at 6 x Ir.
1 60 1 60
40 Rating plug set at
40 Rating plug set at
Class 10 Class 10
0.4 x sensor rating 0.4 x sensor rating
20 20
Minutes

Minutes
Seconds

Seconds

F 10
(Ir=50A)
Line protection mode.
Im set at 2 x Ir.
10
(Ir=64A)
Line protection mode.
Im set at 2 x Ir.
6 6
4 4

2 2

G 1
0,6
1
0,6
Trip Time

Trip Time

0,4 0,4

0,2 0,2

X 0,1
0,06
0,1
0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006 0,006
0,004 0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In x Trip unit rating In

B.12
Record Plus
Time Current Curves

Breaker FE250 / SMR 1 / Sensor 125A Breaker FE250 / SMR 1 / Sensor 160A
10000 10000
120 120
100 6000 100 6000
80 Rating plug set at 1 x sensor rating 80 Rating plug set at 1 x sensor rating
60 4000 60 4000
50 (Ir=125A) 50 (Ir=160A)
40 40
30 2000 Motor protection mode. 30 2000 Motor protection mode.
20 Im set at 13 x Ir. 20 Im set at 13 x Ir.
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5

SMR1 - FE frame
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
(Ir= 125A). (Ir= 160A).
2 2
100 Line protection mode. 100 Line protection mode.
1 Im set at 6 x Ir. 1 Im set at 6 x Ir.
60 60
40 Rating plug set at
40 Rating plug set at
Class 10 Class 10
0.4 x sensor rating 0.4 x sensor rating
20 20
Minutes

Minutes
Seconds

Seconds
(Ir=50A) (Ir=64A)
10 Line protection mode. 10 Line protection mode.
6 Im set at 2 x Ir. 6 Im set at 2 x Ir.
4 4

2 2

1 1
0,6 0,6
Trip Time

Trip Time

0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In x Trip unit rating In B

10000
Breaker FE250 / SMR 1 / Sensor 250A
C
120
100 6000
80 Rating plug set at 1 x sensor rating
60 4000
50 (Ir=250A)
40
2000 Motor protection mode.
30
20
1000
Im set at 13 x Ir. D
10 600
8
6 400
5
4 Rating plug set at 1 x sensor rating
3 200
2
100
(Ir= 250A).
Line protection mode.
Im set at 6 x Ir.
E
1 60
40 Rating plug set at
Class 10
0.4 x sensor rating
20
Minutes
Seconds

10
(Ir=100A)
Line protection mode.
Im set at 2 x Ir.
F
6
4

1
0,6
G
Trip Time

0,4

0,2

0,1
0,06
X
0,04

0,02

0,01
0,006
0,004

0,002

0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In

B.13
Record Plus
Electronic Trip Units

FG400 and FG630 breakers


SMR1 types

Trip units are available in 6 different versions depending its setting. A colour code and a mechanical interlock
on the frame rating and the network frequency. prevent incorrect combinations of electronic trip units
FE400 frame size 50/60 Hz 250, 350 and 400A and rating plugs. The 50/60Hz and 400Hz variants use
FE630 frame size 50/60Hz 400, 500 and 630A the same rating plug.
400 cycle variants (available on request) For special applications a version with disabled LT or
FG400 - 400A, FG 630 - 630A overload protection is available complete with a specific
The trip units must be equipped with a rating plug that rating plug.
establishes the rated current of the protective device and
Trip units

Band timings 1.5 x Ir 7.2 x Ir


3 poli / 3 sganciatori

Line protection 65 - 95 sec 2.0 - 3.0 sec


Motor protection 200 - 300 sec 6.4 - 9.6 sec

How to set the device ST or Im setting


The rating plug defines the long time (LT) setting range Is set in multiples of the LT current setting and has a
and the manner of its adjustment . setting of 2 to 13x this values with 10 setpoints.
The ST setting is limited to 10x on the FG00 400A trip
LT setting with adjustable rating plug unit and FG630 630Amp trip unit .
A One knob with 16 positions allows the user a current
setting (Ir) between 0.625 and 1 times the chosen rating Example
(values in A) A line protection device; required overload or LT setting
B LT setting with switchable rating plug:
280A, short-circuit or ST setting 6 x the LT setting.
SMR1 of 400A +switchable rating plug of 400A.
One knob to set the protection band (line class 2.5 or LT setting .......knob 1 set to line and 315A
motor class 10) and the rated current value (2 current .......knob 2 set at 0.9 (0.9 x 315)
C value settings of 0.625 and 1 x the trip unit rating - in ST setting .......knob 3 set a 6 x (=6 x 280 )
sketch trip unit rating 400A settings 250A or 400A). SMR1 of 400A +adjustable rating plug of 315A.
A second knob with 16 positions allows the user to set LT setting .......knob 1 set at 280
the current (Ir in multipliers of chosen rating). ST setting .......knob 3 set a 6 x (=6 x 280)
D The combination of these two knobs allows a setting
range of 0.4 to 1 x the trip unit rating with 32 setpoints.

E
FG400 & FG630 Breakers - Electronic trip units type SMR1
FG frame Electronic trip unit overview
F In* LT
pick-up band 1.05÷1.2 Ir
ST
pick-up band ± 20% Im
Neutral protection

[A] Ir setting min [A] max [A] Im setting min [A] max [A] 4P4T 4P 3TN 4P3T
160 100 160 200 2080 =Ir =Ir/2
not protected

0.625-1
G SMR1 +
adjustable
FG400 250
250 xIn
160
160
250
250
2-13xIr
10 steps
320
320
3250
3250
=Ir
=Ir
=Ir/2
=Ir/2
N H L 400 16 steps 250 400 500 5200 =Ir =Ir/2
rating plug line prot.
FG630 400 250 400 500 5200 =Ir =Ir/2
630 400 630 2-10 Ir 800 6300 =Ir =Ir/2
X
protected

FG400 250 0.4-1xIn 100 250 200 3250 =Ir =Ir/2


SMR1 +
400A 32 steps 160 400 2-13 Ir 320 3250 =Ir =Ir/2
not

switchable N H L line/mot.
FG630 400 160 400 10 steps 320 5200 =Ir =Ir/2
rating plug prot.
500 250 500 500 6500 =Ir =Ir/2

* Colour code indicates which rating plug can be applied where

B.14
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SMR1 - FG frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.15
Record Plus
Time Current Curves
FG400 and FG630 breakers
SMR1 types

Breaker FG400 / SMR1 / Sensor 250A Breaker FG400 / SMR1 / Sensor 400A
10000 10000
120 120
100 6000 100 6000
80 80
60 4000 60 4000
50 50
40 40
30 2000 30 2000
20 20
1000 Rating plug set at 1 x sensor rating 1000 Rating plug set at 1 x sensor rating
10 600 (Ir= 250A). 10 600 (Ir= 400A).
8 8
6 400 Motor protection mode. 6 400 Motor protection mode.
5 5
4 Im set at 13 x Ir. 4 Im set at 13 x Ir.
3 200 3 200
2 2
100 Rating plug set at 1 x sensor rating 100 Rating plug set at 1 x sensor rating
1 60 (Ir= 400A). 1 60 (Ir= 400A).
40 Line protection mode. 40 Line protection mode.
Im set at 6 x Ir. Im set at 6 x Ir.
20 20
Trip units

Minutes
Minutes
Seconds

Seconds
Class 10 Class 10
10 Rating plug set at 0.4 x sensor 10 Rating plug set at 0.45 x sensor
rating (Ir=100A). rating (Ir=160A).
6 6
Line protection mode Line protection mode
4 Im set at 2 x Ir. 4 Im set at 2 x Ir.

2 2

1 1
0,6 0,6
Trip Time

Trip Time
0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01

A 0,006
0,004
0,006
0,004

0,002 0,002

0,001 0,001
0,1 3 4 5 6 7.28 10 0,1 3 4 5 6 7.28 10
B 0,5 1 2
x Sensor rating Is
20 30 40 60 100 0,5 1 2
x Sensor rating Is
20 30 40 60 100

C 10000
Breaker FG400 / SMR1 / Sensor 400A Mag Break

120
100 6000
80
60 4000
50
40
2000
D 30
20
1000 Thermal Withstand line of brreakker
10 600 allowing:
8
6 400 Class 10 & 20 max. 400A
5 Class 30 max. 320A
4
3 200
E 2
100
1 60
40

20
Seconds
Minutes

F 10 Im set at 2x
6
4

G 1
0,6
Im set at 13x
Trip Time

0,4

0,2

X 0,1
0,06
0,04

0,02

0,01
0,006
0,004

0,002

0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is

B.16
Record Plus
Time Current Curves

Breaker FG630 / SMR1 / Sensor 400A Breaker FG630 / SMR1 / Sensor 500A
10000 10000
120 120
100 6000 100 6000
80 80
60 4000 60 4000
50 50
40 Rating plug set at 1 x sensor rating 40 Rating plug set at 1 x sensor rating
30 2000 30 2000
(Ir=400A) (Ir=500A)
20 20
1000 Motor protection mode 1000 Motor protection mode
Im set at 13 x Ir Im set at 13 x Ir
10 600 10 600
8 8
6 400 6 400

SMR1 - FG frame
5 5
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
(Ir=400A) (Ir=500A)
2 2
100 Line protection mode 100 Line protection mode
1 Im set at 6 x Ir Im set at 6 x Ir
60 1 60
40 40

20 Class 10 20 Class 10
Minutes
Seconds

Minutes
Seconds
10 Rating plug set at 10 Rating plug set at
6 0,4 x sensor rating 6 0,5 x sensor rating
4 (Ir=160A) 4 (Ir=250A)
Line protection mode Line protection mode
2 Im set at 2 x Ir 2 Im set at 2 x Ir

1 1
0,6 0,6
Trip Time

Trip Time

0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 0,02

0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is B

10000
Breaker FG630 / SMR1 / Sensor 630A
10000
Breaker FG630 / SMR1 / Sensor 500A Mag break
C
120 120
100 6000 100 6000
80 80
60 4000 60 4000
50 50
40 Rating plug set at 1 x sensor rating 40
2000 2000
30
20
1000
(Ir=630A)
Motor protection mode
30
20
1000
Thermal Withstand line of breaker
D
Im set at 10 x Ir
10 600 10 600 allowing:
8 8
6 400 6 400 Class 10 & 20 max. 500A
5 5
4 Rating plug set at 1 x sensor rating 4 Class 30 max. 450A
3 200 3 200
2
100
(Ir=630A)
Line protection mode
Im set at 6 x Ir
2
100 E
1 60 1 60
40 40

20 Class 10 20
Minutes

Minutes
Seconds

Seconds

10 Rating plug set at 10


Im set at 2x
F
6 0,4 x sensor rating 6
4 (Ir=250A) 4
Line protection mode
2 Im set at 2 x Ir 2

1
0,6
1
0,6
Im set at 13x
G
Trip Time

Trip Time

0,4 0,4

0,2 0,2

0,1
0,06
0,1
0,06
X
0,04 0,04

0,02 0,02

0,01 0,01
0,006 0,006
0,004 0,004

0,002 0,002

0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is

B.17
Record Plus
Electronic Trip Units All SMR2 trip units have a built-in temperature sensor
that trips the breaker at temperatures above 90°C. It
thus prevents the breaker and electrical components
SMR2 range in its immediate vicinity from overheating. The SMR2 is
also equipped with a so called thermal memory
device. This memory tracks overheating even after the
device has tripped and prevents the breaker from being
The SMR2 is an electronic trip unit offering a fixed
switched whilst its environment is still at a too high
set of sophisticated protective functions that can
temperature.
be extended at will by the addition of seperately
available modules. Designed for use with the
Short-circuit Protection ST (short time)
FG400 and FG630 frame sizes the device has a
Offerering a selective protection against low value
fixed set of 3 protective functions allowing a
short-circuits the Short Time protection is settable from
selective and fully adjustable protection against
1.5 to 12(2) x the adjusted LT protection (Ir). The device
Overloads (LT) and short-circuits (ST and I).
can be set to five time setting bands (STD), this
Both the LT and ST protection can be set to
allowing selectivity between different breaker sizes.
different time settings or bands (LTD and STD)
The STD device can be set to an 'energy curve mode'.
whilst the ST device can be switched to a energy
This mode changes the fixed delay and reaction time
Trip units

protection mode (I2t).


value of the device, when the set current level is
The SMR2 uses rating plugs that give the user the
reached, into a reaction time that depends on the
flexibility to make a last minute choice in the
energy flowing in the circuit .
required current rating, protected poles or
protection band.
Short-circuit Protection I (instantaneous)
Offerering a protection against short-circuits the
Instantaneous protection is settable from 2 to 13(3) x
Overload protection LT (long time) the chosen sensor rating. The I device has no time
The Long Time or overload protection is adjustable delay band so that the breaker immediately trips when
from 0.4 (0.64(1)) to 1 x the chosen sensor ratings in the set threshold is reached.
16 (32(1)) steps. The user can also define one of 6 time
A bands (LTD) each designed to match specific loads, Each SMR2 trip unit comes with a transparent , tamper-
motor or cable characteristics. Of these 6 time band free (sealable) cover, this to prevent unauthorized
settings, 4 have time bands for line applications and manipulation of the breaker settings. They are supplied
2 are dedicated to motor protection (for time band as a simple to mount , plug-in electronic pouch (current
B classes see EN 60 947-4.1). When set to motor sensors supplied with the breaker). The device is
protection mode, a phase loss protection is initiated supplied with an actuator with flux shifter that fits into
that will trip the breaker when the difference in current a pocket in the breaker housing and is then connected
C between one phase current and the other phases to the trip unit . Without a mounted and connected
exceeds 80% for more than two seconds. actuator coil the breaker will not function. In order to
verify a correct operation of the combination a simple
device is available to test the assembly.
D We strongly recommend the use of this test device.

E Adjustable rating plug


An SMR2 rating plug has two setting knobs. The first
is used for the setting of the overload current device
(LT) and has a setting range of 0.625 to 1 x the
F chosen rating over 16 setpoints. The settings on the
devices are in current values thus avoiding the use
of complicated multipliers. The second knob is used
to set the time delay band of the overload protection
G This easy-to-adjust trip unit is equipped with a LT load (LTD) and has 6 possible time settings.
indicator device that operates by means of two LED
indicators located on the trip unit front face. If the load Each trip unit size can be
X reaches a 60% of the set Ir value, a green LED will start
to blink (3 flashes a second). When the load reaches
equipped with one of two
available adjustable rating
75% of Ir it will stop blinking and remain on. The plug types.
second orange LED will start to blink at 95% of the Ir There is a version of the trip
value. It will remain on when the load reaches 105% of unit without rating plug and one in which the two
Ir and a trip is imminent . rating plug types are included. For 4pole trip units
the rating plugs exist in 3 and 4pole protected
versions with a choice in neutral rating between 50
or 100% of the phase value.
(1) '(1) Normaly supplied with two rating plugs, each with a setting range of 0.64-1.
(2) Some types limited to 10 x
(3) Some types limited to 11 x

B.18
Record Plus
FG400 and FG630 breakers
SMR2 types

Each SMR 2 device has three plug in elements of which at battery module also enhances the functionality of the Trip
least two are needed to allow the device to work properly. Reason Indicator Module.
1) A rating plug is plugged into the jack at the top left of the 3) An Extension module providing extra functionality
device. Without rating plug the SMR2 device will not provide and/or features. A standard SMR2 is supplied with a blank
any circuit protection and the breaker will trip immediatley. non function module.
2) A battery module (supplied with trip unit) needs to placed A 24V DC auxiliary supply can be connected to the trip unit
in the appropiate module this to power the thermal memo- via the contact module . This enabling all modules to be
ry within the trip unit when the breaker has tripped. If not used to their full capacity and allowing the use of the ZSI

SMR2 - FG frame
installed the thermal memory function is disabled. The function (if installed in the trip unit).

FG400 & FG 630 Breakers - Electronic trip units type SMR2


FG frame Electronic trip unit overview
In LT ST I Neutral protection
pick-up band 1.05÷1.2 Ir pick-up band ± 20% Ist pick-up band ± 10% In
[A] Ir setting min [A] max [A] Ist setting min [A] max [A] Im setting min [A] max [A] 4P4T 4P 3TN 4P3T
160 100 160 p 150 1920 r 500 3250 =Ir =Ir/2
250 160 250 1.5-12 Ir 240 3000 2-13 Is =Ir =Ir/2
FG400 250 160 250 10 steps 240 3000 10 steps 700 4550 =Ir =Ir/2

not protected
0.4-1 In
350 250 350 500 3500 =Ir =Ir/2
SMR2 + 32 steps
400 250 400 1.5-10 Ir 375 4000 2-11 Is 750 4400 =Ir =Ir/2
adjustable N H L utlising
10 steps 10 steps
rating plug two rating
400 250 400 1.5-12 Ir 375 4800 2-13 Is 1000 6500 =Ir =Ir/2
plugs
FG630 500 400 500 10 steps 600 6000 10 steps =Ir =Ir/2
630 400 630 1.5-10 Ir 600 6300 2-11 Is 1260 6930 =Ir =Ir/2
n 10 steps 10 steps A
LTD, Line no phase loss STD Standard
Setting(1) min max Setting min max
[sec.] [sec.] [msec.] [msec.]
1.25
2.5
1
1.5
1.5
3
0.04
0.12
0.036
0.108
0.07
0.16
B
5 3 5 0.21 0.190 0.26
10 6 o 10 0.31 0.280 0.37
LTD, Motor with phase 0.42 0.380 q 0.49

20
loss protection(1)
10 14
2
-OR- I T
(see trip curves)
C
30 14 o 20

(1) Timing applies at 7.2 x the set current value. (I.)


D

SMR2 front view E


Indicating the location of the 3 poli / 3 sganciatori Modulo SMR2

settings, the battery, rating plug and o


extension modules. The in/out put n
terminals are located within the trip Batteria
F
unit pouch just below the battery
modules and can be accessed by
removing a break away cover. p
q
G
r

B.19
Record Plus
FG400 and FG630 breakers
SMR2 types (continued)

Modules
Ground fault Protection
Each SMR2 device can be equipped with two plug-in
Ground fault alarm
elements, a rating plug and an extension module. The
Load shedding across two channels
extension modules are simple plug-in devices that allow
Trip Reason indicators
the user to enhance the SMR2 as a protective device or
Communication (modbus RTu)
to add in extra functional features. There is a single
Each module has a low level electronic output that can
function module available with Ammeter and a range of
be channeled through the communication bus (when
functional modules each adding two functions to the
present) or in some cases trigger a 1A/250 Volt change-
device. this allows an SMR 2 to be equipped with:
over contact placed in an external contact module
containing four contacts (type FAECM2).
Trip units

Ground fault protection


Designed for protection against indirect contact , the channels, both adjustable from 0.55 to 1 x the set LT
ground fault device measures the vectorial sum of the protection value (Ir).
three phase currents and, if present , that of the neutral Each channel is equiipped with a time delay directly
conductor. If the sum of these values exceeds the set proportional to that of the LTD setting. Chanel 1 is set
current thresholds for a period of time greater than the to a time delay equal to LTD/2 and channel two is set
set time delay, the breaker is tripped. to a time delay of LTD/4. If the current drops below the
The Ground Fault protection option is adjustable from set thresholds the signal is reset . The reset signal being
0.2 to 1 x the chosen sensor ratings in 9 steps. The user given in a time proportional with the chosen LTD curve.
can also define one of 5 delay time bands (GFD) A signal due to a load shedding event can be
designed to allow selectivity between different sensor channeled through the communication output (when
A ratings. present) or be wired out to the contact module.
The GFD device can be set to an 'energy curve mode'. (type ECM)
This mode changes the fixed delay and reaction time
B value of the device, when the set current level is Trip Reason Indicators
reached, into a reaction time that depends on the In order to indicate the reason of a breaker trip a set of
energy flowing in the circuit . tptal of three LED's are provided on the trip unit front
A breaker trip due to a ground fault event can be face. One indicating a trip due to the LT device, one
C channeled through the communication output indicating a trip due to the ST device and one for the
(when present) or be wired out to the contact module. I device.
(type ECM) Without auxilliary power, the use of the trip reason
button is necessary to light up the appropiate LED.
D With auxilliary power the use of the trip reason push
Ground fault alarm
The Ground Fault Alarm option offers the same button is unnecessary.
functionality as the Ground Fault protection, here The three trip signals can be channeled through the
E however ONLY an alarm signal is given and the breaker communication output (when present) or be wired out
is NOT TRIPPED. It is adjustable from 0.2 to 0.8 x the as an overload (LT) or short circuit signal (ST & I) to the
chosen sensor ratings in 12 steps. The user can also contact module (type FAECM)
define one of 5 delay time bands (GFD).
F The GFD device can be set to an 'energy curve mode'. Communication
This changes the fixed delay and reaction time value of When the communication option is added to the SMR2
the device, when the set current level is reached, into a trip unit the following data can be viewed:
G reaction time that depends on the energy flowing in - The position of the switches on all installed devices,
the circuit . thus providing the settings of the breaker.
- Signals indicating on which of the installed protection
A 100mA/240Volt NC contact is included in the module devices the breaker has tripped.
X and can wired out through the 12 pole breaker - Load shedding orders.
connector plug on the breaker. - Zone selective interlock occurrences.
For each breaker with Modbus rtu the use of a internal
Load shedding device communication module AND and external contact
The Load Shedding device (R) is designed to allow the module type FAECM2 (see page b.28) is required.
user to switch off non priority loads before the LT A 24V DC auxiliary supply is needed that supplies the
function trips the breaker due to an overload. It system through the external contact module.
measures the current within the circuit and provides a
signal if the current measured in the three phases
exceeds the set current values. The device has two

B.20
Record Plus
Zone Selective Interlock The ZSI option requires a 24VDC auxiliary supply.
A device that allows the user to achieve selectivity One FAECM2 module connected with one of the
combined with the fastest possible fault reaction time. breakers in the ZSI loop can be used. The FAECM2
When the ZSI is active the SMR2 trip unit will always needs then connected to an auxiliary supply of
trip the breaker as quickly as possible, ignoring the 24V DC.
time delays set by means of the STD or GFD devices. When the breaker is equipped with a "COM" option
However, when a ZSI signal is received from a down- the ZSI status signal is also available on the
stream breaker equipped with an SMR2, the STD or communication output .
GFD of the upstream SMR2 device revert to wherever
the adjustment is set . Ammeter
Provides the user with thecurrent running in one of the
With standard cables the distance between breakers is breaker phases. The device has an accuracy of 10%
a maximum of 30 meters. The use of shielded cables and normally indicates the current in the highest

SMR2 - FG frame
allows the distance between breakers to be increased loaded phase. Use of the push buttons on the module
to 1 km. A maximum of five SMR2 trip units can be front t allows the user to select an indiaction of the
linked in this manner. current in one of the other phases or neutral (if
present). After a set delay of 10 seconds the device
reverts to its standard indication setting.

Each SMR 2 device has three plug in elements of


which two are needed to allow the device to work
properly. A rating plug is needed and is plugged into
the jack at the top left of the device. Without rating
plug the SMR2 device will not provide any circuit Module FAMGAT2
Module FAMGFT2
protection and the breaker will trip immediatley. A combination of the Ground Fault
AAcombination
battery needsof to
theplaced
Ground Fault
in the protectionmodule,
appropiate and the Alarm function and the Trip Reason
Trip Reason Indicators.
this to power the thermal memory within the trip unit , Indicators.
if not installed this function will be disabled.
A
Module FAMGFT2 Module FAMGAM2
A combination of the Ground Fault A combination of the Ground Fault
protection and the Trip Reason indi- alarm function and the B
cators. communication option.

C
Module FAMGFM2 Module FAMGAS2
A combination of the Ground Fault A combination of the Ground Fault
protection and the communication alarm option and the load shedding D
option. device.

E
Module FAMGFS2 Module FAMSM2
A combination of the Ground Fault A combination of the load shedding
protection and the load shedding
device.
device and the communication F
option.

G
Module FAMAM2 Module FAMST2
An Ammeter. A combination of the load shedding
device and the Trip Reason
Indicators.
X

Module FAMB2 Module FAMMT2


Spare filler module. A combination of the comunication
option and the Trip Reason
Indicators.

B.21
Record Plus
Time Current Curves
FG400 and FG630 breakers
SMR2 types
Breaker FG400 / SMR2 / Sensor (trip unit) In=350A
Breaker FG400 / SMR2 / Sensor (trip unit) In=250A
Breaker FG630 / SMR2 / Sensor (trip unit) In=500A
10000 10000
120 120 Highest curve
100 6000 Highest curve 100 6000
80 80 Rating plug set at 1 x sensor rating
60 4000 Rating plug set at 1 x sensor rating (Ir= 250A). 60 4000
50 50 (Ir= 350 or 500A).
40 LTD set at class 30 40
30 2000 30 2000 LTD set at class 30
Ist set at 12 x Ir.
20 20 Ist set at 12 x Ir.
1000 STD set at 420 milliseconds 1000 STD set at 420 milliseconds
Iinst set at 13 x sensor rating
10 600 10 600 Iinst set at 13 x sensor rating
8 8
6 400 6 400
5 Rating plug set at 1 x sensor 5 Rating plug set at 1 x sensor
4 4
200 rating (Ir=250A) 200 rating (Ir=350 or 500A)
3 3
Other LTD classes Other LTD classes
2 2
100 Class 20 (partial curve) 100
Class 20 (partial curve)
1 60 Class 10 (partial curve) 1 60 Class 10 (partial curve)
40 Class 5 (partial curve) 40 Class 5 (partial curve)
Class 2.5 (partial curve) Rating plug set at Class 2.5 (partial curve)
Rating plug set at
20 Class 1.25 20 1 x sensor rating
Trip units

Minutes
Seconds

Minutes
Seconds
1 x sensor rating Class 1.25
(Ir=250A) (Ir=350 or 500A)
10 10
STD bands STD bands
6 6 420 Milliseconds
420 Milliseconds
4 4 310 Nilliseconds
310 Nilliseconds
210 Milliseconds 210 Milliseconds
2 2
120 Miliseconds 120 Miliseconds
1 40 Milliseconds 1 40 Milliseconds
0,6 0,6
Trip Time

Trip Time
0,4 0,4

0,2 0,2

0,1 0,1
0,06 0,06
0,04 0,04

0,02 Lowest curve 0,02 Lowest curve


Rating plug set at 0.4 x Rating plug set at 0.46 x
0,01 0,01
sensor rating (Ir= 100A). sensor rating (Ir= 160 or 250A).
A 0,006
0,004
LTD set at class 1.25
Ist set at 1.5 x Ir.
0,006
0,004
LTD set at class 1.25
Ist set at 1.5 x Ir.
STD set at 40 millisecond STD set at 40 millisecond
0,002 0,002
Iinst set at 2 x sensor rating Iinst set at 2 x sensor rating
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
B x Sensor rating Is x Sensor rating Is

Breaker FG400 / SMR2 / Sensor (trip unit) In=400A


C 10000
Breaker FG630 / SMR2 / Sensor (trip unit) In=630A
10000
Breaker FG630 / SMR2 / Sensor (trip unit) In=400A

120 120 Highest curve


100 6000 Highest curve 100 6000
80 80 Rating plug set at 1 x sensor rating
60 4000 Rating plug set at 1 x sensor rating 60 4000
50 50 (Ir= 400A).
40
(Ir= 400 or 630A). 40
2000 2000 LTD set at class 30
D 30
20
1000
LTD set at class 20
Ist set at 10 x Ir.
STD set at 420 milliseconds
30
20
1000
Ist set at 12 x Ir.
STD set at 420 milliseconds
10 600 Iinst set at 11 x sensor rating
10 600 Iinst set at 13 x sensor rating
8 8
6 400 6 400
5 5
4 4 Rating plug set at 1 x sensor
3 200 Rating plug set at 1 x sensor 3 200
E 2
100 rating (Ir=400 or 630A)
Other LTD classes
2
100
rating (Ir=400A)
Other LTD classes
Class 20 (partial curve)
1 60 1 60
Class 10 (partial curve) Class 10 (partial curve)
40 Class 5 (partial curve) 40
Class 5 (partial curve)
Rating plug set at Rating plug set at
Class 2.5 (partial curve) Class 2.5 (partial curve)
20 1 x sensor rating 20 1 x sensor rating
Minutes
Seconds

Minutes
Seconds

F 10
(Ir=400 or 630A)
STD bands
Class 1.25
10 (Ir=400A)
STD bands
Class 1.25

6 420 Milliseconds 6 420 Milliseconds


4 310 Nilliseconds 4 310 Nilliseconds
210 Milliseconds 210 Milliseconds
2 2
120 Miliseconds 120 Miliseconds

G 1
0,6
40 Milliseconds 1
0,6
40 Milliseconds
Trip Time

Trip Time

0,4 0,4

0,2 0,2

X 0,1
0,06
0,1
0,06
0,04 0,04

0,02 Lowest curve


0,02 Lowest curve
Rating plug set at 0.4 x Rating plug set at 0.4 x
0,01 0,01
sensor rating (Ir= 160 or 250A). sensor rating (Ir= 160A).
0,006 0,006
LTD set at class 1.25 LTD set at class 1.25
0,004 0,004
Ist set at 1.5 x Ir. Ist set at 1.5 x Ir.
0,002 STD set at 40 millisecond 0,002 STD set at 40 millisecond
Iinst set at 2 x sensor rating Iinst set at 2 x sensor rating
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is

B.22
Record Plus
Time Current Curves

Breaker FG400 / SMR2 / Trip Unit In=400A I2T on Breaker FG400 and FG630 Ground Fault
2
100 10
9 GF current value Adjustable
1 60 ST set at 1.5x 8 0.2 to 1 x sensor rating
I set at 12x 7 Lowest band - Green
40 STD set at 420ms
6 GF = 0.2 x Ir GFD = 40 milisec.
I2t ON I2t OFF = continuous line
5 I2t ON band = dotted line
20 STD bands set at:
420ms, 310ms, 4

SMR2 - FG frame
210ms, 120ms
10 or 40ms
I2t = ON 3

4 2

Seconds
Minutes
Seconds

1 1
0,9
0,6 0,8
0,7
0,4
Trip Time

0,6
Trip Time

0,5
0,2
ST set at 10x
0,4
I set at 12x
0,1 STD set at 40ms 0,3
I2t ON
0,06

0,04 0,2

Partial depiction of other GFD bands


set at: 120, 210 OR 310 milisec.
A
0,02
I2t 'OFF'

0,01 0,1
5 6 7,2
1 2 3 4 10
x Sensor rating Is
20 30 40 50 60 100 0,1 0,2 0,4 0,6 0,8 1
x Sensor rating Is
2 3 4 5 6 7 8 10
B

1000
Breaker FG / SMR2 / Load shedding module R channel 1
1000
Breaker FG / SMR2 / Load shedding module R channel 2
C
R channel band R channel band
10 600 Channel 1 - Set at 1 x Ir 10 600 Channel 2 - Set at 0.6 x Ir
8 Bands with LTD set to 8 Bands with LTD set to
Class 30 Class 30
6
5
4
400
Class 20
Class 10
6
5
4
400
Class 20
Class 10
D
200 Class 5 200 Class 5
3 3
Class 2.5 Class 2.5
2 Class 1.25 2 Class 1.25

1
100

1
100
E
60 60

40 40

60 60 F
Minutes
Seconds

Minutes
Seconds

10 10

4
6

4
G
Trip Time

Trip Time

2 2

X
1 1
ST set at 10x ST set at 10x
STD set at 410ms STD set at 320ms
0,6 0,6

0,4 0,4

0,2 0,2

0,1 0,1
0,1 0,2 0,4 0,6 1 2 3 4 6 10 20 30 40 60 100 0,1 0,2 0,4 0,6 1 2 3 4 6 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is

B.23
Record Plus
Electronic trip units

FK frame

SMR1 range
This easy-to-use trip unit with overload and selective
SMR1e, s and g types are designed to allow the user to
short-circuit protection is equippeed with an overload
conveniently tailor his protection to meet individual
signalling option and has a built-in temperature sensor
circuit requirements. The available options include
to prevent the breaker and electrical components in its
adjustable overload pickup values, overload trip time
immediate vicinity from overheating. The 4 pole units are
characteristics, short time pickup circuit values, short
equipped with a switchable neutral protection option,
time delay circuit trip times and energy values. The trip
allowing the user to set the neutral at 0, 50 or 100% of
unit can be equipped with a ground-fault protection and
the phase ratings.
provides a flexible solution to all protection scenarios.

Overload protection LT (long time) sum of these values exceeds the set current thresholds for a
Trip units

The Long Time or overload protection is adjustable from 0.4 period of time greater than the set time delay, the breaker
to 1 x the chosed sensor ratings in 8 steps. The SMR1e has is tripped.
a fixed time band of 5seconds at 7.2 x Ir whilst the SMR1s The Ground Fault protection option is adjustable from
and g variants have a choice of 5 time bands (LTD) each 0.1 to 1 x the chosed sensor ratings in 4 steps. The user can
designed to match specific load characteristics. (For time also define one of 4 delay time bands (GFD) designed to
band classes see EN 60 947-4.1). allow selectivity between different sensor ratings. The
All devices are equipped with three LED's for signalling groundfault device is available in the SMR1g trip unit type.
purposes.
A green LED that indicates that the trip unit is powered up Short-circuit Protection I (instantaneous)
and is measuring and operating correctly. (30% of chosen Offerering a protection against short-circuits the
sensor rating). Instantaneous protection is set at a fixed value depending
A A yellow LED that will astart to blink at 95% of the set Ir on the chosen frame/ contact size. The I device has no time
current (3 flashes a second) when the current level reaches delay band so that the breaker trips as immediatley when
105% of the Ir setting and a trip is imminent the LED will the set threshold is reached. The fixed instanatneous (I) is
light up constantly. set at a current value allows discrimination between
B An over temperature in the trip unit is clearly indicated on different frame sizes and at a level that limits the current
the breaker front face. On the SMR1s and G variants a over and thermal stress in the protected circuit
temperature will trip the breaker.
C Zone Selective Interlock
A device that allows the user to achieve selectivity
combined with the fastesrt possible fault reaction time. With
connected ZSI the SMR1s and SMR1g trip unit will always
D trip the breaker as quickly as possible, ignoring the time
delays set by means of the STD or GFD devices. However
when a ZSI signal is recieved from a downstream breaker
E Short-circuit Protection ST (short time)
equipped with an SMR1a, 1g and 2 the STD or GFD of the
upstream device reverts to wherever the adjustment is set.
Offerering a selective protection against low value short- The Ground Fault and Short Time Zone Selective Interlock
circuits the Short Time protection is settable from 1.5 to 10 x signals are shared on one in/out put .
F the adjusted LT protection (Ir). The device only works when auxiliary power is present and
The SMR1e has a fixed time band of 50 milliseconds, a operates up to a distance between breakers of 1 kilometer.
setting that provides discrimination with downstream FG The use of shielded cable is required. A maximum of five
devices. SMR 1s, g or SMR2 trip units can be linked in this manner.
G Tthe SMR1s and g variants have a choice of four time (not available in the SMR1e)
setting bands (STD), designed to allow selectivity between
different breaker sizes. Here the STD device can be set to an
X 'energy curve mode' that changes the reaction of the device
from a fixed delay and reaction time value when the set
current level is reached to a reaction time that depends on
the energy flowing in the circuit.

Ground fault protection


Designed for protection against indirect contact the ground
fault device measures the vectorial sum of the three phase
currents and, if present, that of the neutral conductor. If the

B.24
Record Plus
Use and Testing Connection of trip unit
Each SMR1e, s or g trip unit comes with a transparent, Each SMR1 s or
tamper-free (sealable) cover, this to prevent unauthorized g trip unit has a
manipulation of the breaker settings. The device is connector
supplied with an electronic actuator coil that fits into a located on the
pocket in the breaker housing and is then connected to the right side of the breaker. This connector is normally hidden
trip unit. In order to verify a correct operation of the behind a break-away cover and is required to connect the
combination a simple test device is available to test the following:
assembly. Auxiliary power supply (24V DC), ZSI in and out,
We strongly recommend the use of this test device. long time pre-alarm signal, connection of external CT for
4 pole groundfault on three pole breakers.

FK800, FK1250 and FK1600 breakers - Electronic trip unit overview

SMR1 - FK frame
FK frame Electronic trip unit overview
In LT ST Neutral protection
pick-up band 1.05÷1.3 Ir pick-up band ± 20% Im Switchable type
[A] Ir setting min [A] max [A] Im settingmin [A] max [A] 4P4T 4P 3TN 4P3T

protected
FK800 800 320 800 480 8000 =Ir =Ir/2
SMR 1e N H L FK1250 1000 0.4 x1 In 400 1000 1.5-10 Ir 600 6000 =Ir =Ir/2

not
1250 in 8 steps 500 1250 in 8 steps 750 12500 =Ir =Ir/2
FK1600 1600 640 1600 960 16000 =Ir =Ir/2
In LT ST Neutral protection
pick-up band 1.05÷1.3 Ir pick-up band ± 20% Im Switchable type
[A] Ir setting min [A] max [A] Im settingmin [A] max [A] 4P4T 4P 3TN 4P3T

protected
FK800 800 320 800 480 8000 =Ir =Ir/2
FK1250 1000 0.4 x1 In 400 1000 1.5-10 Ir 600 6000 =Ir =Ir/2

not
1250 in 8 steps 500 1250 in 8 steps 750 12500 =Ir =Ir/2
FK1600 1600 640 1600 960 16000 =Ir =Ir/2
SMR 1s N H LTD(1) STD(2)
Setting min max Setting min max
[sec.] [sec.] [msec.] [msec.]
10
20
8
16
12
24
0.1
0.2
0.095
0.175
0.17
0.29
A
30 24 36 0.3 0.255 0.41
In LT ST Neutral protection
pick-up band 1.05÷1.3 Ir pick-up band ± 20% Im Switchable type
[A] Ir setting min [A] max [A] Im settingmin [A] max [A] 4P4T 4P 3TN 4P3T B

protected
FK800 800 320 800 480 8000 =Ir =Ir/2
FK1250 1000 0.4 x1 In 400 1000 1.5-10 Ir 600 6000 =Ir =Ir/2

not
1250 in 8 steps 500 1250 in 8 steps 750 12500 =Ir =Ir/2
n p
FK1600 1600 640
LTD(1)
1600 960
STD(2)
16000 =Ir =Ir/2
C
Setting min max Setting min max
[sec.] [sec.] [msec.] [msec.]
SMR 1g * N H 5 4 6 0 0.015 0.05
10
o 8 12 0.1
q 0.095 0.17 D
20 16 24 0.2 0.175 0.29
30 24 36 0.3 0.255 0.41
GF GFD(2)
pick-up band ± 20% Im
Ig settingmin [sec.] max [sec.]
Setting min
[msec.]
max
[msec.] E
r 80 1000 0.1 0.095 0.17
0.1 x1 In 100 1250 0.2 0.175 s 0.29
in 4 steps 128 1600 0.3 0.255 0.41
F
(1) At 7.2 x Ir : Min. is minimum settable delay: Max: Is maximum total tripping time.
(2) At set value : Min. is minimum settable delay: Max: Is maximum total tripping time.

Trip units are available in 4 ratings


G
and 3 different versions depending
on the frame rating and the chosen n p r
functionality. X
FK800 frame size
800A, SMR 1e, s or g
FK1250 frame size o q s
1000 and 1250A,SMR 1e, s or g
FK1600 frame size
1600A,SMR 1e, s or g
Classi
The trip units are an integral part of
the breaker and are NON inter-
changeable.

B.25
Record Plus
Time Current Curves
FK frame

Breaker FK800 / SMR1e 800A Breaker FK800 / SMR1s 800A


Breaker FK1600 / SMR1e 1600A Breaker FK1600 / SMR1s 1600A
10000 10000
120 120
100 6000 100 6000 LT set at 1
80 80
60 4000 Set at 1 x sensor rating 60 4000 Ir=800 or 1600A
50 50 LTD set at:
40 Ir=800A or 1600A 40
30 2000 30 2000 Class 30
Ist set a 10 x Ir
20 20 Class 20
1000 1000
Class 10
10 600 10 600 Class 5
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60 LT set at 0,4 x s-rating
40 Set at 0.4 x sensor rating 40 Ir=320A or 640A
Ir=320A or 640A Set at 1 x sensor rating ST set a 1.5 x Ir
20 Ist set a 1.5 x Ir Ir=800A or 1600A 20 STD set at class 5
Trip units

Minutes
Seconds

Minutes
Seconds
10 Ist set a 6 x Ir 10
6 6
4 4

2 2
ST set at 10x
1 1 STD set at 300ms
0,6 0,6 I2T OFF
Trip Time

Trip Time
0,4 0,4

0,2 0,2
ST set at 1.5x
1,5x
0,1 0,1 STD set at 30ms
I2T =OFF
OFF
0,06 0,06
0,04 0,04

0,02 0,02 STD bands set at:


300ms, 200ms,
0,01 0,01 100ms or 0ms

A 0,006
0,004
0,006
0,004
I2T = ON STD bands set at:
300ms, 200ms,
100ms or 0ms
0,002 0,002
I2T = OFF
0,001 0,001
0,1 0,5 1 2 3 4 5 6 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.2 10 20 30 40 60 100
B x Sensor rating Is (800A or 1600A) x Sensor rating Is (800A or 1600A)

C 10000
Breaker FK1250 / SMR1e 1000 and 1250A
10000
Breaker FK1250 / SMR1s 1000 and 1250A

120 120
100 6000 100 6000 LT set at 1
80 80
60 4000 Set at 1 x sensor rating 60 4000 Ir=1000 or 1250A
50 50 LTD set at:
40 Ir=1000A or 1250A 40
2000 2000
D 30
20
1000
Ist set a 10 x Ir
30
20
1000
Class 30
Class 20
Class 10
10 600 10 600 Class 5
8 8
6 400 6 400
5 5
4 4
3 200 3 200
E 2
100
2
100
1 60 1 60 LT set at 0,4 x s-rating
40 Set at 0.4 x sensor rating 40 Ir=400A or 500A
Ir=400A or 500A Set at 1 x sensor rating ST set a 1.5 x Ir
20 20 STD set at class 5
Minutes
Seconds

Minutes
Seconds

Ist set a 1.5 x Ir Ir=1000A or 1250A


F 10 Ist set a 6 x Ir 10
6 6
4 4

2 2 ST set at 10x

G 1
0,6
1
0,6
STD set at 300ms
I2T OFF
Trip Time

Trip Time

0,4 0,4
ST set at 1.5x
0,2 0,2 STD set at 30ms
I2T OFF
X 0,1
0,06 1250A type
0,1
0,06 1250A type
0,04 0,04
1000A type 1000A type
0,02 0,02 STD bands set at:
300ms, 200ms,
0,01 0,01 100ms or 0ms
0,006 0,006 I2T = ON STD bands set at:
0,004 0,004 300ms, 200ms,
100ms or 0ms
0,002 0,002
I2T = OFF
0,001 0,001
0,1 0,5 1 2 3 4 5 6 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.2 10 20 30 40 60 100
x Sensor rating Is (1000A or 1250A) x Sensor rating Is (1000A or 1250A)

B.26
Record Plus
Time Current Curves

Breaker FK800 / LTM 630 and 800A


Breaker FK800, FK1250 and FK1600 Ground Fault
Breaker FK1600 / LTM 1000 and 1250A
10 10000
9 GF current value
120
100 6000
8 80
Adjustable from 60 4000 Set at 0.8 x In Set at 1 x In
7 0.2 to 1 x sensor rating 50 Ir=500A or 640A Ir=630A or 800A
40
6 LT setting Ir: 30 2000 Ir=800A or 1000A Ir=1000A or 1250A
500ms 20
5 1000
1000ms
10 600
8
4 6 400
GFD bands set at: 5

SMR1 - FK frame
4
100ms 3 200
3 200ms 2
500ms 100
1000ms 1 60
2 40
Seconds

20

Minutes
Seconds
10
6 Set at 5 x In
4
1
0,9 2
0,8
0,7 1
0,6 Set at 10 x In
Trip Time

0,6
Trip Time

0,4
0,5
0,2
0,4 0,1
0,06
0,3 0,04

0,02

0,2 0,01
0,006
0,004 A
0,002

0,001
0,1
0,1 0,5 1 2 3 4 5 6 10 20 30 40 60 100
0,1 0,2 0,4 0,6 0,8 1
x Set LT current Ir
2 3 4 5 6 7 8 10
x Nominal Current In B

Breaker FK800 / Mag Break 800A

10000
Breaker FK1250 / Mag Break 1250A C
120
100 6000
80
60 4000
50
40
2000
30
20
1000
Thermal Withstand of Breaker:
FK800: max in Class 10 & 30: 800A D
FK1250: max in Class 10 & 30: 1250A
10 600
8
6 400
5
4
3 200
2
100 E
1 60
40

20
Minutes
Seconds

10 F
6
Set at 5 x In
4

2 Set at 10 x In

1
0,6
G
Trip Time

0,4

0,2

0,1
0,06
X
0,04

0,02

0,01
0,006
0,004

0,002

0,001
0,1 0,5 1 2 3 4 5 6 7.2 10 20 30 40 60 100
x Nominal Current In

B.27
Record Plus
Electronic Trip Units

Accessories for SMR1 and SMR2


types

Long time module SMR1 (FAMLT)(1) Communication & contact module SMR2 (FAMECM)
This external DIN-rail This external DIN-rail
mounted device with mounted device with
modular dimensions is modular dimensions is
directly connected to the directly connected to the
SMR1electronic trip unit . SMR2 electronic trip unit .
The device is equipped with It is a multi functional unit
a NC 1A/400V AC contact acting as an interface
that opens to a signal between the breaker and
which indicates that a LT the communication network.
Trip units

trip will shortly be initiated To use the communication option the FAMECM module
by the SMR1. requires an auxiliary supply of 24V DC.
The SMR1 emits this before
a trip action is initiated. When set to motor protection The device is also equipped with four NC 1A/400V AC
this occurs 0.5 seconds before the tripping event and contacts that can provide the following outputs:
at 0.05 seconds when set to line protection. Contact is - Breaker trip reason
reset when breaker trips. (Overload (LT) OR Short Circuit (ST/I )
- Load shedding device contacts.
Test kit SMR1 & SMR2 (FAT) and SMR1e,s,g (FNT) Channel 1 AND Channel 2
Designed to test the
actuator trip unit
combinations the
A device is plugged
into the test jack on
the trip unit front
B face. Just remove
the test jack cover,
insert and plug in
the test device.
C Releasing the push
button on the tester FAT front should now initiate a trip
event . The tester requires a 9V battery and is also
equipped with a battery status indicator.
D FNT initiates a trip event when the push buttom is
depressed more than two seconds. It requires an
external 9V supply.
E
Rating plug tool SMR1 & SMR 2 (FAR)
A rating plug can be
removed by using two small
F screwdrivers.
In case of repeated removal
the Record PlusTM rating
G plug removal tool is advised
to enhance the ease and
safety of this operation.

X
(1) Use of an RC suppressor is recommended.
(See Controls and Automation catalogue)

B.28
Record Plus
Trip units

Overview of available types

LTM - Line thermal magnetic MO - Magnetic Only


This trip unit offers This trip unit offers
overload and short- short-circuit protection
circuit protection. only, the device is
The overload protection adjustable from 10 to
is adjustable from 0.8 to 15 x the chosen rating.
1 x the chosen rating In order to prevent the
whilst the short-circuit protection device
protection is set at 10 x (Circuit Breaker) from
the chosen rating (FD overheating, the current
frame) or adjustable of the circuit that it
from 5 to 10 x the protects, needs to be

Trip units
chosen rating (FE and FK frame). limited. (see dotted line)
The unit is designed to protect the lines and/of loads The unit is primarily designed to be used with thermal
present in standard circuits. relays in motor protection circuits.

LTMD - Line thermal magnetic, selective type SMR1 (e)- Selective Electronic Protection(2)
This trip unit offers A trip unit designed to
overload and short- offer a overload (LT) and
circuit protection. short-circuit protection
The overload protection (ST). The overload
is adjustable from 0.8 to protection is adjustable
1 x the chosen rating from 0.4 to 1 x the
whilst the short-circuit chosen rating and has A
protection is set at 10 x two protection bands
the chosen rating (LTD), one for line
(FD frame) or adjustable protection and one for
from 5 to 10 x the motor protection (class
B
chosen rating (FE frame). 10)(1). To ensure full discrimination the short-circuit
The unit is designed to offer discrimination with protection has a current dependant
downstream protection devices. It also protects the fixed time setting that varies per frame size. C
lines and/of loads present in standard circuits. The device is adjustable from 2 to 13* x the set LT
current value.
GTM - Line thermal magnetic The unit is designed to protect all circuit types and to
A trip unit de signed to offer a high level of discrimination with downstream D
offer overload and devices.
short-circuit protection.
The overload protection SMR2 (1s & 1g) - Enhanced Electronic Protection(2)
is adjustable from 0.8 to A trip unit designed to
E
1 x the chosen rating offer a overload (LT) and
whilst the short-circuit short-circuit protection
protection is set at (ST). The overload F
about 4 x the chosen protection is adjustable
rating (FD frame) or from 0.4 to 1 x the
adjustable from 2.5 to chosen rating and has
5 x the chosen rating (FE frame). multiple protection G
Due to its low short-circuit current setting the unit can bands (LTD). The short-
be used to protect long cable runs or to provide circuit protection (ST) is
generator protection. adjustable from 2 to 13 X
x the set LT value and has multiple protection bands
(STD). The short-circuit protection can also be set to an
energy mode. The unit is designed to protect all circuit
types and to offer a high level of discrimination with
downstream devices. Different modules allow the user
to expand the device including groundfault , load
shedding and communications etc.

(1) Not available on FK frame execution.


(2) Text applicable for SMR1/2. For SMR1e, SMR1s and g see relevant
section.

B.29
Just rel
Record Plus
Internal Accessories

C.2 Auxiliary contacts

C.4 Releases

External Accessories

C.6 Residual current devices RCD's

C.8 Rotary handles

C.12 Electrical operators

C.16 Connectivity, 60 mm system

C.18 Changeover / Power transfer systems

Versions

C.22 Plug-in devices

C.23 Drawout devices

C.25 Auxiliary disconnect plugs & sockets

Installation

C.26 Padlocks, keylocks

C.27 Door flanges


The breaker
C.28 Terminal shields

C.29 FD frame adaptors and other accessories


Order codes A
Mounting positions

C.31 Allowed mounting position per frame size


Trip units B
C.31 Breaker supply
Components & Accessories C

Connections
Technical data D
C.32 Standard connection terminals

C.34 Rear connections facilities


Application guide E
C.36 Optional connection terminals

C.38 Optional connection - box clamps


Wiring diagrams F
C.40 Optional connection terminals - extenders variants

C.41 Phase separators & Back plates


Dimensions G

y on us
Numerical Index X

C.1
Record Plus
Internal accessories

Auxiliary contacts

FE & FG frame
Components & accessories

Auxiliary contact blocks are coveniently fitted into an go through channels in the breaker rear. Once this is
auxiliary-device compartment , accessible by removing done the wiring can be stripped and easily connected to
the breaker cover. This fully insulated compartment has the box terminals on the internal accessories. These
several pouches, a number of which are reserved for terminals are designed to connect wiring up to 2.5 mm2.
contact blocks. To allow for a logical and traceable To identify the correct mounting position within the
schematics each contact block has a pre-defined accessory compartment symbols are moulded into the
position within the auxiliary device compartment breaker and contact housing.
indicated by a symbol printed both on the breaker case For Auxiliary switches suited for mounting on the right
and on the auxiliary device itself. and on the left .
External wiring can be brought into the accessory For Bell Alarm switches; Mechanism operated types
compartment through - specifically designed and Trip unit operated types .
positioned - break-out openings in the breaker lid or can

Depending on the the breaker functionality, BAM/CDM (Bell alarm mechanism)


9 different kinds of contacts are available, all meeting Indicates that the breaker has tripped due to one of the
the EN 60947-5-1 and UL standards. The maximum following causes:
number and type of contacts that can be fitted - the trip unit has operated (overload or short circuit)
depends on the frame size (FD, FE, FG). - an RCD operation (earth fault)
Please take in to account that when the device is not - the push-to-trip button on the breaker front has been
A linked or mounted to the breaker, it functions in the
opposite manner. (NO mounted in breaker is NC when
pressed
- a shunt or undervoltage release operation
not mounted in breaker). The contact is a simple click-in block and can only be
This does not apply to the contcats blocks used in the placed in the BAM position inside the accessory
B chassis of the drawout version. compartment indicated by the symbol . By using a
combination of the BAM and BA contacts it is possible
The contact numbering of each device is indicated in to discriminate between the kind of fault the breaker
the shematics next to each photo. eg. 5 or 6
C The intermediate cover of the breaker has a separate
has reacted to.

set of codes that indicate the number of the device 3 versions of bell alarm mechanisms are available:
when it is mounted in the breaker. eg. 1 or 2 + - FABAM10 bell alarm mechanism NO for FE and FG
D The combination of these two codes provides a stan- frame
dardized coding system of each connection point(1). - FABAM01 bell alarm mechanism NC for FE and FG
eg. 15 or 26 frame
- FABAM11 bell alarm mechanism (change over) only
E FAS/CA (open - closed indication) for FD frame
They indicate the breaker contact status (open/closed). (Is delivered with 0.75 mm2 cables of 60 cm length).
The contact is mounted in a simple click-in block and is
F available in 4 different versions:
- FAS10L auxiliary contact left mounted NO
- FAS01R auxiliary contact right mounted NC
- FAS10L auxiliary contact left mounted NO
G - FAS01R auxiliary contact right mounted NC
To indicate the breaker position in the drawout chassis
(see page C.23 and C.24) similar contact blocks are
used, available in two versions:
X - FAS10D auxiliary contact NO
- FAS01D auxiliary contact NC

(1) See wiring diagram section for complete overview.

C.2
Record Plus
BAT/CD (Bell alarm trip unit) Performance
Indicates that the breaker has tripped due to one of the
following cases: The contacts offer a combination of a high thermal
- the trip unit has operated (overload or short circuit) current rating and can be used down to typical PLC
- an RCD operation (earth fault) operating levels of 12V 5 mA, AC/DC. The contacts are
The contact is a simple click-in block and can only be placed self-reansing and offer a life span equivalent to or
in the BAT position inside the accessory compartment exceeding that of the breakers. The values mentioned
(indicated by the symbol ). By using a combination of here have been determined in accordance with the
the BAM and BAT contacts it is possible to discriminate EN 60947-5-1 standard.
between the kind of fault the breaker has reacted to.
4 versions are available:
AC [A] DC [A]

Internal accessories
for general use:
- FABAT10 bell alarm trip NO FAS BAT BAM BAM FAS BAT BAM BAM
(no/nc) (no/nc) (co) (no/nc) (no/co) (no/nc) (co) (no/nc)
- FABAT01 bell alarm trip NC
for use in FE frame thermal magnetic and magnetic ≤ 24V 10 10 10 10 2.5 2.5 4 2.5
48V 10 10 10 10 1.4 1.4 0.5 1.4
only types: 60V 10 10 10 10 1 1 0.3 1
- FEBAT10 bell alarm trip NO 110V 6 6 6 6 0.55 0.55 0.2 0.55
220V 3 3 3 3 0.27 0.27 0.1 0.27
- FEBAT01 bell alarm trip NC 380V 2 2 2 2 0.2 0.2 - 0.2
500V 1.5 1.5 - 1.5 - - - -
600V 1.2 1.2 - 1.2 - - - -

FK frame

Optimized for use in the larger FK frame size mounting and The contact numbering of each device is indicated in the
A
connecting takes place in the same manner as in the FD, FE and shematics next to each photo. eg. 5 or 6
FG frame sizes. The contact blocks are of the change over type
The intermediate cover of the breaker has a separate set
(form C) and are available in easy to mount click in devices with a
of codes that indicate the number of the device when it is B
bell alarm contact or auxiliary switch. A maximum of three
mounted in the breaker. eg. 1 or 2 +
auxiliary swiches and one bell alarm contact can be mounted.
To indicate the breaker position in the drawout chassis (see page The combination of these two codes provides a
C.23 and C.24) a similar contact block is used.) standardized coding system of each connection point . C
eg. 15 or 26

FAS/CA (open - closed) (Bell alarm) D


They indicate the breaker contact status (open/closed). A contact that indicates that the breaker has tripped.
The contacts are mounted in a simple click-in block, of The contact is mounted in a simple click-in block
which a maximum of three fit into the auxiliary device and fits into the auxiliary device compartment (right
compartment (right side). side). E
FNS11R Auxiliary contact right mounted CO BA/CD FNBA11R Bell Alarm contact right mounted CO
F

6 8
G

5
X
Performance
AC [A] DC [A]
FAS (co) BA (co) FAS (co) BA (co)
The values mentioned here have been
≤ 24V 10 10 2 2
determined in accordance with the 48V 6 6 1.5 1.5
EN 60947-5-1 standard and apply for 60V 6 6 1 1
inductive loads. 110V 4 4 0.5 0.5
220V 3 3 0.25 0.25
400V 1.5 1.5 - -

C.3
Record Plus
Internal Accessories

Releases

Shunt and undervoltage releases can be fitted easily and go through channels in the breaker rear.
quickly in a specifically designed accessory Once this is done the wiring can be stripped and easily
Components & accessories

compartment which is accessible by removing the connected to the box terminals on the internal
breaker lid. This fully insulated compartment has several accessories. These terminals are designed to connect
pouches one of which is reserved for a shunt or wiring up to 2.5 mm2.
undervoltage release indicated by a symbol printed in The devices are designed to trip the breaker when its
the breaker case and on the auxiliary device itself. contacts are closed and the handle indicates the "On"
External wiring can be brought into the accessory position. When the breaker contacts are open and the
compartment through - specifically designed and breaker handle indicates "Off" or "Trip" activating the
positioned - break out openings in the breaker lid, or can releases will have no effect .(1)

FE & FG frame

Shunt release (SHT/EA) Undervoltage releases (UVR/MV)

B
The Record PlusTM shunt and undervoltage releases are When the breaker is in the "ON" position and the
common for all frame sizes up to 630A and all offer a undervoltage release is deactivated the breaker will trip
unique combination of low power consumption and a and its contacts will open. In de-energized status the
C kiss-free, lock out operation. Most types are common device prevents the breaker contacts from moving and is
for equivalent AC and DC ratings and all are available suitable for use as a lock-out coil. The connection clamps
in a wide range of voltages. When the breaker is in the are marked D1 and D2. De-energization of the device or a
D "ON" position and the shunt trip is activated the breaker drop in its supply voltage to a value below the mentioned
will trip and its contacts will open. The device can be lower voltage limit will activate the device. To prevent
constantly activated at its nominal voltage allowing it to voltage-dip-driven nuisance tripping an undervoltage
be used as a lock out coil. The connection clamps are release with time delay is available. An external DIN-rail
E marked C1 and C2. Switches, relay contacts and push mountable box contains a time delay unit with settable
buttons can be used to operate the shunt release. The use timings and is linked up with a DC UV undervoltage
of illuminated push buttons is limited by the power that release. This version is only available for an AC voltage of
F these lamps require to operate and the value that the
shunt release requires to trip. Here the maximum total
230/240V.
Voltage operation band (all types)
consumption of the lamps may not exceed 2mA. deactivates between 0.35 - 0.7 Un
Voltage operational band 0.7 - 1.1 Un activates between 0.85 - 1.1 Un
G Minimum pulse duration 10 msec minimum reaction time 10 msec
Total intervention time ≤ 50 msec total intervention time (undelayed type) ≤ 50 msec
delayed version (extra delay) settable 100 to 250 msec
X
Shunt release - Performance Undervoltage releases - Performance
Current consumption Power consumption Current consumption Power consumption
Voltage rating Voltage rating
mA mW/mVA mA mW/mVA
inrush hold inrush hold inrush hold inrush hold

12V dc 200 200 2.4 2.4 24V ac/dc 50 50 1.2 1.2


24V ac/dc 150 150 3.6 3.6 48V ac/dc 20 20 0.96 0.96
48V ac/dc 60 60 2.88 2.88 110/130V ac/dc 15 15 1.8 1.8
110/130V ac/dc 40 40 4.8 4.8 220/240V ac 250V dc 15 15 3.45 3.45
220/240V ac 250V dc 20 20 4.6 4.6 440/440V ac 15 15 6.6 6.6
440/440V ac 15 15 6.6 6.6 480V ac 15 15 7.2 7.2
480V ac 15 15 7.2 7.2

(1) Not applicable for FK Frame undervoltage release.

C.4
Record Plus

Internal accessories
FK frame

Shunt release (SHT/EA) Undervoltage releases (UVR/MV)

B
When the breaker is in the "ON" postion and the shunt trip When the breaker is in the "ON" position and the
is activated the breaker will trip and its contacts will open. undervoltage release is deactivated the breaker will trip
The device can be constantly activated at its nominal and its contacts will open. In de-energized status the
voltage allowing it to be used as a lock out coil. device prevents the breaker contacts from moving and is
C
The connection clamps are marked C1 and C2. suitable for use as a lock-out coil. The connection clamps
Switches, relay contacts and push buttons are used to are marked D1 and D2. De-energization of the device or a
operate the shunt release. drop in its supply voltage to a value below the mentioned D
Voltage operational band 0.7 - 1.1 Un lower voltage limit will activate the device. To prevent
Minimum pulse duration 10 msec voltage-dip-driven nuisance tripping an undervoltage
Total intervention time ≤ 50 msec release with time delay is available. An external DIN-rail
mountable box contains a time delay unit with settable E
timings and is linked up with a DC UV undervoltage
release. This version is only available for an AC voltage of
230/240V. F
voltage operation band (all types)
deactivates between 0.35 - 0.7 Un
activates between 0.85 - 1.1 Un
minimum reaction time 10 msec G
total intervention time (undelayed type) ≤ 50 msec
delayed version (extra delay) settable 100 to 250 msec
X
Shunt release - Performance Undervoltage releases - Performance
Current consumption Power consumption Current consumption Power consumption
Voltage rating Voltage rating
mA mW/mVA mA mW/mVA
inrush hold inrush hold inrush hold inrush hold

24V ac/dc 12.5 1.3 300 30 24V dc 1.3 0.13 30 3


48V ac/dc 6.3 0.6 300 30 24V ac 1.3 0.13 30 3
110/130V ac/dc 2.3 0.2 300 30 48V dc 0.6 0.06 30 3
220/240V ac 250V dc 1.2 0.1 300 30 110-127V ac 0.2 0.02 30 3
380-400V ac 0.8 0.1 300 30 230V ac 0.1 0.01 30 3
400-415V ac 0.1 0.01 30 3

C.5
Record Plus
External accessories

Residual current devices

A Record PlusTM circuit breaker can offer protection on the RCD the breaker connected to the device is
against earth leakage currents by using an add-on tripped.
Components & accessories

residual current device (RCD). A line of three and four The RCD unit´s electrical power is supplied by the line
pole completely integrated add-on devices are available voltage of the breaker it is linked to. By use of a multi-
as side mounted models (FD frame size) or as units that phase bridge the design still works when one phase and
are fitted below the trip unit of the breaker the neutral is present . A pouch on the RCD allows one to
(FD, FE and FG frame sizes). In all cases the RCD unit place one BAT contact NO or NC which allows a remote
interfaces directly with the circuit breaker without the signal on earth faults.
use of any secondary wiring or connections. A Record PlusTM breaker and an RCD combination can be
Each RCD has a sensor placed around the phase and connected like any stand-alone breaker and are
neutral current paths that detects the vectorial sum of available as fixed or plug-in devices. The mains
the phase and neutral currents. When this sum is no connection interface of the RCD is an exact replica of the
longer zero it is assumed that current is flowing to earth breaker connection area, thus allowing the use of all
(residual current). If this value exceeds the threshold set standard breaker terminals.

Designed to meet the latest IEC 947 (industrial), The FD-frame RCD is available in two versions: for
IEC 1009 (residential) and the IEC 755 standards, mounting on the right hand side of the breaker or for
Record PlusTM RCDs are available in a version suited for mounting below the trip unit of the breaker. The side
side or bottom mounting as three and four pole units. mounted type is available in two versions. The first one
The tamper free setting area illustrated below is comes with a multifunctional DIN-rail mounting kit
common for the whole line and includes a mechanical including a connection kit to link up the breaker and the
and an electrical test option. RCD. The connection kit allows the user to feed the
breaker and RCD assembly from a multitude of
A 1. Dielectric plug directions while placing the RCD up- or downstream.
2. Electrical test The second version of the side-mounted RCD is designed
3. Reset for screw mounting and comes with a simplified
B 4. Position indicator
5. Mechanical test
connection set (see sketch). Both side mounted devices
are designed to accommodate a
45 or 64 mm cover plate cut-out. This allows usage in an
environment with other DIN-modular devices or with
C other breakers.
The mechanical test button tests the mechanical
operation of the breaker and RCD unit without power,
whereas the electrical option tests both the electrical
D and mechanical operation of the device. In order to
allow for a dielectric test of the breaker and RCD
combination without damaging the electronics, a so
E called "dielectric disconnect plug unit" is placed within
the setting area. All devices have a setting area with a
standard front cut-out of 45 mm. The device has The screw mounted type that only allows for two
numerous current and time settings and an override connection options is depicted on the right .
F blocking the time settings when set to 30mA. The
devices are class A , surge resistant (500A 8/20
mircoseconds) and are finished with a transparent ,
G tamper-free cover.

The FE- and FG-frame RCD units are designed to be


mounted directly below the breaker trip unit area, thus
forming an integrated circuit breaker plus RCD device.
All 'bottom' mounted devices are available as three and
four pole units and have a setting area that is common
for the whole line.

C.6
Record Plus

Programme overview
FDQI or S FDQ(1) FEQ(1) FEQ(1) FGQ(1)
FD frame side mounted FD frame mounted FE frame mounted FE frame mounted FG frame mounted
below breaker(1) below breaker(1) below breaker(1) below breaker(1)

In (A) 160 160 160 250 400/630

External accessories
Number of poles 3-4 3-4 3-4 3-4 3-4
Delay at 2 Idn [msec] Inst-60-150-300-600 Inst-60-150-300-600 Inst-60-150-300-600 Inst-60-150-300-600 Inst-60-150-300-600
Total tripping time 40-100-190-340-640 40-100-190-340-640 40-100-190-340-640 40-100-190-340-640 40-100-190-340-640
at 2 x Idn [msec]
Available voltages 220-440V / 440-690V 220-440V / 440-690V 220-440V / 440-690V 220-440V / 440-690V 220-440V / 440-690V
(AC..50/60Hz)
Idn setting [A] 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10

(1) Must be linked to the trip unit side of the breaker

Selectivity

To assure selectivity/discrimination between two


residual current devices the following rules are
applicable.

IdU > 2 x IdD


A
Where IdU is the threshold of the upstream device and
IdD that of the downstream one.
B
TrU > ToD
Where TrU is the reaction time of the upstream device
and ToD is the total opening time of the downstream
device. C
The table included here indicates where selectivity/
discrimination can be achieved and takes into account
the threshold and time settings of the devices. D

Selectivity overview
E
outgoing
Elfa Plus"S" F-Q RCD 60 ms F-Q RCD 150 ms F-Q RCD 300 ms F-Q RCD 600 ms
Idn (mA) 300 1000 300 1000 3000 300 1000 3000 300 1000 3000 300 1000 3000
incoming F
ElfaPlus 30 T T T T T T T T T T T T T T
Inst. Type 300 T T T T T T T T T T
1000 T T T T
ElfaPlus 30 T T T T T T T T T
"S" type 300 T T T T T T G
1000 T T T
FD-Q RCD 30 T T T T T T T T T T T T
set at inst. 300 T T T T T T T
1000 T T T
FD-Q RCD 30 T T T T T T T T T X
set at : 300 T T T T T T
60 msec. 1000 T T T
3000
FD-Q RCD 30 T T T T T T
set at : 300 T T T T
150 msec. 1000 T T
3000
FD-Q RCD 30 T T T
set at : 300 T T
300 msec. 1000 T
3000

T = Total (or Full) selectivity

C.7
Record Plus
External accessories

Rotary handles
Rotary handle for use through door or cover plate

The Record PlusTM rotary handle is specifically


Components & accessories

designed to allow the user to change the linear


motion of the breaker to a rotation over a 90 degree
angle. This can be accomplished by simply adding an
adaption box to the breaker front .
The design is universal for the whole breaker line and
has the OFF position placed at
3 o’clock and the ON position at 6 o’clock. The third
breaker position "TRIP" is located between the ON
and the OFF position.
The design has room for two early closing and late
opening contact blocks that , in order to save
installation time, are delivered pre-mounted and
pre-wired with a specific rotary-handle device.
Each Record PlusTM rotary handle is designed to allow
Uniquely designed to allow the
the user to place one to three 5 to 8 mm padlocks to
breaker to be placed behind a
lock the breaker in the "OFF" position.
door or cover plate with the
handle protruding through the
door. The rotary handle features
Record PlusTM rotary handle mounted directly on the a door-opening or cover-plate-removal prevention,
breaker front interlock in the ON position and a mechanism that
automatically trips the breaker if the door or cover
plate is not present (a bypass is available). The rotary
A handle is available in grey for normal applications and
in a yellow/red execution for machine-tool applications.

B A special version is available with two normally open


auxiliary contacts (FABAM10) that are pre-mounted and
pre-wired with leads of 0.75 mm2 and a length of 60
cm. The use of a through door rotary handle door
C flange is recommended.

An extra Ronis or Profalux key lock


D A specifically designed adaptor box with a handle is
can be clicked into the handle
front, thus allowing one to lock the
directly installed onto the breaker front . It is available breaker in the same manner as
in grey for normal applications and in a yellow/red the padlocking device.
E execution for machine tool applications. The Ronis key locks are available in a number of versions:
- A version where each lock has a different key number
- A version where the user can choose one of six keys for
several locks
F

FD 63/160 FE 160/250 FG 400/630 FK 800-1600

C.8
Record Plus

Rotary handle for panel or hinged door mounting

External accessories
A special version is available equipped with two
normally open auxiliary contacts (FABAM10) that are
pre-mounted and pre-wired with leads of 0.75 mm2
and a length of 60 cm.

A handle and escutcheon is mounted on the door or An extra Ronis or Profalux key lock
panel front and connected to the breaker by an can be clicked into the handle
elongation shaft that goes into an adaptor box directly front, thus allowing one to lock the
installed onto the breaker front . The design allows for a breaker in the same manner as
total depth of up to 350 mm (from the back of the the padlocking device.
breaker mounted behind the door or panel and the The Ronis key locks are available in a number of versions:
door front). - A version where each lock has a different key number
The handle is available in grey for normal applications - A version where the user can choose one of six keys for
and in a yellow/red execution for machine-tool several locks
applications. Interlocks that prevent the opening of the
door while the breaker is "ON" (are standard). For A number of accessories are available to allow for
A
override operation see red indicators on euchenon specific applications of the device:
front . - To operate the push to trip from the door front an
accessory allowing for a Bowden cable can be fitted B
All Record PlusTM rotary handles have the same to the rotary handle adaptor (flex operator push to
standard "single hole" front door drilling and are trip)
specifically designed to tackle mounting issues as - An adaptor to allow the use of the device with a
"shaft droop" and tolerance in user drillings. drawout construction on the FE, FG,and FK frame C
sizes
Available in grey or in yellow/red the device is supplied - A "long shaft set" allowing for larger mounting
with an adaptor box for installation on the breaker depths than 350 mm (max. 600 mm) D
front , a mounting position definer, a shaft , a handle
with escutcheon for door or panel mounting and all
necessary fixation hardware.
E

FD 63/160 FE 160/250 FG 400/630 FK 800-1600

C.9
Record Plus
External accessories

Rotary handles - accessories


Extension shaft set Flex operator push to trip (Bowden cable)
- The "long shaft set" - For the door/panel-
Components & accessories

allows the user to mounted rotary


install a breaker with handle accessory
a door or panel - Allows the operation
mounted rotary of the push-to-trip
handle up to a depth button from the
of 600 mm, door front by use of
measured from the a bowden cable
back of the breaker (cable NOT supplied).
to the front of the - Available for FD, FE
door and FG frame sizes.
- The set includes a shaft and a shaft droop prevention
adapter
- Available for all frames
Drawout adaptor
- For use with the
Keylock door/panel
- Mounted onto the mounted rotary
direct or behind- handle with the
door rotary handle, standard or long
the key lock locks shaft .
the operator in the - The device allows
OFF position for the difference in
A - The key can not be breaker position in
operated when the the drawout device (depth difference, withdrawn and
lock is opened: the plugged in)
B key is not - The telescopic construction allows one to close the
removable when the door or panel with the breaker in the withdrawn
breaker is in position
the ON position - Available for FE, FG and FK frame sizes.
C - The Ronis key lock type is available with different key
numbers or with a choice of 6 specifically allocated
key numbers Auxiliary contacts
- The same key can be used for a number of different
D key locks on a number of different breakers
- Special rotary
handle versions can
- The specific order code assures that the key fits be provided with
every lock with the same code, even if ordered at a two FABAM NO
E later date. contacts. These
- Available for all frame sizes close before the
main contacts close
and open after the
F Side-by-side installation adapter boxes main contacts open
- A set of covers that - The contacts come
bridge the gap pre-installed in the
G between breakers rotary handle and have
with rotary handles 2 cables 0.75 mm2, 60 cm long
on use through - Available for FD, FE, FG and FK frame sizes.
cover plate
X - Provides an
aesthetically
pleasing finish to
the breaker fronts
- Available for FD and
FE frame sizes.

C.10
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

External accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C.11
Record Plus
External accessories

Electrical operators

In order to allow a Record PlusTM circuit breaker to be An operating panel placed on the drive front allows one
operated electrically, front mounted electrical drives are to choose between two operational positions
Components & accessories

available. These drives are designed for easy mounting - electrical or manual.
onto the breaker front and offer operating times of The panel includes a padlocking or key-locking device in
75 milliseconds or lower. OFF position, the position indicators and a manual
A specifically designed electrical operator is available for operator.
each frame size (FD, FE, FG or FK) each of which has the The devices are connected by means of IPXXB box
same specific technical design features. terminals accessible from the breaker front and located
A Record PlusTM motor operator has three positions in the immediate vicinity of the terminals of the internal
"OFF", TRIP" and "ON", a three-wire connection scheme accessories. The box terminals allow for wiring with a
and is designed to be fast: all drives close within cross section of 0.5 to 2.5 mm2.
75 milliseconds.

Operation
FD and FE frame FG and FK frame
The Record PlusTM FD and FE frame drives The Record PlusTM FG and FK frame drives
are designed with the same front cut-out in the door or have a front escutcheon housing with all the necessary
panel and total breaker depth, thus allowing a side by operators, indicators and locking features:
side use of the devices. The drives have a front
escutcheon housing with all the necessary operators,
indicators and locking features:
A

O
A ON push-button O
A ON push-button
O
B OFF push-button O
B OFF push-button
O
C Manual / Automatic switch O
C Charging handle
O
D Padlocking device O
D Padlocking rack
O
E Position indicator "OFF"--"TRIP"---"ON" O
E Room for cylinderlock
O
F Local operating handle O
F Manual / Automatic switch

C.12
Record Plus
Mounting and Connection
Each drive comes fully mounted and only requires to
be screwed onto the front of the breaker after
removing the standard handle elongator.(1)
The connections are easily accessible and are placed
within the immediate vicinity of the accessory wiring
outlets. This allows for easy interconnection with other
internal accessories.

(1) On the FG and FK frame sizes the lid needs to be removed

External accessories
Specifications

Operating times FD63 & FD160 FE160 & FE250 FG400 & FG630 FK800, FK1250 & FK1600

"On" - pulse received, breaker ON - by drive 50 millisec. 100 millisec. 50 millisec. 50 millisec.
"Off" - pulse received, breaker OFF- by drive 50 millisec. 100 millisec. 8 seconds 12 seconds
"Off" - pulse received, breaker OFF- by SHT/UVR release 50 millisec. 50 millisec. 50 millisec. 50 millisec.
"Reset" - Time between "OFF" and subsequent "ON" pulse 80 millisec. 80 millisec. 8 seconds 12 seconds

Power consumption and required ratings


Short time pulse power "OFF" 700VA / W 700VA / W 500VA / W 500VA / W
A
Constant power required when in "OFF" position 0 0 0 0
Short time pulse power "ON" 700VA / W 700VA / W 500VA / W 500VA / W
Constant power required when in "ON" position 0 0
Required transformer rating VA (AC use only) 300VA(1) 300VA(1) 300VA 300VA B
Required Push button/Contact rating (A)
AC12 24V AC - - 6 6
AC12 230V AC 2 2 2 2
AC15 24V AC
AC15 230V AC
4
1
4
1
4
1
4
1
C
DC12 24V DC - - 10 10
DC12 220V DC 4 4 4 4
DC14 24V DC 4 4 4 4
DC14 220V DC 1 1 1 1 D
Life Span
Mechanical endurance 10000 10000 5000 5000
Operations per hour 120 120 60 30
E
(1) 24V rating requires a 630VA transformer

C.13
Record Plus
Schematics FD, FE & FG frame
Electrical Operator
Scheme A1 Scheme A2
Suitable for Non Automatic breakers (switch) Suitable for Non Automatic breakers (switch)
Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch.
Components & accessories

ph/+ ph/+
A1 A2 ON OFF
Switch or Relay
contact Connection needed Pushbuttons
on FG frame only
ON OFF
A2 A4 2 A2 A4 2

A1 1 A1 1

External link External link

n/-
n/-

Scheme B1 Scheme B2
Suitable for standard circuit breakers without Shunt or Suitable for standard circuit breakers without Shunt or
Undervoltage release Undervoltage release
Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch. After a fault the breaker goes into 'tripped position'.
After a fault the breaker goes into 'tripped position'. The BAT/CD conatct then prevents further electrical
The BAT/CD contact then prevents further electrical operation.
operation. The breaker MUST be reset locally by hand.
The breaker MUST be reset locally by hand.
A ph/+ ph/+
B1 B2 ON OFF
Switch or Relay
contact Connection needed
Pushbuttons
on FG frame only
ON OFF
B A2 A4 2 A2 A4 2

A1 1 A1 1
C 95 96 95 96
Bell Alarm Contact (BAT)externally linked Bell Alarm Contact (BAT)externally linked
allows local/manual RESET only allows local/manual RESET only
n/- n/-

D
Scheme C1 Scheme C2
Suitable for standard circuit breakers with Shunt or Suitable for standard circuit breakers with Shunt or
Undervoltage release Undervoltage release
E Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch. After a fault the breaker goes into 'tripped position'.
After a fault the breaker goes into 'tripped position'. The BAT/CD contact then prevents further electrical
The BAT/CD contact then prevents further electrical operation.
F operation. The breaker MUST be reset locally by hand.
The breaker MUST be reset locally by hand. If tripped by 'other means' an automatic reset is
If tripped by 'other means' an automatic reset is initiated.
G initiated.

ph/+ ph/+
C1 FD FE/FG C2 ON OFF FD FE/FG
Switch or Relay 81 87 81 87
X contact
ON OFF
84 88
Connection needed
on FG frame only Pushbuttons
84 88

A2 A4 2 Bell Alarm Contact A2 A4 2 Bell Alarm Contact


(BAM) (BAM)
Externally linked Externally linked
Provides automatic Provides automatic
A1 1 reset on all trips A1 1 reset on all trips
except those caused except those caused
by a fault by a fault
95 96 95 96
Bell Alarm Contact (BAT)externally linked Bell Alarm Contact (BAT)externally linked
allows local/manual RESET only allows local/manual RESET only
n/- n/-

C.14
Record Plus
Schematics FK frame Electrical
Operator
Scheme A3 Scheme A4
Suitable for Non Automatic breakers (switch) Suitable for Non Automatic breakers (switch)
Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch. The use of a shunt trip is mandatory.

A3 A4

External accessories
ph/+
ph/+ ph/+
ON OFF
Switch or Relay
contact Pushbutton
Pushbutton
ON OFF External link
External link

1 3 4 6
1 3 4 6 C1
Motor operator
Motor operator

2 8 5 7
2 8 5 7 C2
Shunt
External link Release
External link

n/-
n/- n/-

Scheme B3 Scheme C4
Suitable for standard circuit breakers without Shunt or Suitable for standard circuit breakers with Shunt
Undervoltage release release
A
Control circuit operated with a relay contact or a Control circuit operated with push buttons.
switch. After a shunt trip OFF signal the breaker goes into
After a fault the breaker goes into 'tripped position' . 'tripped position' and is reset automatically. B
The BAT/CD contact then prevents further electrical On all other trip events the breaker MUST be reset
operation. locally by hand.
The breaker MUST be reset locally by hand.
C
B3 C4 External timer contact only
resets breaker after Shunt trip operation
ph/+
ph/+ ph/+
D
ON OFF
Switch or Relay
contact Pushbutton

ON OFF External link


Pushbutton E
1 3 4 6 C1
1 3 4 6
Motor operator
Motor operator
F
2 8 5 7 C2
2 8 5 7
Shunt
Release
95 96
Contact
Timer
Time delay OFF G
15 seconds
timer
Bell Alarm Contact (BAT) externally linked
allows local/manual RESET only

n/-
External links
n/- n/- X

C.15
Record Plus
External accessories

Connectivity - 60 mm system
three and four pole
Components & accessories

Record PlusTM circuit breakers have been designed to be Based on these principles GE Power Controls have
installed easily and quickly with conventional means. devised a unique system that allows the user to mount
The devices can be screw mounted to a mounting plate and connect the breaker before the installation.
or clicked to a symmectrical DIN rail and connected with An adaptor device, specifically designed for the
busbars, cables, flex-bars and ring terminals in a Record PlusTM breaker line and incorperating all the
multitude of configurarations. However, if mounting and connection hardware, is fitted to the breaker using five
connecting the breaker can be cut down to a few simple, to six simple screws. Once mounted the adaptor is then
automateable tasks, installation can become easier and simply plugged on to a three or four pole busbar system
more cost effective. already installed in the switchboard.

Busbar system Mains connection


The heart of the system is formed by a busbar system The system can be connected from the side or front .
based on the 60 mm standard for bar spacing. It is The front connection kit makes use of connection
made up of one of two different sets of three or four modules with connection lugs that are directly plugged
pole supports, designed to allow the use of the on to the busbars. This module comes as a three and
following copper bar dimensions. four pole unit and allows the connection of conductors
20 x 5 mm; recommended for 250A from 1.5 to 70 mm2.
20 x 10 mm; recommended for 400A The side connection kit is made up of single pole
30 x 5 mm; recommended for 400A connectors with terminal covers that allow for the
30 x 10 mm; recommended for 630A connection of Cu conductors with a cross section of 25
A to 300 mm2.

D
As standard the busbar supports are delivered
prepared to receive busbar of cross section Busbar finishing
30 x 5 mm, but they can easily be adapted to each Insulating covers are available to protect the user from
E other dimension mentioned by an integrated spacing inadvertent direct contact with the busbar system.
element . These elements have a standard width of 50mm and
can be coupled laterally offering variable width in order
F By varying the distance between the supports it is
possible to build a three or four pole busbar system
to cover the busbar not yet covered by breakers or
feeding modules.
with the following short circuit ratings:
Endplate covers can be mounted to the busbar
G Busbar system supports in order to provide complete protection
against inadvertent contact to a busbar from the side.
Support Busbar size Peak Thermal
withstand Ipk withstand Icw
spacing (mm) (kA) (kA eff) 1 sec.
X
200 mm 20 x 5 46 21.9
20 x 10 50 23.8
30 x 5 58 27.6
30 x 10 63 30.0
300 mm 20 x 5 40 19.0
20 x 10 43 20.5
30 x 5 52 24.8
30 x 10 56 26.7
400 mm 20 x 5 35 16.7
20 x 10 37 17.6
30 x 5 47 22.4
30 x 10 49 23.3

C.16
Record Plus
The system

For the Record PlusTM FD and FE frame adaptors exist rated them to be removed as they were mounted.
at 160A (FD) and 250A (FE) and in a 3 and 4 pole version. Each adaptor is supplied with the necessary fixation
Designed to allow the use of the breaker at its full rated hardware and a terminal shield to cover the connection
breaking capacity of 150kA at 415V each unit is equipped between the breaker and the adaptor.
with a plug/hang on connection system allowing one to The breaker is mounted and connected to the adaptor by
place it on the busbar system in one simple operation. using two pre-tapped fixation points located at its lower end
The adaptors have been tested to meet the most stringent while its main terminals are used to connect and fix it at the

External accessories
requirements and are equipped with a mechanism allowing upper end of the adaptor.

Adaptor Finishing
The breaker and adaptor mounting is simple and easy. The system can be finished with a cover/trim plate that
The length of the 4 pole adaptor also allows the use of can be found in the GE Power Controls
a bottom mounted RCD. enclosure/systems catalogue. To allow for a standard
cut-out within the cover/trim plate a filler piece is
available in lengths of of 1.2 m. This filler plate is
adapted to the Record PlusTM standard front cut-out of
64 mm.

A
System
Each breaker is fixed on the adapter by means of two
pretapped screws at the bottom and its main terminals
B
at the top.
The breaker and adaptor combination is now quite
simply plug/hung on to the busbars, connecting and C
fixing the breaker in one simple operation.
To allow for a flush-front finishing the adaptors have
been designed to adapt to the difference in breaker
depth and can be used with the standard FD and FE D
frame sizes (FD type without DIN-rail adaptor).
The system can be finished with a cover/trim plate that
can be found in the GE Power Controls enclosure/ E
systems catalogue.

C.17
Record Plus
External accessories Two systems are available
Mechanical interlocking by equipping both devices with
a rotary handle and cylinderlocks with the same key
Changeover/Power transfer number. (2 locks one key)
systems
Components & accessories

The use of an interlock unit mounted behind the two


devices, here the breakers are fitted on to pre-
assembled adapter plates that allow the breaker to
infterface with the interlock unit .

A
Mechanical interlocking is possible for the following
breaker types and combinations
B Two 3 or 4 pole FE frames (10- 250A).
Two 3 or 4 pole FG frames (100- 630A).
Two 3 or 4 pole FK frames (320-1600A).
C One 3 or 4 pole FG frames (100- 630A)
&
One 3 or 4 pole FE frames (10- 250A).
One 3 or 4 pole FK frames (320-1600A)
D &
One 3 or 4 pole FG frames (100- 630A).

E Mechanical interlocking Electrical interlocking


Record PlusTM circuit breaker are designed for use with Two devices can be electrically interlocked by using a
F a number of mechanical interlock systems suitable for combination of shunt and/or undervoltage releases
use with thermal magnetic, magnetic only, non with auxiliary contacts of the early closing and
automatic and electronic circuit breakers. Each system breaking type. The Record PlusTM undervoltage and
only permits one of the two interlocked devices to be shunt release are designed to allow their use as
G switched to the 'on' position. interlocking devices and use a twin coil actuator
design. Rotary handle mechanisms are available with
early closing and breaking auxiliary contacts.
X

C.18
Record Plus
Automatic changeover
E plus model
To assure the continuity of electrical supply within a Is available for changeovers with two devices. In addition
low voltage installation it is desirable that on a to the standard E model features it allows for:
failure of the mains voltage supply a secondary - A generator start up command.
power source takes over. An automatic changeover - An adjustable time delay on the generator start
device transfers the power supply from the main command initiation.
power source to a secondary supply when a voltage - Two connections allowing the input of a signal indicating
monitoring device detects a failure in the mains that the supply of the generator set has reached it's

External accessories
voltage. nominal voltage. Only then will the mains device be
disconnected and the secondary device switched on.
The GEPC devices are available in several versions - An adjustable transfer and retransfer time between the
each tailored to the specific needs of the user and different power supplies.
the design of the installation. - Allows for the connection and disconnection of non
priority loads when switching to the secondary supply.
- Built in communication.
- A terminal that allows the input of a start order of the
generator set independent of the mains supply status.
Here a change over cycle is initiated transferring from
main to secondary supply.
- Adjustable cool down time of generator set.

A
Based on the differences in the configuration of the
power supply, complete systems are available for two
or three power sources(1). A two breaker system allows
B
for a power transfer between a transformer and a
generator set (or two transformers).
C
Controllers Controllers, performance
E model E plus model D
Controllers are available for change over systems Number of devices 2 2
with two breakers allowing for a number of power Positions Aut.- Man.- locked Aut.- Man.- locked
supply configurations. Each controller has a manual, Operating voltage 110 or 230V AC 110 or 230V AC E
Power consumption 18VA 18VA
automatic and locked position, a generator start up Mains voltage monitoring (1) Optional Optional
routine and a full set of pilot lights indicating the Time delay on generator set No Adjustable
start signal 0.1 to 60 sec.
status of the system. Time delay on transfer Fixed 10 sec. Adjustable F
command after mains return 0.1 to 15 min.
Remote order stop included included
Two basic controllers available: Remote transfer order No included
Remote retention of secondary No included
supply order G
E model Non priority load switching No included
Is available for change over systems with two devices. Cool down time gen. Set. Adjustable
0.1 to 60 min.
On a mains supply failure the mains device is Communication RS232 / RS485
disconnected and the secondary device switched on. X
When the mains supply returns, the controller keeps the (1) Optionally, a built-in net and/or generator voltage monitor can be
secondary supply on line for a preset time of 10 seconds. delivered with the controler
It then opens the secondary breaker and closes the mains
breaker. An emergency STOP order can be inputted on the
terminals that will switch both the mains and secondary
device to be switched OFF.

C.19
Record Plus
Automatic system with two
devices
The system consists of two electrically operated
Record PlusTM moulded case circuit breakers equipped
with a walking beam mechanical interlock and a con-
troller that can be mounted in the front of the door or
Components & accessories

cover in which the breakers are installed.

Controller modes
A key operated switch (1) allows the selection of four
different operational modes:
LOCKED - all breakers remain in the position AUTOMATIC Depressing the push buttons that operate
attained before this mode was initiated the breaker in the manual mode have no
A - The push buttons are disabled. effect .
- All automatic transfer functions are non
functional. Mains supply fails
The system remains in its standby mode in
B MANUAL - Taking the conditions normally applied to
E model
and which the mains breaker is 'ON' and the
E model a transfer operation into account , the E plus model secondary supply breaker (generator) is
push buttons allow operation of the 'OFF'.
C breakers. As soon as a signal is received that the
- Pressing the generator 'ON' push button secondary supply voltage is available the
will only result in an operation of the mains breaker is opened and the secondary
breaker if the mains breaker is open and supply breaker closed.
D the generator is on line. (voltage present) If the secondary supply breaker does not
close on the first command, two further
E plus model On use of the E plus controller, pressing the closing orders will be given. If the breaker is
E generator 'ON' push button will give the still unable to close a fault is indicated.
generator an order to start . If second voltage E plus model Issues a start command to the secondary
is available an automatic transfer will be supply. This can be delayed up until
initiated from mains to generator supply. 60 seconds after mains failure.
F This operation can be cancelled by Mains supply returns
depressing the generator 'OFF' or mains 'ON' E model The system remains in its secondary mode.
push button. The secondary breaker (generator) is 'ON'
- Pressing the mains 'ON' push button will and the mains supply breaker is 'OFF' for a
G E model
only result in an operation of the breaker period of 10 seconds. This delay is re-
if the generator breaker is open and the instated if the mains supply fails within this
mains is on line. (voltage present) time frame.
X After this delay the secondary supply
E plus model On use of the E plus controller, pressing the breaker is opened and the mains breaker
mains 'ON' push button will initiate a closed. If the mains breaker does not close
automatic transfer from generator to mains on the first command, two further closing
supply. This operation can be cancelled by orders will be given. If the breaker is still
depressing the mains 'OFF' or generator 'ON' unable to close a fault is indicated.
push button. If the mains voltage is not E plus model Basic operation is the same. However the
present , the cycle will not be carried out . 10 second delay is upgraded to one that is
adjustable from 0 to 15 minutes.

C.20
Record Plus
Pilot lights System performance
ORANGE (4) Mains voltage present .
ORANGE (5) Secondary supply voltage available.

Breaker operation
Push-buttons with pilot lights
GREEN (3) Constantly on: Mains breaker is 'OFF' Operating times (minimum) FE frame FG frame FK frame
Blinking:
Transfer to secondary supply underway Opening (trip) 75 ms. 50 ms. 50 ms.
-OR- Closing (ON) 75 ms. 50 ms. 50 ms.
Reset plus OFF 2 sec. 5 sec. 12 sec.
Fault detected on closing mains breaker
When the key selector switch is in it's

External accessories
manual position the push-button allows one Changeover operation
to switch the mains breaker 'OFF'
Operating times (minimum)
GREEN (6) Constantly on: Secondary supply breaker is
The sum of the operating times of the chosen breaker combination
'OFF' Blinking: plus the time values of the controller.
Transfer to mains supply underway -OR-
Fault detected on closing Secondary
supply breaker Functional diagram
When the key selector switch is in it's In 3 ATS the diagram is adapted to selected type
manual position the push-button allows one OL/SC trip AT stays on stand-by
blinking lit
to switch the Secondary supply breaker
'OFF'
Automatic Blocked Manual
RED (2) Constantly on: Mains breaker is 'ON'.
Blinking: Mains breaker has tripped due to
an overcurrent . (fault mode) Mains Mains P. B. P. B. P. B. P. B.
Voltage Start voltage "Open "Open "Close "Close
When the key selector switch is in it's available Generator defaults Mains" Gen" Mains" Gen"
manual position the push-button allows one Gen
to switch the mains breaker 'ON' Gen. voltage
breaker available
RED (7) Constantly on: Secondary supply breaker is "ON"
'OF'. Waits
10"
waits
0,5"
A
Blinking: Secondary supply breaker has
Gen. Gen Mains
tripped due to an overcurrent . (fault mode) Opens
breaker
Opens Mains b. breaker. breaker.
Gen. Mains b. "OFF"
When the key selector switch is in it's breaker "OFF" "OFF" "OFF"
manual position the push-button allows one Closes Closes Open Open Closes Closes
B
Mains b. Mains Gen Mains Gen Mains Gen
to switch the Secondary supply breaker 'ON' "ON" breaker breaker. breaker. breaker. breaker. breaker.
waits
300"
Stops
Gen
Three
trials
Fault
blinkin
Three
trials
Fault
blinkin
C
lit lit

E plus model extra functionality


- Extra green pilot light indicates that the PLC is on line
and functioning well.
D
- Remote retention of secondary supply
Used to prevent unwanted power transfers and to
prevent these occurring a to high a frequency. E
A specific potential free contact is dedicated to this
function.
- Transfer to secondary supply option
Used to start and keep the secondary supply on line
F
independent of the presence of the mains voltage.
A specific potential free contact is dedicated to this
function. G
- Switching on Non Priority loads
If the secondary supply cannot cope with the full
load of the installation it is necessary that certain
'NON priority loads are deactivated when the X
installation is supplied by the secondary source.
However,after some time some NON priority loads
could become 'Priority loads'.
A potencial free contact is used to activate again
these loads
- Voltage monitoring relays
4 terminals are supplied that allow the connection of
a contact indicating that the chosen supply is
available and meets the standards set by the relay.

C.21
Record Plus
Versions

Plug-in

The Record PlusTM plug-in version allows quick, safe and contacts in the base are connected.
easy interchange of breakers. It is made up of a The Record PlusTM plug in version is available for:
Components & accessories

"standard" fixed-front-connection breaker, a set of plugs, FD frame sizes FD63/160 (maximum 125Amps)
a trip mechanism fitted to the breaker and a monoblock FE frame sizes FE160/250 (maximum 250Amps)
base into which the breaker is plugged. FG frame sizes FG400/FG630 (maximum 630Amps)
When the breaker is removed from the plug-in base it
trips automatically (main contacts open) before the plug- FD and FE frame sizes equipped with "bottom mounted
in contacts in the base are disconnected. RCD unit" can also be transformed into the plug-in
The breaker can be operated (closed and opened) when version. The mobile part of the plug-in version remains
removed from the plug-in base. On attempted insertion the same (plugs and trip mechanism do not change).
of a breaker in the "On" position into the plug-in base, The fixed plug-in base is of a different , elongated type
the Record PlusTM breaker trips before the plug-in and has a seperate catalogue number.

D
Mobile part Monoblock base
E The mobile part that is fitted The monoblock base can be
to the breaker is made up of a mounted to a backplate or on
multi-pole set of plugs that profiles and offers IPXXB
displace the standard front protection for front access.
F connection. It also includes a (FD - IP20, FE and FG - IP40).
trip interlock, that , when It is designed to have exactly
mounted, trips the breaker on the same connection profile
G its removal from the base and as the breaker it goes with,
thus allowing the installation
prevents re-insertion into the
base when the breaker is on. of all terminal shields and
The mobile part is supplied terminals that the standard
X with tamper free short terminal shields. breaker offers. These include rear and angular
connectors, spreaders, customized ring terminal
connectors and extenders.

C.22
Record Plus

Drawout

A drawout version allows one to visibly and positively The cradle allows for placing the breaker in one of three
disconnect the mains supply from the installation. Like positions:
on the plug-in device, interchanging breakers quickly, Connected: Main and auxiliary contacts are fully
safely and effectively is one of the key features of connected to the base
Record PlusTM drawout . It is made up of Test/Disconnected: Main contacts are disconnected.
a breaker ("standard" fixed front connection version), a Auxiliaries can be connected or disconnected. This allows
set of plugs and a trip mechanism that are fitted to the for a complete test of the secondary wiring/functionality
breaker, a monoblock base into which the breaker is without having the mains connected.
plugged and a metal support cradle. Remove: Main and auxiliary contacts are fully
disconnected from the metal support cradle and the
plug-in base, the breaker can be removed.

Versions
A

Mobile part
D
FE and FG frames sizes
The mobile part that is fitted The cradle is of a sturdy metal
to the breaker is made up of a construction and is supplied
multi-pole set of plugs that with an integrated standard E
displace the standard front plug-in base. All standard
connection. It also includes a terminal shields, terminals, the
trip interlock, that , when available accessories for the
mounted, trips the breaker on standard fixed front connection
F
its removal from the base and breaker, can be implemented.
prevents re-insertion into the These include rear and angular
base when the breaker is on. connectors, spreaders, G
The kit includes a sliding customized ring terminal
mechanism linking the breaker to its cradle. As with the connectors and extenders.
plug-in version tamper-free short terminal shields are
included in the kit . FK frames sizes X
The cradle and monoblock base
Cradle with monoblock base are combined to form one
The cradle and monoblock base combination can be integral moulded part . The unit
mounted to a backplate or on profiles and offers IPXXB is available with a front or rear
protection for access from the front of the cradle. It is connection facility that allows
designed to offer the same connection options as the the use of connection clamps
standard fixed front connection circuit breaker. available as accessories for the
standard fixed front connection
Remark: See following page for details on interlocks and cradle breaker.
execution.

C.23
Record Plus
Versions

Drawout, cradle types

FE and FG frame FK frame


Components & accessories

In the drawout version the The FK breaker frame size


Record PlusTM FE and FG drawout system has a cradle
frame breakers use the and monoblock base
standard plug-in base combined to form one
encapsulated in a metal integral moulded part .
cradle. The metal cradle has The design has a escutcheon
a escutcheon that protrudes that protrudes through a
through a door or panel. door or panel.

The escutcheon is The escutcheon is


designed as an designed as an
operation- and operation and
indicator-panel and indicator panel and
includes the following includes the following
elements: elements:
- A slot for handle - A slot for handle
insertion. This to insertion. This to
withdraw the breaker withdraw the breaker
by rotating it anti- by rotating
clockwise, and clockwise to re-insert it into the cradle. it anti-clockwise, and clockwise to re-insert the
A - A locking facility for 3 padlocks of 5 to 8mm (locking
in Disconnected/Test position only)
breaker into the cradle.
- A locking facility for
- Room to place a Ronis keylock (E frame 1, G frame 2) 3 padlocks of 5 to 8 mm (locking in drawout position
(locking in Disconnected/Test position) only)
B - A storage facility for the drawout handle - An escutcheon adaptor is available with space for
- A position indicator: Inserted, Disconnected/Test and one or two Ronis keylocks. (locking in drawout
Withdrawn position)
- A position indicator: Inserted, Withdrawn and Test
C The cradle has space to mount two specifically
designed auxiliary contacts blocks type FAS10D or The cradle permits the mounting of three auxiliary
FAS01D per position Disconnected/Test and contacts, one per position: Inserted, Withdrawn and
D Withdrawn. Test .

When the drawout is mounted behind a panel or door,


the design allows the breaker operators and the When the drawout is mounted behind a panel or door,
E drawout escutcheon to be accesible from the panel or the design allows the breaker operators and the dra-
door front , three executions are possible: wout escutcheon to be accesible from the panel or
door front , three executions are possible:
- Breaker is operated by
F elongated toggle (standard, - Breaker is operated by
included in drawout system) elongated toggle (door
- Breaker with electrical flange to be ordered
G operator (door flange to be seperately)
ordered seperately) - Breaker with electrical
- Breaker is operated by a operator (door flange to
rotary handle type through be ordered seperately)
X door or cover. (door flange to - Breaker is operated by a
be ordered seperately) rotary handle type
through door or cover. (door flange to be ordered
- Breaker is operated by a seperately)
rotary handle on hinged door - Breaker is operated by a rotary handle on hinged
or panel. (telescopic shaft door or panel. (telescopic shaft needs to be ordered
needs to be ordered separately)
seperately)

C.24
Record Plus
Plug-in and Drawout versions
Accessories

Auxiliary disconnect plugs and


sockets (1)

FD, FE and FG frame - 8 pole type(1) FK frame - 6 pole type(1)


A set made up of a plug A 6 pole plug and socket
screwed to the breaker system is available and is
back (mobile part) and a used to allow the auxiliary
socket that clicks into the circuits to be connected
plug-in base (fixed part). and disconnected in the
The socket comes with same manner as the poles.
connected colour coded The plug sits on the back
wiring which allows for an of the breaker and the socket clicks into the base.
easy identification of the

Versions
connection points.The wiring can be passed through On withdrawing and inserting the breaker the 6 pole plug
specifically designed channels that lead from the and socket system only disconnects and connnects once
breaker rear into the accesory compartment . The the test position has been reached. This allowing for a test
socket part can be wired out from the base with wiring position without a seperate plug and socket. The FK socket
up to 2.5 mm2 (front access). Each unit has a total of 8 part can be wired out from the base with wiring up to
poles. The number of connectors that can be used per 1.5 mm2 (front access).
breaker frame size is as follows:

Frame size FD63/160 FE160/250 FG400/630 Frame size FK800/1600 3p FK800/1600 4p


A
Nos of units 1 2 3 Nos of units 4 5
Pin Codes (per connector) 1-8 1-8 1-8 Pin Codes (per connector) 1-6 1-6
Connector coding(2) X X&Y X, Y & Z Connector coding(3) X, Y, Z & A X, Y, Z, A & B
(2) Indicated on monoblock plug in base
(3) Indicated on cradle. B
FD, FE and FG frame - 10 pole type(1)
Rating interchange prevention
A set made up of a socket system C
that can be attached to
the plug-in base or a When a number of
drawout cradle and a plug plug-in or withdrawable
with wiring that is breakers (same frame D
connected to the different ratings) are
accessories. installed in the same
The set is used to allow for panel, it becomes
necessary to determine
E
a test position on a
drawout breaker of the FE which rating fits into
and FG frame sizes and as which plug-in base. This
a supplementary connector for internal accessories on to prevent overload in the cables/conductors F
the FD and FE frame sizes. connected to the base, the size of which are
Each plug and socket has a total of 10 poles. determined by the breaker trip unit value or setting.
A specifically designed Record PlusTM accessory
The plug is fitted with supple wire, cross section
0.75 mm2, length 60 cm. Maximum mounting per prevents misinsertion of a wrongly configured
G
breaker size is: breaker/trip-unit combination in the base.

Frame size FD63/160 FE160/250 FG400/630


The accessory consists of two parts (one code per X
breaker), one fixed on the base, the other on the rear of
breaker. Depending on the placing of the red part in the
Nos of units 2 2 2 plug-in base and the pin the user breaks out on the
Pin Codes (per connector) 1 - 10 1 - 10 1 - 10
Connector coding EL & ER EL & ER EL & ER white part , up to 4 breakers can be equipped with this
mutual rejection feature.

(1) In order to ensure a consistant and traceable wiring diagram of all


internal accessories in each frame sizes a standard scheme is included
in the wiring diagram chapter F of this catalogue. (use is optional)

C.25
Record Plus
Installation

Padlocking device for toggle


handle
Components & accessories

To allow users to safely work on installations or installation


This ensures a complete and safe isolation of the
segments protected by the Record PlusTM moulded case
installation or installation segment from the power
circuit breakers it is possible to padlock the devices in their
supply. Two different padlocking devices are available.
OFF position.

The Record PlusTM remov- A padlocking facility that


able padlock is firmly is screwed on to the
attached to the breaker breaker front and
when it is padlocked and normally remains mount-
can be removed for use ed. This device allows the
on another breaker when breaker to be locked in
not in use. This accessory the OFF position with up
can be used with up to to three padlocks of 5 to
3 padlocks of 5 to 8 mm. 8 mm. The device also
It is available in three covers the push to trip
different versions: one knob.
for the Record PlusTM It is available in three
FD and FE frame, one for different versions for the
the FG frame and a third Record PlusTM FD, FE and
for the FK frame. FG frame.

A Keylocking devices

B Record PlusTM moulded case circuit breakers can also be segments or to interlock one or more breakers. Keylocks
locked in their OFF position by the use of a Keylock. This to are available for all Rotary handle devices, electrical
allow users to work on installations or installation operators and draw-out systems.
C
Pad- and Keylocking options, applicable for Record Plus Breakers
D Overview Frame size Padlock Standard Specifically numbered Profalux key lock
Ronis key lock Ronis key lock
Fixed Removable
FD Frame A(1) A
Toggle operator FE Frame A(1) A
E Breaker locked in "OFF" position FG Frame A(1) A
FK Frame A(1) A
FD Frame S(1) A A A
Directly mounted rotary handle FE Frame S(1) A A A
Breaker locked in "OFF" position FG Frame S(1) A A A
F FK Frame S(1) A A A
FD Frame S(1) A A A
Through panel or door type of rotary handle FE Frame S(1) A A A
Breaker locked in "OFF" position FG Frame S(1) A A A
FK Frame S(1) A A A
G FD Frame S(1) A A A
Panel or door mounted rotary handle FE Frame S(1) A A A
Breaker locked in "OFF" position FG Frame S(1) A A A
FK Frame S(1) A A A
FD Frame S A A
X Electrical drive FE Frame S A A
Breaker locked in "OFF" position FG Frame S A A
FK Frame S A A
Drawout version FE Frame S A A
Locked in Disconnected/Test (2) FG Frame S A A
OR drawout position FK Frame S A A

S= standard feature, A = accessory needed, empty box = not foreseen


(1) the explicitly removing of a plastic part directly beneath the handle operator allows one to padlock or keylock in ON position. (Special applications)
(2) FE and FG; Disconnected/test; FK Drawout position.

C.26
Record Plus
Door flanges

In order to provide an IP40 protection degree of the The devices are available for cutouts with the toggle area,
breaker when mounted through a door or cover plate door breaker front face, motor drive front face or on RCD
flanges are used. A door flange also improves the operating panels. A second type of flange is used for
aesthetics of the cutout in the door and allows for higher rotary handles through door/cover allowing interlocks on
tolerances within the cutout. the device to function correctly.

For Record PlusTM breakers installed through doors,


cover plates or panels the following door flanges are
available:

Toggle area RCD bottom mounted type


Fixation via front with (universal for FD, FE and FG)
2 or 4 screws, universal for Fixation via front with 4

Installation
3 and 4 pole breakers. screws

Type Type

FE frame FEFT FD frame 3p FDFF3


FG frame FGFT FD frame 4p FDFF4
FK frame FNFT FE frame 3p FDFF3
FE frame 4p FDFF3
FG frame 3p FDFF3
FG frame 4p FDFF3
Front face
Fixation via front with
4 screws, available for
Electrical operator
3 and 4 pole breakers
Fixation via front with
4 screws. On the FE, FG and
A
Type
FK breaker types the flange
FD frame 3p FDFF3
can be used with the drawout
FD frame 4p
FE frame 3p
FDFF4
FEFF3
system. B
Available for:
FE frame 4p FEFF4

Type
C
Rotary handle (1)
FD frame FDFE
Fixation via front with
FE frame FEFE
4 screws; is required to allow FG frame FGFE
use of the door lock in ON FK frame FNFE D
position with the through
door/panel rotary handle
type. Is available for:
E
Type

FD & FE frame FDFH F


FG frame FGFH
FK frame FNFH

(1) Customized, variable depth version available for drawout types. G

C.27
Record Plus
Installation

Terminal shields

Terminal shields are installed on the incoming or outgoing Record PlusTM terminal shields are equipped with a tamper
Components & accessories

side of the breaker thus achieving a heightened protection free sealing facility and come in sets of two. They are
degree, independent of the type of connection used. For available in a short or a long version and have been
fixed breakers with rear connnection or the plug-in or with- designed for use on the standard fixed front connection
drawble versions of the Record PlusTM breaker the installion breaker or on the base used for plug in breakers.
of short terminal shields is mandatory and they are nor- Each terminal shield is equipped with easy to remove
mally supplied as part of the kit. breakouts to facilitate the connection of the breaker.

Short type(1) Long type(2)


For use with internal box clamps and rear connection.

B
Short terminal shields Long terminal shields
FD FE FG FK FD FE FG(2) FK
C
With two terminal shields 20 30 60 40 With two terminal shields 97 122 83 160
mounted, Breaker heighth is mounted, Breaker heighth is
increased by: (mm) increased by: (mm)
D
(1) The FK short type is only supplied with rear connection kit. (2) The FG type is of medium length. Special long and widened version
available on request.

E Finger protection caps


Available only for the D frame box terminals, the caps
prevent inadvertent contact with the connection
terminals, thus providing the terminal and breaker with
F an IPXXB protection.
Finger protection caps come as standard with the
magnetic only circuit breakers but they are also
G available in a set containing 12 pieces.

C.28
Record Plus

FD frame adaptors

DIN-rail mounting Adaptor - Cut-out filler


All Record PlusTM FD frame breakers can be installed on To use the cut-out with the breaker face and trip unit
a (symmetric) DIN profile (EN50022) by using an just apply the 'cut-out adaptor' to the D frame trip unit .
adaptor. The DIN-rail adaptor is normally supplied with This sealable cover matches the cut-out perfectly and
most breaker types but can also be purchased offers an aestheticly pleasing blending of both breaker

Mounting positions
seperately. fronts.

A
Side by side mounting with Adapator - Side by side
FE frame breakers mounting with ElfaPlus MCB's B
The FD frame DIN-rail adaptor has a second The FD frame has a 45 mm cut-out allowing it's use
application: when mounted with its DIN-rail mounting next to Elfa Plus MCB's and other modular devices. To
feature facing the breaker rear it serves as a heightner. bridge the diffference in depth between the FD frame C
This change in depth of the D frame allows side by side and the modular devices a special heightning kit is
mounting with E frames. When reversed the adaptor available in a standard length of 354 mm.
turns into a heightner that lifts the D frame, and all its
cut-outs up to the E frame level. The 64 mm cut-out of
D
the D and E frame now match up fully in height and
depth.
E

C.29
Record Plus
Installation

Finishing covers Circuit identification label

FD frame Located just under the toggle of every


Record PlusTM circuit breaker there is an area allocated
Components & accessories

For the Record PlusTM FDS, FDN, FDH and FDL types the specifically to click in a circuit identification lable.
finishing covers are standard. By adding both these A set contains 20 units that are common for all frame
covers and the finger protection caps the breaker has a sizes.
protection degree of IP40.

Cut-out filler plate


The FD & FE frame sizes are designed for side by side
mounting.The cut-out suited for use with both breaker
types has a standard dimension of 64 mm. In order to
FE, FG and FK frame fill in empty or reserve space in the trim/cover plate,a
cut-out filler plate is available in a standardized length
A All Record PlusTM FE, FG and FK frame breakers come of 1.2 meters.
complete with finishing covers (for 3 or 4 pole versions).
However, these covers are also available as seperate
items.
B

C.30
Record Plus
Mounting positions

Allowed mounting position


per frame size Breaker supply

A Upstream

Installation
B C

A
Downstream

Breaker Version A B C Phase/phase Supply FD63/160 FD63/160 FE160 FG400 FK800

FD63/160 DIN rail X X X


voltage Un
(AC/ DC)
side is : C, E, S N, H, L FE250 FG630 FK1600 C
Fix X X X
Plug in X X X 220/240V Upstream A A A A A
FE160 / FE250 Fix X X X Downstream A A A A A
Plug in
Draw out
X
X
X
X
X
X
< 500 V Upstream
Downstream
A
A
A
A
A
A
A
A
A
A
D
FG400 / FG630 Fix X X X ≥ 500V Upstream P P P P P
Plug in X X X Downstream P PB(1) PB N(2) P
Draw out X X X
FK800 / FK1600 Fix X X X E
Draw out X X X

A= Allowed
N= Not allowed F
P= Use of phase separators is obligatory.
PB= Use of phase separators and backplate is obligatory.

(1) The use of the top cavity in the box terminal is mandatory.
(2) H & L versions only G

C.31
Record Plus
Connections

Standard connection terminals

The Record PlusTM connection facilities have been stability assure an easy connection.
Components & accessories

designed with the user in mind. Each of the standard connection options described here
Easy access to the area where the conductor must be applies to the fixed breaker, its plug in or drawout base
placed, their generous dimensions and their inherent and the RCD associated with the frame size.

FD frame FE frame
The FD frame is equipped with box clamps allowing the The FE frame size has a connection area specifically
direct connection of one or two cables. The clamps can designed for the connection of busbars and/or cable
also be used with flat bars up to a width of 12 mm. All lugs. The connection area is designed to allow for
'non standard' connection terminals as extenders, rear maximum access to the front of the terminal. Standard
connections etc. are directly connected to these busbar sizes and cable lugs can be accommodated
standard terminals. The breaker is always supplied with without accessories.
the clamps fully open, and they are equipped with a The connection pads have through holes and are
mechanism that prevents them from inadvertently supported by a simple slide-in fully insulated part that
closing whilst connecting. contains one steel nut per connection point . The
connection bolts have an internal allen key profile
allowing for ease of use in the relatively confined area
just above the connection strap.
'Non-standard' connections as extenders are directly
A fitted onto the standard terminals. In other cases - like
rear connections - the slide-in part is completely
replaced.

F
FD frame box terminals FE frame with removeable cover
FD FE
G
1 cable S min/max [mm2] in top cavity Cu(1) 2.5 - 95(2) W max [mm] 25
2 cables S min/max [mm2] in 2 cavities Cu(2) 2.5 - 35 + t max [mm] 5
4 - 35 i1 max [mm] 11.5
Strippable length L [mm] 17.5 i2 max [mm] 9.8
X W max [mm] 12 Ø max [mm] 9.5
Torque (Allen key in breaker) (Nm max.) 8 L Distance to insulation (min.) 25
Torque (Allen key in breaker) (Nm max.) 25

(1) For aluminium conductors use external box clamps. W = Width of bar or ring terminal / lug
(2) For lower terminal cavity 4 - 70 mm2. t = Thickness of bar or lug
(3) On the FDC and FDE type the top cavity cannot be used. Total Ø = Hole diameter
connection capacity for the FDC and FDE type is thus 1 cable of
2.5 -95 mm2 in lower cavity.

C.32
Record Plus

FG frame FK frame

Connections
The FG frame size has a connection area specifically The FK frame has a connection area specifically
designed for the connection of busbars and/or box designed for the connection of busbars. For the FK800
clamps. The connection area is designed to allow for and FK1250 sizes the standard connection pads offer a
maximum access to the front of the terminal. The choice of the use of 2 M10 or 1 M12 bolt . The FK 1600
connection pads have through holes without screw type can use the same connection facility, but the use
thread and are supported by a simple slide-in fully of specifically designed extended connection pads is
insulated part that contains one steel nut per advised.
connection point . The connection bolts have an internal The estended connections allow the use of
allen key profile allowing for ease of use in the 2 M12 bolts.
relatively confined area just above the connection All 'non standard' connection options are fitted to the
strap. standard connection pads.
'Non-standard' connections as extenders are directly
fitted onto the standard terminals. In other cases - like
rear connections - the slide-in part is completely
replaced.
A

F
FG frame with removeable cover FK frame with removeable cover
FG FK
G
W max [mm] 32 W max [mm] 50
t max [mm] 12 t max [mm] 20
i1 max [mm] 19 i1 max using 2 x M10 [mm] 32
i2 max [mm] 17.5 i2 max using 1 x M12 [mm] 23
Ø max [mm] 11 Ø max [mm] 2 x 11 or 1 x 14 X
L Distance to insulation (min.) 33 Torque (Allen key in breaker) (Nm max. M10) 42
Torque (Allen key in breaker) (Nm max.) 42 Torque (Allen key in breaker) (Nm max. M12) 48

W = Width of bar or ring terminal / lug W = Width of bar or ring terminal / lug
t = Thickness of bar or lug t = Thickness of bar or lug
Ø = Hole diameter Ø = Hole diameter

C.33
Record Plus
Connections

Rear connection facilities

A rear connection kit changes the standard connnection standard fixed-front connection breaker to a model
Components & accessories

configuration of a fixed, plug-in or drawout breaker from where the connection is accessible from the rear. Each
front to rear access. Delivered as a multi-pole set they kit is supplied with a short terminal shield to warrant a
allow an easy and quick change in configuration of the IPXXB protection from the breaker front .

FD frame FE frame
Available as a three or four pole set allowing for the Before a Record PlusTM FE frame size can be configured as
configuration of one side of the breaker. The kits are a rear connected device, the front connection insulation
made up of single pole connectors that are fitted to the part (nut plate) must be removed. The rear connection kit
standard cage terminal (top cavity). The rear that consists of a multi-pole kit held in a rear connection
connections are configured for use with busbars and support plate can then be simply slid into the room just
can be rotated at a ninety degree angle to allow for vacated by the front connection part (nut plate). Available
different incoming busbar configurations. The as a three or four pole set, it allows for the configuration of
connectors can be used with standard external box one side of the breaker. The rear connections are
clamps, with or without phase barriers, and are configured for use with busbars and can be rotated at a
supplied with a short terminal shield. forty five or ninety degree angle to allow for different
incoming busbar configurations. The connectors can be
used with standard internal box clamps, with or without
phase barriers, and are supplied with a short terminal
shield.
A

F
Connection Connection
G pad pad

FD frame rear connection FE frame rear connection


X FD FE

A = vertical distance between connections 150 A = vertical distance between connections 140
d1 = breaker depth with long rear connections 90 d1 = breaker depth with long rear connections 98
d2 = breaker depth with short rear connections 45 d2 = breaker depth with short rear connections 48
d3 = pole spacing 27 d3 = pole spacing 35
V [mm] 14 V [mm] 17.4
t [mm] 4 t [mm] 4
i3 [mm] 10 i3 [mm] 13
M [mm] 22 M [mm] 30
Ø hole max [mm] 7 Ø hole max [mm] 9
Torque (Allen key in breaker) (Nm max.) 8 Torque (Allen key in breaker) (Nm max.) 25
Torque of connection bolt M6 (Nm max). 8 Torque of connection bolt M8 (Nm max). 25

C.34
Record Plus

FG frame FK frame

Connections
Before a Record PlusTM FG frame can be configured as Available as a three or four pole set allowing for the
a rear connected device, the front connection isolation configuration of the load or line side of the breaker. The
part (nut plate) must be removed. The rear connection kits are made up of single pole connectors that are
kit that consists of a multi-pole kit held in a rear screwed to the underside of the standard connection
connection support plate can then be simply slid into pad. The rear connections are configured for use with
the room just vacated by the front connection part . busbars and allow for different incoming busbar
Available as a three or four pole set , it allows for the configurations with a option of rotating them at a
configuration of one side of the breaker. The rear ninety degree angle for edgewise busbar connection.
connections are configured for use with busbars and The connectors can be used with or without phase
can be rotated at a ninety degree angle to allow for barriers, and are supplied with a short terminal shield.
different incoming busbar configurations. The
connectors can be used with or without phase barriers,
and are supplied with a short terminal shield.
A

F
Connection Connection
pad pad
G
FG frame rear connection FK frame rear connection
FG FK X
A = vertical distance between connections 229 A = vertical distance between connections 273
d1 = breaker depth with long rear connections 115 d1 = breaker depth with long rear connections 163
d2 = breaker depth with short rear connections 50 d2 = breaker depth with short rear connections 98
d3 = pole spacing 45 d3 = pole spacing 70
V [mm] 30 V [mm] 40
t [mm] 8 i4 [mm] 15
i3 [mm] 15 i5 [mm] 47
M [mm] 35 M [mm] 115/180
Ø hole max [mm] 13 Ø hole max [mm] 2 x 14
Torque (Allen key in breaker) (Nm max.) 42 Torque (Allen key in breaker) (Nm max.) 14
Torque of connection bolt M12 (Nm max). 42 Torque of connection bolt M12 (Nm max). 48

C.35
Record Plus
Connections

Optional connection terminals

To allow for the different connection options in the configuration of one side of the breaker. The kits are
Components & accessories

different applications of the Record PlusTM circuit breaker made up of single pole connectors that are fitted to the
a large variety of different connection lugs, terminals standard breaker terminal. The connectors are supplied
and multiple connectors are available. These are with all the necesssary connection and fixation
available as a three or four pole set allowing for the hardware.

Extender
Extends the standard connection point to the exterior of the breaker body. Record PlusTM extenders are normally used
when the busbars and cables that are needed to connect the breaker exceed the possibilities of the standard connection
facility or when the use of external box clamps is required.

FD frame & FE frame FG frame & FK frame


The single pole connectors that are fitted to the The single pole connectors that are fitted to the
standard terminal. (FD frame top cavity of box clamp). standard terminal.
The connectors can be used with standard external box The connectors can be used with standard external box
clamps, with or without phase barriers.(1) clamps, with or without phase barriers.(1)

F
FD & FE extenders FG & FK extenders
FD FE FG FK
G
h = heigth dimension of breaker with extenders h = heigth dimension of breaker with extenders
at its top AND bottom. 190 230 at its top AND bottom. 354 452
z [mm] 170 212 z [mm] 314 408
s [mm] 27 35 s [mm] 52.5 100
X y max [mm] 28.5 25.5 y max [mm] 29.5 56
W max [mm] 14 20 W max [mm] 30 50
t max [mm] 5 8 t max [mm] 12 20(10)(3)
L max [mm] 16 18 L max [mm] 32 -
Ø hole max [mm] 7 9 Ø hole max [mm] 13 2 x 11 or
Torque (Allen key in breaker) (Nm max.) 8 25 1 x 13
Torque of connection bolt (Nm max). 8 25 Torque (Allen key in breaker) (Nm max.) 42 M10-42
M12-48
Torque of connection bolt (Nm max). 42 M10-42
M12-48

(1) Use is recommended (1) Use is recommended


(2) Two holes in each connection pad.
(3) 1600A, parallel 10mm bus.

C.36
Record Plus

Spreaders
Increase the pole spacing of the breaker they are used to extend the standard connection points to the exterior of the breaker
body. Record PlusTM spreaders are normally used when the busbars and cables that are needed to connect the breaker exceed

Connections
the possibilities of the standard connection facility or when external lugs are needed. Available for:

FD frame & FE frame FG frame & FK frame


The single pole connectors that are fitted to the The single pole connectors that are fitted to the
standard terminal. (FD frame top cavity of box clamp). standard terminal.
The connectors can be used with standard external The connectors can be used with standard external
lugs, with or without phase barriers.(1) lugs, with or without phase barriers.(1)

F
FD & FE spreaders FG & FK spreaders
FD FE FG FK
G
h = heigth dimension of breaker with extenders h = heigth dimension of breaker with extenders
at its top AND bottom. 190 230 at its top AND bottom. 354 452
z [mm] 170 212 z [mm] 314 408
s [mm] 27 35 s [mm] 52.5 100
y max [mm] 18.5 25.5 y max [mm] 29.5 56 X
W max [mm] 14 18 W max [mm] 30 50
t max [mm] 5 8 t max [mm] 12 20(10)(3)
L max [mm] 16 18 L max [mm] 32 -
Ø hole max [mm] 7 9 Ø hole max [mm] 13 2 x 11
Torque (Allen key in breaker) (Nm max.) 8 25 or 1 x 13
Torque of connection bolt (Nm max). 8 25 Torque (Allen key in breaker) (Nm max.) 42 M10-42
M12-48
Torque of connection bolt (Nm max). 42 M10-42
M12-48

(1) Use is recommended (1) Use is recommended


(3) 1600A, parallel 10mm bus.

C.37
Record Plus
Connections

Optional connection - box clamps

Record PlusTM breakers are designed to save space and connection and durability.
Components & accessories

time in mounting when compared to conventional switch The terminals are suitable for conductors of copper and
gear. To achieve the same savings in the connecting aluminium and meet both the newest version of the
process the Record PlusTM line includes a series of lugs EN 60497 standards and the relevant UL486a and b
meeting the newest and highest standards in ease of regulations.

Internal box clamps


Fit onto the breaker without changing its profile or external dimensions. Available as a three or four pole set allowing the
line or load side of the breaker to be equipped. The set consists of multi-pole units that displace the standard connection
configuration. The sets can also be used on the plug in / drawout base and RCD units.
All clamps are suitable for copper and aluminium conductors.

FE frame (FE160 & FE250) FG frame & FK frame


The set consists of basic 3 or 4 pole pole units that The set consists of basic single pole units that displace
displace the standard connection configuration are mounted above the standard connection pad
(FE frame nut plate). The internal box clamps are used (FG and FK frame). Each box terminal allows the
in the same way on the plug in / drawout base and connection of two to four cable cores per item. The
RCD units. All types can also be mounted to extenders, internal lugs are used in the same way on the plug in /
spreaders or rear connection pads. drawout base and RCD units. All types can also be
mounted to extenders, spreaders or rear connection
pads and can be used with or without phase barriers.
A

FE internal box clamps FG & FK internal box clamps


G
FE160 FE250 FG FK(2) FK(3)

h = heigth dimension of breaker with box clamps the same as h = heigth dimension of breaker with 333 381 354
X mounted at top and bottom. breaker box clamps mounted at top and bottom.
2
L max [mm] 18 18 S max [mm ] 25 - 240 240 240
d max [mm] 16 17.5(1) for L1
S max [mm ]2 2.5 - 95 16 - 150 50 - 300
L = distance to insulation (min.) 21 25 for L2
Torque (Allen key on clamp) (Nm max.) 30 30 Hole L1 = distance to insulation L (min.) 22 - -
Hole L2 = distance to insulation L (min.) 40 - -
Distance to insulation L (min.) - 27.5 36
Torque (Nm max.) 31(L1) 31 31
(1) Most standard 185 mm2 cable sections will also fit into this lug 42(L2)
(hole diameter 17.5 mm)
(2) Terminal for 3 cables
(3) Terminal for 4 cables

C.38
Record Plus

External box clamps FE frame distribution terminal

Connections
To accomodate for larger cross sections Specifically designed to allow the use of the
Record PlusTM clamps can be used in combination with Record PlusTM FE frame as a mains device with cables
extenders and/or spreaders. They are available as a distributing the load over multiple outgoing circuits (or
three or four pole set allowing the line or load side of lines of multiple outgoing circuits). The lugs are available
the breaker to be equipped. Each set consists of basic as a three or four pole set allowing the line or load side of
single pole units with phase seperators. the breaker to be equipped. The sets consist of a number
of fully isolated single pole units that can be assembled
into a multipole distribution block before they are
mounted on the breaker. Each lug allows for a maximum
of four 6-25 mm2 or two 10-35 mm2 copper conductors.

FD & FE external box clamps FE distribution terminal


G
FD FE FE

h = heigth dimension of breaker with box clamps h = heigth dimension of breaker with box clamps mounted
mounted at top and bottom. 190 270 at top and bottom. 250 X
z [mm] 30 50 z [mm] 60
s [mm] 27 35 s max [mm] 35
w [mm] 18.5 30 Torque (Allen key in breaker) (Nm max.) 25
y [mm] 50 55.5 L = distance to insulation (min.) - 35 mm2 18
S max [mm2] 4 - 95 70 - 185 L = distance to insulation (min.) - 25 mm2 11
L = distance to insulation (min.) 20 20 Torque on connection bolt (Nm max.) - 35 mm2 6
Torque (Allen key in breaker) (Nm max.) 8 25 Torque on connection bolt (Nm max.) - 25 mm2 3
Torque on connection bolt (Nm max.) 17 25

C.39
Record Plus
Connections

Optional connection terminals -


extender variants
Components & accessories

The Record PlusTM circuit breaker can be equiped with made up of single pole connectors that are fitted to the
several variants of the standard extender design. These standard breaker terminal. The connectors are supplied
are available as a three or four pole set allowing for the with all the necesssary connection and fixation
configuration of one side of the breaker. The kits are hardware.

Extender twisted Extender heightened


The twisted version extends the standard connection Extends the standard connection points to the exterior
point to the exterior of the breaker body and 'twists' of the breaker body and places them at different
the connection area from horizontal to vertical. It is heights. Record PlusTM extenders are normally used
normally used when the connecting busbars are turned when the busbars and cables that are needed to
90 degrees and with ring terminals. connect the breaker exceed the possibilities of the
standard connection facility, when external lugs are
needed or to interconnect several breakers on the
incoming side.

C Twisted extenders Heightened extenders


FD FE FG FD FE

D h = heigth dimension of breaker with h = heigth dimension of breaker with extenders


extenders at its top AND bottom. 190 230 354 at its top AND bottom. 190 230
Ø hole max [mm] 7 9 13 Ø hole max [mm] 7 9
Torque (Allen key in breaker) (Nm max.) 8 25 42 Torque (Allen key in breaker) (Nm max.) 8 25
E

Extender angled
F
Two more extender variants exist for the FE frame type
only with a connection area set at forty five or ninety
G degrees. The hole dimensions and reqiuired torques are
the same as those required for the heightened
extenders.

C.40
Record Plus

Phase separators and Back plates

Phase separators Back plates


Depending on the rated voltage and the type of Back plates are always used in association with phase
connector, the use of phase separators is preferable separators. Normally used at voltages above 500V they
and in some cases mandatory. prevent breaker venting from leading to dielectric
Record PlusTM phase seperators are simply slid into issues. They also can be used when externally mounted
slots in the breaker housing. To allow for an easy connectors no longer meet the required clearance
installation of the connectors they are made of flexible distances to a metal back plate.
material. They can be mounted in two ways, to allow
for front and rear connection. A back plate suitable for 3 and 4 pole breakers is

Connections
They ensure a correct dielectric separation of the available. The required size is easily achieved by
different connection terminals. breaking off parts along a pre-cut line.
For the Record PlusTM FD, FE, FG and FK frame,
phase separators are available in one set containing 12
pieces.

C.41
Just rel
Record Plus

D.2 Performance figures

D.4 Power dissipation

D.8 Derating at temperatures other than 40°C


The breaker
D.10 Clearances (minimum safety distances)

D.11 Use in indivually mounted enclosures


Order codes A
D.12 Current limitation

D.14 Limitation curves (Energy & Current)


Trip units B
D.16 Environmental considerations

D.18 Use in DC networks


Components & Accessories C
D.19 Use at frequencies other than 50/60 cycles
Technical data D

Application guide E

Wiring diagrams F

Dimensions G

y on us
Numerical Index X

D.1
Record Plus

Circuit Breaker type FD160 FD63/160 FE160


Denomination N H C E S N H L N H L
EN 60947-2 standard
Poles Number of 1 3,4 2(1),3,4 3,4
Rated insulation voltage Ui (Volts) 750 500 750 750 750 750
Rated impulse withstand voltage Uimp [Kilovolt] 3 6 8 8 8 8
Technical data

Rated operational voltage Ue Volts AC 240 500 690 690 690 690
Volts DC 250 - - 500 500 500

Line protection device


Category of use A A A A
Suitable for use as a isolator Positive ON & OFF yes yes yes yes
Rated current Ith = Ie A at 40°C 63 or 160 63 or 160 63 or 160 160
Ultimate breaking capacity Icu [kA] 230/240V AC 25 50 25 40 50 85 100 200 85 100 200
400/415V AC - - 18 25 36 50 80 150 50 80 150
440V AC - - 12 14 25 30 65 130(4) 42 65 130
500V AC - - 10 12 18 22 36 50(4) 30 50 100
690V AC - - - 4.5 6 8 10 12 10 22 75
250V DC Single pole - 50 - - 25 40 65 100 50 85 100
500V DC Two pole - - - - 25 40 65(2) 100(2) 50 85(2) 100(2)
Service breaking capacity Ics (%Icu) ≤ 500V 100% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100%
690V AC - - - 75% 75% 50% 50% 35% 100% 75% 25%
Single phase breaking capacity IIT [kA] 230V AC 25 50 16 25 30 50 80 150 50 80 150
400/415V AC - - - 4.5 6 8 10 12 15 22 36
Endurance (CO operations) Mechanical 10000 10000 25000 40000
Electrical at In 5000 5000 10000 20000
A Endurance (On-Tripped operations)
Electrical at In/2
Mechanical
10000
4000
10000
4000
20000
10000
30000
16000
Trip Units Interchangeable no no no yes
Thermal magnetic line LTM LTM
Thermal magnetic generator GTM GTM
B Thermal magnetic selective
Magnetic only
LTMD
Mag Break TM
LTMD
Mag BreakTM
Electronic selective SMR1
Electronic enhanced
Circuit Breaker type and denomination FD160Y FD 63Y FD160Y FE160Y
C EN 60947-3 standard
Non Automatic breaker (Switch)
Rated current In (class AC23) 220V AC to 690V AC 160 63 160 160
D Rated making capacity
Short-term withstand current Icw [kA]
Icm (kA peak)
Icw eff. 1 second
2.8
2
1.7
1.2
2.8
2
4.9
3
Icw eff. 3 seconds 2 1.2 2 3
Circuit Breaker type FD63/160 FE160
Denomination N H L N H L
E EN 60947-4 standard
Use in motor circuits
Rated current Ith A at 65°C FD50-50 FD160-100 150
F Endurance (CO operations) Mechanical 25000 40000
Electrical at In class AC23 10000 20000
Operations per hour 120 120
Protection Short-circuit only (sep. overload device) Mag BreakTM Mag BreakTM
Overload class 10 and short-circuit SMR1
G Max In (A) class 10 FD63-50 FD160-100 150
Max In (A) class 30 FD63-50 FD160-80 150
Earth fault unit (differential) Optional FDQ type Optional FEQ type
Circuit Breaker / Switch type FD63/160 all types FE160 all types

X NEMA AB1 standard


3ph. interruption ratings [kA] 240V AC - - - - 50 65 100 - 100 150 200
480V AC - - - - 25 36 50 - 50 65 130
600V AC - - - - 6 8 10 - 25 36 42
Installation
Mounting On symmetrical DIN Rail yes yes yes no
Fixed yes yes yes yes
Plug in no yes yes yes
Draw out no no no yes
Connection Front yes yes yes yes
Rear no no yes yes
Dimensions [w x h x d] mm 3 pole, fixed front connection 27 x 130 x 85 81 x 130 x 85 81 x 130 x 85 105 x 170 x 95
4 pole, fixed front connection for single pole 108 x 130 x 85 108 x 130 x 85 140 x 170 x 95
Weights [kg] 3 pole, fixed front connection 0.4 0.9 0.9 1.5
4 pole, fixed front connection for single pole 1.3 1.3 2.0
(1) N type only. (3) Use 2 poles.
(2) Use 3 poles. (4) 160A rating only; derate to 65kA at 440V and 36kA at 500V.
D.2
Record Plus

FE250 FG400 FG630 FK800 FK1250 FK1600


V N H L N H L N H L N H L N H L N H

Performance figures
3,4 3,4 3,4 3,4 3,4 3,4
690 750 750 750 1000 1000 1000
8 8 8 8 8 8 8
500 690 690 690 690 690 690
440 500 - - 500 500 500

A B(5) B(5) B B B
yes yes yes yes yes yes
250 400 630 800 1250 1600
65 85 100 200 85 100 200 85 100 200 85 100 170 85 100 170 85 100
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
25 42 65 130 42 65 130 42 65 130 42 65 80 42 65 80 42 65
18 30 50 100 30 50 100 30 50 100 36 42 50 36 42 50 36 42
- 10 15 22 10 22 75(7) 10 22 40(7) 20 25 30 20 25 30 20 25
25 50 85 100 50(3) 60(3) 80(3) 50(3) 60(3) 80(3) - -
- 50 85(2) 100(2) 36(2) 50(2) 60(2) 36(2) 50(2) 60(2) - -
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 50% 100% 75% 50% 100% 75%
- 100% 75% 50% 100% 45% 25% 100% 45% 25% 100% 75% 50% 100% 75% 50% 100% 75%
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
- 10 15 22 10 (6) (6) 10 (6) (6) 20 25 30 20 25 30 20 25
10000 25000 20000 20000 10000 10000 10000
5000 10000 7500 5000 4000 3000 2000
10000
4000
20000
10000
15000
8000
10000
8000
8000
4000
6000
3000
4000
2000
A
no yes yes yes no no no
LTM LTM LTM
GTM
LTMD
Mag BreakTM Mag BreakTM
B
SMR1 SMR1 SMR1e
SMR2 SMR 1s & g
FE250Y FG400Y FG630Y FK800Y FK1250Y FK1600Y
C

250 400 630 800 1250 1600


6.4
4
8.5
5
11.3
6.5
14.1
10
21.2
15
28.3
20
D
4 5 6.5 10 15 20
FE250 FG400 FG630 FK800 FK1250 FK1600
N H L N H L N H L N H L N H L N H
E

225 350 500 720 1000


25000 20000 20000 10000 10000 F
10000 7500 5000 4000 3000
120 120 60 60 60
Mag BreakTM Mag BreakTM Mag BreakTM Mag BreakTM Mag BreakTM
SMR1 SMR1 or SMR2 SMR1 or SMR2
225 350 500 720 1000 G
225 350 500 720 1000
Optional FEQ type Optional FGQ type Optional FGQ type
FE250 all types FG400 all types FG630 all types FK800 all types FK1250 all types FK1600 all types

X
65 100 150 200 100 150 200 100 150 200 85 - - 85 - - 85 -
36 50 65 130 50 65 130 50 65 130 42 - - 42 - - 42 -
22 25 36 42 25 36 42 25 36 42 25 - - 25 - - 25 -

no no no no no no
yes yes yes yes yes yes
yes yes yes no no no
yes yes yes yes yes yes
yes yes yes yes yes yes
yes yes yes yes yes yes
105 x 170 x 95 140 x 265 x 115 140 x 265 x 115 210 x 320 x 160 210 x 320 x 160 210 x 320 x 160
140 x 170 x 95 185 x 265 x 115 185 x 265 x 115 280 x 320 x 160 280 x 320 x 160 280 x 320 x 160
1.6 4.5 4.5 12.2 18.0 18.0
2.1 6.0 6.0 15.1 23.4 23.4
(5) 350 and 500A executions only (7) On use of FG400 and FG630L type at 690V, one
(6) Please contact us. long and widened terminal shield is required.
D.3
Record Plus
Power dissipation

Standards

The standard for low voltage equipment is defined in


the EN 60439-1, the EN 50298 and the IEC 60890.
These provide a theoretical method to calculate the
temperature rise within an enclosure. The main
element in these calculations is the power dissipation
of the equipment installed. By totalizing this value for
all the installed devices, connections, cables and
busbars it is possible to calculate the temperature rise
within the enclosure. Here, for normal applications a
Technical data

temperature rise within the enclosure of 50 Kelvin is


assumed.
The absolute value of this temperature may not exceed
70°C (the sum of the ambient temperature in Celsius
and the temperature rise in Kelvin).

Use

An enclosure manufacturer can provide the exact data


on the allowable power dissipation within a certain
enclosure. The values depend on the enclosure type,
the ventilation it offers and on where the components
A are located within this enclosure. The example here is
based on the GE Modula 630 enclosure type. The table
indicates the temperature rise within a certain
enclosure dimension. This at the top and middle of the
B enclosure in function of the installed heat dissipation
(products) in Watt .

Mounted on wall - Temperature rise [Kelvin]


D DISSIPATION500x500 500x750 750x500 750x750 750x1000 750x1250 1000x500 1000x750 1000x1000 1000x1250 1250x750 1250x1000
(Watt)Middle Top Middle Top Middle Top Middle Top Middle Top Middle Top Middle Top Middle Top Middle Top Middle Top Middle Top MiddleTop
10 4 5 4 4 4 5
20 8 9 7 7 6 8 5 6 4 5 5 7
E 30 11 13
40 13 16 11 13 11 14 9 11 7 9 6 7 9 13 7 9 5 7 5 6 5 8
50 16 19
60 19 22 16 18 16 19 12 16 10 12 8 10 12 18 10 13 7 10 6 8 8 11 6 8
70 21 25
F 80
90
23
26
28
31
20 23 20 24 15 20 12 16 10 12 16 22 12 16

100 28 33 24 27 23 29 18 23 15 19 12 14 19 27 14 19 11 14 9 12 11 16 9 13
120 32 38 28 31 27 33 21 27 22 31 17 23
140 37 44 31 35 31 38 24 31 19 24 15 19 25 35 19 26 15 19 12 16 15 21 12 16
160 41 48 35 39 34 42 27 34 27 39 21 28
G 180
200
45
49
53
58
38
42
43
47
38
41
46
51
29
32
38
41
24 30 19 23 30
33
43
47
23
25
31
34
18 23 15 19 18 25 15 20

220 53 63 45 51 44 55 34 44 28 35 22 27 35 50 27 37 21 27 18 23 21 30 18 24
240 48 55 47 58 37 47 38 54 29 39
260 52 58 51 62 39 51 32 40 25 31 40 58 31 42 24 31 20 26 24 34 20 27
280 42 54 43 61 33 45
X 300 44 57 36 45 28 35 45 65 35 47 27 35 23 29 27 38 23 30
350 50 64 40 51 32 40 51 73 40 53 30 39 26 33 31 43 25 34
400 45 57 36 44 44 59 34 44 29 37 34 48 28 38
450 49 62 39 48 48 65 37 48 32 40 38 53 31 42
500 43 53 53 71 40 53 34 44 41 58 34 46
550 46 57 44 57 37 47 45 63 37 49
600 49 61 47 61 40 51 48 67 39 53
650 53 65 50 65 42 54 51 72 42 57
700 45 57 45 60
750 48 61 47 63
800 50 64 50 67

D.4
Record Plus
Record Plus TM Power dissipation

The power dissipation tables included here indicate the The tables indicate the Watt loss per pole based on the
DC resistance of the Record PlusTM breakers in cold maximum current load of the breaker. To calculate the
condition.The power dissipation per pole can be total Watt loss for a three or four pole breaker these
calculated with this value and the average current values are multiplied by three.*
flowing within the circuit (formula I2R).

* for circuits with a high 3rd harmonic content, please contact us

Power Dissipation - FD63 frame

Power dissipation
Thermal magn. type (LTM, LTMD, GTM) Mag BreakTM (MO) Switch (Y)

In (A)(1) 16 20 25 32 40 50 63 3 7 12.5 20 30 50 63
Fixed version R in m1 per pole 11.00 5.70 4.00 2.90 2.90 2.25 1.60 110.00 55.00 17.85 10.65 4.75 3.00 0.40
Dissipation Watt single pole 2.82 2.28 2.50 2.97 4.64 5.63 6.35 0.99 2.70 2.79 4.26 4.28 7.50 1.59
Dissipation Watt three poles 8.45 6.84 7.50 8.91 13.92 16.88 19.05 2.97 8.09 8.37 12.78 12.83 22.50 4.76
Plug-in version R in m1 per pole 11.07 5.77 4.07 2.97 2.97 2.32 1.67 110.07 55.07 17.92 10.72 4.82 3.07 0.47
Dissipation Watt single pole 0.28 0.44 0.69 0.75 1.17 1.83 2.91 0.99 2.70 2.80 0.31 0.47 1.31 1.87
Dissipation Watt three poles 0.84 1.32 2.06 2.25 3.52 5.50 8.73 2.97 8.10 8.40 0.94 1.42 3.94 5.60
Fixed version R in m1 per pole 11.08 5.78 4.08 2.98 2.98 2.33 1.68 110.08 55.08 17.93 10.73 4.83 3.08 0.48
with RCD Dissipation Watt single pole 0.29 0.45 0.70 0.76 1.19 1.87 2.96 0.99 2.70 2.80 0.33 0.50 1.39 1.91
Dissipation Watt three poles 0.86 1.34 2.10 2.29 3.58 5.60 8.89 2.97 8.10 8.40 1.00 1.50 4.18 5.72
Plug-in version R in m1 per pole 11.15 5.85 4.15 3.05 3.05 2.40 1.75 110.15 55.15 18.00 10.80 4.90 3.15 0.55
with RCD Dissipation Watt single pole 0.31 0.49 0.76 0.83 1.30 2.03 3.23 0.99 2.70 2.81 0.36 0.54 1.51 2.18
Dissipation Watt three poles 0.94 1.46 2.29 2.50 3.90 6.10 9.68 2.97 8.11 8.44 1.09 1.63 4.54 6.55

Power Dissipation - FD160 frame


Thermal magn. type (LTM, LTMD, GTM) Mag BreakTM (MO) Switch (Y)
In (A) 80 100 125 160 80 100 160

Fixed version R in m1 per pole 0.95 0.70 0.40 0.40 0.45 0.45 0.40
A
Dissipation Watt single pole 6.08 7.00 6.25 10.24 2.88 4.50 10.24
Dissipation Watt three poles 18.24 21.00 18.75 30.72 8.64 13.50 30.72
Plug-in version R in m1 per pole 1.02 0.77 0.47 0.47 0.52 0.52 0.47
Dissipation Watt single pole
Dissipation Watt three poles
6.53
19.58
7.70
23.10
7.34
22.03
12.03
36.10
3.33
9.98
5.20
15.60
12.03
24.06
B
Fixed version R in m1 per pole 1.03 0.78 0.48 0.48 0.53 0.53 0.48
with RCD Dissipation Watt single pole 6.59 7.80 7.50 12.29 3.39 5.30 12.29
Dissipation Watt three poles 19.78 23.40 22.50 36.86 10.18 15.90 36.86
Plug-in version R in m1 per pole
with RCD Dissipation Watt single pole
1.10
7.04
0.85
8.50
0.55
8.59
0.55
14.08
0.60
3.84
0.60
6.00
0.55
14.08
C
Dissipation Watt three poles 21.12 25.50 25.78 42.24 11.52 18.00 42.24

D
Power Dissipation - FE160 frame
Thermal magn. type (LTMD, GTM) Switch (Y)
In (A) 25 32 40 50 63 80 100 125 160 160
E
Fixed version R in m1 per pole 6.30 2.80 2.80 2.05 1.80 1.20 0.70 0.63 0.48 0.30
Dissipation Watt single pole 3.94 2.87 4.48 5.13 7.14 7.68 7.00 9.84 12.29 7.68
Dissipation Watt three poles 11.81 8.60 13.44 15.38 21.43 23.04 21.00 29.53 36.86 23.04
Plug-in version R in m1 per pole 6.36 2.86 2.86 2.11 1.86 1.26 0.76 0.69 0.54 0.36
Dissipation Watt single pole 3.98 2.93 4.58 5.28 7.38 8.06 7.60 10.78 13.82 5.63 F
Dissipation Watt three poles 11.93 8.79 13.73 15.83 22.15 24.19 22.80 32.34 41.47 11.25
Fixed version R in m1 per pole 6.37 2.87 2.87 2.12 1.87 1.27 0.77 0.70 0.55 0.38
with RCD Dissipation Watt single pole 3.98 2.94 4.59 5.30 7.42 8.13 7.70 10.94 14.08 5.94
Dissipation Watt three poles 11.94 8.82 13.78 15.90 22.27 24.38 23.10 32.81 42.24 17.81
Plug-in version R in m1 per pole 6.43 2.93 2.93 2.18 1.93 1.33 0.83 0.76 0.61 0.44 G
with RCD Dissipation Watt single pole 4.02 3.00 4.69 5.45 7.66 8.51 8.30 11.88 15.62 11.56
Dissipation Watt three poles 12.06 9.00 14.06 16.35 22.98 25.54 24.90 35.63 46.85 33.79
Mag BreakTM (MO) FE160 frame electronic type (SMR1)
In (A)(1) 3 7 12.5 20 30 50 80 100 125 160 25 63 125 160 X
Fixed version R in m1 per pole 410.00 110.00 13.30 13.30 3.60 1.70 0.60 0.60 0.32 0.32 0.35 0.35 0.35 0.35
Dissipation Watt single pole 5.02 5.39 2.08 5.32 3.24 4.25 3.84 6.00 3.84 3.84 0.22 1.39 5.47 8.96
Dissipation Watt three poles 15.07 16.17 7.27 15.96 11.34 12.75 11.52 18.00 11.52 11.52 0.66 4.17 16.41 26.88
Plug-in version R in m1 per pole 410.06 110.06 13.36 13.36 3.66 1.76 0.66 0.66 0.38 0.38 0.41 0.41 0.41 0.41
Dissipation Watt single pole 5.02 5.39 2.09 5.34 3.29 4.40 4.22 6.60 5.94 9.73 0.26 1.63 6.41 10.50
Dissipation Watt three poles 15.07 16.18 6.26 16.03 9.88 13.20 12.67 19.80 17.81 29.18 0.77 4.88 19.22 31.49
Fixed version R in m1 per pole 410.07 110.07 13.37 13.37 3.67 1.77 0.67 0.67 0.39 0.39 0.42 0.42 0.42 0.42
with RCD Dissipation Watt single pole 5.02 5.39 2.09 5.35 3.30 4.43 4.29 6.70 6.09 9.98 0.26 1.67 6.56 10.75
Dissipation Watt three poles 15.07 16.18 6.27 16.04 9.91 13.28 12.86 20.10 18.28 29.95 0.79 5.00 19.69 32.26
Plug-in version R in m1 per pole 410.13 110.13 13.43 13.43 3.73 1.83 0.73 0.73 0.45 0.45 0.48 0.48 0.48 0.48
with RCD Dissipation Watt single pole 5.02 5.40 2.10 5.37 3.36 4.58 4.67 7.30 7.03 11.52 0.30 1.91 7.50 12.29
Dissipation Watt three poles 15.07 16.19 6.30 16.12 10.07 13.73 14.02 21.90 14.02 14.02 0.90 5.72 22.50 36.86

(1) All 3A magnetic only ratings can be used at 3.5A

D.5
Record Plus
Power Dissipation - FE250 frame
Thermal magn. type (LTMD, GTM) Switch (Y)
In (A) 80 100 125 160 200 250 250

Fixed version R in m1 per pole 1.10 0.60 0.55 0.40 0.33 0.24 0.20
Dissipation Watt single pole 7.04 6.00 8.59 10.24 13.20 15.00 12.50
Dissipation Watt three poles 21.12 18.00 25.78 30.72 39.60 45.00 37.50
Plug-in version R in m1 per pole 1.16 0.66 0.61 0.46 0.39 0.30 0.26
Dissipation Watt single pole 7.42 6.60 9.53 11.78 15.60 18.75 16.25
Dissipation Watt three poles 22.27 19.80 28.59 35.33 46.80 56.25 48.75
Fixed version R in m1 per pole 1.17 0.67 0.62 0.47 0.40 0.31 0.27
with RCD Dissipation Watt single pole 7.49 6.70 9.69 12.03 16.00 19.38 16.88
Dissipation Watt three poles 22.46 20.10 29.06 36.10 48.00 58.13 50.63
Plug-in version R in m1 per pole 1.23 0.73 0.68 0.53 0.46 0.37 0.33
with RCD Dissipation Watt single pole 7.87 7.30 10.63 13.57 18.40 23.13 20.63
Dissipation Watt three poles 23.62 21.90 31.88 40.70 55.20 69.38 61.88
Mag BreakTM(MO) FE250 frame Electronic type (SMR1)
Technical data

In (A) 160 200 250 125 160 250

Fixed version R in m1 per pole 0.33 0.24 0.20 0.20 0.20 0.20
Dissipation Watt single pole 8.45 2.40 15.00 3.13 5.12 12.50
Dissipation Watt three poles 25.34 7.20 45.00 9.38 15.36 37.50
Plug-in version R in m1 per pole 0.39 0.30 0.30 0.26 0.26 0.26
Dissipation Watt single pole 9.98 3.00 18.75 4.06 6.66 16.25
Dissipation Watt three poles 29.95 9.00 56.25 12.19 19.97 48.75
Fixed version R in m1 per pole 0.40 0.31 0.31 0.27 0.27 0.27
with RCD Dissipation Watt single pole 10.24 3.10 19.38 4.22 6.91 16.88
Dissipation Watt three poles 30.72 9.30 58.13 12.66 20.74 50.63
Plug-in version R in m1 per pole 0.46 0.37 0.37 0.33 0.33 0.33
with RCD Dissipation Watt single pole 11.78 3.70 23.13 5.16 8.45 20.63
Dissipation Watt three poles 35.33 11.10 69.38 15.47 25.34 61.88

Power Dissipation - FG400 & FG 630 frame


FG400/630 frame electronic type (SMR1 & 2) Mag BreakTM(MO) Switch (Y)
A In (A) 250 350 400 500 630 350 500 400 630
Fixed version R in m1 per pole 0.11 0.11 0.11 0.10 0.10 0.11 0.10 0.11 0.10
Dissipation Watt single pole 6.88 13.48 17.60 25.00 39.69 13.48 23.75 17.60 39.69
Dissipation Watt three poles 20.63 40.43 52.80 75.00 119.07 40.43 71.25 52.80 119.07
B Plug-in/Draw- R in m1 per pole
out version Dissipation Watt single pole
0.13
8.13
0.13
15.93
0.13
20.80
0.12
30.00
0.12
47.63
0.13
15.93
0.12
30.00
0.13
20.80
0.12
47.63
Dissipation Watt three poles 24.38 74.78 62.40 90.00 142.88 47.78 90.00 62.40 142.88
Fixed version R in m1 per pole 0.16 0.16 0.16 0.15 0.15 0.16 0.15 0.16 0.15
with RCD Dissipation Watt single pole 10.00 19.60 25.60 37.50 59.54 19.60 37.50 25.60 59.54
C Dissipation Watt three poles
Plug-in/Draw- R in m1 per pole
30.00
0.16
58.80
0.17
76.80
0.17
112.50
0.17
178.61
0.17
58.80
0.17
112.50
0.17
76.80
0.17
178.61
0.17
out version Dissipation Watt single pole 10.00 20.21 26.40 41.25 65.49 20.21 41.25 26.40 65.49
with RCD Dissipation Watt three poles 30.00 60.64 79.20 123.75 196.47 60.64 123.75 79.20 196.47

D
Power Dissipation - FK800, FK1250 & FK1600 frame
Thermal magn. type (LTM) Mag BreakTM(MO) Switch (Y)
E In (A) 630 800 1000 1250 800 1250 800 1250 1600

Fixed version R in m1 per pole 0.04 0.04 0.04 0.04 0.02 0.02 0.02 0.02 0.01
Dissipation Watt single pole 15.88 25.60 35.00 54.69 12.80 23.44 12.80 31.25 25.60
Dissipation Watt three poles 47.63 76.80 105.00 164.06 38.40 70.31 38.40 93.75 76.80
F Draw-out R in m1 per pole 0.07 0.07 0.07 0.07 0.05 0.05 0.05 0.05 0.04
version Dissipation Watt single pole 27.78 44.80 65.00 101.56 32.00 70.31 32.00 78.13 102.40
Dissipation Watt three poles 83.35 134.40 195.00 304.69 96.00 210.94 96.00 234.38 307.20
FK800,1250-1600 frame electronic type (SMR1e, s & g)
G In (A) 800 1000 1250 1600
Fixed version R in m1 per pole 0.04 0.04 0.04 0.03
Dissipation Watt single pole 25.60 35.00 54.69 76.80
Dissipation Watt three poles 76.80 105.00 164.06 230.40
X Draw-out R in m1 per pole 0.07 0.07 0.07 0.06
version Dissipation Watt single pole 25.60 35.00 54.69 76.80
Dissipation Watt three poles 76.80 105.00 164.06 230.40

D.6
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power dissipation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D.7
Record Plus
Derating

Thermal magnetic trip units

The ambient temperature in the direct vicinity of a The Record PlusTM breakers with thermal magnetic and
protective device has an influence on its current carrying magnetic only protection units as the MO, LTM and LTMD
properties. types can be used at currents and temperatures as
indicated in the table.

Maximum permissable current at an ambient temperature of


Fixed breaker Plug in or drawout breaker
Technical data

Type In (A) 40°C 45°C 50°C 55°C 60°C 65°C 70°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C

FD63, FD160, 16 16.0 15.5 15.0 14.6 14.1 13.6 13.1 15.0 14.6 14.1 13.7 13.2 12.8 12.3
FE160 & FE250 25 25.0 24.3 23.5 22.8 22.0 21.3 20.5 23.5 22.8 22.1 21.4 20.7 20.0 19.3
32 32.0 31.0 30.1 29.1 28.2 27.2 26.2 30.1 29.2 28.3 27.4 26.5 25.6 24.7
40 40.0 38.8 37.6 36.4 35.2 34.0 32.8 37.6 36.5 35.3 34.2 33.1 32.0 30.8
50 50.0 48.5 47.0 45.5 44.0 42.5 41.0 47.0 45.6 44.2 42.8 41.4 40.0 38.5
63 63.0 61.1 59.2 57.3 55.4 53.6 51.7 59.2 57.4 55.7 53.9 52.1 50.3 48.6
80 80.0 77.6 75.2 72.8 70.4 68.0 65.6 75.2 72.9 70.7 68.4 66.2 63.9 61.7
100 100 97.0 94.0 91.0 88.0 85.0 82.0 94.0 91.2 88.4 85.5 82.7 79.9 77.1
FD160 125 125 121 118 114 110 106 103 118 114 110 107 103 100 96
160 160 155 150 146 141 136 131
FE160 & FE250 125 125 121 118 114 110 106 103 118 114 110 107 103 100 96
160 160 155 150 146 141 136 131 150 146 141 137 132 128 123
200 200 194 188 182 176 170 164 188 182 177 171 165 160 154
250 250 243 235 228 220 213 205 235 228 221 214 207 200 193
FK800 & FK1250 630 630 611 592 573 554 536 517 630 611 563 545 527 509 491
800 800 776 752 728 704 680 656 800 760 714 692 669 646 623
1000 1000 970 940 910 880 850 820 1000 950 893 865 836 808 779
1250 1250 1213 1175 1138 1100 1063 1025 1250 1188 1116 1081 1045 1009 974
A FD63 & FD160
FE160 & FE250
16
25
16.0
25.0
15.5
24.3
15.0
23.5
14.6
22.8
14.1
22.0
13.6
21.3
13.1
20.5
15.0
23.5
14.6
22.8
14.1
22.1
13.7
21.4
13.2
20.7
12.8
20.0
12.3
19.3
with RCD 32 32.0 31.0 30.1 29.1 28.2 27.2 26.2 30.1 29.2 28.3 27.4 26.5 25.6 24.7
40 40.0 38.8 37.6 36.4 35.2 34.0 32.8 37.6 36.5 35.3 34.2 33.1 32.0 30.8
50 50.0 48.5 47.0 45.5 44.0 42.5 41.0 47.0 45.6 44.2 42.8 41.4 40.0 38.5
B 63
80
63.0
80.0
61.1
77.6
59.2
75.2
57.3
72.8
55.4
70.4
53.6
68.0
51.7
65.6
59.2
75.2
57.4
72.9
55.7
70.7
53.9
68.4
52.1
66.2
50.3
63.9
48.6
61.7
100 100 97.0 94.0 91.0 88.0 85.0 82.0 94.0 91.2 88.4 85.5 82.7 79.9 77.1
FD160 125 119 115 110 108 97 101 97 110 107 104 101 97 94 91
with RCD 160 152 147 141 138 125 129 125 141 137 133 129 124 120 116
C FE160 & FE250
with RCD
125
160
125
152
121
147
118
141
114
138
110
125
106
129
103
125
118
141
114
137
110
133
107
129
103
124
100
120
96
116
200 190 184 177 173 156 162 156 177 171 166 161 156 150 145
250 238 230 221 216 195 202 195 221 214 208 201 194 188 181

D.8
Record Plus
Derating

Electronic trip units

Electronic trip units are less sensitive to fluctuations in into account. The table indicates the maximum values to
ambient temperature than thermal magnetic trip units. which the LT or overload protection of the electronic trip unit
However, to prevent the device and its environment from of the Record PlusTM breaker can be set. This at ambient
exceeding their design values, certain limits must be taken temperatures from 40 to 70°C.

Maximum permissable current at an ambient temperature of


Fixed breaker Plug in or drawout breaker
Type Is(1)(A) 40°C 45°C 50°C 55°C 60°C 65°C 70°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C

FE160 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
125 125 125 125 125 125 125 125 125 125 125 125 125 125 125

Derating
160 160 160 160 156 152 148 144 160 156 152 148 144 140 136
FE250 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
160 160 160 160 160 160 160 160 160 156 152 148 144 140 136
250 250 250 250 244 238 231 225 250 244 238 231 225 219 213
FG400 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250
350 350 350 350 350 350 350 350 350 350 350 350 350 350 340
400 400 400 400 390 380 370 360 400 390 380 370 360 350 340
FG630 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
500 500 500 500 500 500 500 500 500 500 500 500 500 500 481
630 630 614 599 583 567 551 536 583 568 554 539 524 510 481
FK800 800 800 800 760 760 760 680 - 760 741 722 703 722 646 -
FK1250 1000 1000 1000 950 950 900 850 - 950 950 903 879 855 808 -
1250 1250 1250 1188 1188 1125 1000 - 1188 1158 1128 1098 1069 950 -
FK1600 1600 1600 1600 1520 1440 1408 1280 - 1600 1536 1444 1408 1368 1216 -
FE160 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
with RCD 63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
106
A
160 160 156 152 148 144 141 137 152 148 144 141 137 133 129
FE250 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
with RCD 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160

FG400
250
250
250
250
244
250
238
250
244
250
238
250
231
250
225
250
238
250
232
250
226
250
220
250
214
250
208
250
202
250
B
with RCD 350 350 350 350 341 333 324 315 350 351 342 333 324 315 306
400 400 370 360 350 340 330 320 360 351 342 333 324 315 306
FG630 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
with RCD 500
630
500
630
500
567
500
551
500
536
500
520
500
504
488
488
500
520
500
507
494
494
481
481
468
468
455
455
442
442
C

(1) Is = Sensor rating


D

D.9
Record Plus
Clearances

Minimum distances

A modern circuit breaker is designed to interrupt high The Record PlusTM circuit breaker has been designed to
short-circuit currents in a very limited time frame. limit the venting phenomanae to a minimum. However, it
In doing so the breaker vents gas and and a limited is necessary to take the following minimum distances
amount of conductive fragments. into account:

Minimum Distance Minimum Distance


between two side to a front panel
by side mounted from a Record
Technical data

Record PlusTM PlusTM Breakers


Breakers = 0 mm = 0 mm
Protection degree
on breaker front
= IP40

D
Minimum Distances
Distances in mm
E Type a b c d
FD63 & FD/160 To painted metal, non conductive materials and isolated conductors. 0 15
To unpainted metal Voltage ≤ 480V 3 35
Voltage < 600V(1) 5 (2)
F Voltage = 690V(1) 15 (2)
To breaker housing 35 35
To conductors potruding from breaker 35 35
FE160 & FE250 To painted metal, non conductive materials and isolated conductors. 0 20
To unpainted metal Voltage ≤ 480V 5 35
G Voltage < 600V(1) 10 (2)
Voltage = 690V(1) 20 (2)
To breaker housing 35 35
To conductors potruding from breaker 35 35
FG400 & FG630 To painted metal, non conductive materials and isolated conductors. 0 30
X To unpainted metal Voltage ≤ 480V 5 60
Voltage < 600V(1) 10 (2)
Voltage = 690V(3) 20 (2)
To breaker housing 60 60
To conductors potruding from breaker 60 60
FK800, FK 800 To painted metal, non conductive materials and isolated conductors. 0 40
& FK1600 To unpainted metal Voltage ≤ 480V 15 80
Voltage < 600V 20 80
Voltage = 690V 30 80
To breaker housing 140 140
To conductors potruding from breaker 140 140

(1) The use of phase seperators and back plates is obligatory. (3) At 690Volts the FG400L & FG630L must have the power supply connected to the breaker
(2) Size determined by phase seperators. ON side (Line). In this application the use of the widened terminal shield is compulsory.

D.10
Record Plus
Individual mounting of
Record PlusTM in enclosures
Record PlusTM breakers can be placed in enclosures for
use as individually wall mounted feeder units. In order
to ensure a reliable and practical solution each of the
combinations mentioned here have been defined by
strenous testing. Here the properties of all components,

Mounting in enclosures
and their use as a combination have been taken into
account . For all other application of the Record PlusTM
in individually mounted enclosures, please contact us.

VMS, thermoplastic box IP65 with transparent cover. Breaker and terminal covers always have to be ordered
The use of short or long terminal covers for the breaker separately.
is mandatory. Short-circuit rating: 20kA, 440 V

VMS, thermoplastic housing IP65 with opaque cover


Housing
Record Plus Breaker(1) Breaker type Rotary handle type
In (A) Size Type Ref. nr.
125A FD125 with and without RCD FDNRC 440 x 320 x 254 VMS43 + extension frame 855085
160A FE160 FENRC 440 x 320 x 254 VMS43 + extension frame 855087
160A FE160 with RCD FENRC 640 x 320 x 254 VMS63 + extension frame 855088
250A FE250 FENRC 440 x 320 x 254 VMS43 + extension frame 855087
250A FE250 with RCD FENRC 640 x 320 x 254 VMS63 + extension frame 855088
400A FG400 or FG 630 FGNRC (2) (2) (2)
630A FG400 or FG630 with RCD FGNRC (2) (2) (2)

A
PolySafe, glass fibre reinforced Polyester, cabinet IP65 breaker in a VMS box.
with door. Breaker, terminal covers and mounting plate for the
When using Record PlusTM Breaker in polyester cabinets external housing have to be ordered separately.
B
for outdoor use we recommend encapsulating the Short-circuit rating: 20kA, 440 V(3)

C
PolySafe, glass fibre reinforced polyester cabinet IP65
Internal housing VMS External housing Polysafe
Record Plus Breaker(1) Breaker type
In (A) Size Ref. nr. Size Ref. nr.
125A FD125 w/out RCD 440 x 320 x 254 855085(3) 750 x 500 x 320 883008
D
160A FE160 w/out RCD 640 x 320 x 254 855087 / 855088(3) 750 x 500 x 320 883008
250A FE250 w/out RCD 640 x 320 x 254 855087 / 855088(3) 750 x 500 x 320 883008
400A FG400 or FG 630 FGNRC (2) (2) (2)
630A FG400 or FG630 with RCD FGNRC (2) (2) (2) E
(1) Ambient temperature max. 30 degrees centigrade.
(2) Please contact us.
(3)The use of short or long terminal covers on the breaker is mandatory F

D.11
Record Plus
Current limitation

A short-circuit is an overcurrent with a value only limited In modern hi-power electrical distribution networks very
by the impedance of the fault circuit itself. This high prospective fault levels of 100kA or more can occur.
impedance is determined by a number of factors the High prospective short-circuit current values can cause
main ones of which are the available power that a issues in a number of areas:
network can supply and the impedance of the
conductors within the fault circuit .

Electrodynamic forces Thermal stress in Electrical conductors


These are proportional to the square of the crest current Cable have thermal stress limits normaly expressed in
value a A2S value that depend on the cable´s cross section
Technical data

The electrodynamical forces due to the crest current value and its isolation. It is limited to prevent the cable
can seriously damage equipment as busbar systems and isolation from exceeding its temperature
their supports, downstream switchgear etc. limits, the maximum values being specified in the HD
Current limiting devices limit the crest value of the short- 384.4.4.42 and HD 384.5.5.4 standards and
circuit current and thus reduce theses forces. paragraphs.The standards define the use of the
formula:
Magnetic fields K2 x S2
A high level short-circuit produces magnetic fields that K; factor provided in the standard; depends on
prevent electrical equipment as meters and computers the material that the conductor is made of and
from operating correctly. it's insulation
S; cross section of the conductor
Thermal stress (heat)
Thermal stress is proportional to the square of the effective
current value.
K factors acording to HD 384
A The thermal stress limit of cable isolation, busbar supports Insulation Cu Al
and other electrical equipment can be expressed as an
A2S value. This electrical energy value must be kept within 70°C PVC ≤ 300 sq.mm 115 76
certain pre-defined limits to prevent overheating. 70°C PVC > 300 sq.mm 103 68
B To avoid or to limit the effects of these issues the use of
90°C XLPE or EPR
85°C rubber
143
134
94
89
current limiting devices is advisable.

G
Maximum permissable thermal stress in conductors
X Thermal Stress Values
Insulation Core Material S in mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120

A2S A2S A2S A2S A2S A2S A2S A2S A2S A2S A2S A2S
x104 x104 x105 x105 x105 x106 x106 x107 x107 x107 x107 x107
70°C PVC Copper 2.98 8.27 2.12 4.76 13.23 3.39 8.27 1.62 3.31 6.48 11.94 19.04
Aluminium 1.30 3.61 0.92 2.08 5.78 1.48 3.61 0.71 1.44 2.83 5.21 8.32
90°C XLPE or EPR Copper 4.60 12.78 3.27 7.36 20.45 5.23 12.78 2.51 5.11 10.02 18.46 29.45
Aluminium 1.99 5.52 1.41 3.18 8.84 2.26 5.52 1.08 2.21 4.33 7.97 12.72
85°C rubber Copper 4.04 11.22 2.87 6.46 17.96 4.60 11.22 2.20 4.49 8.80 16.21 25.86
Aluminium 1.78 4.95 1.27 2.85 7.92 2.03 4.95 0.97 1.98 3.88 7.15 11.41

D.12
Record Plus

Record PlusTM MCCB’s revolutionary design is equipped The limitation of electrodynamic forces and thermal

Current limitation
with dual contacts placed in a rotary configuration that stress by using back-up protection
enables the device to provide the highest available Protection devices placed downstream from a
interruption ratings in the smallest possible size. When protective device as a Record PlusTM breaker must be
the breaker reacts it does so with more than twice the able to withstand the thermal and
speed and force of conventional breakers, thus electrodynamic effects that occur at its point of
providing excellent current limitation. This results in low installation. Placing current limiting devices upstream
peak current and energy values in the circuit and leads limits these values and can allow the use of smaller
to lower electro-dynamic forces and thermal stress and more economical devices than is possible without
values in the protected electrical conductors, the use of current limitation.
downstream protection devices and equipment .
Back-up protection with Record PlusTM is described in
the application data section of this catalogue.

B
H

D
However, in some cases it is still necessary to check if
the electrical conductors are protected correctly. This
can be verified by taking the cable stress limits
E
published on the previous page and comparing them
with the let-through energy values found in the graphs.
F

D.13
Record Plus
Current limitation data at
400/415V
Technical data

B Thermal stress (Energy)


Limitation data at 400/415V
C

D.14
Record Plus

Current limitation data at 690V

Current limitation
A

Thermal stress (Energy) B


Limitation data at 690V
C

D.15
Record Plus
Environmental considerations

Ambient temperature Other atmospheric conditions

Record PlusTM breakers are designed to operate The breaker is


normally at temperatures of - 20 degrees to + 70°C. designed to operate
Above 40°C derating factors must be applied for two at the temperatures
basic reasons: and relative
- To prevent the materials used to construct the device humidities defined in
from reaching temperatures that have an adverse the EN 60947 clause
effect on their mechanical and/or electrical properties. 6.1.3.1. It also meets
- When the breakers is equipped with a thermal the following
magnetic protection device the bimetal in the device standards:
Technical data

will react to the heat generated by the current flowing


through the device.Typical for this kind of device is that IEC 68-2-1 Cold
IEC 68-2-2 Dry heat
its reaction time speeds up at higher ambient IEC 68-2-11 Salt
temperatures. IEC 68-2-14 Change of temperature
IEC 68-2-27 Shock test
IEC 68-2-29 Bump
To achieve the same IEC 68-2-30 Damp heat cyclic
reaction time on a IEC 68-2-31 Drop
MIL810F Humidity
set current value it
becomes necessary
to derate.
The time current
curves published in Shock & vibration
this catalogue are
always valid for
The Record PlusTM line has been designed to
A operating tempera-
withstand shock and vibration to the following
tures between
standards:
10 and 40°C.
IEC 68-2-6
B Lloyd´s Register of Shippping
Bureau Veritas
Storage temperature JIS 8370
More specifically: Record PlusTM passed the
C following electro-mechanical tests:
A Record PlusTM breaker is able to withstand
non-operational storage temperature ranges of Functions normally while being subjected to
- 40 to + 85°C.
D 30 minutes of random vibration with a power spectral
density of 0.29g2/Hz in the range of 5Hz to 500Hz
(3dB corner points, +-20dB/decade rolloff), this over
Influence of altitude three axes.
E
Functions normally
Up to altitudes of while being
2000 m above sea subjected to
F level no derating of sinusoidal vibration of
breaker current or 5g Peak from 10Hz to
rated voltage is 500Hz using 30
G apllicable. For minute sweeps with
altitudes above additional 30 minute
2000 m the following dwells at the three
factors apply: greatest resonance points in this frequency range, this
X over three axes.

Altitude The product is shock resisitant and can withstand the


following impacts in any possible orientation:
Altitude (meters) 3000m 4000m 5000m 20g, 6ms, 10g, 11ms

Ue max. (Volts) 550V 480V 420V


Max. Thermal current at 40 degrees C 0.98 x In 0.93 x In 0.9 x In

D.16
Record Plus

Electromagnetic compatibility

Meets the most stringent requirement of the Electrostatic discharge


EN 60947-2 and IEC 1000-4. The breaker and electronic EN 70947 Annex F, Sub-clause F6 and the IEC 1000-4-2
trip unit have passed the following tests. (basic standard)
- Passed level 4 air discharge 15kV
Radiated, radio frequency, electromagnetic field
Harmonics, current dips , interruptions and power immunity test
frequency variations. EN 60947-2 Annex F, Sub-clause F7 and
EN 60947-2 Annex F, Sub-clause F4.1 through 3 the IEC 1000-4-3 (basic standard)
All requirements of non-sinusoidal currents resulting - Passed higher than level 4.....field strength 30V/m
from harmonics are met i.e : Electrical fast transient/burst

Environment
EN 60947-2 Annex F, Sub-clause F5 and
- Wave form the IEC 1000-4-4 (basic standard)
consisting of a - Passed level 4 burst peak voltage 4kV
fundamental Surge immunity test
component + 3rd EN 60947-2 Annex F, Sub-clause F5 and
harmonic the IEC 1000-4-5 (basic standard)
component at - Passed level 4 Voltage 1.2μs/50μs 6kV; current
50 and 60Hz 8μs/20μs 3kA
- Wave form Dry heat test
consisting of a EN 60947-2 Annex F, Sub-clause F8
fundamental component + a 5th harmonic component - Passed all test requirements
at 50 and 60Hz Thermal shock test
- Composite wave form with a fundumental EN 60947-2 Annex F, Sub-clause F9
component + 3rd ,5th & 7th and a harmonic at 50 and - No nuisance tripping within the 28-day temperature A
60Hz cycles
- All current dips and current interruptions are met .
- Frequency variation test from 45Hz to 65Hz in 1Hz
steps (required 50Hz to 60Hz in 1Hz steps) B

D.17
Record Plus
Use in DC networks

In both AC and DC networks protective devices are However, the system voltage generally plays a greater
required to interrupt the prospective short-circuit current role (is more difficult to interrupt) while the network
at the point where the device is installed. For circuit defines how many poles need to participate in the
breakers as the Record PlusTM this value is called the interruption.
interuption or breaking capacity (Icu or Ics), a value The drawing below indicates the three possible DC
dependent not only on the prospective fault current networks with the "worst" short-circuit for each of them,
value but also on the system voltage rating. For DC the number of poles that must particpate in the breaking
networks the situation is basically the same as for AC operation and the voltage level that needs to be
networks. interrupted.

Use in DC networks
Technical data

Network Type Center point connected to earth (A) One pole connected to earth (B) Insulated from earth (C)(1)

Electrical schemes

Maximum short-circuit current (Icc max) short-circuit A-B short-circuit A-B or A-C short-circuit A-B
Minimum poles needed 2 (one on each polarity) 1 (unearthed polarity) 2 (one on each pole)
Breaking capacity on each pole Icc max at V/2 Icc max at V Icc max at V

(1) When a pole is grounded due to a first fault nothing happens, on a second fault the network behaves like a system with "one polarity connected to ground"

A
Record PlusTM FD, FE, FG and FK line breakers can be Example
used in DC networks with standard thermal magnetic trip Rated voltage 500 V DC; Rated current 200 A Icc
units. max 50 kA
B For Record PlusTM FG line breakers, please contact us. network A : center point connected to grond
The nominal current rating of the device does not vary in FE250N 3x 250 - 1pole for each polarity
AC or DC applications. The setting of the short-circuit or network B : one pole connected to ground
magnetic device needs to be multiplied by 1.2 to FE250N 3x 250 - 2poles on unearthed polarity.
C determine its threshold in a DC network. network C : insulated network
The table indicates the nominal current , the breaking FE250N 3 x 250 - 1 pole on each polarity
capacity (Icu=Ics) and the number of poles needed to
D participate in the interruption.

Use in DC networks with standard thermal magnetic trip units


E
Breaker Rated current 110 V DC 250 V DC 440 V DC 500 V DC Thermal threshold Magnetic
threshold
FD 63S 16÷ 63 25 (1p) 25 (1p) 25 (2p) - = AC 1.2
F FD 63N 16÷ 63 40 (1p) 40 (1p) 40 (2p) 40 (2p) = AC 1.2
FD 63H 16÷ 63 65 (1p) 65 (1p) 65 (2p) 65 (3p) = AC 1.2
FD 63L 16÷ 63 100 (1p) 100 (1p) 100 (3p) 100 (3p) = AC 1.2
FD160S 64÷160 25 (1p) 25 (1p) 25 (3p) - = AC 1.2
FD160N 64÷640 40 (1p) 40 (1p) 40 (2p) 40 (2p) = AC 1.2
G FD160H 64÷640 65 (1p) 65 (1p) 65 (2p) 65 (3p) = AC 1.2
FD160L 64÷640 100 (1p) 100 (1p) 100 (3p) 100 (3p) = AC 1.2
FE160N 25÷160 50 (1p) 50 (1p) 50 (2p) 50 (2p) = AC 1.2
FE160H 25÷160 85 (1p) 85 (1p) 85 (2p) 85 (3p) = AC 1.2
FE160L 25÷160 100 (1p) 100 (1p) 100 (3p) 100 (3p) = AC 1.2
X FE250V 125÷250 25 (1p) 25 (1p) 25 (2p) - = AC 1.2
FE250N 125÷250 50 (1p) 50 (1p) 50 (2p) 50 (2p) = AC 1.2
FE250H 125÷250 85 (1p) 85 (1p) 85 (2p) 85 (3p) = AC 1.2
FE250L 125÷250 100 (1p) 100 (1p) 100 (3p) 100 (3p) = AC 1.2
FG400N
FG400H
FG400L
FK800N 500÷800 50 (1p) 50 (2p) 36 (3p) 36 (3p) = AC 1.2
FK800H 500÷800 60 (1p) 60 (2p) 60 (3p) 60 (3p) = AC 1.2
FK800L 500÷800 80 (1p) 80 (2p) 80 (3p) 80 (3p) = AC 1.2
FK1250N 640÷1250 50 (1p) 50 (2p) 36 (3p) 36 (3p) = AC 1.2
FK1250N 640÷1250 60 (1p) 60 (2p) 60 (3p) 60 (3p) = AC 1.2
FK1250L 640÷1250 80 (1p) 80 (2p) 80 (3p) 80 (3p) = AC 1.2

D.18
Record Plus
Use at frequencies other
than 50/60 cycles

Performance characteristics of protective devices used in The breakers can be used at 16 2/3 (applications in rail
electrical distribution networks or systems vary transport) and 400hz (aviation) if the following is taken
according to the network's rated frequency. into account:
The Record PlusTM family of circuit breakers is designed a) The rated breaking capacity is decreased (1)
to offer their best performance at 50/60 Hz network. b) The device trip unit settings are modified

Use in special networks


Here the correct setting of the trip unit is vital to ensure
that the circuit breaker performs well in the electrical
distribution network.

Thermal magnetic trip units Electronic (SMR1) trip units

Record PlusTM breakers and their trip units can be used The breakers and their trip units can be used at
at 16 2/3 Hz and 400 Hz provided that the trip units are 400 Hz (aircraft) provided that the trip units are set
set accordingly.The table indicates the coefficients to accordingly.
be applied for 16 2/3 Hz and 400 Hz applications. The table indicates the coefficients to be applied for
16 2/3 Hz and 400 Hz applications.
Kt (for thermal)
Km (for magnetic) Kt (for LT)
Km (for ST)
The current values for each environment can be
calculated by multiplying the values set on the breaker The current values for each environment can be
by the coefiicients mentioned in the tables. calculated by multiplying the values set on the breaker
by the coefiicients mentioned in the tables.
A
Use in networks with a frequency of 16 2/3 and 400 cycles
Breaker Rated current Trip Unit type Thermal or LT settings Magnetic or ST settings B
Kt16 (16 2/3Hz) Kt400 (400 Hz) Km16 (16 2/3Hz) Km400 (400 Hz)

FD63N, H or L 8÷63 LTMD, GTM or MO 1 0.95 0.8 1.6


FD160N, H or L 64÷160 LTMD, GTM or MO 1 0.9 0.8 1.6
FE160N, H or L
FE160N, H or L
8÷63
64÷160
LTM, LTMD, GTM or MO
LTM, LTMD, GTM or MO
1
1
0.95
0.9
0.8
0.8
1.6
1.6
C
FE250N, H or L 80÷250 LTMD, GTM or MO 1 0.9 0.8 1.6
FE160N, H or L 10÷125 SMR1 1 1 1 1
FE160N, H or L 160 SMR1 1 0.9 1 1
FE250N, H or L
FE250N, H or L
40÷125
64÷250
SMR1
SMR1
1
1
1
0.9
1
1
1
1
D
FG400N, H or L 100÷400 SMR1 1 0.8 1 1
FG630N, H or L 160÷630 SMR1 1 0.8 1 1
FK800N, H or L 320÷800 LTM 1 0.6 1 1
FK1250N, H or L 400÷1250 LTM 1 0.6 1 1 E

Example thermal threshold is 160 x 0.9 = 144A at 40° F


A FE160N with LTMD 160A trip unit in a 400 Hz Thus the current in the circuit may not exceed this value
network: Im = 1200 ≥
(from the table Kt400 = 0.9 / Km400 = 1.6) the real magnetic threshold is 1120 x 1.6 = 1920A
If Ir is set at 160A and Im set at 1200A the real G
(1) Please consult us.

D.19
Just rel
Record Plus

E.3 Introduction The breaker


E.4 Protection against short-circuit

E.8 Personnel protection (direct and indirect contact) Order codes A


E.14 Selectivity/Discrimination

E.20 Back-up protection Trip units B


E.22 Selectivity Plus

E.25 Coordination with loadbreak disconnect switches


Components & Accessories C
E.26 Protection of motor circuits (coordination type 2)

E.34 Protection of LV/LV transformer


Technical data D
E.35 Protection of capacitor banks
Application guide E

Wiring diagrams F

Dimensions G

y on us
Numerical Index X

E.1
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application guide

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E.2
Record Plus
Introduction The breaker settings
The main breaker settings are :
- Overload protection or LT setting ... Ir
A protection device like the Record PlusTM circuit - Magnetic or ST setting …. Im
breaker is used in a wide variety of environments to
protect conductors, equipment and devices in low Ir setting
voltage distribution circuits. To use this product to its The HD 384 (IEC 364) installation regulations state that
full potential it is necessary to verify that it functions the Ir value is determined by use of the following two
correctly in the environment in which it is used and formulae:
that it meets the Electrotechnical requirements of the IB < Ir ≤ IZ
circuit it protects. It ≤ 1.45 x IZ
Terminology
Environment IB = Circuit design current

Application guide
Record PlusTM breakers function well in almost any Ir = Current set on breaker
industrial environment . The EN 60947-2 defines the IZ = Current carrying capacity of electrical conductor
It = Tripping current of the protection device
main aspects of what is meant by "industrial
(Record PlusTM MCCB It ≤ 1.3 x Ir)
environment":
Temperature:
Use of the above mentioned formulae and the
Relative humidity:
Record PlusTM characteristics give the following results:
Altitude:
Breaker setting Ir ≤ IZ (It ≤ 1.3 x IZ)
Pollution:
In practice Ir is generally set at a value equal to IZ.
Network harmonic content:
Shock and vibration resistance:
Im setting - protected equipment
For conditions other than the above mentioned please
The magnetic or ST setting of a breaker (Im) is primarily
refer to page D.16 in which the effects of the
defined by the characteristics of the equipment and
environment are defined.
devices in the circuit .
The Record PlusTM device is equipped with trip units
Maximum short-circuit current
that react to fault currents when needed but are
Protective devices as the Record PlusTM circuit breaker
specifically designed not to react to most inrush-
must be able to interrupt the maximum short-circuit
current at the point where they are installed.
current profiles. A
The details included in this section on devices as LV/LV
The interruption ratings of these breakers (breaking
transformers and the time current curves of the
capacity) can be found elsewhere in this catalog.
breaker published elsewhere in this catalogue allow a
definition of the Im value.
B
Design current of a circuit
The equipment and devices in an electrical circuit
Im setting - protected lines
determines it's current load. The electrical conductor
cross sections that can be used in the circuit are
On a short-circuit event the total circuit impedance C
determines the highest and the lowest current that can
determined by a number of factors i.e.
flow in the circuit . It is necessary not only to verify if
the protective device can interrupt the maximum
- The design current of the circuit (IB).
short-circuit value but also if the device protecting the D
- Conductor type and it's insulation.
circuit reacts and disconnects in time at the lowest
(current capacity = IZ)
possible short-circuit value.
- Installation method.
- Temperature.
Due to the fact that a major part of the circuit
impedance is formed by electrical conductors like
E
- Number of conductors mounted in each others
cables, busbar systems etc. within the circuit , this
vicinity.
requirement has a limiting effect on the length of the

The resulting combinations of current load and


conductors used in the circuit . F
electrical conductor cross sections are beyond the There are two conditions that have to be met:
scope of this catalogue, however a number of a) The weakest short-circuit current must be
frequently used values are: disconnected before the electrical conductors G
exceed their temperature limits.
b) A current to earth (fault current) must be
Conductor cross section 10mm2 25mm2 50mm2 70mm2 95mm2 disconnected before inadvertent contact to
normally non-conductive parts causes injury. X
IB with Cu conductors in A 50 90 130 170 210 Please refer to the pages E.6 and E.13 for more details.
IB with AL conductors in A 35 70 100 130 160

E.3
Record Plus
Protection against short-circuits

Maximum short-circuit ratings


Protective devices as the Record PlusTM circuit breaker Calculated maximum short-circuit values (3 phase 400V network)
must be able to interrupt the maximum short-circuit MV/LV Transformer(s) Medium Voltage power SKQ in MvA
current at the point where they are installed. SrT Ukr % 100 150 200 300 400 500
The interruption ratings of these breakers (breaking Maximum short-circuit Values in kA (Ik3max)
capacity) can be found elsewhere in this catalogue. 100 4 3.5 3.6 3.6 3.6 3.6 3.6
For the calculation of the short-circuit current at the 160 4 5.6 5.7 5.7 5.7 5.7 5.8
point where the breaker is installed a pan-European 250 4 8.5 8.7 8.8 8.9 8.9 9.0
315 4 10.6 10.9 11.0 11.1 11.2 11.2
document is now available in the form of the 400 4 13.2 13.6 13.8 14.0 14.2 14.2
Application guide

R064-003.The values published here are based on this 500 4 16.2 16.8 17.1 17.4 17.6 17.7
630 4 19.8 20.7 21.2 21.7 22.0 22.2
document .
630 5 16.3 16.9 17.2 17.6 17.7 17.8
630 6 13.8 14.3 14.5 14.7 14.8 14.9
Power supply 800 6 17.1 17.8 18.2 18.5 18.7 18.8
1000 6 20.8 21.8 22.3 22.9 23.2 23.4
The values mentioned in table indicate the effective 1250 6 25.1 26.6 27.4 28.3 28.7 29.0
values of the highest three phase short-circuit current 1600 6 30.6 32.9 34.2 35.6 36.3 36.8
that is available at the connection terminals of the 2000 6 36.4 39.7 41.6 43.6 44.7 45.4
2500 6 42.9 47.5 50.2 53.2 54.8 55.9
incoming transformer(s). 2 x 400 4 24.2 25.7 26.4 27.2 27.7 27.9
2 x 500 4 29.1 31.2 32.3 33.5 34.2 34.6
Incoming transformers 2 x 630 4 34.9 37.9 39.6 41.4 42.4 43.0
2 x 630 5 29.3 31.4 32.5 33.8 34.4 34.8
2 x 630 6 25.3 26.8 27.6 28.5 29.0 29.3
2 x 800 6 30.6 32.9 34.2 35.6 36.3 36.8
2 x 1000 6 36.4 39.7 41.6 43.6 44.7 45.4
2 x 1250 6 42.9 47.5 50.2 53.2 54.8 55.9
2 x 1600 6 50.7 57.3 61.3 65.9 68.4 70.0
2 x 2000 6 58.3 67.3 72.8 79.4 83.1 85.5
2 x 2500 6 66.3 78.1 85.7 94.9 100.3 103.9
3 x 400 4 33.6 36.4 37.9 39.6 40.5 41.1
A 3 x 500
3 x 630
4
4
39.7
46.8
43.7
52.3
45.9
55.6
48.5
59.4
49.8
61.4
50.7
62.7
3 x 630 5 40.0 43.9 46.2 48.8 50.2 51.0
3 x 630 6 34.9 37.9 39.6 41.4 42.4 43.0
3 x 800 6 41.6 46.0 48.5 51.3 52.8 53.8
B 3 x 1000
3 x 1250
6
6
48.6
56.1
54.6
64.3
58.2
69.3
62.3
75.3
64.6
78.6
66.0
80.8
Installation 3 x 1600 6 64.8 76.1 83.3 91.9 97.0 100.3
3 x 2000 6 72.9 87.5 97.2 109.2 116.4 121.2
3 x 2500 6 81.0 99.4 112.1 128.6 138.7 145.6
C Formulas
Medium voltage impedance
Terminology
(m Uo sqrt 3)2 SkQ = short-circuit power of the medium/high voltage
ZQ = mOhm
D SkQ
SrT
network
= power rating of the MV/LV transformer
MV/LV transformer impedance Ukr = short-circuit voltage in %, according to HD 398
m = no load factor; 1.05 assumed
(m Uo sqrt 3)2 Ukr Cmax. = voltage factor; 1.05 assumed
Zr = x mOhm
E SrT 100% Uo = phase to neutral voltage
Ik3max = maximum 3 phase short-circuit current
Maximum short-circuit calculation X = total reactance
XQ = 0.995 x ZQ
(cmax * m *Uo sqrt 3)2
F Ik3max =
Sqrt (R2 + X2)
kA XT
R
= 0.95 x ZT
= total resistance
RQ = 0.1 x XQ*
RT = 0.31 x ZT

G * See IEC 909

E.4
Record Plus
Influence of cable runs
It is possible to calculate short-circuit values within
circuits by determining the impedance, reactance and

Protection against short-circuit


resistance of the power supply and by adding those of
cable runs. These values are used here to calculate the Short-circuit values within circuits
maximum short-circuit levels at the end of a defined
cable run. Ik3 max. without IK3 max in kA at point where Record PlusTM MCCB
cable run is to be installed (This value must be ≤ Icu or Ics)

Values used 145 80 65 50 30 25 22 20 15 10 6


Specific resistance of copper and aluminum at 20°C 140 80 65 50 30 25 22 20 15 10 6
130 80 65 50 30 25 22 20 15 10 6
120 80 65 50 30 25 22 20 15 10 6
l0 = 18.51 m1 mm2/m. for copper cores 110 80 65 50 30 25 22 20 15 10 6
29.41 m1 mm2/m. for aluminum cores 100 65 65 50 30 25 22 20 15 10 6
90 65 65 50 30 25 22 20 15 10 6
80 65 50 50 30 22 20 20 15 10 6
Reactance of multicore cables h 0.08 m1 /m. 70 65 50 50 25 22 20 20 15 10 6
60 50 50 50 25 22 20 20 15 10 6
50 50 36 36 22 20 20 20 15 10 6
Examples 45 50 36 30 22 20 20 20 15 10 6
Ik3 max. at cable run start 50kA 40 36 36 30 20 20 20 15 15 10 6
35 30 30 25 20 20 15 15 15 10 6
54 meters of 185 mm2 cable 30 30 25 22 20 20 15 15 15 10 6
Ik3 max. at cable run end 22kA 25 22 22 20 15 15 15 15 10 10 6
20 - - - 15 15 15 15 10 10 6
15 - - - - - 10 10 10 10 6
Ik3 max. at cable run start 120kA 10 - - - - - - - - 6 6
12 meters of 185 mm2 cable
Ik3 max. at cable run end 80kA Cable cross section Required minimum length in meters of cable run of the mentioned
Cu mm2 AL mm2 cross section to achieve the Ik3 max mentioned above

1.5 0.5 0.5 0.5 1 1 1 1 1.5 2 3.5


2.5 4 0.5 0.5 0.5 1 1.5 1.5 1.5 2 3.5 5.5
4 6 0.5 0.5 1 1.5 2 2.5 2.5 4 5 9
6
10
10
16
1
1
1
2
1.5
2
2.5
4
3
5
3.5
5.5
3.5
6
5
8
8
13
13
21
A
16 25 1.5 2.5 3.5 6 8 9 10 13 20 35
25 35 2.5 4 5 9 12 13 15 20 32 55
35 50 3 4 7 13 16 18 20 28 42 70
50
70
70
95
4
6
6
8
9
12
18
24
22
30
25
35
29
40
39
55
60
85
100
135
B
2 x 35 2 x 50 6 8 13 25 32 36 40 55 85 140
95 150 7 11 16 32 39 46 51 70 110 180
2 x 50 2 x 70 8 12 18 35 44 52 58 80 120 200
120
150
185
240
9
10
13
15
19
23
38
46
48
58
55
66
62
75
85
100
130
155
220
255
C
2 x 70 2 x 95 11 16 24 50 60 70 80 110 170 270
185 12 18 27 54 65 76 84 116 180 300
240 14 21 32 32 78 88 98 135 210 340
2 x 95
300
2 x150 14
16
21
24
32
35
65
70
80
85
95
100
105
110
140
150
220
230
360
380
D
2 x120 2 x185 17 27 42 80 95 110 125 170 260 430
2 x150 20 30 48 91 115 135 150 200 310 510
3 x 95 3 x150 21 33 51 95 120 140 155 210 320 540
2 x185 23 35 53 105 130 155 170 235 360 590 E
3 x120 25 38 57 115 145 165 185 255 390 645
2 x240 28 41 62 125 155 180 200 270 410 675
3 x150 3 x240 30 45 68 140 170 200 220 300 460 765
3 x185 35 53 79 160 195 230 255 350 530 880
3 x240 41 80 125 185 230 265 295 410 620 F

E.5
Record Plus
Protection against short-circuits

Weakest short-circuit current


Maximum thermal stress in isolated conductors
It is necessary to verify that the permissible thermal (x 103) and k factors accordance with HD 384-5-54.
stress in conductors is not exceeded at the maximum
Insulation material K factor Rubber PVC XLPE EPR
short-circuit level and at the weakest short-circuit level. Copper conductors 134 115 143 143
Verification on the maximum short-circuit level is S in mm 2
Maximum thermal stress x 103
described on page E.4 of this catalogue. For the 1.5 40 30 46 46
weakest short-circuit value it is necessary to verify that 2.5 112 83 128 128
the protective devices as the Record PlusTM circuit 4 287 212 327 327
6 646 476 736 736
breaker trips before the conductors reach the 10 1796 1323 2045 2045
Application guide

mentioned limits. On using circuit breakers it is 16 4597 3386 5235 5235


25 11223 8266 12781 12781
generally sufficient to check if the weakest short-circuit
35 21996 16201 25050 25050
current trips the short-circuit protective element of the 50 44890 33063 51123 51123
device. 70 87984 64803 100200 100200
95 162053 119356 184552 184552
120 258566 190440 294466 294466
Permissible thermal stress in conductors 185 614544 452626 699867 699867
For insulated conductors and cables this is defined by 240 1034266 761760 1177862 1177862
300 1616040 1190250 1840410 1840410
the formula:
t ≤ K2 S2 Insulation material K factor Rubber PVC XLPE EPR
Ik2 Alumin. conductors 89 76 94 94
S in mm 2 3
Terminology Maximum thermal stress x 10
t = the short-circuit time in seconds 4 127 92 141 141
k = a factor determined by the conductor in accordance with 6 285 208 318 318
HD384-5-54 10 792 578 884 884
Ik = the weakest short-circuit current in A 16 2028 1479 2262 2262
25 4951 3610 5523 5523
S = the conductor cross section in mm2
35 9703 7076 10824 10824
50 19803 14440 22090 22090
A The table included here indicates the factor k for 70
95
38813
71487
28302
52128
43296
79745
43296
79745
conductors with different insulation materials and the
120 114062 83174 127238 127238
calculated energy values for the conductor cross 185 271096 197684 302412 302412
sections. 240 456250 332698 508954 508954
B 300 712890 519840 795240 795240

Weakest short-circuit current calculations


For the most commonly applied network configuration, Terminology
C 3 phase with neutral, the weakest short-circuit is the
Phase to Neutral value.
Ikmin = Weakest short-circuit current
0.8 = Assumed factor for the impedance of the upstream
The network configuration determines the value of this network
Cmin = Voltage factor; 0.95 assumed
current . Cases where the Phase to Earth or two Phase
Uo = Phase to neutral voltage
D value is the weakest are also commonplace. X = Reactance of the conductors or cables in the circuit
Basically, the weakest short-circuit current is reactance of multi core cables X in m1/m 0.08
determined by the highest impedance loop in the R = Resistance of the conductors or cables in the circuit
circuit that the breaker is protecting. based on the following basic data:
E Due to the simple fact that the impedance of this loop
23.69 m1 mm2/m. for copper cores*
37.64 m1 mm2/m. for aluminum cores*
is mainly determined by the conductors included in the The values are in accordance with the Cenelec R064-003 document
circuit , their maximum length is limited. An for calculating the weakest short-circuit current with circuit
F approximation of the effect of the conductor or cable breakers (warme state value)
k1, k2 k3 = Correction factors, see next page
length on the weakest short-circuit is possible by using
the following formula: * = 1.28 x 18.51 and 1.28 x 29.41.

G Ikmin= 0.8 x Cmin x Uo x k1 x k2 x k3 Amp


Sqrt(R2 + X2)

E.6
Record Plus

Maximum conductor length

Protection against short-circuit


To meet the requirements the short-circuit device of Maximum cable length in meters in a 3 phase + neutral
the circuit breaker (Im) must react to the weakest network (U0=230V) Based on multicore cables with an
EPR/XLPE insulation (worst case)
short-circuit current . The table indicates the maximum
cable length where this condition is still met . short-circuit setting of Record PlusTM device in Amps
Cu conductor
The tolerances on the settings of the short-circuit Cross section 50 75 100 125 150 200 250 300 350 400 450 500
S in mm2
device in the breaker are taken into account (factor 1.5 92 61 46 37 31 23
included in calculations of 1.2). 2.5 154 102 77 61 51 38 31 26 22 19 17 15
4 246 164 123 98 82 61 49 41 35 31 27 25
6 246 246 184 148 123 92 74 61 53 46 41 37
Correction factors k 10 246 307 246 205 154 123 102 88 77 68 61
For a 3 phase circuit with no neutral and a voltage of 16 393 327 246 196 164 140 123 109 98
25 393 511 383 306 255 219 191 170 153
400V between phases: 35 534 427 356 305 267 237 214
k1 = 1.74 50 534 606 505 433 379 337 303
70 698 598 524 465 419
95 698 795 695 618 556
For a single phase circuit with neutral and a voltage of 120 855 760 684
230V between phase and neutral: 150 855 914 823
185 914 965
k1 = 1.00
short-circuit setting of Record PlusTM device in Amps
For a 3 phase circuit with neutral, a voltage of 400V Cu conductor
Cross section 600 700 800 900 1000 1250 1500 1750 2000 2500 3000 3500
between phase and a neutral with 0.5 x the phase S in mm2
cross section: 2.5 13
4 20 18 15 14
k1 = 0.67 6 31 26 23 20 18 15 12
10 51 44 38 34 31 25 20 18 15 12
For a number of multi-core cables in parallel 16 82 70 61 55 49 39 33 28 25 20 16 14
25 128 109 96 85 77 61 51 44 38 31 26 22
k2 for 2 cores = 2.00 35 178 153 134 119 107 85 71 61 53 43 36 31
k2 for 3 cores = 2.65 50
70
253
349
217
299
189
262
168
233
152
209
121
168
101
140
87
120
76
105
61
84
51
70
43
60
A
95 464 397 348 309 278 222 185 159 139 111 93 79
For multicore cables with conductors made of 120 570 488 427 380 342 274 228 195 171 137 114 98
aluminum: 150 686 588 514 457 411 329 274 235 206 165 137 118
185
240
804
955
689
819
603
717
536
637
482
573
386
459
322
382
276
328
241
287
193
229
161
191
138
164
B
Cu conductor Cross section k3 300 926 810 720 648 518 432 370 324 259 216 185
S in mm2

= 4 ≤ 50
70
0.63
0.64
Cu conductor
short-circuit setting of Record PlusTM device in Amps
C
Cross section 4000 4500 5000 5500 6000 6500 7000 7500 8000 9000 10000 12000
95 0.65 S in mm2
120 0.66 16 12
150 0.67 25 19 17
185
240
0.69
0.72
35
50
27
38
24
34
21
30
19
28
18
25 23 22 20
D
300 0.76 70 52 47 42 38 35 32 30 28 26 23
95 70 62 56 51 46 43 40 37 35 31 28 23
150 85 76 68 62 57 53 49 46 43 38 34 28
185 103 91 82 75 69 63 59 55 51 46 41 34 E
185 121 107 96 88 80 74 69 64 60 54 48 40
240 143 127 115 104 96 88 82 76 72 64 57 48
300 162 144 130 118 108 100 93 86 81 72 65 54

E.7
Record Plus
Personnel protection
If, in low voltage installations, a person makes contact If, in a low voltage installation, a person comes into
with two or more conductive materials/ surfaces with a contact with an earthed part that has accidentally
different electrical potential he or she will risk a been connected to a live conductor, he or she will risk a
potentially dangerous electrical shock. potentially dangerous electrical shock.
This results in an electrical current flowing through the The level of voltage over the contact , and the length of
persons body, the effects of which are indicated in time that the person has to endure this contact can be
figure 1 and the accompanying text . dangerous. This so called 'Touch Voltage' must be
(source IEC 60479-1) limited to values that a human being can endure
without physiological damage.
The environment in which the fault occurs, dry or
Application guide

humid, also plays a role in defining 'touch voltage'


values.
The IEC 60479-1 standard defines numerous touch
voltages or UL values.

50V AC........In a dry environment


25V AC........In a humid environment

The IEC 60479-1 defines that this so called 'Touch


Voltage' must be disconnected within 5 seconds.
Based on the environment and the associated 'Touch
Voltage' maximum disconnect times are also specified
for a range of higher voltage value.

Maximum Disconnect times and touch Voltages


Zone Physiological effects

A 1 Usually has no reactions or effects.


Measured Voltage
U in Volts
Touch Voltage UL= 50V
Maximum Disconnect time (s)
2 Usually has no harmful effects. AC Voltage DC Network
3 Usually, no organic damage is expected.
Here the likelihood is present of muscular contractions and <50 5 5
B difficulty in breathing. Reversible disturbances in the
formation and conductance of impulses in the heart,
50
75
5
0.6
5
5
including arterial fibrillation and transient cardiac arrest 90 0.45 5
without ventricular fibrillation are possible. 120 0.34 5
These effects increase with current magnitude and time. 150 0.27 1
C 4 In addition to he effects of Zone 3, the probability of
ventricular fibrillation increases from 5% (curve c2) , to about
220
280
0.17
0.12
0.4
0.3
50% (curve c3) and beyond 50% above curve c3. Increasing 350 0.08 0.2
with magnitude and time are pathophysiological effects as 500 0.04 0.1
cardiac and breathing arrest, whilst heavy burns are possible.
D
The term Personnel protection, as used here, entails the
prevention of, or limitation of the effects of electrical
shocks that occur during one of two possible contact
E scenario's, direct and indirect .

E.8
Record Plus
Direct contact Indirect contact
Caused by an accident in which a person comes into Caused when person comes into contact with an
contact with a live electrical conductor and a second earthed part that has accidentally been connected to a
conductive part . Here the person in question becomes live conductor. The level of voltage over the contact ,
a part of the electrical circuit , the current in which is and the length of time that the person has to endure
determined by the resistance of the earth and that of this contact can be dangerous. This so called 'Touch
the human body. Voltage' must be limited to values that a human being
can endure without physiological damage.

Personnel protection
How to protect against? How to protect against?
The following methods can be used (source HD384) The following concepts can be applied (source HD384)
- The use of very low voltage systems as: - The use of very low voltage systems as:
SELV (safe, extra low voltage), PELV (protective extra SELV (safe, extra low voltage), PELV (protective extra A
low voltage) and low voltage) and
FELV (functional extra low voltage) FELV (functional extra low voltage)
- Appropriate conductor insulation. - Automatic disconnection of the power supply to the
- The use of mechanical barriers or that of enclosures installation, or a part thereof.
B
with the appropriate protection degree. (IP-) - The use of materials that provide total insulation
- Take the defined safety distances into account when (class II)
installing C
- The use of complementary protection, RCD's with a
sensitivity ≤ 30mA

- The use of a non conductive environment , i.e. All D


exposed conductive parts cannot be accessed or
touched in normal operational conditions.
Here the use of protective conductors is prohibited, E
whilst floor and walls must have a certain insulation
resistance. (Un<500V AC,
50 kOhm; Un >= 500V AC, 100 kOhm.)
- The use of equipotential bonding or links. These to F
avoid potential differences between normally non-
conductive materials/surfaces. These may not be
connected to earth.
G
- The use of LV/LV transformers with insulating
properties.
X

E.9
Record Plus
Record Plus TM circuit breakers, TT system characteristics
used to protect against direct , One point of the power supply is connected to earth
or indirect contact whilst all conductive parts in the installation are
connected to electrically independent earth electrodes.
As moulded case circuit breakers, Record PlusTM have
properties that automatically forfill a number of the
requirements concerning direct and indirect contact . L1
When installed correctly, with the appropriate L2
L3
cover/trim/front plates the device itself offers a high 1 N
protection degree of up to IP40 whilst the moulded
7
case housing construction ensures a class II protection.
3
Application guide

Direct contact
They can be equipped with RCD's of 30mA that are
required as a complementary protection. 5
4
6 6
Indirect contact
Ideally suited to be used as a device to allow automatic
disconnection of the supply of a part or a full 2

installation. This making use of one of three available


protection devices.
O
1 Power supply.
O
2 Power supply earthing (R N)
- A short-circuit protection that can be set over a wide
O
3 Low voltage installation, consumer portion.
range and normally can be set to detect most earth
O
4 Equipment present in installation.
fault currents.
O
5 Exposed conductive parts/surfaces.
- An optional RCD device that can detect earth fault
O
6 Installation earthing. (R A)
currents down to extremely low levels.
O
7 Optional RCD device.
- The larger frame size can be equipped with a ground
A fault protection device that can be set to detect If a fault to earth or insulation fault occurs, a circuit
medium to low earth fault currents. comes into being, in which the current runs through the
live conductor that has caused the fault and the two
earth electrodes RA and RB. On indirect contact the
B Protection against indirect touch voltage UL is directly dependant on the value of
the local earth electrode RA and the resistance of the
contact by automatic protective conductor by which it is connected.
C disconnection of the power The following formula is valid:
supply RA x IA ≤ UL
Use of the automatic disconnection of the power RA = Resistance of local electrode and it's
D supply concept requires that a number of elements is connecting protective conductor.
IA = With circuit breakers the short-circuit
taken into account in a coordinated manner, i.e.:
protective element of the device (magnetic
operating threshold of the protective device)
E - The characteristics of the network
(earthing system - TT, IT, TN as described). Due to the very low values of RA required by the
- The properties of the protective conductors. application of this rule the use of RCD's (see table
- The tripping threshold and disconnect time of the below) is widespread, and mandatory in several
F protective device. European countries. (IA is then replaced by the Idn of
- The properties of the environment . the RCD)

G This to ensure that the touch voltage does not exceed


the values of UL = 50V AC in a dry environment and
Touch
Examples of RA value based on
Voltage UL IA = 200A IA = 500A Idn 300mA Idn 1A Idn 3A
UL = 25V AC in a humid environment and that higher
25V 0.1251 0.051 831 251 81
voltages are disconnected within the perscribed 50V 0.251 0.011 1671 501 171
X maximum disconnect time.

E.10
Record Plus
TN system characteristics
One or more points of the power supply are connected If a fault to earth or insulation fault occurs, a circuit
to earth whilst all conductive parts in the installation comes into being, in which the current runs through the
are electrically connected to this point by protective live conductor that has caused the fault and the
conductors. (PE or PEN conductors). The system exits in protective conductor (PE or PEN). The fault circuit has a
three main variants: voltage equal to the phase to earth voltage U0 of the
TNC The neutral and protective conductor are system.
combined. (PEN) On indirect contact the touch voltage UL is not
TNS The neutral(N) and protective conductor (PE) exceeded if the following conditions are met
are separate.

Personnel protection
Zs x IA ≤ U0
TNCS The supply is configured as a TNC, the system
changes to a TNS system at a Zs = Impedance of the fault circuit .
pre-defined point in the LV installation. IA = The operating threshold of the protective
device, that warranties a total disconnection
time dependant on the phase to earth system
TNC voltage. (see table insert)
L1 U0 = The phase to earth voltage of the system.
L2
L3
1 PEN If the ZS value reaches high values due to long cable
7
runs the use of RCD's is allowed. (I A is then replaced by
8
the Idn of the RCD).
3

A second option is the use of a ground fault device.


In all cases the Interruption of the protective conductor
5 is prohibited.
4

The following disconnection times are mandatory:

2 6

Network voltage Maximum disconnecting time A


Phase-Neutral U0 (AC system)
O
1 Power supply.
O
2 Power supply earthing. 127V
230V
0.8 sec.
0.4 sec.
O
3 Low voltage installation, consumer portion.
400V 0.2 sec. B
O
4 Equipment present in installation. > 400V 0.1 sec.
O
5 Exposed conductive parts/surfaces.
O
6 Additional supply earthing.
O
7 Protective conductor combined with the neutral. C
O
8 Protective device.

TNS
L1
D
L2
L3
1 N

6
PE E
7

3
F
5
4
0
G
2

X
O
1 Power supply.
O
2 Power supply earthing.
O
3 Low voltage installation, consumer portion.
O
4 Equipment present in installation.
O
5 Exposed conductive parts/surfaces.
O
6 Protective conductor.
O
7 Protective device.

Remark : a TNCS system is not depicted

E.11
Record Plus
IT system characteristics Required calculations in TN and
The supply is isolated from earth or connected to earth
IT networks
by means of an impedance of a relatively high value. In both the IT and TN network configuration it is
The conductive parts in the installation are connected necessary to verify that the protective device will
to earth electrodes. interrupt the circuit within the defined disconnection
time. Here the worst case scenario needs to be taken
L1
L2
into account and the weakest possible current flowing
L3 in the circuit , on a insulation or earth fault must be
1
defined (The fault current If).
8

3 Here it is also necessary to establish that the protective


7
Application guide

device will disconnect within the time limits defined for


the different phase to phase and phase to neutral
5
network voltages, at this current level (Id). To determine
4
the fault current, the voltage of the circuit and it's
impedance must be known. The circuit impedance being
that of the upstream installation and that of the live and
6
protective conductor.
2

O
1 Power supply.
O
2 Power supply earthing. Use of Record Plus TM breakers in
O
3 Low voltage installation, consumer portion. this application
O
4 Equipment present in installation.
O
5 Exposed conductive parts/surfaces. Circuit breakers of the Record PlusTM type disconnect
O
6 Impedance for insulation from earth. within 0.1 seconds on their magnetic threshold (Im on
O
7 Insulation monitoring device + surge protection the electromechanical device) and within 0.2 seconds
O
8 Protective device. on their ST device (Im on the SMR1 electronic device*).
A To assure a disconnection that meets the requirements
On the first fault to earth or insulation fault in an IT the circuit fault current Id must be higher than the Im
system, the protective device does not need to react . value.
Here no fault circuit to earth exists and no potentially With the Im value and the system voltage it is now
B dangerous contact can occur. possible to calculate the maximum ZS value of the fault
However, depending on the location of the fault to circuit . This is mainly made up of the electrical
earth the first fault modifies the system from an conductors in the circuit , therefore these calculations
C isolated IT into a non isolated TN or TT system. result in a maximum cable run length.
To indicate that the IT system is no longer functional
the use of insulation monitoring devices providing a Formula for calculating the cable run length.
visual and sonorous alarm of the event is necessary.
D With the first fault still existing, a second fault to earth Lmax= 0.8 x
Cmin x _ x Uo
x k1 x k2 x k3 meters
must cause an automatic disconnection of the supply {2 x [= 3(R2 + X2)]} x (Im x kt)

that must meet the conditions and formulae set out for
E TT and TN systems indicated here. Terminology
The possible distribution of a neutral within the system Lmax = Maximum cable run length
does modify the allowed disconnection times as 0.8 = Assumed factor for the impedance of the upstream
indicated in the table below. network.
F Cmin. = Voltage factor; 0.95 assumed
_ = Coefficient depending on earthing system
TN = 1 IT no neutral = 0.86 IT with neutral = 0.5
Network voltage Maximum disconnecting time
(AC system) Uo = Phase to neutral voltage
Phase-Neutral U0 /
X = Reactance of the conductors or cables in the circuit.
G Phase-Phase Un
No neutral distributed Neutral distributed Reactance of multi core cables h m1 /m. 0.08
R = Resistance of the conductors or cables in the circuit.
127/230V 0.8 sec. 5 sec. based on the following basic data:
230/400V 0.4 sec. 0.8 sec.
l1 = 23.69 m1 mm2/m. for copper cores.*
400/690V 0.2 sec. 0.4 sec.
X 37.64 m1 mm2/m. for aluminum cores.*
Im x kt = Magnetic or ST setting of breaker (Im) x plus tolerance factor
Remark (kt[=1.2])
On a second insulation fault the protective device can be required to
k1-3 = Correction factor (see page with cable run calculations)
interrupt the full fault current in a circuit with a voltage equal to the
phase to phase value Un. The requirements for interrupting this single These being the values in accordance with the Cenelec
phase fault are now included in the EN 60947-2 (appendix H). Needless R064-003 document for calculating the weakest short-circuit
to say that the Record PlusTM breaker meet these requirements, the current with circuit breakers (worst case assumed)
exact single phase or I values are mentioned in the tables covering
IT
the technical data of the breaker.
* = 1.28 x 18.51 and 1.28 x 29.41.

E.12
Record Plus
Cable run length calculations Maximum cable length in meters in a 3 phase TN system
(U0=230V). For IT system see text, calculations based on
device muticore cables. (worst case)

To meet the requirements the short-circuit device (Im) Cu conductor short-circuit setting of Record PlusTM device in Amps

of the circuit breaker must react to a current equal or Cross section 50 75 100 125 150 200 250 300 350 400 450 500
S in mm2
lower than the fault current (If). 1.5 92 61 46 37 31 23
The table indicates the maximum cable lengths where 2.5 154 102 77 61 51 38 31 26 22 19 17 15
4 246 164 123 98 82 61 49 41 35 31 27 25
this condition is still met . This taking into account the 6 246 246 184 148 123 92 74 61 53 46 41 37
tolerances on the settings of the short-circuit device in 10 246 307 246 205 154 123 102 88 77 68 61
the breaker. (see factor kt [=1.2]) 16 393 327 246 196 164 140 123 109 98
25 393 511 383 306 255 219 191 170 153

Personnel protection
35 534 427 356 305 267 237 214
Correction factors _ 50 534 606 505 433 379 337 303
70 698 598 524 465 419
For TN networks and IT networks with different voltages 95 698 795 695 618 556
and with or without distributed neutral. 120 855 760 684
150 855 914 823
185 914 965
Neutral distributed
TN network
Uo/Un Yes No
_ _ Cu conductor short-circuit setting of Record PlusTM device in Amps
Cross section 600 700 800 900 1000 1250 1500 1750 2000 2500 3000 3500
127 /230V AC 0.55 1.00 S in mm2
230/400V AC 1.00 1.74 2.5 13
400/690V AC 1.74 3.00 4 20 18 15 14
6 31 26 23 20 18 15 12
10 51 44 38 34 31 25 20 18 15 12
16 82 70 61 55 49 39 33 28 25 20 16 14
Neutral distributed 25 128 109 96 85 77 61 51 44 38 31 26 22
IT network
Uo/Un Yes No 35 178 153 134 119 107 85 71 61 53 43 36 31
_ _ 50 253 217 189 168 152 121 101 87 76 61 51 43
70 349 299 262 233 209 168 140 120 105 84 70 60
127 /230V AC 0.28 0.49 95 464 397 348 309 278 222 185 159 139 111 93 79
230/400V AC 0.50 0.86 120 570 488 427 380 342 274 228 195 171 137 114 98
400/690V AC 0.87 1.48 150 686 588 514 457 411 329 274 235 206 165 137 118
185 804 689 603 536 482 386 322 276 241 193 161 138
240
300
955 819
926
717
810
637
720
573
648
459
518
382
432
328
370
287
324
229
259
191
216
164
185
A
Correction factor k1
For a 3 phase circuit with a voltage of 400V between TM
short-circuit setting of Record Plus device in Amps
Cu conductor
phases and a protective conductor with a cross section Cross section 4000 4500 5000 5500 6000 6500 7000 7500 8000 9000 10000 12000
S in mm2
B
smaller than the phase value.
16 12
25 19 17
Sph/Spe or pen k1 35 27 24 21 19 18
50
70
38
52
34
47
30
42
28
38
25
35
23
32
22
30
20
28 26 23
C
1.00 1.00 95 70 62 56 51 46 43 40 37 35 31 28 23
0.67 0.75 150 85 76 68 62 57 53 49 46 43 38 34 28
0.50 0.67 185 103 91 82 75 69 63 59 55 51 46 41 34
0.33 0.50 185
240
121
143
107
127
96
115
88
104
80
96
74
88
69
82
64
76
60
72
54
64
48
57
40
48
D
300 162 144 130 118 108 100 93 86 81 72 65 54

Correction factor k2
For a number multi core cables in parallel
E
k2 2 = 2.00
k2 3 = 2.65
F
Correction factor k3
For multicore cables with conductors made of
aluminium.
G
AL conductor k3
cross section
S in mm2
X
= 4 ≤ 50 0.63
70 0.64
95 0.65
120 0.66
150 0.67
185 0.69
240 0.72
300 0.76

E.13
Record Plus
Selectivity/Discrimination Fig. 1

Fig. 1 depicts a typical distribution network. Here


outgoing circuits are designed for the current load and
the characteristics of the equipment within the circuit.
Outgoing circuits that protect a certain area are placed
together in panels or form groups within panels.
Typically this group of circuits is protected by a second,
similar device, the characteristics of which are
determined in the same manner. This system can be
extended to a multiple level distribution network.
In case of a fault it is necessary that the device nearest
Application guide

to the fault reacts while all others remain closed.


This capability is called discrimination (UK) or selectivity
(USA and Europe). If this requirement is not met, a fault
(F) in one arm of the distribution system will cause a
number of upstream protection devices wired in series to
trip. Thus a minor fault in a socket outlet of a circuit can
cause whole floors, buildings or building complexes to be
cut off from the power supply.

Record PlusTM breakers are specifically designed to


discriminate. By introducing Record PlusTM. GE sets a new
standard in circuit breakers by offering total selectivity
for all normally proportioned distribution systems.

EN 60947-2 amendment 1, app. A defines under


“Coordination” that discrimination/selectivity may be
A partial up to a pre-defined current limit (Is).
Discrimination is considered total when the current
limit is equal to the rated short-circuit breaking
capacity (Icu or Ics) of the downstream device.
B Discrimination/Selectivity is determined by comparing
Fig. 2
the time it takes an upstream device to react at a
specific current value and - again - comparing this to
the time it takes a downstream device to clear the fault
C at the same current level. (see Fig. 2) The comparison of
these two time spans can be used to define whether
discrimination is present or not .
D We have simplified this comparison by applying a
multiplication factor between downstream and
upstream devices. With the values indicated in the
table we can guarantee discrimination.
E (see page E.15)

F 3D discrimination
Record PlusTM downstream-protection-device breakers
limit the energy and current in the protected circuit in a
G limited time frame. The use of relatively minor time
delays in the short-circuit protection of the upstream Fig. 3
breaker, allows the Record PlusTM line of circuit breakers
X to achieve total discrimination. Fig. 3 depicts this
comparison technique. In this graph the Grey area
indicates the time and current values the downstream
Msec.
breaker allows to flow in the circuit . The coloured area
depicts the current- and energy-reaction level of the
upstream device within a certain set time frame.

A2S
A

E.14
Record Plus
How to determine
discrimination/selectivity with
Record Plus TM (and associated
devices)

Table D1 to D5 (page E.16-E.19) indicate the discrimination up to the highest breaking capacity of the

Selectivity/Discrimination
discrimination levels that can be achieved with devices.
Record PlusTM and associated devices. Where These discrimination/selectivity limits are only valid if the
discrimination is partial the selectivity limits in kA (Is) are ratio between the current settings, ratings or time
mentioned in kA. settings of the upstream and downstream breaker are
Where a "T" is found in the tables, this indicates total equal or higher than the factor indicated here.

Selectivity/Discrimination
Downstream device Upstream device
Record PlusTM MCCB
LTM or LTMD SMR1, 1e, 1s or 1g SMR2
Redline & Hti MCB B, C & D curve Ir factor 1.6 Ir factor 2 Ir factor * 1.6
Im factor 2 Ist factor 1.5 Ist factor 1.5
Surion Manual Motor Starter Thermal mag or Mag. Only Ir factor 3 Ir factor 2 Ir factor * 1.6
Im factor 3 Ist factor 1.5 Ist factor 1.5
TM
Record Plus MCCB LTM or LTMD Ir factor 1.6 Ir factor 2 Ir factor * 1.6
Im factor 1.5 Ist factor 1.5 Ist factor 1.5
SMR1 Ir factor 1.6 Ir factor 1.6 Ir factor * 1.6
Im factor 1.5 Ist factor 1.5 Ist factor 1.5

SMR1, 1e, 1s or 1g SMR2

Record PlusTM MCCB SMR1s Ir factor 1.6 Ir factor 1.6


SMR2 LTD set at one class higher
Ist factor 1.5
LTD set at one class higher
IIst factor 1.5
A
STD Set at one band higher STD Set at one band higher
Inst. factor 1.5
A2S Set at one band higher

Mpact ACB
B
MPRO 17 MPRO 20, 30 & 40
Record PlusTM MCCB SMR1 Ir factor 1.6 Ir factor 1.6
Ist factor
STD timing
1.5
0.2
LTD Class
Ist factor
20
1.5
C
STD timing 0.2
A2S band 0.1
Record PlusTM MCCB SMR1s Ir factor 1.6 Ir factor 1.6
SMR2 Ist facto 1.5
STD Set at one band higher
LTD set at one class higher
Ist factor 1.5
D
STD Set at one band higher
2
A S Set at one band higher

E
* LTD set at class 20

Terminology
F
LTM Thermal magnetic Trip Unit
Ir = Overload setting Im = Magnetic setting
LTMD Selective Thermal magnetic Trip Unit
Ir = Overload setting Im = Magnetic setting
Mag. BreakTM Magnetic Only Trip Unit G
Im = Magnetic setting
SMR1 & SMR1e Selective Electronic Trip unit
Ir = Setting on LT device Ist = Setting on ST device
SMR1s,g and SMR2 Enhanced Electronic Trip unit
MPRO 17, 20, 30 & 40 Mpact Electronic Trip Units X
Ir = Setting on LT device Ist = Setting on ST device

LTD class, time setting at 7.2 x Ir STD Delay setting on ST device


A2S Cropped short time device delay setting
Inst . = Setting on I (Instantaneous) device

E.15
Record Plus
Table D1 - Selectivity/Discrimination
Record PlusTM type
Upstream
FD160E FD160S FD160N, H & L

In (A) 40 50 63 80 100 125 160 40 50 63 80 100 125 160 40 50 63 80 100 125 160
Downstream Selectivity limit in kA
Redline ≤16 0.6 2.5 T T T T T T T T T T T T T T T T T T T
G60 & DM60 20 0.6 2.5 3 T T T T 3.5 T T T T T T 3.5 T T T T T T
25 - 0.8 1.2 T T T T 1.6 3.5 T T T T T 1.6 3.5 T T T T T
C45 & C60 32 - - 1.2 3 T T T - - T T T T T - - T T T T T
40 - - - 3 4 T T - - - T T T T - - T T T T T
50 - - - 1.2 1.5 T T - - - 3.5 T T T - - - 3.5 T T T
63 - - - - 1.5 2 T - - - - T T T - - - - T T T
G100 & DM100 ≤16 0.6 2.5 6 6 T T T T T T T T T T T T T T T T T
20 0.6 2.5 2.5 6 8 T T 3.5 T T T T T T 3.5 T T T T T T
Application guide

25 - 0.8 1.2 6 6 T T 1.6 3.5 T T T T T 1.6 3.5 T T T T T


32 - - 1.2 3 6 8 T - - 6 6 T T T - 2.5 T T T T T
40 - - - 3 4 6 6 - - - 6 T T T - - T T T T T
50 - - - 1.2 1.5 6 6 - - - 3.5 8 T T - - - 3.5 T T T
63 - - - - 1.5 2 2 - - - - 8 T T - - - - 8 T T
GT25 B/C curve ≤16 0.6 2.5 6 6 10 T T 10 10 T T T T T 10 10 T T T T T
20 0.6 2.5 3 6 8 T T 3.5 10 T T T T T 3.5 10 T T T T T
25 - 0.8 1.2 6 6 10 T 1.6 3.5 15 15 T T T 1.6 3.5 15 15 T T T
32 - - 1.2 3 6 8 10 - - 6 6 10 T T - - 10 10 T T T
40 - - - 3 4 6 6 - - - 6 10 T T - - 10 10 15 T T
50 - - - 1.2 1.5 6 6 - - - 3.5 8 10 T - - - 3.5 10 T T
63 - - - - 1.5 2 2 - - - - 8 10 T - - - - 8 T T
Hti - B/C curve 80 - - - - - 1.9 1.9 - - - - - 2.5 2.5 - - - - - 2.5 2.5
100 - - - - - - 1.9 - - - - - - 2.5 - - - - - - 2.5
S90 - C curve ≤32 0.6 0.8 0.9 1.2 1.5 1.9 1.9 0.8 1 1.2 15 15 15 15 0.8 1 1.2 15 15 15 15
40 - - 0.9 1.2 1.5 1.9 1.9 - - 1.2 15 15 15 15 - - 1.2 15 15 15 15
50 - - - 1.2 1.5 1.9 1.9 - - - 15 15 15 15 - - - 15 15 15 15
63 - - - - 1.5 1.9 1.9 - - - - 15 15 15 - - - - 15 15 15
80 - - - - - 1.9 1.9 - - - - - 15 15 - - - - - 15 15
100 - - - - - - 1.9 - - - - - - 15 - - - - - - 15
Surion ≤20 0.6 2.5 6 6 10 T T 10 10 T T T T T T T T T T T T
GPS1BS & GPS1MS 25 0.6 1 1.2 6 6 10 T 1.6 3.5 15 15 T T T 1.6 3.5 T T T T T
A GPS2BS & GPS2MS 32
40
-
-
1
-
1.2
1.2
3
3
6
4
8
6
10
6
-
-
-
-
6
-
6
6
10
10
T
T
T
T
-
-
2.5
-
T
T
T
T
T
T
T
T
T
T
50 - - - 1.2 1.6 6 6 - - - 3.5 8 10 T - - - 3.5 T T T
63 - - - - 1.6 2 2 - - - - 8 10 T - - - - 8 T T
Surion ≤20 T T T T T T T T T T T T T T T T T T T T T
B GPS1BH & GPS1MH
GPS2BH & GPS2MH
25
32
-
-
2.5
-
15
6
15
6
T
8
T
10
T
T
-
-
3.5
-
15
6
15
15
T
10
T
T
T
T
-
-
3.5
-
15
6
15
15
T
10
T
T
T
T
40 - - - 6 8 10 T - - - 6 10 T T - - - 6 10 T T
50 - - - - 6 8 T - - - - 8 10 T - - - - 8 10 T
63 - - - - - 8 T - - - - - 10 T - - - - - 10 T
C Record PlusTM
FD160E
≤25
32
0.4
-
0.5
0.5
0.6
0.6
0.8
0.8
1
1
1.3
1.3
1.3
1.3
0.6
-
0.8
0.8
0.9
0.9
1.2
1.2
1.5
1.5
3.5
3.5
3,5
3.5
0.6
-
0.8
0.8
0.9
0.9
1.2
1.2
1.5
1.5
3.5
3.5
3.5
3.5
40 - - 0.6 0.8 1 1.3 1.3 - - 0.9 1.2 1.5 3.5 3.5 - - 0.9 1.2 1.5 3.5 3.5
50 - - - 0.8 1 1.3 1.3 - - - 1.2 1.5 3.5 3.5 - - - 1.2 1.5 3.5 3.5
63 - - - - 1 1.3 1.3 - - - - 1.5 3.5 3.5 - - - - 1.5 3.5 3.5
D 80 - - - - - - 1.3 - - - - - - 3.5 - - - - - - 3.5

* T = Total: selective unil the lowest Icu value of the two devices placed in series.

E.16
Record Plus
Table D2 - Selectivity/Discrimination
Record PlusTM type
Upstream
FE160N, H & L - LTM FE160N, H & L - LTMD FE160N, H & L - SMR1 FE250N, H & L - LTMD FE250N, H & L - SMR1

In (A) 63 80 100 125 160 100 125 160 63 125 160 125 160 200&250 125 160 250
Downstream Selectivity limit in kA
Redline ≤20 T T T T T T T T T T T T T T T T T
G60 & DM60 25 1.2 T T T T T T T T T T T T T T T T

Selectivity/Discrimination
32 1.2 3 T T T T T T T T T T T T T T T
C45 & C60 40 - 3 4 T T T T T - T T T T T T T T
50 - 1.2 1.5 T T T T T - T T T T T T T T
63 - - 1.5 2 T - T T - T T T T T T T T
G100 & DM100 ≤16 6 6 T T T T T T T T T T T T T T T
20 2.5 6 8 T T T T T T T T T T T T T T
25 1.2 6 6 T T T T T T T T T T T T T T
32 1.2 3 6 8 T T T T T T T T T T T T T
40 - 3 4 6 6 T T T T T T T T T T T T
50 - 1.2 1.5 6 6 T T T - T T T T T T T T
63 - - 1.5 2 2 - T T - T T T T T T T T
GT25 B/C curve ≤16 6 6 10 T T T T T T T T T T T T T T
20 2.5 6 8 T T T T T T T T T T T T T T
25 1.2 6 6 10 T T T T T T T T T T T T T
32 1.2 3 6 8 10 T T T T T T T T T T T T
40 - 3 4 6 6 T T T T T T T T T T T T
50 - 1.2 1.5 6 6 T T T - T T T T T T T T
63 - - 1.5 2 2 - T T - T T T T T T T T
Hti - B/C curve 80 - - - 1 2 - T T - T T - T T - T T
100 - - - - 2 - - T - - T - T T - T T
125 - - - - - - - T - - T - - T - - T
S90 - C curve ≤32 0.6 0.8 0.95 1.2 1.5 T T T T T T T T T T T T
40 - - 0.9 1.2 1.5 T T T T T T T T T T T T
50 - - - 1.2 1.5 T T T - T T T T T T T T
63 - - - - 1.5 - T T - T T T T T T T T
80 - - - - 1.5 - T T - T T - T T - T T
100 - - - - - - - T - - T - T T - T T
Surion ≤20 0.6 3 6 6 10 T T T T T T T T T T T T
GPS1BS & GPS1MS 25 0.6 3 6 6 10 T T T T T T T T T T T T
GPS2BS & GPS2MS 32
40
0.6
0.6
3
1
3
1
6
6
8
6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A
50 - 1 1 3 6 T T T - T T T T T T T T
63 - - 1 3 4 - T T - T T T T T T T T
Surion ≤20 0.6 2.5 6 6 10 T T T T T T T T T T T T
GPS1BH & GPS1MH
GPS2BH & GPS2MH
25
32
0.6
0.6
2.5
2.5
6
3
6
6
10
8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B
40 0.6 1 1.2 6 6 T T T T T T T T T T T T
50 - 1 1.2 2.5 6 T T T - T T T T T T T T
63 - - 1.2 2.5 6 - T T - T T T T T T T T
Record PlusTM
FD160E
≤40
50
0.6
-
1
1
1
1
1
1
2
2
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
C
63 - - 1 1 2 T T T - T T T T T T T T
80 - - - 1 2 - T T - T T T T T T T T
100 - - - - 2 - - T - - T - T T - T T
125
160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
T
-
-
-
-
-
T
-
-
-
-
-
T
T
-
-
-
-
T
T
D
TM
Record Plus ≤40 0.63 0.8 1 1.25 1.6 30 30 30 36 36 36 42 42 42 50 50 50
FD160S 50 - 0.8 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50
FD160N 63 - - 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50
FD160H 80 - - - 1.25 1.6 - 30 30 - 36 36 42 42 42 50 50 50 E
FD160L 100 - - - - 1.6 - - 30 - - 36 - 42 42 - 50 50
125 - - - - - - - - - - - - - 42 - - 50
160 - - - - - - - - - - - - - 42 - - 50
Record PlusTM ≤40 0.6 0.8 1 1.25 1.6 30 30 30 36 36 36 42 42 42 50 50 50
FE160N LTM 50 - 0.8 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50 F
FE160H LTM 63 - - 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50
FE160L LTM 80 - - - 1.25 1.6 - 30 30 - 36 36 42 42 42 - 50 50
100 - - - - 1.6 - - 30 - - 36 - 42 42 - 50 50
125 - - - - - - - - - - 36 - - 42 - - 50
G
* T = Total: selective unil the lowest Icu value of the two devices placed in series.

E.17
Record Plus
Table D3 - Selectivity/Discrimination
Record PlusTM type
Upstream
FE160N,H&L - SMR1 FE250N,H&L - LTMD FE250N,H&L - SMR1 FG400/630N, H&L - SMR1 & SMR2(1)

In (A) 63 125 160 125 160 200&250 125 160 250 400/250 400/350 400/400 630/400 630/500 630/630
Downstream Selectivity limit in kA
Redline
G60 B/C curve ≤40 T T T T T T T T T T T T T T T
G100 B/C curve 50 - T T T T T T T T T T T T T T
GT25 B/C curve 63 - T T - T T - T T T T T T T T
Hti - B/C curve ≤80 - - T - T T - T T T T T T T T
100 - - T - T T - T T T T T T T T
125 - - - - - T - - T T T T T T T
S90 - C curve ≤40 T T T T T T T T T T T T T T T
50 - T T T T T T T T T T T T T T
Application guide

63 - T T T T T T T T T T T T T T
80 - - T - T T - T T T T T T T T
100 - - - - - T - - T T T T T T T
Surion ≤40 T T T T T T T T T T T T T T T
GPS1BS & GPS1MS 50 - T T T T T T T T T T T T T T
GPS2BS & GPS2MS 63 - T T T T T T T T T T T T T T
GPS1BH & GPS1MH ≤40 - T T T T T T T T T T T T T T
GPS2BH & GPS2MH 50 - T T T T T T T T T T T T T T
63 - T T T T T T T T T T T T T T
Record PlusTM ≤32 T T T T T T T T T T T T T T T
FD160E 40 T T T T T T T T T T T T T T T
FD160S 50 - T T T T T T T T T T T T T T
LTM 63 - T T T T T T T T T T T T T T
80 - T T T T T T T T T T T T T T
100 - - T - T T - T T T T T T T T
125 - - - - - T - - T T T T T T T
160 - - - - - T - - T T T T T T T
Record PlusTM ≤32 T T T T T T T T T T T T T T T
FD160 N, H & L 40 36 36 36 42 42 42 50 50 50 T T T T T T
LTMD & MO 50 - 36 36 42 42 42 50 50 50 T T T T T T
63 - 36 36 42 42 42 50 50 50 T T T T T T
80 - 36 36 42 42 42 50 50 50 T T T T T T
A 100
125
-
-
-
-
36
-
-
-
42
-
42
42
-
-
50
-
50
50
T
T
T
T
T
T
T
T
T
T
T
T
160 - - - - - 42 - - 50 T T T T T T
Record PlusTM ≤32 36 36 36 42 42 42 50 50 50 T T T T T T
FE160 N, H & L 40 36 36 36 42 42 42 50 50 50 T T T T T T
B LTM & MO 50
63
-
-
36
36
36
36
42
42
42
42
42
42
50
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
T
T
80 - 36 36 - 42 42 - 50 50 T T T T T T
100 - - 36 - 42 42 - 50 50 T T T T T T
125 - - - - - 42 - - 50 - T T T T T
C Record PlusTM
160
≤32
-
0.8
-
1.8
-
2.2
-
1.3
-
1.6
42
2.5
-
1.8
-
2.2
50
3.5
-
T
T
T
T
T
T
T
T
T
T
T
FE160 N, H & L 40 0.8 1.8 2.2 1.3 1.6 2.5 1.8 2.2 3.5 T T T T T T
LTMD 50 - 1.8 2.2 - 1.6 2.5 - 2.2 3.5 T T T T T T
SMR1 63 - 1.8 2.2 - 1.6 2.5 - 2.2 3.5 T T T T T T
D 80
100
-
-
-
-
2.2
2.2
-
-
1.6
1.6
2.5
2.5
-
-
2.2
2.2
3.5
3.5
T
T
T
T
T
T
T
T
T
T
T
T
125 - - - - - 2.5 - - 3.5 T T T T T T
160 - - - - - 2.5 - - 3.5 T T T T T T
Record PlusTM 125 - - - - - 2.5 - - 3.5 15 15 15 T T T
E FE250 N, H & L 160 - - - - - - - - - - 15 15 T T T
LTMD 200 - - - - - - - - - - 15 15 T T T
SMR1 250 - - - - - - - - - - 15 15 T T T
Record PlusTM 250 - - - - - - - - - - - - 6 6 6
FG400 N, H & L 350 - - - - - - - - - - - - - 6 6
F SMR1 400 - - - - - - - - - - - - - - 6

* T = Total: selective unil the lowest Icu value of the two devices placed in series.
(1) ...../..... = Contact rating/Sensor rating
G

E.18
Record Plus
Table D4 - Selectivity/Discrimination
Record PlusTM type
Upstream
FK800N&H SMR1 FK800L SMR1 FK1250N&H SMR1 FK1250L SMR1 FK1600N&H SMR

In (A) 800 800 1000 1250 1000 1250 1600


Downstream Selectivity limit in kA
Redline
G60/100/GT25 All T T T T T T T

Selectivity/Discrimination
Surion
GPS All T T T T T T T
Hti All T T T T T T T
S90 All T T T T T T T
Record PlusTM
FD160 E, S, N, H & L All T T T T T T T
FE160N, H and L All T T T T T T T
FE250 N, H & L All T T T T T T T
FG400 N, H & L All T T T T T T T
FG630N, H & L All 25 25 T T T T T
FK800 N, H & L All - - 15 15 15 15 25
FK1250 N, H & L All - - - - - - 25

* T = Total: selective until the Icu of the downstream device OR the Icu of the upstream device

Table D5 - Selectivity/Discrimination
M Pact ACB type
Upstream
Frame1 N and H type Frame2 N and H type

In (A) 400 800 1000 1250 1600 2000 2500 1000 1250 1600 2000 2500 3200 4000
Downstream Selectivity limit in kA
Redline
G60/100/GT25 All T T T T T T T T T T T T T T
Surion
GPS All T T T T T T T T T T T T T T
Hti
S90
All T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A
Record PlusTM
FD160 E, S, N, H & L All T T T T T T T T T T T T T T
FE160 N, H & L All T T T T T T T T T T T T T T
FE250 N, H & L
FG400 N, H & L
All
250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B
350 - T T T T T T T T T T T T T
400 - T T T T T T T T T T T T T
FG630 N, H & L 400 - T T T T T T T T T T T T T
500
630
-
-
-
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
C
FK800 N, H & L All - - - T T T T T T T T T T T
FK1250 N, H & L 1000 - - - - T T T - T T T T T T
1250 - - - - - T T - - T T T T T
FK1600 N and H
Mpact ACB
1600
400
-
-
-
T
-
T
-
T
-
T
T
T
T
T
-
T
-
T
-
T
T
T
T
T
T
T
T
T
D
Frame 1 800 - - - T T T T - T T T T T T
Frame 2 1000 - - - - T T T - - T T T T T
1250 - - - - - T T - - - T T T T
1600 - - - - - - T - - - - T T T E
2000 - - - - - - T - - - - - T T
2500 - - - - - - - - - - - - - T

* T = Total: selective until the Icu of the downstream device OR the Icu of the upstream device F

E.19
Record Plus
Back-up protection
One of the operational requirements for a protective
device is that its rated short-circuit breaking capacity
Icu or Ics is either equal or greater than the prospective
short-circuit current at the point where it is installed.
EN 60384 defines one exception to this in clause 434:

The upstream device must posses the necessary rated


short-circuit breaking capacity at its point of installation.
The upstream device must coordinate with the
downstream device in a manner that will limit the energy
Application guide

and short-circuit values to levels that the downstream


device can handle.

Use of current limitation


Installing an upstream device that limits the prospective
short-circuit values will enable the user to place a
downstream device with a lower breaking capacity.
The coordination between the two devices allows
excellent breaking capacity at a low cost.
A
Record PlusTM
The Record PlusTM rotating dual contact configuration
B limits the energy and current values of prospective faults
to extremely low values. This key design feature allows
the use of cost-effective downstream devices while
C maintaining overall system protection.
Back-up protection is inherently „unselective“ or
„non-discriminating“. That means that the upstream
device must react first in order to protect the
D downstream device. However, the Record PlusTM devices
are so current limiting that the current and energy
values present in the circuit do not trip the upstream
breaker. Please refer to the details on „Selectivity Plus“
E for a description of this technique.

The tables B1 and B2 are in complete accordance with


F the EN 60947-2 requirements and have been verified
through experiment where necessary. They provide data
for the Record PlusTM breaker and the other
GE Power Controls/Industrial Systems product lines.
G The values are only applicable for the devices
mentioned.

E.20
Record Plus
Table B1 - Back-up protection at 230/240V
Record PlusTM type
Upstream

FK1250N

FK1600N
FK1250H

FK1600H
FD63/160N

FD63/160H
FD63/160E

FK1250L
FD63/160S

FD63/160L

FG400N

FG630N
FG400H

FG630H

FK800N

FK800H
FE160N

FE250N
FE160H

FE250H

FG400L

FG630L

FK800L
FE160L

FE250L
Icu

Downstream In (A) 36 50 85 100 200 85 100 200 85 100 200 85 100 200 85 100 200 80 100 170 80 100 170 80 100
Icu of the combination in kA
Redline
C30 3 4.5 6 8 10 12 8 10 12 4.5 6 8 - - - - - - - - - - - - - -
C60 & DME60 6 10 12 15 18 22 15 18 22 10 12 15 - - - - - - - - - - - - - -
G60 & DM60 6 22 25 36 85 85 36 85 85 36 50 50 16 16 16 14 14 14 - - - - - - - -
G100 & DM100 10 30 36 50 100 100 50 100 100 50 65 65 22 22 22 16 16 16 - - - - - - - -
GT25 ≤25A 25 36 50 85 100 100 85 100 100 85 85 85 - - - - - - - - - - - - - -

Back-up protection
GT25 32 & 40A 20 30 36 65 100 100 65 100 100 65 85 85 - - - - - - - - - - - - - -
GT25 50 & 63A 15 25 30 50 100 100 50 100 100 50 65 65 - - - - - - - - - - - - - -
Hti 15 25 30 50 100 100 50 100 100 50 65 65 - - - - - - - - - - - - - -
S90 25 36 50 85 100 100 85 100 100 85 85 85 - - - - - - - - - - - - - -
Surion
GPS1A ≤16A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS1A >16A 50 - - 85 100 150 - 100 150 - 100 150 - - - - - - - - - - - - - -
GPS1HA all 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2A ≤16A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2A >16A 50 - - 85 100 150 - 100 150 - 100 150 - - - - - - - - - - - - - -
GPS2HA all 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
Record PlusTM
FD160E 36 - 50 65 85 100 65 85 100 65 85 100 65 85 100 65 85 100 - - - - - - - -
FD160S 50 - - - 85 100 - 85 100 - 85 100 - 85 100 - 85 100 - - - - - - - -
FD160N 85 - - - 100 200 - 100 200 - 100 200 - 100 200 - 100 200 80 100 150 80 100 150 80 100
FD160H 100 - - - - 200 - - 200 - - 200 - - 200 - - 200 - 100 150 - 100 150 - 100
FE160N 85 - - - - - - 100 200 - 100 200 - 100 200 - 100 200 80 100 150 80 100 150 80 100
FE160H 100 - - - - - - - 200 - - 200 - - 200 - - 200 - 100 150 - 100 150 - 100
FE250N 85 - - - - - - - - - 100 200 - 100 200 - 100 200 80 100 150 80 100 150 80 100
FE250H 100 - - - - - - - - - - 200 - - 200 - - 200 - 100 150 - 100 150 - 100
FG400N 85 - - - - - - - - - - - - 100 200 - 100 200 80 100 150 80 100 150 80 100
FG400H 100 - - - - - - - - - - - - - 200 - - 200 - 100 150 - 100 150 - 100
FG630N 85 - - - - - - - - - - - - - - - 100 200 80 100 150 80 100 150 80 100
FG630H 100 - - - - - - - - - - - - - - - - 200 - 100 150 - 100 150 - 100
FK800N
FK800H
80
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
- 80 100 150 80 100 150 80 100
- - 100 170 - 100 170 - 100
A
FK1250N 80 - - - - - - - - - - - - - - - - - 80 100 170 80 100 170 80 100
FK1250H 100 - - - - - - - - - - - - - - - - - - 100 170 - 100 170 - 100

Table B2 - Back-up protection at 400/415V B


Record PlusTM type
Upstream
FK1250N

FK1600N
FK1250H

FK1600H
FD63/160N

FD63/160H
FD63/160E

FK1250L
FD63/160S

FD63/160L

FG400N

FG630N
FG400H

FG630H

FK800N

FK800H
FE160N

FE250N
FE160H

FE250H

FG400L

FG630L

FK800L
FE160L

FE250L

Icu C
Downstream In (A) 25 30 50 80 150 50 80 150 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
Icu of the combination in kA
Redline
G60 & DM60 6 15 22 30 36 40 30 36 40 22 30 36 12 12 12 10 10 10 - - - - - - - -
D
G100 & DM100 10 15 25 36 40 50 36 40 50 25 36 40 22 22 22 16 16 16 - - - - - - - -
GT25 ≤25A 25 - 30 40 50 65 40 50 65 30 40 40 - - - - - - - - - - - - - -
GT25 32 & 40A 20 - 30 36 40 50 36 40 50 30 36 40 - - - - - - - - - - - - - -
GT25 50 & 63A 15 - 25 36 40 50 36 40 50 25 36 40 - - - - - - - - - - - - - - E
Hti 10 15 25 36 40 50 36 40 50 25 36 36 - - - - - - - - - - - - - -
S90 15 - 25 36 40 50 36 40 50 25 36 40 - - - - - - - - - - - - - -
Surion
GPS1A ≤10A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS1A 12.5A 50 - - - 80 150 - 80 150 - 80 150 - - - - - - - - - - - - - - F
GPS1A ≥16A 25 - - 40 50 65 40 50 65 40 50 65 - - - - - - - - - - - - - -
GPS1HA ≤12.5A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS1HA >12.5A 50 - - - 80 150 - 80 150 - 80 150 - - - - - - - - - - - - - -
GPS2A 10A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2A > 10A 25 - - 40 50 65 40 50 65 40 50 65 - - - - - - - - - - - - - - G
GPS2HA 10A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2HA > 10A 50 - - - 80 150 - 80 150 - 80 150 - - - - - - - - - - - - - -
Record PlusTM
FD160E 25 - 30 36 42 50 36 42 50 36 42 50 36 42 50 36 42 50 - - - - - - - -
FD160S 36 - - 42 50 65 42 50 65 42 50 65 42 50 65 42 50 65 - - - - - - - - X
FD160N 50 - - - 80 150 - 80 150 - 80 150 - 80 150 - 80 150 - 80 100 - 80 100 - 80
FD160H 80 - - - - 150 - - 150 - - 150 - - 150 - - 150 - - 100 - - 100 - -
FE160N 50 - - - - - - 80 150 - 80 150 - 80 150 - 80 150 - 80 100 - 80 100 - 80
FE160H 80 - - - - - - - 150 - - 150 - - 150 - - 150 - - 100 - - 100 - -
FE250N 50 - - - - - - - - - 80 150 - 80 150 - 80 150 - 80 100 - 80 100 - 80
FE250H 80 - - - - - - - - - - 150 - - 150 - - 150 - - 100 - - 100 - -
FG400N 50 - - - - - - - - - - - - 80 150 - 80 150 - 80 100 - 80 100 - 80
FG400H 80 - - - - - - - - - - - - - 150 - - 150 - - 100 - - 100 - -
FG630N 50 - - - - - - - - - - - - - - - 80 150 - 80 100 - 80 100 - 80
FG630H 80 - - - - - - - - - - - - - - - - 150 - - 100 - - 100 - -
FK800N 50 - - - - - - - - - - - - - - - - - - 80 100 - 80 100 - 80
FK800H 80 - - - - - - - - - - - - - - - - - - - 100 - - 100 - -
FK1250N 50 - - - - - - - - - - - - - - - - - - 80 100 - 80 100 - 80
FK1250H 80 - - - - - - - - - - - - - - - - - - - 100 - - 100 - -

E.21
Record Plus
Application guide
Selectivity Plus

Back-up protection requires an upstream device to open in the rated short-circuit breaking capacity of the downstream
order to protect the downstream device(s) before the down- breaker.
stream devices can be damaged. For continuity of service it is Tables DB1 to DB5 provide the data for the
desirable that the upstream device remains closed and that Record PlusTM breaker line used in combination with the
only the downstream device closest to the fault reacts. ElfaPlus, Surion and MPact protection devices. The values in
The Record PlusTM family of breakers resolves this paradox: the the table are in kA and indicate the results of the Selectivity
breakers are so current limiting that let-through energy and Plus technique.
current are not sufficient to operate the upstream breaker. Before the slash the discrimination limit in kA, after the slash
Application guide

The result discrimination to current levels that are higher than the back-up protection value at 400V in kA (e.g. 50/80).

Table DB1 - Selectivity Plus


Record PlusTM type
Upstream
FD160N - LTMD FD160H - LTMD FD160L - LTMD

In (A) 63 80 100 125 160 63 80 100 125 160 63 80 100 125 160
Downstream Selectivity limit in kA / Maximum Icu of combination at 400/415V ac
Redline ≤20 16/16 16/16 16/16 16/16 16/16 22/22 22/22 22/22 22/22 22/22 25/25 25/25 25/25 25/25 25/25
G30 B/C curve 25 15/16 15/16 16/16 16/16 16/16 15/22 15/22 22/22 22/22 22/22 15/25 15/25 25/25 25/25 25/25
32 10/16 10/16 16/16 16/16 16/16 10/22 10/22 22/22 22/22 22/22 10/25 10/25 25/25 25/25 25/25
40 - 10/16 15/16 16/16 16/16 - 10/22 22/22 22/22 22/22 - 10/25 15/25 25/25 25/25
50 - - 10/16 16/16 16/16 - - 22/22 22/22 22/22 - - 10/25 22/25 22/25
63 - - - 16/16 16/16 - - - 22/22 22/22 - - - 22/25 22/25
G60 B/C curve ≤20 25/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36
25 15/25 15/25 25/25 25/25 25/25 15/30 30/30 30/30 30/30 30/30 22/36 30/36 30/36 30/36 30/36
32 10/25 10/25 25/25 25/25 25/25 10/30 30/30 30/30 30/30 30/30 16/36 25/36 25/36 25/36 25/36
A 40
50
-
-
10/25
-
15/25
10/25
25/25
22/25
25/25
22/25
-
-
22/30
-
30/30
22/30
30/30
22/30
30/30
22/30
-
-
22/36 25/36 25/36 25/36
- 22/36 22/36 22/36
63 - - - 22/25 22/25 - - - 22/30 22/30 - - - 22/36 22/36
G100 B/C curve ≤20 25/30 30/30 30/30 30/30 30/30 30/36 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 36/42
25 15/30 15/30 30/30 30/30 30/30 15/36 15/36 30/36 30/36 30/36 15/42 15/42 30/42 30/42 30/42
B 32
40
10/30
-
10/30
10/30
30/30
15/30
30/30
25/30
30/30
25/30
10/36
-
10/36
10/36
25/36
15/36
25/36
25/36
25/36
25/36
10/42 10/42 25/42 25/42 25/42
- 10/42 15/42 25/42 25/42
50 - - 10/30 22/30 22/30 - - 10/36 22/36 22/36 - - 10/42 22/42 22/42
63 - - - 22/30 22/30 - - - 22/36 22/36 - - - 22/42 22/42
GT25 B/C curve ≤20 30/36 36/36 36/36 36/36 36/36 30/42 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50 36/50
C 25
32
15/36
10/36
15/36
10/36
30/36
30/36
30/36
30/36
30/36
30/36
15/42
10/42
15/42
10/42
30/42
30/42
30/42
30/42
30/42
30/42
15/50 15/50 30/50 30/50 30/50
10/50 10/50 30/50 30/50 30/50
40 - 10/36 15/36 25/36 25/36 - 10/42 15/42 25/42 25/42 - 10/50 15/50 25/50 25/50
50 - - 10/36 22/36 22/36 - - 10/42 22/42 22/42 - - 10/50 22/50 22/50
63 - - - 22/36 22/36 - - - 22/42 22/42 - - - 22/50 22/50
D Surion
GPS1BA
≤10
12.5
50/50
36/36
50/50
36/36
50/50
36/36
50/50
36/36
50/50
36/36
80/80
42/42
80/80
42/42
80/80
42/42
80/80
42/42
80/80
42/42
150/150 150/150 150/150 150/150 150/150
50/50 50/50 50/50 50/50 50/50
GPS1MA 16/20 36/36 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 50/50
GPS2BA 25/32 36/36 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 50/50
GPS2MA 40 - 36/36 36/36 36/36 36/36 - 42/42 42/42 42/42 42/42 - 50/50 50/50 50/50 50/50
E 50/63 - - 36/36 36/36 36/36 - - 42/42 42/42 42/42 - - 50/50 50/50 50/50
GPS1BH ≤10 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
GPS1MH 12.5 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
GPS2BH 16/20 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
GPS2MH 25/32 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
F 50/63 - - 50/50 50/50 50/50 - - 80/80 80/80 80/80 - - 150/150 150/150 150/150

Table DB1a - Selectivity Plus


G Record PlusTM type
Upstream
FD160N - LMLD FD160H - LMLD FD160L - LMLD

X Downstream
In (A) 63 80 100 125 160 63 80 100 125 160 63 80 100 125 160

Selectivity limit in kA / Maximum Icu of combination at 230/240V AC

≤20A 8/8 8/8 8/8 8/8 8/8 10/10 10/10 10/10 10/10 10/10 12/12 12/12 12/12 12/12 12/12
C30 B/C curve 25A 8/8 8/8 8/8 8/8 8/8 10/10 10/10 10/10 10/10 10/10 12/12 12/12 12/12 12/12 12/12
32A 6/6 8/8 8/8 8/8 8/8 8/8 10/10 10/10 10/10 10/10 10/10 12/12 12/12 12/12 12/12
40A - 8/8 8/8 8/8 8/8 - 10/10 10/10 10/10 10/10 - 12/12 12/12 12/12 12/12
≤20A 12/12 12/12 12/12 12/12 12/12 15/15 15/15 15/15 15/15 15/15 18/18 18/18 18/18 18/18 18/18
C60 B/C curve & DME60 25A 12/12 12/12 12/12 12/12 12/12 15/15 15/15 15/15 15/15 15/15 18/18 18/18 18/18 18/18 18/18
32A 10/10 12/12 12/12 12/12 12/12 12/12 15/15 15/15 15/15 15/15 15/15 18/18 18/18 18/18 18/18
40A - 12/12 12/12 12/12 12/12 - 15/15 15/15 15/15 15/15 - 15/18 18/18 18/18 18/18

E.22
Record Plus
Table DB2 - Selectivity Plus
Record PlusTM type
Upstream FE160N-LTMD/SMR1 FE160H-LTMD/SMR1 FE160L-LTMD/SMR1 FE250N-LTMD/SMR1 FE250H-LTMD/SMR1 FE250L-LTMD/SMR1

In (A) 100 125 160 100 125 160 100 125 160 125 160/200 250 125 160/200 250 125 160/200 250
Downstream Selectivity limit in kA / Maximum Icu of combination at 400/415V ac
Redline ≤20 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
G30 B/C curve 25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
32 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
40 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
50 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
63 - 16/16 16/16 - 22/22 22/22 - 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
G60 B/C curve ≤20 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
25 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
32 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
40 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36

Selectivity Plus
50 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
63 - 30/30 30/30 - 36/36 36/36 - 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
G100 B/C curve ≤20 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
25 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
32 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
40 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
50 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
63 - 36/36 36/36 - 40/40 40/40 - 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
GT25 B/C curve ≤20 40/40 40/40 40/40 50/50 50/50 50/50 65/65 65/65 65/65 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 40/40
25 40/40 40/40 40/40 50/50 50/50 50/50 65/65 65/65 65/65 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 40/40
32 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40
40 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40
50 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
63 - 36/36 36/36 - 40/40 40/40 - 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
Surion ≤10 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
GPS1BA 12.5 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
GPS1MA 16/20 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
GPS2BA 25/32 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
GPS2MA 40 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
50/63 - 36/36 36/36 - 42/42 42/42 - 50/50 50/50 - 36/36 36/36 - 42/42 42/42 - 50/50 50/50
GPS1BH
GPS1MH
≤10
12.5
50/50
50/50
50/50
50/50
50/50
50/50
80/80
80/80
80/80
80/80
80/80
80/80
150/150150/150150/150
150/150150/150150/150
50/50
50/50
50/50
50/50
50/50
50/50
80/80
80/80
80/80
80/80
80/80
80/80
150/150150/150150/150
150/150150/150150/150
A
GPS2BH 16/20 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
GPS2MH 25/32 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
40 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
50/63 - 50/50 50/50 - 80/80 80/80 - 150/150150/150 - 50/50 50/50 - 80/80 80/80 - 150/150150/150 B
Table DB2a - Selectivity Plus
Record PlusTM type
C
Upstream
FE160N - LMLD/SMR1 FE160H - LTMD/SMR1 FE160L - LTMD/SMR1 FE250N - LTMD/SMR1 FE250H - LTMD/SMR1 FE250L - LTMD/SMR1

In (A) 100 125 160 100 125 160 100 125 160 125 160/200 250 125 160/200 250
Downstream D
Selectivity limit in kA / Maximum Icu of combination at 230/240V AC
≤20A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12
C30 B/C curve 25A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12
32A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 E
40A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12
≤20A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15
C60 B/C curve & DME60 25A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15
32A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15
40A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15 F

E.23
Record Plus
Table DB3 - Selectivity Plus
Record PlusTM type
Upstream
FE160H-LTMD FE160L-LTMD FE160H-SMR1 FE160L-SMR1 FE250H-LTMD FE250L-LTMD FE250H-SMR1 FE250L-SMR1

In (A) 125 160 125 160 125 160 125 160 160/200 250 160/200 250 160 250 160 250
Downstream Selectivity limit in kA / Maximum Icu of combination
Record PlusTM
FD 63S LTMD 30/42 30/42 30/50 30/50 36/42 36/42 36/50 36/50 42/42 42/42 42/50 42/50 42/42 42/42 50/50 50/50
FD 63N LTMD 30/80 30/80 30/150 30/150 36/80 36/80 36/150 36/150 42/80 42/80 42/150 42/150 50/80 50/80 50/150 50/150
FD 63H LTMD - - 30/150 30/150 - - 36/150 36/150 - - 42/150 42/150 - - 50/150 50/150
FD160S LTMD ≤80A 30/42 30/42 30/50 30/50 36/42 36/42 36/50 36/50 42/42 42/42 42/50 42/50 42/42 42/42 50/50 50/50
FD160N LTMD ≤80A 30/80 30/80 30/150 30/150 36/80 36/80 36/150 36/150 42/80 42/80 42/150 42/150 50/80 50/80 50/150 50/150
FD160H LTMD ≤80A - - 30/150 30/150 - - 36/150 36/150 - - 42/150 42/150 - - 50/150 50/150
FE 160N LTM ≤80A 30/80 30/80 30/150 30/150 36/80 36/80 36/150 36/150 42/80 42/80 42/150 42/150 50/80 50/80 50/150 50/150
FE 160H LTM ≤80A - - 30/150 30/150 - - 36/150 36/150 - - 42/150 42/150 - - 50/150 50/150
Application guide

Table DB4 - Selectivity Plus


Record PlusTM type
Upstream
FG400H-SMR FG400L-SMR FG630H-SMR FG630L-SMR

In (A) 250 350 400 250 350 400 250 350 400 250 350 400
Downstream Selectivity limit in kA / Maximum Icu of combination
Record PlusTM
FD 63S LTMD 50/50 50/50 50/50 65/65 65/65 65/65 50/50 50/50 50/50 65/65 65/65 65/65
FD 63N LTMD 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FD 63H LTMD 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150
FD160S LTMD 50/50 50/50 50/50 65/65 65/65 65/65 50/50 50/50 50/50 65/65 65/65 65/65
FD160N LTMD 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FD160H LTMD - 150/150 150/150 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150
FE 160N LTM &LTMD 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FE 160H LTM & LTMD - 150/150 150/150 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150
FE 160N SMR1 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FE 160H SMR1 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150
A
Table DB5 - Selectivity Plus
B Upstream
Record PlusTM type
FK800H-SMR FK800L-SMR FK1250H-SMR FK1250L-SMR FK1600H-SMR

In (A) 800 800 1000 1250 1000 1250 1600


Downstream
C Record PlusTM
Selectivity limit in kA / Maximum Icu of combination

FD 63N LTMD 80/80 80/80 80/80 80/80 80/80 80/80 80/80


FD 63H LTMD 80/80 100/100 80/80 80/80 100/100 100/100 80/80
FE 160N LTMD-SMR1 80/80 80/80 80/80 80/80 80/80 80/80 80/80
D FE 160H LTMD -SMR1
FE 250N LTMD -SMR1
80/80
80/80
100/100
80/80
80/80
80/80
80/80
80/80
100/100
80/80
100/100
80/80
80/80
80/80
FE 250H LTMD-SMR1 80/80 100/100 80/80 80/80 100/100 100/100 80/80
FG 400N SMR 80/80 80/80 80/80 80/80 80/80 80/80 80/80
FG 400H SMR 80/80 100/100 80/80 80/80 100/100 100/100 80/80
E FG 630N SMR 80/80 80/80 80/80 80/80 80/80 80/80 80/80
FG 630H SMR 80/80 100/100 80/80 80/80 100/100 100/100 80/80

E.24
Record Plus
Coordination with loadbreak
disconnect switches

Coordination with disconnectors


Record PlusTM circuit breakers excel in their
characteristics as current and energy limiting
devices. This allows one to use lighter and more
economical downstream busbar systems and
switchgear.

A frequently used combination is that of a


Record PlusTM breaker, used as a protection and
switching device in the mains switchboard, and a
Dilos loadbreak switch, as an incomer, in a
downstream, secondary switchboard. In this
application the Dilos needs to be able to withstand
the current and energy values on a short-circuit
event , this taking the limiting effects of the
upstream breaker into account .

The table indicates the maximum prospective


short-circuit that the combination of an upstream
Record PlusTM and a downstream Dilos or
Record PlusTM in its switch disconnect variant
(type Y) can withstand.

Protection of Switch Disconnectors (Dilos or Record Plus) with Record Plus circuit breakers - Valid for 400/415V AC A
Upstream Record PlusTM Breaking capacity, Downstream Dilos Maximum allowable Downstream Record Maximum allowable
circuit breaker Icu=Ics (kA eff.) switch short-circuit (kA eff.) PlusTM switch short-circuit (kA eff.)
of combination of combination
FD63/160S 36 Dilos 1 & 1H
Dilos 2
18
18
FD63Y
FD160Y
36
36
B
FD63/160N 50 Dilos 1 & 1H 25 FD63Y 50
Dilos 2 25 FD160Y 50
FD63/160H 80 Dilos 1 & 1H 30 FD63Y 80

FD63/160L 150
Dilos 2
Dilos 1 & 1H
30
36
FD160Y
FD63Y
80
150
C
Dilos 2 36 FD160Y 150
FE160N 50 Dilos 1 & 1H 25 FD63Y 50
Dilos 2 25 FD160Y 50
FE160H 80 Dilos 1 & 1H
Dilos 2
30
30
FD63Y
FD160Y
80
80
D
FE160L 150 Dilos 1 & 1H 36 FD63Y 150
Dilos 2 36 FD160Y 150
FE250N 50 Dilos 3 50 FE250Y 50
FE250H 80 Dilos 3 80 FE250Y 80 E
FE250L 150 Dilos 3 150 FE250Y 150
FG400N 50 Dilos 4 50 FG400Y 50
FG400H 80 Dilos 4 80 FG400Y 80
FG400L 150 Dilos 4 150 FG400Y 150
FG630N 50 Dilos 4 50 FG630Y 50 F
FG630H 80 Dilos 4 80 FG630Y 80
FG630L 150 Dilos 4 150 FG630Y 150
FK800N 50 Dilos 6 50 FK800Y 50
FK800H 80 Dilos 6 80 FK800Y 80
FK1250N 50 Dilos 6 50 FK1250Y 50 G
FK1250H 80 Dilos 6 80 FK1250Y 80
FK1600N 50 Dilos 7 50 FK1600Y 50
FK1600H 80 Dilos 7 80 FK1600Y 80

E.25
Record Plus
Protection of motor circuits

General
In a circuit that provides power to a motor a
number of protective and control devices are
normally present . The combination of these
devices must be coordinated to ensure the
efficiency and an optimal protection of the motor.
Here, the protection of such circuits strongly
depends on the operational requirements, as
the application for which the motor is used, the
Application guide

required starting frequency, the required service


level and the applicable safety standards.

Protection of the electrical circuit


The motor circuit must provide the following
functionality:
• Isolate the circuit from the network for maintenance.
• Protect against short-circuits in the equipment ,
the starter and the cables within the circuit .
• Protect against overloads in the equipment ,
the starter and the cables within the circuit .
• Protect against faults specific to the motor within it's
application.
Control of the motor in question, this covering starting,
stopping, speed control etc.
A Standards
The requirements for circuits supplying a motor, in Category Load type Contactor usage
general called "motor starters", can be found in the
B IEC 60947-4-1. To define the components for isolation, AC1
AC2
Non Inductive motors
Slip ring motors
Energization
Starting
overload and short-circuit protection the following Switching off whilst running
elements must be defined: Regenerative breaking
• Depending on the type of electrical motor and it’s Inching
C operational requirements, four motor utilization
AC3 Squirrel-cage motors Energization
Switching off whilst running
categories have been defined. These have an impact AC4 Squirrel-cage motors Starting
(cos phi = 0.45 ≤ 100A) Switching off whilst running
on the characteristics of the control element within
(cos phi = 0.35 > 100A) Regenerative breaking
D the circuit . These so called AC classes are depicted in Plugging
Inching
the table on the right .
• The required trip curve class of the overload
protection, this depending on the motor application,
E the classes 10A, 10, 20 and 30 are normally used,
Required tripping times at

Trip class 1.2 x In 1.5 x In 7.2 x In


the requirements for which are indicated in the table.
• Isolation and safety during maintenance. Use of 10A t < 2 hours t < 2 min. 2 ≤ t ≤ 10 sec.
10 t < 2 hours t < 4 min. 4 ≤ t ≤ 10 sec.
F the Record PlusTM breaker here provides an
enhancement of the present standard requirement
20 t < 2 hours t < 8 min. 6 ≤ t ≤ 20 sec.
30 t < 2 hours t < 12 min. 9 ≤ t ≤ 30 sec.
for POSITIVE OFF adding in a POSITIVE ON
indication.
G

E.26
Record Plus
Coordination type 2 test sequence
Coordination
The standards require tests to define the
Motor current Ie (AC3) Test with current " r "
coordination between the devices within the motor
starter. Depending on the state of the components
Ie ≤ 16A 1 kA
after the test two coordination classes 1 and 2 16 < Ie ≤ 63A 3 kA
have been defined. 63 < Ie ≤ 125A 5 kA

Protection of motor circuits


125 < Ie ≤ 315A 10 kA
315 < Ie ≤ 630A 18 kA
• After this test the original characterstics of the contactor and
The unique properties of the Record PlusTM breaker thermal relay MUST remain unchanged.
allow GE to offer solutions meeting the highest • After this test the short-circuit protection must trip within 10 ms
standards. For this reason all tables published here at a fault current ≥ 15 x In.
only refer to coordination type 2.

This entails that the GE equipment meets the Short-circuit test

following standards
• No or minor weldings of the contactors after testing; This value which is generally ≤ 50kA is used to check the coordination
of the devices used in the motor starter circuit. For each combination
contact separation is simple and easy with Record PlusTM breakers this value is mentioned in the tables on
• The switchgear and controlgear are fully operational pages E.28, 29, 30, 31, 32 and 33.
After a test with this current the following conditions must be met:
after the tests indicated here. • No or minor weldings of the contactors after testing; contact
separation is simple and easy
• The switchgear and controlgear are fully operational after the test.

Solutions with the Record PlusTM breaker


Motor starters are compiled with a number of
GE components. This is to offer the required
functionality of the motor starter circuit and to
allow a choice in the execution thereof.

Option 1 Option 2
A
Electronic circuit
Magnetic only breaker as the short-
circuit breaker as the circuit and
Overload protection
B
short-circuit
protection device. device.

C
Contactor for control Contactor for control
purposes. purposes.

D
Separate thermal relay
for class 10 or
class 30 as overload E
protection.

After power is disconnected (circuit interruption after a fault) the


G
breaker has no thermal memory function. This implies that after an
overload, immediate breaker reset and re-energization of the
circuit is possible.
In order to prevent this a Long time module can be utilized that X
closes a contact on an overload just before the breaker trips. This
allowing the contactor in the circuit to be de-energized and a external
thermal memory to be initialized, before the breaker trips.

The sketch here depicts the long time module as an


optional add on in the circuit diagram. Here the breaker
is the short-circuit protection device AND a backup
overload protection. If the contactor fails to open on a
long time module signal the breaker will trip.

E.27
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L
Icc values in kA Ue=230V AC Icc values in kA Ue=400/415V AC
FD63/160 85 100 130 FD63/160 50 80 130
FE160/250 85 100 130 FE160/250 50 80 130
FG 400/630 85 100 130 FG 400/630 50 80 130
FK 800/1250 85 100 130 FK 800/1250 50 80 100

Selection of associated components(1)


Motor Breaker details Contactor Motor Breaker details Contactor

P(kw) In Type Ie Im Type+O.R. P(kw) In Type Ie Im Type


Application guide

0.37 2.0 FD63/FE160 3(2) 30 CL25+RT1J


0.55 2.8 FD63/FE160 3(2) 36 CL25+RT1K
0.75 3.5 FD63/FE160 3(2) 70 CL25+RT1K 0.75 2.0 FD63/FE160 3(2) 30 CL25+RT1J
1.1 5.0 FD63/FE160 7 70 CL03+RT12L 1.1 2.6 FD63/FE160 3(2) 33 CL25+RT1K
1.5 6.1 FD63/FE160 7 80 CL03+RT1M 1.5 3.6 FD63/FE160 7 70 CL03+RT1K
2.2 8.7 FD63/FE160 12.5(3) 125 CL06+RT2AN 2.2 5.0 FD63/FE160 7 80 CL03+RT12L
3 11.5 FD63/FE160 12.5(3) 150 CL06+RT2AN 3 6.6 FD63/FE160 7 86 CL03+RT1M
4 14.5 FD63/FE160 20(3) 200 CL06+RT2B 4 8.3 FD63/FE160 12.5(3) 125 CL06+RT2AN
5.5 20.0 FD63/FE160 20(3) 260 CL06-RT2C 5.5 11.5 FD63/FE160 12.5(3) 150 CL06+RT2AN
7.5 28 FD63/FE160 30(4) 364 CL06-RT2D 7.5 16.1 FD63/FE160 20(3) 200 CL06+RT2B
10 36 FD63/FE160 50 500 CL06+RT2E 10 21 FD63/FE160 30(4) 300 CL06-RT2C
11 39 FD63/FE160 50 507 CL06+RT2E 11 22 FD63/FE160 30(4) 300 CL06-RT2C
15 50 FD63/FE160 50 650 CL06+RT2G 15 30 FD63/FE160 30(4) 390 CL06-RT2D
18.5 64 FD/FE160 80(5) 832 CL09+RT2J 18.5 37 FD63/FE160 50 478 CL06+RT2E
22 75 FD/FE160 80(5) 975 CL09+RT2J 22 43 FD63/FE160 50 561 CL06+RT2G
25 85 FD/FE160 100 1020 CL09+RT2L 25 49 FD63/FE160 50 635 CL06+RT2G
30 100 FD160 100 1300 CL09+RT2M 30 58 FD/FE160 80(5) 800 CL09+RT2H
30 100 FE160 100 1300 CK75C+RT2M 37 72 FD/FE160 80(5) 934 CL09+RT2J
Short-circuit Protection by means 37 125 FE160 125 1625 CK85B+RT3E 45 86 FD160 100 1121 CL09+RT2L
of Magnetic Only MCCB. 45 150 FE160 160 1950 CK85B+RT3F 45 86 FE160 100 1121 CK75C+RT2L
Overload Protection by means of 55 180 FE250 250 2500 CK95B+RT3F 55 104 FE160 125 1346 CK85B+RT3E
a direct heated electromechani- 75 250 FG400 250 3250 CK10B+RT4P 75 144 FE160 160 1869 CK85B+RT3F
A cal thermal relay
Phase Loss protection
90
110
312
360
FG400
FG400
400
400
4056
4680
CK10B+RT5C 90
CK12B+RT5C 110
179
207
FE250
FE250
250
250
2500
2691
CK95B+RT4N
CK10B+RT4P
(Thermal relay feature) 132 430 FG630 500 5590 CK12B+RT5D 132 247 FG400 250 3214 CK10B+RT4R
Control by GE contactor 160 520 FK800 800 6760 CK13B+RT5E 160 300 FG400 400 3900 CK10B+RT5C
200 630 FK800 800 6930 CK13B+RT5E 200 360 FG400 400 4680 CK12B+RT5C
B -
-
-
-
-
-
-
-
-
-
-
-
220
250
400
462
FG630
FG630
500
500
5200
6004
CK12B+RT5D
CK12B+RT5D
- - - - - - 300 560 FK800 800 6720 CK13B+RT5E
- - - - - - 315 582 FK800 800 6985 CK13B+RT5C
- - - - - - 335 619 FK800 800 6810 CK13B+RT5C
C
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic
setting of the breaker
(2) The 3Amp device is designed to operate at a current level up to 3.5Amps
D (3) FD63 type; contactor size can be reduced to CL04
(4) FD63 type; contactor size can be reduced to CL45
(5) FD160 type; contactor size can be reduced to CL08

E.28
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L Type N H L
Icc values in kA Ue=440V AC Icc values in kA Ue=500/525V AC Icc values in kA Ue=690V AC
FD63/160 30 50 80 FD63/160 - 36 50 FD63/160 - 6
FE160/250 42 65 130 FE160/250 - 50 80 FE160/250 - 22 Tests

Protection of motor circuits


FG 400/630 42 65 130 FG 400/630 - 50 80 FG 400/630 - 22 pending
FK 800/1250 42 65 80 FK 800/1250 - 36 50 FK 800/1250 - 22

Selection of associated components(1)


Motor Breaker details Contactor Motor Breaker details Contactor Motor Breaker details Contactor

P(kw) In Type Ie Im Type+O.R. P(kw) In Type Ie Im Type+O.R. P(kw) In Type Ie Im Type+O.R.

0.8 1.9 FD63/FE160 3(2) 30 CL25+RT1J 0.8 1.5 FD63/FE160 3(2) 30 CL25+RT1H
1.1 2.5 FD63/FE160 3(2) 30 CL25+RT1K 1.1 2.0 FD63/FE160 3(2) 30 CL25+RT1J 1.5 2.0 FD63/FE160 3(2) 30 CL25+RT1J
1.5 3.4 FD63/FE160 3(2) 70 CL25+RT1K 1.5 2.6 FD63/FE160 3(2) 40 CL25+RT1K 2.2 2.9 FD63/FE160 3(2) 38 CL25+RT1K
2.2 4.6 FD63/FE160 7 70 CL03+RT12L 2.2 3.8 FD63/FE160 7 70 CL03+RT12L 3 3.5 FD63/FE160 3(2) 70 CL25+RT1K
3 6.0 FD63/FE160 7 78 CL03+RT1M 3 5.0 FD63/FE160 7 70 CL03+RT1M 3.7 4.6 FD63/FE160 7 70 CL03+RT12L
4 7.6 FD63/FE160 12.5(3) 100 CL06+RT2AN 4 6.5 FD63/FE160 7 85 CL03+RT1M 4 5.0 FD63/FE160 7 70 CL03+RT12L
5.5 10.5 FD63/FE160 12.5(3) 136 CL03+RT2AN 5.5 9.0 FD63/FE160 12.5(3) 125 CL06+RT2AN 5.5 7.0 FD63/FE160 7 91 CL03+RT12M
7.5 14.6 FD63/FE160 20(3) 200 CL06+RT2B 7.5 12.0 FD63/FE160 12.5(3) 156 CL06+RT2BP 7.5 9.0 FD63/FE160 12.5(3) 125 CL07+RT2AN
10 18.8 FD63/FE160 20(3) 245 CL06+RT2B 10 15.0 FD63/FE160 20(3) 200 CL06+RT2B 11 12.5 FD63/FE160 12.5(3) 163 CL07+RT2BP
11 20 FD63/FE160 30(4) 300 CL06-RT2C 11 18.4 FD63/FE160 20(3) 300 CL06-RT2B 13 16.0 FD63/FE160 20(3) 208 CL07+RT2B
15 27 FD63/FE160 30(4) 355 CL06-RT2D 15 23 FD63/FE160 30(4) 300 CL06-RT2C 15 18.0 FD63/FE160 20(3) 234 CL07+RT2B
18.5 33 FD63/FE160 50 500 CL06+RT2E 18.5 29 FD63/FE160 30(4) 371 CL06-RT2D 18.5 23 FD63/FE160 30(4) 300 CL09+RT2C
22 39 FD63/FE160 50 510 CL06+RT2E 22 33 FD63/FE160 50 500 CL06+RT2E 22 25 FD63/FE160 30(4) 325 CL09+RT2D
25 44 FD63/FE160 50 578 CL06+RT2G - - - - - - - - - - - -
30 52 FD/FE160 80 680 CL09+RT2H 30 45 FD63/FE160 50 585 CL06+RT2G 30 35 FD63/FE160 50 500 CL09+RT2E
37 65 FD/FE160 80 849 CL09+RT2J 37 55 FD/FE160 80(5) 800 CL09+RT2J 37 42 FD63/FE160 50 546 CL09+RT2E
45 78 FD/FE160 80 1019 CL09+RT2J 45 65 FD/FE160 100 1000 CL09+RT2J 45 49 FD63/FE160 50 637 CL09+RT2G
55 86 FD160 100 1223 CL09+RT2L 55 80 FD160 100 1100 CL09+RT2S 55 60 FD/FE160 80(5) 800 CL09+RT2J
55 94 FE160 100 1223 CK75C+RT2L 55 80 FE160 100 1100 CK75C+RT2J 75 80 FD/FE160 80(5) 1040 CL09+R2TL
75 131 FE160 160 1699 CK85B+RT3E 75 110 FE160 125 1430 CK85B+RT3D 90 100 FD160 100 1300 CL09+R2TL
90
110
163
188
FE250
FE250
250
250
2500
2500
CK95B+RT3F
CK95B+RT4P
90
110
130
156
FE160
FE160
160
160
1690
2028
CK95B+RT3E
CK95B+RT3F
90
110
100
120
FE160
FE160
100
125
1300
1560
CK85B+RT2M
CK85B+RT3E
A
132 225 FE250 250 2922 CK95B+RT4R 132 190 FE250 250 2500 CK95B+RT4P 132 140 FE160 160 1820 CK95B+RT3F
160 300 FG400 400 3900 CK10B+RT5C 160 228 FE250 250 2964 CK95B+RT4R 160 175 FE250 250 2100 CK95B+RT4N
200 360 FG400 400 4680 CK12B+RT5C 200 281 FG400 400 3653 CK10B+RT5C 200 220 FE250 250 2860 CK10B+RT4R
220
250
400
462
FG630
FG630
500
500
5200
6004
CK12B+RT5D
CK12B+RT5D
220
-
310
-
FG400
-
400
-
4030
-
CK10B+RT5C
-
220
250
240
270
FG400
FG400
250
400
3120
3510
CK10B+RT4R
CK10B+RT5C
B
300 509 FK800 800 6619 CK13B+RT5E - - - - - - - - - - - -
315 529 FK800 800 6880 CK13B+RT5E 315 445 FG630 500 5785 CK12B+RT5D - - - - - -
335 563 FK800 800 6754 CK13B+RT5E 335 460 FG630 500 5980 CK12B+RT5D 335 335 FG400 400 4355 CK10B+RT5C
355
375
596
630
FK800
FK800
800
800
6560
6930
CK13B+RT5E
CK13B+RT6A
355
375
500
530
FK800
FK800
800
800
6500
6890
CK13B+RT5E
CK13B+RT5E 375
-
400
- -
FG630
-
500
-
5200
-
CK12B+RT5D
C
- - - - - - 400 570 FK800 800 6840 CK13B+RT5E - - - - - -
- - - - - - 450 630 FK800 800 7560 CK13B+RT6A 450 480 FG630 500 6240 CK12B+RT5D
- - - - - - - - - - - - 500 530 FK800 800 6360 CK13B+RT5E
- - - - - - - - - - - - 560 580 FK800 800 6380 CK13B+RT5E D

E.29
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection (with SMR2 other classes possible)
Upstream Record PlusTM Breaker selection
Type N H L Type N H L
Icc values in kA Ue=230V AC Icc values in kA Ue=400/415V AC
FE160/250 85 100 130 FE160/250 50 80 130
FG 400/630 85 100 130 FG 400/630 50 80 130

Selection of associated components(1)


Motor Breaker details Contactor Motor Breaker details Contactor

P(kw) In Type Ie Ist Type P(kw) In Type Ie Im Type


Application guide

3 11.5 FE160 25 150 CL08 - - - - - -


4 14.5 FE160 25 189 CL08 - - - - - -
5.5 20 FE160 25 260 CL08 5.5 11.5 FE160 25 150 CL08
7.5 28 FE160 63 364 CL09 7.5 16.1 FE160 25 200 CL08
10 36 FE160 63 468 CL09 10 21 FE160 25 300 CL08
11 39 FE160 63 507 CL09 11 22 FE160 25 300 CL08
15 50 FE160 63 650 CL09 15 30 FE160 63 390 CL09
18.5 64 FE160 125 832 CK85B 18.5 37 FE160 63 478 CL09
22 75 FE160 125 975 CK85B 22 43 FE160 63 561 CL09
25 85 FE160 125 1105 CK85B 25 49 FE160 63 635 CL09
30 100 FE160 125 1300 CK85B 30 58 FE160 63 800 CL09
37 125 FE160 160 1625 CK95B 37 72 FE160 125 934 CK85B
45 150 FE160 160 1950 CK95B 45 86 FE160 125 1121 CK85B
55 180 FE250 250 2340 CK95B 55 104 FE160 125 1346 CK85B
75 250 FG400 250 3000 CK95B 75 144 FE160 160 1869 CK85B
90 312 FG400 400 4056 CK10C 90 179 FE250 250 2500 CK95B
110 360 FG400 400 4680 CK12B 110 207 FE250 250 2691 CK95B
132 430 FG630 500 5590 CK12B 132 247 FG400 250 2967 CK95B
Short-circuit and Overload - - - - - - 160 300 FG400 400 3900 CK10C
protection by means of Electronic - - - - - - 200 360 FG400 400 4680 CK12B
MCCB. - - - - - - 220 400 FG630 500 5200 CK12B
Phase Loss protection (in MCCB) - - - - - - 250 462 FG630 500 6004 CK12B
A Overload backup protection, and
overload alarm on use of LT
module. (1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic
Control by GE contactor setting of the breaker

E.30
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection (with SMR2 other classes possible)
Upstream Record PlusTM Breaker selection
Type N H L Type N H L Type N H L
Icc values in kA Ue=440V AC Icc values in kA Ue=690V AC
FE160/250 42 65 130 FE160/250 - 50 80 FE160/250 - 22 50
FG 400/630 50 65 130 FG 400/630 - 50 80 FG 400/630 - 22 50

Protection of motor circuits


Selection of associated components(1)
Motor Breaker details Contactor Motor Breaker details Contactor Motor Breaker details Contactor

P(kw) In Type Ie Im Type P(kw) In Type Ie Im Type P(kw) In Type Ie Im Type

- - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - -
5.5 10.5 FE160 25 136 CL08 - - - - - - - - - - - -
7.5 14.6 FE160 25 200 CL08 7.5 12.0 FE160 25 156 CL09 - - - - - -
10 18.8 FE160 25 245 CL08 10 15.0 FE160 25 200 CL09 10 11.5 FE160 25 150 CK85B
11 20 FE160 25 265 CL08 11 18.4 FE160 25 300 CL09 - - - - - -
15 27 FE160 63 355 CL09 15 23 FE160 25 300 CL09 15 17.1 FE160 25 223 CK85B
18.5 33 FE160 63 500 CL09 18.5 29 FE160 63 371 CL10 18.5 20 FE160 25 260 CK85B
22 39 FE160 63 510 CL09 22 33 FE160 63 423 CL10 - - - - - -
25 44 FE160 63 578 CL09 - - - - - - - - - - -
30 52 FE160 63 680 CL09 30 45 FE160 63 585 CL10 30 35 FE160 63 500 CK85B
37 65 FE160 125 849 CK85B 37 55 FE160 63 800 CL10 37 42 FE160 63 546 CK85B
45 78 FE160 125 1019 CK85B - - - - - - 45 49 FE160 63 637 CK85B
55 94 FE160 125 1223 CK85B 55 80 FE160 125 1040 55 60 FE160 63 800 CK85B
75 131 FE160 160 1699 CK85B 75 110 FE160 125 1430 CK85B 75 80 FE160 125 1040 CK85B
90 163 FE250 250 2500 CK95B 90 130 FE160 160 1690 CK85B 90 100 FE160 125 1300 CK85B
110 188 FE250 250 2500 CK95B 110 156 FE160 160 2028 CK85B 110 120 FE160 125 1560 CK85B
132 225 FE250 250 2922 CK95B 132 190 FE250 250 2500 CK95B 132 140 FE160 160 1820 CK85B
160 300 FG400 400 3900 CK10C 160 228 FE250 250 2964 CK95B 160 175 FE250 250 2275 CK10C
200 360 FG400 400 4680 CK12B 200 281 FG400 400 3653 CK10C 200 220 FE250 250 2860 CK10C
220 400 FG630 500 5200 CK12B 220 310 FG400 400 4030 CK10C 220 240 FG400 250 3120 CK10C
250 462 FG630 500 6004 CK12B - - - - - - 250 270 FG400 400 3510 CK10C
-
-
-
-
-
-
-
-
-
-
-
-
-
315
-
445
-
FG630
-
500
-
5785
-
CK12B
-
-
-
-
-
-
-
-
-
-
-
-
A
- - - - - - 335 460 FG630 500 5980 CK12B 335 335 FG400 400 4355 CK10C
- - - - - - 355 500 FG630 500 6500 CK12B - - - - - -
- - - - - - - - - - - - 375 400 FG630 500 5200 CK12B
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
450
-
480
-
FG630
-
500
-
6240
-
CK12B
B

(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker
C

E.31
Record Plus
Coordination type II - EN 60947-4 - Class 20(3) protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L
Icc values in kA Ue=230V AC Icc values in kA Ue=400/415V AC
FD63/160 85 100 130 FD63/160 50 80 130
FE160/250 85 100 130 FE160/250 50 80 130
FG 400/630 85 100 130 FG 400/630 50 80 130
FK 800/1250 85 100 130 FK 800/1250 50 80 100

Selection of associated components(1)


Motor Breaker details Contactor Motor Breaker details Contactor

P(kw) In Type Ie Im Type+O.R. P(kw) In Type Ie Im Type+O.R.


Application guide

0.37 2.0 FD63/FE160 3(2) 35 CL25+RT12J


0.55 2.8 FD63/FE160 3(2) 35 CL25+RT12K
0.75 3.5 FD63/FE160 3(2) 46 CL25+RT12K 0.75 2.0 FD63/FE160 3(2) 35 CL25+RT12J
1.1 5.0 FD63/FE160 7 70 CL03+RT12L 1.1 2.6 FD63/FE160 3(2) 35 CL25+RT12K
1.5 6.1 FD63/FE160 7 80 CL03+RT12M 1.5 3.6 FD63/FE160 7 70 CL03+RT12K
2.2 8.7 FD63/FE160 12.5(4) 125 CL06+RT2AN 2.2 5.0 FD63/FE160 7 80 CL03+RT12L
3 11.5 FD63/FE160 12.5(4) 150 CL06+RT2AN 3 6.6 FD63/FE160 7 86 CL03+RT12M
4 14.5 FD63/FE160 20(4) 200 CL06+RT2B 4 8.3 FD63/FE160 12.5(4) 125 CL06+RT2AN
5.5 20.0 FD63/FE160 20(4) 260 CL06-RT2C 5.5 11.5 FD63/FE160 12.5(4) 150 CL06+RT2AN
7.5 28 FD63/FE160 30(5) 364 CL06-RT22D 7.5 16.1 FD63/FE160 20(4) 200 CL06+RT2B
10 36 FD63/FE160 50 500 CL06+RT22E 10 21 FD63/FE160 30(5) 300 CL06-RT2C
11 39 FD63/FE160 50 507 CL06+RT22E 11 22 FD63/FE160 30(5) 300 CL06-RT2C
15 50 FD63/FE160 50 650 CL06+RT22G 15 30 FD63/FE160 30(5) 390 CL06-RT22D
18.5 64 FD/FE160 80(6) 832 CL09+RT22J 18.5 37 FD63/FE160 50 478 CL06+RT22E
22 75 FD/FE160 80(6) 975 CL09+RT22J 22 43 FD63/FE160 50 561 CL06+RT22G
25 85 FD/FE160 100 1020 CL09+RT22L 25 49 FD63/FE160 50 635 CL06+RT22G
30 100 FD160 100 1300 CL09+RT22M 30 58 FD/FE160 80(6) 800 CL09+RT22H
30 100 FE160 100 1300 CK75C+RT22M 37 72 FD/FE160 80(6) 934 CL09+RT22J
Short-circuit Protection by means 37 125 FE160 125 1625 CK85B+RT32E 45 86 FD160 100 1121 CL09+RT22L
of Magnetic Only MCCB. 45 150 FE160 160 1950 CK85B+RT32F 45 86 FE160 100 1121 CK75C+RT22L
Overload Protection by means of 55 180 FE250 250 2500 CK95B+RT32F 55 104 FE160 125 1346 CK85B+RT32E
a electromechanical thermal 75 250 FG400 250 3250 CK10B+RT5LB 75 144 FE160 160 1869 CK85B+RT32F
A relay.
Phase Loss protection (Thermal
90
110
312
360
FG400
FG400
400
400
4056
4680
CK10B+RT5LB 90
CK12B+RT5LC 110
179
207
FE250
FE250
250
250
2500 CK95B+RT32F
2691 CK10B+RT5LB
relay feature) 132 430 FG630 500 5590 CK12B+RT5LD 132 247 FG400 250 3214 CK10B+RT5LB
Control by GE contactor 160 520 FK800 800 6760 CK13B+RT5LE 160 300 FG400 400 3900 CK10B+RT5LB
200 630 FK800 800 6930 CK13B+RT5LE 200 360 FG400 400 4680 CK12B+RT52LC
B -
-
-
-
-
-
-
-
-
-
-
-
220
250
400
462
FG630
FG630
500
500
5200 CK12B+RT52LD
6004 CK12B+RT52LD
- - - - - - 300 560 FK800 800 6720 CK13B+RT5LE
- - - - - - 315 582 FK800 800 6985 CK13B+RT5LE
- - - - - - 335 619 FK800 800 6810 CK13B+RT5LE
C
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic
setting of the breaker.
(2) The 3Amp device is designed to operate at a current level up to 3.5Amps.
D (3) Class 30 on request.
(4) FD63 type; contactor size can be reduced to CL04
(5) FD63 type; contactor size can be reduced to CL45
(6) FD160 type; contactor size can be reduced to CL08

E.32
Record Plus
Coordination type II - EN 60947-4 - Class 20(3) protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L Type N H L
Icc values in kA Ue=440V AC Icc values in kA Ue=500/525V AC Icc values in kA Ue=690V AC
FD63/160 30 50 80 FD63/160 - 36 50 FD63/160 - 6 10
FE160/250 42 65 130 FE160/250 - 50 80 FE160/250 - 22 50

Protection of motor circuits


FG 400/630 42 65 130 FG 400/630 - 50 80 FG 400/630 - 22 50
FK 800/1250 42 65 80 FK 800/1250 - 36 50 FK 800/1250 - 22 30

Selection of associated components(1)


Motor Breaker details Contactor Motor Breaker details Contactor Motor Breaker details Contactor

P(kw) In Type Ie Im Type+O.R. P(kw) In Type Ie Im Type+O.R. P(kw) In Type Ie Im Type+O.R.

0.75 1.9 FD63/FE160 3(2) 30 CL25+RT12J 0.75 1.5 FD63/FE160 3(2) 30 CL25+RT12H
1.1 2.5 FD63/FE160 3(2) 30 CL25+RT12K 1.1 2.0 FD63/FE160 3(2) 30 CL25+RT12J
1.5 3.4 FD63/FE160 3(2) 70 CL25+RT12K 1.5 2.6 FD63/FE160 3(2) 40 CL25+RT12K 1.5 2.0 FD63/FE160 3(2) 30 CL25+RT12J
2.2 4.6 FD63/FE160 7 70 CL03+RT12L 2.2 3.8 FD63/FE160 7 70 CL03+RT12L 2.2 2.9 FD63/FE160 3(2) 38 CL25+RT12K
3 6.0 FD63/FE160 7 78 CL03+RT12M 3 5.0 FD63/FE160 7 70 CL03+RT12M 3 3.5 FD63/FE160 3(2) 46 CL25+RT12K
4 7.6 FD63/FE160 12.5(4) 100 CL06+RT2AN 4 6.5 FD63/FE160 7 85 CL03+RT12M 3.7 4.6 FD63/FE160 7 70 CL03+RT12L
5.5 10.5 FD63/FE160 12.5(4) 136 CL06+RT2AN 5.5 9.0 FD63/FE160 12.5(4) 125 CL06+RT2AN 4 5.0 FD63/FE160 7 70 CL03+RT12L
7.5 14.6 FD63/FE160 20(4) 200 CL06+RT2B 7.5 12.0 FD63/FE160 12.5(4) 156 CL06+RT2BP 5.5 7.0 FD63/FE160 7 91 CL03+RT12M
10 18.8 FD63/FE160 20(4) 245 CL06+RT2B 10 15.0 FD63/FE160 20(4) 200 CL06+RT2B 7.5 9.0 FD63/FE160 12.5(4) 125 CL07+RT2AN
11 20 FD63/FE160 30(5) 300 CL06-RT2C 11 18.4 FD63/FE160 20(4) 300 CL06-RT2B 11 12.5 FD63/FE160 12.5(4) 163 CL07+RT2BP
15 27 FD63/FE160 30(5) 355 CL06-RT22D 15 23 FD63/FE160 30(5) 300 CL06-RT2C 13 16.0 FD63/FE160 20(4) 208 CL07+RT2B
18.5 33 FD63/FE160 50 500 CL06+RT22E 18.5 29 FD63/FE160 30(5) 371 CL06-RT22D 15 18.0 FD63/FE160 20(4) 234 CL07+RT2B
22 39 FD63/FE160 50 510 CL06+RT22E 22 33 FD63/FE160 50 500 CL06+RT22E 18.5 23 FD63/FE160 30(5) 300 CL09+RT2C
25 44 FD63/FE160 50 578 CL06+RT22G - - - - - - 22 25 FD63/FE160 30(5) 325 CL09+RT22D
30 52 FD/FE160 80(6) 680 CL09+RT22H 30 45 FD63/FE160 50 585 CL06+RT22G - - - - - -
37 65 FD/FE160 80(6) 849 CL09+RT22J 37 55 FD/FE160 80(6) 800 CL09+RT22J 30 35 FD63/FE160 50 500 CL09+RT22E
45 78 FD/FE160 80 1019 CL09+RT22J 45 65 FD/FE160 100 1000 CL09+RT22J 37 42 FD63/FE160 50 546 CL09+RT22F
55 94 FD160 100 1223 CL09+RT22L 55 80 FD160 100 1000 CL09+RT22J 45 49 FD63/FE160 50 637 CL09+RT22G
55 94 FE160 100 1223 CK75C+RT22L 55 80 FE160 100 1100 CK75C+RT22J 55 60 FD/FE160 80(6) 800 CL09+RT22J
75 131 FE160 160 1699 CK85B+RT32E 75 110 FE160 125 1430 CK85B+RT32D 75 80 FD/FE160 80(6) 1040 CL09+R2T2L
90
110
163
188
FE250
FE250
250
250
2500 CK95B+RT32F
2500 CK95B+RT5LB
90
110
130
156
FE160
FE160
160
160
1690 CK95B+RT32E
2028 CK95B+RT32F
90
110
100
120
FD/FE160 100
FE160 125
1300 CK85B+RT22M
1560 CK85B+RT32E
A
132 225 FE250 250 2922 CK95B+RT5LB 132 190 FE250 250 2500 CK95B+RT5LB 132 140 FE160 160 1820 CK95B+RT32F
160 300 FG400 400 3900 CK10B+RT5LC 160 228 FE250 250 2964 CK95B+RT5LB 160 175 FE250 250 2100 CK95B+RT32F
200 360 FG400 400 4680 CK12B+RT5LD 200 281 FG400 400 3653 CK10B+RT5LC 200 220 FE250 250 2860 CK10B+RT5LB
220
250
400
462
FG630
FG630
500
500
5200 CK12B+RT5LD
6004 CK12B+RT5LD
220
-
310
-
FG400
-
400
-
4030 CK10B+RT5LC
- -
220
250
240
270
FG400
FG400
250
400
3120 CK10B+RT5LB
3510 CK10B+RT5LC
B
300 509 FK800 800 6619 CK13B+RT5LE - - - - - - - - - - - -
315 529 FK800 800 6880 CK13B+RT5LE 315 445 FG630 500 5785 CK12B+RT5LD - - - - - -
335 563 FK800 800 6754 CK13B+RT5LE 335 460 FG630 500 5980 CK12B+RT5LD 335 335 FG400 400 4355 CK10B+RT5LC
355
375
596
630
FK800
FK800
800
800
6560 CK13B+RT5LE
6930 CK13B+RT5LE
355
375
500
530
FK800
FK800
800
800
6500 CK13B+RT5LE
6890 CK13B+RT5LE
-
375
-
400
-
FG630
-
500
- -
5200 CK12B+RT5LD
C
- - - - - - 400 570 FK800 800 6840 CK13B+RT5LE - - - - - -
- - - - - - 450 630 FK800 800 7560 CK13B+RT5LE 450 480 FG630 500 6240 CK12B+RT5LD
- - - - - - - - - - - - 500 530 FK800 800 6360 CK13B+RT5LE
- - - - - - - - - - - - 560 580 FK800 800 6380 CK13B+RT5LE D

E.33
Record Plus
Protection of LV/LV transformers
Transformers generally produce a very high inrush
current . The crest value of the first half cycle may
reach values of 15 to 25 times the effective rated
current .
For a protective device capable of protecting these FD160 LTMD type
units this must be taken into account . Manufacturers
data and tests have indicated that a protective device
FD160 SMR1 type
feeding a transformer must be capable of carrying the
following current values without tripping (see graph
insert).
Application guide

Maximum crest inrush values


Transformer 1st period 2nd period after 3 periods
value 5 ms 25 ms. 45 ms.
< 50 kvA 25 x In 12 x In 5 x In
≥ 50 kvA 15 x In 8 x In 3.5 x In

Protection of LV/LV transformers with


Record PlusTM circuit breakers have been designed to Record Plus circuit breakers
cope with this kind of phenomenae. The adjacent table
Transformer ratings Record Plus breaker choice
indicates the types to select , based on the breaker
3ph 230V Type Trip unit Ist
characteristics, the transformer ratings and the above 1ph 230V 3ph 400V
1ph 400V type & *
mentioned inrush current prognoses. kVA In kVA In kVA In rating
2.5 10 4 10 6.3 9 FD160N,FD160H or L LTMD-25 250
4 11 5 12 8 12 FD160N,FD160H or L LTMD-25 250
5 17 6.3 16 10 14 FD160N,FD160H or L LTMD-32 320
8 20 12.5 18 FD160N,FD160H or L LTMD-32 320
A 6.3
8
27
34
10
12.5
24
30
16
20
23
28
FD160N,FD160H or L
FD160N,FD160H or L
LTMD-40 400
LTMD-50 500
10 42 16 39 25 35 FD160N,FD160H or L LTMD-63 630
12.5 53 20 49 31.5 44 FD160N,FD160H or L LTMD-80 800
25 61 40 56 FD160N,FD160H or L LTMD-100 1000
B 16
20
68
84 31.5 77
50 70 FD160N,FD160H or L
FD160N,FD160H or L
LTMD-125 1250
LTMD-125 1250
40 98 63 89 FE160N, H or L SMR1-125
25 105 50 122 80 113 FE160N, H or L SMR1-125
31.5 133 63 154 100 141 FE160N, H or L SMR1-160
C 40
50
169
211
80
100
195
244
125
160
176
225
FE250N, H or L
FE250N, H or L
SMR1-250
SMR1-250
63 266 125 305 200 287 FG400N, H or L SMR1-350
80 338 160 390 250 352 FG400N, H or L SMR1-350
100 422 315 444 FG630N, H or L SMR1-500
D 125
160
528
675
400
500
563
704
FG630N, H or L
FK800N or H
SMR1-630
SMR- 800
630 887 FK1250N or H SMR-1000
800 1126 FK1250N or H SMR-1250
1000 1408 FK1600N or H SMR-1600
E
* Magnetic threshold of breaker

E.34
Record Plus
Protection of capacitor banks
(power factor improvement units)
For circuit breakers and particularly for the
Record PlusTM device, designed to offer high making Un = 230V (phase to phase voltage)

Protection of capacitor banks


and breaking capacities under adverse conditions, the
Capacitor rating Record Plus Ir setting
switching of capacitor banks has little to no effect on (kVAr) breaker (min)
the breaker, its characteristics as a protective device,
5 FD160N, FD160H or L 18 A
or on its lifespan. 7.5 FD160N, FD160H or L 27 A
10 FD160N, FD160H or L 36 A
12.5 FD160N, FD160H or L 45 A
However, the current flowing in the circuit can trip a
15 FD160N, FD160H or L 54 A
circuit breaker and a capacitor load displays certain 20 FD160N, FD160H or L 72 A
anomalies. In a circuit with capacitors the maximum 25 FD160N, FD160H or L 90 A
30 FD160N, FD160H or L 108 A
current flow in the circuit cannot be assumed to be the 35 FD160N or FE160N, H or L 126 A
calculated capacitor current only. The effective value 40 FE160N, H or L 144 A
must be increased due to harmonic content (a factor 45 FE250N, H or L 162 A
50 FE250N, H or L 179 A
normally taken as 30%) and an allowance for the 60 FE250N, H or L 215 A
tolerances in the capacitance of the unit itself. 75 FG400N, H or L 269 A
90 FG400N, H or L 323 A
(10% assumed).
100 FG400N, H or L 359 A
120 FG630N, H or L 431 A
In order to protect these devices without running into 150 FG630N, H or L 538 A
180 FK800N or H 646 A
regular nuisance tripping due to overloads please refer
to the adjacent table in which the correct Record PlusTM
breaker is specified to protect and switch the indicated
capacitor banks at several different voltages.
Un = 400V (phase to phase voltage)
Capacitor rating Record Plus Ir setting
(kVAr) breaker (min)
10 FD160N, FD160H or L 21 A
15
20
FD160N, FD160H or L
FD160N, FD160H or L
31 A
41 A
A
25 FD160N, FD160H or L 52 A
30 FD160N, FD160H or L 62 A
35 FD160N, FD160H or L 72 A
40
45
FD160N, FD160H or L
FD160N, FD160H or L
83 A
93 A
B
50 FD160N, FD160H or L 103 A
60 FD160N, FD160H or L 124 A
70 FD160N or FE160N, H or L 144 A
80
90
FE250,N,H or L
FE250N, H or L
165 A
186 A
C
100 FE250N, H or L 206 A
120 FE250N, H or L 248 A
140 FG400N, H or L 289 A
160
180
FG400N, H or L
FG400N, H or L
330 A
372 A
D
200 FG630N, H or L 413 A
250 FG630N, H or L 516 A
300 FG630N, H or L 619 A
350 FK800N or H 722 A E

E.35
Just rel
Record Plus

The breaker

Order codes A
F.2 FD frame, plug in device (8 & 10 pole connectors)

F.2 FE frame, plug in device (8 pole connectors)


Trip units B
F.2 FE frame, plug in device (10 pole connectors)

F.3 FE frame, draw out device (10 pole connectors)


Components & Accessories C
F.3 FG frame, plug in device (8 pole connectors)

F.3 FG frame, plug in device (10 pole connectors)


Technical data D
F.4 FG frame, draw out device (10 pole connectors)
Application guide E
F.4 FK frame, draw out device (6 pole connectors)

F.5 FG frame, SMR 2 Trip unit connection


Wiring diagrams F

Dimensions G

y on us
Numerical Index X

F.1
Record Plus
Recommended wiring diagrams

FD frame, plug in device (8 & 10 pole connectors)

X... ER
Wiring diagrams

7-

gy bk

bI ye
gy - grey
bl - blue
bk - black
ye - yellow

FE frame, plug in device (8 pole connectors)

B 41

4-
42

C
43 gy bk

4-
D 44 bI ye

gy - grey
bl - blue
E bk - black
ye - yellow

FE frame, plug in device (10 pole connectors)


F

G
EL ER

85 41 75
X 8- 4- 7-
86 42 86

87 43 gy bk 77

8- 4- 7-
88 44 bI ye 78
RCD

gy - grey
bl - blue
bk - black
ye - yellow

F.2
Record Plus

FE frame, draw out device (10 pole connectors)

EL 9 10 ER 9 10

T1 P1

Wiring diagrams
T- P-
T2 P2

T3 gy bk P3

T- P-
T4 bI ye P4

FG frame, plug in device (8 pole connectors)

gy - grey
bl - blue
bk - black D
ye - yellow

E
FG frame, plug in device (10 pole connectors)
F

EL ER G

gy - grey
bl - blue
bk - black
ye - yellow

F.3
Record Plus
Recommended Wiring diagrams

FG frame, draw out device (10 pole connectors)

EL ER
Wiring diagrams

T-

T-

A
FK frame 3 pole, draw out device (6 pole connectors)
B

F.4
Record Plus

FK frame 4 pole, draw out device (6 pole connectors)

Wiring diagrams
A

FG frame, SMR 2 trip unit connection


C

D
11
12

10
9
8
7
6
5
4
3
2
1

E
External CT-

External CT+

GFA - F
GFA +

ZSI_OUT -

ZSI_OUT +

ZSI_IN -

ZSI_IN +
G
Aux_GND
12 AUX GND
Target Output and Comm Adaptor

Aux_DC
11 AUX DC
Tx

Rx
10 TX
9 RX
RLY 1A
RLY 1B
X
FAMECM 434013

8 EXT_GND RLY 2A
7 +24 VDC RLY 2B
6 EXT_GND RLY 3A
5 COM + RLY 3B
4 COM + RLY 4A
3 COM_GND RLY 4B
2 COM -

- +
19 to 29 VDC
-
+ G - 1 COM -

Modbus/RS485
POWER Connect LEGEND :
SUPPLY 1.RLY - Relays are 3A/250 VAC
2
2. - Standard 3 m (0.75mm -600VAC)Cable

F.5
Just rel
Record Plus
FD & FE frame
G.2 Breakers
G.3 Phase separators
G.3 Residual current devices RCD’s
G.5 Electrical operators
G.6 Rotary handles
G.8 Plug-in version
G.9 Drawout version
G.10 Door flanges
G.11 Padlock fixed
G.12 Backplate
G.13 Terminal shields

FG frame
G.14 Breakers
G.15 Residual current devices RCD’s
G.16 Electrical operators
G.17 Rotary handles
G.18 Plug-in version The breaker
G.18 Drawout version
G.19 Mechanical interlock Order codes A
G.20 Door flanges
G.21 Padlocking fixed
Trip units B
G.21 Backplate
G.22 Terminal shields
Components & Accessories C
FK frame
G.24 Breakers
G.24 Electrical operators
Technical data D
G.25 Rotary handles
G.26 Drawout version Application guide E
G.26 Phase separators
G.27 Door flanges
Wiring diagrams F
G.28 Mechanical interlock
G.29 Terminal shields
Dimensions G

y on us
Connectivity
Numerical Index X
G.30 Connectivity-60 mm system FD and FE frames

G.32 FG & FK frame, external groundfault sensors


G.32 FE, FG & FK frame, Controller for changeover device
G.33 FG frame SMR2, Trip unit accessory; FACM module
G.33 Relay RD5 and RD6
G.33 Rectangular sensor
G.33 Circular sensor

G.1
Record Plus
Dimensional Drawings

Breakers - FD63/160 fixed, front connected

.
. .
Dimensions

.
.
.

C Breakers - FE160 and FE250 fixed, front connected

E
. .

F .

X
. .
. .

G.2
Record Plus
Dimensional Drawings

RCD side mounted - FD63/160

.
. .
. . .

FD & FE frame
. .
.
. . .
. .
.

Breakers with phase separator - FD and FE frames C

Y2 E

Dimensions F
FD63 FE160
FD160 FE250

X2 X1
X3
X1 330 410
G
X2 245 304
X3 287,5 357
Y1 63 72,5
Y2 105,5 126
X

Y1

G.3
Record Plus
Dimensional Drawings

RCD bottom mounted - FD63/160

.
.

.
Dimensions

.
. .
.
A .

C RCD bottom mounted - FE160 and FE250

E
.
.

F
.

X
.

.
.

.
. .

G.4
Record Plus
Dimensional Drawings

Breakers with electrical operator - FD63/160

185
145

FD & FE frame
49.3
50.9
79.8
83
40.5 40.5
81 108

43.5
83

33.6 A
147 87

Breakers with electrical operator - FE160 and FE250 C

194
155 D

E
61.9
56.9

79.8
96.4

F
52.25 52.25
104.5 139.5
G
55.25

X
83

33.6

110.5
157

G.5
Record Plus
Dimensional Drawings

Rotary handle - Breaker and through panel mounted - FD63/160

52.2
1.8 25.2
214.5
27 27 7 174.5

33.8
55
28.3
Dimensions

2.5
81.5
1.5

11.7 10 70
27 76
81 121 4

C Rotary handle - Breaker and through panel mounted - FE160 and FE250

D 95
52.5 81 30
5.8 29.2
33.8
28.3
22.3

E
12.45

62.5
81.5

F
28.7

G
1.5

X 11.7
73.50
49.5
86
81
121
94.6 125
105 174.5
214.5

G.6
Record Plus
Dimensional Drawings

Rotary handle - Door mounted FD63/160


L = H - 75
30.25
25.2 141.5 H - 117
1.8 131.5
Rm
64 in 8
0
5

30.25
33.8
55
72

FD & FE frame
1.5 Min 5 Max.

67 40
64
76
145 ) H ) 250
11.7

72

A
L
=
H
-7

33
5

250 ) H ) 350
H= ) 600 (FDNRE) long Shaft
B

Rotary handle - Door mounted - FE 160 and FE250 C


L = H - 75
141.5
30.25
131.5 H - 117
29.2 81 Rm
in 8
0
D
30.25

E
33.8
72

F
1.5 Min 5 Max.

73.5 G
86 67 40
145 ) H ) 250
72 X
L
=
H
-7
5

33
250 ) H ) 350
H= ) 600 (FDNRE) long Shaft

G.7
Record Plus
Dimensional Drawings

Plug-in version - FD63/160

.
. . .
Dimensions

. .

C Plug-in version - FE160 and FE250

E . .
. . . .

G.8
Record Plus
Dimensional Drawings

Drawout version - FE160 and FE250

FD & FE frame
1) Mounting on panel/backplate or on profiles
2) Mounting through a front panel
(all electrical connection behind panel)
3) Mounting of device through door or panel
(parts for operating the drawout mechanism/breaker pass
through the door or panel*) A
*Here a door flange (model for rotary handle) can be used
4) Mounting of device behind door or panel
(all parts for operating the drawout mechanism/breaker behind
the door or panel) B

FE Frame, 2 pcs. mechanically interlocked C

460,3
E
166,3
420
134
240,2
128,9
25,3 92,7 48
F
9,1

G
108

G.9
Record Plus
Dimensional Drawings

Door flanges - FD63/160, FE160 and FE250


Breaker front Toggle area RCD
FDFF3 FDFF4 FEFT FDFF3
FEFF3 FEFF4 FDFF4

X W3
A W2 W1
W1
B
Dimensions

Y
R2 max. C Z

3p Breaker hole
4p Breaker hole

Dimensions
A B C Rmin W1(max) W2(max) W3(max) X Y Z
FDFF3 FD 63/160 3p 13,5 55 55 80 83,2 85,8 93,2 114 78 1...4
FDFF4 FD 63/160 4p 13,5 55 55 93,5 83,2 85,8 93,2 146 78 1...4
FEFF3 FE160/250 3p 17,5 55,5 70,5 91,75 89,2 - - 138 97 1...4
FEFF4 FE160/250 4p 17,5 55,5 70,5 102,5 89,2 - - 173 97 1...4
FEFT FE 160/250 3p/4p 17,5 55,5 70,5 93,5 93,2 - - 60 97 1...4

A
FDFF3 (RCD*) FD 63/160 3p 13,5 155 42 80 83,2 85,8 93,2 114 78 1...4
FDFF4 (RCD*) FD 63/160 4p 13,5 155 42 93,5 83,2 85,8 93,2 146 78 1...4

B FDFF3 (RCD*) FE160/250 3p/4p 18 182,1 42 80 89,2 - - 114 78 1...4

C Door flanges - FD63/160, FE160 and FE250


FDFE FDFH
FEFE

D
Electrical Operator X Rotary Handle
A
W1 W1
E B
Y
R2 max. C
F
3p Breaker hole
4p Breaker hole

G
Z
Z

X
Dimensions
3+4 pole versions A B C Rmin W1(max) X Y Z
FDFE FD 63/160 Electr. Operator 13.5 49.5 64.5 80 141 148.5 124.5 1...4
FEFE FE 160/250 Electr. Operator 17.5 46 80 100 170 172 124.5 1...4

FDFH FD63/160 Rotary Handle 13.5 46,25 63.75 100 125 120 120 1...4
FEFH FE 160/250 Rotary Handle 17.5 46.25 81.75 100 125 120 120 1...4

G.10
Record Plus
Dimensional Drawings

Padlock fixed - FD63/160

30.6 63.5 35.9

FD & FE frame
129.7
112.7

88.7
82.6

Padlock fixed - FE160 and FE250 C

E
42.5 67 60.5

G
137
121
88.5

97

G.11
Record Plus
Dimensional Drawings

Backplate - FD63/160

Y4
Y3 Z
Dimensions
Dimensions

FD 63
FD 160
X1 230
X2 330
X1 X2 Y1 108
Y2 81
Y3 108
Y4 135
Z 1
Y2
Y1

C Backplate - FE160 and FE250

E
Y4
Y3 Z Dimensions
FE160
F FE250
X1 310
X2 410

G X1 X2 Y1 139.5
Y2 104.5
Y3 139.5

X Y4 175
Z 1
Y2
Y1

G.12
Record Plus
Dimensional Drawings

Breaker with short terminal shields - FD63/160

.
.

FD & FE frame
.

Breaker with long terminal shields - FD63/160 C

. D
.

E
.

G.13
Record Plus
Dimensional Drawings

Breaker with short terminal shields - FE160 and FE250


Dimensions

C Breaker with long terminal shields - FE160 and FE250


.
.
.

E
.

G
.

G.14
Record Plus
Dimensional Drawings

Breakers - FG400/630 fixed, front connected

FG frame
A

RCD bottom mounted - FG 400/630 C

F
.

. .
. . .
. .

G.15
Record Plus
Dimensional Drawings

Breaker with electrical operator - FG400/630

39.7

122
143.6
30.7
Dimensions

278 69.5
69.5
174
139
71.5

124

31.7
A 238.5
141

G.16
Record Plus
Dimensional Drawings

Rotary handle, breaker and through panel mounted - FG400/630

211.25
138.7 106 55
90
16.75 45

37.75
30

FG frame
101

63.25
129

39.25 111
93 161
108.6

Rotary handle, door mounted - FG400/630 C

G.17
Record Plus
Dimensional Drawings

Plug-in version - FG400/630


Dimensions

C Drawout version - FG400/630

185.7 230.7
D 45 45
92.85
45
115.35
45 45 21.5
90

E
148.5

180.5
100
200

361
297

F
328

G 92.85 69.35 48 183.7 48 21.5


138.7 211
266.2 260 / 286 / 292
221.2
229.25 274.25 297
X 48

22.5 235 6
6 118
59 6
98.5

45
150

22.5
60

197
120
300

332
300
150
166

104.35
45 96
Backplate mounting Rear mounting Rail mounting Panel door cutout

G.18
Record Plus
Dimensional Drawings

FG Frame, 2 pcs. mechanically interlocked

208
460
159
420 154
302,1 138
25,3 101,6 48
10,5

FG frame
152
108

FG Frame and FE Frame. mechanically interlocked C

460,3
E
166,3 25,3 420 208
134 159
128,9 154
144,8
102
48
138
F
10,5

48
9,1

G
108
152

G.19
Record Plus
Dimensional Drawings

Door flanges - FG400/630


Dimensions

X
A W1 W1

R2 max. C Z

3p Breaker hole
4p Breaker hole

A Dimensions
A B C Rmin W1(max) X Y Z
FGFT FG 400/630 Toggle 3p/4p 22.5 73 127 100 115 95 135 1...4

B FDFF4 FG 400/630 RCD 3p/4p 22.5 297.5 68.5 93.5 115 146 78 1...4

C Door flanges - FG400/630

D 159
A
79,5
CL of Breaker

B 85
E Electrical Operator
170
Rotary Handle
W1 Y CL of Breaker
R2 max. C

F 3p Breaker hole
4p Breaker hole
X
mm

X
Z
Z

Dimensions
3+4 pole versions A B C Rmin W1(max) X Y Z
FGFE FG 400/630 Electr. Operator 70.5 85 145 100 238.5 41 126 1...4
FGFH FG 400/630 Rotary Handle 22.5 72.5 129 115 161 191 181.5 1...4

G.20
Record Plus
Dimensional Drawings

Padlock fixed - FG400/630

56 121 138.7
69.35
54

FG frame
102

105
262

26.5
131
106

71
177
142

Backplate - FG400/630 C

Y1
D
Y2 Z

E
X1 X2 X3 X4

Dimensions G
FG400
FG630
X1 322
X2 346
X
X3 367
X4 459
Y1 (3p) 160
Y1 (4p) 205
Y2 (3p) 139
Y2 (4p) 184
Z 1.5

G.21
Record Plus
Dimensional Drawings

Breaker with short terminal shields - FG400/630

24.35 45 45 24.35
159.5
Dimensions

102
185.4

229.05
316.8
321.8
198.8
321.8
63 89.3
95.7
138.7 (3p) 99.3
A 183.7 (4p) 110.5

C Breaker with medium terminal shields - FG400/630

D
159.5 24.35 45 45 24.35

F
102
185.4

229.05

344.8
344.8

63 89.3
94.7
138.7 (3p) 99.3
183.7 (4p) 110.5

G.22
Record Plus
Dimensional Drawings

Breaker with long and wide terminal shields - FG400/630

198 (3P)
263 (4P)

FG frame
499
A
159,5

G.23
Record Plus
Dimensional Drawings

Breakers - FK800/1250/1600 fixed, front connected

35 140 29
35 12
98 20
9 M12 M10 5
M8
20
Dimensions

169

158

60
280

278
320

102
298
130

M8

50 70 25 70 70 135
70 70 70 70 70 140
210 280 148
25 260

C Breaker with electrical operator - FK800/1250/1600

E 210 280
105 105

F
142

320

G
94
51

151

X
100 140
204 220
330 max

G.24
Record Plus
Dimensional Drawings

Rotary handle, door mounted - FK800/1250/1600

277.5
210 260
61.5 140 70
35 35 135

52.5
28.5

FK frame
86.5
180
278

148
140 152
166.5 210
300

Rotary handle, breaker and through panel mounted - FK800/1250/1600 C


226.5
210 24.5 min.
R150
26.5 35 135
35 min
13.5 D
52.5

E
278

67 40

1.5... 5max. F

148
37.5 152 G
240... 430

X
52.5
32

25

70 H < 600 (FNNRE)

G.25
Record Plus
Dimensional Drawings

Drawout version - FK800/1250/1600

Plug in position
Testposition
connected
211
125 273 125
out 34.5 73 23
59
Dimensions

189
189
189

20

55
140

325
325

360
74

out: 261
17

250 out: 372.6 / test: 357.6 / in: 338.1 250


in: 34.5
test: 15
A

C Breakers with phase separator - FG and FK frames

E Y2

F Dimensions
FG 400 FK 800
FG 630 FK 1250
FK 1600

G X2 X1
X3
X1 459 484
X2 - -
X3 - -

X Y1 90 135
Y2 - -

Y1

G.26
Record Plus
Dimensional Drawings

Door flanges - FK800/1250/1600

FK frame
W1

X
A

R2 max. C Z

3p Breaker hole
4p Breaker hole

A
Dimensions
A B C Rmin W1(max) X Y Z
FNFT FK 800/1250/1600 3p/4p 35 130 150 120 153 101 104 1...4 B

Door flanges - FK800/1250/1600 C


ON
Tripped
X
A D
B

R2 max. C
E
3p
4p

F
Z W1

G
min
86,5

Dimensions
3 + 4 pole versions A B C Rmin W1(max) X Y Z
FNFE FK 800/1250/1600 Electr. operator 35 129 151 120 220 142 125 1...4
FNFH FK 800/1250/1600 Rotary handle 35 114 163 190 210 232.5 232.5 1...4

G.27
Record Plus
Dimensional Drawings

FK Frame, 2 pcs. mechanically interlocked

660 315,8
203,6
600 195,8
490 190,8
470 55,8
45 102 280,8 47,2
max. 100 33,2
Dimensions

69,2
440
410

C FK Frame and FG Frame. mechanically interlocked

D 221,2
172,2
167,2 660
158,2 490
151,2 470
E 61,2 102 74,5
69,2

106,9

F
440
410

33,2 max 100


80
47,2
55,8
190,8
195,8
203,6
315,8

G.28
Record Plus
Dimensional Drawings

Breaker with long terminal shields - FK800/1250/1600

140

FK frame
480

231
210 260
280
A

G.29
Record Plus
Dimensional Drawings

Connectivity 60 mm system - FD and FE frame 3 pole

57 52 52
29 29
31 32
15

15

20-30

31.5
20
10 5
30

37.5
60
Dimensions

5-10

60
180
75
6.8

194
60

60
12
10.5

54
18

10.3

74
65
A 1.5

B
36

81

185 23 27 27
52.5
20-30

13.5
C
27

65
60

55

32
110

D
170
60

5-10
5-10
E 32 76
22.5

F
60

105
165

35 35
G 17.5 53
20-30

35
92.5
60

55.5
60

X
32
20-30

202
60

70.5
89.5

5-10

27 28
54 41.5 22 86

G.30
Record Plus
Dimensional Drawings

Connectivity 60 mm system - FD and FE frame 4 pole

57 52 55
29 29 31 32
15
15

10-20
5

31.5
20
30

37.5

10
60

Connectivity
5-10

60
75
60

125
240
6.8

60
252
60

12 60
10.5

18

72

10.3
A
74
65
36

1.5

245 23
B
108
27 27 27
20-30

13.5 52.5
75
C
5-10 27
60

55
110

32

D
22.5

60

230
60

5-10
E
60

32 76

F
225

140
60

35 35 35
17.5 53
20-30

35 35
G
92.5
55.5
60

32
60

X
60

70.5

242
89.5
20-30

60

5-10
27 28
54 41.5
22 86

G.31
Record Plus
Dimensional Drawings

FG & FK frame, external groundfault sensors


FG type FK type
Outline G frame GF

49 mm
61 mm

12
Dimensions

40
14 mm 6 mm

54 mm

4
12 mm dia

49

219
99
90
123 mm

93 mm

68 mm

39 39

40
A
50
30 mm 75
50 mm
B

C FE, FG & FK frame, Controller for changeover device

D
Controller type E and E Plus, front view Cut-out for panel or door mounting
Ø6
414 414

E
4xØ6
195

179

F
179

G 430

X Controller type E, top view Controller type E Plus, top view


170
110

G.32
Record Plus
Dimensional Drawings

FG frame SMR2 Trip unit accessory; FACM module


70
8,6 30,7

1,4
43,2

46
60
86

91

Connectivity
1,4

28,5

47,5
57,5

Relay RD5 and RD6 Rectangular sensor

C
Dimensions
axb H h E e d
BTR 175 70x175 162 85 261 46 225
D
BTR 305 115x305 226 116 402 55 360
BTR 350 150x350 271 140 460 55 415
E

Circular sensor
F

Dimensions
Ø A B C E F G
G
TTD22 22 52 21 56 27 65
TT35 35 118 90 78.5 27 104
TT60 60 143 102 94.5 27 117
X
TT80 80 163 110 114.5 27 125
TT110 110 198 140 150.5 32 155
TT160 160 248 181 200.5 32 197
TT210 210 298 210 250.5 32 227
Base for DIN-rail or
screw mounting included
TT0110 110 198 140 150.5 32 155 198
TT0210 210 298 210 250.5 32 227 296

G.33
Record Plus
Numerical index
Numerical index

G
X.1 Numerical index by catalogue number
X.7 Numerical index by reference number
X
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
BT... FDBEH3 430885 A.9 FDH36MC050ED 430019 A.7 FDKD3 430966 A.10
BTR 175 704154 A.39 FDBEH4 430886 A.9 FDH36MC080GD 430318 A.7 FDKD4 430967 A.10
BTR 305 704155 A.39 FDBES3 430887 A.9 FDH36MC100GD 430321 A.7 FDKE 617947 A.10
BTR 350 704156 A.39 FDBES4 430888 A.9 FDH36TD016ED 430020 A.6 FDKM1 436720 A.10
FA... FDBRC3 430889 A.9 FDH36TD020ED 430021 A.6 FDL36MC020ED 430065 A.7
FA1BPH 430813 A.8 FDBRC4 430890 A.9 FDH36TD025ED 430022 A.6 FDL36MC030ED 430066 A.7
FA1BR1 430088 A.8 FDBRCL2 433357 A.9 FDH36TD032ED 430023 A.6 FDL36MC050ED 430067 A.7
FA1BR2 430089 A.8 FDBRCS2 433358 A.9 FDH36TD040ED 430024 A.6 FDL36MC080GD 430498 A.7
FA1BR3 430504 A.8 FDBSS3 430891 A.9 FDH36TD050ED 430025 A.6 FDL36MC100GD 430501 A.7
FA1BR4 430505 A.8 FDBSS4 430892 A.9 FDH36TD063ED 430026 A.6 FDL36TD025ED 430070 A.6
FA1BR5 430506 A.8 FDC35TE016ED 433907 A.5 FDH36TD080GD 430338 A.6 FDL36TD032ED 430071 A.6
FA1BR6 430507 A.8 FDC35TE020ED 433911 A.5 FDH36TD100GD 430341 A.6 FDL36TD040ED 430072 A.6

By catalogue number
FA1BRH 430068 A.8 FDC35TE025ED 433914 A.5 FDH36TD125GD 430344 A.6 FDL36TD050ED 430073 A.6
FABAM01 432000 A.20 FDC35TE032ED 433918 A.5 FDH36TD160GD 435821 A.6 FDL36TD063ED 430074 A.6
FABAM10 432003 A.20 FDC35TE040ED 436117 A.5 FDH36TG025ED 430027 A.6 FDL36TD080GD 430518 A.6
FABAT01 430815 A.8 FDC35TE050ED 436118 A.5 FDH36TG032ED 430028 A.6 FDL36TD100GD 430521 A.6
FABAT10 430818 A.8 FDC35TE063ED 436133 A.5 FDH36TG040ED 430029 A.6 FDL36TD125GD 430524 A.6
FAC 430821 A.10 FDC35TE080GD 436143 A.5 FDH36TG050ED 430030 A.6 FDL36TD160GD 435845 A.6
FAECA3 436453 A.47 FDC35TE100GD 436144 A.5 FDH36TG063ED 430031 A.6 FDL436MC020ED 430077 A.7
FAECA6 872240 A.47 FDC35TE125GD 433924 A.5 FDH36TG080GD 430357 A.6 FDL436MC030ED 430078 A.7
FAECE3 872141 A.47 FDC35TE160GD 433925 A.5 FDH36TG100GD 430360 A.6 FDL436MC050ED 430079 A.7
FAECE6 872140 A.47 FDC45TE016ED 433948 A.5 FDH36TG125GD 430363 A.6 FDL436MC080GD 430537 A.7
FAMAM2 436183 A.26 FDC45TE020ED 433949 A.5 FDH36TG160GD 435824 A.6 FDL436MC100GD 430540 A.7
FAMB2 434448 A.26 FDC45TE025ED 433950 A.5 FDH436MC003ED 436398 A.7 FDL436TD025ED 430082 A.6
FAMECM 434013 A.26 FDC45TE032ED 433951 A.5 FDH436MC007ED 430032 A.7 FDL436TD032ED 430083 A.6
FAMGAM2 436185 A.26 FDC45TE040ED 433952 A.5 FDH436MC012ED 430033 A.7 FDL436TD040ED 430084 A.6
FAMGAS2 436186 A.26 FDC45TE050ED 433953 A.5 FDH436MC020ED 430034 A.7 FDL436TD050ED 430085 A.6
FAMGAT2 436187 A.26 FDC45TE063ED 433954 A.5 FDH436MC030ED 430035 A.7 FDL436TD063ED 430086 A.6
FAMGFM2 436188 A.26 FDC45TE080GD 436145 A.5 FDH436MC050ED 430036 A.7 FDL436TD080GD 430557 A.6
FAMGFS2 436189 A.26 FDC45TE100GD 436146 A.5 FDH436MC080GD 430376 A.7 FDL436TD100GD 430560 A.6
FAMGFT2 436190 A.26 FDC45TE125GD 436147 A.5 FDH436MC100GD 430379 A.7 FDL436TD125GD 430563 A.6
FAMLT1 433376 A.22 FDC45TE160GD 436148 A.5 FDH436TD016ED 430037 A.6 FDL436TD160GD 435848 A.6
FAMMT2 436191 A.26 FDDDF3 430893 A.9 FDH436TD020ED 430038 A.6 FDL456TD063ED 430087 A.6
FAMSM2 436192 A.26 FDDDF4 430896 A.9 FDH436TD025ED 430039 A.6 FDL456TD080GD 430568 A.6
FAMST2 436197 A.26 FDDFF3 430899 A.9 FDH436TD032ED 430040 A.6 FDL456TD100GD 430571 A.6
FAPF8 430823 A.9 FDDFF4 430902 A.9 FDH436TD040ED 430041 A.6 FDL456TD125GD 430574 A.6
FAPFM 430824 A.9 FDDFQ3 433489 A.9 FDH436TD050ED 430042 A.6 FDL456TD160GD 435851 A.6
FAPIP 430825 A.9 FDDFQ4 433492 A.9 FDH436TD063ED 430043 A.6 FDL46TD025ED 430090 A.6
FAPM8
FAPPS
430826
430827
A.9
A.9
FDDMP3
FDDMP4
430905
430908
A.9
A.9
FDH436TD080GD
FDH436TD100GD
430396
430399
A.6
A.6
FDL46TD032ED
FDL46TD040ED
430091
430092
A.6
A.6
A
FAR 433500 A.22 FDE36TE016ED 433649 A.5 FDH436TD125GD 430402 A.6 FDL46TD050ED 430093 A.6
FAS01D 436309 A.21 FDE36TE020ED 433651 A.5 FDH436TD160GD 435827 A.6 FDL46TD063ED 430094 A.6
FAS01L 430828 A.8 FDE36TE025ED 433653 A.5 FDH436TG025ED 430044 A.6 FDL46TD080GD 430591 A.6
FAS01R
FAS10D
430831
436310
A.8
A.21
FDE36TE032ED
FDE36TE040ED
433655
433657
A.5
A.5
FDH436TG032ED
FDH436TG040ED
430045
430046
A.6
A.6
FDL46TD100GD
FDL46TD125GD
430594
430597
A.6
A.6
B
FAS10L 430834 A.8 FDE36TE050ED 433659 A.5 FDH436TG050ED 430047 A.6 FDL46TD160GD 435854 A.6
FAS10R 430837 A.8 FDE36TE063ED 433661 A.5 FDH436TG063ED 430048 A.6 FDN13TF016EF 433316 A.5
FASHTB 430840 A.8 FDE36TE080GD 433663 A.5 FDH436TG080GD 430415 A.6 FDN13TF020EF 433322 A.5
FASHTD
FASHTF
430843
430846
A.8
A.8
FDE36TE100GD
FDE36TE125GD
433665
433667
A.5
A.5
FDH436TG100GD
FDH436TG125GD
430418
430421
A.6
A.6
FDN13TF025EF
FDN13TF032EF
433328
433334
A.5
A.5
C
FASHTH 435118 A.8 FDE36TE160GD 433669 A.5 FDH436TG160GD 435830 A.6 FDN13TF040EF 433340 A.5
FASHTJ 430849 A.8 FDE46TE016ED 433697 A.5 FDH456TD063ED 430049 A.6 FDN13TF050EF 433346 A.5
FASHTN 430852 A.8 FDE46TE020ED 433699 A.5 FDH456TD080GD 430426 A.6 FDN13TF063EF 433352 A.5
FASHTU
FAT
430855
431402
A.8
A.22
FDE46TE025ED
FDE46TE032ED
433701
433703
A.5
A.5
FDH456TD100GD
FDH456TD125GD
430429
430432
A.6
A.6
FDN13TF080GF
FDN13TF100GF
433519
433522
A.5
A.5
D
FAUVDN 430858 A.8 FDE46TE040ED 433705 A.5 FDH456TD160GD 435833 A.6 FDN13TF125GF 433525 A.5
FAUVR8 436472 A.8 FDE46TE050ED 433707 A.5 FDH456TG063ED 430050 A.6 FDN13TF160GF 433527 A.5
FAUVRB 440018 A.8 FDE46TE063ED 433709 A.5 FDH456TG080GD 430437 A.6 FDN36MC003ED 436409 A.7
FAUVRD
FAUVRF
430861
430864
A.8
A.8
FDE46TE080GD
FDE46TE100GD
433711
433713
A.5
A.5
FDH456TG100GD
FDH456TG125GD
430440
430443
A.6
A.6
FDN36MC007ED
FDN36MC012ED
430095
430096
A.7
A.7
E
FAUVRH 435120 A.8 FDE46TE125GD 433715 A.5 FDH456TG160GD 435836 A.6 FDN36MC020ED 430097 A.7
FAUVRJ 430867 A.8 FDE46TE160GD 433717 A.5 FDH46TD016ED 430051 A.6 FDN36MC030ED 430098 A.7
FAUVRN 430870 A.8 FDEMF8 430920 A.8 FDH46TD020ED 430052 A.6 FDN36MC050ED 430099 A.7
FAUVRU
FB...
430873 A.8 FDEMFD
FDEMFF
430926
430929
A.8
A.8
FDH46TD025ED
FDH46TD032ED
430053
430054
A.6
A.6
FDN36MC080GD
FDN36MC100GD
430610
430613
A.7
A.7
F
FBAD3 433443 A.43 FDEMFH 430932 A.8 FDH46TD040ED 430055 A.6 FDN36TD016ED 430100 A.6
FBAD4 433446 A.43 FDEMFJ 430935 A.8 FDH46TD050ED 430056 A.6 FDN36TD020ED 430101 A.6
FBAE3 433449 A.43 FDEMFN 430938 A.8 FDH46TD063ED 430057 A.6 FDN36TD025ED 430102 A.6
FBAE4
FBB3E
433452
433455
A.43
A.43
FDFE
FDFF3
432010
430941
A.10
A.10
FDH46TD080GD
FDH46TD100GD
430460
430463
A.6
A.6
FDN36TD032ED
FDN36TD040ED
430103
430104
A.6
A.6
G
FBB3S 433458 A.43 FDFF4 430942 A.10 FDH46TD125GD 430466 A.6 FDN36TD050ED 430105 A.6
FBB4E 433461 A.43 FDFH 430829 A.10 FDH46TD160GD 435839 A.6 FDN36TD063ED 430106 A.6
FBB4S 433464 A.43 FDH13TF016EF 433246 A.5 FDH46TG025ED 430058 A.6 FDN36TD080GD 430630 A.6
FBCI3
FBCI4
433377
433444
A.43
A.43
FDH13TF020EF
FDH13TF025EF
433255
433262
A.5
A.5
FDH46TG032ED
FDH46TG040ED
430059
430060
A.6
A.6
FDN36TD100GD
FDN36TD125GD
430633
430636
A.6
A.6
X
FBF6 883970 A.9 FDH13TF032EF 433268 A.5 FDH46TG050ED 430061 A.6 FDN36TD160GD 433572 A.6
FBTF3L12 433456 A.43 FDH13TF040EF 433274 A.5 FDH46TG063ED 430062 A.6 FDN36TG025ED 430107 A.6
FBTF4L12 433497 A.43 FDH13TF050EF 433280 A.5 FDH46TG080GD 430479 A.6 FDN36TG032ED 430108 A.6
FBTS10L12 433474 A.43 FDH13TF063EF 433286 A.5 FDH46TG100GD 430482 A.6 FDN36TG040ED 430109 A.6
FBTS1L12 433468 A.43 FDH13TF080GF 433292 A.5 FDH46TG125GD 430485 A.6 FDN36TG050ED 430110 A.6
FD... FDH13TF100GF 433298 A.5 FDH46TG160GD 435842 A.6 FDN36TG063ED 430111 A.6
FD1BPE 430876 A.8 FDH13TF125GF 433304 A.5 FDJB 430945 A.9 FDN36TG080GD 430649 A.6
FD1BRE 430877 A.8 FDH13TF160GF 433310 A.5 FDJK 430069 A.9 FDN36TG100GD 430652 A.6
FD1PF 430878 A.10 FDH36MC003ED 436396 A.7 FDJL3 430951 A.9 FDN36TG125GD 430655 A.6
FD1PR 430879 A.10 FDH36MC007ED 430015 A.7 FDJL4 430954 A.9 FDN36TG160GD 433575 A.6
FDBAM11 430880 A.8 FDH36MC012ED 430016 A.7 FDJP 430957 A.9 FDN436MC003ED 436411 A.7
FDBEA3 430883 A.9 FDH36MC020ED 430017 A.7 FDJS3 430960 A.9 FDN436MC007ED 430112 A.7
FDBEA4 430884 A.9 FDH36MC030ED 430018 A.7 FDJS4 430963 A.9 FDN436MC012ED 430113 A.7

X.1
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FDN436MC020ED 430114 A.7 FDQDS4M 431022 A.8 FEH36MC003JF 436361 A.14 FEH456TD200KF 432266 A.16
FDN436MC030ED 430115 A.7 FDS35TD016ED 430161 A.5 FEH36MC007JF 434742 A.14 FEH456TD250KF 432269 A.16
FDN436MC050ED 430116 A.7 FDS35TD020ED 430163 A.5 FEH36MC012JF 434745 A.14 FEH456TG100JF 436026 A.13
FDN436MC080GD 430668 A.7 FDS35TD025ED 430165 A.5 FEH36MC020JF 434748 A.14 FEH456TG125JF 436027 A.13
FDN436MC100GD 430671 A.7 FDS35TD032ED 430167 A.5 FEH36MC030JF 434751 A.14 FEH456TG160JF 436028 A.13
FDN436TD016ED 430117 A.6 FDS35TD040ED 430169 A.5 FEH36MC050JF 434754 A.14 FEH456TG160KF 435908 A.16
FDN436TD020ED 430118 A.6 FDS35TD050ED 430178 A.5 FEH36MC080JF 435893 A.14 FEH456TG200KF 435909 A.16
FDN436TD025ED 430119 A.6 FDS35TD063ED 432952 A.5 FEH36MC100JF 434757 A.14 FEH456TG250KF 435910 A.16
FDN436TD032ED 430120 A.6 FDS35TD080GD 432955 A.5 FEH36MC125JF 436327 A.14 FEH46AA025JBF 435863 A.14
FDN436TD040ED 430121 A.6 FDS35TD100GD 432958 A.5 FEH36MC160JF 434763 A.14 FEH46AA063JEF 435866 A.14
FDN436TD050ED 430122 A.6 FDS35TD125GD 432961 A.5 FEH36MC160KF 434766 A.16 FEH46AA125JGF 431201 A.14
FDN436TD063ED 430123 A.6 FDS35TD160GD 433602 A.5 FEH36MC200KF 436754 A.16 FEH46AA125KGF 431824 A.17
FDN436TD080GD 430688 A.6 FDS45TD016ED 430224 A.5 FEH36MC250KF 434769 A.16 FEH46AA160JJF 431204 A.14
FDN436TD100GD 430691 A.6 FDS45TD020ED 430226 A.5 FEH36SA125JGF 431138 A.15 FEH46AA160KJF 431207 A.17
FDN436TD125GD 430694 A.6 FDS45TD025ED 430228 A.5 FEH36SA160JJF 431141 A.15 FEH46AA250KKF 431210 A.17
FDN436TD160GD 433578 A.6 FDS45TD032ED 430230 A.5 FEH36SA160KJF 431144 A.17 FEH46SA125JGF 431336 A.15
FDN436TG025ED 430124 A.6 FDS45TD040ED 430232 A.5 FEH36SA250KKF 431147 A.17 FEH46SA160JJF 431339 A.15
Numerical index

FDN436TG032ED 430125 A.6 FDS45TD050ED 430241 A.5 FEH36TA025JF 434772 A.13 FEH46SA160KJF 431342 A.17
FDN436TG040ED 430126 A.6 FDS45TD063ED 432964 A.5 FEH36TA032JF 434775 A.13 FEH46SA250KKF 431345 A.17
FDN436TG050ED 430127 A.6 FDS45TD080GD 432967 A.5 FEH36TA040JF 434778 A.13 FEH46TA025JF 434883 A.13
FDN436TG063ED 430128 A.6 FDS45TD100GD 432970 A.5 FEH36TA050JF 434781 A.13 FEH46TA032JF 434886 A.13
FDN436TG080GD 430707 A.6 FDS45TD125GD 432973 A.5 FEH36TA063JF 434784 A.13 FEH46TA040JF 434889 A.13
FDN436TG100GD 430710 A.6 FDS45TD160GD 433604 A.5 FEH36TA080JF 431165 A.13 FEH46TA050JF 434892 A.13
FDN436TG125GD 430713 A.6 FDTCA1316 433400 A.9 FEH36TA100JF 431171 A.13 FEH46TA063JF 434895 A.13
FDN436TG160GD 433581 A.6 FDTCA1416 433401 A.9 FEH36TA125JF 431177 A.13 FEH46TA080JF 431363 A.13
FDN456TD063ED 430129 A.6 FDUA3 431025 A.10 FEH36TA160JF 431183 A.13 FEH46TA100JF 431369 A.13
FDN456TD080GD 430718 A.6 FDUA4 431026 A.10 FEH36TD100JF 431007 A.13 FEH46TA125JF 431375 A.13
FDN456TD100GD 430721 A.6 FDUF3 430830 A.9 FEH36TD125JF 431021 A.13 FEH46TA160JF 431381 A.13
FDN456TD125GD 430724 A.6 FDUF4 430832 A.9 FEH36TD125KF 431393 A.16 FEH46TD100JF 432287 A.13
FDN456TD160GD 433584 A.6 FDUT 433539 A.10 FEH36TD160JF 431965 A.13 FEH46TD125JF 432296 A.13
FDN456TG063ED 430130 A.6 FDY306D063ED 430150 A.7 FEH36TD160KF 431980 A.16 FEH46TD125KF 432300 A.16
FDN456TG080GD 430729 A.6 FDY306D160GD 430805 A.7 FEH36TD200KF 432076 A.16 FEH46TD160JF 432303 A.13
FDN456TG100GD 430732 A.6 FDY406D063ED 430151 A.7 FEH36TD250KF 432096 A.16 FEH46TD160KF 432307 A.16
FDN456TG125GD 430735 A.6 FDY406D160GD 430810 A.7 FEH36TG100JF 434808 A.13 FEH46TD200KF 432311 A.16
FDN456TG160GD 433587 A.6 FE... FEH36TG125JF 434811 A.13 FEH46TD250KF 432316 A.16
FDN46TD016ED 430131 A.6 FE1BPE 432011 A.20 FEH36TG160JF 434817 A.13 FEH46TG100JF 434919 A.13
FDN46TD020ED 430132 A.6 FE1BPW 432184 A.21 FEH36TG160KF 434820 A.16 FEH46TG125JF 434922 A.13
FDN46TD025ED 430133 A.6 FE1BRE 432012 A.20 FEH36TG200KF 434823 A.16 FEH46TG160JF 434928 A.13
A FDN46TD032ED
FDN46TD040ED
430134
430135
A.6
A.6
FE1BRW
FE1I2
432188
437001
A.21
A.46
FEH36TG250KF
FEH406F160JF
434826
431213
A.16
A.18
FEH46TG160KF
FEH46TG200KF
434931
434934
A.16
A.16
FDN46TD050ED 430136 A.6 FE1PF 432017 A.22 FEH406F250KF 431216 A.19 FEH46TG250KF 434937 A.16
FDN46TD063ED 430137 A.6 FEBAT01 430969 A.20 FEH436MC050JF 434829 A.14 FEJB 432073 A.22
FDN46TD080GD 430752 A.6 FEBAT10 430970 A.20 FEH436MC100JF 434832 A.14 FEJL3 432079 A.22
B FDN46TD100GD
FDN46TD125GD
430755
430758
A.6
A.6
FEBE43
FEBE44
432018
432019
A.21
A.21
FEH436MC125JF
FEH436MC160JF
436329
434838
A.14
A.14
FEJL4
FEJN3
432082
436467
A.22
A.21
FDN46TD160GD 433590 A.6 FEBE93 432020 A.21 FEH436MC160KF 434841 A.16 FEJN4 436468 A.21
FDN46TG025ED 430138 A.6 FEBE94 432021 A.21 FEH436MC200KF 436755 A.16 FEJP 432085 A.22
FDN46TG032ED 430139 A.6 FEBEA3 432022 A.21 FEH436MC250KF 434844 A.16 FEJS3 432088 A.22
C FDN46TG040ED
FDN46TG050ED
430140
430141
A.6
A.6
FEBEA4
FEBEH3
432023
432024
A.21
A.21
FEH436SA125JGF
FEH436SA160JJF
431225
431228
A.15
A.15
FEJS4
FEL306F160JF
432091
431419
A.22
A.18
FDN46TG063ED 430142 A.6 FEBEH4 432025 A.21 FEH436SA160KJF 431231 A.17 FEL306F250KF 431422 A.19
FDN46TG080GD 430771 A.6 FEBES3 432026 A.21 FEH436SA250KKF 431234 A.17 FEL36AA025JBF 435869 A.14
FDN46TG100GD 430774 A.6 FEBES4 432027 A.21 FEH436TA025JF 434847 A.13 FEL36AA063JEF 435872 A.14
D FDN46TG125GD
FDN46TG160GD
430777
433593
A.6
A.6
FEBRC3
FEBRC4
432028
432029
A.21
A.21
FEH436TA032JF
FEH436TA040JF
434850
434853
A.13
A.13
FEL36AA125JGF
FEL36AA125KGF
431405
431836
A.14
A.17
FDN66TD016ED 430143 A.5 FEBRCS3 432190 A.21 FEH436TA050JF 434856 A.13 FEL36AA160JJF 431410 A.14
FDN66TD020ED 430144 A.5 FEBRCS4 432191 A.21 FEH436TA063JF 434859 A.13 FEL36AA160KJF 431413 A.17
FDN66TD025ED 430145 A.5 FEBSS3 432032 A.21 FEH436TA080JF 431252 A.13 FEL36AA250KKF 431416 A.17
E FDN66TD032ED
FDN66TD040ED
430146
430147
A.5
A.5
FEBSS4
FEDDF3
432033
432034
A.21
A.21
FEH436TA100JF
FEH436TA125JF
431258
431264
A.13
A.13
FEL36MC003JF
FEL36MC007JF
436363
434940
A.14
A.14
FDN66TD050ED 430148 A.5 FEDDF4 432037 A.21 FEH436TA160JF 431270 A.13 FEL36MC012JF 434943 A.14
FDN66TD063ED 430149 A.5 FEDFF3 432040 A.21 FEH436TD100JF 432198 A.13 FEL36MC020JF 434946 A.14
FDN66TD080GD 430794 A.5 FEDFF4 432043 A.21 FEH436TD125JF 432205 A.13 FEL36MC030JF 434949 A.14
F FDN66TD100GD
FDN66TD125GD
430797
430800
A.5
A.5
FEDFQ3
FEDFQ4
430987
431842
A.21
A.21
FEH436TD125KF
FEH436TD160JF
432209
432214
A.16
A.13
FEL36MC050JF
FEL36MC080JF
434952
435896
A.14
A.14
FDN66TD160GD 433599 A.5 FEDMP3 432046 A.21 FEH436TD160KF 432218 A.16 FEL36MC100JF 434955 A.14
FDNFT 430968 A.8 FEDMP4 432049 A.21 FEH436TD200KF 432223 A.16 FEL36MC125JF 436331 A.14
FDNR4 430971 A.8 FEEMF8 435812 A.20 FEH436TD250KF 432227 A.16 FEL36MC160JF 434961 A.14
G FDNRC/5
FDNRCV/5
436474
436475
A.8
A.8
FEEMFD
FEEMFF
432052
432055
A.20
A.20
FEH436TG100JF
FEH436TG125JF
435902
435903
A.13
A.13
FEL36MC160KF
FEL36MC200KF
434964
436756
A.16
A.16
FDNRD/5 436476 A.8 FEEMFH 432058 A.20 FEH436TG160JF 435904 A.13 FEL36MC250KF 434967 A.16
FDNRDV/5 436477 A.8 FEEMFJ 432061 A.20 FEH436TG160KF 435905 A.16 FEL36SA125JGF 431431 A.15
FDNRE 430986 A.8 FEEMFN 432064 A.20 FEH436TG200KF 435906 A.16 FEL36SA160JJF 431434 A.15
X FDNRF/5
FDNRFV/5
436478
436479
A.8
A.8
FEEO1J
FEEO1N
437000
437003
A.47
A.47
FEH436TG250KF
FEH456SA125JGF
435907
431285
A.16
A.15
FEL36SA160KJF
FEL36SA250KKF
431437
431440
A.17
A.17
FDNRY/5 436487 A.8 FEFE 430943 A.22 FEH456SA160JJF 431288 A.15 FEL36TA025JF 434970 A.13
FDNRYV/5 436488 A.8 FEFF3 432067 A.22 FEH456SA160KJF 431291 A.17 FEL36TA032JF 434973 A.13
FDNRZ/5 436489 A.8 FEFF4 432068 A.22 FEH456SA250KKF 431294 A.17 FEL36TA040JF 434976 A.13
FDNRZV/5 436490 A.8 FEFT 432071 A.22 FEH456TA063JF 434871 A.13 FEL36TA050JF 434979 A.13
FDQDB3H 433364 A.8 FEH306F160JF 431126 A.18 FEH456TA080JF 431300 A.13 FEL36TA063JF 434982 A.13
FDQDB3M 433370 A.8 FEH306F250KF 431129 A.19 FEH456TA100JF 431306 A.13 FEL36TA080JF 431458 A.13
FDQDB4H 433373 A.8 FEH36AA025JBF 435857 A.14 FEH456TA125JF 431312 A.13 FEL36TA100JF 431464 A.13
FDQDB4M 433379 A.8 FEH36AA063JEF 435860 A.14 FEH456TA160JF 431318 A.13 FEL36TA125JF 431470 A.13
FDQDI3M 433388 A.8 FEH36AA125JGF 431112 A.14 FEH456TD100JF 432242 A.13 FEL36TA160JF 431476 A.13
FDQDI4M 433397 A.8 FEH36AA125KGF 431116 A.17 FEH456TD125JF 432250 A.13 FEL36TD100JF 432332 A.13
FDQDS3H 433542 A.8 FEH36AA160JJF 431117 A.14 FEH456TD125KF 432254 A.16 FEL36TD125JF 432341 A.13
FDQDS3M 431013 A.8 FEH36AA160KJF 431120 A.17 FEH456TD160JF 432259 A.13 FEL36TD125KF 432344 A.16
FDQDS4H 433548 A.8 FEH36AA250KKF 431123 A.17 FEH456TD160KF 432263 A.16 FEL36TD160JF 432349 A.13

X.2
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FEL36TD160KF 432353 A.16 FEL46TD125KF 432924 A.16 FEN436TG100JF 436014 A.13 FERJ3G0080 432186 A.14
FEL36TD200KF 432357 A.16 FEL46TD160JF 432927 A.13 FEN436TG125JF 436015 A.13 FERJ3G0125 432192 A.14
FEL36TD250KF 432361 A.16 FEL46TD160KF 432930 A.16 FEN436TG160JF 436016 A.13 FERJ3J0100 432189 A.14
FEL36TG100JF 435923 A.13 FEL46TD200KF 432933 A.16 FEN436TG160KF 436017 A.16 FERJ3J0160 432195 A.14
FEL36TG125JF 435926 A.13 FEL46TD250KF 432936 A.16 FEN436TG200KF 436018 A.16 FERJ3K0160 432204 A.17
FEL36TG160JF 435932 A.13 FEL46TG100JF 435992 A.13 FEN436TG250KF 436019 A.16 FERJ3K0250 432207 A.17
FEL36TG160KF 435935 A.16 FEL46TG125JF 435995 A.13 FEN456SA125JGF 431871 A.15 FERJ43B0016 432210 A.14
FEL36TG200KF 435938 A.16 FEL46TG160JF 436002 A.13 FEN456SA160JJF 431874 A.15 FERJ43B0025 432213 A.14
FEL36TG250KF 435941 A.16 FEL46TG160KF 436005 A.16 FEN456SA160KJF 431877 A.17 FERJ43E0040 432216 A.14
FEL406F160JF 431506 A.18 FEL46TG200KF 436008 A.16 FEN456SA250KKF 431880 A.17 FERJ43E0063 432219 A.14
FEL406F250KF 431509 A.19 FEL46TG250KF 436011 A.16 FEN456TA063JF 435202 A.13 FERJ43G0080 432222 A.14
FEL436MC050JF 434994 A.14 FEN306F160JF 431712 A.18 FEN456TA080JF 431886 A.13 FERJ43G0125 432228 A.14

By catalogue number
FEL436MC100JF 434997 A.14 FEN306F250KF 431715 A.19 FEN456TA100JF 431892 A.13 FERJ43J0100 432225 A.14
FEL436MC125JF 436333 A.14 FEN36AA025JBF 435881 A.14 FEN456TA125JF 431898 A.13 FERJ43J0160 432231 A.14
FEL436MC160JF 435004 A.14 FEN36AA063JEF 435884 A.14 FEN456TA160JF 431904 A.13 FERJ43K0160 432240 A.17
FEL436MC160KF 435007 A.16 FEN36AA125JGF 431698 A.14 FEN456TD100JF 433028 A.13 FERJ43K0250 432243 A.17
FEL436MC200KF 436763 A.16 FEN36AA125KGF 431920 A.17 FEN456TD125JF 433034 A.13 FERJ45E0063 432249 A.14
FEL436MC250KF 435010 A.16 FEN36AA160JJF 431703 A.14 FEN456TD125KF 433037 A.16 FERJ45G0080 432252 A.14
FEL436SA125JGF 431518 A.15 FEN36AA160KJF 431706 A.17 FEN456TD160JF 433040 A.13 FERJ45G0125 432258 A.14
FEL436SA160JJF 431521 A.15 FEN36AA250KKF 431709 A.17 FEN456TD160KF 433043 A.16 FERJ45J0100 432255 A.14
FEL436SA160KJF 431524 A.17 FEN36MC003JF 436365 A.14 FEN456TD200KF 433046 A.16 FERJ45J0160 432261 A.14
FEL436SA250KKF 431527 A.17 FEN36MC007JF 435073 A.14 FEN456TD250KF 433049 A.16 FERJ45K0160 432270 A.17
FEL436TA025JF 435013 A.13 FEN36MC012JF 435076 A.14 FEN456TG100JF 436020 A.13 FERJ45K0250 432273 A.17
FEL436TA032JF 435016 A.13 FEN36MC020JF 435079 A.14 FEN456TG125JF 436021 A.13 FERJ4B0016 432276 A.14
FEL436TA040JF 435019 A.13 FEN36MC030JF 435082 A.14 FEN456TG160JF 436022 A.13 FERJ4B0025 432279 A.14
FEL436TA050JF 435022 A.13 FEN36MC050JF 435085 A.14 FEN456TG160KF 436023 A.16 FERJ4E0040 432282 A.14
FEL436TA063JF 435025 A.13 FEN36MC080JF 435899 A.14 FEN456TG200KF 436024 A.16 FERJ4E0063 432285 A.14
FEL436TA080JF 431545 A.13 FEN36MC100JF 435088 A.14 FEN456TG250KF 436025 A.16 FERJ4G0080 432288 A.14
FEL436TA100JF 431551 A.13 FEN36MC125JF 436335 A.14 FEN46AA025JBF 435887 A.14 FERJ4G0125 432294 A.14
FEL436TA125JF 431557 A.13 FEN36MC160JF 435094 A.14 FEN46AA063JEF 435890 A.14 FERJ4J0100 432291 A.14
FEL436TA160JF 431563 A.13 FEN36MC160KF 435097 A.16 FEN46AA125JGF 431787 A.14 FERJ4J0160 432297 A.14
FEL436TD100JF 432374 A.13 FEN36MC200KF 436764 A.16 FEN46AA125KGF 431938 A.17 FERJ4K0160 432306 A.17
FEL436TD125JF 432573 A.13 FEN36MC250KF 435100 A.16 FEN46AA160JJF 431790 A.14 FERJ4K0250 432309 A.17
FEL436TD125KF 432576 A.16 FEN36SA125JGF 431724 A.15 FEN46AA160KJF 431793 A.17 FERS3B0025 432312 A.15
FEL436TD160JF 432585 A.13 FEN36SA160JJF 431727 A.15 FEN46AA250KKF 431796 A.17 FERS3E0063 432315 A.15
FEL436TD160KF 432588 A.16 FEN36SA160KJF 431730 A.17 FEN46SA125JGF 431922 A.15 FERS3G0125 432318 A.15
FEL436TD200KF 432618 A.16 FEN36SA250KKF 431733 A.17 FEN46SA160JJF 431925 A.15 FERS3J0160 432321 A.15
FEL436TD250KF 432621 A.16 FEN36TA025JF 435103 A.13 FEN46SA160KJF 431928 A.17 FERS3K0250 432327 A.17
FEL436TG100JF
FEL436TG125JF
435944
435947
A.13
A.13
FEN36TA032JF
FEN36TA040JF
435106
435109
A.13
A.13
FEN46SA250KKF
FEN46TA025JF
431931
435214
A.17
A.13
FERS43B0025
FERS43E0063
432330
432333
A.15
A.15
A
FEL436TG160JF 435950 A.13 FEN36TA050JF 435112 A.13 FEN46TA032JF 435217 A.13 FERS43G0125 432336 A.15
FEL436TG160KF 435953 A.16 FEN36TA063JF 435115 A.13 FEN46TA040JF 435220 A.13 FERS43J0160 432339 A.15
FEL436TG200KF 435956 A.16 FEN36TA080JF 431751 A.13 FEN46TA050JF 435223 A.13 FERS43K0250 432345 A.17
FEL436TG250KF
FEL456SA125JGF
435959
431578
A.16
A.15
FEN36TA100JF
FEN36TA125JF
431757
431763
A.13
A.13
FEN46TA063JF
FEN46TA080JF
435226
431949
A.13
A.13
FERS45E0063
FERS45G0125
432348
432351
A.15
A.15
B
FEL456SA160JJF 431581 A.15 FEN36TA160JF 431769 A.13 FEN46TA100JF 431955 A.13 FERS45J0160 432354 A.15
FEL456SA160KJF 431584 A.17 FEN36TD100JF 432945 A.13 FEN46TA125JF 431961 A.13 FERS45K0250 432360 A.17
FEL456SA250KKF 431587 A.17 FEN36TD125JF 432953 A.13 FEN46TA160JF 431967 A.13 FERS4B0025 432363 A.15
FEL456TA063JF
FEL456TA080JF
435037
431593
A.13
A.13
FEN36TD125KF
FEN36TD160JF
432962
432971
A.16
A.13
FEN46TD100JF
FEN46TD125JF
433061
433067
A.13
A.13
FERS4E0063
FERS4G0125
432366
432369
A.15
A.15
C
FEL456TA100JF 431599 A.13 FEN36TD160KF 432976 A.16 FEN46TD125KF 433070 A.16 FERS4J0160 432372 A.15
FEL456TA125JF 431605 A.13 FEN36TD200KF 432979 A.16 FEN46TD160JF 433073 A.13 FERS4K0250 432378 A.17
FEL456TA160JF 431611 A.13 FEN36TD250KF 432982 A.16 FEN46TD160KF 433076 A.16 FETAA3J0025 432414 A.18
FEL456TD100JF
FEL456TD125JF
432699
432747
A.13
A.13
FEN36TG100JF
FEN36TG125JF
435139
435142
A.13
A.13
FEN46TD200KF
FEN46TD250KF
433079
433082
A.16
A.16
FETAA3J0063
FETAA3J0125
432417
432420
A.18
A.18
D
FEL456TD125KF 432780 A.16 FEN36TG160JF 435148 A.13 FEN46TG100JF 435250 A.13 FETAA3J0160 432423 A.18
FEL456TD160JF 432834 A.13 FEN36TG160KF 435151 A.16 FEN46TG125JF 435253 A.13 FETAA3K0125 432004 A.19
FEL456TD160KF 432843 A.16 FEN36TG200KF 435154 A.16 FEN46TG160JF 435259 A.13 FETAA3K0160 432426 A.19
FEL456TD200KF
FEL456TD250KF
432868
432871
A.16
A.16
FEN36TG250KF
FEN406F160JF
435157
431799
A.16
A.18
FEN46TG160KF
FEN46TG200KF
435262
435265
A.16
A.16
FETAA3K0250
FETAA4J0025
432429
432432
A.19
A.18
E
FEL456TG100JF 435962 A.13 FEN406F250KF 431802 A.19 FEN46TG250KF 435268 A.16 FETAA4J0063 432435 A.18
FEL456TG125JF 435965 A.13 FEN436MC050JF 435160 A.14 FENFT 433531 A.20 FETAA4J0125 432438 A.18
FEL456TG160JF 435968 A.13 FEN436MC100JF 435163 A.14 FENR4 432099 A.20 FETAA4J0160 432441 A.18
FEL456TG160KF
FEL456TG200KF
435971
435974
A.16
A.16
FEN436MC125JF
FEN436MC160JF
436356
435169
A.14
A.14
FENRC
FENRC/5
432102
436491
A.46
A.20
FETAA4K0125
FETAA4K0160
432007
432444
A.19
A.19
F
FEL456TG250KF 435977 A.16 FEN436MC160KF 435172 A.16 FENRCV/5 436492 A.20 FETAA4K0250 432447 A.19
FEL46AA025JBF 435875 A.14 FEN436MC200KF 436765 A.16 FENRD/5 436493 A.20 FETCA1316 432156 A.21
FEL46AA063JEF 435878 A.14 FEN436MC250KF 435175 A.16 FENRDV/5 436494 A.20 FETCA1320 432157 A.21
FEL46AA125JGF
FEL46AA125KGF
431494
431890
A.14
A.17
FEN436SA125JGF
FEN436SA160JJF
431811
431814
A.15
A.15
FENRF/5
FENRFV/5
436495
436496
A.20
A.20
FETCA1323
FETCA1416
432160
432158
A.21
A.21
G
FEL46AA160JJF 431497 A.14 FEN436SA160KJF 431817 A.17 FENRW 432120 A.20 FETCA1420 432159 A.21
FEL46AA160KJF 431500 A.17 FEN436SA250KKF 431820 A.17 FENRX/5 436499 A.45 FETCA1423 432161 A.21
FEL46AA250KKF 431503 A.17 FEN436TA025JF 435178 A.13 FENRY/5 436500 A.20 FETCA630A 880954 A.21
FEL46SA125JGF
FEL46SA160JJF
431629
431632
A.15
A.15
FEN436TA032JF
FEN436TA040JF
435181
435184
A.13
A.13
FENRYV/5
FENRZ/5
436501
436502
A.20
A.20
FETCA640A
FETD30J0160
880955
432480
A.21
A.18
X
FEL46SA160KJF 431635 A.17 FEN436TA050JF 435187 A.13 FENRZV/5 436503 A.20 FETD30K0250 432483 A.19
FEL46SA250KKF 431638 A.17 FEN436TA063JF 435190 A.13 FEQDB3HJ 432132 A.20 FETD40J0160 432486 A.18
FEL46TA025JF 435049 A.13 FEN436TA080JF 431838 A.13 FEQDB3HK 432135 A.20 FETD40K0250 432489 A.19
FEL46TA032JF 435052 A.13 FEN436TA100JF 431844 A.13 FEQDB3MJ 432138 A.20 FETMC3J0012 432495 A.18
FEL46TA040JF 435055 A.13 FEN436TA125JF 431850 A.13 FEQDB3MK 432141 A.20 FETMC3J0020 432498 A.18
FEL46TA050JF 435058 A.13 FEN436TA160JF 431856 A.13 FEQDB4HJ 432144 A.20 FETMC3J0030 434736 A.18
FEL46TA063JF 435061 A.13 FEN436TD100JF 432994 A.13 FEQDB4HK 432147 A.20 FETMC3J0050 432501 A.18
FEL46TA080JF 431656 A.13 FEN436TD125JF 433001 A.13 FEQDB4MJ 432150 A.20 FETMC3J0080 436078 A.18
FEL46TA100JF 431662 A.13 FEN436TD125KF 433004 A.16 FEQDB4MK 432153 A.20 FETMC3J0100 432504 A.18
FEL46TA125JF 431668 A.13 FEN436TD160JF 433007 A.13 FERJ3B0016 432174 A.14 FETMC3J0125 436358 A.18
FEL46TA160JF 431674 A.13 FEN436TD160KF 433010 A.16 FERJ3B0025 432177 A.14 FETMC3J0160 432510 A.18
FEL46TD100JF 432907 A.13 FEN436TD200KF 433013 A.16 FERJ3E0040 432180 A.14 FETMC3K0160 432513 A.19
FEL46TD125JF 432921 A.13 FEN436TD250KF 433016 A.16 FERJ3E0063 432183 A.14 FETMC3K0200 436778 A.19

X.3
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FETMC3K0250 432516 A.19 FETTG4J0160 432777 A.18 FGH36VA630NNF 434958 A.28 FGL46AA400LLF 431330 A.25
FETMC43J0050 432528 A.18 FETTG4K0160 432786 A.19 FGH406F250LF 434234 A.29 FGL46AA400NLF 434534 A.27
FETMC43J0100 432531 A.18 FETTG4K0200 432789 A.19 FGH406F400LF 431150 A.29 FGL46AA500NNF 434770 A.27
FETMC43J0125 436359 A.18 FETTG4K0250 432792 A.19 FGH406F400NF 431153 A.30 FGL46AA630NNF 431333 A.27
FETMC43J0160 432537 A.18 FEUA3 432162 A.22 FGH406F630NF 431156 A.30 FGL46KA250LKF 436153 A.26
FETMC43K0160 432540 A.19 FEUA4 432163 A.22 FGH436BM400LLF 434669 A.25 FGL46KA350LLF 434468 A.26
FETMC43K0200 436779 A.19 FEUT 433540 A.22 FGH436BM500NNF 434672 A.27 FGL46KA400LLF 436154 A.26
FETMC43K0250 432543 A.19 FEV36TA125KF 432416 A.16 FGH436SA250LKF 434235 A.25 FGL46KA400NLF 436155 A.28
FETTA3J0025 432546 A.18 FEV36TA160KF 436798 A.16 FGH436SA400LLF 434408 A.25 FGL46KA500NNF 434782 A.28
FETTA3J0032 432549 A.18 FEV36TA200KF 431058 A.16 FGH436SA400NLF 431168 A.27 FGL46KA630NNF 434068 A.28
FETTA3J0040 432552 A.18 FEV36TA250KF 431061 A.16 FGH436SA500NNF 434621 A.27 FGL46SA250LKF 434246 A.25
FETTA3J0050 432555 A.18 FEV46TA125KF 431082 A.16 FGH436VA400LLF 434960 A.26 FGL46SA400LLF 434474 A.25
FETTA3J0063 432558 A.18 FEV46TA160KF 436817 A.16 FGH436VA630NNF 434965 A.28 FGL46SA400NLF 431449 A.27
FETTA3J0080 432561 A.18 FEV46TA200KF 431094 A.16 FGH456SA250LKF 434236 A.25 FGL46SA500NNF 434806 A.27
FETTA3J0100 432564 A.18 FEV46TA250KF 431097 A.16 FGH456SA400LLF 434414 A.25 FGL46VA400LLF 435128 A.26
FETTA3J0125 432567 A.18 FEWS3 432168 A.21 FGH456SA400NLF 431198 A.27 FGL46VA630NNF 435134 A.28
FETTA3J0160 432570 A.18 FEWS4 432171 A.21 FGH456SA500NNF 434627 A.27 FGN306F250LF 434247 A.29
Numerical index

FETTA43J0025 432391 A.18 FEY306D160JF 431988 A.15 FGH456VA400LLF 434971 A.26 FGN306F400LF 431473 A.29
FETTA43J0032 432394 A.18 FEY306D250KF 431991 A.17 FGH456VA630NNF 434977 A.28 FGN306F400NF 431488 A.30
FETTA43J0040 432397 A.18 FEY406D160JF 431994 A.15 FGH46AA250LKF 434237 A.25 FGN306F630NF 431491 A.30
FETTA43J0050 432400 A.18 FEY406D250KF 431997 A.17 FGH46AA400LLF 431106 A.25 FGN36AA250LKF 434248 A.25
FETTA43J0063 432403 A.18 FF... FGH46AA400NLF 434432 A.27 FGN36AA400LLF 431455 A.25
FETTA43J0080 432406 A.18 FFKN46NE100SQF 435450 A.36 FGH46AA500NNF 434630 A.27 FGN36AA400NLF 434561 A.27
FETTA43J0100 432409 A.18 FG... FGH46AA630NNF 431132 A.27 FGN36AA500NNF 434812 A.27
FETTA43J0125 432412 A.18 FG1BPE 431403 A.31 FGH46KA250LKF 434041 A.26 FGN36AA630NNF 431461 A.27
FETTA43J0160 432582 A.18 FG1BPW 433406 A.32 FGH46KA350LLF 434420 A.26 FGN36BM400LLF 434687 A.25
FETTA45J0063 432603 A.18 FG1BRE 431404 A.31 FGH46KA400LLF 434042 A.26 FGN36BM500NNF 434690 A.27
FETTA45J0080 432606 A.18 FG1BRW 433407 A.32 FGH46KA400NLF 434043 A.28 FGN36KA250LKF 434073 A.26
FETTA45J0100 432609 A.18 FG1I2 437005 A.46 FGH46KA500NNF 434633 A.28 FGN36KA350LLF 434483 A.26
FETTA45J0125 432612 A.18 FG1I4 437009 A.46 FGH46KA630NNF 434044 A.28 FGN36KA400LLF 436156 A.26
FETTA45J0160 432615 A.18 FG1PF 431408 A.33 FGH46SA250LKF 434238 A.25 FGN36KA400NLF 436157 A.28
FETTA4J0025 432636 A.18 FG1PR 431409 A.33 FGH46SA400LLF 434426 A.25 FGN36KA500NNF 434824 A.28
FETTA4J0032 432639 A.18 FGBEA3 431686 A.32 FGH46SA400NLF 431240 A.27 FGN36KA630NNF 436158 A.28
FETTA4J0040 432642 A.18 FGBEA4 431690 A.32 FGH46SA500NNF 434642 A.27 FGN36SA250LKF 434249 A.25
FETTA4J0050 432645 A.18 FGBEH3 431691 A.32 FGH46VA400LLF 434983 A.26 FGN36SA400LLF 434489 A.25
FETTA4J0063 432648 A.18 FGBEH4 431695 A.32 FGH46VA630NNF 435003 A.28 FGN36SA400NLF 431530 A.27
FETTA4J0080 432651 A.18 FGBES3 431696 A.32 FGJB 432840 A.33 FGN36SA500NNF 434835 A.27
FETTA4J0100 432654 A.18 FGBES4 431697 A.32 FGJM3 432846 A.33 FGN36VA400LLF 435140 A.26
A FETTA4J0125
FETTA4J0160
432657
432660
A.18
A.18
FGBRC3
FGBRC4
431701
431702
A.32
A.32
FGJM4
FGJN3
432849
436469
A.33
A.32
FGN36VA630NNF
FGN406F250LF
435146
434250
A.28
A.29
FETTD3J0100 433159 A.18 FGBRCS3 432193 A.32 FGJN4 436470 A.32 FGN406F400LF 431548 A.29
FETTD3J0125 433164 A.18 FGBRCS4 432194 A.32 FGJP 432852 A.33 FGN406F400NF 431554 A.30
FETTD3J0160 433168 A.18 FGBSS3 431981 A.32 FGJS3 432855 A.33 FGN406F630NF 431560 A.30
B FETTD3K0125
FETTD3K0160
433182
433186
A.19
A.19
FGBSS4
FGDDF3
431982
430944
A.32
A.32
FGJS4
FGJW3
432858
432861
A.33
A.33
FGN436BM400LLF
FGN436BM500NNF
434693
434696
A.25
A.27
FETTD3K0200 433191 A.19 FGDDF4 431064 A.32 FGJW4 432864 A.33 FGN436SA250LKF 434251 A.25
FETTD3K0250 433195 A.19 FGDFF3 431983 A.32 FGL306F250LF 434239 A.29 FGN436SA400LLF 435277 A.25
FETTD43J0100 433201 A.18 FGDFF4 431986 A.32 FGL306F400LF 431261 A.29 FGN436SA400NLF 431596 A.27
C FETTD43J0125
FETTD43J0160
433204
433207
A.18
A.18
FGDMP3
FGDMP4
432796
432799
A.32
A.32
FGL306F400NF
FGL306F630NF
431267
431282
A.30
A.30
FGN436SA500NNF
FGN436VA400LLF
434848
435152
A.27
A.26
FETTD43K0125 433216 A.19 FGEMF8 432811 A.31 FGL36AA250LKF 434240 A.25 FGN436VA630NNF 435158 A.28
FETTD43K0160 433219 A.19 FGEMFD 432817 A.31 FGL36AA400LLF 431246 A.25 FGN456SA250LKF 434252 A.25
FETTD43K0200 433222 A.19 FGEMFF 432820 A.31 FGL36AA400NLF 434459 A.27 FGN456SA400LLF 434504 A.25
D FETTD43K0250
FETTD45J0100
433225
433231
A.19
A.18
FGEMFH
FGEMFJ
432823
432826
A.31
A.31
FGL36AA500NNF
FGL36AA630NNF
434645
431249
A.27
A.27
FGN456SA400NLF
FGN456SA500NNF
431626
434860
A.27
A.27
FETTD45J0125 433234 A.18 FGEMFN 432829 A.31 FGL36BM400LLF 434675 A.25 FGN456VA400LLF 435164 A.26
FETTD45J0160 433239 A.18 FGEO2J 437004 A.47 FGL36BM500NNF 434678 A.27 FGN456VA630NNF 435167 A.28
FETTD45K0125 433252 A.19 FGEO2N 437007 A.47 FGL36KA250LKF 434049 A.26 FGN46AA250LKF 434253 A.25
E FETTD45K0160
FETTD45K0200
433257
433260
A.19
A.19
FGEO3J
FGEO3N
437008
437010
A.47
A.47
FGL36KA350LLF
FGL36KA400LLF
434438
434050
A.26
A.26
FGN46AA400LLF
FGN46AA400NLF
431536
434636
A.25
A.27
FETTD45K0250 433263 A.19 FGFE 430544 A.33 FGL36KA400NLF 434051 A.28 FGN46AA500NNF 434866 A.27
FETTD4J0100 433269 A.18 FGFH 430545 A.33 FGL36KA500NNF 434651 A.28 FGN46AA630NNF 431539 A.27
FETTD4J0125 433272 A.18 FGFT 432836 A.33 FGL36KA630NNF 434052 A.28 FGN46KA250LKF 436159 A.26
F FETTD4J0160
FETTD4K0125
433275
433284
A.18
A.19
FGGS0250
FGGS0400
431870
432838
A.33
A.33
FGL36SA250LKF
FGL36SA400LLF
434241
434444
A.25
A.25
FGN46KA350LLF
FGN46KA400LLF
434510
436160
A.26
A.26
FETTD4K0160 433287 A.19 FGGS0630 432839 A.33 FGL36SA400NLF 431309 A.27 FGN46KA400NLF 436161 A.28
FETTD4K0200 433290 A.19 FGH306F250LF 434231 A.29 FGL36SA500NNF 434657 A.27 FGN46KA500NNF 434872 A.28
FETTD4K0250 433293 A.19 FGH306F400LF 431050 A.29 FGL36VA400LLF 435065 A.26 FGN46KA630NNF 434092 A.28
G FETTG3J0100
FETTG3J0125
433296
432693
A.18
A.18
FGH306F400NF
FGH306F630NF
431067
431073
A.30
A.30
FGL36VA630NNF
FGL406F250LF
435071
434242
A.28
A.29
FGN46SA250LKF
FGN46SA400LLF
434254
435280
A.25
A.25
FETTG3J0160 432696 A.18 FGH36AA250LKF 434232 A.25 FGL406F400LF 431351 A.29 FGN46SA400NLF 431650 A.27
FETTG3K0160 432705 A.19 FGH36AA400LLF 431032 A.25 FGL406F400NF 431354 A.30 FGN46SA500NNF 434884 A.27
FETTG3K0200 432708 A.19 FGH36AA400NLF 433142 A.27 FGL406F630NF 431357 A.30 FGN46VA400LLF 435170 A.26
X FETTG3K0250
FETTG43J0100
432711
433311
A.19
A.18
FGH36AA500NNF
FGH36AA630NNF
434600
431038
A.27
A.27
FGL436BM400LLF
FGL436BM500NNF
434681
434684
A.25
A.27
FGN46VA630NNF
FGNFT
435176
432867
A.28
A.31
FETTG43J0125 432717 A.18 FGH36BM400LLF 434663 A.25 FGL436SA250LKF 434243 A.25 FGNRC 432873 A.46
FETTG43J0160 432720 A.18 FGH36BM500NNF 434666 A.27 FGL436SA400LLF 434453 A.25 FGNRC/5 436504 A.31
FETTG43K0160 432729 A.19 FGH36KA250LKF 436150 A.26 FGL436SA400NLF 431372 A.27 FGNRCV/5 436505 A.31
FETTG43K0200 432732 A.19 FGH36KA350LLF 434393 A.26 FGL436SA500NNF 434758 A.27 FGNRD/5 436506 A.31
FETTG43K0250 432735 A.19 FGH36KA400LLF 436151 A.26 FGL436VA400LLF 435077 A.26 FGNRDV/5 436507 A.31
FETTG45J0100 433326 A.18 FGH36KA400NLF 436152 A.28 FGL436VA630NNF 435091 A.28 FGNRE 434735 A.31
FETTG45J0125 432741 A.18 FGH36KA500NNF 434606 A.28 FGL456SA250LKF 434244 A.25 FGNRF/5 436509 A.31
FETTG45J0160 432744 A.18 FGH36KA630NNF 434028 A.28 FGL456SA400LLF 434462 A.25 FGNRFV/5 436510 A.31
FETTG45K0160 432753 A.19 FGH36SA250LKF 434233 A.25 FGL456SA400NLF 431425 A.27 FGNRW 433892 A.31
FETTG45K0200 432756 A.19 FGH36SA400LLF 434399 A.25 FGL456SA500NNF 434764 A.27 FGNRX/5 436512 A.45
FETTG45K0250 432759 A.19 FGH36SA400NLF 431091 A.27 FGL456VA400LLF 435095 A.26 FGNRY/5 436513 A.31
FETTG4J0100 433332 A.18 FGH36SA500NNF 434612 A.27 FGL456VA630NNF 435122 A.28 FGNRYV/5 436514 A.31
FETTG4J0125 432774 A.18 FGH36VA400LLF 434953 A.26 FGL46AA250LKF 434245 A.25 FGNRZ/5 436515 A.31

X.4
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FGNRZV/5 436516 A.31 FGRS43LL0400 434516 A.29 FKH46NS800PPF 435375 A.35 FNECE6 436449 A.47
FGQDB3H 430856 A.31 FGRS43NL0400 433241 A.27 FKL36NE100SQF 435545 A.36 FNEMF3 435686 A.38
FGQDB3M 430860 A.31 FGRS43NN0500 434521 A.27 FKL36NE125SSF 435546 A.36 FNEMF6 435689 A.38
FGQDB4H 430865 A.31 FGRS45LK0250 434311 A.25 FKL36NE800PPF 435390 A.35 FNEMFD 435683 A.38
FGQDB4M 430869 A.31 FGRS45LL0400 434525 A.25 FKL36NM125SF 435561 A.36 FNEMFF 435680 A.38
FGRJ3LK0160 434337 A.25 FGRS45LL0400 434525 A.29 FKL36NM800PF 435539 A.35 FNEMFJ 436457 A.38
FGRJ3LK0250 434341 A.25 FGRS45NL0400 433247 A.27 FKL36NT100SF 435555 A.36 FNEMFN 436456 A.38
FGRJ3LL0250 435343 A.25 FGRS45NN0500 434530 A.27 FKL36NT125SF 435557 A.36 FNFE 435713 A.40
FGRJ3LL0400 433151 A.25 FGRS4LK0250 434315 A.25 FKL36NT630PF 435480 A.35 FNFH 435714 A.40
FGRJ3NL0250 433148 A.27 FGRS4LL0400 434537 A.25 FKL36NT800PF 435372 A.35 FNFHW 436590 A.40
FGRJ3NL0400 435182 A.27 FGRS4LL0400 434537 A.29 FKL436NM125SF 435573 A.36 FNFT 435715 A.40
FGRJ3NN0400 433154 A.27 FGRS4NL0400 433253 A.27 FKL436NM800PF 435543 A.35 FNFW 435578 A.39

By catalogue number
FGRJ3NN0630 433157 A.27 FGRS4NN0500 434542 A.27 FKL436NT100SF 435567 A.36 FNGS0800 433419 A.40
FGRJ43LK0160 434345 A.25 FGTAA3L0250 434319 A.29 FKL436NT125SF 435569 A.36 FNGS1000 433421 A.40
FGRJ43LK0250 434349 A.25 FGTAA3L0400 431718 A.29 FKL436NT630PF 435534 A.35 FNGS1250 435709 A.40
FGRJ43LL0250 435356 A.25 FGTAA3N0400 431721 A.30 FKL436NT800PF 435535 A.35 FNGS1600 436471 A.40
FGRJ43LL0400 433163 A.25 FGTAA3N0500 434893 A.30 FKL46NE100SQF 435547 A.36 FNJL3 435716 A.40
FGRJ43NL0250 433160 A.27 FGTAA3N0630 431736 A.30 FKL46NE125SSF 435549 A.36 FNJL4 435719 A.40
FGRJ43NL0400 435188 A.27 FGTAA4L0250 434323 A.29 FKL46NE800PPF 435282 A.35 FNJP 435722 A.40
FGRJ43NN0400 433166 A.27 FGTAA4L0400 431742 A.29 FKN36NE100SQF 435396 A.36 FNNRC 435726 A.46
FGRJ43NN0630 433169 A.27 FGTAA4N0400 431745 A.30 FKN36NE125SSF 435384 A.36 FNNRC/5 436517 A.38
FGRJ45LK0160 434353 A.25 FGTAA4N0500 434899 A.30 FKN36NE160TTF 435387 A.37 FNNRCV/5 436518 A.38
FGRJ45LK0250 434357 A.25 FGTAA4N0630 431748 A.30 FKN36NE800PPF 435393 A.35 FNNRD/5 436519 A.38
FGRJ45LL0250 435367 A.25 FGTCA1327 435107 A.32 FKN36NG100SQF 435414 A.36 FNNRDV/5 436520 A.38
FGRJ45LL0400 433175 A.25 FGTCA1427 435116 A.32 FKN36NG125SSF 435402 A.36 FNNRE 435738 A.38
FGRJ45LL0400 433175 A.29 FGTCA230B 433412 A.32 FKN36NG160TTF 435405 A.37 FNNRF/5 436522 A.38
FGRJ45NL0250 433172 A.27 FGTCA240B 433413 A.32 FKN36NG800PPF 435411 A.35 FNNRFV/5 436524 A.38
FGRJ45NL0400 435194 A.27 FGTKA3L0250 434201 A.29 FKN36NM125SF 435558 A.36 FNNRW 435745 A.38
FGRJ45NN0400 433178 A.27 FGTKA3L0350 434902 A.29 FKN36NM800PF 435537 A.35 FNNRX/5 436526 A.45
FGRJ45NN0630 433181 A.27 FGTKA3L0400 434202 A.29 FKN36NS100SQF 435432 A.36 FNNRY/5 436527 A.38
FGRJ45NN0630 433181 A.30 FGTKA3N0400 434203 A.30 FKN36NS125SSF 435420 A.36 FNNRYV/5 436528 A.38
FGRJ4LK0160 434361 A.25 FGTKA3N0500 434905 A.30 FKN36NS160TTF 435423 A.37 FNNRZ/5 436530 A.38
FGRJ4LK0250 434365 A.25 FGTKA3N0630 434204 A.30 FKN36NS800PPF 435429 A.35 FNNRZV/5 436531 A.38
FGRJ4LL0250 435397 A.25 FGTKA4L0250 434205 A.29 FKN36NT100SF 435550 A.36 FNPFM 435758 A.39
FGRJ4LL0400 433187 A.25 FGTKA4L0350 434908 A.29 FKN36NT125SF 435551 A.36 FNS11L 435760 A.39
FGRJ4LL0400 433187 A.29 FGTKA4L0400 434261 A.29 FKN36NT630PF 435444 A.35 FNS11R 436401 A.38
FGRJ4NL0250 433184 A.27 FGTKA4N0400 434263 A.30 FKN36NT800PF 435336 A.35 FNSHT8 435692 A.38
FGRJ4NL0400 435200 A.27 FGTKA4N0500 434911 A.30 FKN436NM125SF 435570 A.36 FNSHTD 435693 A.38
FGRJ4NN0400
FGRJ4NN0630
433190
433193
A.27
A.27
FGTKA4N0630
FGUA3
434265
432908
A.30
A.33
FKN436NM800PF
FKN436NT100SF
435541
435562
A.35
A.36
FNSHTF
FNSHTJ
435694
435695
A.38
A.38
A
FGRJ4NN0630 433193 A.30 FGUA4 432909 A.33 FKN436NT125SF 435563 A.36 FNSHTN 435696 A.38
FGRL3LK0160 436162 A.26 FGUT 433541 A.33 FKN436NT630PF 435408 A.35 FNT 435704 A.40
FGRL3LK0250 434098 A.26 FGWS3 432910 A.32 FKN436NT800PF 435300 A.35 FNTCA3327 436316 A.39
FGRL3LL0250
FGRL3LL0350
435399
435400
A.26
A.26
FGWS4
FGY306D400LF
432913
431659
A.32
A.26
FKN46NE125SSF
FKN46NE160TTF
435438
435441
A.36
A.37
FNTCA3427
FNTCA4327
436651
433438
A.39
A.39
B
FGRL3LL0400 434099 A.26 FGY306D630NF 431665 A.28 FKN46NE800PPF 435447 A.35 FNTCA4427 433439 A.39
FGRL3NL0250 435206 A.28 FGY406D400LF 431671 A.26 FKN46NG100SQF 435468 A.36 FNUA3 435762 A.40
FGRL3NL0400 435212 A.28 FGY406D630NF 431687 A.28 FKN46NG125SSF 435456 A.36 FNUA4 435763 A.40
FGRL3NN0400
FGRL3NN0500
434471
434473
A.28
A.28
FK...
FKEO4J 437011 A.47
FKN46NG160TTF
FKN46NG800PPF
435459
435465
A.37
A.35
FNUT
FNUVD6
435764
435697
A.40
A.38
C
FGRL3NN0630 434100 A.28 FKEO4N 437014 A.47 FKN46NS100SQF 435486 A.36 FNUVR1 435698 A.38
FGRL43LK0160 434101 A.26 FKEO5J 437015 A.47 FKN46NS125SSF 435474 A.36 FNUVR6 435699 A.38
FGRL43LK0250 436177 A.26 FKEO5N 437017 A.47 FKN46NS160TTF 435477 A.37 FNUVR8 435700 A.38
FGRL43LL0250
FGRL43LL0350
435410
435412
A.26
A.26
FKH36NE100SQF
FKH36NE125SSF
435288
435276
A.36
A.36
FKN46NS800PPF
FKY306DN100SF
435483
435381
A.35
A.37
FNUVRD
FNUVRF
435701
435702
A.38
A.38
D
FGRL43LL0400 436178 A.26 FKH36NE160TTF 435279 A.37 FKY306DN125SF 435489 A.37 FNUVRJ 437018 A.45
FGRL43NL0250 435218 A.28 FKH36NE800PPF 435285 A.35 FKY306DN160TF 435492 A.37 FNWS3AP 433436 A.39
FGRL43NL0400 435224 A.28 FKH36NG100SQF 435306 A.36 FKY306DN800PF 435495 A.37 FNWS3AT 435757 A.39
FGRL43NN0400
FGRL43NN0500
435419
435427
A.28
A.28
FKH36NG125SSF
FKH36NG160TTF
435294
435297
A.36
A.37
FKY406DN100SF
FKY406DN125SF
435273
435498
A.37
A.37
FNWS3WP
FNWS3WT
433434
436482
A.39
A.39
E
FGRL43NN0630 436179 A.28 FKH36NG800PPF 435303 A.35 FKY406DN160TF 435501 A.37 FNWS4AP 433440 A.39
FGRL45LK0160 434105 A.26 FKH36NM125SF 435559 A.36 FKY406DN800PF 435504 A.37 FNWS4AT 435759 A.39
FGRL45LK0250 434106 A.26 FKH36NM800PF 435538 A.35 FN... FNWS4WP 436481 A.39
FGRL45LL0250
FGRL45LL0350
434495
435266
A.26
A.26
FKH36NS100SQF
FKH36NS125SSF
435324
435312
A.36
A.36
FN1BPE
FN1BRE
435678
435679
A.38
A.38
FNWS4WT
RD...
433442 A.39 F
FGRL45LL0400 434107 A.26 FKH36NS160TTF 435315 A.37 FN1BRW1 435575 A.39 RD1D 110 872225 A.39
FGRL45NL0250 435230 A.28 FKH36NS800PPF 435321 A.35 FN1BRW2 435577 A.39 RD1D 220 872224 A.39
FGRL45NL0400 435236 A.28 FKH36NT100SF 435553 A.36 FN1BRY1 433415 A.39 RD1D 380 872226 A.39
FGRL45NN0400
FGRL45NN0500
434497
435272
A.28
A.28
FKH36NT125SF
FKH36NT630PF
435554
435426
A.36
A.35
FN1BRY2
FN1I2F
435574
433416
A.39
A.46
RD5 110
RD5 220
704175
704169
A.39
A.39
G
FGRL45NN0630 436180 A.28 FKH36NT800PF 435318 A.35 FN1I4F 437016 A.46 RD5 380 704176 A.39
FGRL4LK0160 434109 A.26 FKH436NM125SF 435571 A.36 FN1PR 433417 A.40 RD6 110 704178 A.39
FGRL4LK0250 436181 A.26 FKH436NM800PF 435542 A.35 FNBA11R 435761 A.38 RD6 220 704177 A.39
FGRL4LL0250
FGRL4LL0350
435433
435302
A.26
A.26
FKH436NT100SF
FKH436NT125SF
435565
435566
A.36
A.36
FNBES3P
FNBES3R
435706
433420
A.39
A.39
RD6 380
RDFR
704179
872227
A.39
A.49
X
FGRL4LL0400 434111 A.26 FKH436NT630PF 435462 A.35 FNBES4P 435707 A.39 TT...
FGRL4NL0250 435254 A.28 FKH436NT800PF 435354 A.35 FNBES4R 433422 A.39 TT 210 560096 A.39
FGRL4NL0400 435260 A.28 FKH46NE100SQF 435342 A.36 FNBRC3 433423 A.39 TT 35 560091 A.39
FGRL4NN0400 434501 A.28 FKH46NE125SSF 435330 A.36 FNBRC4 433425 A.39 TT 60 560092 A.39
FGRL4NN0500 435309 A.28 FKH46NE160TTF 435333 A.37 FNBRCS3 433426 A.39 TT 80 560093 A.39
FGRL4NN0630 434112 A.28 FKH46NE800PPF 435339 A.35 FNBRCS4 433427 A.39 TT110 560094 A.39
FGRS3LK0250 434303 A.25 FKH46NG100SQF 435360 A.36 FNBSS3P 435708 A.39 TT160 560095 A.39
FGRS3LL0400 435435 A.25 FKH46NG125SSF 435348 A.36 FNBSS3R 435710 A.39 TTD 22 560090 A.39
FGRS3LL0400 435435 A.29 FKH46NG160TTF 435351 A.37 FNBSS4P 435711 A.39 TTO 110 560097 A.39
FGRS3NL0400 433235 A.27 FKH46NG800PPF 435357 A.35 FNBSS4R 435712 A.39 TTO 210 560098 A.39
FGRS3NN0500 434512 A.27 FKH46NS100SQF 435378 A.36 FNECA3 436452 A.47
FGRS43LK0250 434307 A.25 FKH46NS125SSF 435366 A.36 FNECA6 436451 A.47
FGRS43LL0400 434516 A.25 FKH46NS160TTF 435369 A.37 FNECE3 436450 A.47

X.5
Record Plus
Notes

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Numerical index

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

X.6
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
430... 430108 FDN36TG032ED A.6 430506 FA1BR5 A.8 430883 FDBEA3 A.9
430015 FDH36MC007ED A.7 430109 FDN36TG040ED A.6 430507 FA1BR6 A.8 430884 FDBEA4 A.9
430016 FDH36MC012ED A.7 430110 FDN36TG050ED A.6 430518 FDL36TD080GD A.6 430885 FDBEH3 A.9
430017 FDH36MC020ED A.7 430111 FDN36TG063ED A.6 430521 FDL36TD100GD A.6 430886 FDBEH4 A.9
430018 FDH36MC030ED A.7 430112 FDN436MC007ED A.7 430524 FDL36TD125GD A.6 430887 FDBES3 A.9
430019 FDH36MC050ED A.7 430113 FDN436MC012ED A.7 430537 FDL436MC080GD A.7 430888 FDBES4 A.9
430020 FDH36TD016ED A.6 430114 FDN436MC020ED A.7 430540 FDL436MC100GD A.7 430889 FDBRC3 A.9
430021 FDH36TD020ED A.6 430115 FDN436MC030ED A.7 430544 FGFE A.33 430890 FDBRC4 A.9
430022 FDH36TD025ED A.6 430116 FDN436MC050ED A.7 430545 FGFH A.33 430891 FDBSS3 A.9
430023 FDH36TD032ED A.6 430117 FDN436TD016ED A.6 430557 FDL436TD080GD A.6 430892 FDBSS4 A.9
430024 FDH36TD040ED A.6 430118 FDN436TD020ED A.6 430560 FDL436TD100GD A.6 430893 FDDDF3 A.9
430025 FDH36TD050ED A.6 430119 FDN436TD025ED A.6 430563 FDL436TD125GD A.6 430896 FDDDF4 A.9

By reference number
430026 FDH36TD063ED A.6 430120 FDN436TD032ED A.6 430568 FDL456TD080GD A.6 430899 FDDFF3 A.9
430027 FDH36TG025ED A.6 430121 FDN436TD040ED A.6 430571 FDL456TD100GD A.6 430902 FDDFF4 A.9
430028 FDH36TG032ED A.6 430122 FDN436TD050ED A.6 430574 FDL456TD125GD A.6 430905 FDDMP3 A.9
430029 FDH36TG040ED A.6 430123 FDN436TD063ED A.6 430591 FDL46TD080GD A.6 430908 FDDMP4 A.9
430030 FDH36TG050ED A.6 430124 FDN436TG025ED A.6 430594 FDL46TD100GD A.6 430920 FDEMF8 A.8
430031 FDH36TG063ED A.6 430125 FDN436TG032ED A.6 430597 FDL46TD125GD A.6 430926 FDEMFD A.8
430032 FDH436MC007ED A.7 430126 FDN436TG040ED A.6 430610 FDN36MC080GD A.7 430929 FDEMFF A.8
430033 FDH436MC012ED A.7 430127 FDN436TG050ED A.6 430613 FDN36MC100GD A.7 430932 FDEMFH A.8
430034 FDH436MC020ED A.7 430128 FDN436TG063ED A.6 430630 FDN36TD080GD A.6 430935 FDEMFJ A.8
430035 FDH436MC030ED A.7 430129 FDN456TD063ED A.6 430633 FDN36TD100GD A.6 430938 FDEMFN A.8
430036 FDH436MC050ED A.7 430130 FDN456TG063ED A.6 430636 FDN36TD125GD A.6 430941 FDFF3 A.10
430037 FDH436TD016ED A.6 430131 FDN46TD016ED A.6 430649 FDN36TG080GD A.6 430942 FDFF4 A.10
430038 FDH436TD020ED A.6 430132 FDN46TD020ED A.6 430652 FDN36TG100GD A.6 430943 FEFE A.22
430039 FDH436TD025ED A.6 430133 FDN46TD025ED A.6 430655 FDN36TG125GD A.6 430944 FGDDF3 A.32
430040 FDH436TD032ED A.6 430134 FDN46TD032ED A.6 430668 FDN436MC080GD A.7 430945 FDJB A.9
430041 FDH436TD040ED A.6 430135 FDN46TD040ED A.6 430671 FDN436MC100GD A.7 430951 FDJL3 A.9
430042 FDH436TD050ED A.6 430136 FDN46TD050ED A.6 430688 FDN436TD080GD A.6 430954 FDJL4 A.9
430043 FDH436TD063ED A.6 430137 FDN46TD063ED A.6 430691 FDN436TD100GD A.6 430957 FDJP A.9
430044 FDH436TG025ED A.6 430138 FDN46TG025ED A.6 430694 FDN436TD125GD A.6 430960 FDJS3 A.9
430045 FDH436TG032ED A.6 430139 FDN46TG032ED A.6 430707 FDN436TG080GD A.6 430963 FDJS4 A.9
430046 FDH436TG040ED A.6 430140 FDN46TG040ED A.6 430710 FDN436TG100GD A.6 430966 FDKD3 A.10
430047 FDH436TG050ED A.6 430141 FDN46TG050ED A.6 430713 FDN436TG125GD A.6 430967 FDKD4 A.10
430048 FDH436TG063ED A.6 430142 FDN46TG063ED A.6 430718 FDN456TD080GD A.6 430968 FDNFT A.8
430049 FDH456TD063ED A.6 430143 FDN66TD016ED A.5 430721 FDN456TD100GD A.6 430969 FEBAT01 A.20
430050 FDH456TG063ED A.6 430144 FDN66TD020ED A.5 430724 FDN456TD125GD A.6 430970 FEBAT10 A.20
430051 FDH46TD016ED A.6 430145 FDN66TD025ED A.5 430729 FDN456TG080GD A.6 430971 FDNR4 A.8
430052
430053
FDH46TD020ED
FDH46TD025ED
A.6
A.6
430146
430147
FDN66TD032ED
FDN66TD040ED
A.5
A.5
430732
430735
FDN456TG100GD
FDN456TG125GD
A.6
A.6
430986
430987
FDNRE
FEDFQ3
A.8
A.21
A
430054 FDH46TD032ED A.6 430148 FDN66TD050ED A.5 430752 FDN46TD080GD A.6 431...
430055 FDH46TD040ED A.6 430149 FDN66TD063ED A.5 430755 FDN46TD100GD A.6 431007 FEH36TD100JF A.13
430056 FDH46TD050ED A.6 430150 FDY306D063ED A.7 430758 FDN46TD125GD A.6 431013 FDQDS3M A.8
430057
430058
FDH46TD063ED
FDH46TG025ED
A.6
A.6
430151
430161
FDY406D063ED
FDS35TD016ED
A.7
A.5
430771
430774
FDN46TG080GD
FDN46TG100GD
A.6
A.6
431021
431022
FEH36TD125JF
FDQDS4M
A.13
A.8
B
430059 FDH46TG032ED A.6 430163 FDS35TD020ED A.5 430777 FDN46TG125GD A.6 431025 FDUA3 A.10
430060 FDH46TG040ED A.6 430165 FDS35TD025ED A.5 430794 FDN66TD080GD A.5 431026 FDUA4 A.10
430061 FDH46TG050ED A.6 430167 FDS35TD032ED A.5 430797 FDN66TD100GD A.5 431032 FGH36AA400LLF A.25
430062
430065
FDH46TG063ED
FDL36MC020ED
A.6
A.7
430169
430178
FDS35TD040ED
FDS35TD050ED
A.5
A.5
430800
430805
FDN66TD125GD
FDY306D160GD
A.5
A.7
431038
431050
FGH36AA630NNF
FGH306F400LF
A.27
A.29
C
430066 FDL36MC030ED A.7 430224 FDS45TD016ED A.5 430810 FDY406D160GD A.7 431058 FEV36TA200KF A.16
430067 FDL36MC050ED A.7 430226 FDS45TD020ED A.5 430813 FA1BPH A.8 431061 FEV36TA250KF A.16
430068 FA1BRH A.8 430228 FDS45TD025ED A.5 430815 FABAT01 A.8 431064 FGDDF4 A.32
430069
430070
FDJK
FDL36TD025ED
A.9
A.6
430230
430232
FDS45TD032ED
FDS45TD040ED
A.5
A.5
430818
430821
FABAT10
FAC
A.8
A.10
431067
431073
FGH306F400NF
FGH306F630NF
A.30
A.30
D
430071 FDL36TD032ED A.6 430241 FDS45TD050ED A.5 430823 FAPF8 A.9 431082 FEV46TA125KF A.16
430072 FDL36TD040ED A.6 430318 FDH36MC080GD A.7 430824 FAPFM A.9 431091 FGH36SA400NLF A.27
430073 FDL36TD050ED A.6 430321 FDH36MC100GD A.7 430825 FAPIP A.9 431094 FEV46TA200KF A.16
430074
430077
FDL36TD063ED
FDL436MC020ED
A.6
A.7
430338
430341
FDH36TD080GD
FDH36TD100GD
A.6
A.6
430826
430827
FAPM8
FAPPS
A.9
A.9
431097
431106
FEV46TA250KF
FGH46AA400LLF
A.16
A.25
E
430078 FDL436MC030ED A.7 430344 FDH36TD125GD A.6 430828 FAS01L A.8 431112 FEH36AA125JGF A.14
430079 FDL436MC050ED A.7 430357 FDH36TG080GD A.6 430829 FDFH A.10 431116 FEH36AA125KGF A.17
430082 FDL436TD025ED A.6 430360 FDH36TG100GD A.6 430830 FDUF3 A.9 431117 FEH36AA160JJF A.14
430083
430084
FDL436TD032ED
FDL436TD040ED
A.6
A.6
430363
430376
FDH36TG125GD
FDH436MC080GD
A.6
A.7
430831
430832
FAS01R
FDUF4
A.8
A.9
431120
431123
FEH36AA160KJF
FEH36AA250KKF
A.17
A.17
F
430085 FDL436TD050ED A.6 430379 FDH436MC100GD A.7 430834 FAS10L A.8 431126 FEH306F160JF A.18
430086 FDL436TD063ED A.6 430396 FDH436TD080GD A.6 430837 FAS10R A.8 431129 FEH306F250KF A.19
430087 FDL456TD063ED A.6 430399 FDH436TD100GD A.6 430840 FASHTB A.8 431132 FGH46AA630NNF A.27
430088
430089
FA1BR1
FA1BR2
A.8
A.8
430402
430415
FDH436TD125GD
FDH436TG080GD
A.6
A.6
430843
430846
FASHTD
FASHTF
A.8
A.8
431138
431141
FEH36SA125JGF
FEH36SA160JJF
A.15
A.15
G
430090 FDL46TD025ED A.6 430418 FDH436TG100GD A.6 430849 FASHTJ A.8 431144 FEH36SA160KJF A.17
430091 FDL46TD032ED A.6 430421 FDH436TG125GD A.6 430852 FASHTN A.8 431147 FEH36SA250KKF A.17
430092 FDL46TD040ED A.6 430426 FDH456TD080GD A.6 430855 FASHTU A.8 431150 FGH406F400LF A.29
430093
430094
FDL46TD050ED
FDL46TD063ED
A.6
A.6
430429
430432
FDH456TD100GD
FDH456TD125GD
A.6
A.6
430856
430858
FGQDB3H
FAUVDN
A.31
A.8
431153
431156
FGH406F400NF
FGH406F630NF
A.30
A.30
X
430095 FDN36MC007ED A.7 430437 FDH456TG080GD A.6 430860 FGQDB3M A.31 431165 FEH36TA080JF A.13
430096 FDN36MC012ED A.7 430440 FDH456TG100GD A.6 430861 FAUVRD A.8 431168 FGH436SA400NLF A.27
430097 FDN36MC020ED A.7 430443 FDH456TG125GD A.6 430864 FAUVRF A.8 431171 FEH36TA100JF A.13
430098 FDN36MC030ED A.7 430460 FDH46TD080GD A.6 430865 FGQDB4H A.31 431177 FEH36TA125JF A.13
430099 FDN36MC050ED A.7 430463 FDH46TD100GD A.6 430867 FAUVRJ A.8 431183 FEH36TA160JF A.13
430100 FDN36TD016ED A.6 430466 FDH46TD125GD A.6 430869 FGQDB4M A.31 431198 FGH456SA400NLF A.27
430101 FDN36TD020ED A.6 430479 FDH46TG080GD A.6 430870 FAUVRN A.8 431201 FEH46AA125JGF A.14
430102 FDN36TD025ED A.6 430482 FDH46TG100GD A.6 430873 FAUVRU A.8 431204 FEH46AA160JJF A.14
430103 FDN36TD032ED A.6 430485 FDH46TG125GD A.6 430876 FD1BPE A.8 431207 FEH46AA160KJF A.17
430104 FDN36TD040ED A.6 430498 FDL36MC080GD A.7 430877 FD1BRE A.8 431210 FEH46AA250KKF A.17
430105 FDN36TD050ED A.6 430501 FDL36MC100GD A.7 430878 FD1PF A.10 431213 FEH406F160JF A.18
430106 FDN36TD063ED A.6 430504 FA1BR3 A.8 430879 FD1PR A.10 431216 FEH406F250KF A.19
430107 FDN36TG025ED A.6 430505 FA1BR4 A.8 430880 FDBAM11 A.8 431225 FEH436SA125JGF A.15

X.7
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
431228 FEH436SA160JJF A.15 431596 FGN436SA400NLF A.27 431986 FGDFF4 A.32 432207 FERJ3K0250 A.17
431231 FEH436SA160KJF A.17 431599 FEL456TA100JF A.13 431988 FEY306D160JF A.15 432209 FEH436TD125KF A.16
431234 FEH436SA250KKF A.17 431605 FEL456TA125JF A.13 431991 FEY306D250KF A.17 432210 FERJ43B0016 A.14
431240 FGH46SA400NLF A.27 431611 FEL456TA160JF A.13 431994 FEY406D160JF A.15 432213 FERJ43B0025 A.14
431246 FGL36AA400LLF A.25 431626 FGN456SA400NLF A.27 431997 FEY406D250KF A.17 432214 FEH436TD160JF A.13
431249 FGL36AA630NNF A.27 431629 FEL46SA125JGF A.15 432... 432216 FERJ43E0040 A.14
431252 FEH436TA080JF A.13 431632 FEL46SA160JJF A.15 432000 FABAM01 A.20 432218 FEH436TD160KF A.16
431258 FEH436TA100JF A.13 431635 FEL46SA160KJF A.17 432003 FABAM10 A.20 432219 FERJ43E0063 A.14
431261 FGL306F400LF A.29 431638 FEL46SA250KKF A.17 432004 FETAA3K0125 A.19 432222 FERJ43G0080 A.14
431264 FEH436TA125JF A.13 431650 FGN46SA400NLF A.27 432007 FETAA4K0125 A.19 432223 FEH436TD200KF A.16
431267 FGL306F400NF A.30 431656 FEL46TA080JF A.13 432010 FDFE A.10 432225 FERJ43J0100 A.14
431270 FEH436TA160JF A.13 431659 FGY306D400LF A.26 432011 FE1BPE A.20 432227 FEH436TD250KF A.16
431282 FGL306F630NF A.30 431662 FEL46TA100JF A.13 432012 FE1BRE A.20 432228 FERJ43G0125 A.14
431285 FEH456SA125JGF A.15 431665 FGY306D630NF A.28 432017 FE1PF A.22 432231 FERJ43J0160 A.14
431288 FEH456SA160JJF A.15 431668 FEL46TA125JF A.13 432018 FEBE43 A.21 432240 FERJ43K0160 A.17
431291 FEH456SA160KJF A.17 431671 FGY406D400LF A.26 432019 FEBE44 A.21 432242 FEH456TD100JF A.13
431294 FEH456SA250KKF A.17 431674 FEL46TA160JF A.13 432020 FEBE93 A.21 432243 FERJ43K0250 A.17
Numerical index

431300 FEH456TA080JF A.13 431686 FGBEA3 A.32 432021 FEBE94 A.21 432249 FERJ45E0063 A.14
431306 FEH456TA100JF A.13 431687 FGY406D630NF A.28 432022 FEBEA3 A.21 432250 FEH456TD125JF A.13
431309 FGL36SA400NLF A.27 431690 FGBEA4 A.32 432023 FEBEA4 A.21 432252 FERJ45G0080 A.14
431312 FEH456TA125JF A.13 431691 FGBEH3 A.32 432024 FEBEH3 A.21 432254 FEH456TD125KF A.16
431318 FEH456TA160JF A.13 431695 FGBEH4 A.32 432025 FEBEH4 A.21 432255 FERJ45J0100 A.14
431330 FGL46AA400LLF A.25 431696 FGBES3 A.32 432026 FEBES3 A.21 432258 FERJ45G0125 A.14
431333 FGL46AA630NNF A.27 431697 FGBES4 A.32 432027 FEBES4 A.21 432259 FEH456TD160JF A.13
431336 FEH46SA125JGF A.15 431698 FEN36AA125JGF A.14 432028 FEBRC3 A.21 432261 FERJ45J0160 A.14
431339 FEH46SA160JJF A.15 431701 FGBRC3 A.32 432029 FEBRC4 A.21 432263 FEH456TD160KF A.16
431342 FEH46SA160KJF A.17 431702 FGBRC4 A.32 432032 FEBSS3 A.21 432266 FEH456TD200KF A.16
431345 FEH46SA250KKF A.17 431703 FEN36AA160JJF A.14 432033 FEBSS4 A.21 432269 FEH456TD250KF A.16
431351 FGL406F400LF A.29 431706 FEN36AA160KJF A.17 432034 FEDDF3 A.21 432270 FERJ45K0160 A.17
431354 FGL406F400NF A.30 431709 FEN36AA250KKF A.17 432037 FEDDF4 A.21 432273 FERJ45K0250 A.17
431357 FGL406F630NF A.30 431712 FEN306F160JF A.18 432040 FEDFF3 A.21 432276 FERJ4B0016 A.14
431363 FEH46TA080JF A.13 431715 FEN306F250KF A.19 432043 FEDFF4 A.21 432279 FERJ4B0025 A.14
431369 FEH46TA100JF A.13 431718 FGTAA3L0400 A.29 432046 FEDMP3 A.21 432282 FERJ4E0040 A.14
431372 FGL436SA400NLF A.27 431721 FGTAA3N0400 A.30 432049 FEDMP4 A.21 432285 FERJ4E0063 A.14
431375 FEH46TA125JF A.13 431724 FEN36SA125JGF A.15 432052 FEEMFD A.20 432287 FEH46TD100JF A.13
431381 FEH46TA160JF A.13 431727 FEN36SA160JJF A.15 432055 FEEMFF A.20 432288 FERJ4G0080 A.14
431393 FEH36TD125KF A.16 431730 FEN36SA160KJF A.17 432058 FEEMFH A.20 432291 FERJ4J0100 A.14
431402 FAT A.22 431733 FEN36SA250KKF A.17 432061 FEEMFJ A.20 432294 FERJ4G0125 A.14
A 431403
431404
FG1BPE
FG1BRE
A.31
A.31
431736
431742
FGTAA3N0630
FGTAA4L0400
A.30
A.29
432064
432067
FEEMFN
FEFF3
A.20
A.22
432296
432297
FEH46TD125JF
FERJ4J0160
A.13
A.14
431405 FEL36AA125JGF A.14 431745 FGTAA4N0400 A.30 432068 FEFF4 A.22 432300 FEH46TD125KF A.16
431408 FG1PF A.33 431748 FGTAA4N0630 A.30 432071 FEFT A.22 432303 FEH46TD160JF A.13
431409 FG1PR A.33 431751 FEN36TA080JF A.13 432073 FEJB A.22 432306 FERJ4K0160 A.17
B 431410
431413
FEL36AA160JJF
FEL36AA160KJF
A.14
A.17
431757
431763
FEN36TA100JF
FEN36TA125JF
A.13
A.13
432076
432079
FEH36TD200KF
FEJL3
A.16
A.22
432307
432309
FEH46TD160KF
FERJ4K0250
A.16
A.17
431416 FEL36AA250KKF A.17 431769 FEN36TA160JF A.13 432082 FEJL4 A.22 432311 FEH46TD200KF A.16
431419 FEL306F160JF A.18 431787 FEN46AA125JGF A.14 432085 FEJP A.22 432312 FERS3B0025 A.15
431422 FEL306F250KF A.19 431790 FEN46AA160JJF A.14 432088 FEJS3 A.22 432315 FERS3E0063 A.15
C 431425
431431
FGL456SA400NLF
FEL36SA125JGF
A.27
A.15
431793
431796
FEN46AA160KJF
FEN46AA250KKF
A.17
A.17
432091
432096
FEJS4
FEH36TD250KF
A.22
A.16
432316
432318
FEH46TD250KF
FERS3G0125
A.16
A.15
431434 FEL36SA160JJF A.15 431799 FEN406F160JF A.18 432099 FENR4 A.20 432321 FERS3J0160 A.15
431437 FEL36SA160KJF A.17 431802 FEN406F250KF A.19 432102 FENRC A.46 432327 FERS3K0250 A.17
431440 FEL36SA250KKF A.17 431811 FEN436SA125JGF A.15 432120 FENRW A.20 432330 FERS43B0025 A.15
D 431449
431455
FGL46SA400NLF
FGN36AA400LLF
A.27
A.25
431814
431817
FEN436SA160JJF
FEN436SA160KJF
A.15
A.17
432132
432135
FEQDB3HJ
FEQDB3HK
A.20
A.20
432332
432333
FEL36TD100JF
FERS43E0063
A.13
A.15
431458 FEL36TA080JF A.13 431820 FEN436SA250KKF A.17 432138 FEQDB3MJ A.20 432336 FERS43G0125 A.15
431461 FGN36AA630NNF A.27 431824 FEH46AA125KGF A.17 432141 FEQDB3MK A.20 432339 FERS43J0160 A.15
431464 FEL36TA100JF A.13 431836 FEL36AA125KGF A.17 432144 FEQDB4HJ A.20 432341 FEL36TD125JF A.13
E 431470
431473
FEL36TA125JF
FGN306F400LF
A.13
A.29
431838
431842
FEN436TA080JF
FEDFQ4
A.13
A.21
432147
432150
FEQDB4HK
FEQDB4MJ
A.20
A.20
432344
432345
FEL36TD125KF
FERS43K0250
A.16
A.17
431476 FEL36TA160JF A.13 431844 FEN436TA100JF A.13 432153 FEQDB4MK A.20 432348 FERS45E0063 A.15
431488 FGN306F400NF A.30 431850 FEN436TA125JF A.13 432156 FETCA1316 A.21 432349 FEL36TD160JF A.13
431491 FGN306F630NF A.30 431856 FEN436TA160JF A.13 432157 FETCA1320 A.21 432351 FERS45G0125 A.15
F 431494
431497
FEL46AA125JGF
FEL46AA160JJF
A.14
A.14
431870
431871
FGGS0250
FEN456SA125JGF
A.33
A.15
432158
432159
FETCA1416
FETCA1420
A.21
A.21
432353
432354
FEL36TD160KF
FERS45J0160
A.16
A.15
431500 FEL46AA160KJF A.17 431874 FEN456SA160JJF A.15 432160 FETCA1323 A.21 432357 FEL36TD200KF A.16
431503 FEL46AA250KKF A.17 431877 FEN456SA160KJF A.17 432161 FETCA1423 A.21 432360 FERS45K0250 A.17
431506 FEL406F160JF A.18 431880 FEN456SA250KKF A.17 432162 FEUA3 A.22 432361 FEL36TD250KF A.16
G 431509
431518
FEL406F250KF
FEL436SA125JGF
A.19
A.15
431886
431890
FEN456TA080JF
FEL46AA125KGF
A.13
A.17
432163
432168
FEUA4
FEWS3
A.22
A.21
432363
432366
FERS4B0025
FERS4E0063
A.15
A.15
431521 FEL436SA160JJF A.15 431892 FEN456TA100JF A.13 432171 FEWS4 A.21 432369 FERS4G0125 A.15
431524 FEL436SA160KJF A.17 431898 FEN456TA125JF A.13 432174 FERJ3B0016 A.14 432372 FERS4J0160 A.15
431527 FEL436SA250KKF A.17 431904 FEN456TA160JF A.13 432177 FERJ3B0025 A.14 432374 FEL436TD100JF A.13
X 431530
431536
FGN36SA400NLF
FGN46AA400LLF
A.27
A.25
431920
431922
FEN36AA125KGF
FEN46SA125JGF
A.17
A.15
432180
432183
FERJ3E0040
FERJ3E0063
A.14
A.14
432378
432391
FERS4K0250
FETTA43J0025
A.17
A.18
431539 FGN46AA630NNF A.27 431925 FEN46SA160JJF A.15 432184 FE1BPW A.21 432394 FETTA43J0032 A.18
431545 FEL436TA080JF A.13 431928 FEN46SA160KJF A.17 432186 FERJ3G0080 A.14 432397 FETTA43J0040 A.18
431548 FGN406F400LF A.29 431931 FEN46SA250KKF A.17 432188 FE1BRW A.21 432400 FETTA43J0050 A.18
431551 FEL436TA100JF A.13 431938 FEN46AA125KGF A.17 432189 FERJ3J0100 A.14 432403 FETTA43J0063 A.18
431554 FGN406F400NF A.30 431949 FEN46TA080JF A.13 432190 FEBRCS3 A.21 432406 FETTA43J0080 A.18
431557 FEL436TA125JF A.13 431955 FEN46TA100JF A.13 432191 FEBRCS4 A.21 432409 FETTA43J0100 A.18
431560 FGN406F630NF A.30 431961 FEN46TA125JF A.13 432192 FERJ3G0125 A.14 432412 FETTA43J0125 A.18
431563 FEL436TA160JF A.13 431965 FEH36TD160JF A.13 432193 FGBRCS3 A.32 432414 FETAA3J0025 A.18
431578 FEL456SA125JGF A.15 431967 FEN46TA160JF A.13 432194 FGBRCS4 A.32 432416 FEV36TA125KF A.16
431581 FEL456SA160JJF A.15 431980 FEH36TD160KF A.16 432195 FERJ3J0160 A.14 432417 FETAA3J0063 A.18
431584 FEL456SA160KJF A.17 431981 FGBSS3 A.32 432198 FEH436TD100JF A.13 432420 FETAA3J0125 A.18
431587 FEL456SA250KKF A.17 431982 FGBSS4 A.32 432204 FERJ3K0160 A.17 432423 FETAA3J0160 A.18
431593 FEL456TA080JF A.13 431983 FGDFF3 A.32 432205 FEH436TD125JF A.13 432426 FETAA3K0160 A.19

X.8
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
432429 FETAA3K0250 A.19 432840 FGJB A.33 433216 FETTD43K0125 A.19 433474 FBTS10L12 A.43
432432 FETAA4J0025 A.18 432843 FEL456TD160KF A.16 433219 FETTD43K0160 A.19 433489 FDDFQ3 A.9
432435 FETAA4J0063 A.18 432846 FGJM3 A.33 433222 FETTD43K0200 A.19 433492 FDDFQ4 A.9
432438 FETAA4J0125 A.18 432849 FGJM4 A.33 433225 FETTD43K0250 A.19 433497 FBTF4L12 A.43
432441 FETAA4J0160 A.18 432852 FGJP A.33 433231 FETTD45J0100 A.18 433500 FAR A.22
432444 FETAA4K0160 A.19 432855 FGJS3 A.33 433234 FETTD45J0125 A.18 433519 FDN13TF080GF A.5
432447 FETAA4K0250 A.19 432858 FGJS4 A.33 433235 FGRS3NL0400 A.27 433522 FDN13TF100GF A.5
432480 FETD30J0160 A.18 432861 FGJW3 A.33 433239 FETTD45J0160 A.18 433525 FDN13TF125GF A.5
432483 FETD30K0250 A.19 432864 FGJW4 A.33 433241 FGRS43NL0400 A.27 433527 FDN13TF160GF A.5
432486 FETD40J0160 A.18 432867 FGNFT A.31 433246 FDH13TF016EF A.5 433531 FENFT A.20
432489 FETD40K0250 A.19 432868 FEL456TD200KF A.16 433247 FGRS45NL0400 A.27 433539 FDUT A.10
432495 FETMC3J0012 A.18 432871 FEL456TD250KF A.16 433252 FETTD45K0125 A.19 433540 FEUT A.22

By reference number
432498 FETMC3J0020 A.18 432873 FGNRC A.46 433253 FGRS4NL0400 A.27 433541 FGUT A.33
432501 FETMC3J0050 A.18 432907 FEL46TD100JF A.13 433255 FDH13TF020EF A.5 433542 FDQDS3H A.8
432504 FETMC3J0100 A.18 432908 FGUA3 A.33 433257 FETTD45K0160 A.19 433548 FDQDS4H A.8
432510 FETMC3J0160 A.18 432909 FGUA4 A.33 433260 FETTD45K0200 A.19 433572 FDN36TD160GD A.6
432513 FETMC3K0160 A.19 432910 FGWS3 A.32 433262 FDH13TF025EF A.5 433575 FDN36TG160GD A.6
432516 FETMC3K0250 A.19 432913 FGWS4 A.32 433263 FETTD45K0250 A.19 433578 FDN436TD160GD A.6
432528 FETMC43J0050 A.18 432921 FEL46TD125JF A.13 433268 FDH13TF032EF A.5 433581 FDN436TG160GD A.6
432531 FETMC43J0100 A.18 432924 FEL46TD125KF A.16 433269 FETTD4J0100 A.18 433584 FDN456TD160GD A.6
432537 FETMC43J0160 A.18 432927 FEL46TD160JF A.13 433272 FETTD4J0125 A.18 433587 FDN456TG160GD A.6
432540 FETMC43K0160 A.19 432930 FEL46TD160KF A.16 433274 FDH13TF040EF A.5 433590 FDN46TD160GD A.6
432543 FETMC43K0250 A.19 432933 FEL46TD200KF A.16 433275 FETTD4J0160 A.18 433593 FDN46TG160GD A.6
432546 FETTA3J0025 A.18 432936 FEL46TD250KF A.16 433280 FDH13TF050EF A.5 433599 FDN66TD160GD A.5
432549 FETTA3J0032 A.18 432945 FEN36TD100JF A.13 433284 FETTD4K0125 A.19 433602 FDS35TD160GD A.5
432552 FETTA3J0040 A.18 432952 FDS35TD063ED A.5 433286 FDH13TF063EF A.5 433604 FDS45TD160GD A.5
432555 FETTA3J0050 A.18 432953 FEN36TD125JF A.13 433287 FETTD4K0160 A.19 433649 FDE36TE016ED A.5
432558 FETTA3J0063 A.18 432955 FDS35TD080GD A.5 433290 FETTD4K0200 A.19 433651 FDE36TE020ED A.5
432561 FETTA3J0080 A.18 432958 FDS35TD100GD A.5 433292 FDH13TF080GF A.5 433653 FDE36TE025ED A.5
432564 FETTA3J0100 A.18 432961 FDS35TD125GD A.5 433293 FETTD4K0250 A.19 433655 FDE36TE032ED A.5
432567 FETTA3J0125 A.18 432962 FEN36TD125KF A.16 433296 FETTG3J0100 A.18 433657 FDE36TE040ED A.5
432570 FETTA3J0160 A.18 432964 FDS45TD063ED A.5 433298 FDH13TF100GF A.5 433659 FDE36TE050ED A.5
432573 FEL436TD125JF A.13 432967 FDS45TD080GD A.5 433304 FDH13TF125GF A.5 433661 FDE36TE063ED A.5
432576 FEL436TD125KF A.16 432970 FDS45TD100GD A.5 433310 FDH13TF160GF A.5 433663 FDE36TE080GD A.5
432582 FETTA43J0160 A.18 432971 FEN36TD160JF A.13 433311 FETTG43J0100 A.18 433665 FDE36TE100GD A.5
432585 FEL436TD160JF A.13 432973 FDS45TD125GD A.5 433316 FDN13TF016EF A.5 433667 FDE36TE125GD A.5
432588 FEL436TD160KF A.16 432976 FEN36TD160KF A.16 433322 FDN13TF020EF A.5 433669 FDE36TE160GD A.5
432603 FETTA45J0063 A.18 432979 FEN36TD200KF A.16 433326 FETTG45J0100 A.18 433697 FDE46TE016ED A.5
432606
432609
FETTA45J0080
FETTA45J0100
A.18
A.18
432982
432994
FEN36TD250KF
FEN436TD100JF
A.16
A.13
433328
433332
FDN13TF025EF
FETTG4J0100
A.5
A.18
433699
433701
FDE46TE020ED
FDE46TE025ED
A.5
A.5
A
432612 FETTA45J0125 A.18 433... 433334 FDN13TF032EF A.5 433703 FDE46TE032ED A.5
432615 FETTA45J0160 A.18 433001 FEN436TD125JF A.13 433340 FDN13TF040EF A.5 433705 FDE46TE040ED A.5
432618 FEL436TD200KF A.16 433004 FEN436TD125KF A.16 433346 FDN13TF050EF A.5 433707 FDE46TE050ED A.5
432621
432636
FEL436TD250KF
FETTA4J0025
A.16
A.18
433007
433010
FEN436TD160JF
FEN436TD160KF
A.13
A.16
433352
433357
FDN13TF063EF
FDBRCL2
A.5
A.9
433709
433711
FDE46TE063ED
FDE46TE080GD
A.5
A.5
B
432639 FETTA4J0032 A.18 433013 FEN436TD200KF A.16 433358 FDBRCS2 A.9 433713 FDE46TE100GD A.5
432642 FETTA4J0040 A.18 433016 FEN436TD250KF A.16 433364 FDQDB3H A.8 433715 FDE46TE125GD A.5
432645 FETTA4J0050 A.18 433028 FEN456TD100JF A.13 433370 FDQDB3M A.8 433717 FDE46TE160GD A.5
432648
432651
FETTA4J0063
FETTA4J0080
A.18
A.18
433034
433037
FEN456TD125JF
FEN456TD125KF
A.13
A.16
433373
433376
FDQDB4H
FAMLT1
A.8
A.22
433892
433907
FGNRW
FDC35TE016ED
A.31
A.5
C
432654 FETTA4J0100 A.18 433040 FEN456TD160JF A.13 433377 FBCI3 A.43 433911 FDC35TE020ED A.5
432657 FETTA4J0125 A.18 433043 FEN456TD160KF A.16 433379 FDQDB4M A.8 433914 FDC35TE025ED A.5
432660 FETTA4J0160 A.18 433046 FEN456TD200KF A.16 433388 FDQDI3M A.8 433918 FDC35TE032ED A.5
432693
432696
FETTG3J0125
FETTG3J0160
A.18
A.18
433049
433061
FEN456TD250KF
FEN46TD100JF
A.16
A.13
433397
433400
FDQDI4M
FDTCA1316
A.8
A.9
433924
433925
FDC35TE125GD
FDC35TE160GD
A.5
A.5
D
432699 FEL456TD100JF A.13 433067 FEN46TD125JF A.13 433401 FDTCA1416 A.9 433948 FDC45TE016ED A.5
432705 FETTG3K0160 A.19 433070 FEN46TD125KF A.16 433406 FG1BPW A.32 433949 FDC45TE020ED A.5
432708 FETTG3K0200 A.19 433073 FEN46TD160JF A.13 433407 FG1BRW A.32 433950 FDC45TE025ED A.5
432711
432717
FETTG3K0250
FETTG43J0125
A.19
A.18
433076
433079
FEN46TD160KF
FEN46TD200KF
A.16
A.16
433412
433413
FGTCA230B
FGTCA240B
A.32
A.32
433951
433952
FDC45TE032ED
FDC45TE040ED
A.5
A.5
E
432720 FETTG43J0160 A.18 433082 FEN46TD250KF A.16 433415 FN1BRY1 A.39 433953 FDC45TE050ED A.5
432729 FETTG43K0160 A.19 433142 FGH36AA400NLF A.27 433416 FN1I2F A.46 433954 FDC45TE063ED A.5
432732 FETTG43K0200 A.19 433148 FGRJ3NL0250 A.27 433417 FN1PR A.40 434...
432735
432741
FETTG43K0250
FETTG45J0125
A.19
A.18
433151
433154
FGRJ3LL0400
FGRJ3NN0400
A.25
A.27
433419
433420
FNGS0800
FNBES3R
A.40
A.39
434013
434028
FAMECM
FGH36KA630NNF
A.26
A.28
F
432744 FETTG45J0160 A.18 433157 FGRJ3NN0630 A.27 433421 FNGS1000 A.40 434041 FGH46KA250LKF A.26
432747 FEL456TD125JF A.13 433159 FETTD3J0100 A.18 433422 FNBES4R A.39 434042 FGH46KA400LLF A.26
432753 FETTG45K0160 A.19 433160 FGRJ43NL0250 A.27 433423 FNBRC3 A.39 434043 FGH46KA400NLF A.28
432756
432759
FETTG45K0200
FETTG45K0250
A.19
A.19
433163
433164
FGRJ43LL0400
FETTD3J0125
A.25
A.18
433425
433426
FNBRC4
FNBRCS3
A.39
A.39
434044
434049
FGH46KA630NNF
FGL36KA250LKF
A.28
A.26
G
432774 FETTG4J0125 A.18 433166 FGRJ43NN0400 A.27 433427 FNBRCS4 A.39 434050 FGL36KA400LLF A.26
432777 FETTG4J0160 A.18 433168 FETTD3J0160 A.18 433434 FNWS3WP A.39 434051 FGL36KA400NLF A.28
432780 FEL456TD125KF A.16 433169 FGRJ43NN0630 A.27 433436 FNWS3AP A.39 434052 FGL36KA630NNF A.28
432786
432789
FETTG4K0160
FETTG4K0200
A.19
A.19
433172
433175
FGRJ45NL0250
FGRJ45LL0400
A.27
A.25
433438
433439
FNTCA4327
FNTCA4427
A.39
A.39
434068
434073
FGL46KA630NNF
FGN36KA250LKF
A.28
A.26
X
432792 FETTG4K0250 A.19 433178 FGRJ45NN0400 A.27 433440 FNWS4AP A.39 434092 FGN46KA630NNF A.28
432796 FGDMP3 A.32 433181 FGRJ45NN0630 A.27 433442 FNWS4WT A.39 434098 FGRL3LK0250 A.26
432799 FGDMP4 A.32 433182 FETTD3K0125 A.19 433443 FBAD3 A.43 434099 FGRL3LL0400 A.26
432811 FGEMF8 A.31 433184 FGRJ4NL0250 A.27 433444 FBCI4 A.43 434100 FGRL3NN0630 A.28
432817 FGEMFD A.31 433186 FETTD3K0160 A.19 433446 FBAD4 A.43 434101 FGRL43LK0160 A.26
432820 FGEMFF A.31 433187 FGRJ4LL0400 A.25 433449 FBAE3 A.43 434105 FGRL45LK0160 A.29
432823 FGEMFH A.31 433190 FGRJ4NN0400 A.27 433452 FBAE4 A.43 434106 FGRL45LK0250 A.26
432826 FGEMFJ A.31 433191 FETTD3K0200 A.19 433455 FBB3E A.43 434107 FGRL45LL0400 A.26
432829 FGEMFN A.31 433193 FGRJ4NN0630 A.27 433456 FBTF3L12 A.43 434109 FGRL4LK0160 A.26
432834 FEL456TD160JF A.13 433195 FETTD3K0250 A.19 433458 FBB3S A.43 434111 FGRL4LL0400 A.26
432836 FGFT A.33 433201 FETTD43J0100 A.18 433461 FBB4E A.43 434112 FGRL4NN0630 A.28
432838 FGGS0400 A.33 433204 FETTD43J0125 A.18 433464 FBB4S A.43 434201 FGTKA3L0250 A.29
432839 FGGS0630 A.33 433207 FETTD43J0160 A.18 433468 FBTS1L12 A.43 434202 FGTKA3L0400 A.29

X.9
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
434203 FGTKA3N0400 A.30 434657 FGL36SA500NNF A.27 434967 FEL36MC250KF A.16 435223 FEN46TA050JF A.13
434204 FGTKA3N0630 A.30 434663 FGH36BM400LLF A.25 434970 FEL36TA025JF A.13 435224 FGRL43NL0400 A.28
434205 FGTKA4L0250 A.29 434666 FGH36BM500NNF A.27 434971 FGH456VA400LLF A.26 435226 FEN46TA063JF A.13
434231 FGH306F250LF A.29 434669 FGH436BM400LLF A.25 434973 FEL36TA032JF A.13 435230 FGRL45NL0250 A.28
434232 FGH36AA250LKF A.25 434672 FGH436BM500NNF A.27 434976 FEL36TA040JF A.13 435236 FGRL45NL0400 A.28
434233 FGH36SA250LKF A.25 434675 FGL36BM400LLF A.25 434977 FGH456VA630NNF A.28 435250 FEN46TG100JF A.13
434234 FGH406F250LF A.29 434678 FGL36BM500NNF A.27 434979 FEL36TA050JF A.13 435253 FEN46TG125JF A.13
434235 FGH436SA250LKF A.25 434681 FGL436BM400LLF A.25 434982 FEL36TA063JF A.13 435254 FGRL4NL0250 A.28
434236 FGH456SA250LKF A.25 434684 FGL436BM500NNF A.27 434983 FGH46VA400LLF A.26 435259 FEN46TG160JF A.13
434237 FGH46AA250LKF A.25 434687 FGN36BM400LLF A.25 434994 FEL436MC050JF A.14 435260 FGRL4NL0400 A.28
434238 FGH46SA250LKF A.25 434690 FGN36BM500NNF A.27 434997 FEL436MC100JF A.14 435262 FEN46TG160KF A.16
434239 FGL306F250LF A.29 434693 FGN436BM400LLF A.25 435... 435265 FEN46TG200KF A.16
434240 FGL36AA250LKF A.25 434696 FGN436BM500NNF A.27 435003 FGH46VA630NNF A.28 435266 FGRL45LL0350 A.26
434241 FGL36SA250LKF A.25 434735 FGNRE A.31 435004 FEL436MC160JF A.14 435268 FEN46TG250KF A.16
434242 FGL406F250LF A.29 434736 FETMC3J0030 A.18 435007 FEL436MC160KF A.16 435272 FGRL45NN0500 A.28
434243 FGL436SA250LKF A.25 434742 FEH36MC007JF A.14 435010 FEL436MC250KF A.16 435273 FKY406DN100SF A.37
434244 FGL456SA250LKF A.25 434745 FEH36MC012JF A.14 435013 FEL436TA025JF A.13 435276 FKH36NE125SSF A.36
Numerical index

434245 FGL46AA250LKF A.25 434748 FEH36MC020JF A.14 435016 FEL436TA032JF A.13 435277 FGN436SA400LLF A.25
434246 FGL46SA250LKF A.25 434751 FEH36MC030JF A.14 435019 FEL436TA040JF A.13 435279 FKH36NE160TTF A.37
434247 FGN306F250LF A.29 434754 FEH36MC050JF A.14 435022 FEL436TA050JF A.13 435280 FGN46SA400LLF A.25
434248 FGN36AA250LKF A.25 434757 FEH36MC100JF A.14 435025 FEL436TA063JF A.13 435282 FKL46NE800PPF A.35
434249 FGN36SA250LKF A.25 434758 FGL436SA500NNF A.27 435037 FEL456TA063JF A.13 435285 FKH36NE800PPF A.35
434250 FGN406F250LF A.29 434763 FEH36MC160JF A.14 435049 FEL46TA025JF A.13 435288 FKH36NE100SQF A.36
434251 FGN436SA250LKF A.25 434764 FGL456SA500NNF A.27 435052 FEL46TA032JF A.13 435294 FKH36NG125SSF A.36
434252 FGN456SA250LKF A.25 434766 FEH36MC160KF A.16 435055 FEL46TA040JF A.13 435297 FKH36NG160TTF A.37
434253 FGN46AA250LKF A.25 434769 FEH36MC250KF A.16 435058 FEL46TA050JF A.13 435300 FKN436NT800PF A.35
434254 FGN46SA250LKF A.25 434770 FGL46AA500NNF A.27 435061 FEL46TA063JF A.13 435302 FGRL4LL0350 A.26
434261 FGTKA4L0400 A.29 434772 FEH36TA025JF A.13 435065 FGL36VA400LLF A.26 435303 FKH36NG800PPF A.35
434263 FGTKA4N0400 A.30 434775 FEH36TA032JF A.13 435071 FGL36VA630NNF A.28 435306 FKH36NG100SQF A.36
434265 FGTKA4N0630 A.30 434778 FEH36TA040JF A.13 435073 FEN36MC007JF A.14 435309 FGRL4NN0500 A.28
434303 FGRS3LK0250 A.25 434781 FEH36TA050JF A.13 435076 FEN36MC012JF A.14 435312 FKH36NS125SSF A.36
434307 FGRS43LK0250 A.25 434782 FGL46KA500NNF A.28 435077 FGL436VA400LLF A.26 435315 FKH36NS160TTF A.37
434311 FGRS45LK0250 A.25 434784 FEH36TA063JF A.13 435079 FEN36MC020JF A.14 435318 FKH36NT800PF A.35
434315 FGRS4LK0250 A.25 434806 FGL46SA500NNF A.27 435082 FEN36MC030JF A.14 435321 FKH36NS800PPF A.35
434319 FGTAA3L0250 A.29 434808 FEH36TG100JF A.13 435085 FEN36MC050JF A.14 435324 FKH36NS100SQF A.36
434323 FGTAA4L0250 A.29 434811 FEH36TG125JF A.13 435088 FEN36MC100JF A.14 435330 FKH46NE125SSF A.36
434337 FGRJ3LK0160 A.25 434812 FGN36AA500NNF A.27 435091 FGL436VA630NNF A.28 435333 FKH46NE160TTF A.37
434341 FGRJ3LK0250 A.25 434817 FEH36TG160JF A.13 435094 FEN36MC160JF A.14 435336 FKN36NT800PF A.35
A 434345
434349
FGRJ43LK0160
FGRJ43LK0250
A.25
A.25
434820
434823
FEH36TG160KF
FEH36TG200KF
A.16
A.16
435095
435097
FGL456VA400LLF
FEN36MC160KF
A.26
A.16
435339
435342
FKH46NE800PPF
FKH46NE100SQF
A.35
A.36
434353 FGRJ45LK0160 A.25 434824 FGN36KA500NNF A.28 435100 FEN36MC250KF A.16 435343 FGRJ3LL0250 A.25
434357 FGRJ45LK0250 A.25 434826 FEH36TG250KF A.16 435103 FEN36TA025JF A.13 435348 FKH46NG125SSF A.36
434361 FGRJ4LK0160 A.25 434829 FEH436MC050JF A.14 435106 FEN36TA032JF A.13 435351 FKH46NG160TTF A.37
B 434365
434393
FGRJ4LK0250
FGH36KA350LLF
A.25
A.26
434832
434835
FEH436MC100JF
FGN36SA500NNF
A.14
A.27
435107
435109
FGTCA1327
FEN36TA040JF
A.32
A.13
435354
435356
FKH436NT800PF
FGRJ43LL0250
A.35
A.25
434399 FGH36SA400LLF A.25 434838 FEH436MC160JF A.14 435112 FEN36TA050JF A.13 435357 FKH46NG800PPF A.35
434408 FGH436SA400LLF A.25 434841 FEH436MC160KF A.16 435115 FEN36TA063JF A.13 435360 FKH46NG100SQF A.36
434414 FGH456SA400LLF A.25 434844 FEH436MC250KF A.16 435116 FGTCA1427 A.32 435366 FKH46NS125SSF A.36
C 434420
434426
FGH46KA350LLF
FGH46SA400LLF
A.26
A.25
434847
434848
FEH436TA025JF
FGN436SA500NNF
A.13
A.27
435118
435120
FASHTH
FAUVRH
A.8
A.8
435367
435369
FGRJ45LL0250
FKH46NS160TTF
A.25
A.37
434432 FGH46AA400NLF A.27 434850 FEH436TA032JF A.13 435122 FGL456VA630NNF A.28 435372 FKL36NT800PF A.35
434438 FGL36KA350LLF A.26 434853 FEH436TA040JF A.13 435128 FGL46VA400LLF A.26 435375 FKH46NS800PPF A.35
434444 FGL36SA400LLF A.25 434856 FEH436TA050JF A.13 435134 FGL46VA630NNF A.28 435378 FKH46NS100SQF A.36
D 434448
434453
FAMB2
FGL436SA400LLF
A.26
A.25
434859
434860
FEH436TA063JF
FGN456SA500NNF
A.13
A.27
435139
435140
FEN36TG100JF
FGN36VA400LLF
A.13
A.26
435381
435384
FKY306DN100SF
FKN36NE125SSF
A.37
A.36
434459 FGL36AA400NLF A.27 434866 FGN46AA500NNF A.27 435142 FEN36TG125JF A.13 435387 FKN36NE160TTF A.37
434462 FGL456SA400LLF A.25 434871 FEH456TA063JF A.13 435146 FGN36VA630NNF A.28 435390 FKL36NE800PPF A.35
434468 FGL46KA350LLF A.26 434872 FGN46KA500NNF A.28 435148 FEN36TG160JF A.13 435393 FKN36NE800PPF A.35
E 434471
434473
FGRL3NN0400
FGRL3NN0500
A.28
A.28
434883
434884
FEH46TA025JF
FGN46SA500NNF
A.13
A.27
435151
435152
FEN36TG160KF
FGN436VA400LLF
A.16
A.26
435396
435397
FKN36NE100SQF
FGRJ4LL0250
A.36
A.25
434474 FGL46SA400LLF A.25 434886 FEH46TA032JF A.13 435154 FEN36TG200KF A.16 435399 FGRL3LL0250 A.26
434483 FGN36KA350LLF A.26 434889 FEH46TA040JF A.13 435157 FEN36TG250KF A.16 435400 FGRL3LL0350 A.26
434489 FGN36SA400LLF A.25 434892 FEH46TA050JF A.13 435158 FGN436VA630NNF A.28 435402 FKN36NG125SSF A.36
F 434495
434497
FGRL45LL0250
FGRL45NN0400
A.26
A.28
434893
434895
FGTAA3N0500
FEH46TA063JF
A.30
A.13
435160
435163
FEN436MC050JF
FEN436MC100JF
A.14
A.14
435405
435408
FKN36NG160TTF
FKN436NT630PF
A.37
A.35
434501 FGRL4NN0400 A.28 434899 FGTAA4N0500 A.30 435164 FGN456VA400LLF A.26 435410 FGRL43LL0250 A.26
434504 FGN456SA400LLF A.25 434902 FGTKA3L0350 A.29 435167 FGN456VA630NNF A.28 435411 FKN36NG800PPF A.35
434510 FGN46KA350LLF A.26 434905 FGTKA3N0500 A.30 435169 FEN436MC160JF A.14 435412 FGRL43LL0350 A.26
G 434512
434516
FGRS3NN0500
FGRS43LL0400
A.27
A.25
434908
434911
FGTKA4L0350
FGTKA4N0500
A.29
A.30
435170
435172
FGN46VA400LLF
FEN436MC160KF
A.26
A.16
435414
435419
FKN36NG100SQF
FGRL43NN0400
A.36
A.28
434521 FGRS43NN0500 A.27 434919 FEH46TG100JF A.13 435175 FEN436MC250KF A.16 435420 FKN36NS125SSF A.36
434525 FGRS45LL0400 A.25 434922 FEH46TG125JF A.13 435176 FGN46VA630NNF A.28 435423 FKN36NS160TTF A.37
434530 FGRS45NN0500 A.27 434928 FEH46TG160JF A.13 435178 FEN436TA025JF A.13 435426 FKH36NT630PF A.35
X 434534
434537
FGL46AA400NLF
FGRS4LL0400
A.27
A.25
434931
434934
FEH46TG160KF
FEH46TG200KF
A.16
A.16
435181
435182
FEN436TA032JF
FGRJ3NL0400
A.13
A.27
435427
435429
FGRL43NN0500
FKN36NS800PPF
A.28
A.35
434542 FGRS4NN0500 A.27 434937 FEH46TG250KF A.16 435184 FEN436TA040JF A.13 435432 FKN36NS100SQF A.36
434561 FGN36AA400NLF A.27 434940 FEL36MC007JF A.14 435187 FEN436TA050JF A.13 435433 FGRL4LL0250 A.26
434600 FGH36AA500NNF A.27 434943 FEL36MC012JF A.14 435188 FGRJ43NL0400 A.27 435435 FGRS3LL0400 A.25
434606 FGH36KA500NNF A.28 434946 FEL36MC020JF A.14 435190 FEN436TA063JF A.13 435438 FKN46NE125SSF A.36
434612 FGH36SA500NNF A.27 434949 FEL36MC030JF A.14 435194 FGRJ45NL0400 A.27 435441 FKN46NE160TTF A.37
434621 FGH436SA500NNF A.27 434952 FEL36MC050JF A.14 435200 FGRJ4NL0400 A.27 435444 FKN36NT630PF A.35
434627 FGH456SA500NNF A.27 434953 FGH36VA400LLF A.26 435202 FEN456TA063JF A.13 435447 FKN46NE800PPF A.35
434630 FGH46AA500NNF A.27 434955 FEL36MC100JF A.14 435206 FGRL3NL0250 A.28 435450 FFKN46NE100SQF A.36
434633 FGH46KA500NNF A.28 434958 FGH36VA630NNF A.28 435212 FGRL3NL0400 A.28 435456 FKN46NG125SSF A.36
434636 FGN46AA400NLF A.27 434960 FGH436VA400LLF A.26 435214 FEN46TA025JF A.13 435459 FKN46NG160TTF A.37
434642 FGH46SA500NNF A.27 434961 FEL36MC160JF A.14 435217 FEN46TA032JF A.13 435462 FKH436NT630PF A.35
434645 FGL36AA500NNF A.27 434964 FEL36MC160KF A.16 435218 FGRL43NL0250 A.28 435465 FKN46NG800PPF A.35
434651 FGL36KA500NNF A.28 434965 FGH436VA630NNF A.28 435220 FEN46TA040JF A.13 435468 FKN46NG100SQF A.36

X.10
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
435474 FKN46NS125SSF A.36 435821 FDH36TD160GD A.6 436152 FGH36KA400NLF A.28 436513 FGNRY/5 A.31
435477 FKN46NS160TTF A.37 435824 FDH36TG160GD A.6 436153 FGL46KA250LKF A.26 436514 FGNRYV/5 A.31
435480 FKL36NT630PF A.35 435827 FDH436TD160GD A.6 436154 FGL46KA400LLF A.26 436515 FGNRZ/5 A.31
435483 FKN46NS800PPF A.35 435830 FDH436TG160GD A.6 436155 FGL46KA400NLF A.28 436516 FGNRZV/5 A.31
435486 FKN46NS100SQF A.36 435833 FDH456TD160GD A.6 436156 FGN36KA400LLF A.26 436517 FNNRC/5 A.38
435489 FKY306DN125SF A.37 435836 FDH456TG160GD A.6 436157 FGN36KA400NLF A.28 436518 FNNRCV/5 A.38
435492 FKY306DN160TF A.37 435839 FDH46TD160GD A.6 436158 FGN36KA630NNF A.28 436519 FNNRD/5 A.38
435495 FKY306DN800PF A.37 435842 FDH46TG160GD A.6 436159 FGN46KA250LKF A.26 436520 FNNRDV/5 A.38
435498 FKY406DN125SF A.37 435845 FDL36TD160GD A.6 436160 FGN46KA400LLF A.26 436522 FNNRF/5 A.38
435501 FKY406DN160TF A.37 435848 FDL436TD160GD A.6 436161 FGN46KA400NLF A.28 436524 FNNRFV/5 A.38
435504 FKY406DN800PF A.37 435851 FDL456TD160GD A.6 436162 FGRL3LK0160 A.26 436526 FNNRX/5 A.45
435534 FKL436NT630PF A.35 435854 FDL46TD160GD A.6 436177 FGRL43LK0250 A.26 436527 FNNRY/5 A.38

By reference number
435535 FKL436NT800PF A.35 435857 FEH36AA025JBF A.14 436178 FGRL43LL0400 A.26 436528 FNNRYV/5 A.38
435537 FKN36NM800PF A.35 435860 FEH36AA063JEF A.14 436179 FGRL43NN0630 A.28 436530 FNNRZ/5 A.38
435538 FKH36NM800PF A.35 435863 FEH46AA025JBF A.14 436180 FGRL45NN0630 A.28 436531 FNNRZV/5 A.38
435539 FKL36NM800PF A.35 435866 FEH46AA063JEF A.14 436181 FGRL4LK0250 A.26 436590 FNFHW A.40
435541 FKN436NM800PF A.35 435869 FEL36AA025JBF A.14 436183 FAMAM2 A.26 436651 FNTCA3427 A.39
435542 FKH436NM800PF A.35 435872 FEL36AA063JEF A.14 436185 FAMGAM2 A.26 436720 FDKM1 A.10
435543 FKL436NM800PF A.35 435875 FEL46AA025JBF A.14 436186 FAMGAS2 A.26 436754 FEH36MC200KF A.16
435545 FKL36NE100SQF A.36 435878 FEL46AA063JEF A.14 436187 FAMGAT2 A.28 436755 FEH436MC200KF A.16
435546 FKL36NE125SSF A.36 435881 FEN36AA025JBF A.14 436188 FAMGFM2 A.26 436756 FEL36MC200KF A.16
435547 FKL46NE100SQF A.36 435884 FEN36AA063JEF A.14 436189 FAMGFS2 A.26 436763 FEL436MC200KF A.16
435549 FKL46NE125SSF A.36 435887 FEN46AA025JBF A.14 436190 FAMGFT2 A.26 436764 FEN36MC200KF A.16
435550 FKN36NT100SF A.36 435890 FEN46AA063JEF A.14 436191 FAMMT2 A.26 436765 FEN436MC200KF A.16
435551 FKN36NT125SF A.36 435893 FEH36MC080JF A.14 436192 FAMSM2 A.26 436778 FETMC3K0200 A.19
435553 FKH36NT100SF A.36 435896 FEL36MC080JF A.14 436197 FAMST2 A.26 436779 FETMC43K0200 A.19
435554 FKH36NT125SF A.36 435899 FEN36MC080JF A.14 436309 FAS01D A.21 436798 FEV36TA160KF A.16
435555 FKL36NT100SF A.36 435902 FEH436TG100JF A.13 436310 FAS10D A.21 436817 FEV46TA160KF A.16
435557 FKL36NT125SF A.36 435903 FEH436TG125JF A.13 436316 FNTCA3327 A.39 437...
435558 FKN36NM125SF A.36 435904 FEH436TG160JF A.13 436327 FEH36MC125JF A.14 437000 FEEO1J A.47
435559 FKH36NM125SF A.36 435905 FEH436TG160KF A.16 436329 FEH436MC125JF A.14 437001 FE1I2 A.46
435561 FKL36NM125SF A.36 435906 FEH436TG200KF A.16 436331 FEL36MC125JF A.14 437003 FEEO1N A.47
435562 FKN436NT100SF A.36 435907 FEH436TG250KF A.16 436333 FEL436MC125JF A.14 437004 FGEO2J A.47
435563 FKN436NT125SF A.36 435908 FEH456TG160KF A.16 436335 FEN36MC125JF A.14 437005 FG1I2 A.46
435565 FKH436NT100SF A.36 435909 FEH456TG200KF A.16 436356 FEN436MC125JF A.14 437007 FGEO2N A.47
435566 FKH436NT125SF A.36 435910 FEH456TG250KF A.16 436358 FETMC3J0125 A.18 437008 FGEO3J A.47
435567 FKL436NT100SF A.36 435923 FEL36TG100JF A.13 436359 FETMC43J0125 A.18 437009 FG1I4 A.46
435569 FKL436NT125SF A.36 435926 FEL36TG125JF A.13 436361 FEH36MC003JF A.14 437010 FGEO3N A.47
435570
435571
FKN436NM125SF
FKH436NM125SF
A.36
A.36
435932
435935
FEL36TG160JF
FEL36TG160KF
A.13
A.16
436363
436365
FEL36MC003JF
FEN36MC003JF
A.14
A.14
437011
437014
FKEO4J
FKEO4N
A.47
A.47
A
435573 FKL436NM125SF A.36 435938 FEL36TG200KF A.16 436396 FDH36MC003ED A.7 437015 FKEO5J A.47
435574 FN1BRY2 A.39 435941 FEL36TG250KF A.16 436398 FDH436MC003ED A.7 437016 FN1I4F A.46
435575 FN1BRW1 A.39 435944 FEL436TG100JF A.13 436401 FNS11R A.38 437017 FKEO5N A.47
435577
435578
FN1BRW2
FNFW
A.39
A.39
435947
435950
FEL436TG125JF
FEL436TG160JF
A.13
A.13
436409
436411
FDN36MC003ED
FDN436MC003ED
A.7
A.7
437018
440...
FNUVRJ A.45 B
435678 FN1BPE A.38 435953 FEL436TG160KF A.16 436449 FNECE6 A.47 440018 FAUVRB A.8
435679 FN1BRE A.38 435956 FEL436TG200KF A.16 436450 FNECE3 A.47 560...
435680 FNEMFF A.38 435959 FEL436TG250KF A.16 436451 FNECA6 A.47 560090 TTD 22 A.39
435683
435686
FNEMFD
FNEMF3
A.38
A.38
435962
435965
FEL456TG100JF
FEL456TG125JF
A.13
A.13
436452
436453
FNECA3
FAECA3
A.47
A.47
560091
560092
TT 35
TT 60
A.39
A.39
C
435689 FNEMF6 A.38 435968 FEL456TG160JF A.13 436456 FNEMFN A.38 560093 TT 80 A.39
435692 FNSHT8 A.38 435971 FEL456TG160KF A.16 436457 FNEMFJ A.38 560094 TT110 A.39
435693 FNSHTD A.38 435974 FEL456TG200KF A.16 436467 FEJN3 A.21 560095 TT160 A.39
435694
435695
FNSHTF
FNSHTJ
A.38
A.38
435977
435992
FEL456TG250KF
FEL46TG100JF
A.16
A.13
436468
436469
FEJN4
FGJN3
A.21
A.32
560096
560097
TT 210
TTO 110
A.39
A.39
D
435696 FNSHTN A.38 435995 FEL46TG125JF A.13 436470 FGJN4 A.32 560098 TTO 210 A.39
435697 FNUVD6 A.38 436... 436471 FNGS1600 A.40 617...
435698 FNUVR1 A.38 436002 FEL46TG160JF A.13 436472 FAUVR8 A.8 617947 FDKE A.10
435699
435700
FNUVR6
FNUVR8
A.38
A.38
436005
436008
FEL46TG160KF
FEL46TG200KF
A.16
A.16
436474
436475
FDNRC/5
FDNRCV/5
A.8
A.8
704...
704154 BTR 175 A.39
E
435701 FNUVRD A.38 436011 FEL46TG250KF A.16 436476 FDNRD/5 A.8 704155 BTR 305 A.39
435702 FNUVRF A.38 436014 FEN436TG100JF A.13 436477 FDNRDV/5 A.8 704156 BTR 350 A.39
435704 FNT A.40 436015 FEN436TG125JF A.13 436478 FDNRF/5 A.8 704169 RD5 220 A.39
435706
435707
FNBES3P
FNBES4P
A.39
A.39
436016
436017
FEN436TG160JF
FEN436TG160KF
A.13
A.16
436479
436481
FDNRFV/5
FNWS4WP
A.8
A.39
704175
704176
RD5 110
RD5 380
A.39
A.39
F
435708 FNBSS3P A.39 436018 FEN436TG200KF A.16 436482 FNWS3WT A.39 704177 RD6 220 A.39
435709 FNGS1250 A.40 436019 FEN436TG250KF A.16 436487 FDNRY/5 A.8 704178 RD6 110 A.39
435710 FNBSS3R A.39 436020 FEN456TG100JF A.13 436488 FDNRYV/5 A.8 704179 RD6 380 A.39
435711
435712
FNBSS4P
FNBSS4R
A.39
A.39
436021
436022
FEN456TG125JF
FEN456TG160JF
A.13
A.13
436489
436490
FDNRZ/5
FDNRZV/5
A.8
A.8
872...
872052 A.47
G
435713 FNFE A.40 436023 FEN456TG160KF A.16 436491 FENRC/5 A.20 872140 FAECE6 A.47
435714 FNFH A.40 436024 FEN456TG200KF A.16 436492 FENRCV/5 A.20 872141 FAECE3 A.47
435715 FNFT A.40 436025 FEN456TG250KF A.16 436493 FENRD/5 A.20 872224 RD1D 220 A.39
435716
435719
FNJL3
FNJL4
A.40
A.40
436026
436027
FEH456TG100JF
FEH456TG125JF
A.13
A.13
436494
436495
FENRDV/5
FENRF/5
A.20
A.20
872225
872226
RD1D 110
RD1D 380
A.39
A.39
X
435722 FNJP A.40 436028 FEH456TG160JF A.13 436496 FENRFV/5 A.20 872227 RDFR A.49
435726 FNNRC A.46 436078 FETMC3J0080 A.18 436499 FENRX/5 A.45 872240 FAECA6 A.47
435738 FNNRE A.38 436117 FDC35TE040ED A.5 436500 FENRY/5 A.20 880...
435745 FNNRW A.38 436118 FDC35TE050ED A.5 436501 FENRYV/5 A.20 880954 FETCA630A A.21
435757 FNWS3AT A.39 436133 FDC35TE063ED A.5 436502 FENRZ/5 A.20 880955 FETCA640A A.21
435758 FNPFM A.39 436143 FDC35TE080GD A.5 436503 FENRZV/5 A.20 883...
435759 FNWS4AT A.39 436144 FDC35TE100GD A.5 436504 FGNRC/5 A.31 883970 FBF6 A.9
435760 FNS11L A.39 436145 FDC45TE080GD A.5 436505 FGNRCV/5 A.31
435761 FNBA11R A.38 436146 FDC45TE100GD A.5 436506 FGNRD/5 A.31
435762 FNUA3 A.40 436147 FDC45TE125GD A.5 436507 FGNRDV/5 A.31
435763 FNUA4 A.40 436148 FDC45TE160GD A.5 436509 FGNRF/5 A.31
435764 FNUT A.40 436150 FGH36KA250LKF A.26 436510 FGNRFV/5 A.31
435812 FEEMF8 A.20 436151 FGH36KA400LLF A.26 436512 FGNRX/5 A.45

X.11
Record Plus

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Numerical index

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The policy of GE Consumer &
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . is. one. of .continuous
Industrial . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
improvement.
The right is reserved to alter the
.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . or any
design . structural
. . . details. .of .
the products at any time without
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
giving notice.
.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
April 2006
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . GE. Consumer
. . &. Industrial
. . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

X.12
GE Consumer & Industrial

37690
Power Protection

The Power Protection division of


GE Consumer & Industrial is a first class
European supplier of low-voltage products
including wiring devices, residential and
industrial electrical distribution components,
automation products, enclosures and
switchboards. Demand for the company’s
products comes from wholesalers, installers,
panel-board builders, contractors, OEMs
and utilities worldwide
www.ge.com/eu/powerprotection

GE POWER CONTROLS Ltd


Lincoln Road
Enfield
Middlesex EN1 1SB
United Kingdom

Tel. 0800 587 1251


Fax 0800 587 1239
E-mail: gepcuk@gepc.ge.com

GE imagination at work
690011
Ref. I/3198/E/E 3.0 Ed. 05/06
© Copyright GE Power Controls 2006

You might also like