Record Plus
Record Plus
Record Plus
Power Protection
Record Plus
Moulded Case Circuit Breakers
Selective & Current Limiting
GE imagination at work
Record Plus
The breaker
Order codes A
Trip units B
Technical data D
Application guide E
Wiring diagrams F
Dimensions G
Numerical Index X
Record Plus
Rated operational voltage Ue Volts AC 240 500 690 690 690 690
Volts DC 250 - - 500 500 500
Performance figures
3,4 3,4 3,4 3,4 3,4 3,4
690 750 750 750 1000 1000 1000
8 8 8 8 8 8 8
500 690 690 690 690 690 690
440 500 - - 500 500 500
A B(5) B(5) B B B
yes yes yes yes yes yes
250 400 630 800 1250 1600
65 85 100 200 85 100 200 85 100 200 85 100 170 85 100 170 85 100
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
25 42 65 130 42 65 130 42 65 130 42 65 80 42 65 80 42 65
18 30 50 100 30 50 100 30 50 100 36 42 50 36 42 50 36 42
- 10 15 22 10 22 75(7) 10 22 40(7) 20 25 30 20 25 30 20 25
25 50 85 100 50(3) 60(3) 80(3) 50(3) 60(3) 80(3) - -
- 50 85(2) 100(2) 36(2) 50(2) 60(2) 36(2) 50(2) 60(2) - -
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 50% 100% 75% 50% 100% 75%
- 100% 75% 50% 100% 45% 25% 100% 45% 25% 100% 75% 50% 100% 75% 50% 100% 75%
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
- 10 15 22 10 (6) (6) 10 (6) (6) 20 25 30 20 25 30 20 25
10000 25000 20000 20000 10000 10000 10000
5000 10000 7500 5000 4000 3000 2000
10000 20000 15000 10000 8000 6000 4000
4000 10000 8000 8000 4000 3000 2000
no yes yes yes no no no
LTM LTM LTM
GTM
LTMD
Mag BreakTM Mag BreakTM
SMR1 SMR1 SMR1e
SMR2 SMR 1s & g
FE250Y FG400Y FG630Y FK800Y FK1250Y FK1600Y
no no no no no no
yes yes yes yes yes yes
yes yes yes no no no
yes yes yes yes yes yes
yes yes yes yes yes yes
yes yes yes yes yes yes
105 x 170 x 95 140 x 265 x 115 140 x 265 x 115 210 x 320 x 160 210 x 320 x 160 210 x 320 x 160
140 x 170 x 95 185 x 265 x 115 185 x 265 x 115 280 x 320 x 160 280 x 320 x 160 280 x 320 x 160
1.6 4.5 4.5 12.2 18.0 18.0
2.1 6.0 6.0 15.1 23.4 23.4
(5) 350 and 500A executions only (7) On use of FG400 and FG630L type at 690V, one
(6) Please contact us. long and widened terminal shield is required.
33
Record Plus
Breaker type
Insulation
voltage
FE250 Product
description
Breaker frame
rating enclosed
Breaking
capacity Connection
(IEC values) torques
6 digit
reference plus
trip unit rating
Serial number 200A
Catalogue
Standards number
Certification
Record Plus
The Record PlusTM line of circuit breakers has been Meeting the international standards. The requirements
designed to comply with the following standards: are met of BS, VDE, UTE, KEMA, CEI. Record Plus breakers
EN 60947 Low-voltage switchgear and controlgear have been tested in acordance with the NEMA standards
EN 60947-1: General rules
EN 60947-2: Circuit-breakers For the Record Plus product certificates are
EN 60947-3: Switches, disconnectors, switch- available from the following regulatory bodies:
disconnectors and fuse-combination units Germanische Lloyds - RINA
EN 60947-4-1: Contactors and motor-starters Lloyds Register of Shipping - CCC (China)
Section One: Electromechanical contactors and Further tests are being undertaken to meet the
motorstarters requirements of the following regulatory bodies:
EN 60947-5-1: Control circuit devices and switching Bureau Veritas - Det Norske Veritas
elements
Section One: Electromechanical control circuit devices Please contact us to check the availability of individual
The compliance has been verified by two testing authorities: certificates.
LOVAG and KEMA (appropriate certificates are available
on request)
4
Record Plus
Contents
Common accessories
safe & easy to mount
Versatile installation
options
55
Record Plus
The Record PlusTM family of circuit breakers has been developed as a line of aesthetically and
technically coordinated protection devices for low voltage distribution and control applications.
The circuit breakers are available in four sizes, each of which is tailored to the individual requirements
associated with its application.
The line offers a current range running from 3A to 1600A in single, 3 and 4 pole ratings. Numerous
versions as fixed, plug in and draw out are available and the line is completed with a full range of
accessories.
environment with modular equipment and in FD63/160 types in panels. FE sizes are
industrial applications. It is supplied with equipped with an easily accessible busbar
IPXXB terminals suitable for direct connection connection and can also be supplied with
of one or two conductors totalling up to 95 cable lugs for use with copper or aluminum
mm2 and is available as a thermal-magnetic conductors. The design allows the use of
breaker, a moulded case switch, and as a interchangeable thermal-magnetic,
magnetic-only motor circuit protector. magnetic-only, and electronic trip units.
The FD63/160 bridges the gap between
residential miniature circuit breakers and
industrial moulded case circuit breakers.
6
Record Plus
A complete line of
selective & current limiting breakers
FG400 and FG 630 FK 800, 1250 and 1600
Rated at 400 and 630A, the FG frame size Rated at 800,1250 and 1600A, the FK frame
includes all of the advanced features of the sizes are designed for use with the FG400
FD and FE frame sizes. and 630 frame sizes. The design uses
The FG connection area features easy-to- electronic trips units available in a number of
access busbar connections. Cable lugs for performance ranges and allowing a wide
use with single or multiple copper or variety of setting options and groundfault
aluminum conductors are optionally protection. If needed thermal-magnetic and
available. The breaker is designed for use magnetic only trip units are also available.
with interchangeable electronic units that The FK connection area features easy-to-
can be easily adapted to multiple levels of access busbar connections or cable lugs for
protection. use with single or multiple copper or
aluminum conductors.
77
Record Plus
Record PlusTM circuit breakers are designed to protect, isolate and switch circuits in low voltage
distribution networks. Circuit protection is provided by a combination of the devices unique current
limiting properties and integrated protection devices commonly referred to as trip units.
The trip units are designed to protect circuits and/or the equipment connected to these circuits and
exist as electromechanical or electronic devices. Numerous electromechanical types are available as
thermal magnetic devices with overload and short-circuit protection or magnetic-only types providing
short-circuit protection. Electronic devices offering wide setting ranges and a more sophisticated level of
protection are available in several versions. Each trip unit has a setting area finished with a sealable
transparant trip unit door.
Devices available in a current range of 16 to The Record PlusTM FE, FG and FK sizes can be
1250A(1) as single, two, three or four pole equipped with rigorously designed and tested
devices. The electromechanical trip units exist interchangeable electronic trip units available
as thermal magnetic, magnetic-only and in three and four pole units in currents
generator protection models. The high- ranging from 25 to 1600A.
performance thermal magnetic trip units
exist as selective and non-selective versions The SMR1 and SMR2 types offer ajustable
and are equipped with a fault indicator that overload and selective short-circuit protection.
distinguishes between overload and short- The SMR1 range is designed for simplicity
circuit events in accordance with HD 384. and includes numerous exciting features
This patented safety feature allows users to such as an overload signalling option, a built-
reduce downtime by resetting the breaker in temperature sensor and rating plugs
directly after an overload event. suitable for both line and motor protection.
8
Record Plus
Protection with
flexible & interchangeable
trip units
Personnel protection
A line of three and four pole add-on residual
current devices are available as side or
bottom mounted units with ratings up to
630A and sensitivities of 30mA to 10A.
The devices slide on to the breaker easily and
are fixed by simply tightening the main
electrical connections. Designed to meet the
latest standards, they each have a
mechanical and electrical test option and
share a common cut out.
A de-electric disconnect plug unit and setting
areas with transparent, tamper-free cover
are standard for the whole line.
For ratings above 630A, seperate sensors
and relays are available, or an integrated
ground fault protection can be used.
9
Record Plus
Common accessories
safe & easy to mount
10
Record Plus
Mounting Wiring
Internal accessories can be easily External wiring is routed through the
clicked into conveniently marked areas top or the side of the breaker lid
in the isolated compartment. through break out openings.
Clearly marked indication of the The wiring can then be connected to
accessory position and a mechanical the accessory terminals. These cage
interchange prevention system assure terminals allow for cross sections from
an error-proof and solid mounting of 0.75 to 2.5 mm2 and even allow the
the accessory. connection of two wires.
All contact points are coded in
accordance with the EN 60947
standard thus allowing for universal
wiring diagrams.
Releases
The shunt and undervoltage releases are a totally new design combining the
best in electromechanical and electronic engineering. Most releases are
common for AC and DC voltages and are available in a wide voltage range.
They combine low power consumption, a kiss-free, lock-out design and the
ease of use common to all Record PlusTM internal accessories.
11
Record Plus
Wide range of
electrical & mechanical operators
Record Plus
Easy to install
The handles are available as a breaker mounted device, a type
that can be mounted through a door or a panel and a version
where the operator is mounted on the door or panel front.
The door and/or panel mounted units are equipped with
(bypassable) interlocks to prevent the door from opening or the
panel being removed whilst the breaker is ON. The door/panel
mounted operators use a drilling common across the line.
Each breaker size and breaking capacity rating has its own
escutcheon and handle that can be equipped with padlocks
and/or a keylock.
12
Record Plus
Safe to operate
Locking/Interlocking devices
To allow users to safely work on the installations or installation segments
protected by the Record PlusTM moulded case circuit breakers it is
possible to padlock the devices in their OFF position. A padlocking facility
can be attached to the breaker front allowing the breaker to be equipped
with up to three padlocks of 5 to 8 mm.
A second type (depicted in the photo) is only firmly attached to the
breaker when it is padlocked and can be removed for use on another
breaker when not in use. Key locking devices allow the creation of
multiple key interlocking configurations. A walking beam system is
available for interlocking two or three breakers. The system can be
upgraded to a fully automatic power transfer system.
Easy to operate
Electrical operators
Front mounted devices that allow electrical
operation of the breaker on which the device
is mounted. Common to all electrical
operators is a closing speed lower than
80 milliseconds, the same three wire
electrical scheme and a clear and accurate
ON, OFF and TRIPPED indication in the
devices front face. Each device has two
operational positions electrical or manual
and can be padlocked or
key-locked in OFF position. Easy connection
is achieved by locating the terminals in the
immediate vicinity of those of the internal
accessories and by using terminals with a
connection capacity of
0.5 to 2.5 mm2.
13
Record Plus
Terminal shields
Each breaker can be fitted with tamper resistant, short or
long, terminal shields that allow a IP30 finishing of the
product. Backplates and phase separators complete this line
and consistently enable the user to connect the products in
a safe manner. Specific applications, extra accessories are
available for some breaker sizes like the FD160 with its IPXXB
terminal covers and the FG frame with its widened long
terminal shield.
14
Record Plus
Plug-in systems
Plug-in mounting systems are available for current ratings through
630A in both kit and assembled options. The plug-in system
consists of a single-piece moulded base in an IPXXB configuration.
The mounting system features a safety interlock which ensures
that the breaker is mechanically tripped before it is fully withdrawn
or re-inserted in the ON position.
An optional set of plug-in terminal block(s) are available
for use with internal accessory connections. Plug-in
mounting bases are normally supplied with exactly the
same front access terminal configuration as the standard
fixed breaker. This allows the use of the
same wide range of connection accessories that are
available in kit form on the fixed version. These includs
rear and angular connectors, spreaders, customised ring
terminal connectors and extenders. Internal accessories
can be easily clicked into conveniently marked areas in
the isolated compartment. Clearly marked indication of
the accessory position and a mechanical interchange
prevention system assures an error-proof and solid
mounting of the accessory.
Draw-out system
Simple, hand-operated draw-out mechanisms are available for
breakers up to 1600A. The draw-out system enables Record PlusTM
breakers to be configured as fully isolated devices with three
positions: Inserted, Test & Isolated, Remove
The system makes use of the plug-in base and offers all the
advantages of these IPXXB devices such as the safety
interlock system which makes sure that the breaker is
mechanically tripped before it is fully withdrawn or
re-inserted in the "on" position.
They also allow the use of the same optional set of plug-in terminal
block(s) for use with internal accessory connections and are
normally supplied with exactly the same front access terminal
configuration as the standard fixed breaker.
External wiring is routed through the top or the side of the breaker
lid through break out openings. All contact points are coded in
accordance with the EN 60947 standard thus allowing for universal
wiring diagrams.
Connectivity
The installation of a breaker is much easier and more cost effective
when the mounting and connecting of the breaker can be reduced
to a few simple, automateable tasks. Based on these principles
GE Power Controls have devised a unique system
that allows the user to mount and connect the
breaker before installation.
An adaptor plate, specifically designed for the
Record PlusTM breaker line and incorporating all the
connection hardware, is fitted to the breaker using
5 to 6 simple screws. Once mounted the adaptor is
then simply plugged onto a three or four pole busbar
system already installed in the equipment.
15
Record Plus
Using world class design and development
tools like Six Sigma, Computer Simulation
and Lean Manufacturing, Record PlusTM is
intended to meet and exceed the most
stringent quality and safety standards.
At GE we are proud to offer a product that
will offer years of reliable and dependable
protection.
GE Power Controls’ name is synonymous
with a broad range of products designed to
meet our customer’s changing and
competitive environment. Our drive to
exceed our customer’s expectations is the
Record Plus
16
Record Plus
Application Software
The new HD 384 and R064-03 stan-
dards require that the design of a low
voltage distribution system includes
the determination of all perspective
short-circuit and fault currents levels.
GE Power Controls have developed a
windows based software package to
do this: Procera Plus offers a multi
standard and multi lingual software
package to accompany our new
product line.
Implementation Software
Two ranges of software are designed
to allow a user to select the correct
protection devices, the associated
components needed to install it,
and a distribution system in which
they can be installed.
The software can be linked with
Procera and automatically produces
drawings and ordering details.
17
17
Record Plus
Record Plus
18
Record Plus
A.4 FD frame
A.8 Accessories
A.12 FE frame
A.20 Accessories
Order codes A
A.24 FG frame
Trip units B
A.25 Complete circuit breakers FG400 & FG630
Numerical Index X
A.1
Record Plus
How to order a standard breaker
To determine the basic breaker, the required current rating, the
short circuit breaking capacity and the number of switched and
protected poles must be defined. This information can be found on
page 2 and 3 of this catalogue and is repeated in short-form within
the ordering code part of each breaker size.
After selecting the basic device the circuit protection element or trip
unit needs to be defined. These are available in numerous types,
each of which is described briefly in the ordering code part of each
breaker size, whilst a full functional description can be found in the
relative section B of this catalogue.
With the above mentioned information the correct code for the
required moulded case circuit breaker can be found in the order
Order codes
code pages. Here the selected product is a version suited for fixed
mounting and front access connection.
Internal accessories
Common internal acessories are available from the FD63/160 frame
size till the FG400/630 frame size. Taking into account
the maximum breaker content the ordering procedure just requires
a correct code selection.
The FK800, 1250 and 1600 types have equivalent accesories.
Operators
The breakers are normally supplied with an elongated toggle
operator. Other operators, as rotary handles and electrical
A operators, can be ordered seperately.
Connection options
If the standard connection options do not meet the
G requirements a wide variety of others is available.
The connection options are supplied in kit form for mounting
on one side (load or line) of a breaker and can be used for the fixed,
plug-in or draw-out version of the breaker.
X
Installation accessories
Additional requirements, as to the protection degree of the
connection area, the locking or padlocking of the breaker and
finishing of cut-outs for operators can be met by the use of these
parts.
A.2
Record Plus
Order codes
A
A.3
Record Plus
FD frame
Breaking capacities
Protection
Order codes
3 N,H
7 N,H
12.5 N,H
LTM 16 C,E S,N,H 16 N,H
Line thermal magnetic protection FD63 20 C,E S,N,H N,H,L 20 N,H
LTMD (2,3 & 25 C,E S,N,H,L N,H 25 N,H
4 pole) 30 N,H,L FD160
Selective thermal magnetic
32 C,E S,N,H,L N,H (single 32 N,H
protection 40 C,E S,N,H,L N,H pole) 40 N,H
GTM 50 C,E S,N,H,L N,H N,H,L 50 N,H
A Generator thermal magnetic 63 C,E S,N,H,L N,H 63 N,H
protection FD160 80 C,E S,N,H,L N,H N,H,L 80 N,H
Mag BreakTM (2,3 & 100 C,E S,N,H,L N,H N,H,L 100 N,H
4 pole) 125 C,E S,N,H,L N,H 125 N,H
B Magnetic Only protection
160 C,E S,N,H,L N,H 160 N,H
Y
Non Automatic or switch
Number of poles/ Number of poles/
(not mentioned in tables) protected poles protected
C (trips) poles (trips)
Accessories
F O
1 Auxiliary contact left mounted
(NO or NC)
O
2 Auxiliary contact right mounted
G O
3
(NO or NC)
Bell Alarm trip unit (NO or NC)
O
4 Bell Alarm mechanism (CO)(1)
O
5 Shunt or Undervoltage release
X O
6 Operators
Rotary Handle
Electrical Operator
O
7 RCD, side or bottom mounted(1)
(Insert indicates Bell alarm contact
mounting)
O
8 Plug in system(1)
A.4
Record Plus
FD63/160 - Complete circuit breaker
Line Thermal Magnetic LTM (fixed settings)
3 pole 3 trips 4 pole 4 trips(1)
FD frame
16 FDE36TE016ED 433649 FDE46TE016ED 433697
20 FDE36TE020ED 433651 FDE46TE020ED 433699
25 FDE36TE025ED 433653 FDE46TE025ED 433701
32 FDE36TE032ED 433655 FDE46TE032ED 433703
40 FDE36TE040ED 433657 FDE46TE040ED 433705
25kA 50 FDE36TE050ED 433659 FDE46TE050ED 433707
FDE 63 FDE36TE063ED 433661 FDE46TE063ED 433709
80 FDE36TE080GD 433663 FDE46TE080GD 433711
100 FDE36TE100GD 433665 FDE46TE100GD 433713
125 FDE36TE125GD 433667 FDE46TE125GD 433715
160 FDE36TE160GD 433669 FDE46TE160GD 433717
2 pole 2 trips
D
16 FDN66TD016ED 430143
20 FDN66TD020ED 430144
25 FDN66TD025ED 430145
32 FDN66TD032ED 430146 E
40 FDN66TD040ED 430147
50kA 50 FDN66TD050ED 430148
FDN 63 FDN66TD063ED 430149
80 FDN66TD080GD 430794
100 FDN66TD100GD 430797 F
125 FDN66TD125GD 430800
160 FDN66TD160GD 433599
One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware G
Line Thermal Magnetic LTM (fixed settings)
1 pole 1 trip(2) 1 pole 1 trip(2) X
16 FDN13TF016EF 433316 FDH13TF016EF 433246
20 FDN13TF020EF 433322 FDH13TF020EF 433255
240V 25 FDN13TF025EF 433328 240V FDH13TF025EF 433262
25kA 32 FDN13TF032EF 433334 50kA FDH13TF032EF 433268
FDN 40 FDN13TF040EF 433340 FDH FDH13TF040EF 433274
50 FDN13TF050EF 433346 FDH13TF050EF 433280
63 FDN13TF063EF 433352 FDH13TF063EF 433286
80 FDN13TF080GF 433519 FDH13TF080GF 433292
100 FDN13TF100GF 433522 FDH13TF100GF 433298
125 FDN13TF125GF 433525 FDH13TF125GF 433304
160 FDN13TF160GF 433527 FDH13TF160GF 433310
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Fixation hardware not suitable for mounting of one individual single pole breaker (see page A.10)
A.5
Record Plus
FD63/160 - Complete circuit breaker
Generator Thermal Magnetic GTM (settable thermals)
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
16 FDN36TD016ED 430100 FDN436TD016ED 430117 FDN46TD016ED 430131 - -
20 FDN36TD020ED 430101 FDN436TD020ED 430118 FDN46TD020ED 430132 - -
25 FDN36TD025ED 430102 FDN436TD025ED 430119 FDN46TD025ED 430133 - -
50kA 32 FDN36TD032ED 430103 FDN436TD032ED 430120 FDN46TD032ED 430134 - -
FDN 40 FDN36TD040ED 430104 FDN436TD040ED 430121 FDN46TD040ED 430135 - -
50 FDN36TD050ED 430105 FDN436TD050ED 430122 FDN46TD050ED 430136 - -
63 FDN36TD063ED 430106 FDN436TD063ED 430123 FDN46TD063ED 430137 FDN456TD063ED 430129
80 FDN36TD080GD 430630 FDN436TD080GD 430688 FDN46TD080GD 430752 FDN456TD080GD 430718
100 FDN36TD100GD 430633 FDN436TD100GD 430691 FDN46TD100GD 430755 FDN456TD100GD 430721
125 FDN36TD125GD 430636 FDN436TD125GD 430694 FDN46TD125GD 430758 FDN456TD125GD 430724
160 FDN36TD160GD 433572 FDN436TD160GD 433578 FDN46TD160GD 433590 FDN456TD160GD 433584
One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
B Breaker finishing covers + Fixation hardware
C 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
25 FDN36TG025ED 430107 FDN436TG025ED 430124 FDN46TG025ED 430138 - -
32 FDN36TG032ED 430108 FDN436TG032ED 430125 FDN46TG032ED 430139 - -
40 FDN36TG040ED 430109 FDN436TG040ED 430126 FDN46TG040ED 430140 - -
50 FDN36TG050ED 430110 FDN436TG050ED 430127 FDN46TG050ED 430141 - -
D 50 kA
FDN
63 FDN36TG063ED 430111 FDN436TG063ED 430128 FDN46TG063ED 430142 FDN456TG063ED 430130
80 FDN36TG080GD 430649 FDN436TG080GD 430707 FDN46TG080GD 430771 FDN456TG080GD 430729
100 FDN36TG100GD 430652 FDN436TG100GD 430710 FDN46TG100GD 430774 FDN456TG100GD 430732
125 FDN36TG125GD 430655 FDN436TG125GD 430713 FDN46TG125GD 430777 FDN456TG125GD 430735
160 FDN36TG160GD 433575 FDN436TG160GD 433581 FDN46TG160GD 433593 FDN456TG160GD 433587
E
25 FDH36TG025ED 430027 FDH436TG025ED 430044 FDH46TG025ED 430058 - -
32 FDH36TG032ED 430028 FDH436TG032ED 430045 FDH46TG032ED 430059 - -
40 FDH36TG040ED 430029 FDH436TG040ED 430046 FDH46TG040ED 430060 - -
F 50 FDH36TG050ED 430030 FDH436TG050ED 430047 FDH46TG050ED 430061 - -
63 FDH36TG063ED 430031 FDH436TG063ED 430048 FDH46TG063ED 430062 FDH456TG063ED 430050
80kA 80 FDH36TG080GD 430357 FDH436TG080GD 430415 FDH46TG080GD 430479 FDH456TG080GD 430437
FDH 100 FDH36TG100GD 430360 FDH436TG100GD 430418 FDH46TG100GD 430482 FDH456TG100GD 430440
125 FDH36TG125GD 430363 FDH436TG125GD 430421 FDH46TG125GD 430485 FDH456TG125GD 430443
G 160 FDH36TG160GD 435824 FDH436TG160GD 435830 FDH46TG160GD 435842 FDH456TG160GD 435836
One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware
X
(1) Neutral on the left. If neutral on the right is needed, please contact us.
A.6
Record Plus
FD63/160 - Complete circuit breaker
Motor Protection (Mag BreakTM) Magnetic Only Breakers
3 pole 4 pole(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
3 FDN36MC003ED 436409 FDN436MC003ED 436411
7 FDN36MC007ED 430095 FDN436MC007ED 430112
50kA 12.5 FDN36MC012ED 430096 FDN436MC012ED 430113
FDN 20 FDN36MC020ED 430097 FDN436MC020ED 430114
30 FDN36MC030ED 430098 FDN436MC030ED 430115
50 FDN36MC050ED 430099 FDN436MC050ED 430116
80 FDN36MC080GD 430610 FDN436MC080GD 430668
100 FDN36MC100GD 430613 FDN436MC100GD 430671
FD frame
FDH 30 FDH36MC030ED 430018 FDH436MC030ED 430035
50 FDH36MC050ED 430019 FDH436MC050ED 430036
80 FDH36MC080GD 430318 FDH436MC080GD 430376
100 FDH36MC100GD 430321 FDH436MC100GD 430379
One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware + IPXXB covers (Finger protection on connection clamps)
A
Complete Non-Automatic Circuit Breaker (Switch)
In (A) 3 pole 4 pole(1)
63 FDY306D063ED 430150 FDY406D063ED 430151
B
FDY 160 FDY306D160GD 430805 FDY406D160GD 430810
One code covers: A standard fixed front connection breaker + DIN-Rail mounting kit + Toggle elongator +
Breaker finishing covers + Fixation hardware C
(1) Neutral on the left. If neutral on the right is needed, please contact us.
D
A.7
Record Plus
FD - Internal accessories
Normally open Normally closed Changeover
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FD - Operators
Electrical operators 24V AC/DC FDEMFD 430926
48V AC/DC FDEMFF 430929
60V AC/DC FDEMFH 430932
110V AC/DC FDEMFJ 430935
220/250V AC/DC FDEMFN 430938
400/440V AC FDEMF8 430920
One code covers an RCD with: Sealable connection cover (cut-out adaptor FDUF)
(1) Not for all FDC and FDE types (4) On request 1xNO/1xNC is available.
(2) Key included (5) Not possible on FDC and FDE types with TF and TC trip unit.
(3) Add door flange FDFH to allow use of the door interlock options 100/200V AC rating available on request
A.8
Record Plus
FD - Plug-in system(1)
3 pole 4 pole
Main system
complete Cat. no. Ref. no. Cat. no. Ref. no.
Fixed part for breaker & RCD FDDFQ3 433489 FDDFQ4 433492
Mobile part for breaker & RCD FDDMP3 430905 FDDMP4 430908
Fixed Mobile Complete set: Fixed and mobile part with connection and fixation hardware
Fixed part: Fixed base with connection and fixation and hardware
Mobile part: Mechanism trip device, terminal shields and set of 3 or 4 pole plugs
FD frame
Insertion prevention kit Insertion prevention kit
(of ….wrong A rating) FAPIP 430825
FD - Connections: Optional(4)
3 pole 4 pole
Extenders
Standard flat type (a) FDBES3 430887 FDBES4 430888
Heightened type (b) FDBEH3 430885 FDBEH4 430886
Twisted 90° (c) FDBEA3 430883 FDBEA4 430884
(a) (b) (c)
FD - Installation accessories
3 pole 4 pole E
Terminal shields
(with finishing covers) Long, set of 2 pcs. FDJL3 430951 FDJL4 430954
X
Covers Cutout adaptor, Breaker + Trip unit FDUF3 430830 FDUF4 430832
(1) Plug-in system max. 125A. (4) Set for equipping the line OR load side of breaker.
(2) Only necessary when internal accessories or an electrical (5) Supplied with mag. break types.
operator are used.
(3) External box clamps are always delivered with standard extender
A.9
Record Plus
FD - Installation accessories (continued)
Padlocking devices for Cat. no. Ref. no. Cat. no. Ref. no.
toggle operator(1)
Padlocking removable FD1PR 430879
Heightning set for Length = (18 mod. of 18 mm) 354 mm FDKE 617947
Redline/ElfaPlus MCB's
A Door Flanges
Breaker front face and RCD FDFF3
3 pole
430941 FDFF4
4 pole
430942
Rotary handle (through cover plate model) FDFH 430829 - -
D
(1) Padlocks not included
(2) Supplied with breakers, not with all FDC and FDE types
E
A.10
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FD frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.11
Record Plus
FE Frame
Breaking capacities
Icu 400/415V AC in kA eff.
Type V N H L
FE160 50 80 150
FE250 36 50 80 150
Protection
3 N, H, L
7 N, H, L
12.5 N, H, L
20 N, H, L
25 N, H, L N, H, L
30 N, H, L
32 N, H, L
LTM
FE160 40 N, H, L
Line thermal magnetic protection 50 N, H, L N, H, L
LTMD 63 N, H, L N, H, L
Selective thermal magnetic 80 N, H, L N, H, L
protection 100 N, H, L N, H, L N, H, L N, H, L
GTM 125 N, H, L N, H, L N, H, L N, H, L N, H, L
A Generator thermal magnetic 160 N, H, L N, H, L N, H, L N, H, L N, H, L
125 N, H, L N, H, L
protection
FE250 160 V N, H, L N, H, L N, H, L N, H, L
Mag BreakTM 200 V N, H, L N, H, L N, H, L
B Magnetic Only protection 250 V N, H, L N, H, L N, H, L N, H, L
SMR1
Selective electronic trip unit
Number of poles/
Y protected poles
C Non Automatic or switch (trips)
(not mentioned in tables)
3 pole 3 trips V, N, H, L N, H, L N, H N, H, L N, H, L
4 pole 3 trips N, H, L N, H, L N, H N, H, L N, H, L
D 4 pole 4 trips V, N, H, L N, H, L N, H N, H, L
4 pole 3.5 trips N, H, L N, H, L N, H N, H, L
(N=50%)(1)
(1) Rated current ≥ 63A
E
Accessories (main types)
F O
1 Auxiliary contact left mounted
(NO or NC) 1 or 2pcs.
O
2 Auxiliary contact right mounted
G O
3
(NO or NC) 1 or 2pcs.
Bell Alarm thermal magnetic trip unit
(NO or NC)
O
3 a Bell Alarm electronic trip unit (NO or NC)
X O
4 Bell Alarm mechanism (NO or NC)
O
5 Shunt or Undervoltage release
O
5 a Actuator for electronic trip unit .
O
6 Operators
Rotary handle
Electrical operator
O
7 Bottom mounted RCD (below trip unit)
(Insert indicates Bell alarm contact mounting)
O
8 Plug-in or draw-out system
A.12
Record Plus
FE160 - Complete circuit breaker
Line Thermal Magnetic LTM (adjustable settings)
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FE frame
100 FEH36TA100JF 431171 FEH436TA100JF 431258 FEH46TA100JF 431369 FEH456TA100JF 431306
125 FEH36TA125JF 431177 FEH436TA125JF 431264 FEH46TA125JF 431375 FEH456TA125JF 431312
160 FEH36TA160JF 431183 FEH436TA160JF 431270 FEH46TA160JF 431381 FEH456TA160JF 431318
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware A
Selective Thermal Magnetic LTMD (adjustable settings)
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 100 FEN36TD100JF 432945 FEN436TD100JF 432994 FEN46TD100JF 433061 FEN456TD100JF 433028
B
FEN 125 FEN36TD125JF 432953 FEN436TD125JF 433001 FEN46TD125JF 433067 FEN456TD125JF 433034
160 FEN36TD160JF 432971 FEN436TD160JF 433007 FEN46TD160JF 433073 FEN456TD160JF 433040
150 kA 100 FEL36TD100JF 432332 FEL436TD100JF 432374 FEL46TD100JF 432907 FEL456TD100JF 432699
D
FEL 125 FEL36TD125JF 432341 FEL436TD125JF 432573 FEL46TD125JF 432921 FEL456TD125JF 432747
160 FEL36TD160JF 432349 FEL436TD160JF 432585 FEL46TD160JF 432927 FEL456TD160JF 432834
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware E
F
Generator Thermal Magnetic GTM
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 100 FEN36TG100JF 435139 FEN436TG100JF 436014 FEN46TG100JF 435250 FEN456TG100JF 436020 G
FEN 125 FEN36TG125JF 435142 FEN436TG125JF 436015 FEN46TG125JF 435253 FEN456TG125JF 436021
160 FEN36TG160JF 435148 FEN436TG160JF 436016 FEN46TG160JF 435259 FEN456TG160JF 436022
150 kA 100 FEL36TG100JF 435923 FEL436TG100JF 435944 FEL46TG100JF 435992 FEL456TG100JF 435962
FEL 125 FEL36TG125JF 435926 FEL436TG125JF 435947 FEL46TG125JF 435995 FEL456TG125JF 435965
160 FEL36TG160JF 435932 FEL436TG160JF 435950 FEL46TG160JF 436002 FEL456TG160JF 435968
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware
(1) Neutral on the left. If neutral on the right is needed, please contact us.
A.13
Record Plus
FE160 - Complete circuit breaker
Motor protection (Mag BreakTM) Magnetic Only Breaker(2)
3 pole 3 trips 4 pole 3 trips(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
3 FEN36MC003JF 436365 - -
7 FEN36MC007JF 435073 - -
50kA 12.5 FEN36MC012JF 435076 - -
FEN 20 FEN36MC020JF 435079 - -
30 FEN36MC030JF 435082 - -
50 FEN36MC050JF 435085 FEN436MC050JF 435160
80 FEN36MC080JF 435899 - -
100 FEN36MC100JF 435088 FEN436MC100JF 435163
125 FEN36MC125JF 436335 FEN436MC125JF 436356
160 FEN36MC160JF 435094 FEN436MC160JF 435169
3 FEH36MC003JF 436361 - -
7 FEH36MC007JF 434742 - -
Order codes
3 FEL36MC003JF 436363 - -
7 FEL36MC007JF 434940 - -
12.5 FEL36MC012JF 434943 - -
20 FEL36MC020JF 434946 - -
30 FEL36MC030JF 434949 - -
150kA 50 FEL36MC050JF 434952 FEL436MC050JF 434994
FEL 80 FEL36MC080JF 435896 - -
100 FEL36MC100JF 434955 FEL436MC100JF 434997
A 125
160
FEL36MC125JF
FEL36MC160JF
436331
434961
FEL436MC125JF
FEL436MC160JF
436333
435004
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware
D
25 FEH36AA025JBF 435857 FEH46AA025JBF 435863
63 FEH36AA063JEF 435860 FEH46AA063JEF 435866
80 kA 125 FEH36AA125JGF 431112 FEH46AA125JGF 431201
E FEH 160 FEH36AA160JJF 431117 FEH46AA160JJF 431204
160A 100 FERJ3J0100 432189 FERJ43J0100 432225 FERJ4J0100 432291 FERJ45J0100 432255
160 FERJ3J0160 432195 FERJ43J0160 432231 FERJ4J0160 432297 FERJ45J0160 432261
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) All 3 and 7Amp FE size magnetic only breaker types have a breaking capacity at 690 Volt of 10kA.
A.14
Record Plus
FE160 - Complete circuit breaker
Ir 0.4: 1xIn Switchable Rating Plugs for Trip Units SMR1
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
125A 125 FERS3G0125 432318 FERS43G0125 432336 FERS4G0125 432369 FERS45G0125 432351
160A 160 FERS3J0160 432321 FERS43J0160 432339 FERS4J0160 432372 FERS45J0160 432354
50 kA
FEN
FE frame
125 FEH36SA125JGF 431138 FEH436SA125JGF 431225 FEH46SA125JGF 431336 FEH456SA125JGF 431285
160 FEH36SA160JJF 431141 FEH436SA160JJF 431228 FEH46SA160JJF 431339 FEH456SA160JJF 431288
80 kA
FEH
A
125 FEL36SA125JGF 431431 FEL436SA125JGF 431518 FEL46SA125JGF 431629 FEL456SA125JGF 431578
160 FEL36SA160JJF 431434 FEL436SA160JJF 431521 FEL46SA160JJF 431632 FEL456SA160JJF 431581
150 kA
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware B
FEL
FEY One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware E
F
(1) Neutral on the left. If neutral on the right is needed, please contact us
A.15
Record Plus
FE250 - Complete circuit breaker
Line Thermal Magnetic LTM (adjustable settings)
3 pole 3 trips 4 pole 4 trips(1)
One code covers: A standard fixed front connection breaker + Fixation hardware
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware
E
Motor protection (Mag BreakTM) Magnetic Only Breaker
In (A) 3 pole 3 trips 4 pole 3 trips(1)
F 50kA 160 FEN36MC160KF 435097 FEN436MC160KF 435172
FEN 200 FEN36MC200KF 436764 FEN436MC200KF 436765
250 FEN36MC250KF 435100 FEN436MC250KF 435175
G
160 FEH36MC160KF 434766 FEH436MC160KF 434841
80kA 200 FEH36MC200KF 436754 FEH436MC200KF 436755
FEH 250 FEH36MC250KF 434769 FEH436MC250KF 434844
X
160 FEL36MC160KF 434964 FEL436MC160KF 435007
200 FEL36MC200KF 436756 FEL436MC200KF 436763
150kA 250 FEL36MC250KF 434967 FEL436MC250KF 435010
FEL
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware
(1) Neutral on the left. If neutral on the right is needed, please contact us.
A.16
Record Plus
FE250 - Complete circuit breaker
Selective Electronic Trip Unit (SMR1) without Rating Plug
3 pole 4 pole(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50 kA
FEN 125 FEN36AA125KGF 431920 FEN46AA125KGF 431938
160 FEN36AA160KJF 431706 FEN46AA160KJF 431793
250 FEN36AA250KKF 431709 FEN46AA250KKF 431796
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware
FE frame
Ir 0.625: 1xIn Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
125A 80 FERJ3G0080 432186 FERJ43G0080 432222 FERJ4G0080 432288 FERJ45G0080 432252
125 FERJ3G0125 432192 FERJ43G0125 432228 FERJ4G0125 432294 FERJ45G0125 432258
160A 100 FERJ3J0100 432189 FERJ43J0100 432225 FERJ4J0100 432291 FERJ45J0100 432255
160 FERJ3J0160 432195 FERJ43J0160 432231 FERJ4J0160 432297 FERJ45J0160 432261
250A 160 FERJ3K0160 432204 FERJ43K0160 432240 FERJ4K0160 432306 FERJ45K0160 432270
250 FERJ3K0250 432207 FERJ43K0250 432243 FERJ4K0250 432309 FERJ45K0250 432273
250A 250 FERS3K0250 432327 FERS43K0250 432345 FERS4K0250 432378 FERS45K0250 432360 B
Selective Electronic Trip Unit (SMR1) with Switchable Rating Plug
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50 kA 160 FEN36SA160KJF 431730 FEN436SA160KJF 431817 FEN46SA160KJF 431928 FEN456SA160KJF 431877
C
FEN 250 FEN36SA250KKF 431733 FEN436SA250KKF 431820 FEN46SA250KKF 431931 FEN456SA250KKF 431880
D
160 FEH36SA160KJF 431144 FEH436SA160KJF 431231 FEH46SA160KJF 431342 FEH456SA160KJF 431291
250 FEH36SA250KKF 431147 FEH436SA250KKF 431234 FEH46SA250KKF 431345 FEH456SA250KKF 431294
80 kA
FEH E
G
Complete Non-Automatic Circuit Breaker (Switch)
In (A) 3 pole 4 pole(1)
X
FEY 250 FEY306D250KF 431991 FEY406D250KF 431997
One code covers: A standard fixed front connection breaker + Toggle elongator + Breaker finishing covers + Fixation hardware
(1) Neutral on the left. If neutral on the right is needed, please contact us
A.17
Record Plus
FE160 - Circuit breaker in components
Breaker frames: Without trip unit
3 pole 4 pole
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FEN
160 FEN306F160JF 431712 FEN406F160JF 431799
80kA
FEH 160 FEH306F160JF 431126 FEH406F160JF 431213
Trip units: Mag BreakTM, Magnetic only type for motor protection
C In (A) 3 pole 3 trips 4 pole 3 trips(1)
12.5 FETMC3J0012 432495 - -
20 FETMC3J0020 432498 - -
30 FETMC3J0030 434736 - -
D MC 50
80
FETMC3J0050
FETMC3J0080
432501
436078
FETMC43J0050
-
432528
-
100 FETMC3J0100 432504 FETMC43J0100 432531
125 FETMC3J0125 436358 FETMC43J0125 436359
160 FETMC3J0160 432510 FETMC43J0160 432537
E
Trip units: Selective Electronic type without Rating Plug
In (A) 3 pole 4 pole(1)
F 25 FETAA3J0025 432414 FETAA4J0025 432432
SMR1 63 FETAA3J0063 432417 FETAA4J0063 432435
125 FETAA3J0125 432420 FETAA4J0125 432438
160 FETAA3J0160 432423 FETAA4J0160 432441
A.18
Record Plus
FE250 - Circuit breaker in components
Breaker frames: Without trip unit
3 pole 4 pole
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FEN
250 FEN306F250KF 431715 FEN406F250KF 431802
80kA
FEH 250 FEH306F250KF 431129 FEH406F250KF 431216
FE frame
200 FETTD3K0200 433191 FETTD43K0200 433222 FETTD4K0200 433290 FETTD45K0200 433260
250 FETTD3K0250 433195 FETTD43K0250 433225 FETTD4K0250 433293 FETTD45K0250 433263
Trip units: Mag BreakTM, Magnetic only type for motor protection
In (A) 3 pole 3 trips 4 pole 3 trips(1)
MC 160
200
FETMC3K0160
FETMC3K0200
432513
436778
FETMC43K0160
FETMC43K0200
432540
436779
A
250 FETMC3K0250 432516 FETMC43K0250 432543
(1) Neutral on the left. If neutral on the right is needed, please contact us.
E
A.19
Record Plus
FE - Internal accessories
Normally open Normally closed
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FE - Operators
Electrical operators 24V AC/DC FEEMFD 432052
48V AC/DC FEEMFF 432055
60V AC/DC FEEMFH 432058
110/130V AC/DC FEEMFJ 432061
220/250V AC/DC FEEMFN 432064
400/440V AC FEEMF8 435812
Flex oper. adaptor push to trip, set of 2 pcs. (a) FENFT 433531 Only for use with panel or door mounted type
Extension shaft kit (max. 600 mm) (b) FDNRE 430986 Only for use with panel or door mounted type
D (a) (b)
Side-by-side installation adapter kit (c) FENR4 432099 Not for use with panel or door mounted type
One code covers an RCD with: Fixation hardware + Sealable interconnection cover
A.20
Record Plus
FE - Plug-in system
3 pole 4 pole
Main system
Cat. no. Ref. no. Cat. no. Ref. no.
FE frame
(of ….wrong A rating)
Spares Set of nutplates and connection bolts FEJN3 436467 FEJN4 436468
(For connection of bases used as spare)
FE - Drawout system
Main system 3 pole 4 pole
Complete set FEWS3 432168 FEWS4 432171
One code covers the fixed and withdrawable part of the draw-out system, with plug-in base, mounting accessories and fixation hardware
A
B
Accessories (for auxiliary Keylock in draw-out position Ronis(1) (a) FE1BRW 432188
disconnects see plug-in system) Keylock in draw-out pos. Profalux(1) (b) FE1BPW 432184
FE - Connections: Optional
D
3 pole 4 pole
Extenders(3)
Standard flat type (a) FEBES3 432026 FEBES4 432027
Heightened type (b) FEBEH3 432024 FEBEH4 432025 E
Twisted 90° (c) FEBEA3 432022 FEBEA4 432023
(a) (b) (c) (d) (e) Angled 45° (d) FEBE43 432018 FEBE44 432019
Angled 90° (e) FEBE93 432020 FEBE94 432021
F
Spreader flat(3) Pole spacing 45mm FEBSS3 432032 FEBSS4 432033
Internal box
2.5 - 95mm2 16 - 150mm2 X
clamps Box Clamp Cu/Al, set 3 pole FETCA1316 432156 FETCA1320 432157
(3) Box Clamp Cu/Al, set 4 pole FETCA1416 432158 FETCA1420 432159
70 - 185mm2
External
box clamps Box Clamp Cu/Al, set 3 pole(2) FETCA1323 432160
(3) Box Clamp Cu/Al, set 4 pole(2) FETCA1423 432161
Covers Cutout filler for cover plate (64 mm), FBF6 883970
length of 1.2 m
Order codes
(b)
(a)
A
3 pole 4 pole
Door flanges
B Breaker front face FEFF3 432067 FEFF4 432068
3 pole 4 pole
D Spare parts
Finishing covers, set of 2 pcs.(2) FEUA3 432162 FEUA4 432163
(c)
A.22
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FE frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.23
Record Plus
FG Frame
Breaking capacities
Protection
A
250 N, H, L N, H, L N, H, L
FG400 350 N, H, L N, H, L N, H, L
400 N, H, L N, H, L -
400 N, H, L N, H, L -
FG630 500 N, H, L N, H, L N, H, L
630 N, H, L N, H, L -
LTM(1)
Line thermal magnetic protection
SMR1 Number of poles /
Selective electronic protection. protected poles (trips)
SMR2
3 pole 3 trips N, H, L N, H, L N, H, L
Modular electronic protection with
A enhanced functionality
4 pole 3 trips N, H, L N, H, L N, H, L
4 pole 4 trips N, H, L N, H, L
Mag BreakTM 4 pole 3.5 trips (N=50%) N, H, L N, H, L
Magnetic Only protection
B Y
Non Automatic or switch
(not mentioned in tables)
C
(1) Consult us for availability
F O
1 Auxiliary contact left mounted
(NO or NC) 1, 2 or 3pcs.
O
2 Auxiliary contact right mounted
G O
3
(NO or NC) 1 or 2pcs.
Bell Alarm thermal magnetic trip unit
(NO or NC)
O
3 a Bell Alarm electronic trip unit (NO or NC)
X O
4 Bell Alarm mechanism (NO or NC)
O
5 Shunt or Undervoltage release
O
5 a Actuator for electronic trip unit .
O
6 Operators
Rotary handle
Electrical operator
O
7 Bottom mounted RCD (below trip unit)
(Insert indicates Bell alarm contact mounting)
Bottom mounted version is also available. 6
O
8 Plug in or draw out system
A.24
Record Plus
FG400 - Complete circuit breaker
Selective Electronic Trip Unit (SMR1) without Rating Plug
3 pole 4 pole(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 250 FGN36AA250LKF 434248 FGN46AA250LKF 434253
400 FGN36AA400LLF 431455 FGN46AA400LLF 431536
FG frame
150kA
FGL
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRJ3LK0160 434337 FGRJ43LK0160 434345 FGRJ4LK0160 434361 FGRJ45LK0160 434353
250 FGRJ3LK0250 434341 FGRJ43LK0250 434349 FGRJ4LK0250 434365 FGRJ45LK0250 434357
400A 250 FGRJ3LL0250 435343 FGRJ43LL0250 435356 FGRJ4LL0250 435397 FGRJ45LL0250 435367
400 FGRJ3LL0400 433151 FGRJ43LL0400 433163 FGRJ4LL0400 433187 FGRJ45LL0400 433175
Type line/Motor
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
A
3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 250 FGRS3LK0250 434303 FGRS43LK0250 434307 FGRS4LK0250 434315 FGRS45LK0250 434311
400A 400 FGRS3LL0400 435435 FGRS43LL0400 434516 FGRS4LL0400 434537 FGRS45LL0400 434525 B
Selective Electronic Trip Unit (SMR1) with switchable Rating Plug
50kA
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1) C
FGN 250 FGN36SA250LKF 434249 FGN436SA250LKF 434251 FGN46SA250LKF 434254 FGN456SA250LKF 434252
400 FGN36SA400LLF 434489 FGN436SA400LLF 435277 FGN46SA400LLF 435280 FGN456SA400LLF 434504
80kA 250 FGH36SA250LKF 434233 FGH436SA250LKF 434235 FGH46SA250LKF 434238 FGH456SA250LKF 434236
D
FGH 400 FGH36SA400LLF 434399 FGH436SA400LLF 434408 FGH46SA400LLF 434426 FGH456SA400LLF 434414
X
400 FGL36BM400LLF 434675 FGL436BM400LLF 434681
150kA
FGL One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator + Rating plug +
Breaker finishing covers + Fixation hardware
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for use with switchable rating plug only.
A.25
Record Plus
FG400 - Complete circuit breaker
Modular Electronic Trip Unit (SMR2) without Rating Plug
3 pole 4 pole(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 250 FGN36KA250LKF 434073 FGN46KA250LKF 436159
350(2) FGN36KA350LLF 434483 FGN46KA350LLF 434510
400 FGN36KA400LLF 436156 FGN46KA400LLF 436160
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Filller for extension module and battery socket + Breaker finishing covers + Fixation hardware
LT: Ir = 0.625-1 x In
LTD: Line & Motor; 8 options Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRL3LK0160 436162 FGRL43LK0160 434101 FGRL4LK0160 434109 FGRL45LK0160 434105
250 FGRL3LK0250 434098 FGRL43LK0250 436177 FGRL4LK0250 436181 FGRL45LK0250 434106
400A 250 FGRL3LL0250 435399 FGRL43LL0250 435410 FGRL4LL0250 435433 FGRL45LL0250 434495
400 FGRL3LL0400 434099 FGRL43LL0400 436178 FGRL4LL0400 434111 FGRL45LL0400 434107
350(2)
350(2) FGRL3LL0350 435400 FGRL43LL0350 435412 FGRL4LL0350 435302 FGRL45LL0350 435266
Modular Electronic Trip Unit (SMR2) with two adjustable Rating Plugs, setting 0.4 - 1 x In
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50kA
A FGN 400 FGN36VA400LLF 435140 FGN436VA400LLF 435152 FGN46VA400LLF 435170 FGN456VA400LLF 435164
80kA
FGH 400 FGH36VA400LLF 434953 FGH436VA400LLF 434960 FGH46VA400LLF 434983 FGH456VA400LLF 434971
Other Modules
G
External communication and contact module (4 contacts, 1A/400V)(3) FAMECM 434013
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle elongator +
Breaker finishing covers + Fixation hardware
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for Motor Protection
(3) Is needed for Modbus communication (1 per breaker).
A.26
Record Plus
FG630 - Complete circuit breaker
Selective Electronic Trip Unit (SMR1) without Rating Plug
3 pole 4 pole(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 400 FGN36AA400NLF 434561 FGN46AA400NLF 434636
500(2) FGN36AA500NNF 434812 FGN46AA500NNF 434866
630 FGN36AA630NNF 431461 FGN46AA630NNF 431539
FG frame
Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRJ3NL0250 433148 FGRJ43NL0250 433160 FGRJ4NL0250 433184 FGRJ45NL0250 433172
400 FGRJ3NL0400 435182 FGRJ43NL0400 435188 FGRJ4NL0400 435200 FGRJ45NL0400 435194
630A 400 FGRJ3NN0400 433154 FGRJ43NN0400 433166 FGRJ4NN0400 433190 FGRJ45NN0400 433178
630 FGRJ3NN0630 433157 FGRJ43NN0630 433169 FGRJ4NN0630 433193 FGRJ45NN0630 433181
Type line/Motor
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 400 FGRS3NL0400 433235 FGRS43NL0400 433241 FGRS4NL0400 433253 FGRS45NL0400 433247
500(2) 500 FGRS3NN0500 434512 FGRS43NN0500 434521 FGRS4NN0500 434542 FGRS45NN0500 434530 A
Selective Electronic Trip Unit (SMR1) with Rating Plug, without Overload (LT) protection (Motor)
In (A) 3 pole 3 trips 4 pole 3 trips(1) F
50kA
FGN 500 FGN36BM500NNF 434690 FGN436BM500NNF 434696
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for use with Switchable Rating Plug only.
A.27
Record Plus
FG630 - Complete circuit breaker
Modular Electronic Trip Unit (SMR2) without Rating Plug
3 pole 4 pole(1)
In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
50kA
FGN 400 FGN36KA400NLF 436157 FGN46KA400NLF 436161
500(2) FGN36KA500NNF 434824 FGN46KA500NNF 434872
630 FGN36KA630NNF 436158 FGN46KA630NNF 434092
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Filller for extension module and battery socket + Breaker finishing covers + Fixation hardware
LT: Ir = 0.625-1 x In
LTD: Line & Motor; 8 options Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRL3NL0250 435206 FGRL43NL0250 435218 FGRL4NL0250 435254 FGRL45NL0250 435230
400 FGRL3NL0400 435212 FGRL43NL0400 435224 FGRL4NL0400 435260 FGRL45NL0400 435236
630A 400 FGRL3NN0400 434471 FGRL43NN0400 435419 FGRL4NN0400 434501 FGRL45NN0400 434497
630 FGRL3NN0630 434100 FGRL43NN0630 436179 FGRL4NN0630 434112 FGRL45NN0630 436180
500(2)
500(2) FGRL3NN0500 434473 FGRL43NN0500 435427 FGRL4NN0500 435309 FGRL45NN0500 435272
Modular ElectronicTrip Unit (SMR2) with two Adjustable Rating Plugs, setting 0.4 - 1 x In
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
50kA
A FGN 630 FGN36VA630NNF 435146 FGN436VA630NNF 435158 FGN46VA630NNF 435176 FGN456VA630NNF 435167
80kA
FGH 630 FGH36VA630NNF 434958 FGH436VA630NNF 434965 FGH46VA630NNF 435003 FGH456VA630NNF 434977
Other Modules
G
External communication and contact module (4 contacts, 1 A/400V)(3) FAMECM 434013
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) Specifically configured for Motor Protection.
(3) Is needed for Modbus communication (1 per breaker).
A.28
Record Plus
FG400 - Circuit breaker in components
Breaker frame without Trip Unit
3 pole 4 pole(1)
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FGN
250 FGN306F250LF 434247 FGN406F250LF 434250
400 FGN306F400LF 431473 FGN406F400LF 431548
FG frame
3 pole 4 pole(1) Long time protection Adj. Ir= 0.4 - 1 x In
Two long time delay bands Line, no phase loss protection
250 FGTAA3L0250 434319 FGTAA4L0250 434323 (with choice of protection mode) Motor with phase loss protection
SMR1 400 FGTAA3L0400 431718 FGTAA4L0400 431742 Short time protection Adj. 2 - 13 x Ir (current dependant
delay) (2)
Instantaneous protection Fixed 14 x Is (2)
Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRJ3LK0160 434337 FGRJ43LK0160 434345 FGRJ4LK0160 434361 FGRJ45LK0160 434353
250 FGRJ3LK0250 434341 FGRJ43LK0250 434349 FGRJ4LK0250 434365 FGRJ45LK0250 434357
400A 250 FGRJ3LL0250 435343 FGRJ43LL0250 435356 FGRJ4LL0250 435397 FGRJ45LL0250 435367
400 FGRJ3LL0400 433151 FGRJ43LL0400 433163 FGRJ4LL0400 433187 FGRJ45LL0400 433175
Type line/Motor
A
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A
400
250
350
FGRS3LK0250
FGRS3LL0400
434303
435435
FGRS43LK0250
FGRS43LL0400
434307
434516
FGRS4LK0250
FGRS4LL0400
434315
434537
FGRS45LK0250
FGRS45LL0400
434311
434525
B
LT: Ir = 0.625-1 x In
Instantaneous protection
E
LTD: Line & Motor; 8 options Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
In (A) 3 pole 3 trips 4 pole 3 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
250A 160 FGRL3LK0160 436162 FGRL43LK0160 434101 FGRL4LK0160 434109 FGRL45LK0160 434105 F
250 FGRL3LK0250 434098 FGRL43LK0250 436177 FGRL4LK0250 436181 FGRL45LK0250 434106
400A 250 FGRL3LL0250 435399 FGRL43LL0250 435410 FGRL4LL0250 435433 FGRL45LL0250 434495
400 FGRL3LL0400 434099 FGRL43LL0400 436178 FGRL4LL0400 434111 FGRL45LL0400 434107
350A(3) 350 FGRL3LL0350 435400 FGRL43LL0350 435412 FGRL4LL0350 435302 FGRL45LL0350 435266 G
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) 400A trip unit limited to 5 LTD band settings(SMR2), a maximum ST setting of 10 x Ir and a maximum instantaneous setting of 11 x Is.
(3) Specifically configured for Motor Protection X
A.29
Record Plus
FG630 - Circuit breaker in components
Breaker frame without Trip Unit
3 pole 4 pole(1)
50kA In (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FGN
400 FGN306F400NF 431488 FGN406F400NF 431554
630 FGN306F630NF 431491 FGN406F630NF 431560
Type line 0.625 - 1 x In Adjustable Rating Plugs for Trip Units SMR1
In (A) 3 pole 3 trips 4 pole(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRJ3NL0250 433148 FGRJ43NL0250 433160 FGRJ4NL0250 433184 FGRJ45NL0250 433172
400 FGRJ3NL0400 435182 FGRJ43NL0400 435188 FGRJ4NL0400 435200 FGRJ45NL0400 435194
630A 400 FGRJ3NN0400 433154 FGRJ43NN0400 433166 FGRJ4NN0400 433190 FGRJ45NN0400 433178
630 FGRJ3NN0630 433157 FGRJ43NN0630 433169 FGRJ4NN0630 433193 FGRJ45NN0630 433181
Type line/Motor
0.4 - 1 x In Switchable Rating Plugs for Trip Units SMR1
A In (A) 3 pole 3 trips 4 pole(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 400 FGRS3NL0400 433235 FGRS43NL0400 433241 FGRS4NL0400 433253 FGRS45NL0400 433247
500(3) 500 FGRS3NN0500 434512 FGRS43NN0500 434521 FGRS4NN0500 434542 FGRS45NN0500 434530
B
Modular Electronic Trip Unit (SMR2) without Rating Plug
3 pole 4 pole 3 trips(1) 4 for line, no phase loss protection Adj. Ir= 0.4 - 1 x In
Six long time delay bands 4 for line, no phase loss protection
C 400 FGTKA3N0400 434203 FGTKA4N0400 434263 2 for motor, with phase loss
protection(2)
SMR2 500(3) FGTKA3N0500 434905 FGTKA4N0500 434911 Short time protection Adj. 1.5-12 x Ir(2)
630(2) FGTKA3N0630 434204 FGTKA4N0630 434265 Switchable to I2 t curve
Five short time delay bands From 40 to 410 milliseconds
Instantaneous protection Adj. 2-13 x Is(2)
D LT: Ir = 0.625-1 x In
Adjustable LT & LTD settable Rating Plugs for Trip Units SMR2
LTD: Line & Motor; 8 options
In (A) 3 pole 3 trips 4 pole 4 trips(1) 4 pole 4 trips(1) 4 pole 3.5 trips (N=50%)(1)
400A 250 FGRL3NL0250 435206 FGRL43NL0250 435218 FGRL4NL0250 435254 FGRL45NL0250 435230
E 400 FGRL3NL0400 435212 FGRL43NL0400 435224 FGRL4NL0400 435260 FGRL45NL0400 435236
630A 400 FGRL3NN0400 434471 FGRL43NN0400 435419 FGRL4NN0400 434501 FGRL45NN0400 434497
630 FGRL3NN0630 434100 FGRL43NN0630 436179 FGRL4NN0630 434112 FGRL45NN0630 436180
F 500(3) 500 FGRL3NN0500 434473 FGRL43NN0500 435427 FGRL4NN0500 435309 FGRL45NN0500 435272
Other Modules
SMR2 External communication and contact module (4 contacts, 1A/400V)(4) FAMECM 434013
One code covers: Module and connection hardware
(1) Neutral on the left. If neutral on the right is needed, please contact us.
(2) 630A trip unit limited to 5 LTD band settings(SMR2), a maximum ST setting of 10 x Ir and a maximum instantaneous setting of 11 x Is.
A.30 (3)
(4)
Specifically configured for Motor Protection
Is needed for Modbus communication (1 per breaker).
Record Plus
FG - Internal accessories
Normally open Normally closed
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FG frame
FG - Operators
Electrical operators 24V AC/DC FGEMFD 432817
48V AC/DC FGEMFF 432820
60V AC/DC FGEMFH 432823
110/127V AC/DC FGEMFJ 432826
220/250V AC/DC FGEMFN 432829
400/440V AC FGEMF8 432811
Grey
Red
-
-
-
-
-
-
-
-
FGNRD/5
FGNRDV/5
436506
436507
B
Grey + Early closing Aux. Switches 2xNO(4) - - - - FGNRZ/5 436515
Red + Early closing Aux. Switches 2xNO(4) - - - - FGNRZV/5 436516
Accessories C
Flex operator adaptor push to trip (a) FGNFT 432867 Only for use with panel or door mounted type
(a) (b)
Extension shaft kit (max. 600 mm) (b) FGNRE 434735 Only for use with panel or door mounted type
One code covers an RCD with: Fixation hardware + Sealable interconnection cover
A.31
Record Plus
FG - Plug-in system
3 pole 4 pole
Main system
Cat. no. Ref. no. Cat. no. Ref. no.
Complete set: Fixed and mobile part with connection and fixation hardware
Fixed part: Fixed base with connection and fixation and hardware
Mobile part: Mechanism trip device, terminal shields and set of 3 or 4 pole plugs
Spares Set of nutplates and connection bolts FGJN3 436469 FGJN4 436470
(For connection of bases used as spare)
FG - Drawout system
Main system 3 pole 4 pole
Complete set FGWS3 432910 FGWS4 432913
One code covers the fixed and withdrawable part of the draw-out system, with plug-in base, mounting accessories and fixation hardware.
B
Accessories (for Keylock in draw-out position Ronis(1) (a) FG1BRW 433407
auxiliary disconnects Keylock in draw-out position Profalux(1) (b) FG1BPW 433406
see plug-in system)
C Position indication contact NO (c) FAS01D 436309
Position indication contact NC (c) FAS10D 436310
Rear connections(2) Set 3 pole (2 short, 1 long) FGBRC3 431701 FGBRC4 431702
X Set 4 pole (2 short, 2 long)
Set 3 pole (3 short) FGBRCS3 432193 FGBRCS4 432194
Set 4 pole (4 short)
A.32
Record Plus
FG - Installation accessories
3 pole 4 pole
Terminal shields
(with finishing covers) Cat. no. Ref. no. Cat. no. Ref. no.
Long and widened type for spreaders FGJW3 432861 FGJW4 432864
and 690V applications, set of 2 pcs
FG frame
(a)
(b)
3 pole
Door flanges
RCD unit front face for 3 and 4 pole FDFF3 430941
Front face toggle area FGFT 432836
Rotary handle (through cover plate model)
Motor operator
FGFH
FGFE
430545
430544
A
Spare parts
3 pole 4 pole B
Finishing covers, set of 2 pcs. FGUA3 432908 FGUA4 432909
(b)
E
Long time module (SMR1 only) (c) FAMLT1 433376
(c) G
Ground Fault SMR2 Sensor 250A (d) FGGS0250 431870
A.33
Record Plus
FK Frame
Breaking capacities
Protection
FK800 630 N, H, L
800 N, H, L N, H, L N, H, L N, H N, H
FK1250 1000 N, H, L N, H, L N, H N, H
1250 N, H, L N, H, L N, H, L N, H N, H
FK1600 1600 N, H N, H N, H
LTM
Line thermal magnetic
protection Number of poles /
SMR1e protected poles (trips)
Selective electronic protection.
3 pole 3 trips N, H, L N, H, L N, H, L N, H N, H
SMR1s
A Selective electronic protection with
4 pole 3 trips N, H, L N, H, L N, H, L N, H N, H
4 pole 4 trips(1) N, H, L N, H N, H
enhanced functionality
SMR1g (1) Switchable, 0%, 50% or 100% neutral protection
B Selective electronic protection with
enhanced functionality and ground
fault
Mag BreakTM
C Magnetic only breaker for motor
protection
Y
Non Automatic or switch
D (not mentioned in tables)
E
Accessories (main types)
F O
1 A maximum of one Bell Alarm contact AND
3 aux. contacts (all of CO type)
O
2 Shunt or Undervoltage release
G O
3 Operators
Rotary handle
OR
Electrical operator
X O
4 Draw out system
O
5 Connectors for auxiliary wiring
O
6 RCD with separate sensor
A.34
Record Plus
FK800 - Complete circuit breaker
Selective Electronic Trip Unit type SMR1e
FK frame
FKN 800 FKN36NS800PPF 435429 FKN46NS800PPF 435483
80kA G
FKH 800 FKH36NM800PF 435538 FKH436NM800PF 435542
A.35
Record Plus
FK1250 - Complete circuit breaker
Selective Electronic Trip Unit type SMR1e
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
Order codes
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
C One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
E
80kA 1000 FKH36NT100SF 435553 FKH436NT100SF 435565
FKH 1250 FKH36NT125SF 435554 FKH436NT125SF 435566
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
G
Motor Protection (Mag BreakTM ) Magnetic Only Breaker
In (A) 3 pole 3 trips 4 pole 3 trips(2)
50kA
X FKN 1250 FKN36NM125SF 435558 FKN436NM125SF 435570
80kA
FKH 1250 FKH36NM125SF 435559 FKH436NM125SF 435571
100kA
1250 FKL36NM125SF 435561 FKL436NM125SF 435573
FKL
One code covers: A standard fixed front connection breaker + Assembled dummy trip unit + Toggle elongator +
Breaker finishing covers + Fixation hardware
A.36
Record Plus
FK1600 - Complete circuit breaker
Selective Electronic Trip Unit type SMR1e
FK frame
80kA 1600 FKH36NS160TTF 435315 FKH46NS160TTF 435369
FKH
One code covers: A standard fixed front connection breaker + Assembled trip unit + Toggle Elongator +
Breaker finishing covers + Fixation hardware
One code covers: A standard fixed front connection breaker + Assembled dummy trip unit + Toggle elongator +
D
Breaker finishing covers + Fixation hardware
E
(1) Switchable 0%, 50% or 100% neutral protection, neutral on left.
(2) Neutral on left
A.37
Record Plus
FK - Internal accessories
Changeover
Contacts
Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no.
FK - Operators
Electrical operators 24V AC/DC FNEMFD 435683
48V AC/DC FNEMFF 435680
110V AC FNEMF3 435686
110V DC FNEMFJ 436457
230V AC FNEMF6 435689
(a) 250V DC FNEMFN 436456
D Accessories
Extension shaft kit (max. 600 mm) (a) FNNRE 435738 Only for use with panel or door mounted type
(a) Flex operator adaptor push to trip (b) FGNFT 432867 Only for use with panel or door mounted type
E
(b) Adaptor for drawout (c) FNNRW 435745
(c)
Ronis keylock 1104B nr. BC 1027(1) (d) FA1BR1 430088
Ronis keylock 1104B nr. BC 1053(1) (d) FA1BR2 430089
F Ronis keylock 1104B nr. BC 2932(1) (d) FA1BR3 430504
(d) Ronis keylock 1104B nr. BC 2911(1) (d) FA1BR4 430505
Ronis keylock 1104B nr. BC 2936(1) (d) FA1BR5 430506
Ronis keylock 1104B nr. BC 2940(1) (d) FA1BR6 430507
Ronis lock with random key(1) (d) FA1BRH 430068
G (e) Profalux lock with random key(1) (e) FA1BPH 430813
A.38
Record Plus
FK - Residual current devices
Relay IΔ n Operating Settable Nr. of Cat. no. Ref. no. Pack.
voltage delay modules
RD5 0.03 ... 1A 110V AC 0-1s 3 RD5 110 704175 1
0.03 ... 1A 220V AC 0-1s 3 RD5 220 704169 1
0.03 ... 1A 380V AC 0-1s 3 RD5 380 704176 1
FK frame
Round Internal diameter Ø 22mm Din Rail type TTD 22 560090 1
Round; splittable Internal diameter Ø 110mm TTO 110 560097 1
Round; splittable Internal diameter Ø 210mm TTO 210 560098 1
FK - Drawout system
3 pole 4 pole
Main system
Model with front connection
Complete set for FK800 FNWS3WP 433434 FNWS4WP 436481
Complete set for FK1250 & FK1600 FNWS3WT 436482 FNWS4WT 433442
One code covers the fixed and withdrawable part of the draw-out system, with plug-in base, mounting accessories and fixation hardware. B
Auxiliary Complete set 6 pole FNPFM 435758
disconnects
(Secondary
wiring)
C
FK - Connections: optional F
3 pcs 4 pcs
Terminal
extenders(2) Flat FK800 - FK1250 FNBES3P 435706 FNBES4P 435707
Internal box clamps(2) Box Clamp Cu/Al, for 3 x 70-240 sq.mm. FNTCA3327 436316 FNTCA3427 436651
Box Clamp Cu/Al, for 4 x 70-240 sq.mm. FNTCA4327 433438 FNTCA4427 433439
B
Spare parts Finishing covers (set of 2 pieces) FNUA3 435762 FNUA4 435763
D
FK - Accessories electronic trip units
E Battery test device (a) FNT 435704
G (a) (b)
A.40
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FK frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D
D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.41
Record Plus
Connectivity
F O
1 Busbar support
O
2 Busbars (not part of offering)
O
3 Connection set
G O
4 Lateral connection set
O
5 Support cover
O
6 Adaptor FD
O
7 Adaptor FE
X O
8 Busbar covers
O
9 Trim/Cover plate filler
A.42
Record Plus
Connectivity system with 60mm spacing; three and four pole
Busbar supports
3 pole 4 pole
Connections
Incoming from side Incoming from front
1 pole for lateral bar, flexible bar or cable connection FBTS1L12 433468 - -
Cu/Al 35-240 mm2 for busbar section 5 mm
Connectivity
1 pole for lateral bar, flexible bar or cable connection FBTS10L12 433474 - -
Cu/Al 35-300 mm2 for busbar section 10 mm
3 pole set for conductors 1.5 to 70mm2 - - FBTF3L12 433456
4 pole set for conductors 1.5 to 70mm2 - - FBTF4L12 433497
Adaptors
3 pole 4 pole
FD frame 160A FBAD3 433443 FBAD4 433446
FE frame 250A FBAE3 433449 FBAE4 433452
Installation
A
Busbar cover adjustable 3pole FBCI3 433377
Busbar cover adjustable 4pole FBCI4 433444
Filler for cover plate cut out of 64mm l=1.2m FBF6 883970 B
A.43
Record Plus
Changeover devices
Available device
D combinations
Main device Secundary device
N R
E FE 160 10 - 160A FE 160 10 - 160A
FE 250 80 - 250A FE 250 80 - 250A
O
1 Mechanical interlock for two breakers
O
2 Breaker mounting plates
O
3 Mechanical interlock with lock in rotary handles
O
4 Electrical interlock with UVR and SHT release
O
5 Controller for automatic changeover suitable for two breakers Technical features pg. C.18
O
6 Electrical operators
A.44
Record Plus
Changeover systems
FK800/1600
FK800/1600
FG400/630
FG400/630
FE160/250
FE160/250
FE 160: page A.13 FE 250 : page A.16
Changeover devices
FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
FK1600: page A.37 Cat. no. Ref. no. Qty
A.45
Record Plus
Mechanical interlocking of two breakers
System with walking beam
Main Secondary Required components
Device Device Listed protection devices are breakers or
N (left) R (right) switches Option 1
order codes can be found on :
FK800/1600
FK800/1600
FG400/630
FG400/630
FE160/250
FE160/250
FE 160: page A.13 FE 250 : page A.16
FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
Cat. no. Ref. no. Qty
FK1600: page A.37
System with rotary handles, 1 key and two locks (Ronis 1104) (1)
Main Secondary Required components
Device Device Listed protection devices are breakers or
A N (left) R (right) switches
order codes can be found on :
Option 2
FK800/1600
FK800/1600
FG400/630
FG400/630
FE160/250
FE160/250
A.46
Record Plus
Complete automatic changeover sets
Two power supplies, ONLY one of which is allowed to supply the network
Main Secondary Required main components
Device Device Listed protection devices are breakers or
N (left) R (right) switches
order codes can be found on :
FK800/1600
FK800/1600
FG400/630
FG400/630
FE160/250
FE160/250
FE 160: page A.13 FE 250 : page A.16
FG 400: page A.25 FG 630 : page A.27
FK 800: page A.35 FK1250 : page A.36
Cat. no. Ref. no. Qty
FK1600: page A.37
Option 1
Changeover devices
accessories for two FE frames - WITHOUT CONTROLLER
x • •x System 220V 50/60Hz with all necessary breaker FEEO1N 437003 1
accessories for two FE frames - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1
Option 2
accessories for two FG frames - WITHOUT CONTROLLER
x • •x System 220V 50/60Hz with all necessary breaker FGEO2N 437007 1
accessories for two FG frames - WITHOUT CONTROLLER
Controller type E or E plus FAEC -- 87- - - - 1
G
(1) This are the reference numbers for the controler in english version. For other languages, consult us.
A.47
Record Plus
Residual current devices with separate
sensors
Function
RCD Relay
The relay part of the RCD device is a DIN-rail mounted device containing
the electronics and the setting area. On receipt of a signal from the
sensor two contacts are operated.
Sensor
Placed around the phase and neutral current paths it detects the vectorial sum of
Order codes
the current in the circuit. When this sum is no longer zero, a signal is sent to the
connected RCD relay.
The connection between the relay and the sensor should be as short as possible,
the maximum circuit resistance may not exceed 30 Ohm.
If the lead length is longer than 5 meters and/or the sensitivity is adjusted to
values < 0.5A the use of screened cables and earthed screening is recommended.
The same recommendation applies in cases where the sensor is installed in an
Applications environment where strong magnetic fields occur.
For high nominal currents or high sensitivities the cables must be centered within
the sensor.
The use of an oversized sensor and/or reduced cable cross sections not centraly
passing within the sensor could result in inaccurate readings.
A
Characteristics
B RCD Relay
• Complies with EN 50082 & EN 60730
• For sinusoidal and pulsating earth leakages
• Test button and reset (memory clean) button
C • Permanent working signal (green) and tripping signal (red) by means of LED
• Adjustable time delay (except 30mA) by means of potentiometer
• Two output contacts, one potential free
• Automatic test feature of the combination relay/sensor is provided
D • On disconnection of the sensor, the relay trips
• Plug-in terminal block
• Width: 3 modules of 18 mm
E • For installation in modular enclosures, DIN-rail mounted
Sensor
• Accuracy: 3/10,000 of the phase current (TTO type 1/10,000)
• Frequency: from 4 to 400Hz
F • Sealable cover terminals
• For use with the relay types RD1D, RD5 and RD6 as described here.
Also applicable for use with the reconnection relay RRC1 and RRC2
(see seperate publications)
G
Dimensions pg G.33
A.48
Record Plus
RD range differential relay
IΔn Operating Settable Nr. of Cat. no. Ref. no. Pack.
voltage delay modules
RD5 0.03 ... 1A 110V AC 0-1s 3 RD5 110 704175 1
0.03 ... 1A 220/230V AC 0-1s 3 RD5 220 704169 1
0.03 ... 1A 380/400V AC 0-1s 3 RD5 380 704176 1
Sensor
Closed model; internal diameter 22mm , suitable for DIN rail mounting TTD 22 560090 1
Closed model; internal diameter 35mm TT 35 560091 1
Closed model; internal diameter 60mm TT 60 560092 1
Closed model; internal diameter 80mm TT 80 560093 1
Closed model; internal diameter 110mm TT110 560094 1
Closed model; internal diameter 160mm TT160 560095 1
Closed model; internal diameter 210mm TT 210 560096 1
Accessories
Through Panel/Door mounting kit for relay with DIN -rail, mounting RDFR 872227 1
A
hardware and doorflange.
C
Wiring Diagram
SHT UVR* F
*12 = SHT
13 = UVR
A.49
Just rel
Record Plus
Technical data D
Application guide E
Wiring diagrams F
Dimensions G
y on us
Numerical Index X
B.1
Record Plus
Thermal Magnetic Trip Units
FD frame
Record PlusTM circuit breakers are designed to isolate and The trip units have been designed with the user in mind.
switch low voltage distribution circuits and to protect the The trip unit ratings are always indicated in amperes.
conductors, equipment and devices included in these To prevent unauthorized manipulation of the breaker
circuits. settings each trip unit comes with a transparent ,
The FD frame size is designed to use electro-mechanical tamper-free (sealable) cover.
trip units. These are typical thermal magnetic devices All units come as 3 and 4 pole devices (2p on request)
which offer an overload (thermal) and short-circuit and are available in a number of application-defined
protection (magnetic). subvariants.
The breaker can also be equipped with a Mag BreakTM
magnetic-only trip unit that offers short-circuit
protection.
Trip units
The trip unit is an integrated part of the breaker and is Mag BreakTM (magnetic only)
not interchangeable. The following versions are (FD..MO sub type)
available: Available in the FD63/160N, H and L breaker types.
A trip unit designed to offer short-circuit protection
LTM (line protection thermal magnetic) only and specifically suited for motor protection in
(FD...TF sub type) coordination with a contactor and a thermal relay
Available in the Concise (FD63/160C) and Effective (EN 60947-4).
breaker type (FD63/160E). Has a settable magnetic threshold of 10 to 15 x In.
Has no thermal setting option and a magnetic release
A set at 10 x In.(1) Y (non automatic - switch disconnector)
Designed for the protection of generic loads. A device available in a 63A and 160A variant .
Has no protection elements.
LTM (line protection thermal magnetic) Designed as switch disconnector
B (FD..TC & TE sub type)
Available in the Concise (FD63/160C) and Effective
breaker type (FD63/160E).
C Has a thermal settingof 0.8 to 1 times and a magnetic
release set at 10(1) x the selected rating. Designed for
the protection of generic loads.
B.2
Record Plus
FD63/160 breakers - trip unit overview
FD frame Trip unit overview
In Thermal setting Ir Magnetic setting Im Neutral protection
Sub- pick-up band 1.05 ÷ 1.3 Ir pick-up band ± 20% Im
Type type Applicable for breaker types [A] min [A] max [A] fix [A] 4P4T 4P 3.5T 4P3T
16 16 160 =Ir
20 20 200 =Ir
25 25 250 =Ir
32 32 320 =Ir
LTM F.D C E 40 Ir = In 40 10 x In 400 =Ir
50 50 500 =Ir
63 63 630 =Ir
80 80 800 =Ir
100 100 1000 =Ir
125 125 1250 =Ir
160 160 8 x In 1280 =Ir
16 12.8 16 160 =Ir
20 16 20 200 =Ir
25 20 25 250 =Ir
32 25.6 32 320 =Ir
LTM C.D C E 40 Ir = 32 40 10 x In 400 =Ir
50 40 50 500 =Ir
FD frame
E.D. 0.8÷1In
63 50.4 63 630 =Ir
80 64 80 800 =Ir
100 80 100 1000 =Ir
125 100 125 1250 =Ir
160 128 160 8 x In 1280 =Ir
16 12.8 16 160 =Ir
20 16 20 200 =Ir
25 20 25 250 =Ir
not protected
40 32 40 160 =Ir
50 40 50 200 =Ir
GTM G.D N H Ir = n
63
80
0.8÷1In 50.4
64
63
80 4 x In
252
320
=Ir
=Ir =Ir/2
B
100 80 100 400 =Ir =Ir/2
125 100 125 500 =Ir =Ir/2
160 128 160 640 =Ir =Ir/2
3
7
35
70
52.5
105
C
not protected
12.5 Adjust- 125 187.5
20 able 200 300
Mag. N H
30 10÷15In 300 450
BreakTM L No protection
50
80
500
800
750
1200
D
100 1000 1500
Y Y 63 No protection
160
E
(1) Not available in S type
n
G
Depicted is the LTMD type
B.3
Record Plus
Time Current Curves
FD frame
Breaker FD63 / LTM 16-63A Breaker FD160 / LTM 80, 100 & 125A
10000 10000
120 120
100 6000 100 6000
80 80
60 4000 60 4000 Set at 1 x In
50 Set at 0,8 x In Set at 1 x In 50 Set at 0,8 x In
40 40 Ir=80, 100 or 125A
30 2000 30 2000 Ir=64,80 or 100A
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40
20 20
Trip units
Minutes
Seconds
Minutes
Seconds
10 10
6 6
4 4
2 2
1 1
0,6 LTM type 0,6 LTM type
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
A 0,006
0,004
0,006
0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
B x Nominal Current In x Nominal Current In
C 10000
Breaker FD160 / LTM 160A
10000
Breaker FD63 / LTMD 16-32A
120 120
100 6000 100 6000
80 80
60 4000 Set at 1 x In 60 4000 Set at 1 x In
50 Set at 0,8 x In 50 Set at 0,8 x In
40 Ir=160A 40 Ir=16 or 20A
2000 2000
D 30
20
1000
Ir=128A 30
20
1000
Ir=12,5 or 16A
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
E 2
100
2
100
1 60 1 60
40 40
20 20
Minutes
Seconds
Minutes
Seconds
F 10 10
6 6
4 4
2 2
G 1
0,6 LTM type
1
0,6 LTM type
Trip Time
Trip Time
0,4 0,4
0,2 0,2
X 0,1
0,06
0,1
0,06
0,04 0,04
0,02 0,02
0,01 0,01
0,006 0,006
0,004 0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In
B.4
Record Plus
Time Current Curves
Breaker FD63 / LTMD-GTM 40, 50 & 63A Breaker FD160 / LTMD-GTM 80, 100 and 125A
10000 10000
120 120
100 6000 100 6000
80 80 Set at 0,8 x In Set at 1 x In
60 4000 Set at 1 x In 60 4000
50 Set at 0,8 x In 50 Ir=64,80 or 100A Ir=80, 100 or 125A
40 Ir=40, 50 or 63A 40
30 2000 Ir=32,40 or 50A 30 2000
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40
20 20
Minutes
Seconds
Minutes
Seconds
FD frame
10 10
6 6
4 4
GTM type
2 2 GTM type
1 1
0,6 LTMD type 0,6 LTMD type
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In B
10000
Breaker FD160 / LTMD-GTM 160A
10000
Breaker FD160 / Mag. Break 80 and 100A C
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80
60 4000 60 4000
50 Ir=128A Ir=160A 50
40 40
2000 2000
30
20
1000
30
20
1000 Thermal Withstand of Breaker
D
10 600 10 600 FD63 type
8 8 Max in Class 10 and 30
6 400 6 400
5 5 63 Amp
4 4
3 200 3 200
2
100
2
100 E
1 60 1 60
40 40 Thermal Withstand of Breaker
FD160 type
20 20 Max in Class 30 80 Amp
Minutes
Seconds
Minutes
Seconds
1
0,6 LTMD type
1
0,6 Set at 15 x In
G
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1
0,06
0,1
0,06
X
0,04 0,04
0,02 0,02
0,01 0,01
0,006 0,006
0,004 0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 67,2 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In
B.5
Record Plus
Thermal Magnetic Trip Units
FE frame
The breaker is built up of a frame and an inter- overload fault and, in accordance with the HD 384
changeable trip unit . The interchangeability also includes standards to immediately reclose after an overload
the electronic trip unit and the non-automatic switch event . Each trip unit is equipped with an interchange
variant . The FE frame size trip units are designed to prevention interlock that does not allow one to
distinguish between an overload or short-circuit and are incorrectly place a 200 or 250A trip unit in a 160A frame
equipped with indicating flags. This patented GE system size.
saves down time by enabling the user to identify an
B.6
Record Plus
FE160 and FE250 breakers - trip unit overview (electromechanical)
FE frame Electro-mechanical trip unit overview
In Thermal Ir Magnetic Im Neutral protection
Sub- pick-up band 1.05 ÷ 1.3 Ir pick-up band ± 20% Im
Type type Applicable for breaker types [A] min [A] max [A] min [A] max [A] 4P4T 4P 3.5T 4P3T
25 20 25 200 =Ir
32 26 32 256 =Ir
not protected
40 32 40 Fixed 320 =Ir
50 40 50 8 x In 400 =Ir
LTM A.E N H L 63 adjustable 50 63 504 =Ir =Ir/2
FE160
80 0.8÷1xIn 64 80 400 800 =Ir =Ir/2
100 80 100 adjustable 500 1000 =Ir =Ir/2
125 100 125 5÷10 In 625 1250 =Ir =Ir/2
160 128 160 800 1600 =Ir =Ir/2
100 80 100 500 1000 =Ir
not protected
FE160 125 adjustable 100 125 adjustable 625 1250 =Ir
LTMD D.E N H L 160 0.8÷1xIn 128 160 5÷10 In 800 1600 =Ir
125 100 125 625 1250 =Ir =Ir/2
FE250 160 adjustable 128 160 adjustable 800 1600 =Ir =Ir/2
200 0.8÷1xIn 160 200 5÷10 In 1000 2000 =Ir =Ir/2
250 200 250 1250 2500 =Ir =Ir/2
40 32 40 160 =Ir
FE frame
50 40 50 Fixed 200 =Ir
FE160 63 adjustable 50 63 4 x In 252 =Ir =Ir/2
100 0.8÷1xIn 80 100 400 =Ir =Ir/2
GTM G.E N H 125 100 125 375 625 =Ir =Ir/2
160 128 160 480 800 =Ir =Ir/2
125 100 125 adjustable 375 625 =Ir =Ir/2
160 adjustable 128 160 3-5 In 480 800 =Ir =Ir/2
FE250
200 0.8÷1xIn 160 n 200 600
o 1000 =Ir =Ir/2
250 200 250 750 1250 =Ir =Ir/2
3,5 24,5 52,5
7 adjustable 49 105
12,5 7÷15In 87,5 188
20 140 300
not protected
Mag. FE160 30 210 450
BreakTM N H L 50 500 750
80
100
No protection
adjustable
800
1000
1200
1500
A
125 10÷15In 1250 1875
160 1600 2400
FE250 160 1600 2400
200
250
2000
2500
3000
3750
B
FE160 160
Y Y No protection
FE250 250
C
n o
B.7
Record Plus
Time Current Curves
FE frame
Breaker FE160 / GTM-LTM 25-32A Breaker FE160 / GTM-LTM 40, 50 and 63A
10000 10000
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80 Set at 0,8 x In Set at 1 x In
60 4000 60 4000
50 Ir=20 or 25A Ir=25 or 32A 50 Ir=32, 40 or 50A Ir=40, 50 or 63A
40 40
30 2000 30 2000
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40
20 20
Trip units
Minutes
Minutes
Seconds
Seconds
10 10
6 6
4 4
GTM type GTM type
2 2
1 1
LTM type LTM type
0,6 0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
A 0,006
0,004
0,006
0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.2 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
B x Nominal Current In x Nominal Current In
C 10000
Breaker FE160 / GTM-LTM 801), 100, 125 and 160A
1) 80A type not available in GTM version
10000
Breaker FE160 / LTMD 100, 125 and 160A
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80 Set at 0,8 x In Set at 1 x In
60 4000 60 4000
50 Ir=64, 80, 100 or 128A Ir=80, 100, 125 or 160A 50 Ir=80, 100 or 128A Ir=100, 125 or 160A
40 40
2000 2000
D 30
20
1000
30
20
1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
E 2
100
2
100
1 60 1 60
40 40
20 20
Minutes
Minutes
Seconds
Seconds
F 10 10
6 6
4 4
GTM type
2 Adjustable 2
G 1
0,6
3-5 x In
1
0,6
LTMD type
Adjustable
Trip Time
Trip Time
0,02 0,02
0,01 0,01
0,006 0,006
0,004 0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Nominal Current In x Nominal Current In
B.8
Record Plus
Time Current Curves
Breaker FE250 / GTM 125, 160, 200 and 250A Breaker FE250 / LTMD 125, 160, 200 and 250A
10000 10000
120 120
100 6000 100 6000
80 Set at 0,8 x In Set at 1 x In 80 Set at 0,8 x In Set at 1 x In
60 4000 60 4000
50 Ir=128, 200 or 250A Ir=160, 200 or 250A 50 Ir=100, 125, Ir=125, 160, 200 or 250A
40 40 160 or 200A
30 2000 30 2000
20 20
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 4
3 200 3 200
2 2
100 100
1 60 1 60
40 40
20 20
Minutes
Minutes
Seconds
Seconds
FE frame
10 10
6 6
4 4
2 2
Trip Time
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 8 10 20 30 40 60 100
x Nominal Current In x Nominal Current In B
Breaker FE160 / Mag. Break 3, 5, 12.5, 20, 30, 50, 80, 100, 125 and 160A
10000
Breaker FE250 / Mag. Break 160, 200 and 250A C
120
100 6000
80
60 4000
50
40
2000
30
20
1000 Thermal Whitstand of Breaker D
FE160 type
10 600
8 Max in Class 10 and 30
6 400
5 150 Amp
4
3 200
2
100 E
1 60
40 Thermal Whitstand of Breaker
FE250 type
20 Max in Class 10 and 30
Minutes
Seconds
10 225 Amp
F
6
4
1
0,6
Set at 10 x In
G
Set at 15 x In
Trip Time
0,4
0,2
0,1
0,06
X
0,04
0,02
0,01
0,006
0,004
0,002
0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In
B.9
Record Plus
Electronic Trip Units
SMR range
Electronic trip units that offer sophisticated protective circuits in mind and has been rigorously tested to cope
functions and wide setting bands are standard with harmonic currents, electromagnetic fields, inrush
protection devices for the FG400, FG630, FK800, FK1250 currents and spikes, thus preventing phenomanae as
and FK1600 frame sizes. The FE frame can be equipped incorrect current measurement and nuisance tripping.
with interchangeable trip units offering a choice of the The devices exist in a number of performance tiers, the
electronic or the electro-mechanical device. Each SMR1 device for the FE and FG frame sizes, the SMR 2 for
electronic device has been designed with the the FG frame size and the SMR1e, 1s and 1g types for
abnormalities of modern low voltage distribution the FK frame size.
The SMR1 trip unit type is available for all FE and FG the user flexibility to make a last minute
frame sizes. The device has two basic protective choice in the required current rating,
functions. The first is a Long Time or overload protected poles or protection band.
protection with two time bands designed to match These exist in two variants, adjustable
motor or cable characteristics and a user defineable and switchable. In order to prevent an
setting range. When set to motor protection mode a insertion of a rating plug into the
phase loss protection is initiated that will trip the incorrect trip unit (number of poles and
breaker when the difference in current between one current rating) a mechanical interlock
phase line and the average of all three phase drops and color coding system are present .
below 20% .
The second device, the Short Time protection, offers The device is supplied with an electronic actuator coil
A protection against short-circuits and is settable from that fits into a pocket in the breaker housing and is
2 to 13 (1) x the adjusted LT protection. then connected to the trip unit . Without mounted and
connected actuator coil the breaker will not function.
However, in order to verify a correct operation of the
B combination a simple test device is available to test the
assembly.
We strongly recommend the use of this test device.
C Adjustable rating plug
This easy-to-adjust trip unit is equipped with a LT Specifically designed for line protection with a
pre-alarm device made up of a LED indicator on the setting range of 0.625 to 1 x the plug rating over 16
D trip unit front face and an electronic contact . setpoints. The settings on the devices are in current
Before the breaker trip is initialized the LED will at first values and thus allow for ease of setting.
start to blink (at about 0.95 x Ir). When the current Each trip unit size can be
flowing through the breaker reaches about 1.05 x Ir equipped with one of two
E and a trip is imminent , the LED stops blinking, remains available adjustable rating
on and an electronic contact closes, this just before the plugs types. For 4 pole trip
circuit breaker trips and power is disconnected. This units the rating plugs exist
F electronic signal can be linked to an external LT in 3 and 4pole protected versions with a choice in
module that transforms the electronic signal into one neutral rating between 50 or 100% of the phase
that allows the operation of an external relay. value.
(The LT module is a modular DIN-rail device).
G Switchable rating plug
Allows for a choice of line or class 10 motor
All SMR 1 trip units have a built-in temperature sensor
protection(2). The device has two setting knobs: one
that trips the breaker at temperatures above 90°C. It
for the desired rating and band selection and one for
X thus prevents the breaker and electrical components in
its immediate vicinity from overheating.
the definite current setting.
The current setting is in multiples of the selected
rating and has a range of 0.4 to 1 x the trip unit size
Each SMR1 trip unit comes with a transparent , tamper-
over 32 setpoints. Each
free (sealable) cover, this to prevent unauthorized
trip unit size has one
manipulation of the breaker settings. In the FE frame
switchable rating plug. For
size they are supplied in a single housing including
4 pole trip units the rating
current sensors that can fully displace the alternative
plugs exist in 3 and 4 pole
electromechanical device while the FG type is supplied
protected versions with a choice in neutral rating
as an electronic pouch (current sensors supplied with
between 50 or 100% of the phase value.
the breaker).
B.10
Record Plus
FE160 and FE250 breakers
SMR1 types
Trip units are available in 10 different versions depending prevent incorrect combinations of electronic trip units and
on the frame rating and the network frequency. rating plugs. The 50/60Hz and 400Hz variants use the
FE 160 frame size 50/60 Hz 25, 63, 125 and 160A same rating plug. When NO rating plug is installed in the
FE250 frame size 50/60Hz 125, 160 and 250A breaker, all protective functions remain operational. This
400 cycle variants (available on request) at a reduced current rating. (15 -20 % of the chosen trip
FE160 - 125 and 160A, FE 250 - 250A unit rating).
The trip units must be equipped with a rating plug that For applications where a overload protection is NOT
establishes the rated current of the protective device and needed a version with disabled LT protection is available.
its setting. A colour code and a mechanical interlock
SMR1 - FE frame
FE 160 & FE 250 Breakers - Electronic Trip Unit Overview
FE frame Electronic trip unit overview
In* LT ST Neutral protection
pick-up band 1.05÷1.2 Ir pick-up band ± 20% Im
[A] Ir setting min [A] max [A] Im setting min [A] max [A] 4P4R 4P 3.5T 4P3R
16 10 16 20 208 =Ir
25 16 25 32 325 =Ir
40 0.625-1xIn 25 40 50 520 =Ir
63 16 steps 40 63 2-13xIr 79 819 =Ir =Ir/2
FE160 80 line 50 80 10 steps 101 1040 =Ir =Ir/2
not protected
SMR1 +
125 protection 80 125 160 1625 =Ir =Ir/2
adjustable N H L 100 63 100 126 1300 =Ir =Ir/2
rating plug
160 100 160 200 2080 =Ir =Ir/2
80 50 80 79 819 =Ir =Ir/2
125 0.625-1xIn 63 125 126 1625 =Ir =Ir/2
FE250 100 16 steps 80 100 2-13xIr 160 1300 =Ir =Ir/2
160 line 100 160 10 steps 200 2080 =Ir =Ir/2
160
250
protection 100
160
160
250
200
320
2080
3250
=Ir
=Ir
=Ir/2
=Ir/2
A
25 0.4-1xIn 10 25 20 325 =Ir
not protected
FE160 63 32 steps 25 63 2-13xIr 50 819 =Ir =Ir/2
SMR1 + N H L 125 line/mot. 50 125 10 steps 100 1625 =Ir =Ir/2
switchable
160
125
protection
0.4-1xIn 32
64
50
160
125
128
100
2080
1625
=Ir
=Ir
=Ir/2
=Ir/2
B
rating plug 2-13xIr
FE250 160 steps line/ n 64 o 160 10 steps 128 p 2080 =Ir =Ir/2
250 mot. prot. 100 250 200 3250 =Ir =Ir/2
* Colour code indicates which rating plug can be applied where On switching to Motor Protection a phase loss protection is initiated. C
Do not use for line protection.
n o p
Band timings 1.5 x Ir 7.2 x Ir 3 poli / 3 sganciatori
D
Line protection 65 - 95 sec 2.0 - 3.0 sec
Motor protection 200 - 300 sec 6.4 - 9.6 sec
E
How to set the device ST or Im setting
The defined rating plug defines the long time (LT) Is set in multiples of the LT current setting and has a
setting range and the manner of its adjustment . setting of 2 to 13 x this value with 10 setpoints. F
LT setting with adjustable rating plug Example
One knob with 16 positions allows the user a current A line protection device; required overload or LT setting
setting (Ir) between 0.625 and 1 times the chosen 120A, short-circuit or ST setting 8 x the G
rating. (values in A) LT setting.
SMR1 of 250A + switchable rating plug of 250A.
LT setting with switchable rating plug LT setting ..........knob 1 set to line and 160A
One knob to set the protection band (line class 5 or ........knob 2 set at 0.75 (0.75 x 160 = 120A)
X
motor class 10) and the rated current value ST setting..........knob 3 set a 8 x (= 8 x 120)
(2 current value settings of 0.625 and 1 x the trip unit SMR1 of 250A + adjustable rating plug of 160A.
rating) - in sketch trip unit rating 250A settings LT setting ..........knob 2 set at 120 (value on scale)
160A or 250A. ST setting..........knob 3 set at 8 x (= 8 x 120)
A second knob with 16 positions allows the user to set
the current (Ir in multipliers of chosen rating).
The combination of these two knobs allows a setting
range of 0.4 to 1 x the trip unit rating with
32 setpoints.
B.11
Record Plus
Time Current Curves
FE160 and FE250 breakers
SMR1 types
Breaker FE160 / SMR 1 / Sensor 25A Breaker FE160 / SMR 1 / Sensor 63A
10000 10000
120 120
100 6000 100 6000
80 Rating plug set at 1 x sensor rating 80 Rating plug set at 1 x sensor rating
60 4000 60 4000
50 (Ir=25A) 50 (Ir=63A)
40 40
30 2000 Motor protection mode. 30 2000 Motor protection mode.
20 Im set at 13 x Ir. 20 Im set at 13 x Ir.
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
(Ir= 25A). (Ir= 63A).
2 2
100 Line protection mode. 100 Line protection mode.
1 Im set at 6 x Ir. 1 Im set at 6 x Ir.
60 60
40 Rating plug set at
40 Rating plug set at
Class 10 Class 10
0.4 x sensor rating 0.4 x sensor rating
20 20
Trip units
Minutes
Minutes
Seconds
Seconds
(Ir=10A) (Ir=25A)
10 Line protection mode. 10 Line protection mode.
6 Im set at 13 x Ir. 6 Im set at 2 x Ir.
4 4
2 2
1 1
0,6 0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
A 0,006
0,004
0,006
0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
B x Trip unit rating In x Trip unit rating In
C 10000
Breaker FE160 / SMR 1 / Sensor 125A
10000
Breaker FE160 / SMR 1 / Sensor 160A
120 120
100 6000 100 6000
80 Rating plug set at 1 x sensor rating 80 Rating plug set at 1 x sensor rating
60 4000 60 4000
50 (Ir=125A) 50 (Ir=160A)
40 40
2000 Motor protection mode. 2000 Motor protection mode.
D 30
20
1000
Im set at 13 x Ir.
30
20
1000
Im set at 13 x Ir.
10 600 10 600
8 8
6 400 6 400
5 5
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
E 2
100
(Ir= 125A).
Line protection mode.
Im set at 6 x Ir.
2
100
(Ir= 160A).
Line protection mode.
Im set at 6 x Ir.
1 60 1 60
40 Rating plug set at
40 Rating plug set at
Class 10 Class 10
0.4 x sensor rating 0.4 x sensor rating
20 20
Minutes
Minutes
Seconds
Seconds
F 10
(Ir=50A)
Line protection mode.
Im set at 2 x Ir.
10
(Ir=64A)
Line protection mode.
Im set at 2 x Ir.
6 6
4 4
2 2
G 1
0,6
1
0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
X 0,1
0,06
0,1
0,06
0,04 0,04
0,02 0,02
0,01 0,01
0,006 0,006
0,004 0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In x Trip unit rating In
B.12
Record Plus
Time Current Curves
Breaker FE250 / SMR 1 / Sensor 125A Breaker FE250 / SMR 1 / Sensor 160A
10000 10000
120 120
100 6000 100 6000
80 Rating plug set at 1 x sensor rating 80 Rating plug set at 1 x sensor rating
60 4000 60 4000
50 (Ir=125A) 50 (Ir=160A)
40 40
30 2000 Motor protection mode. 30 2000 Motor protection mode.
20 Im set at 13 x Ir. 20 Im set at 13 x Ir.
1000 1000
10 600 10 600
8 8
6 400 6 400
5 5
SMR1 - FE frame
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
(Ir= 125A). (Ir= 160A).
2 2
100 Line protection mode. 100 Line protection mode.
1 Im set at 6 x Ir. 1 Im set at 6 x Ir.
60 60
40 Rating plug set at
40 Rating plug set at
Class 10 Class 10
0.4 x sensor rating 0.4 x sensor rating
20 20
Minutes
Minutes
Seconds
Seconds
(Ir=50A) (Ir=64A)
10 Line protection mode. 10 Line protection mode.
6 Im set at 2 x Ir. 6 Im set at 2 x Ir.
4 4
2 2
1 1
0,6 0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In x Trip unit rating In B
10000
Breaker FE250 / SMR 1 / Sensor 250A
C
120
100 6000
80 Rating plug set at 1 x sensor rating
60 4000
50 (Ir=250A)
40
2000 Motor protection mode.
30
20
1000
Im set at 13 x Ir. D
10 600
8
6 400
5
4 Rating plug set at 1 x sensor rating
3 200
2
100
(Ir= 250A).
Line protection mode.
Im set at 6 x Ir.
E
1 60
40 Rating plug set at
Class 10
0.4 x sensor rating
20
Minutes
Seconds
10
(Ir=100A)
Line protection mode.
Im set at 2 x Ir.
F
6
4
1
0,6
G
Trip Time
0,4
0,2
0,1
0,06
X
0,04
0,02
0,01
0,006
0,004
0,002
0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Trip unit rating In
B.13
Record Plus
Electronic Trip Units
Trip units are available in 6 different versions depending its setting. A colour code and a mechanical interlock
on the frame rating and the network frequency. prevent incorrect combinations of electronic trip units
FE400 frame size 50/60 Hz 250, 350 and 400A and rating plugs. The 50/60Hz and 400Hz variants use
FE630 frame size 50/60Hz 400, 500 and 630A the same rating plug.
400 cycle variants (available on request) For special applications a version with disabled LT or
FG400 - 400A, FG 630 - 630A overload protection is available complete with a specific
The trip units must be equipped with a rating plug that rating plug.
establishes the rated current of the protective device and
Trip units
E
FG400 & FG630 Breakers - Electronic trip units type SMR1
FG frame Electronic trip unit overview
F In* LT
pick-up band 1.05÷1.2 Ir
ST
pick-up band ± 20% Im
Neutral protection
[A] Ir setting min [A] max [A] Im setting min [A] max [A] 4P4T 4P 3TN 4P3T
160 100 160 200 2080 =Ir =Ir/2
not protected
0.625-1
G SMR1 +
adjustable
FG400 250
250 xIn
160
160
250
250
2-13xIr
10 steps
320
320
3250
3250
=Ir
=Ir
=Ir/2
=Ir/2
N H L 400 16 steps 250 400 500 5200 =Ir =Ir/2
rating plug line prot.
FG630 400 250 400 500 5200 =Ir =Ir/2
630 400 630 2-10 Ir 800 6300 =Ir =Ir/2
X
protected
switchable N H L line/mot.
FG630 400 160 400 10 steps 320 5200 =Ir =Ir/2
rating plug prot.
500 250 500 500 6500 =Ir =Ir/2
B.14
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SMR1 - FG frame
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.15
Record Plus
Time Current Curves
FG400 and FG630 breakers
SMR1 types
Breaker FG400 / SMR1 / Sensor 250A Breaker FG400 / SMR1 / Sensor 400A
10000 10000
120 120
100 6000 100 6000
80 80
60 4000 60 4000
50 50
40 40
30 2000 30 2000
20 20
1000 Rating plug set at 1 x sensor rating 1000 Rating plug set at 1 x sensor rating
10 600 (Ir= 250A). 10 600 (Ir= 400A).
8 8
6 400 Motor protection mode. 6 400 Motor protection mode.
5 5
4 Im set at 13 x Ir. 4 Im set at 13 x Ir.
3 200 3 200
2 2
100 Rating plug set at 1 x sensor rating 100 Rating plug set at 1 x sensor rating
1 60 (Ir= 400A). 1 60 (Ir= 400A).
40 Line protection mode. 40 Line protection mode.
Im set at 6 x Ir. Im set at 6 x Ir.
20 20
Trip units
Minutes
Minutes
Seconds
Seconds
Class 10 Class 10
10 Rating plug set at 0.4 x sensor 10 Rating plug set at 0.45 x sensor
rating (Ir=100A). rating (Ir=160A).
6 6
Line protection mode Line protection mode
4 Im set at 2 x Ir. 4 Im set at 2 x Ir.
2 2
1 1
0,6 0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
A 0,006
0,004
0,006
0,004
0,002 0,002
0,001 0,001
0,1 3 4 5 6 7.28 10 0,1 3 4 5 6 7.28 10
B 0,5 1 2
x Sensor rating Is
20 30 40 60 100 0,5 1 2
x Sensor rating Is
20 30 40 60 100
C 10000
Breaker FG400 / SMR1 / Sensor 400A Mag Break
120
100 6000
80
60 4000
50
40
2000
D 30
20
1000 Thermal Withstand line of brreakker
10 600 allowing:
8
6 400 Class 10 & 20 max. 400A
5 Class 30 max. 320A
4
3 200
E 2
100
1 60
40
20
Seconds
Minutes
F 10 Im set at 2x
6
4
G 1
0,6
Im set at 13x
Trip Time
0,4
0,2
X 0,1
0,06
0,04
0,02
0,01
0,006
0,004
0,002
0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is
B.16
Record Plus
Time Current Curves
Breaker FG630 / SMR1 / Sensor 400A Breaker FG630 / SMR1 / Sensor 500A
10000 10000
120 120
100 6000 100 6000
80 80
60 4000 60 4000
50 50
40 Rating plug set at 1 x sensor rating 40 Rating plug set at 1 x sensor rating
30 2000 30 2000
(Ir=400A) (Ir=500A)
20 20
1000 Motor protection mode 1000 Motor protection mode
Im set at 13 x Ir Im set at 13 x Ir
10 600 10 600
8 8
6 400 6 400
SMR1 - FG frame
5 5
4 Rating plug set at 1 x sensor rating 4 Rating plug set at 1 x sensor rating
3 200 3 200
(Ir=400A) (Ir=500A)
2 2
100 Line protection mode 100 Line protection mode
1 Im set at 6 x Ir Im set at 6 x Ir
60 1 60
40 40
20 Class 10 20 Class 10
Minutes
Seconds
Minutes
Seconds
10 Rating plug set at 10 Rating plug set at
6 0,4 x sensor rating 6 0,5 x sensor rating
4 (Ir=160A) 4 (Ir=250A)
Line protection mode Line protection mode
2 Im set at 2 x Ir 2 Im set at 2 x Ir
1 1
0,6 0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
0,006
0,004
0,006
0,004
A
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is B
10000
Breaker FG630 / SMR1 / Sensor 630A
10000
Breaker FG630 / SMR1 / Sensor 500A Mag break
C
120 120
100 6000 100 6000
80 80
60 4000 60 4000
50 50
40 Rating plug set at 1 x sensor rating 40
2000 2000
30
20
1000
(Ir=630A)
Motor protection mode
30
20
1000
Thermal Withstand line of breaker
D
Im set at 10 x Ir
10 600 10 600 allowing:
8 8
6 400 6 400 Class 10 & 20 max. 500A
5 5
4 Rating plug set at 1 x sensor rating 4 Class 30 max. 450A
3 200 3 200
2
100
(Ir=630A)
Line protection mode
Im set at 6 x Ir
2
100 E
1 60 1 60
40 40
20 Class 10 20
Minutes
Minutes
Seconds
Seconds
1
0,6
1
0,6
Im set at 13x
G
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1
0,06
0,1
0,06
X
0,04 0,04
0,02 0,02
0,01 0,01
0,006 0,006
0,004 0,004
0,002 0,002
0,001 0,001
0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.28 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is
B.17
Record Plus
Electronic Trip Units All SMR2 trip units have a built-in temperature sensor
that trips the breaker at temperatures above 90°C. It
thus prevents the breaker and electrical components
SMR2 range in its immediate vicinity from overheating. The SMR2 is
also equipped with a so called thermal memory
device. This memory tracks overheating even after the
device has tripped and prevents the breaker from being
The SMR2 is an electronic trip unit offering a fixed
switched whilst its environment is still at a too high
set of sophisticated protective functions that can
temperature.
be extended at will by the addition of seperately
available modules. Designed for use with the
Short-circuit Protection ST (short time)
FG400 and FG630 frame sizes the device has a
Offerering a selective protection against low value
fixed set of 3 protective functions allowing a
short-circuits the Short Time protection is settable from
selective and fully adjustable protection against
1.5 to 12(2) x the adjusted LT protection (Ir). The device
Overloads (LT) and short-circuits (ST and I).
can be set to five time setting bands (STD), this
Both the LT and ST protection can be set to
allowing selectivity between different breaker sizes.
different time settings or bands (LTD and STD)
The STD device can be set to an 'energy curve mode'.
whilst the ST device can be switched to a energy
This mode changes the fixed delay and reaction time
Trip units
B.18
Record Plus
FG400 and FG630 breakers
SMR2 types
Each SMR 2 device has three plug in elements of which at battery module also enhances the functionality of the Trip
least two are needed to allow the device to work properly. Reason Indicator Module.
1) A rating plug is plugged into the jack at the top left of the 3) An Extension module providing extra functionality
device. Without rating plug the SMR2 device will not provide and/or features. A standard SMR2 is supplied with a blank
any circuit protection and the breaker will trip immediatley. non function module.
2) A battery module (supplied with trip unit) needs to placed A 24V DC auxiliary supply can be connected to the trip unit
in the appropiate module this to power the thermal memo- via the contact module . This enabling all modules to be
ry within the trip unit when the breaker has tripped. If not used to their full capacity and allowing the use of the ZSI
SMR2 - FG frame
installed the thermal memory function is disabled. The function (if installed in the trip unit).
not protected
0.4-1 In
350 250 350 500 3500 =Ir =Ir/2
SMR2 + 32 steps
400 250 400 1.5-10 Ir 375 4000 2-11 Is 750 4400 =Ir =Ir/2
adjustable N H L utlising
10 steps 10 steps
rating plug two rating
400 250 400 1.5-12 Ir 375 4800 2-13 Is 1000 6500 =Ir =Ir/2
plugs
FG630 500 400 500 10 steps 600 6000 10 steps =Ir =Ir/2
630 400 630 1.5-10 Ir 600 6300 2-11 Is 1260 6930 =Ir =Ir/2
n 10 steps 10 steps A
LTD, Line no phase loss STD Standard
Setting(1) min max Setting min max
[sec.] [sec.] [msec.] [msec.]
1.25
2.5
1
1.5
1.5
3
0.04
0.12
0.036
0.108
0.07
0.16
B
5 3 5 0.21 0.190 0.26
10 6 o 10 0.31 0.280 0.37
LTD, Motor with phase 0.42 0.380 q 0.49
20
loss protection(1)
10 14
2
-OR- I T
(see trip curves)
C
30 14 o 20
B.19
Record Plus
FG400 and FG630 breakers
SMR2 types (continued)
Modules
Ground fault Protection
Each SMR2 device can be equipped with two plug-in
Ground fault alarm
elements, a rating plug and an extension module. The
Load shedding across two channels
extension modules are simple plug-in devices that allow
Trip Reason indicators
the user to enhance the SMR2 as a protective device or
Communication (modbus RTu)
to add in extra functional features. There is a single
Each module has a low level electronic output that can
function module available with Ammeter and a range of
be channeled through the communication bus (when
functional modules each adding two functions to the
present) or in some cases trigger a 1A/250 Volt change-
device. this allows an SMR 2 to be equipped with:
over contact placed in an external contact module
containing four contacts (type FAECM2).
Trip units
B.20
Record Plus
Zone Selective Interlock The ZSI option requires a 24VDC auxiliary supply.
A device that allows the user to achieve selectivity One FAECM2 module connected with one of the
combined with the fastest possible fault reaction time. breakers in the ZSI loop can be used. The FAECM2
When the ZSI is active the SMR2 trip unit will always needs then connected to an auxiliary supply of
trip the breaker as quickly as possible, ignoring the 24V DC.
time delays set by means of the STD or GFD devices. When the breaker is equipped with a "COM" option
However, when a ZSI signal is received from a down- the ZSI status signal is also available on the
stream breaker equipped with an SMR2, the STD or communication output .
GFD of the upstream SMR2 device revert to wherever
the adjustment is set . Ammeter
Provides the user with thecurrent running in one of the
With standard cables the distance between breakers is breaker phases. The device has an accuracy of 10%
a maximum of 30 meters. The use of shielded cables and normally indicates the current in the highest
SMR2 - FG frame
allows the distance between breakers to be increased loaded phase. Use of the push buttons on the module
to 1 km. A maximum of five SMR2 trip units can be front t allows the user to select an indiaction of the
linked in this manner. current in one of the other phases or neutral (if
present). After a set delay of 10 seconds the device
reverts to its standard indication setting.
C
Module FAMGFM2 Module FAMGAS2
A combination of the Ground Fault A combination of the Ground Fault
protection and the communication alarm option and the load shedding D
option. device.
E
Module FAMGFS2 Module FAMSM2
A combination of the Ground Fault A combination of the load shedding
protection and the load shedding
device.
device and the communication F
option.
G
Module FAMAM2 Module FAMST2
An Ammeter. A combination of the load shedding
device and the Trip Reason
Indicators.
X
B.21
Record Plus
Time Current Curves
FG400 and FG630 breakers
SMR2 types
Breaker FG400 / SMR2 / Sensor (trip unit) In=350A
Breaker FG400 / SMR2 / Sensor (trip unit) In=250A
Breaker FG630 / SMR2 / Sensor (trip unit) In=500A
10000 10000
120 120 Highest curve
100 6000 Highest curve 100 6000
80 80 Rating plug set at 1 x sensor rating
60 4000 Rating plug set at 1 x sensor rating (Ir= 250A). 60 4000
50 50 (Ir= 350 or 500A).
40 LTD set at class 30 40
30 2000 30 2000 LTD set at class 30
Ist set at 12 x Ir.
20 20 Ist set at 12 x Ir.
1000 STD set at 420 milliseconds 1000 STD set at 420 milliseconds
Iinst set at 13 x sensor rating
10 600 10 600 Iinst set at 13 x sensor rating
8 8
6 400 6 400
5 Rating plug set at 1 x sensor 5 Rating plug set at 1 x sensor
4 4
200 rating (Ir=250A) 200 rating (Ir=350 or 500A)
3 3
Other LTD classes Other LTD classes
2 2
100 Class 20 (partial curve) 100
Class 20 (partial curve)
1 60 Class 10 (partial curve) 1 60 Class 10 (partial curve)
40 Class 5 (partial curve) 40 Class 5 (partial curve)
Class 2.5 (partial curve) Rating plug set at Class 2.5 (partial curve)
Rating plug set at
20 Class 1.25 20 1 x sensor rating
Trip units
Minutes
Seconds
Minutes
Seconds
1 x sensor rating Class 1.25
(Ir=250A) (Ir=350 or 500A)
10 10
STD bands STD bands
6 6 420 Milliseconds
420 Milliseconds
4 4 310 Nilliseconds
310 Nilliseconds
210 Milliseconds 210 Milliseconds
2 2
120 Miliseconds 120 Miliseconds
1 40 Milliseconds 1 40 Milliseconds
0,6 0,6
Trip Time
Trip Time
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
Minutes
Seconds
F 10
(Ir=400 or 630A)
STD bands
Class 1.25
10 (Ir=400A)
STD bands
Class 1.25
G 1
0,6
40 Milliseconds 1
0,6
40 Milliseconds
Trip Time
Trip Time
0,4 0,4
0,2 0,2
X 0,1
0,06
0,1
0,06
0,04 0,04
B.22
Record Plus
Time Current Curves
Breaker FG400 / SMR2 / Trip Unit In=400A I2T on Breaker FG400 and FG630 Ground Fault
2
100 10
9 GF current value Adjustable
1 60 ST set at 1.5x 8 0.2 to 1 x sensor rating
I set at 12x 7 Lowest band - Green
40 STD set at 420ms
6 GF = 0.2 x Ir GFD = 40 milisec.
I2t ON I2t OFF = continuous line
5 I2t ON band = dotted line
20 STD bands set at:
420ms, 310ms, 4
SMR2 - FG frame
210ms, 120ms
10 or 40ms
I2t = ON 3
4 2
Seconds
Minutes
Seconds
1 1
0,9
0,6 0,8
0,7
0,4
Trip Time
0,6
Trip Time
0,5
0,2
ST set at 10x
0,4
I set at 12x
0,1 STD set at 40ms 0,3
I2t ON
0,06
0,04 0,2
0,01 0,1
5 6 7,2
1 2 3 4 10
x Sensor rating Is
20 30 40 50 60 100 0,1 0,2 0,4 0,6 0,8 1
x Sensor rating Is
2 3 4 5 6 7 8 10
B
1000
Breaker FG / SMR2 / Load shedding module R channel 1
1000
Breaker FG / SMR2 / Load shedding module R channel 2
C
R channel band R channel band
10 600 Channel 1 - Set at 1 x Ir 10 600 Channel 2 - Set at 0.6 x Ir
8 Bands with LTD set to 8 Bands with LTD set to
Class 30 Class 30
6
5
4
400
Class 20
Class 10
6
5
4
400
Class 20
Class 10
D
200 Class 5 200 Class 5
3 3
Class 2.5 Class 2.5
2 Class 1.25 2 Class 1.25
1
100
1
100
E
60 60
40 40
60 60 F
Minutes
Seconds
Minutes
Seconds
10 10
4
6
4
G
Trip Time
Trip Time
2 2
X
1 1
ST set at 10x ST set at 10x
STD set at 410ms STD set at 320ms
0,6 0,6
0,4 0,4
0,2 0,2
0,1 0,1
0,1 0,2 0,4 0,6 1 2 3 4 6 10 20 30 40 60 100 0,1 0,2 0,4 0,6 1 2 3 4 6 10 20 30 40 60 100
x Sensor rating Is x Sensor rating Is
B.23
Record Plus
Electronic trip units
FK frame
SMR1 range
This easy-to-use trip unit with overload and selective
SMR1e, s and g types are designed to allow the user to
short-circuit protection is equippeed with an overload
conveniently tailor his protection to meet individual
signalling option and has a built-in temperature sensor
circuit requirements. The available options include
to prevent the breaker and electrical components in its
adjustable overload pickup values, overload trip time
immediate vicinity from overheating. The 4 pole units are
characteristics, short time pickup circuit values, short
equipped with a switchable neutral protection option,
time delay circuit trip times and energy values. The trip
allowing the user to set the neutral at 0, 50 or 100% of
unit can be equipped with a ground-fault protection and
the phase ratings.
provides a flexible solution to all protection scenarios.
Overload protection LT (long time) sum of these values exceeds the set current thresholds for a
Trip units
The Long Time or overload protection is adjustable from 0.4 period of time greater than the set time delay, the breaker
to 1 x the chosed sensor ratings in 8 steps. The SMR1e has is tripped.
a fixed time band of 5seconds at 7.2 x Ir whilst the SMR1s The Ground Fault protection option is adjustable from
and g variants have a choice of 5 time bands (LTD) each 0.1 to 1 x the chosed sensor ratings in 4 steps. The user can
designed to match specific load characteristics. (For time also define one of 4 delay time bands (GFD) designed to
band classes see EN 60 947-4.1). allow selectivity between different sensor ratings. The
All devices are equipped with three LED's for signalling groundfault device is available in the SMR1g trip unit type.
purposes.
A green LED that indicates that the trip unit is powered up Short-circuit Protection I (instantaneous)
and is measuring and operating correctly. (30% of chosen Offerering a protection against short-circuits the
sensor rating). Instantaneous protection is set at a fixed value depending
A A yellow LED that will astart to blink at 95% of the set Ir on the chosen frame/ contact size. The I device has no time
current (3 flashes a second) when the current level reaches delay band so that the breaker trips as immediatley when
105% of the Ir setting and a trip is imminent the LED will the set threshold is reached. The fixed instanatneous (I) is
light up constantly. set at a current value allows discrimination between
B An over temperature in the trip unit is clearly indicated on different frame sizes and at a level that limits the current
the breaker front face. On the SMR1s and G variants a over and thermal stress in the protected circuit
temperature will trip the breaker.
C Zone Selective Interlock
A device that allows the user to achieve selectivity
combined with the fastesrt possible fault reaction time. With
connected ZSI the SMR1s and SMR1g trip unit will always
D trip the breaker as quickly as possible, ignoring the time
delays set by means of the STD or GFD devices. However
when a ZSI signal is recieved from a downstream breaker
E Short-circuit Protection ST (short time)
equipped with an SMR1a, 1g and 2 the STD or GFD of the
upstream device reverts to wherever the adjustment is set.
Offerering a selective protection against low value short- The Ground Fault and Short Time Zone Selective Interlock
circuits the Short Time protection is settable from 1.5 to 10 x signals are shared on one in/out put .
F the adjusted LT protection (Ir). The device only works when auxiliary power is present and
The SMR1e has a fixed time band of 50 milliseconds, a operates up to a distance between breakers of 1 kilometer.
setting that provides discrimination with downstream FG The use of shielded cable is required. A maximum of five
devices. SMR 1s, g or SMR2 trip units can be linked in this manner.
G Tthe SMR1s and g variants have a choice of four time (not available in the SMR1e)
setting bands (STD), designed to allow selectivity between
different breaker sizes. Here the STD device can be set to an
X 'energy curve mode' that changes the reaction of the device
from a fixed delay and reaction time value when the set
current level is reached to a reaction time that depends on
the energy flowing in the circuit.
B.24
Record Plus
Use and Testing Connection of trip unit
Each SMR1e, s or g trip unit comes with a transparent, Each SMR1 s or
tamper-free (sealable) cover, this to prevent unauthorized g trip unit has a
manipulation of the breaker settings. The device is connector
supplied with an electronic actuator coil that fits into a located on the
pocket in the breaker housing and is then connected to the right side of the breaker. This connector is normally hidden
trip unit. In order to verify a correct operation of the behind a break-away cover and is required to connect the
combination a simple test device is available to test the following:
assembly. Auxiliary power supply (24V DC), ZSI in and out,
We strongly recommend the use of this test device. long time pre-alarm signal, connection of external CT for
4 pole groundfault on three pole breakers.
SMR1 - FK frame
FK frame Electronic trip unit overview
In LT ST Neutral protection
pick-up band 1.05÷1.3 Ir pick-up band ± 20% Im Switchable type
[A] Ir setting min [A] max [A] Im settingmin [A] max [A] 4P4T 4P 3TN 4P3T
protected
FK800 800 320 800 480 8000 =Ir =Ir/2
SMR 1e N H L FK1250 1000 0.4 x1 In 400 1000 1.5-10 Ir 600 6000 =Ir =Ir/2
not
1250 in 8 steps 500 1250 in 8 steps 750 12500 =Ir =Ir/2
FK1600 1600 640 1600 960 16000 =Ir =Ir/2
In LT ST Neutral protection
pick-up band 1.05÷1.3 Ir pick-up band ± 20% Im Switchable type
[A] Ir setting min [A] max [A] Im settingmin [A] max [A] 4P4T 4P 3TN 4P3T
protected
FK800 800 320 800 480 8000 =Ir =Ir/2
FK1250 1000 0.4 x1 In 400 1000 1.5-10 Ir 600 6000 =Ir =Ir/2
not
1250 in 8 steps 500 1250 in 8 steps 750 12500 =Ir =Ir/2
FK1600 1600 640 1600 960 16000 =Ir =Ir/2
SMR 1s N H LTD(1) STD(2)
Setting min max Setting min max
[sec.] [sec.] [msec.] [msec.]
10
20
8
16
12
24
0.1
0.2
0.095
0.175
0.17
0.29
A
30 24 36 0.3 0.255 0.41
In LT ST Neutral protection
pick-up band 1.05÷1.3 Ir pick-up band ± 20% Im Switchable type
[A] Ir setting min [A] max [A] Im settingmin [A] max [A] 4P4T 4P 3TN 4P3T B
protected
FK800 800 320 800 480 8000 =Ir =Ir/2
FK1250 1000 0.4 x1 In 400 1000 1.5-10 Ir 600 6000 =Ir =Ir/2
not
1250 in 8 steps 500 1250 in 8 steps 750 12500 =Ir =Ir/2
n p
FK1600 1600 640
LTD(1)
1600 960
STD(2)
16000 =Ir =Ir/2
C
Setting min max Setting min max
[sec.] [sec.] [msec.] [msec.]
SMR 1g * N H 5 4 6 0 0.015 0.05
10
o 8 12 0.1
q 0.095 0.17 D
20 16 24 0.2 0.175 0.29
30 24 36 0.3 0.255 0.41
GF GFD(2)
pick-up band ± 20% Im
Ig settingmin [sec.] max [sec.]
Setting min
[msec.]
max
[msec.] E
r 80 1000 0.1 0.095 0.17
0.1 x1 In 100 1250 0.2 0.175 s 0.29
in 4 steps 128 1600 0.3 0.255 0.41
F
(1) At 7.2 x Ir : Min. is minimum settable delay: Max: Is maximum total tripping time.
(2) At set value : Min. is minimum settable delay: Max: Is maximum total tripping time.
B.25
Record Plus
Time Current Curves
FK frame
Minutes
Seconds
Minutes
Seconds
10 Ist set a 6 x Ir 10
6 6
4 4
2 2
ST set at 10x
1 1 STD set at 300ms
0,6 0,6 I2T OFF
Trip Time
Trip Time
0,4 0,4
0,2 0,2
ST set at 1.5x
1,5x
0,1 0,1 STD set at 30ms
I2T =OFF
OFF
0,06 0,06
0,04 0,04
A 0,006
0,004
0,006
0,004
I2T = ON STD bands set at:
300ms, 200ms,
100ms or 0ms
0,002 0,002
I2T = OFF
0,001 0,001
0,1 0,5 1 2 3 4 5 6 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.2 10 20 30 40 60 100
B x Sensor rating Is (800A or 1600A) x Sensor rating Is (800A or 1600A)
C 10000
Breaker FK1250 / SMR1e 1000 and 1250A
10000
Breaker FK1250 / SMR1s 1000 and 1250A
120 120
100 6000 100 6000 LT set at 1
80 80
60 4000 Set at 1 x sensor rating 60 4000 Ir=1000 or 1250A
50 50 LTD set at:
40 Ir=1000A or 1250A 40
2000 2000
D 30
20
1000
Ist set a 10 x Ir
30
20
1000
Class 30
Class 20
Class 10
10 600 10 600 Class 5
8 8
6 400 6 400
5 5
4 4
3 200 3 200
E 2
100
2
100
1 60 1 60 LT set at 0,4 x s-rating
40 Set at 0.4 x sensor rating 40 Ir=400A or 500A
Ir=400A or 500A Set at 1 x sensor rating ST set a 1.5 x Ir
20 20 STD set at class 5
Minutes
Seconds
Minutes
Seconds
2 2 ST set at 10x
G 1
0,6
1
0,6
STD set at 300ms
I2T OFF
Trip Time
Trip Time
0,4 0,4
ST set at 1.5x
0,2 0,2 STD set at 30ms
I2T OFF
X 0,1
0,06 1250A type
0,1
0,06 1250A type
0,04 0,04
1000A type 1000A type
0,02 0,02 STD bands set at:
300ms, 200ms,
0,01 0,01 100ms or 0ms
0,006 0,006 I2T = ON STD bands set at:
0,004 0,004 300ms, 200ms,
100ms or 0ms
0,002 0,002
I2T = OFF
0,001 0,001
0,1 0,5 1 2 3 4 5 6 10 20 30 40 60 100 0,1 0,5 1 2 3 4 5 6 7.2 10 20 30 40 60 100
x Sensor rating Is (1000A or 1250A) x Sensor rating Is (1000A or 1250A)
B.26
Record Plus
Time Current Curves
SMR1 - FK frame
4
100ms 3 200
3 200ms 2
500ms 100
1000ms 1 60
2 40
Seconds
20
Minutes
Seconds
10
6 Set at 5 x In
4
1
0,9 2
0,8
0,7 1
0,6 Set at 10 x In
Trip Time
0,6
Trip Time
0,4
0,5
0,2
0,4 0,1
0,06
0,3 0,04
0,02
0,2 0,01
0,006
0,004 A
0,002
0,001
0,1
0,1 0,5 1 2 3 4 5 6 10 20 30 40 60 100
0,1 0,2 0,4 0,6 0,8 1
x Set LT current Ir
2 3 4 5 6 7 8 10
x Nominal Current In B
10000
Breaker FK1250 / Mag Break 1250A C
120
100 6000
80
60 4000
50
40
2000
30
20
1000
Thermal Withstand of Breaker:
FK800: max in Class 10 & 30: 800A D
FK1250: max in Class 10 & 30: 1250A
10 600
8
6 400
5
4
3 200
2
100 E
1 60
40
20
Minutes
Seconds
10 F
6
Set at 5 x In
4
2 Set at 10 x In
1
0,6
G
Trip Time
0,4
0,2
0,1
0,06
X
0,04
0,02
0,01
0,006
0,004
0,002
0,001
0,1 0,5 1 2 3 4 5 6 7.2 10 20 30 40 60 100
x Nominal Current In
B.27
Record Plus
Electronic Trip Units
Long time module SMR1 (FAMLT)(1) Communication & contact module SMR2 (FAMECM)
This external DIN-rail This external DIN-rail
mounted device with mounted device with
modular dimensions is modular dimensions is
directly connected to the directly connected to the
SMR1electronic trip unit . SMR2 electronic trip unit .
The device is equipped with It is a multi functional unit
a NC 1A/400V AC contact acting as an interface
that opens to a signal between the breaker and
which indicates that a LT the communication network.
Trip units
trip will shortly be initiated To use the communication option the FAMECM module
by the SMR1. requires an auxiliary supply of 24V DC.
The SMR1 emits this before
a trip action is initiated. When set to motor protection The device is also equipped with four NC 1A/400V AC
this occurs 0.5 seconds before the tripping event and contacts that can provide the following outputs:
at 0.05 seconds when set to line protection. Contact is - Breaker trip reason
reset when breaker trips. (Overload (LT) OR Short Circuit (ST/I )
- Load shedding device contacts.
Test kit SMR1 & SMR2 (FAT) and SMR1e,s,g (FNT) Channel 1 AND Channel 2
Designed to test the
actuator trip unit
combinations the
A device is plugged
into the test jack on
the trip unit front
B face. Just remove
the test jack cover,
insert and plug in
the test device.
C Releasing the push
button on the tester FAT front should now initiate a trip
event . The tester requires a 9V battery and is also
equipped with a battery status indicator.
D FNT initiates a trip event when the push buttom is
depressed more than two seconds. It requires an
external 9V supply.
E
Rating plug tool SMR1 & SMR 2 (FAR)
A rating plug can be
removed by using two small
F screwdrivers.
In case of repeated removal
the Record PlusTM rating
G plug removal tool is advised
to enhance the ease and
safety of this operation.
X
(1) Use of an RC suppressor is recommended.
(See Controls and Automation catalogue)
B.28
Record Plus
Trip units
Trip units
chosen rating (FE and FK frame). limited. (see dotted line)
The unit is designed to protect the lines and/of loads The unit is primarily designed to be used with thermal
present in standard circuits. relays in motor protection circuits.
LTMD - Line thermal magnetic, selective type SMR1 (e)- Selective Electronic Protection(2)
This trip unit offers A trip unit designed to
overload and short- offer a overload (LT) and
circuit protection. short-circuit protection
The overload protection (ST). The overload
is adjustable from 0.8 to protection is adjustable
1 x the chosen rating from 0.4 to 1 x the
whilst the short-circuit chosen rating and has A
protection is set at 10 x two protection bands
the chosen rating (LTD), one for line
(FD frame) or adjustable protection and one for
from 5 to 10 x the motor protection (class
B
chosen rating (FE frame). 10)(1). To ensure full discrimination the short-circuit
The unit is designed to offer discrimination with protection has a current dependant
downstream protection devices. It also protects the fixed time setting that varies per frame size. C
lines and/of loads present in standard circuits. The device is adjustable from 2 to 13* x the set LT
current value.
GTM - Line thermal magnetic The unit is designed to protect all circuit types and to
A trip unit de signed to offer a high level of discrimination with downstream D
offer overload and devices.
short-circuit protection.
The overload protection SMR2 (1s & 1g) - Enhanced Electronic Protection(2)
is adjustable from 0.8 to A trip unit designed to
E
1 x the chosen rating offer a overload (LT) and
whilst the short-circuit short-circuit protection
protection is set at (ST). The overload F
about 4 x the chosen protection is adjustable
rating (FD frame) or from 0.4 to 1 x the
adjustable from 2.5 to chosen rating and has
5 x the chosen rating (FE frame). multiple protection G
Due to its low short-circuit current setting the unit can bands (LTD). The short-
be used to protect long cable runs or to provide circuit protection (ST) is
generator protection. adjustable from 2 to 13 X
x the set LT value and has multiple protection bands
(STD). The short-circuit protection can also be set to an
energy mode. The unit is designed to protect all circuit
types and to offer a high level of discrimination with
downstream devices. Different modules allow the user
to expand the device including groundfault , load
shedding and communications etc.
B.29
Just rel
Record Plus
Internal Accessories
C.4 Releases
External Accessories
Versions
Installation
Connections
Technical data D
C.32 Standard connection terminals
y on us
Numerical Index X
C.1
Record Plus
Internal accessories
Auxiliary contacts
FE & FG frame
Components & accessories
Auxiliary contact blocks are coveniently fitted into an go through channels in the breaker rear. Once this is
auxiliary-device compartment , accessible by removing done the wiring can be stripped and easily connected to
the breaker cover. This fully insulated compartment has the box terminals on the internal accessories. These
several pouches, a number of which are reserved for terminals are designed to connect wiring up to 2.5 mm2.
contact blocks. To allow for a logical and traceable To identify the correct mounting position within the
schematics each contact block has a pre-defined accessory compartment symbols are moulded into the
position within the auxiliary device compartment breaker and contact housing.
indicated by a symbol printed both on the breaker case For Auxiliary switches suited for mounting on the right
and on the auxiliary device itself. and on the left .
External wiring can be brought into the accessory For Bell Alarm switches; Mechanism operated types
compartment through - specifically designed and Trip unit operated types .
positioned - break-out openings in the breaker lid or can
set of codes that indicate the number of the device 3 versions of bell alarm mechanisms are available:
when it is mounted in the breaker. eg. 1 or 2 + - FABAM10 bell alarm mechanism NO for FE and FG
D The combination of these two codes provides a stan- frame
dardized coding system of each connection point(1). - FABAM01 bell alarm mechanism NC for FE and FG
eg. 15 or 26 frame
- FABAM11 bell alarm mechanism (change over) only
E FAS/CA (open - closed indication) for FD frame
They indicate the breaker contact status (open/closed). (Is delivered with 0.75 mm2 cables of 60 cm length).
The contact is mounted in a simple click-in block and is
F available in 4 different versions:
- FAS10L auxiliary contact left mounted NO
- FAS01R auxiliary contact right mounted NC
- FAS10L auxiliary contact left mounted NO
G - FAS01R auxiliary contact right mounted NC
To indicate the breaker position in the drawout chassis
(see page C.23 and C.24) similar contact blocks are
used, available in two versions:
X - FAS10D auxiliary contact NO
- FAS01D auxiliary contact NC
C.2
Record Plus
BAT/CD (Bell alarm trip unit) Performance
Indicates that the breaker has tripped due to one of the
following cases: The contacts offer a combination of a high thermal
- the trip unit has operated (overload or short circuit) current rating and can be used down to typical PLC
- an RCD operation (earth fault) operating levels of 12V 5 mA, AC/DC. The contacts are
The contact is a simple click-in block and can only be placed self-reansing and offer a life span equivalent to or
in the BAT position inside the accessory compartment exceeding that of the breakers. The values mentioned
(indicated by the symbol ). By using a combination of here have been determined in accordance with the
the BAM and BAT contacts it is possible to discriminate EN 60947-5-1 standard.
between the kind of fault the breaker has reacted to.
4 versions are available:
AC [A] DC [A]
Internal accessories
for general use:
- FABAT10 bell alarm trip NO FAS BAT BAM BAM FAS BAT BAM BAM
(no/nc) (no/nc) (co) (no/nc) (no/co) (no/nc) (co) (no/nc)
- FABAT01 bell alarm trip NC
for use in FE frame thermal magnetic and magnetic ≤ 24V 10 10 10 10 2.5 2.5 4 2.5
48V 10 10 10 10 1.4 1.4 0.5 1.4
only types: 60V 10 10 10 10 1 1 0.3 1
- FEBAT10 bell alarm trip NO 110V 6 6 6 6 0.55 0.55 0.2 0.55
220V 3 3 3 3 0.27 0.27 0.1 0.27
- FEBAT01 bell alarm trip NC 380V 2 2 2 2 0.2 0.2 - 0.2
500V 1.5 1.5 - 1.5 - - - -
600V 1.2 1.2 - 1.2 - - - -
FK frame
Optimized for use in the larger FK frame size mounting and The contact numbering of each device is indicated in the
A
connecting takes place in the same manner as in the FD, FE and shematics next to each photo. eg. 5 or 6
FG frame sizes. The contact blocks are of the change over type
The intermediate cover of the breaker has a separate set
(form C) and are available in easy to mount click in devices with a
of codes that indicate the number of the device when it is B
bell alarm contact or auxiliary switch. A maximum of three
mounted in the breaker. eg. 1 or 2 +
auxiliary swiches and one bell alarm contact can be mounted.
To indicate the breaker position in the drawout chassis (see page The combination of these two codes provides a
C.23 and C.24) a similar contact block is used.) standardized coding system of each connection point . C
eg. 15 or 26
6 8
G
5
X
Performance
AC [A] DC [A]
FAS (co) BA (co) FAS (co) BA (co)
The values mentioned here have been
≤ 24V 10 10 2 2
determined in accordance with the 48V 6 6 1.5 1.5
EN 60947-5-1 standard and apply for 60V 6 6 1 1
inductive loads. 110V 4 4 0.5 0.5
220V 3 3 0.25 0.25
400V 1.5 1.5 - -
C.3
Record Plus
Internal Accessories
Releases
Shunt and undervoltage releases can be fitted easily and go through channels in the breaker rear.
quickly in a specifically designed accessory Once this is done the wiring can be stripped and easily
Components & accessories
compartment which is accessible by removing the connected to the box terminals on the internal
breaker lid. This fully insulated compartment has several accessories. These terminals are designed to connect
pouches one of which is reserved for a shunt or wiring up to 2.5 mm2.
undervoltage release indicated by a symbol printed in The devices are designed to trip the breaker when its
the breaker case and on the auxiliary device itself. contacts are closed and the handle indicates the "On"
External wiring can be brought into the accessory position. When the breaker contacts are open and the
compartment through - specifically designed and breaker handle indicates "Off" or "Trip" activating the
positioned - break out openings in the breaker lid, or can releases will have no effect .(1)
FE & FG frame
B
The Record PlusTM shunt and undervoltage releases are When the breaker is in the "ON" position and the
common for all frame sizes up to 630A and all offer a undervoltage release is deactivated the breaker will trip
unique combination of low power consumption and a and its contacts will open. In de-energized status the
C kiss-free, lock out operation. Most types are common device prevents the breaker contacts from moving and is
for equivalent AC and DC ratings and all are available suitable for use as a lock-out coil. The connection clamps
in a wide range of voltages. When the breaker is in the are marked D1 and D2. De-energization of the device or a
D "ON" position and the shunt trip is activated the breaker drop in its supply voltage to a value below the mentioned
will trip and its contacts will open. The device can be lower voltage limit will activate the device. To prevent
constantly activated at its nominal voltage allowing it to voltage-dip-driven nuisance tripping an undervoltage
be used as a lock out coil. The connection clamps are release with time delay is available. An external DIN-rail
E marked C1 and C2. Switches, relay contacts and push mountable box contains a time delay unit with settable
buttons can be used to operate the shunt release. The use timings and is linked up with a DC UV undervoltage
of illuminated push buttons is limited by the power that release. This version is only available for an AC voltage of
F these lamps require to operate and the value that the
shunt release requires to trip. Here the maximum total
230/240V.
Voltage operation band (all types)
consumption of the lamps may not exceed 2mA. deactivates between 0.35 - 0.7 Un
Voltage operational band 0.7 - 1.1 Un activates between 0.85 - 1.1 Un
G Minimum pulse duration 10 msec minimum reaction time 10 msec
Total intervention time ≤ 50 msec total intervention time (undelayed type) ≤ 50 msec
delayed version (extra delay) settable 100 to 250 msec
X
Shunt release - Performance Undervoltage releases - Performance
Current consumption Power consumption Current consumption Power consumption
Voltage rating Voltage rating
mA mW/mVA mA mW/mVA
inrush hold inrush hold inrush hold inrush hold
C.4
Record Plus
Internal accessories
FK frame
B
When the breaker is in the "ON" postion and the shunt trip When the breaker is in the "ON" position and the
is activated the breaker will trip and its contacts will open. undervoltage release is deactivated the breaker will trip
The device can be constantly activated at its nominal and its contacts will open. In de-energized status the
voltage allowing it to be used as a lock out coil. device prevents the breaker contacts from moving and is
C
The connection clamps are marked C1 and C2. suitable for use as a lock-out coil. The connection clamps
Switches, relay contacts and push buttons are used to are marked D1 and D2. De-energization of the device or a
operate the shunt release. drop in its supply voltage to a value below the mentioned D
Voltage operational band 0.7 - 1.1 Un lower voltage limit will activate the device. To prevent
Minimum pulse duration 10 msec voltage-dip-driven nuisance tripping an undervoltage
Total intervention time ≤ 50 msec release with time delay is available. An external DIN-rail
mountable box contains a time delay unit with settable E
timings and is linked up with a DC UV undervoltage
release. This version is only available for an AC voltage of
230/240V. F
voltage operation band (all types)
deactivates between 0.35 - 0.7 Un
activates between 0.85 - 1.1 Un
minimum reaction time 10 msec G
total intervention time (undelayed type) ≤ 50 msec
delayed version (extra delay) settable 100 to 250 msec
X
Shunt release - Performance Undervoltage releases - Performance
Current consumption Power consumption Current consumption Power consumption
Voltage rating Voltage rating
mA mW/mVA mA mW/mVA
inrush hold inrush hold inrush hold inrush hold
C.5
Record Plus
External accessories
A Record PlusTM circuit breaker can offer protection on the RCD the breaker connected to the device is
against earth leakage currents by using an add-on tripped.
Components & accessories
residual current device (RCD). A line of three and four The RCD unit´s electrical power is supplied by the line
pole completely integrated add-on devices are available voltage of the breaker it is linked to. By use of a multi-
as side mounted models (FD frame size) or as units that phase bridge the design still works when one phase and
are fitted below the trip unit of the breaker the neutral is present . A pouch on the RCD allows one to
(FD, FE and FG frame sizes). In all cases the RCD unit place one BAT contact NO or NC which allows a remote
interfaces directly with the circuit breaker without the signal on earth faults.
use of any secondary wiring or connections. A Record PlusTM breaker and an RCD combination can be
Each RCD has a sensor placed around the phase and connected like any stand-alone breaker and are
neutral current paths that detects the vectorial sum of available as fixed or plug-in devices. The mains
the phase and neutral currents. When this sum is no connection interface of the RCD is an exact replica of the
longer zero it is assumed that current is flowing to earth breaker connection area, thus allowing the use of all
(residual current). If this value exceeds the threshold set standard breaker terminals.
Designed to meet the latest IEC 947 (industrial), The FD-frame RCD is available in two versions: for
IEC 1009 (residential) and the IEC 755 standards, mounting on the right hand side of the breaker or for
Record PlusTM RCDs are available in a version suited for mounting below the trip unit of the breaker. The side
side or bottom mounting as three and four pole units. mounted type is available in two versions. The first one
The tamper free setting area illustrated below is comes with a multifunctional DIN-rail mounting kit
common for the whole line and includes a mechanical including a connection kit to link up the breaker and the
and an electrical test option. RCD. The connection kit allows the user to feed the
breaker and RCD assembly from a multitude of
A 1. Dielectric plug directions while placing the RCD up- or downstream.
2. Electrical test The second version of the side-mounted RCD is designed
3. Reset for screw mounting and comes with a simplified
B 4. Position indicator
5. Mechanical test
connection set (see sketch). Both side mounted devices
are designed to accommodate a
45 or 64 mm cover plate cut-out. This allows usage in an
environment with other DIN-modular devices or with
C other breakers.
The mechanical test button tests the mechanical
operation of the breaker and RCD unit without power,
whereas the electrical option tests both the electrical
D and mechanical operation of the device. In order to
allow for a dielectric test of the breaker and RCD
combination without damaging the electronics, a so
E called "dielectric disconnect plug unit" is placed within
the setting area. All devices have a setting area with a
standard front cut-out of 45 mm. The device has The screw mounted type that only allows for two
numerous current and time settings and an override connection options is depicted on the right .
F blocking the time settings when set to 30mA. The
devices are class A , surge resistant (500A 8/20
mircoseconds) and are finished with a transparent ,
G tamper-free cover.
C.6
Record Plus
Programme overview
FDQI or S FDQ(1) FEQ(1) FEQ(1) FGQ(1)
FD frame side mounted FD frame mounted FE frame mounted FE frame mounted FG frame mounted
below breaker(1) below breaker(1) below breaker(1) below breaker(1)
External accessories
Number of poles 3-4 3-4 3-4 3-4 3-4
Delay at 2 Idn [msec] Inst-60-150-300-600 Inst-60-150-300-600 Inst-60-150-300-600 Inst-60-150-300-600 Inst-60-150-300-600
Total tripping time 40-100-190-340-640 40-100-190-340-640 40-100-190-340-640 40-100-190-340-640 40-100-190-340-640
at 2 x Idn [msec]
Available voltages 220-440V / 440-690V 220-440V / 440-690V 220-440V / 440-690V 220-440V / 440-690V 220-440V / 440-690V
(AC..50/60Hz)
Idn setting [A] 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10 0.03 - 0.3 - 1 - 3 - 10
Selectivity
Selectivity overview
E
outgoing
Elfa Plus"S" F-Q RCD 60 ms F-Q RCD 150 ms F-Q RCD 300 ms F-Q RCD 600 ms
Idn (mA) 300 1000 300 1000 3000 300 1000 3000 300 1000 3000 300 1000 3000
incoming F
ElfaPlus 30 T T T T T T T T T T T T T T
Inst. Type 300 T T T T T T T T T T
1000 T T T T
ElfaPlus 30 T T T T T T T T T
"S" type 300 T T T T T T G
1000 T T T
FD-Q RCD 30 T T T T T T T T T T T T
set at inst. 300 T T T T T T T
1000 T T T
FD-Q RCD 30 T T T T T T T T T X
set at : 300 T T T T T T
60 msec. 1000 T T T
3000
FD-Q RCD 30 T T T T T T
set at : 300 T T T T
150 msec. 1000 T T
3000
FD-Q RCD 30 T T T
set at : 300 T T
300 msec. 1000 T
3000
C.7
Record Plus
External accessories
Rotary handles
Rotary handle for use through door or cover plate
C.8
Record Plus
External accessories
A special version is available equipped with two
normally open auxiliary contacts (FABAM10) that are
pre-mounted and pre-wired with leads of 0.75 mm2
and a length of 60 cm.
A handle and escutcheon is mounted on the door or An extra Ronis or Profalux key lock
panel front and connected to the breaker by an can be clicked into the handle
elongation shaft that goes into an adaptor box directly front, thus allowing one to lock the
installed onto the breaker front . The design allows for a breaker in the same manner as
total depth of up to 350 mm (from the back of the the padlocking device.
breaker mounted behind the door or panel and the The Ronis key locks are available in a number of versions:
door front). - A version where each lock has a different key number
The handle is available in grey for normal applications - A version where the user can choose one of six keys for
and in a yellow/red execution for machine-tool several locks
applications. Interlocks that prevent the opening of the
door while the breaker is "ON" (are standard). For A number of accessories are available to allow for
A
override operation see red indicators on euchenon specific applications of the device:
front . - To operate the push to trip from the door front an
accessory allowing for a Bowden cable can be fitted B
All Record PlusTM rotary handles have the same to the rotary handle adaptor (flex operator push to
standard "single hole" front door drilling and are trip)
specifically designed to tackle mounting issues as - An adaptor to allow the use of the device with a
"shaft droop" and tolerance in user drillings. drawout construction on the FE, FG,and FK frame C
sizes
Available in grey or in yellow/red the device is supplied - A "long shaft set" allowing for larger mounting
with an adaptor box for installation on the breaker depths than 350 mm (max. 600 mm) D
front , a mounting position definer, a shaft , a handle
with escutcheon for door or panel mounting and all
necessary fixation hardware.
E
C.9
Record Plus
External accessories
C.10
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.11
Record Plus
External accessories
Electrical operators
In order to allow a Record PlusTM circuit breaker to be An operating panel placed on the drive front allows one
operated electrically, front mounted electrical drives are to choose between two operational positions
Components & accessories
available. These drives are designed for easy mounting - electrical or manual.
onto the breaker front and offer operating times of The panel includes a padlocking or key-locking device in
75 milliseconds or lower. OFF position, the position indicators and a manual
A specifically designed electrical operator is available for operator.
each frame size (FD, FE, FG or FK) each of which has the The devices are connected by means of IPXXB box
same specific technical design features. terminals accessible from the breaker front and located
A Record PlusTM motor operator has three positions in the immediate vicinity of the terminals of the internal
"OFF", TRIP" and "ON", a three-wire connection scheme accessories. The box terminals allow for wiring with a
and is designed to be fast: all drives close within cross section of 0.5 to 2.5 mm2.
75 milliseconds.
Operation
FD and FE frame FG and FK frame
The Record PlusTM FD and FE frame drives The Record PlusTM FG and FK frame drives
are designed with the same front cut-out in the door or have a front escutcheon housing with all the necessary
panel and total breaker depth, thus allowing a side by operators, indicators and locking features:
side use of the devices. The drives have a front
escutcheon housing with all the necessary operators,
indicators and locking features:
A
O
A ON push-button O
A ON push-button
O
B OFF push-button O
B OFF push-button
O
C Manual / Automatic switch O
C Charging handle
O
D Padlocking device O
D Padlocking rack
O
E Position indicator "OFF"--"TRIP"---"ON" O
E Room for cylinderlock
O
F Local operating handle O
F Manual / Automatic switch
C.12
Record Plus
Mounting and Connection
Each drive comes fully mounted and only requires to
be screwed onto the front of the breaker after
removing the standard handle elongator.(1)
The connections are easily accessible and are placed
within the immediate vicinity of the accessory wiring
outlets. This allows for easy interconnection with other
internal accessories.
External accessories
Specifications
Operating times FD63 & FD160 FE160 & FE250 FG400 & FG630 FK800, FK1250 & FK1600
"On" - pulse received, breaker ON - by drive 50 millisec. 100 millisec. 50 millisec. 50 millisec.
"Off" - pulse received, breaker OFF- by drive 50 millisec. 100 millisec. 8 seconds 12 seconds
"Off" - pulse received, breaker OFF- by SHT/UVR release 50 millisec. 50 millisec. 50 millisec. 50 millisec.
"Reset" - Time between "OFF" and subsequent "ON" pulse 80 millisec. 80 millisec. 8 seconds 12 seconds
C.13
Record Plus
Schematics FD, FE & FG frame
Electrical Operator
Scheme A1 Scheme A2
Suitable for Non Automatic breakers (switch) Suitable for Non Automatic breakers (switch)
Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch.
Components & accessories
ph/+ ph/+
A1 A2 ON OFF
Switch or Relay
contact Connection needed Pushbuttons
on FG frame only
ON OFF
A2 A4 2 A2 A4 2
A1 1 A1 1
n/-
n/-
Scheme B1 Scheme B2
Suitable for standard circuit breakers without Shunt or Suitable for standard circuit breakers without Shunt or
Undervoltage release Undervoltage release
Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch. After a fault the breaker goes into 'tripped position'.
After a fault the breaker goes into 'tripped position'. The BAT/CD conatct then prevents further electrical
The BAT/CD contact then prevents further electrical operation.
operation. The breaker MUST be reset locally by hand.
The breaker MUST be reset locally by hand.
A ph/+ ph/+
B1 B2 ON OFF
Switch or Relay
contact Connection needed
Pushbuttons
on FG frame only
ON OFF
B A2 A4 2 A2 A4 2
A1 1 A1 1
C 95 96 95 96
Bell Alarm Contact (BAT)externally linked Bell Alarm Contact (BAT)externally linked
allows local/manual RESET only allows local/manual RESET only
n/- n/-
D
Scheme C1 Scheme C2
Suitable for standard circuit breakers with Shunt or Suitable for standard circuit breakers with Shunt or
Undervoltage release Undervoltage release
E Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch. After a fault the breaker goes into 'tripped position'.
After a fault the breaker goes into 'tripped position'. The BAT/CD contact then prevents further electrical
The BAT/CD contact then prevents further electrical operation.
F operation. The breaker MUST be reset locally by hand.
The breaker MUST be reset locally by hand. If tripped by 'other means' an automatic reset is
If tripped by 'other means' an automatic reset is initiated.
G initiated.
ph/+ ph/+
C1 FD FE/FG C2 ON OFF FD FE/FG
Switch or Relay 81 87 81 87
X contact
ON OFF
84 88
Connection needed
on FG frame only Pushbuttons
84 88
C.14
Record Plus
Schematics FK frame Electrical
Operator
Scheme A3 Scheme A4
Suitable for Non Automatic breakers (switch) Suitable for Non Automatic breakers (switch)
Control circuit operated with a relay contact or a Control circuit operated with push buttons
switch. The use of a shunt trip is mandatory.
A3 A4
External accessories
ph/+
ph/+ ph/+
ON OFF
Switch or Relay
contact Pushbutton
Pushbutton
ON OFF External link
External link
1 3 4 6
1 3 4 6 C1
Motor operator
Motor operator
2 8 5 7
2 8 5 7 C2
Shunt
External link Release
External link
n/-
n/- n/-
Scheme B3 Scheme C4
Suitable for standard circuit breakers without Shunt or Suitable for standard circuit breakers with Shunt
Undervoltage release release
A
Control circuit operated with a relay contact or a Control circuit operated with push buttons.
switch. After a shunt trip OFF signal the breaker goes into
After a fault the breaker goes into 'tripped position' . 'tripped position' and is reset automatically. B
The BAT/CD contact then prevents further electrical On all other trip events the breaker MUST be reset
operation. locally by hand.
The breaker MUST be reset locally by hand.
C
B3 C4 External timer contact only
resets breaker after Shunt trip operation
ph/+
ph/+ ph/+
D
ON OFF
Switch or Relay
contact Pushbutton
n/-
External links
n/- n/- X
C.15
Record Plus
External accessories
Connectivity - 60 mm system
three and four pole
Components & accessories
Record PlusTM circuit breakers have been designed to be Based on these principles GE Power Controls have
installed easily and quickly with conventional means. devised a unique system that allows the user to mount
The devices can be screw mounted to a mounting plate and connect the breaker before the installation.
or clicked to a symmectrical DIN rail and connected with An adaptor device, specifically designed for the
busbars, cables, flex-bars and ring terminals in a Record PlusTM breaker line and incorperating all the
multitude of configurarations. However, if mounting and connection hardware, is fitted to the breaker using five
connecting the breaker can be cut down to a few simple, to six simple screws. Once mounted the adaptor is then
automateable tasks, installation can become easier and simply plugged on to a three or four pole busbar system
more cost effective. already installed in the switchboard.
D
As standard the busbar supports are delivered
prepared to receive busbar of cross section Busbar finishing
30 x 5 mm, but they can easily be adapted to each Insulating covers are available to protect the user from
E other dimension mentioned by an integrated spacing inadvertent direct contact with the busbar system.
element . These elements have a standard width of 50mm and
can be coupled laterally offering variable width in order
F By varying the distance between the supports it is
possible to build a three or four pole busbar system
to cover the busbar not yet covered by breakers or
feeding modules.
with the following short circuit ratings:
Endplate covers can be mounted to the busbar
G Busbar system supports in order to provide complete protection
against inadvertent contact to a busbar from the side.
Support Busbar size Peak Thermal
withstand Ipk withstand Icw
spacing (mm) (kA) (kA eff) 1 sec.
X
200 mm 20 x 5 46 21.9
20 x 10 50 23.8
30 x 5 58 27.6
30 x 10 63 30.0
300 mm 20 x 5 40 19.0
20 x 10 43 20.5
30 x 5 52 24.8
30 x 10 56 26.7
400 mm 20 x 5 35 16.7
20 x 10 37 17.6
30 x 5 47 22.4
30 x 10 49 23.3
C.16
Record Plus
The system
For the Record PlusTM FD and FE frame adaptors exist rated them to be removed as they were mounted.
at 160A (FD) and 250A (FE) and in a 3 and 4 pole version. Each adaptor is supplied with the necessary fixation
Designed to allow the use of the breaker at its full rated hardware and a terminal shield to cover the connection
breaking capacity of 150kA at 415V each unit is equipped between the breaker and the adaptor.
with a plug/hang on connection system allowing one to The breaker is mounted and connected to the adaptor by
place it on the busbar system in one simple operation. using two pre-tapped fixation points located at its lower end
The adaptors have been tested to meet the most stringent while its main terminals are used to connect and fix it at the
External accessories
requirements and are equipped with a mechanism allowing upper end of the adaptor.
Adaptor Finishing
The breaker and adaptor mounting is simple and easy. The system can be finished with a cover/trim plate that
The length of the 4 pole adaptor also allows the use of can be found in the GE Power Controls
a bottom mounted RCD. enclosure/systems catalogue. To allow for a standard
cut-out within the cover/trim plate a filler piece is
available in lengths of of 1.2 m. This filler plate is
adapted to the Record PlusTM standard front cut-out of
64 mm.
A
System
Each breaker is fixed on the adapter by means of two
pretapped screws at the bottom and its main terminals
B
at the top.
The breaker and adaptor combination is now quite
simply plug/hung on to the busbars, connecting and C
fixing the breaker in one simple operation.
To allow for a flush-front finishing the adaptors have
been designed to adapt to the difference in breaker
depth and can be used with the standard FD and FE D
frame sizes (FD type without DIN-rail adaptor).
The system can be finished with a cover/trim plate that
can be found in the GE Power Controls enclosure/ E
systems catalogue.
C.17
Record Plus
External accessories Two systems are available
Mechanical interlocking by equipping both devices with
a rotary handle and cylinderlocks with the same key
Changeover/Power transfer number. (2 locks one key)
systems
Components & accessories
A
Mechanical interlocking is possible for the following
breaker types and combinations
B Two 3 or 4 pole FE frames (10- 250A).
Two 3 or 4 pole FG frames (100- 630A).
Two 3 or 4 pole FK frames (320-1600A).
C One 3 or 4 pole FG frames (100- 630A)
&
One 3 or 4 pole FE frames (10- 250A).
One 3 or 4 pole FK frames (320-1600A)
D &
One 3 or 4 pole FG frames (100- 630A).
C.18
Record Plus
Automatic changeover
E plus model
To assure the continuity of electrical supply within a Is available for changeovers with two devices. In addition
low voltage installation it is desirable that on a to the standard E model features it allows for:
failure of the mains voltage supply a secondary - A generator start up command.
power source takes over. An automatic changeover - An adjustable time delay on the generator start
device transfers the power supply from the main command initiation.
power source to a secondary supply when a voltage - Two connections allowing the input of a signal indicating
monitoring device detects a failure in the mains that the supply of the generator set has reached it's
External accessories
voltage. nominal voltage. Only then will the mains device be
disconnected and the secondary device switched on.
The GEPC devices are available in several versions - An adjustable transfer and retransfer time between the
each tailored to the specific needs of the user and different power supplies.
the design of the installation. - Allows for the connection and disconnection of non
priority loads when switching to the secondary supply.
- Built in communication.
- A terminal that allows the input of a start order of the
generator set independent of the mains supply status.
Here a change over cycle is initiated transferring from
main to secondary supply.
- Adjustable cool down time of generator set.
A
Based on the differences in the configuration of the
power supply, complete systems are available for two
or three power sources(1). A two breaker system allows
B
for a power transfer between a transformer and a
generator set (or two transformers).
C
Controllers Controllers, performance
E model E plus model D
Controllers are available for change over systems Number of devices 2 2
with two breakers allowing for a number of power Positions Aut.- Man.- locked Aut.- Man.- locked
supply configurations. Each controller has a manual, Operating voltage 110 or 230V AC 110 or 230V AC E
Power consumption 18VA 18VA
automatic and locked position, a generator start up Mains voltage monitoring (1) Optional Optional
routine and a full set of pilot lights indicating the Time delay on generator set No Adjustable
start signal 0.1 to 60 sec.
status of the system. Time delay on transfer Fixed 10 sec. Adjustable F
command after mains return 0.1 to 15 min.
Remote order stop included included
Two basic controllers available: Remote transfer order No included
Remote retention of secondary No included
supply order G
E model Non priority load switching No included
Is available for change over systems with two devices. Cool down time gen. Set. Adjustable
0.1 to 60 min.
On a mains supply failure the mains device is Communication RS232 / RS485
disconnected and the secondary device switched on. X
When the mains supply returns, the controller keeps the (1) Optionally, a built-in net and/or generator voltage monitor can be
secondary supply on line for a preset time of 10 seconds. delivered with the controler
It then opens the secondary breaker and closes the mains
breaker. An emergency STOP order can be inputted on the
terminals that will switch both the mains and secondary
device to be switched OFF.
C.19
Record Plus
Automatic system with two
devices
The system consists of two electrically operated
Record PlusTM moulded case circuit breakers equipped
with a walking beam mechanical interlock and a con-
troller that can be mounted in the front of the door or
Components & accessories
Controller modes
A key operated switch (1) allows the selection of four
different operational modes:
LOCKED - all breakers remain in the position AUTOMATIC Depressing the push buttons that operate
attained before this mode was initiated the breaker in the manual mode have no
A - The push buttons are disabled. effect .
- All automatic transfer functions are non
functional. Mains supply fails
The system remains in its standby mode in
B MANUAL - Taking the conditions normally applied to
E model
and which the mains breaker is 'ON' and the
E model a transfer operation into account , the E plus model secondary supply breaker (generator) is
push buttons allow operation of the 'OFF'.
C breakers. As soon as a signal is received that the
- Pressing the generator 'ON' push button secondary supply voltage is available the
will only result in an operation of the mains breaker is opened and the secondary
breaker if the mains breaker is open and supply breaker closed.
D the generator is on line. (voltage present) If the secondary supply breaker does not
close on the first command, two further
E plus model On use of the E plus controller, pressing the closing orders will be given. If the breaker is
E generator 'ON' push button will give the still unable to close a fault is indicated.
generator an order to start . If second voltage E plus model Issues a start command to the secondary
is available an automatic transfer will be supply. This can be delayed up until
initiated from mains to generator supply. 60 seconds after mains failure.
F This operation can be cancelled by Mains supply returns
depressing the generator 'OFF' or mains 'ON' E model The system remains in its secondary mode.
push button. The secondary breaker (generator) is 'ON'
- Pressing the mains 'ON' push button will and the mains supply breaker is 'OFF' for a
G E model
only result in an operation of the breaker period of 10 seconds. This delay is re-
if the generator breaker is open and the instated if the mains supply fails within this
mains is on line. (voltage present) time frame.
X After this delay the secondary supply
E plus model On use of the E plus controller, pressing the breaker is opened and the mains breaker
mains 'ON' push button will initiate a closed. If the mains breaker does not close
automatic transfer from generator to mains on the first command, two further closing
supply. This operation can be cancelled by orders will be given. If the breaker is still
depressing the mains 'OFF' or generator 'ON' unable to close a fault is indicated.
push button. If the mains voltage is not E plus model Basic operation is the same. However the
present , the cycle will not be carried out . 10 second delay is upgraded to one that is
adjustable from 0 to 15 minutes.
C.20
Record Plus
Pilot lights System performance
ORANGE (4) Mains voltage present .
ORANGE (5) Secondary supply voltage available.
Breaker operation
Push-buttons with pilot lights
GREEN (3) Constantly on: Mains breaker is 'OFF' Operating times (minimum) FE frame FG frame FK frame
Blinking:
Transfer to secondary supply underway Opening (trip) 75 ms. 50 ms. 50 ms.
-OR- Closing (ON) 75 ms. 50 ms. 50 ms.
Reset plus OFF 2 sec. 5 sec. 12 sec.
Fault detected on closing mains breaker
When the key selector switch is in it's
External accessories
manual position the push-button allows one Changeover operation
to switch the mains breaker 'OFF'
Operating times (minimum)
GREEN (6) Constantly on: Secondary supply breaker is
The sum of the operating times of the chosen breaker combination
'OFF' Blinking: plus the time values of the controller.
Transfer to mains supply underway -OR-
Fault detected on closing Secondary
supply breaker Functional diagram
When the key selector switch is in it's In 3 ATS the diagram is adapted to selected type
manual position the push-button allows one OL/SC trip AT stays on stand-by
blinking lit
to switch the Secondary supply breaker
'OFF'
Automatic Blocked Manual
RED (2) Constantly on: Mains breaker is 'ON'.
Blinking: Mains breaker has tripped due to
an overcurrent . (fault mode) Mains Mains P. B. P. B. P. B. P. B.
Voltage Start voltage "Open "Open "Close "Close
When the key selector switch is in it's available Generator defaults Mains" Gen" Mains" Gen"
manual position the push-button allows one Gen
to switch the mains breaker 'ON' Gen. voltage
breaker available
RED (7) Constantly on: Secondary supply breaker is "ON"
'OF'. Waits
10"
waits
0,5"
A
Blinking: Secondary supply breaker has
Gen. Gen Mains
tripped due to an overcurrent . (fault mode) Opens
breaker
Opens Mains b. breaker. breaker.
Gen. Mains b. "OFF"
When the key selector switch is in it's breaker "OFF" "OFF" "OFF"
manual position the push-button allows one Closes Closes Open Open Closes Closes
B
Mains b. Mains Gen Mains Gen Mains Gen
to switch the Secondary supply breaker 'ON' "ON" breaker breaker. breaker. breaker. breaker. breaker.
waits
300"
Stops
Gen
Three
trials
Fault
blinkin
Three
trials
Fault
blinkin
C
lit lit
C.21
Record Plus
Versions
Plug-in
The Record PlusTM plug-in version allows quick, safe and contacts in the base are connected.
easy interchange of breakers. It is made up of a The Record PlusTM plug in version is available for:
Components & accessories
"standard" fixed-front-connection breaker, a set of plugs, FD frame sizes FD63/160 (maximum 125Amps)
a trip mechanism fitted to the breaker and a monoblock FE frame sizes FE160/250 (maximum 250Amps)
base into which the breaker is plugged. FG frame sizes FG400/FG630 (maximum 630Amps)
When the breaker is removed from the plug-in base it
trips automatically (main contacts open) before the plug- FD and FE frame sizes equipped with "bottom mounted
in contacts in the base are disconnected. RCD unit" can also be transformed into the plug-in
The breaker can be operated (closed and opened) when version. The mobile part of the plug-in version remains
removed from the plug-in base. On attempted insertion the same (plugs and trip mechanism do not change).
of a breaker in the "On" position into the plug-in base, The fixed plug-in base is of a different , elongated type
the Record PlusTM breaker trips before the plug-in and has a seperate catalogue number.
D
Mobile part Monoblock base
E The mobile part that is fitted The monoblock base can be
to the breaker is made up of a mounted to a backplate or on
multi-pole set of plugs that profiles and offers IPXXB
displace the standard front protection for front access.
F connection. It also includes a (FD - IP20, FE and FG - IP40).
trip interlock, that , when It is designed to have exactly
mounted, trips the breaker on the same connection profile
G its removal from the base and as the breaker it goes with,
thus allowing the installation
prevents re-insertion into the
base when the breaker is on. of all terminal shields and
The mobile part is supplied terminals that the standard
X with tamper free short terminal shields. breaker offers. These include rear and angular
connectors, spreaders, customized ring terminal
connectors and extenders.
C.22
Record Plus
Drawout
A drawout version allows one to visibly and positively The cradle allows for placing the breaker in one of three
disconnect the mains supply from the installation. Like positions:
on the plug-in device, interchanging breakers quickly, Connected: Main and auxiliary contacts are fully
safely and effectively is one of the key features of connected to the base
Record PlusTM drawout . It is made up of Test/Disconnected: Main contacts are disconnected.
a breaker ("standard" fixed front connection version), a Auxiliaries can be connected or disconnected. This allows
set of plugs and a trip mechanism that are fitted to the for a complete test of the secondary wiring/functionality
breaker, a monoblock base into which the breaker is without having the mains connected.
plugged and a metal support cradle. Remove: Main and auxiliary contacts are fully
disconnected from the metal support cradle and the
plug-in base, the breaker can be removed.
Versions
A
Mobile part
D
FE and FG frames sizes
The mobile part that is fitted The cradle is of a sturdy metal
to the breaker is made up of a construction and is supplied
multi-pole set of plugs that with an integrated standard E
displace the standard front plug-in base. All standard
connection. It also includes a terminal shields, terminals, the
trip interlock, that , when available accessories for the
mounted, trips the breaker on standard fixed front connection
F
its removal from the base and breaker, can be implemented.
prevents re-insertion into the These include rear and angular
base when the breaker is on. connectors, spreaders, G
The kit includes a sliding customized ring terminal
mechanism linking the breaker to its cradle. As with the connectors and extenders.
plug-in version tamper-free short terminal shields are
included in the kit . FK frames sizes X
The cradle and monoblock base
Cradle with monoblock base are combined to form one
The cradle and monoblock base combination can be integral moulded part . The unit
mounted to a backplate or on profiles and offers IPXXB is available with a front or rear
protection for access from the front of the cradle. It is connection facility that allows
designed to offer the same connection options as the the use of connection clamps
standard fixed front connection circuit breaker. available as accessories for the
standard fixed front connection
Remark: See following page for details on interlocks and cradle breaker.
execution.
C.23
Record Plus
Versions
C.24
Record Plus
Plug-in and Drawout versions
Accessories
Versions
connection points.The wiring can be passed through On withdrawing and inserting the breaker the 6 pole plug
specifically designed channels that lead from the and socket system only disconnects and connnects once
breaker rear into the accesory compartment . The the test position has been reached. This allowing for a test
socket part can be wired out from the base with wiring position without a seperate plug and socket. The FK socket
up to 2.5 mm2 (front access). Each unit has a total of 8 part can be wired out from the base with wiring up to
poles. The number of connectors that can be used per 1.5 mm2 (front access).
breaker frame size is as follows:
C.25
Record Plus
Installation
A Keylocking devices
B Record PlusTM moulded case circuit breakers can also be segments or to interlock one or more breakers. Keylocks
locked in their OFF position by the use of a Keylock. This to are available for all Rotary handle devices, electrical
allow users to work on installations or installation operators and draw-out systems.
C
Pad- and Keylocking options, applicable for Record Plus Breakers
D Overview Frame size Padlock Standard Specifically numbered Profalux key lock
Ronis key lock Ronis key lock
Fixed Removable
FD Frame A(1) A
Toggle operator FE Frame A(1) A
E Breaker locked in "OFF" position FG Frame A(1) A
FK Frame A(1) A
FD Frame S(1) A A A
Directly mounted rotary handle FE Frame S(1) A A A
Breaker locked in "OFF" position FG Frame S(1) A A A
F FK Frame S(1) A A A
FD Frame S(1) A A A
Through panel or door type of rotary handle FE Frame S(1) A A A
Breaker locked in "OFF" position FG Frame S(1) A A A
FK Frame S(1) A A A
G FD Frame S(1) A A A
Panel or door mounted rotary handle FE Frame S(1) A A A
Breaker locked in "OFF" position FG Frame S(1) A A A
FK Frame S(1) A A A
FD Frame S A A
X Electrical drive FE Frame S A A
Breaker locked in "OFF" position FG Frame S A A
FK Frame S A A
Drawout version FE Frame S A A
Locked in Disconnected/Test (2) FG Frame S A A
OR drawout position FK Frame S A A
C.26
Record Plus
Door flanges
In order to provide an IP40 protection degree of the The devices are available for cutouts with the toggle area,
breaker when mounted through a door or cover plate door breaker front face, motor drive front face or on RCD
flanges are used. A door flange also improves the operating panels. A second type of flange is used for
aesthetics of the cutout in the door and allows for higher rotary handles through door/cover allowing interlocks on
tolerances within the cutout. the device to function correctly.
Installation
3 and 4 pole breakers. screws
Type Type
Type
C
Rotary handle (1)
FD frame FDFE
Fixation via front with
FE frame FEFE
4 screws; is required to allow FG frame FGFE
use of the door lock in ON FK frame FNFE D
position with the through
door/panel rotary handle
type. Is available for:
E
Type
C.27
Record Plus
Installation
Terminal shields
Terminal shields are installed on the incoming or outgoing Record PlusTM terminal shields are equipped with a tamper
Components & accessories
side of the breaker thus achieving a heightened protection free sealing facility and come in sets of two. They are
degree, independent of the type of connection used. For available in a short or a long version and have been
fixed breakers with rear connnection or the plug-in or with- designed for use on the standard fixed front connection
drawble versions of the Record PlusTM breaker the installion breaker or on the base used for plug in breakers.
of short terminal shields is mandatory and they are nor- Each terminal shield is equipped with easy to remove
mally supplied as part of the kit. breakouts to facilitate the connection of the breaker.
B
Short terminal shields Long terminal shields
FD FE FG FK FD FE FG(2) FK
C
With two terminal shields 20 30 60 40 With two terminal shields 97 122 83 160
mounted, Breaker heighth is mounted, Breaker heighth is
increased by: (mm) increased by: (mm)
D
(1) The FK short type is only supplied with rear connection kit. (2) The FG type is of medium length. Special long and widened version
available on request.
C.28
Record Plus
FD frame adaptors
Mounting positions
seperately. fronts.
A
Side by side mounting with Adapator - Side by side
FE frame breakers mounting with ElfaPlus MCB's B
The FD frame DIN-rail adaptor has a second The FD frame has a 45 mm cut-out allowing it's use
application: when mounted with its DIN-rail mounting next to Elfa Plus MCB's and other modular devices. To
feature facing the breaker rear it serves as a heightner. bridge the diffference in depth between the FD frame C
This change in depth of the D frame allows side by side and the modular devices a special heightning kit is
mounting with E frames. When reversed the adaptor available in a standard length of 354 mm.
turns into a heightner that lifts the D frame, and all its
cut-outs up to the E frame level. The 64 mm cut-out of
D
the D and E frame now match up fully in height and
depth.
E
C.29
Record Plus
Installation
For the Record PlusTM FDS, FDN, FDH and FDL types the specifically to click in a circuit identification lable.
finishing covers are standard. By adding both these A set contains 20 units that are common for all frame
covers and the finger protection caps the breaker has a sizes.
protection degree of IP40.
C.30
Record Plus
Mounting positions
A Upstream
Installation
B C
A
Downstream
A= Allowed
N= Not allowed F
P= Use of phase separators is obligatory.
PB= Use of phase separators and backplate is obligatory.
(1) The use of the top cavity in the box terminal is mandatory.
(2) H & L versions only G
C.31
Record Plus
Connections
The Record PlusTM connection facilities have been stability assure an easy connection.
Components & accessories
designed with the user in mind. Each of the standard connection options described here
Easy access to the area where the conductor must be applies to the fixed breaker, its plug in or drawout base
placed, their generous dimensions and their inherent and the RCD associated with the frame size.
FD frame FE frame
The FD frame is equipped with box clamps allowing the The FE frame size has a connection area specifically
direct connection of one or two cables. The clamps can designed for the connection of busbars and/or cable
also be used with flat bars up to a width of 12 mm. All lugs. The connection area is designed to allow for
'non standard' connection terminals as extenders, rear maximum access to the front of the terminal. Standard
connections etc. are directly connected to these busbar sizes and cable lugs can be accommodated
standard terminals. The breaker is always supplied with without accessories.
the clamps fully open, and they are equipped with a The connection pads have through holes and are
mechanism that prevents them from inadvertently supported by a simple slide-in fully insulated part that
closing whilst connecting. contains one steel nut per connection point . The
connection bolts have an internal allen key profile
allowing for ease of use in the relatively confined area
just above the connection strap.
'Non-standard' connections as extenders are directly
A fitted onto the standard terminals. In other cases - like
rear connections - the slide-in part is completely
replaced.
F
FD frame box terminals FE frame with removeable cover
FD FE
G
1 cable S min/max [mm2] in top cavity Cu(1) 2.5 - 95(2) W max [mm] 25
2 cables S min/max [mm2] in 2 cavities Cu(2) 2.5 - 35 + t max [mm] 5
4 - 35 i1 max [mm] 11.5
Strippable length L [mm] 17.5 i2 max [mm] 9.8
X W max [mm] 12 Ø max [mm] 9.5
Torque (Allen key in breaker) (Nm max.) 8 L Distance to insulation (min.) 25
Torque (Allen key in breaker) (Nm max.) 25
(1) For aluminium conductors use external box clamps. W = Width of bar or ring terminal / lug
(2) For lower terminal cavity 4 - 70 mm2. t = Thickness of bar or lug
(3) On the FDC and FDE type the top cavity cannot be used. Total Ø = Hole diameter
connection capacity for the FDC and FDE type is thus 1 cable of
2.5 -95 mm2 in lower cavity.
C.32
Record Plus
FG frame FK frame
Connections
The FG frame size has a connection area specifically The FK frame has a connection area specifically
designed for the connection of busbars and/or box designed for the connection of busbars. For the FK800
clamps. The connection area is designed to allow for and FK1250 sizes the standard connection pads offer a
maximum access to the front of the terminal. The choice of the use of 2 M10 or 1 M12 bolt . The FK 1600
connection pads have through holes without screw type can use the same connection facility, but the use
thread and are supported by a simple slide-in fully of specifically designed extended connection pads is
insulated part that contains one steel nut per advised.
connection point . The connection bolts have an internal The estended connections allow the use of
allen key profile allowing for ease of use in the 2 M12 bolts.
relatively confined area just above the connection All 'non standard' connection options are fitted to the
strap. standard connection pads.
'Non-standard' connections as extenders are directly
fitted onto the standard terminals. In other cases - like
rear connections - the slide-in part is completely
replaced.
A
F
FG frame with removeable cover FK frame with removeable cover
FG FK
G
W max [mm] 32 W max [mm] 50
t max [mm] 12 t max [mm] 20
i1 max [mm] 19 i1 max using 2 x M10 [mm] 32
i2 max [mm] 17.5 i2 max using 1 x M12 [mm] 23
Ø max [mm] 11 Ø max [mm] 2 x 11 or 1 x 14 X
L Distance to insulation (min.) 33 Torque (Allen key in breaker) (Nm max. M10) 42
Torque (Allen key in breaker) (Nm max.) 42 Torque (Allen key in breaker) (Nm max. M12) 48
W = Width of bar or ring terminal / lug W = Width of bar or ring terminal / lug
t = Thickness of bar or lug t = Thickness of bar or lug
Ø = Hole diameter Ø = Hole diameter
C.33
Record Plus
Connections
A rear connection kit changes the standard connnection standard fixed-front connection breaker to a model
Components & accessories
configuration of a fixed, plug-in or drawout breaker from where the connection is accessible from the rear. Each
front to rear access. Delivered as a multi-pole set they kit is supplied with a short terminal shield to warrant a
allow an easy and quick change in configuration of the IPXXB protection from the breaker front .
FD frame FE frame
Available as a three or four pole set allowing for the Before a Record PlusTM FE frame size can be configured as
configuration of one side of the breaker. The kits are a rear connected device, the front connection insulation
made up of single pole connectors that are fitted to the part (nut plate) must be removed. The rear connection kit
standard cage terminal (top cavity). The rear that consists of a multi-pole kit held in a rear connection
connections are configured for use with busbars and support plate can then be simply slid into the room just
can be rotated at a ninety degree angle to allow for vacated by the front connection part (nut plate). Available
different incoming busbar configurations. The as a three or four pole set, it allows for the configuration of
connectors can be used with standard external box one side of the breaker. The rear connections are
clamps, with or without phase barriers, and are configured for use with busbars and can be rotated at a
supplied with a short terminal shield. forty five or ninety degree angle to allow for different
incoming busbar configurations. The connectors can be
used with standard internal box clamps, with or without
phase barriers, and are supplied with a short terminal
shield.
A
F
Connection Connection
G pad pad
A = vertical distance between connections 150 A = vertical distance between connections 140
d1 = breaker depth with long rear connections 90 d1 = breaker depth with long rear connections 98
d2 = breaker depth with short rear connections 45 d2 = breaker depth with short rear connections 48
d3 = pole spacing 27 d3 = pole spacing 35
V [mm] 14 V [mm] 17.4
t [mm] 4 t [mm] 4
i3 [mm] 10 i3 [mm] 13
M [mm] 22 M [mm] 30
Ø hole max [mm] 7 Ø hole max [mm] 9
Torque (Allen key in breaker) (Nm max.) 8 Torque (Allen key in breaker) (Nm max.) 25
Torque of connection bolt M6 (Nm max). 8 Torque of connection bolt M8 (Nm max). 25
C.34
Record Plus
FG frame FK frame
Connections
Before a Record PlusTM FG frame can be configured as Available as a three or four pole set allowing for the
a rear connected device, the front connection isolation configuration of the load or line side of the breaker. The
part (nut plate) must be removed. The rear connection kits are made up of single pole connectors that are
kit that consists of a multi-pole kit held in a rear screwed to the underside of the standard connection
connection support plate can then be simply slid into pad. The rear connections are configured for use with
the room just vacated by the front connection part . busbars and allow for different incoming busbar
Available as a three or four pole set , it allows for the configurations with a option of rotating them at a
configuration of one side of the breaker. The rear ninety degree angle for edgewise busbar connection.
connections are configured for use with busbars and The connectors can be used with or without phase
can be rotated at a ninety degree angle to allow for barriers, and are supplied with a short terminal shield.
different incoming busbar configurations. The
connectors can be used with or without phase barriers,
and are supplied with a short terminal shield.
A
F
Connection Connection
pad pad
G
FG frame rear connection FK frame rear connection
FG FK X
A = vertical distance between connections 229 A = vertical distance between connections 273
d1 = breaker depth with long rear connections 115 d1 = breaker depth with long rear connections 163
d2 = breaker depth with short rear connections 50 d2 = breaker depth with short rear connections 98
d3 = pole spacing 45 d3 = pole spacing 70
V [mm] 30 V [mm] 40
t [mm] 8 i4 [mm] 15
i3 [mm] 15 i5 [mm] 47
M [mm] 35 M [mm] 115/180
Ø hole max [mm] 13 Ø hole max [mm] 2 x 14
Torque (Allen key in breaker) (Nm max.) 42 Torque (Allen key in breaker) (Nm max.) 14
Torque of connection bolt M12 (Nm max). 42 Torque of connection bolt M12 (Nm max). 48
C.35
Record Plus
Connections
To allow for the different connection options in the configuration of one side of the breaker. The kits are
Components & accessories
different applications of the Record PlusTM circuit breaker made up of single pole connectors that are fitted to the
a large variety of different connection lugs, terminals standard breaker terminal. The connectors are supplied
and multiple connectors are available. These are with all the necesssary connection and fixation
available as a three or four pole set allowing for the hardware.
Extender
Extends the standard connection point to the exterior of the breaker body. Record PlusTM extenders are normally used
when the busbars and cables that are needed to connect the breaker exceed the possibilities of the standard connection
facility or when the use of external box clamps is required.
F
FD & FE extenders FG & FK extenders
FD FE FG FK
G
h = heigth dimension of breaker with extenders h = heigth dimension of breaker with extenders
at its top AND bottom. 190 230 at its top AND bottom. 354 452
z [mm] 170 212 z [mm] 314 408
s [mm] 27 35 s [mm] 52.5 100
X y max [mm] 28.5 25.5 y max [mm] 29.5 56
W max [mm] 14 20 W max [mm] 30 50
t max [mm] 5 8 t max [mm] 12 20(10)(3)
L max [mm] 16 18 L max [mm] 32 -
Ø hole max [mm] 7 9 Ø hole max [mm] 13 2 x 11 or
Torque (Allen key in breaker) (Nm max.) 8 25 1 x 13
Torque of connection bolt (Nm max). 8 25 Torque (Allen key in breaker) (Nm max.) 42 M10-42
M12-48
Torque of connection bolt (Nm max). 42 M10-42
M12-48
C.36
Record Plus
Spreaders
Increase the pole spacing of the breaker they are used to extend the standard connection points to the exterior of the breaker
body. Record PlusTM spreaders are normally used when the busbars and cables that are needed to connect the breaker exceed
Connections
the possibilities of the standard connection facility or when external lugs are needed. Available for:
F
FD & FE spreaders FG & FK spreaders
FD FE FG FK
G
h = heigth dimension of breaker with extenders h = heigth dimension of breaker with extenders
at its top AND bottom. 190 230 at its top AND bottom. 354 452
z [mm] 170 212 z [mm] 314 408
s [mm] 27 35 s [mm] 52.5 100
y max [mm] 18.5 25.5 y max [mm] 29.5 56 X
W max [mm] 14 18 W max [mm] 30 50
t max [mm] 5 8 t max [mm] 12 20(10)(3)
L max [mm] 16 18 L max [mm] 32 -
Ø hole max [mm] 7 9 Ø hole max [mm] 13 2 x 11
Torque (Allen key in breaker) (Nm max.) 8 25 or 1 x 13
Torque of connection bolt (Nm max). 8 25 Torque (Allen key in breaker) (Nm max.) 42 M10-42
M12-48
Torque of connection bolt (Nm max). 42 M10-42
M12-48
C.37
Record Plus
Connections
Record PlusTM breakers are designed to save space and connection and durability.
Components & accessories
time in mounting when compared to conventional switch The terminals are suitable for conductors of copper and
gear. To achieve the same savings in the connecting aluminium and meet both the newest version of the
process the Record PlusTM line includes a series of lugs EN 60497 standards and the relevant UL486a and b
meeting the newest and highest standards in ease of regulations.
h = heigth dimension of breaker with box clamps the same as h = heigth dimension of breaker with 333 381 354
X mounted at top and bottom. breaker box clamps mounted at top and bottom.
2
L max [mm] 18 18 S max [mm ] 25 - 240 240 240
d max [mm] 16 17.5(1) for L1
S max [mm ]2 2.5 - 95 16 - 150 50 - 300
L = distance to insulation (min.) 21 25 for L2
Torque (Allen key on clamp) (Nm max.) 30 30 Hole L1 = distance to insulation L (min.) 22 - -
Hole L2 = distance to insulation L (min.) 40 - -
Distance to insulation L (min.) - 27.5 36
Torque (Nm max.) 31(L1) 31 31
(1) Most standard 185 mm2 cable sections will also fit into this lug 42(L2)
(hole diameter 17.5 mm)
(2) Terminal for 3 cables
(3) Terminal for 4 cables
C.38
Record Plus
Connections
To accomodate for larger cross sections Specifically designed to allow the use of the
Record PlusTM clamps can be used in combination with Record PlusTM FE frame as a mains device with cables
extenders and/or spreaders. They are available as a distributing the load over multiple outgoing circuits (or
three or four pole set allowing the line or load side of lines of multiple outgoing circuits). The lugs are available
the breaker to be equipped. Each set consists of basic as a three or four pole set allowing the line or load side of
single pole units with phase seperators. the breaker to be equipped. The sets consist of a number
of fully isolated single pole units that can be assembled
into a multipole distribution block before they are
mounted on the breaker. Each lug allows for a maximum
of four 6-25 mm2 or two 10-35 mm2 copper conductors.
h = heigth dimension of breaker with box clamps h = heigth dimension of breaker with box clamps mounted
mounted at top and bottom. 190 270 at top and bottom. 250 X
z [mm] 30 50 z [mm] 60
s [mm] 27 35 s max [mm] 35
w [mm] 18.5 30 Torque (Allen key in breaker) (Nm max.) 25
y [mm] 50 55.5 L = distance to insulation (min.) - 35 mm2 18
S max [mm2] 4 - 95 70 - 185 L = distance to insulation (min.) - 25 mm2 11
L = distance to insulation (min.) 20 20 Torque on connection bolt (Nm max.) - 35 mm2 6
Torque (Allen key in breaker) (Nm max.) 8 25 Torque on connection bolt (Nm max.) - 25 mm2 3
Torque on connection bolt (Nm max.) 17 25
C.39
Record Plus
Connections
The Record PlusTM circuit breaker can be equiped with made up of single pole connectors that are fitted to the
several variants of the standard extender design. These standard breaker terminal. The connectors are supplied
are available as a three or four pole set allowing for the with all the necesssary connection and fixation
configuration of one side of the breaker. The kits are hardware.
Extender angled
F
Two more extender variants exist for the FE frame type
only with a connection area set at forty five or ninety
G degrees. The hole dimensions and reqiuired torques are
the same as those required for the heightened
extenders.
C.40
Record Plus
Connections
They ensure a correct dielectric separation of the available. The required size is easily achieved by
different connection terminals. breaking off parts along a pre-cut line.
For the Record PlusTM FD, FE, FG and FK frame,
phase separators are available in one set containing 12
pieces.
C.41
Just rel
Record Plus
Application guide E
Wiring diagrams F
Dimensions G
y on us
Numerical Index X
D.1
Record Plus
Rated operational voltage Ue Volts AC 240 500 690 690 690 690
Volts DC 250 - - 500 500 500
Performance figures
3,4 3,4 3,4 3,4 3,4 3,4
690 750 750 750 1000 1000 1000
8 8 8 8 8 8 8
500 690 690 690 690 690 690
440 500 - - 500 500 500
A B(5) B(5) B B B
yes yes yes yes yes yes
250 400 630 800 1250 1600
65 85 100 200 85 100 200 85 100 200 85 100 170 85 100 170 85 100
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
25 42 65 130 42 65 130 42 65 130 42 65 80 42 65 80 42 65
18 30 50 100 30 50 100 30 50 100 36 42 50 36 42 50 36 42
- 10 15 22 10 22 75(7) 10 22 40(7) 20 25 30 20 25 30 20 25
25 50 85 100 50(3) 60(3) 80(3) 50(3) 60(3) 80(3) - -
- 50 85(2) 100(2) 36(2) 50(2) 60(2) 36(2) 50(2) 60(2) - -
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 50% 100% 75% 50% 100% 75%
- 100% 75% 50% 100% 45% 25% 100% 45% 25% 100% 75% 50% 100% 75% 50% 100% 75%
36 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
- 10 15 22 10 (6) (6) 10 (6) (6) 20 25 30 20 25 30 20 25
10000 25000 20000 20000 10000 10000 10000
5000 10000 7500 5000 4000 3000 2000
10000
4000
20000
10000
15000
8000
10000
8000
8000
4000
6000
3000
4000
2000
A
no yes yes yes no no no
LTM LTM LTM
GTM
LTMD
Mag BreakTM Mag BreakTM
B
SMR1 SMR1 SMR1e
SMR2 SMR 1s & g
FE250Y FG400Y FG630Y FK800Y FK1250Y FK1600Y
C
X
65 100 150 200 100 150 200 100 150 200 85 - - 85 - - 85 -
36 50 65 130 50 65 130 50 65 130 42 - - 42 - - 42 -
22 25 36 42 25 36 42 25 36 42 25 - - 25 - - 25 -
no no no no no no
yes yes yes yes yes yes
yes yes yes no no no
yes yes yes yes yes yes
yes yes yes yes yes yes
yes yes yes yes yes yes
105 x 170 x 95 140 x 265 x 115 140 x 265 x 115 210 x 320 x 160 210 x 320 x 160 210 x 320 x 160
140 x 170 x 95 185 x 265 x 115 185 x 265 x 115 280 x 320 x 160 280 x 320 x 160 280 x 320 x 160
1.6 4.5 4.5 12.2 18.0 18.0
2.1 6.0 6.0 15.1 23.4 23.4
(5) 350 and 500A executions only (7) On use of FG400 and FG630L type at 690V, one
(6) Please contact us. long and widened terminal shield is required.
D.3
Record Plus
Power dissipation
Standards
Use
100 28 33 24 27 23 29 18 23 15 19 12 14 19 27 14 19 11 14 9 12 11 16 9 13
120 32 38 28 31 27 33 21 27 22 31 17 23
140 37 44 31 35 31 38 24 31 19 24 15 19 25 35 19 26 15 19 12 16 15 21 12 16
160 41 48 35 39 34 42 27 34 27 39 21 28
G 180
200
45
49
53
58
38
42
43
47
38
41
46
51
29
32
38
41
24 30 19 23 30
33
43
47
23
25
31
34
18 23 15 19 18 25 15 20
220 53 63 45 51 44 55 34 44 28 35 22 27 35 50 27 37 21 27 18 23 21 30 18 24
240 48 55 47 58 37 47 38 54 29 39
260 52 58 51 62 39 51 32 40 25 31 40 58 31 42 24 31 20 26 24 34 20 27
280 42 54 43 61 33 45
X 300 44 57 36 45 28 35 45 65 35 47 27 35 23 29 27 38 23 30
350 50 64 40 51 32 40 51 73 40 53 30 39 26 33 31 43 25 34
400 45 57 36 44 44 59 34 44 29 37 34 48 28 38
450 49 62 39 48 48 65 37 48 32 40 38 53 31 42
500 43 53 53 71 40 53 34 44 41 58 34 46
550 46 57 44 57 37 47 45 63 37 49
600 49 61 47 61 40 51 48 67 39 53
650 53 65 50 65 42 54 51 72 42 57
700 45 57 45 60
750 48 61 47 63
800 50 64 50 67
D.4
Record Plus
Record Plus TM Power dissipation
The power dissipation tables included here indicate the The tables indicate the Watt loss per pole based on the
DC resistance of the Record PlusTM breakers in cold maximum current load of the breaker. To calculate the
condition.The power dissipation per pole can be total Watt loss for a three or four pole breaker these
calculated with this value and the average current values are multiplied by three.*
flowing within the circuit (formula I2R).
Power dissipation
Thermal magn. type (LTM, LTMD, GTM) Mag BreakTM (MO) Switch (Y)
In (A)(1) 16 20 25 32 40 50 63 3 7 12.5 20 30 50 63
Fixed version R in m1 per pole 11.00 5.70 4.00 2.90 2.90 2.25 1.60 110.00 55.00 17.85 10.65 4.75 3.00 0.40
Dissipation Watt single pole 2.82 2.28 2.50 2.97 4.64 5.63 6.35 0.99 2.70 2.79 4.26 4.28 7.50 1.59
Dissipation Watt three poles 8.45 6.84 7.50 8.91 13.92 16.88 19.05 2.97 8.09 8.37 12.78 12.83 22.50 4.76
Plug-in version R in m1 per pole 11.07 5.77 4.07 2.97 2.97 2.32 1.67 110.07 55.07 17.92 10.72 4.82 3.07 0.47
Dissipation Watt single pole 0.28 0.44 0.69 0.75 1.17 1.83 2.91 0.99 2.70 2.80 0.31 0.47 1.31 1.87
Dissipation Watt three poles 0.84 1.32 2.06 2.25 3.52 5.50 8.73 2.97 8.10 8.40 0.94 1.42 3.94 5.60
Fixed version R in m1 per pole 11.08 5.78 4.08 2.98 2.98 2.33 1.68 110.08 55.08 17.93 10.73 4.83 3.08 0.48
with RCD Dissipation Watt single pole 0.29 0.45 0.70 0.76 1.19 1.87 2.96 0.99 2.70 2.80 0.33 0.50 1.39 1.91
Dissipation Watt three poles 0.86 1.34 2.10 2.29 3.58 5.60 8.89 2.97 8.10 8.40 1.00 1.50 4.18 5.72
Plug-in version R in m1 per pole 11.15 5.85 4.15 3.05 3.05 2.40 1.75 110.15 55.15 18.00 10.80 4.90 3.15 0.55
with RCD Dissipation Watt single pole 0.31 0.49 0.76 0.83 1.30 2.03 3.23 0.99 2.70 2.81 0.36 0.54 1.51 2.18
Dissipation Watt three poles 0.94 1.46 2.29 2.50 3.90 6.10 9.68 2.97 8.11 8.44 1.09 1.63 4.54 6.55
Fixed version R in m1 per pole 0.95 0.70 0.40 0.40 0.45 0.45 0.40
A
Dissipation Watt single pole 6.08 7.00 6.25 10.24 2.88 4.50 10.24
Dissipation Watt three poles 18.24 21.00 18.75 30.72 8.64 13.50 30.72
Plug-in version R in m1 per pole 1.02 0.77 0.47 0.47 0.52 0.52 0.47
Dissipation Watt single pole
Dissipation Watt three poles
6.53
19.58
7.70
23.10
7.34
22.03
12.03
36.10
3.33
9.98
5.20
15.60
12.03
24.06
B
Fixed version R in m1 per pole 1.03 0.78 0.48 0.48 0.53 0.53 0.48
with RCD Dissipation Watt single pole 6.59 7.80 7.50 12.29 3.39 5.30 12.29
Dissipation Watt three poles 19.78 23.40 22.50 36.86 10.18 15.90 36.86
Plug-in version R in m1 per pole
with RCD Dissipation Watt single pole
1.10
7.04
0.85
8.50
0.55
8.59
0.55
14.08
0.60
3.84
0.60
6.00
0.55
14.08
C
Dissipation Watt three poles 21.12 25.50 25.78 42.24 11.52 18.00 42.24
D
Power Dissipation - FE160 frame
Thermal magn. type (LTMD, GTM) Switch (Y)
In (A) 25 32 40 50 63 80 100 125 160 160
E
Fixed version R in m1 per pole 6.30 2.80 2.80 2.05 1.80 1.20 0.70 0.63 0.48 0.30
Dissipation Watt single pole 3.94 2.87 4.48 5.13 7.14 7.68 7.00 9.84 12.29 7.68
Dissipation Watt three poles 11.81 8.60 13.44 15.38 21.43 23.04 21.00 29.53 36.86 23.04
Plug-in version R in m1 per pole 6.36 2.86 2.86 2.11 1.86 1.26 0.76 0.69 0.54 0.36
Dissipation Watt single pole 3.98 2.93 4.58 5.28 7.38 8.06 7.60 10.78 13.82 5.63 F
Dissipation Watt three poles 11.93 8.79 13.73 15.83 22.15 24.19 22.80 32.34 41.47 11.25
Fixed version R in m1 per pole 6.37 2.87 2.87 2.12 1.87 1.27 0.77 0.70 0.55 0.38
with RCD Dissipation Watt single pole 3.98 2.94 4.59 5.30 7.42 8.13 7.70 10.94 14.08 5.94
Dissipation Watt three poles 11.94 8.82 13.78 15.90 22.27 24.38 23.10 32.81 42.24 17.81
Plug-in version R in m1 per pole 6.43 2.93 2.93 2.18 1.93 1.33 0.83 0.76 0.61 0.44 G
with RCD Dissipation Watt single pole 4.02 3.00 4.69 5.45 7.66 8.51 8.30 11.88 15.62 11.56
Dissipation Watt three poles 12.06 9.00 14.06 16.35 22.98 25.54 24.90 35.63 46.85 33.79
Mag BreakTM (MO) FE160 frame electronic type (SMR1)
In (A)(1) 3 7 12.5 20 30 50 80 100 125 160 25 63 125 160 X
Fixed version R in m1 per pole 410.00 110.00 13.30 13.30 3.60 1.70 0.60 0.60 0.32 0.32 0.35 0.35 0.35 0.35
Dissipation Watt single pole 5.02 5.39 2.08 5.32 3.24 4.25 3.84 6.00 3.84 3.84 0.22 1.39 5.47 8.96
Dissipation Watt three poles 15.07 16.17 7.27 15.96 11.34 12.75 11.52 18.00 11.52 11.52 0.66 4.17 16.41 26.88
Plug-in version R in m1 per pole 410.06 110.06 13.36 13.36 3.66 1.76 0.66 0.66 0.38 0.38 0.41 0.41 0.41 0.41
Dissipation Watt single pole 5.02 5.39 2.09 5.34 3.29 4.40 4.22 6.60 5.94 9.73 0.26 1.63 6.41 10.50
Dissipation Watt three poles 15.07 16.18 6.26 16.03 9.88 13.20 12.67 19.80 17.81 29.18 0.77 4.88 19.22 31.49
Fixed version R in m1 per pole 410.07 110.07 13.37 13.37 3.67 1.77 0.67 0.67 0.39 0.39 0.42 0.42 0.42 0.42
with RCD Dissipation Watt single pole 5.02 5.39 2.09 5.35 3.30 4.43 4.29 6.70 6.09 9.98 0.26 1.67 6.56 10.75
Dissipation Watt three poles 15.07 16.18 6.27 16.04 9.91 13.28 12.86 20.10 18.28 29.95 0.79 5.00 19.69 32.26
Plug-in version R in m1 per pole 410.13 110.13 13.43 13.43 3.73 1.83 0.73 0.73 0.45 0.45 0.48 0.48 0.48 0.48
with RCD Dissipation Watt single pole 5.02 5.40 2.10 5.37 3.36 4.58 4.67 7.30 7.03 11.52 0.30 1.91 7.50 12.29
Dissipation Watt three poles 15.07 16.19 6.30 16.12 10.07 13.73 14.02 21.90 14.02 14.02 0.90 5.72 22.50 36.86
D.5
Record Plus
Power Dissipation - FE250 frame
Thermal magn. type (LTMD, GTM) Switch (Y)
In (A) 80 100 125 160 200 250 250
Fixed version R in m1 per pole 1.10 0.60 0.55 0.40 0.33 0.24 0.20
Dissipation Watt single pole 7.04 6.00 8.59 10.24 13.20 15.00 12.50
Dissipation Watt three poles 21.12 18.00 25.78 30.72 39.60 45.00 37.50
Plug-in version R in m1 per pole 1.16 0.66 0.61 0.46 0.39 0.30 0.26
Dissipation Watt single pole 7.42 6.60 9.53 11.78 15.60 18.75 16.25
Dissipation Watt three poles 22.27 19.80 28.59 35.33 46.80 56.25 48.75
Fixed version R in m1 per pole 1.17 0.67 0.62 0.47 0.40 0.31 0.27
with RCD Dissipation Watt single pole 7.49 6.70 9.69 12.03 16.00 19.38 16.88
Dissipation Watt three poles 22.46 20.10 29.06 36.10 48.00 58.13 50.63
Plug-in version R in m1 per pole 1.23 0.73 0.68 0.53 0.46 0.37 0.33
with RCD Dissipation Watt single pole 7.87 7.30 10.63 13.57 18.40 23.13 20.63
Dissipation Watt three poles 23.62 21.90 31.88 40.70 55.20 69.38 61.88
Mag BreakTM(MO) FE250 frame Electronic type (SMR1)
Technical data
Fixed version R in m1 per pole 0.33 0.24 0.20 0.20 0.20 0.20
Dissipation Watt single pole 8.45 2.40 15.00 3.13 5.12 12.50
Dissipation Watt three poles 25.34 7.20 45.00 9.38 15.36 37.50
Plug-in version R in m1 per pole 0.39 0.30 0.30 0.26 0.26 0.26
Dissipation Watt single pole 9.98 3.00 18.75 4.06 6.66 16.25
Dissipation Watt three poles 29.95 9.00 56.25 12.19 19.97 48.75
Fixed version R in m1 per pole 0.40 0.31 0.31 0.27 0.27 0.27
with RCD Dissipation Watt single pole 10.24 3.10 19.38 4.22 6.91 16.88
Dissipation Watt three poles 30.72 9.30 58.13 12.66 20.74 50.63
Plug-in version R in m1 per pole 0.46 0.37 0.37 0.33 0.33 0.33
with RCD Dissipation Watt single pole 11.78 3.70 23.13 5.16 8.45 20.63
Dissipation Watt three poles 35.33 11.10 69.38 15.47 25.34 61.88
D
Power Dissipation - FK800, FK1250 & FK1600 frame
Thermal magn. type (LTM) Mag BreakTM(MO) Switch (Y)
E In (A) 630 800 1000 1250 800 1250 800 1250 1600
Fixed version R in m1 per pole 0.04 0.04 0.04 0.04 0.02 0.02 0.02 0.02 0.01
Dissipation Watt single pole 15.88 25.60 35.00 54.69 12.80 23.44 12.80 31.25 25.60
Dissipation Watt three poles 47.63 76.80 105.00 164.06 38.40 70.31 38.40 93.75 76.80
F Draw-out R in m1 per pole 0.07 0.07 0.07 0.07 0.05 0.05 0.05 0.05 0.04
version Dissipation Watt single pole 27.78 44.80 65.00 101.56 32.00 70.31 32.00 78.13 102.40
Dissipation Watt three poles 83.35 134.40 195.00 304.69 96.00 210.94 96.00 234.38 307.20
FK800,1250-1600 frame electronic type (SMR1e, s & g)
G In (A) 800 1000 1250 1600
Fixed version R in m1 per pole 0.04 0.04 0.04 0.03
Dissipation Watt single pole 25.60 35.00 54.69 76.80
Dissipation Watt three poles 76.80 105.00 164.06 230.40
X Draw-out R in m1 per pole 0.07 0.07 0.07 0.06
version Dissipation Watt single pole 25.60 35.00 54.69 76.80
Dissipation Watt three poles 76.80 105.00 164.06 230.40
D.6
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power dissipation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.7
Record Plus
Derating
The ambient temperature in the direct vicinity of a The Record PlusTM breakers with thermal magnetic and
protective device has an influence on its current carrying magnetic only protection units as the MO, LTM and LTMD
properties. types can be used at currents and temperatures as
indicated in the table.
Type In (A) 40°C 45°C 50°C 55°C 60°C 65°C 70°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C
FD63, FD160, 16 16.0 15.5 15.0 14.6 14.1 13.6 13.1 15.0 14.6 14.1 13.7 13.2 12.8 12.3
FE160 & FE250 25 25.0 24.3 23.5 22.8 22.0 21.3 20.5 23.5 22.8 22.1 21.4 20.7 20.0 19.3
32 32.0 31.0 30.1 29.1 28.2 27.2 26.2 30.1 29.2 28.3 27.4 26.5 25.6 24.7
40 40.0 38.8 37.6 36.4 35.2 34.0 32.8 37.6 36.5 35.3 34.2 33.1 32.0 30.8
50 50.0 48.5 47.0 45.5 44.0 42.5 41.0 47.0 45.6 44.2 42.8 41.4 40.0 38.5
63 63.0 61.1 59.2 57.3 55.4 53.6 51.7 59.2 57.4 55.7 53.9 52.1 50.3 48.6
80 80.0 77.6 75.2 72.8 70.4 68.0 65.6 75.2 72.9 70.7 68.4 66.2 63.9 61.7
100 100 97.0 94.0 91.0 88.0 85.0 82.0 94.0 91.2 88.4 85.5 82.7 79.9 77.1
FD160 125 125 121 118 114 110 106 103 118 114 110 107 103 100 96
160 160 155 150 146 141 136 131
FE160 & FE250 125 125 121 118 114 110 106 103 118 114 110 107 103 100 96
160 160 155 150 146 141 136 131 150 146 141 137 132 128 123
200 200 194 188 182 176 170 164 188 182 177 171 165 160 154
250 250 243 235 228 220 213 205 235 228 221 214 207 200 193
FK800 & FK1250 630 630 611 592 573 554 536 517 630 611 563 545 527 509 491
800 800 776 752 728 704 680 656 800 760 714 692 669 646 623
1000 1000 970 940 910 880 850 820 1000 950 893 865 836 808 779
1250 1250 1213 1175 1138 1100 1063 1025 1250 1188 1116 1081 1045 1009 974
A FD63 & FD160
FE160 & FE250
16
25
16.0
25.0
15.5
24.3
15.0
23.5
14.6
22.8
14.1
22.0
13.6
21.3
13.1
20.5
15.0
23.5
14.6
22.8
14.1
22.1
13.7
21.4
13.2
20.7
12.8
20.0
12.3
19.3
with RCD 32 32.0 31.0 30.1 29.1 28.2 27.2 26.2 30.1 29.2 28.3 27.4 26.5 25.6 24.7
40 40.0 38.8 37.6 36.4 35.2 34.0 32.8 37.6 36.5 35.3 34.2 33.1 32.0 30.8
50 50.0 48.5 47.0 45.5 44.0 42.5 41.0 47.0 45.6 44.2 42.8 41.4 40.0 38.5
B 63
80
63.0
80.0
61.1
77.6
59.2
75.2
57.3
72.8
55.4
70.4
53.6
68.0
51.7
65.6
59.2
75.2
57.4
72.9
55.7
70.7
53.9
68.4
52.1
66.2
50.3
63.9
48.6
61.7
100 100 97.0 94.0 91.0 88.0 85.0 82.0 94.0 91.2 88.4 85.5 82.7 79.9 77.1
FD160 125 119 115 110 108 97 101 97 110 107 104 101 97 94 91
with RCD 160 152 147 141 138 125 129 125 141 137 133 129 124 120 116
C FE160 & FE250
with RCD
125
160
125
152
121
147
118
141
114
138
110
125
106
129
103
125
118
141
114
137
110
133
107
129
103
124
100
120
96
116
200 190 184 177 173 156 162 156 177 171 166 161 156 150 145
250 238 230 221 216 195 202 195 221 214 208 201 194 188 181
D.8
Record Plus
Derating
Electronic trip units are less sensitive to fluctuations in into account. The table indicates the maximum values to
ambient temperature than thermal magnetic trip units. which the LT or overload protection of the electronic trip unit
However, to prevent the device and its environment from of the Record PlusTM breaker can be set. This at ambient
exceeding their design values, certain limits must be taken temperatures from 40 to 70°C.
FE160 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
Derating
160 160 160 160 156 152 148 144 160 156 152 148 144 140 136
FE250 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
160 160 160 160 160 160 160 160 160 156 152 148 144 140 136
250 250 250 250 244 238 231 225 250 244 238 231 225 219 213
FG400 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250
350 350 350 350 350 350 350 350 350 350 350 350 350 350 340
400 400 400 400 390 380 370 360 400 390 380 370 360 350 340
FG630 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
500 500 500 500 500 500 500 500 500 500 500 500 500 500 481
630 630 614 599 583 567 551 536 583 568 554 539 524 510 481
FK800 800 800 800 760 760 760 680 - 760 741 722 703 722 646 -
FK1250 1000 1000 1000 950 950 900 850 - 950 950 903 879 855 808 -
1250 1250 1250 1188 1188 1125 1000 - 1188 1158 1128 1098 1069 950 -
FK1600 1600 1600 1600 1520 1440 1408 1280 - 1600 1536 1444 1408 1368 1216 -
FE160 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
with RCD 63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
125
63
106
A
160 160 156 152 148 144 141 137 152 148 144 141 137 133 129
FE250 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
with RCD 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160
FG400
250
250
250
250
244
250
238
250
244
250
238
250
231
250
225
250
238
250
232
250
226
250
220
250
214
250
208
250
202
250
B
with RCD 350 350 350 350 341 333 324 315 350 351 342 333 324 315 306
400 400 370 360 350 340 330 320 360 351 342 333 324 315 306
FG630 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
with RCD 500
630
500
630
500
567
500
551
500
536
500
520
500
504
488
488
500
520
500
507
494
494
481
481
468
468
455
455
442
442
C
D.9
Record Plus
Clearances
Minimum distances
A modern circuit breaker is designed to interrupt high The Record PlusTM circuit breaker has been designed to
short-circuit currents in a very limited time frame. limit the venting phenomanae to a minimum. However, it
In doing so the breaker vents gas and and a limited is necessary to take the following minimum distances
amount of conductive fragments. into account:
D
Minimum Distances
Distances in mm
E Type a b c d
FD63 & FD/160 To painted metal, non conductive materials and isolated conductors. 0 15
To unpainted metal Voltage ≤ 480V 3 35
Voltage < 600V(1) 5 (2)
F Voltage = 690V(1) 15 (2)
To breaker housing 35 35
To conductors potruding from breaker 35 35
FE160 & FE250 To painted metal, non conductive materials and isolated conductors. 0 20
To unpainted metal Voltage ≤ 480V 5 35
G Voltage < 600V(1) 10 (2)
Voltage = 690V(1) 20 (2)
To breaker housing 35 35
To conductors potruding from breaker 35 35
FG400 & FG630 To painted metal, non conductive materials and isolated conductors. 0 30
X To unpainted metal Voltage ≤ 480V 5 60
Voltage < 600V(1) 10 (2)
Voltage = 690V(3) 20 (2)
To breaker housing 60 60
To conductors potruding from breaker 60 60
FK800, FK 800 To painted metal, non conductive materials and isolated conductors. 0 40
& FK1600 To unpainted metal Voltage ≤ 480V 15 80
Voltage < 600V 20 80
Voltage = 690V 30 80
To breaker housing 140 140
To conductors potruding from breaker 140 140
(1) The use of phase seperators and back plates is obligatory. (3) At 690Volts the FG400L & FG630L must have the power supply connected to the breaker
(2) Size determined by phase seperators. ON side (Line). In this application the use of the widened terminal shield is compulsory.
D.10
Record Plus
Individual mounting of
Record PlusTM in enclosures
Record PlusTM breakers can be placed in enclosures for
use as individually wall mounted feeder units. In order
to ensure a reliable and practical solution each of the
combinations mentioned here have been defined by
strenous testing. Here the properties of all components,
Mounting in enclosures
and their use as a combination have been taken into
account . For all other application of the Record PlusTM
in individually mounted enclosures, please contact us.
VMS, thermoplastic box IP65 with transparent cover. Breaker and terminal covers always have to be ordered
The use of short or long terminal covers for the breaker separately.
is mandatory. Short-circuit rating: 20kA, 440 V
A
PolySafe, glass fibre reinforced Polyester, cabinet IP65 breaker in a VMS box.
with door. Breaker, terminal covers and mounting plate for the
When using Record PlusTM Breaker in polyester cabinets external housing have to be ordered separately.
B
for outdoor use we recommend encapsulating the Short-circuit rating: 20kA, 440 V(3)
C
PolySafe, glass fibre reinforced polyester cabinet IP65
Internal housing VMS External housing Polysafe
Record Plus Breaker(1) Breaker type
In (A) Size Ref. nr. Size Ref. nr.
125A FD125 w/out RCD 440 x 320 x 254 855085(3) 750 x 500 x 320 883008
D
160A FE160 w/out RCD 640 x 320 x 254 855087 / 855088(3) 750 x 500 x 320 883008
250A FE250 w/out RCD 640 x 320 x 254 855087 / 855088(3) 750 x 500 x 320 883008
400A FG400 or FG 630 FGNRC (2) (2) (2)
630A FG400 or FG630 with RCD FGNRC (2) (2) (2) E
(1) Ambient temperature max. 30 degrees centigrade.
(2) Please contact us.
(3)The use of short or long terminal covers on the breaker is mandatory F
D.11
Record Plus
Current limitation
A short-circuit is an overcurrent with a value only limited In modern hi-power electrical distribution networks very
by the impedance of the fault circuit itself. This high prospective fault levels of 100kA or more can occur.
impedance is determined by a number of factors the High prospective short-circuit current values can cause
main ones of which are the available power that a issues in a number of areas:
network can supply and the impedance of the
conductors within the fault circuit .
The electrodynamical forces due to the crest current value and its isolation. It is limited to prevent the cable
can seriously damage equipment as busbar systems and isolation from exceeding its temperature
their supports, downstream switchgear etc. limits, the maximum values being specified in the HD
Current limiting devices limit the crest value of the short- 384.4.4.42 and HD 384.5.5.4 standards and
circuit current and thus reduce theses forces. paragraphs.The standards define the use of the
formula:
Magnetic fields K2 x S2
A high level short-circuit produces magnetic fields that K; factor provided in the standard; depends on
prevent electrical equipment as meters and computers the material that the conductor is made of and
from operating correctly. it's insulation
S; cross section of the conductor
Thermal stress (heat)
Thermal stress is proportional to the square of the effective
current value.
K factors acording to HD 384
A The thermal stress limit of cable isolation, busbar supports Insulation Cu Al
and other electrical equipment can be expressed as an
A2S value. This electrical energy value must be kept within 70°C PVC ≤ 300 sq.mm 115 76
certain pre-defined limits to prevent overheating. 70°C PVC > 300 sq.mm 103 68
B To avoid or to limit the effects of these issues the use of
90°C XLPE or EPR
85°C rubber
143
134
94
89
current limiting devices is advisable.
G
Maximum permissable thermal stress in conductors
X Thermal Stress Values
Insulation Core Material S in mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120
A2S A2S A2S A2S A2S A2S A2S A2S A2S A2S A2S A2S
x104 x104 x105 x105 x105 x106 x106 x107 x107 x107 x107 x107
70°C PVC Copper 2.98 8.27 2.12 4.76 13.23 3.39 8.27 1.62 3.31 6.48 11.94 19.04
Aluminium 1.30 3.61 0.92 2.08 5.78 1.48 3.61 0.71 1.44 2.83 5.21 8.32
90°C XLPE or EPR Copper 4.60 12.78 3.27 7.36 20.45 5.23 12.78 2.51 5.11 10.02 18.46 29.45
Aluminium 1.99 5.52 1.41 3.18 8.84 2.26 5.52 1.08 2.21 4.33 7.97 12.72
85°C rubber Copper 4.04 11.22 2.87 6.46 17.96 4.60 11.22 2.20 4.49 8.80 16.21 25.86
Aluminium 1.78 4.95 1.27 2.85 7.92 2.03 4.95 0.97 1.98 3.88 7.15 11.41
D.12
Record Plus
Record PlusTM MCCB’s revolutionary design is equipped The limitation of electrodynamic forces and thermal
Current limitation
with dual contacts placed in a rotary configuration that stress by using back-up protection
enables the device to provide the highest available Protection devices placed downstream from a
interruption ratings in the smallest possible size. When protective device as a Record PlusTM breaker must be
the breaker reacts it does so with more than twice the able to withstand the thermal and
speed and force of conventional breakers, thus electrodynamic effects that occur at its point of
providing excellent current limitation. This results in low installation. Placing current limiting devices upstream
peak current and energy values in the circuit and leads limits these values and can allow the use of smaller
to lower electro-dynamic forces and thermal stress and more economical devices than is possible without
values in the protected electrical conductors, the use of current limitation.
downstream protection devices and equipment .
Back-up protection with Record PlusTM is described in
the application data section of this catalogue.
B
H
D
However, in some cases it is still necessary to check if
the electrical conductors are protected correctly. This
can be verified by taking the cable stress limits
E
published on the previous page and comparing them
with the let-through energy values found in the graphs.
F
D.13
Record Plus
Current limitation data at
400/415V
Technical data
D.14
Record Plus
Current limitation
A
D.15
Record Plus
Environmental considerations
D.16
Record Plus
Electromagnetic compatibility
Environment
EN 60947-2 Annex F, Sub-clause F5 and
- Wave form the IEC 1000-4-4 (basic standard)
consisting of a - Passed level 4 burst peak voltage 4kV
fundamental Surge immunity test
component + 3rd EN 60947-2 Annex F, Sub-clause F5 and
harmonic the IEC 1000-4-5 (basic standard)
component at - Passed level 4 Voltage 1.2μs/50μs 6kV; current
50 and 60Hz 8μs/20μs 3kA
- Wave form Dry heat test
consisting of a EN 60947-2 Annex F, Sub-clause F8
fundamental component + a 5th harmonic component - Passed all test requirements
at 50 and 60Hz Thermal shock test
- Composite wave form with a fundumental EN 60947-2 Annex F, Sub-clause F9
component + 3rd ,5th & 7th and a harmonic at 50 and - No nuisance tripping within the 28-day temperature A
60Hz cycles
- All current dips and current interruptions are met .
- Frequency variation test from 45Hz to 65Hz in 1Hz
steps (required 50Hz to 60Hz in 1Hz steps) B
D.17
Record Plus
Use in DC networks
In both AC and DC networks protective devices are However, the system voltage generally plays a greater
required to interrupt the prospective short-circuit current role (is more difficult to interrupt) while the network
at the point where the device is installed. For circuit defines how many poles need to participate in the
breakers as the Record PlusTM this value is called the interruption.
interuption or breaking capacity (Icu or Ics), a value The drawing below indicates the three possible DC
dependent not only on the prospective fault current networks with the "worst" short-circuit for each of them,
value but also on the system voltage rating. For DC the number of poles that must particpate in the breaking
networks the situation is basically the same as for AC operation and the voltage level that needs to be
networks. interrupted.
Use in DC networks
Technical data
Network Type Center point connected to earth (A) One pole connected to earth (B) Insulated from earth (C)(1)
Electrical schemes
Maximum short-circuit current (Icc max) short-circuit A-B short-circuit A-B or A-C short-circuit A-B
Minimum poles needed 2 (one on each polarity) 1 (unearthed polarity) 2 (one on each pole)
Breaking capacity on each pole Icc max at V/2 Icc max at V Icc max at V
(1) When a pole is grounded due to a first fault nothing happens, on a second fault the network behaves like a system with "one polarity connected to ground"
A
Record PlusTM FD, FE, FG and FK line breakers can be Example
used in DC networks with standard thermal magnetic trip Rated voltage 500 V DC; Rated current 200 A Icc
units. max 50 kA
B For Record PlusTM FG line breakers, please contact us. network A : center point connected to grond
The nominal current rating of the device does not vary in FE250N 3x 250 - 1pole for each polarity
AC or DC applications. The setting of the short-circuit or network B : one pole connected to ground
magnetic device needs to be multiplied by 1.2 to FE250N 3x 250 - 2poles on unearthed polarity.
C determine its threshold in a DC network. network C : insulated network
The table indicates the nominal current , the breaking FE250N 3 x 250 - 1 pole on each polarity
capacity (Icu=Ics) and the number of poles needed to
D participate in the interruption.
D.18
Record Plus
Use at frequencies other
than 50/60 cycles
Performance characteristics of protective devices used in The breakers can be used at 16 2/3 (applications in rail
electrical distribution networks or systems vary transport) and 400hz (aviation) if the following is taken
according to the network's rated frequency. into account:
The Record PlusTM family of circuit breakers is designed a) The rated breaking capacity is decreased (1)
to offer their best performance at 50/60 Hz network. b) The device trip unit settings are modified
Record PlusTM breakers and their trip units can be used The breakers and their trip units can be used at
at 16 2/3 Hz and 400 Hz provided that the trip units are 400 Hz (aircraft) provided that the trip units are set
set accordingly.The table indicates the coefficients to accordingly.
be applied for 16 2/3 Hz and 400 Hz applications. The table indicates the coefficients to be applied for
16 2/3 Hz and 400 Hz applications.
Kt (for thermal)
Km (for magnetic) Kt (for LT)
Km (for ST)
The current values for each environment can be
calculated by multiplying the values set on the breaker The current values for each environment can be
by the coefiicients mentioned in the tables. calculated by multiplying the values set on the breaker
by the coefiicients mentioned in the tables.
A
Use in networks with a frequency of 16 2/3 and 400 cycles
Breaker Rated current Trip Unit type Thermal or LT settings Magnetic or ST settings B
Kt16 (16 2/3Hz) Kt400 (400 Hz) Km16 (16 2/3Hz) Km400 (400 Hz)
D.19
Just rel
Record Plus
Wiring diagrams F
Dimensions G
y on us
Numerical Index X
E.1
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application guide
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E.2
Record Plus
Introduction The breaker settings
The main breaker settings are :
- Overload protection or LT setting ... Ir
A protection device like the Record PlusTM circuit - Magnetic or ST setting …. Im
breaker is used in a wide variety of environments to
protect conductors, equipment and devices in low Ir setting
voltage distribution circuits. To use this product to its The HD 384 (IEC 364) installation regulations state that
full potential it is necessary to verify that it functions the Ir value is determined by use of the following two
correctly in the environment in which it is used and formulae:
that it meets the Electrotechnical requirements of the IB < Ir ≤ IZ
circuit it protects. It ≤ 1.45 x IZ
Terminology
Environment IB = Circuit design current
Application guide
Record PlusTM breakers function well in almost any Ir = Current set on breaker
industrial environment . The EN 60947-2 defines the IZ = Current carrying capacity of electrical conductor
It = Tripping current of the protection device
main aspects of what is meant by "industrial
(Record PlusTM MCCB It ≤ 1.3 x Ir)
environment":
Temperature:
Use of the above mentioned formulae and the
Relative humidity:
Record PlusTM characteristics give the following results:
Altitude:
Breaker setting Ir ≤ IZ (It ≤ 1.3 x IZ)
Pollution:
In practice Ir is generally set at a value equal to IZ.
Network harmonic content:
Shock and vibration resistance:
Im setting - protected equipment
For conditions other than the above mentioned please
The magnetic or ST setting of a breaker (Im) is primarily
refer to page D.16 in which the effects of the
defined by the characteristics of the equipment and
environment are defined.
devices in the circuit .
The Record PlusTM device is equipped with trip units
Maximum short-circuit current
that react to fault currents when needed but are
Protective devices as the Record PlusTM circuit breaker
specifically designed not to react to most inrush-
must be able to interrupt the maximum short-circuit
current at the point where they are installed.
current profiles. A
The details included in this section on devices as LV/LV
The interruption ratings of these breakers (breaking
transformers and the time current curves of the
capacity) can be found elsewhere in this catalog.
breaker published elsewhere in this catalogue allow a
definition of the Im value.
B
Design current of a circuit
The equipment and devices in an electrical circuit
Im setting - protected lines
determines it's current load. The electrical conductor
cross sections that can be used in the circuit are
On a short-circuit event the total circuit impedance C
determines the highest and the lowest current that can
determined by a number of factors i.e.
flow in the circuit . It is necessary not only to verify if
the protective device can interrupt the maximum
- The design current of the circuit (IB).
short-circuit value but also if the device protecting the D
- Conductor type and it's insulation.
circuit reacts and disconnects in time at the lowest
(current capacity = IZ)
possible short-circuit value.
- Installation method.
- Temperature.
Due to the fact that a major part of the circuit
impedance is formed by electrical conductors like
E
- Number of conductors mounted in each others
cables, busbar systems etc. within the circuit , this
vicinity.
requirement has a limiting effect on the length of the
E.3
Record Plus
Protection against short-circuits
R064-003.The values published here are based on this 500 4 16.2 16.8 17.1 17.4 17.6 17.7
630 4 19.8 20.7 21.2 21.7 22.0 22.2
document .
630 5 16.3 16.9 17.2 17.6 17.7 17.8
630 6 13.8 14.3 14.5 14.7 14.8 14.9
Power supply 800 6 17.1 17.8 18.2 18.5 18.7 18.8
1000 6 20.8 21.8 22.3 22.9 23.2 23.4
The values mentioned in table indicate the effective 1250 6 25.1 26.6 27.4 28.3 28.7 29.0
values of the highest three phase short-circuit current 1600 6 30.6 32.9 34.2 35.6 36.3 36.8
that is available at the connection terminals of the 2000 6 36.4 39.7 41.6 43.6 44.7 45.4
2500 6 42.9 47.5 50.2 53.2 54.8 55.9
incoming transformer(s). 2 x 400 4 24.2 25.7 26.4 27.2 27.7 27.9
2 x 500 4 29.1 31.2 32.3 33.5 34.2 34.6
Incoming transformers 2 x 630 4 34.9 37.9 39.6 41.4 42.4 43.0
2 x 630 5 29.3 31.4 32.5 33.8 34.4 34.8
2 x 630 6 25.3 26.8 27.6 28.5 29.0 29.3
2 x 800 6 30.6 32.9 34.2 35.6 36.3 36.8
2 x 1000 6 36.4 39.7 41.6 43.6 44.7 45.4
2 x 1250 6 42.9 47.5 50.2 53.2 54.8 55.9
2 x 1600 6 50.7 57.3 61.3 65.9 68.4 70.0
2 x 2000 6 58.3 67.3 72.8 79.4 83.1 85.5
2 x 2500 6 66.3 78.1 85.7 94.9 100.3 103.9
3 x 400 4 33.6 36.4 37.9 39.6 40.5 41.1
A 3 x 500
3 x 630
4
4
39.7
46.8
43.7
52.3
45.9
55.6
48.5
59.4
49.8
61.4
50.7
62.7
3 x 630 5 40.0 43.9 46.2 48.8 50.2 51.0
3 x 630 6 34.9 37.9 39.6 41.4 42.4 43.0
3 x 800 6 41.6 46.0 48.5 51.3 52.8 53.8
B 3 x 1000
3 x 1250
6
6
48.6
56.1
54.6
64.3
58.2
69.3
62.3
75.3
64.6
78.6
66.0
80.8
Installation 3 x 1600 6 64.8 76.1 83.3 91.9 97.0 100.3
3 x 2000 6 72.9 87.5 97.2 109.2 116.4 121.2
3 x 2500 6 81.0 99.4 112.1 128.6 138.7 145.6
C Formulas
Medium voltage impedance
Terminology
(m Uo sqrt 3)2 SkQ = short-circuit power of the medium/high voltage
ZQ = mOhm
D SkQ
SrT
network
= power rating of the MV/LV transformer
MV/LV transformer impedance Ukr = short-circuit voltage in %, according to HD 398
m = no load factor; 1.05 assumed
(m Uo sqrt 3)2 Ukr Cmax. = voltage factor; 1.05 assumed
Zr = x mOhm
E SrT 100% Uo = phase to neutral voltage
Ik3max = maximum 3 phase short-circuit current
Maximum short-circuit calculation X = total reactance
XQ = 0.995 x ZQ
(cmax * m *Uo sqrt 3)2
F Ik3max =
Sqrt (R2 + X2)
kA XT
R
= 0.95 x ZT
= total resistance
RQ = 0.1 x XQ*
RT = 0.31 x ZT
E.4
Record Plus
Influence of cable runs
It is possible to calculate short-circuit values within
circuits by determining the impedance, reactance and
E.5
Record Plus
Protection against short-circuits
E.6
Record Plus
= 4 ≤ 50
70
0.63
0.64
Cu conductor
short-circuit setting of Record PlusTM device in Amps
C
Cross section 4000 4500 5000 5500 6000 6500 7000 7500 8000 9000 10000 12000
95 0.65 S in mm2
120 0.66 16 12
150 0.67 25 19 17
185
240
0.69
0.72
35
50
27
38
24
34
21
30
19
28
18
25 23 22 20
D
300 0.76 70 52 47 42 38 35 32 30 28 26 23
95 70 62 56 51 46 43 40 37 35 31 28 23
150 85 76 68 62 57 53 49 46 43 38 34 28
185 103 91 82 75 69 63 59 55 51 46 41 34 E
185 121 107 96 88 80 74 69 64 60 54 48 40
240 143 127 115 104 96 88 82 76 72 64 57 48
300 162 144 130 118 108 100 93 86 81 72 65 54
E.7
Record Plus
Personnel protection
If, in low voltage installations, a person makes contact If, in a low voltage installation, a person comes into
with two or more conductive materials/ surfaces with a contact with an earthed part that has accidentally
different electrical potential he or she will risk a been connected to a live conductor, he or she will risk a
potentially dangerous electrical shock. potentially dangerous electrical shock.
This results in an electrical current flowing through the The level of voltage over the contact , and the length of
persons body, the effects of which are indicated in time that the person has to endure this contact can be
figure 1 and the accompanying text . dangerous. This so called 'Touch Voltage' must be
(source IEC 60479-1) limited to values that a human being can endure
without physiological damage.
The environment in which the fault occurs, dry or
Application guide
E.8
Record Plus
Direct contact Indirect contact
Caused by an accident in which a person comes into Caused when person comes into contact with an
contact with a live electrical conductor and a second earthed part that has accidentally been connected to a
conductive part . Here the person in question becomes live conductor. The level of voltage over the contact ,
a part of the electrical circuit , the current in which is and the length of time that the person has to endure
determined by the resistance of the earth and that of this contact can be dangerous. This so called 'Touch
the human body. Voltage' must be limited to values that a human being
can endure without physiological damage.
Personnel protection
How to protect against? How to protect against?
The following methods can be used (source HD384) The following concepts can be applied (source HD384)
- The use of very low voltage systems as: - The use of very low voltage systems as:
SELV (safe, extra low voltage), PELV (protective extra SELV (safe, extra low voltage), PELV (protective extra A
low voltage) and low voltage) and
FELV (functional extra low voltage) FELV (functional extra low voltage)
- Appropriate conductor insulation. - Automatic disconnection of the power supply to the
- The use of mechanical barriers or that of enclosures installation, or a part thereof.
B
with the appropriate protection degree. (IP-) - The use of materials that provide total insulation
- Take the defined safety distances into account when (class II)
installing C
- The use of complementary protection, RCD's with a
sensitivity ≤ 30mA
E.9
Record Plus
Record Plus TM circuit breakers, TT system characteristics
used to protect against direct , One point of the power supply is connected to earth
or indirect contact whilst all conductive parts in the installation are
connected to electrically independent earth electrodes.
As moulded case circuit breakers, Record PlusTM have
properties that automatically forfill a number of the
requirements concerning direct and indirect contact . L1
When installed correctly, with the appropriate L2
L3
cover/trim/front plates the device itself offers a high 1 N
protection degree of up to IP40 whilst the moulded
7
case housing construction ensures a class II protection.
3
Application guide
Direct contact
They can be equipped with RCD's of 30mA that are
required as a complementary protection. 5
4
6 6
Indirect contact
Ideally suited to be used as a device to allow automatic
disconnection of the supply of a part or a full 2
E.10
Record Plus
TN system characteristics
One or more points of the power supply are connected If a fault to earth or insulation fault occurs, a circuit
to earth whilst all conductive parts in the installation comes into being, in which the current runs through the
are electrically connected to this point by protective live conductor that has caused the fault and the
conductors. (PE or PEN conductors). The system exits in protective conductor (PE or PEN). The fault circuit has a
three main variants: voltage equal to the phase to earth voltage U0 of the
TNC The neutral and protective conductor are system.
combined. (PEN) On indirect contact the touch voltage UL is not
TNS The neutral(N) and protective conductor (PE) exceeded if the following conditions are met
are separate.
Personnel protection
Zs x IA ≤ U0
TNCS The supply is configured as a TNC, the system
changes to a TNS system at a Zs = Impedance of the fault circuit .
pre-defined point in the LV installation. IA = The operating threshold of the protective
device, that warranties a total disconnection
time dependant on the phase to earth system
TNC voltage. (see table insert)
L1 U0 = The phase to earth voltage of the system.
L2
L3
1 PEN If the ZS value reaches high values due to long cable
7
runs the use of RCD's is allowed. (I A is then replaced by
8
the Idn of the RCD).
3
2 6
TNS
L1
D
L2
L3
1 N
6
PE E
7
3
F
5
4
0
G
2
X
O
1 Power supply.
O
2 Power supply earthing.
O
3 Low voltage installation, consumer portion.
O
4 Equipment present in installation.
O
5 Exposed conductive parts/surfaces.
O
6 Protective conductor.
O
7 Protective device.
E.11
Record Plus
IT system characteristics Required calculations in TN and
The supply is isolated from earth or connected to earth
IT networks
by means of an impedance of a relatively high value. In both the IT and TN network configuration it is
The conductive parts in the installation are connected necessary to verify that the protective device will
to earth electrodes. interrupt the circuit within the defined disconnection
time. Here the worst case scenario needs to be taken
L1
L2
into account and the weakest possible current flowing
L3 in the circuit , on a insulation or earth fault must be
1
defined (The fault current If).
8
O
1 Power supply.
O
2 Power supply earthing. Use of Record Plus TM breakers in
O
3 Low voltage installation, consumer portion. this application
O
4 Equipment present in installation.
O
5 Exposed conductive parts/surfaces. Circuit breakers of the Record PlusTM type disconnect
O
6 Impedance for insulation from earth. within 0.1 seconds on their magnetic threshold (Im on
O
7 Insulation monitoring device + surge protection the electromechanical device) and within 0.2 seconds
O
8 Protective device. on their ST device (Im on the SMR1 electronic device*).
A To assure a disconnection that meets the requirements
On the first fault to earth or insulation fault in an IT the circuit fault current Id must be higher than the Im
system, the protective device does not need to react . value.
Here no fault circuit to earth exists and no potentially With the Im value and the system voltage it is now
B dangerous contact can occur. possible to calculate the maximum ZS value of the fault
However, depending on the location of the fault to circuit . This is mainly made up of the electrical
earth the first fault modifies the system from an conductors in the circuit , therefore these calculations
C isolated IT into a non isolated TN or TT system. result in a maximum cable run length.
To indicate that the IT system is no longer functional
the use of insulation monitoring devices providing a Formula for calculating the cable run length.
visual and sonorous alarm of the event is necessary.
D With the first fault still existing, a second fault to earth Lmax= 0.8 x
Cmin x _ x Uo
x k1 x k2 x k3 meters
must cause an automatic disconnection of the supply {2 x [= 3(R2 + X2)]} x (Im x kt)
that must meet the conditions and formulae set out for
E TT and TN systems indicated here. Terminology
The possible distribution of a neutral within the system Lmax = Maximum cable run length
does modify the allowed disconnection times as 0.8 = Assumed factor for the impedance of the upstream
indicated in the table below. network.
F Cmin. = Voltage factor; 0.95 assumed
_ = Coefficient depending on earthing system
TN = 1 IT no neutral = 0.86 IT with neutral = 0.5
Network voltage Maximum disconnecting time
(AC system) Uo = Phase to neutral voltage
Phase-Neutral U0 /
X = Reactance of the conductors or cables in the circuit.
G Phase-Phase Un
No neutral distributed Neutral distributed Reactance of multi core cables h m1 /m. 0.08
R = Resistance of the conductors or cables in the circuit.
127/230V 0.8 sec. 5 sec. based on the following basic data:
230/400V 0.4 sec. 0.8 sec.
l1 = 23.69 m1 mm2/m. for copper cores.*
400/690V 0.2 sec. 0.4 sec.
X 37.64 m1 mm2/m. for aluminum cores.*
Im x kt = Magnetic or ST setting of breaker (Im) x plus tolerance factor
Remark (kt[=1.2])
On a second insulation fault the protective device can be required to
k1-3 = Correction factor (see page with cable run calculations)
interrupt the full fault current in a circuit with a voltage equal to the
phase to phase value Un. The requirements for interrupting this single These being the values in accordance with the Cenelec
phase fault are now included in the EN 60947-2 (appendix H). Needless R064-003 document for calculating the weakest short-circuit
to say that the Record PlusTM breaker meet these requirements, the current with circuit breakers (worst case assumed)
exact single phase or I values are mentioned in the tables covering
IT
the technical data of the breaker.
* = 1.28 x 18.51 and 1.28 x 29.41.
E.12
Record Plus
Cable run length calculations Maximum cable length in meters in a 3 phase TN system
(U0=230V). For IT system see text, calculations based on
device muticore cables. (worst case)
To meet the requirements the short-circuit device (Im) Cu conductor short-circuit setting of Record PlusTM device in Amps
of the circuit breaker must react to a current equal or Cross section 50 75 100 125 150 200 250 300 350 400 450 500
S in mm2
lower than the fault current (If). 1.5 92 61 46 37 31 23
The table indicates the maximum cable lengths where 2.5 154 102 77 61 51 38 31 26 22 19 17 15
4 246 164 123 98 82 61 49 41 35 31 27 25
this condition is still met . This taking into account the 6 246 246 184 148 123 92 74 61 53 46 41 37
tolerances on the settings of the short-circuit device in 10 246 307 246 205 154 123 102 88 77 68 61
the breaker. (see factor kt [=1.2]) 16 393 327 246 196 164 140 123 109 98
25 393 511 383 306 255 219 191 170 153
Personnel protection
35 534 427 356 305 267 237 214
Correction factors _ 50 534 606 505 433 379 337 303
70 698 598 524 465 419
For TN networks and IT networks with different voltages 95 698 795 695 618 556
and with or without distributed neutral. 120 855 760 684
150 855 914 823
185 914 965
Neutral distributed
TN network
Uo/Un Yes No
_ _ Cu conductor short-circuit setting of Record PlusTM device in Amps
Cross section 600 700 800 900 1000 1250 1500 1750 2000 2500 3000 3500
127 /230V AC 0.55 1.00 S in mm2
230/400V AC 1.00 1.74 2.5 13
400/690V AC 1.74 3.00 4 20 18 15 14
6 31 26 23 20 18 15 12
10 51 44 38 34 31 25 20 18 15 12
16 82 70 61 55 49 39 33 28 25 20 16 14
Neutral distributed 25 128 109 96 85 77 61 51 44 38 31 26 22
IT network
Uo/Un Yes No 35 178 153 134 119 107 85 71 61 53 43 36 31
_ _ 50 253 217 189 168 152 121 101 87 76 61 51 43
70 349 299 262 233 209 168 140 120 105 84 70 60
127 /230V AC 0.28 0.49 95 464 397 348 309 278 222 185 159 139 111 93 79
230/400V AC 0.50 0.86 120 570 488 427 380 342 274 228 195 171 137 114 98
400/690V AC 0.87 1.48 150 686 588 514 457 411 329 274 235 206 165 137 118
185 804 689 603 536 482 386 322 276 241 193 161 138
240
300
955 819
926
717
810
637
720
573
648
459
518
382
432
328
370
287
324
229
259
191
216
164
185
A
Correction factor k1
For a 3 phase circuit with a voltage of 400V between TM
short-circuit setting of Record Plus device in Amps
Cu conductor
phases and a protective conductor with a cross section Cross section 4000 4500 5000 5500 6000 6500 7000 7500 8000 9000 10000 12000
S in mm2
B
smaller than the phase value.
16 12
25 19 17
Sph/Spe or pen k1 35 27 24 21 19 18
50
70
38
52
34
47
30
42
28
38
25
35
23
32
22
30
20
28 26 23
C
1.00 1.00 95 70 62 56 51 46 43 40 37 35 31 28 23
0.67 0.75 150 85 76 68 62 57 53 49 46 43 38 34 28
0.50 0.67 185 103 91 82 75 69 63 59 55 51 46 41 34
0.33 0.50 185
240
121
143
107
127
96
115
88
104
80
96
74
88
69
82
64
76
60
72
54
64
48
57
40
48
D
300 162 144 130 118 108 100 93 86 81 72 65 54
Correction factor k2
For a number multi core cables in parallel
E
k2 2 = 2.00
k2 3 = 2.65
F
Correction factor k3
For multicore cables with conductors made of
aluminium.
G
AL conductor k3
cross section
S in mm2
X
= 4 ≤ 50 0.63
70 0.64
95 0.65
120 0.66
150 0.67
185 0.69
240 0.72
300 0.76
E.13
Record Plus
Selectivity/Discrimination Fig. 1
F 3D discrimination
Record PlusTM downstream-protection-device breakers
limit the energy and current in the protected circuit in a
G limited time frame. The use of relatively minor time
delays in the short-circuit protection of the upstream Fig. 3
breaker, allows the Record PlusTM line of circuit breakers
X to achieve total discrimination. Fig. 3 depicts this
comparison technique. In this graph the Grey area
indicates the time and current values the downstream
Msec.
breaker allows to flow in the circuit . The coloured area
depicts the current- and energy-reaction level of the
upstream device within a certain set time frame.
A2S
A
E.14
Record Plus
How to determine
discrimination/selectivity with
Record Plus TM (and associated
devices)
Table D1 to D5 (page E.16-E.19) indicate the discrimination up to the highest breaking capacity of the
Selectivity/Discrimination
discrimination levels that can be achieved with devices.
Record PlusTM and associated devices. Where These discrimination/selectivity limits are only valid if the
discrimination is partial the selectivity limits in kA (Is) are ratio between the current settings, ratings or time
mentioned in kA. settings of the upstream and downstream breaker are
Where a "T" is found in the tables, this indicates total equal or higher than the factor indicated here.
Selectivity/Discrimination
Downstream device Upstream device
Record PlusTM MCCB
LTM or LTMD SMR1, 1e, 1s or 1g SMR2
Redline & Hti MCB B, C & D curve Ir factor 1.6 Ir factor 2 Ir factor * 1.6
Im factor 2 Ist factor 1.5 Ist factor 1.5
Surion Manual Motor Starter Thermal mag or Mag. Only Ir factor 3 Ir factor 2 Ir factor * 1.6
Im factor 3 Ist factor 1.5 Ist factor 1.5
TM
Record Plus MCCB LTM or LTMD Ir factor 1.6 Ir factor 2 Ir factor * 1.6
Im factor 1.5 Ist factor 1.5 Ist factor 1.5
SMR1 Ir factor 1.6 Ir factor 1.6 Ir factor * 1.6
Im factor 1.5 Ist factor 1.5 Ist factor 1.5
Mpact ACB
B
MPRO 17 MPRO 20, 30 & 40
Record PlusTM MCCB SMR1 Ir factor 1.6 Ir factor 1.6
Ist factor
STD timing
1.5
0.2
LTD Class
Ist factor
20
1.5
C
STD timing 0.2
A2S band 0.1
Record PlusTM MCCB SMR1s Ir factor 1.6 Ir factor 1.6
SMR2 Ist facto 1.5
STD Set at one band higher
LTD set at one class higher
Ist factor 1.5
D
STD Set at one band higher
2
A S Set at one band higher
E
* LTD set at class 20
Terminology
F
LTM Thermal magnetic Trip Unit
Ir = Overload setting Im = Magnetic setting
LTMD Selective Thermal magnetic Trip Unit
Ir = Overload setting Im = Magnetic setting
Mag. BreakTM Magnetic Only Trip Unit G
Im = Magnetic setting
SMR1 & SMR1e Selective Electronic Trip unit
Ir = Setting on LT device Ist = Setting on ST device
SMR1s,g and SMR2 Enhanced Electronic Trip unit
MPRO 17, 20, 30 & 40 Mpact Electronic Trip Units X
Ir = Setting on LT device Ist = Setting on ST device
E.15
Record Plus
Table D1 - Selectivity/Discrimination
Record PlusTM type
Upstream
FD160E FD160S FD160N, H & L
In (A) 40 50 63 80 100 125 160 40 50 63 80 100 125 160 40 50 63 80 100 125 160
Downstream Selectivity limit in kA
Redline ≤16 0.6 2.5 T T T T T T T T T T T T T T T T T T T
G60 & DM60 20 0.6 2.5 3 T T T T 3.5 T T T T T T 3.5 T T T T T T
25 - 0.8 1.2 T T T T 1.6 3.5 T T T T T 1.6 3.5 T T T T T
C45 & C60 32 - - 1.2 3 T T T - - T T T T T - - T T T T T
40 - - - 3 4 T T - - - T T T T - - T T T T T
50 - - - 1.2 1.5 T T - - - 3.5 T T T - - - 3.5 T T T
63 - - - - 1.5 2 T - - - - T T T - - - - T T T
G100 & DM100 ≤16 0.6 2.5 6 6 T T T T T T T T T T T T T T T T T
20 0.6 2.5 2.5 6 8 T T 3.5 T T T T T T 3.5 T T T T T T
Application guide
* T = Total: selective unil the lowest Icu value of the two devices placed in series.
E.16
Record Plus
Table D2 - Selectivity/Discrimination
Record PlusTM type
Upstream
FE160N, H & L - LTM FE160N, H & L - LTMD FE160N, H & L - SMR1 FE250N, H & L - LTMD FE250N, H & L - SMR1
In (A) 63 80 100 125 160 100 125 160 63 125 160 125 160 200&250 125 160 250
Downstream Selectivity limit in kA
Redline ≤20 T T T T T T T T T T T T T T T T T
G60 & DM60 25 1.2 T T T T T T T T T T T T T T T T
Selectivity/Discrimination
32 1.2 3 T T T T T T T T T T T T T T T
C45 & C60 40 - 3 4 T T T T T - T T T T T T T T
50 - 1.2 1.5 T T T T T - T T T T T T T T
63 - - 1.5 2 T - T T - T T T T T T T T
G100 & DM100 ≤16 6 6 T T T T T T T T T T T T T T T
20 2.5 6 8 T T T T T T T T T T T T T T
25 1.2 6 6 T T T T T T T T T T T T T T
32 1.2 3 6 8 T T T T T T T T T T T T T
40 - 3 4 6 6 T T T T T T T T T T T T
50 - 1.2 1.5 6 6 T T T - T T T T T T T T
63 - - 1.5 2 2 - T T - T T T T T T T T
GT25 B/C curve ≤16 6 6 10 T T T T T T T T T T T T T T
20 2.5 6 8 T T T T T T T T T T T T T T
25 1.2 6 6 10 T T T T T T T T T T T T T
32 1.2 3 6 8 10 T T T T T T T T T T T T
40 - 3 4 6 6 T T T T T T T T T T T T
50 - 1.2 1.5 6 6 T T T - T T T T T T T T
63 - - 1.5 2 2 - T T - T T T T T T T T
Hti - B/C curve 80 - - - 1 2 - T T - T T - T T - T T
100 - - - - 2 - - T - - T - T T - T T
125 - - - - - - - T - - T - - T - - T
S90 - C curve ≤32 0.6 0.8 0.95 1.2 1.5 T T T T T T T T T T T T
40 - - 0.9 1.2 1.5 T T T T T T T T T T T T
50 - - - 1.2 1.5 T T T - T T T T T T T T
63 - - - - 1.5 - T T - T T T T T T T T
80 - - - - 1.5 - T T - T T - T T - T T
100 - - - - - - - T - - T - T T - T T
Surion ≤20 0.6 3 6 6 10 T T T T T T T T T T T T
GPS1BS & GPS1MS 25 0.6 3 6 6 10 T T T T T T T T T T T T
GPS2BS & GPS2MS 32
40
0.6
0.6
3
1
3
1
6
6
8
6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A
50 - 1 1 3 6 T T T - T T T T T T T T
63 - - 1 3 4 - T T - T T T T T T T T
Surion ≤20 0.6 2.5 6 6 10 T T T T T T T T T T T T
GPS1BH & GPS1MH
GPS2BH & GPS2MH
25
32
0.6
0.6
2.5
2.5
6
3
6
6
10
8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B
40 0.6 1 1.2 6 6 T T T T T T T T T T T T
50 - 1 1.2 2.5 6 T T T - T T T T T T T T
63 - - 1.2 2.5 6 - T T - T T T T T T T T
Record PlusTM
FD160E
≤40
50
0.6
-
1
1
1
1
1
1
2
2
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
C
63 - - 1 1 2 T T T - T T T T T T T T
80 - - - 1 2 - T T - T T T T T T T T
100 - - - - 2 - - T - - T - T T - T T
125
160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
T
-
-
-
-
-
T
-
-
-
-
-
T
T
-
-
-
-
T
T
D
TM
Record Plus ≤40 0.63 0.8 1 1.25 1.6 30 30 30 36 36 36 42 42 42 50 50 50
FD160S 50 - 0.8 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50
FD160N 63 - - 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50
FD160H 80 - - - 1.25 1.6 - 30 30 - 36 36 42 42 42 50 50 50 E
FD160L 100 - - - - 1.6 - - 30 - - 36 - 42 42 - 50 50
125 - - - - - - - - - - - - - 42 - - 50
160 - - - - - - - - - - - - - 42 - - 50
Record PlusTM ≤40 0.6 0.8 1 1.25 1.6 30 30 30 36 36 36 42 42 42 50 50 50
FE160N LTM 50 - 0.8 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50 F
FE160H LTM 63 - - 1 1.25 1.6 30 30 30 - 36 36 42 42 42 50 50 50
FE160L LTM 80 - - - 1.25 1.6 - 30 30 - 36 36 42 42 42 - 50 50
100 - - - - 1.6 - - 30 - - 36 - 42 42 - 50 50
125 - - - - - - - - - - 36 - - 42 - - 50
G
* T = Total: selective unil the lowest Icu value of the two devices placed in series.
E.17
Record Plus
Table D3 - Selectivity/Discrimination
Record PlusTM type
Upstream
FE160N,H&L - SMR1 FE250N,H&L - LTMD FE250N,H&L - SMR1 FG400/630N, H&L - SMR1 & SMR2(1)
In (A) 63 125 160 125 160 200&250 125 160 250 400/250 400/350 400/400 630/400 630/500 630/630
Downstream Selectivity limit in kA
Redline
G60 B/C curve ≤40 T T T T T T T T T T T T T T T
G100 B/C curve 50 - T T T T T T T T T T T T T T
GT25 B/C curve 63 - T T - T T - T T T T T T T T
Hti - B/C curve ≤80 - - T - T T - T T T T T T T T
100 - - T - T T - T T T T T T T T
125 - - - - - T - - T T T T T T T
S90 - C curve ≤40 T T T T T T T T T T T T T T T
50 - T T T T T T T T T T T T T T
Application guide
63 - T T T T T T T T T T T T T T
80 - - T - T T - T T T T T T T T
100 - - - - - T - - T T T T T T T
Surion ≤40 T T T T T T T T T T T T T T T
GPS1BS & GPS1MS 50 - T T T T T T T T T T T T T T
GPS2BS & GPS2MS 63 - T T T T T T T T T T T T T T
GPS1BH & GPS1MH ≤40 - T T T T T T T T T T T T T T
GPS2BH & GPS2MH 50 - T T T T T T T T T T T T T T
63 - T T T T T T T T T T T T T T
Record PlusTM ≤32 T T T T T T T T T T T T T T T
FD160E 40 T T T T T T T T T T T T T T T
FD160S 50 - T T T T T T T T T T T T T T
LTM 63 - T T T T T T T T T T T T T T
80 - T T T T T T T T T T T T T T
100 - - T - T T - T T T T T T T T
125 - - - - - T - - T T T T T T T
160 - - - - - T - - T T T T T T T
Record PlusTM ≤32 T T T T T T T T T T T T T T T
FD160 N, H & L 40 36 36 36 42 42 42 50 50 50 T T T T T T
LTMD & MO 50 - 36 36 42 42 42 50 50 50 T T T T T T
63 - 36 36 42 42 42 50 50 50 T T T T T T
80 - 36 36 42 42 42 50 50 50 T T T T T T
A 100
125
-
-
-
-
36
-
-
-
42
-
42
42
-
-
50
-
50
50
T
T
T
T
T
T
T
T
T
T
T
T
160 - - - - - 42 - - 50 T T T T T T
Record PlusTM ≤32 36 36 36 42 42 42 50 50 50 T T T T T T
FE160 N, H & L 40 36 36 36 42 42 42 50 50 50 T T T T T T
B LTM & MO 50
63
-
-
36
36
36
36
42
42
42
42
42
42
50
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
T
T
80 - 36 36 - 42 42 - 50 50 T T T T T T
100 - - 36 - 42 42 - 50 50 T T T T T T
125 - - - - - 42 - - 50 - T T T T T
C Record PlusTM
160
≤32
-
0.8
-
1.8
-
2.2
-
1.3
-
1.6
42
2.5
-
1.8
-
2.2
50
3.5
-
T
T
T
T
T
T
T
T
T
T
T
FE160 N, H & L 40 0.8 1.8 2.2 1.3 1.6 2.5 1.8 2.2 3.5 T T T T T T
LTMD 50 - 1.8 2.2 - 1.6 2.5 - 2.2 3.5 T T T T T T
SMR1 63 - 1.8 2.2 - 1.6 2.5 - 2.2 3.5 T T T T T T
D 80
100
-
-
-
-
2.2
2.2
-
-
1.6
1.6
2.5
2.5
-
-
2.2
2.2
3.5
3.5
T
T
T
T
T
T
T
T
T
T
T
T
125 - - - - - 2.5 - - 3.5 T T T T T T
160 - - - - - 2.5 - - 3.5 T T T T T T
Record PlusTM 125 - - - - - 2.5 - - 3.5 15 15 15 T T T
E FE250 N, H & L 160 - - - - - - - - - - 15 15 T T T
LTMD 200 - - - - - - - - - - 15 15 T T T
SMR1 250 - - - - - - - - - - 15 15 T T T
Record PlusTM 250 - - - - - - - - - - - - 6 6 6
FG400 N, H & L 350 - - - - - - - - - - - - - 6 6
F SMR1 400 - - - - - - - - - - - - - - 6
* T = Total: selective unil the lowest Icu value of the two devices placed in series.
(1) ...../..... = Contact rating/Sensor rating
G
E.18
Record Plus
Table D4 - Selectivity/Discrimination
Record PlusTM type
Upstream
FK800N&H SMR1 FK800L SMR1 FK1250N&H SMR1 FK1250L SMR1 FK1600N&H SMR
Selectivity/Discrimination
Surion
GPS All T T T T T T T
Hti All T T T T T T T
S90 All T T T T T T T
Record PlusTM
FD160 E, S, N, H & L All T T T T T T T
FE160N, H and L All T T T T T T T
FE250 N, H & L All T T T T T T T
FG400 N, H & L All T T T T T T T
FG630N, H & L All 25 25 T T T T T
FK800 N, H & L All - - 15 15 15 15 25
FK1250 N, H & L All - - - - - - 25
* T = Total: selective until the Icu of the downstream device OR the Icu of the upstream device
Table D5 - Selectivity/Discrimination
M Pact ACB type
Upstream
Frame1 N and H type Frame2 N and H type
In (A) 400 800 1000 1250 1600 2000 2500 1000 1250 1600 2000 2500 3200 4000
Downstream Selectivity limit in kA
Redline
G60/100/GT25 All T T T T T T T T T T T T T T
Surion
GPS All T T T T T T T T T T T T T T
Hti
S90
All T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A
Record PlusTM
FD160 E, S, N, H & L All T T T T T T T T T T T T T T
FE160 N, H & L All T T T T T T T T T T T T T T
FE250 N, H & L
FG400 N, H & L
All
250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B
350 - T T T T T T T T T T T T T
400 - T T T T T T T T T T T T T
FG630 N, H & L 400 - T T T T T T T T T T T T T
500
630
-
-
-
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
C
FK800 N, H & L All - - - T T T T T T T T T T T
FK1250 N, H & L 1000 - - - - T T T - T T T T T T
1250 - - - - - T T - - T T T T T
FK1600 N and H
Mpact ACB
1600
400
-
-
-
T
-
T
-
T
-
T
T
T
T
T
-
T
-
T
-
T
T
T
T
T
T
T
T
T
D
Frame 1 800 - - - T T T T - T T T T T T
Frame 2 1000 - - - - T T T - - T T T T T
1250 - - - - - T T - - - T T T T
1600 - - - - - - T - - - - T T T E
2000 - - - - - - T - - - - - T T
2500 - - - - - - - - - - - - - T
* T = Total: selective until the Icu of the downstream device OR the Icu of the upstream device F
E.19
Record Plus
Back-up protection
One of the operational requirements for a protective
device is that its rated short-circuit breaking capacity
Icu or Ics is either equal or greater than the prospective
short-circuit current at the point where it is installed.
EN 60384 defines one exception to this in clause 434:
E.20
Record Plus
Table B1 - Back-up protection at 230/240V
Record PlusTM type
Upstream
FK1250N
FK1600N
FK1250H
FK1600H
FD63/160N
FD63/160H
FD63/160E
FK1250L
FD63/160S
FD63/160L
FG400N
FG630N
FG400H
FG630H
FK800N
FK800H
FE160N
FE250N
FE160H
FE250H
FG400L
FG630L
FK800L
FE160L
FE250L
Icu
Downstream In (A) 36 50 85 100 200 85 100 200 85 100 200 85 100 200 85 100 200 80 100 170 80 100 170 80 100
Icu of the combination in kA
Redline
C30 3 4.5 6 8 10 12 8 10 12 4.5 6 8 - - - - - - - - - - - - - -
C60 & DME60 6 10 12 15 18 22 15 18 22 10 12 15 - - - - - - - - - - - - - -
G60 & DM60 6 22 25 36 85 85 36 85 85 36 50 50 16 16 16 14 14 14 - - - - - - - -
G100 & DM100 10 30 36 50 100 100 50 100 100 50 65 65 22 22 22 16 16 16 - - - - - - - -
GT25 ≤25A 25 36 50 85 100 100 85 100 100 85 85 85 - - - - - - - - - - - - - -
Back-up protection
GT25 32 & 40A 20 30 36 65 100 100 65 100 100 65 85 85 - - - - - - - - - - - - - -
GT25 50 & 63A 15 25 30 50 100 100 50 100 100 50 65 65 - - - - - - - - - - - - - -
Hti 15 25 30 50 100 100 50 100 100 50 65 65 - - - - - - - - - - - - - -
S90 25 36 50 85 100 100 85 100 100 85 85 85 - - - - - - - - - - - - - -
Surion
GPS1A ≤16A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS1A >16A 50 - - 85 100 150 - 100 150 - 100 150 - - - - - - - - - - - - - -
GPS1HA all 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2A ≤16A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2A >16A 50 - - 85 100 150 - 100 150 - 100 150 - - - - - - - - - - - - - -
GPS2HA all 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
Record PlusTM
FD160E 36 - 50 65 85 100 65 85 100 65 85 100 65 85 100 65 85 100 - - - - - - - -
FD160S 50 - - - 85 100 - 85 100 - 85 100 - 85 100 - 85 100 - - - - - - - -
FD160N 85 - - - 100 200 - 100 200 - 100 200 - 100 200 - 100 200 80 100 150 80 100 150 80 100
FD160H 100 - - - - 200 - - 200 - - 200 - - 200 - - 200 - 100 150 - 100 150 - 100
FE160N 85 - - - - - - 100 200 - 100 200 - 100 200 - 100 200 80 100 150 80 100 150 80 100
FE160H 100 - - - - - - - 200 - - 200 - - 200 - - 200 - 100 150 - 100 150 - 100
FE250N 85 - - - - - - - - - 100 200 - 100 200 - 100 200 80 100 150 80 100 150 80 100
FE250H 100 - - - - - - - - - - 200 - - 200 - - 200 - 100 150 - 100 150 - 100
FG400N 85 - - - - - - - - - - - - 100 200 - 100 200 80 100 150 80 100 150 80 100
FG400H 100 - - - - - - - - - - - - - 200 - - 200 - 100 150 - 100 150 - 100
FG630N 85 - - - - - - - - - - - - - - - 100 200 80 100 150 80 100 150 80 100
FG630H 100 - - - - - - - - - - - - - - - - 200 - 100 150 - 100 150 - 100
FK800N
FK800H
80
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
- 80 100 150 80 100 150 80 100
- - 100 170 - 100 170 - 100
A
FK1250N 80 - - - - - - - - - - - - - - - - - 80 100 170 80 100 170 80 100
FK1250H 100 - - - - - - - - - - - - - - - - - - 100 170 - 100 170 - 100
FK1600N
FK1250H
FK1600H
FD63/160N
FD63/160H
FD63/160E
FK1250L
FD63/160S
FD63/160L
FG400N
FG630N
FG400H
FG630H
FK800N
FK800H
FE160N
FE250N
FE160H
FE250H
FG400L
FG630L
FK800L
FE160L
FE250L
Icu C
Downstream In (A) 25 30 50 80 150 50 80 150 50 80 150 50 80 150 50 80 150 50 80 100 50 80 100 50 80
Icu of the combination in kA
Redline
G60 & DM60 6 15 22 30 36 40 30 36 40 22 30 36 12 12 12 10 10 10 - - - - - - - -
D
G100 & DM100 10 15 25 36 40 50 36 40 50 25 36 40 22 22 22 16 16 16 - - - - - - - -
GT25 ≤25A 25 - 30 40 50 65 40 50 65 30 40 40 - - - - - - - - - - - - - -
GT25 32 & 40A 20 - 30 36 40 50 36 40 50 30 36 40 - - - - - - - - - - - - - -
GT25 50 & 63A 15 - 25 36 40 50 36 40 50 25 36 40 - - - - - - - - - - - - - - E
Hti 10 15 25 36 40 50 36 40 50 25 36 36 - - - - - - - - - - - - - -
S90 15 - 25 36 40 50 36 40 50 25 36 40 - - - - - - - - - - - - - -
Surion
GPS1A ≤10A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS1A 12.5A 50 - - - 80 150 - 80 150 - 80 150 - - - - - - - - - - - - - - F
GPS1A ≥16A 25 - - 40 50 65 40 50 65 40 50 65 - - - - - - - - - - - - - -
GPS1HA ≤12.5A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS1HA >12.5A 50 - - - 80 150 - 80 150 - 80 150 - - - - - - - - - - - - - -
GPS2A 10A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2A > 10A 25 - - 40 50 65 40 50 65 40 50 65 - - - - - - - - - - - - - - G
GPS2HA 10A 100 - - - - 150 - - 150 - - 150 - - - - - - - - - - - - - -
GPS2HA > 10A 50 - - - 80 150 - 80 150 - 80 150 - - - - - - - - - - - - - -
Record PlusTM
FD160E 25 - 30 36 42 50 36 42 50 36 42 50 36 42 50 36 42 50 - - - - - - - -
FD160S 36 - - 42 50 65 42 50 65 42 50 65 42 50 65 42 50 65 - - - - - - - - X
FD160N 50 - - - 80 150 - 80 150 - 80 150 - 80 150 - 80 150 - 80 100 - 80 100 - 80
FD160H 80 - - - - 150 - - 150 - - 150 - - 150 - - 150 - - 100 - - 100 - -
FE160N 50 - - - - - - 80 150 - 80 150 - 80 150 - 80 150 - 80 100 - 80 100 - 80
FE160H 80 - - - - - - - 150 - - 150 - - 150 - - 150 - - 100 - - 100 - -
FE250N 50 - - - - - - - - - 80 150 - 80 150 - 80 150 - 80 100 - 80 100 - 80
FE250H 80 - - - - - - - - - - 150 - - 150 - - 150 - - 100 - - 100 - -
FG400N 50 - - - - - - - - - - - - 80 150 - 80 150 - 80 100 - 80 100 - 80
FG400H 80 - - - - - - - - - - - - - 150 - - 150 - - 100 - - 100 - -
FG630N 50 - - - - - - - - - - - - - - - 80 150 - 80 100 - 80 100 - 80
FG630H 80 - - - - - - - - - - - - - - - - 150 - - 100 - - 100 - -
FK800N 50 - - - - - - - - - - - - - - - - - - 80 100 - 80 100 - 80
FK800H 80 - - - - - - - - - - - - - - - - - - - 100 - - 100 - -
FK1250N 50 - - - - - - - - - - - - - - - - - - 80 100 - 80 100 - 80
FK1250H 80 - - - - - - - - - - - - - - - - - - - 100 - - 100 - -
E.21
Record Plus
Application guide
Selectivity Plus
Back-up protection requires an upstream device to open in the rated short-circuit breaking capacity of the downstream
order to protect the downstream device(s) before the down- breaker.
stream devices can be damaged. For continuity of service it is Tables DB1 to DB5 provide the data for the
desirable that the upstream device remains closed and that Record PlusTM breaker line used in combination with the
only the downstream device closest to the fault reacts. ElfaPlus, Surion and MPact protection devices. The values in
The Record PlusTM family of breakers resolves this paradox: the the table are in kA and indicate the results of the Selectivity
breakers are so current limiting that let-through energy and Plus technique.
current are not sufficient to operate the upstream breaker. Before the slash the discrimination limit in kA, after the slash
Application guide
The result discrimination to current levels that are higher than the back-up protection value at 400V in kA (e.g. 50/80).
In (A) 63 80 100 125 160 63 80 100 125 160 63 80 100 125 160
Downstream Selectivity limit in kA / Maximum Icu of combination at 400/415V ac
Redline ≤20 16/16 16/16 16/16 16/16 16/16 22/22 22/22 22/22 22/22 22/22 25/25 25/25 25/25 25/25 25/25
G30 B/C curve 25 15/16 15/16 16/16 16/16 16/16 15/22 15/22 22/22 22/22 22/22 15/25 15/25 25/25 25/25 25/25
32 10/16 10/16 16/16 16/16 16/16 10/22 10/22 22/22 22/22 22/22 10/25 10/25 25/25 25/25 25/25
40 - 10/16 15/16 16/16 16/16 - 10/22 22/22 22/22 22/22 - 10/25 15/25 25/25 25/25
50 - - 10/16 16/16 16/16 - - 22/22 22/22 22/22 - - 10/25 22/25 22/25
63 - - - 16/16 16/16 - - - 22/22 22/22 - - - 22/25 22/25
G60 B/C curve ≤20 25/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36
25 15/25 15/25 25/25 25/25 25/25 15/30 30/30 30/30 30/30 30/30 22/36 30/36 30/36 30/36 30/36
32 10/25 10/25 25/25 25/25 25/25 10/30 30/30 30/30 30/30 30/30 16/36 25/36 25/36 25/36 25/36
A 40
50
-
-
10/25
-
15/25
10/25
25/25
22/25
25/25
22/25
-
-
22/30
-
30/30
22/30
30/30
22/30
30/30
22/30
-
-
22/36 25/36 25/36 25/36
- 22/36 22/36 22/36
63 - - - 22/25 22/25 - - - 22/30 22/30 - - - 22/36 22/36
G100 B/C curve ≤20 25/30 30/30 30/30 30/30 30/30 30/36 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 36/42
25 15/30 15/30 30/30 30/30 30/30 15/36 15/36 30/36 30/36 30/36 15/42 15/42 30/42 30/42 30/42
B 32
40
10/30
-
10/30
10/30
30/30
15/30
30/30
25/30
30/30
25/30
10/36
-
10/36
10/36
25/36
15/36
25/36
25/36
25/36
25/36
10/42 10/42 25/42 25/42 25/42
- 10/42 15/42 25/42 25/42
50 - - 10/30 22/30 22/30 - - 10/36 22/36 22/36 - - 10/42 22/42 22/42
63 - - - 22/30 22/30 - - - 22/36 22/36 - - - 22/42 22/42
GT25 B/C curve ≤20 30/36 36/36 36/36 36/36 36/36 30/42 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50 36/50
C 25
32
15/36
10/36
15/36
10/36
30/36
30/36
30/36
30/36
30/36
30/36
15/42
10/42
15/42
10/42
30/42
30/42
30/42
30/42
30/42
30/42
15/50 15/50 30/50 30/50 30/50
10/50 10/50 30/50 30/50 30/50
40 - 10/36 15/36 25/36 25/36 - 10/42 15/42 25/42 25/42 - 10/50 15/50 25/50 25/50
50 - - 10/36 22/36 22/36 - - 10/42 22/42 22/42 - - 10/50 22/50 22/50
63 - - - 22/36 22/36 - - - 22/42 22/42 - - - 22/50 22/50
D Surion
GPS1BA
≤10
12.5
50/50
36/36
50/50
36/36
50/50
36/36
50/50
36/36
50/50
36/36
80/80
42/42
80/80
42/42
80/80
42/42
80/80
42/42
80/80
42/42
150/150 150/150 150/150 150/150 150/150
50/50 50/50 50/50 50/50 50/50
GPS1MA 16/20 36/36 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 50/50
GPS2BA 25/32 36/36 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 50/50
GPS2MA 40 - 36/36 36/36 36/36 36/36 - 42/42 42/42 42/42 42/42 - 50/50 50/50 50/50 50/50
E 50/63 - - 36/36 36/36 36/36 - - 42/42 42/42 42/42 - - 50/50 50/50 50/50
GPS1BH ≤10 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
GPS1MH 12.5 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
GPS2BH 16/20 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
GPS2MH 25/32 50/50 50/50 50/50 50/50 50/50 80/80 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 150/150
F 50/63 - - 50/50 50/50 50/50 - - 80/80 80/80 80/80 - - 150/150 150/150 150/150
X Downstream
In (A) 63 80 100 125 160 63 80 100 125 160 63 80 100 125 160
≤20A 8/8 8/8 8/8 8/8 8/8 10/10 10/10 10/10 10/10 10/10 12/12 12/12 12/12 12/12 12/12
C30 B/C curve 25A 8/8 8/8 8/8 8/8 8/8 10/10 10/10 10/10 10/10 10/10 12/12 12/12 12/12 12/12 12/12
32A 6/6 8/8 8/8 8/8 8/8 8/8 10/10 10/10 10/10 10/10 10/10 12/12 12/12 12/12 12/12
40A - 8/8 8/8 8/8 8/8 - 10/10 10/10 10/10 10/10 - 12/12 12/12 12/12 12/12
≤20A 12/12 12/12 12/12 12/12 12/12 15/15 15/15 15/15 15/15 15/15 18/18 18/18 18/18 18/18 18/18
C60 B/C curve & DME60 25A 12/12 12/12 12/12 12/12 12/12 15/15 15/15 15/15 15/15 15/15 18/18 18/18 18/18 18/18 18/18
32A 10/10 12/12 12/12 12/12 12/12 12/12 15/15 15/15 15/15 15/15 15/15 18/18 18/18 18/18 18/18
40A - 12/12 12/12 12/12 12/12 - 15/15 15/15 15/15 15/15 - 15/18 18/18 18/18 18/18
E.22
Record Plus
Table DB2 - Selectivity Plus
Record PlusTM type
Upstream FE160N-LTMD/SMR1 FE160H-LTMD/SMR1 FE160L-LTMD/SMR1 FE250N-LTMD/SMR1 FE250H-LTMD/SMR1 FE250L-LTMD/SMR1
In (A) 100 125 160 100 125 160 100 125 160 125 160/200 250 125 160/200 250 125 160/200 250
Downstream Selectivity limit in kA / Maximum Icu of combination at 400/415V ac
Redline ≤20 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
G30 B/C curve 25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
32 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
40 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
50 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
63 - 16/16 16/16 - 22/22 22/22 - 25/25 25/25 16/16 16/16 16/16 22/22 22/22 22/22 25/25 25/25 25/25
G60 B/C curve ≤20 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
25 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
32 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
40 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
Selectivity Plus
50 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
63 - 30/30 30/30 - 36/36 36/36 - 40/40 40/40 22/22 22/22 22/22 30/30 30/30 30/30 36/36 36/36 36/36
G100 B/C curve ≤20 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
25 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
32 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
40 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
50 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
63 - 36/36 36/36 - 40/40 40/40 - 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
GT25 B/C curve ≤20 40/40 40/40 40/40 50/50 50/50 50/50 65/65 65/65 65/65 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 40/40
25 40/40 40/40 40/40 50/50 50/50 50/50 65/65 65/65 65/65 30/30 30/30 30/30 40/40 40/40 40/40 40/40 40/40 40/40
32 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40
40 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 30/30 30/30 30/30 36/36 36/36 36/36 40/40 40/40 40/40
50 36/36 36/36 36/36 40/40 40/40 40/40 50/50 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
63 - 36/36 36/36 - 40/40 40/40 - 50/50 50/50 25/25 25/25 25/25 36/36 36/36 36/36 40/40 40/40 40/40
Surion ≤10 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
GPS1BA 12.5 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
GPS1MA 16/20 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
GPS2BA 25/32 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
GPS2MA 40 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50 36/36 36/36 36/36 42/42 42/42 42/42 50/50 50/50 50/50
50/63 - 36/36 36/36 - 42/42 42/42 - 50/50 50/50 - 36/36 36/36 - 42/42 42/42 - 50/50 50/50
GPS1BH
GPS1MH
≤10
12.5
50/50
50/50
50/50
50/50
50/50
50/50
80/80
80/80
80/80
80/80
80/80
80/80
150/150150/150150/150
150/150150/150150/150
50/50
50/50
50/50
50/50
50/50
50/50
80/80
80/80
80/80
80/80
80/80
80/80
150/150150/150150/150
150/150150/150150/150
A
GPS2BH 16/20 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
GPS2MH 25/32 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
40 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150 50/50 50/50 50/50 80/80 80/80 80/80 150/150150/150150/150
50/63 - 50/50 50/50 - 80/80 80/80 - 150/150150/150 - 50/50 50/50 - 80/80 80/80 - 150/150150/150 B
Table DB2a - Selectivity Plus
Record PlusTM type
C
Upstream
FE160N - LMLD/SMR1 FE160H - LTMD/SMR1 FE160L - LTMD/SMR1 FE250N - LTMD/SMR1 FE250H - LTMD/SMR1 FE250L - LTMD/SMR1
In (A) 100 125 160 100 125 160 100 125 160 125 160/200 250 125 160/200 250
Downstream D
Selectivity limit in kA / Maximum Icu of combination at 230/240V AC
≤20A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12
C30 B/C curve 25A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12
32A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 E
40A 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12 8/8 8/8 8/8 10/10 10/10 10/10 12/12 12/12 12/12
≤20A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15
C60 B/C curve & DME60 25A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15
32A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15
40A 15/15 15/15 15/15 18/18 18/18 18/18 22/22 22/22 22/22 10/10 10/10 10/10 12/12 12/12 12/12 15/15 15/15 15/15 F
E.23
Record Plus
Table DB3 - Selectivity Plus
Record PlusTM type
Upstream
FE160H-LTMD FE160L-LTMD FE160H-SMR1 FE160L-SMR1 FE250H-LTMD FE250L-LTMD FE250H-SMR1 FE250L-SMR1
In (A) 125 160 125 160 125 160 125 160 160/200 250 160/200 250 160 250 160 250
Downstream Selectivity limit in kA / Maximum Icu of combination
Record PlusTM
FD 63S LTMD 30/42 30/42 30/50 30/50 36/42 36/42 36/50 36/50 42/42 42/42 42/50 42/50 42/42 42/42 50/50 50/50
FD 63N LTMD 30/80 30/80 30/150 30/150 36/80 36/80 36/150 36/150 42/80 42/80 42/150 42/150 50/80 50/80 50/150 50/150
FD 63H LTMD - - 30/150 30/150 - - 36/150 36/150 - - 42/150 42/150 - - 50/150 50/150
FD160S LTMD ≤80A 30/42 30/42 30/50 30/50 36/42 36/42 36/50 36/50 42/42 42/42 42/50 42/50 42/42 42/42 50/50 50/50
FD160N LTMD ≤80A 30/80 30/80 30/150 30/150 36/80 36/80 36/150 36/150 42/80 42/80 42/150 42/150 50/80 50/80 50/150 50/150
FD160H LTMD ≤80A - - 30/150 30/150 - - 36/150 36/150 - - 42/150 42/150 - - 50/150 50/150
FE 160N LTM ≤80A 30/80 30/80 30/150 30/150 36/80 36/80 36/150 36/150 42/80 42/80 42/150 42/150 50/80 50/80 50/150 50/150
FE 160H LTM ≤80A - - 30/150 30/150 - - 36/150 36/150 - - 42/150 42/150 - - 50/150 50/150
Application guide
In (A) 250 350 400 250 350 400 250 350 400 250 350 400
Downstream Selectivity limit in kA / Maximum Icu of combination
Record PlusTM
FD 63S LTMD 50/50 50/50 50/50 65/65 65/65 65/65 50/50 50/50 50/50 65/65 65/65 65/65
FD 63N LTMD 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FD 63H LTMD 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150 150/150
FD160S LTMD 50/50 50/50 50/50 65/65 65/65 65/65 50/50 50/50 50/50 65/65 65/65 65/65
FD160N LTMD 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FD160H LTMD - 150/150 150/150 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150
FE 160N LTM <MD 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FE 160H LTM & LTMD - 150/150 150/150 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150
FE 160N SMR1 80/80 80/80 80/80 150/150 150/150 150/150 80/80 80/80 80/80 150/150 150/150 150/150
FE 160H SMR1 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150 - 150/150 150/150
A
Table DB5 - Selectivity Plus
B Upstream
Record PlusTM type
FK800H-SMR FK800L-SMR FK1250H-SMR FK1250L-SMR FK1600H-SMR
E.24
Record Plus
Coordination with loadbreak
disconnect switches
Protection of Switch Disconnectors (Dilos or Record Plus) with Record Plus circuit breakers - Valid for 400/415V AC A
Upstream Record PlusTM Breaking capacity, Downstream Dilos Maximum allowable Downstream Record Maximum allowable
circuit breaker Icu=Ics (kA eff.) switch short-circuit (kA eff.) PlusTM switch short-circuit (kA eff.)
of combination of combination
FD63/160S 36 Dilos 1 & 1H
Dilos 2
18
18
FD63Y
FD160Y
36
36
B
FD63/160N 50 Dilos 1 & 1H 25 FD63Y 50
Dilos 2 25 FD160Y 50
FD63/160H 80 Dilos 1 & 1H 30 FD63Y 80
FD63/160L 150
Dilos 2
Dilos 1 & 1H
30
36
FD160Y
FD63Y
80
150
C
Dilos 2 36 FD160Y 150
FE160N 50 Dilos 1 & 1H 25 FD63Y 50
Dilos 2 25 FD160Y 50
FE160H 80 Dilos 1 & 1H
Dilos 2
30
30
FD63Y
FD160Y
80
80
D
FE160L 150 Dilos 1 & 1H 36 FD63Y 150
Dilos 2 36 FD160Y 150
FE250N 50 Dilos 3 50 FE250Y 50
FE250H 80 Dilos 3 80 FE250Y 80 E
FE250L 150 Dilos 3 150 FE250Y 150
FG400N 50 Dilos 4 50 FG400Y 50
FG400H 80 Dilos 4 80 FG400Y 80
FG400L 150 Dilos 4 150 FG400Y 150
FG630N 50 Dilos 4 50 FG630Y 50 F
FG630H 80 Dilos 4 80 FG630Y 80
FG630L 150 Dilos 4 150 FG630Y 150
FK800N 50 Dilos 6 50 FK800Y 50
FK800H 80 Dilos 6 80 FK800Y 80
FK1250N 50 Dilos 6 50 FK1250Y 50 G
FK1250H 80 Dilos 6 80 FK1250Y 80
FK1600N 50 Dilos 7 50 FK1600Y 50
FK1600H 80 Dilos 7 80 FK1600Y 80
E.25
Record Plus
Protection of motor circuits
General
In a circuit that provides power to a motor a
number of protective and control devices are
normally present . The combination of these
devices must be coordinated to ensure the
efficiency and an optimal protection of the motor.
Here, the protection of such circuits strongly
depends on the operational requirements, as
the application for which the motor is used, the
Application guide
E.26
Record Plus
Coordination type 2 test sequence
Coordination
The standards require tests to define the
Motor current Ie (AC3) Test with current " r "
coordination between the devices within the motor
starter. Depending on the state of the components
Ie ≤ 16A 1 kA
after the test two coordination classes 1 and 2 16 < Ie ≤ 63A 3 kA
have been defined. 63 < Ie ≤ 125A 5 kA
following standards
• No or minor weldings of the contactors after testing; This value which is generally ≤ 50kA is used to check the coordination
of the devices used in the motor starter circuit. For each combination
contact separation is simple and easy with Record PlusTM breakers this value is mentioned in the tables on
• The switchgear and controlgear are fully operational pages E.28, 29, 30, 31, 32 and 33.
After a test with this current the following conditions must be met:
after the tests indicated here. • No or minor weldings of the contactors after testing; contact
separation is simple and easy
• The switchgear and controlgear are fully operational after the test.
Option 1 Option 2
A
Electronic circuit
Magnetic only breaker as the short-
circuit breaker as the circuit and
Overload protection
B
short-circuit
protection device. device.
C
Contactor for control Contactor for control
purposes. purposes.
D
Separate thermal relay
for class 10 or
class 30 as overload E
protection.
E.27
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L
Icc values in kA Ue=230V AC Icc values in kA Ue=400/415V AC
FD63/160 85 100 130 FD63/160 50 80 130
FE160/250 85 100 130 FE160/250 50 80 130
FG 400/630 85 100 130 FG 400/630 50 80 130
FK 800/1250 85 100 130 FK 800/1250 50 80 100
E.28
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L Type N H L
Icc values in kA Ue=440V AC Icc values in kA Ue=500/525V AC Icc values in kA Ue=690V AC
FD63/160 30 50 80 FD63/160 - 36 50 FD63/160 - 6
FE160/250 42 65 130 FE160/250 - 50 80 FE160/250 - 22 Tests
0.8 1.9 FD63/FE160 3(2) 30 CL25+RT1J 0.8 1.5 FD63/FE160 3(2) 30 CL25+RT1H
1.1 2.5 FD63/FE160 3(2) 30 CL25+RT1K 1.1 2.0 FD63/FE160 3(2) 30 CL25+RT1J 1.5 2.0 FD63/FE160 3(2) 30 CL25+RT1J
1.5 3.4 FD63/FE160 3(2) 70 CL25+RT1K 1.5 2.6 FD63/FE160 3(2) 40 CL25+RT1K 2.2 2.9 FD63/FE160 3(2) 38 CL25+RT1K
2.2 4.6 FD63/FE160 7 70 CL03+RT12L 2.2 3.8 FD63/FE160 7 70 CL03+RT12L 3 3.5 FD63/FE160 3(2) 70 CL25+RT1K
3 6.0 FD63/FE160 7 78 CL03+RT1M 3 5.0 FD63/FE160 7 70 CL03+RT1M 3.7 4.6 FD63/FE160 7 70 CL03+RT12L
4 7.6 FD63/FE160 12.5(3) 100 CL06+RT2AN 4 6.5 FD63/FE160 7 85 CL03+RT1M 4 5.0 FD63/FE160 7 70 CL03+RT12L
5.5 10.5 FD63/FE160 12.5(3) 136 CL03+RT2AN 5.5 9.0 FD63/FE160 12.5(3) 125 CL06+RT2AN 5.5 7.0 FD63/FE160 7 91 CL03+RT12M
7.5 14.6 FD63/FE160 20(3) 200 CL06+RT2B 7.5 12.0 FD63/FE160 12.5(3) 156 CL06+RT2BP 7.5 9.0 FD63/FE160 12.5(3) 125 CL07+RT2AN
10 18.8 FD63/FE160 20(3) 245 CL06+RT2B 10 15.0 FD63/FE160 20(3) 200 CL06+RT2B 11 12.5 FD63/FE160 12.5(3) 163 CL07+RT2BP
11 20 FD63/FE160 30(4) 300 CL06-RT2C 11 18.4 FD63/FE160 20(3) 300 CL06-RT2B 13 16.0 FD63/FE160 20(3) 208 CL07+RT2B
15 27 FD63/FE160 30(4) 355 CL06-RT2D 15 23 FD63/FE160 30(4) 300 CL06-RT2C 15 18.0 FD63/FE160 20(3) 234 CL07+RT2B
18.5 33 FD63/FE160 50 500 CL06+RT2E 18.5 29 FD63/FE160 30(4) 371 CL06-RT2D 18.5 23 FD63/FE160 30(4) 300 CL09+RT2C
22 39 FD63/FE160 50 510 CL06+RT2E 22 33 FD63/FE160 50 500 CL06+RT2E 22 25 FD63/FE160 30(4) 325 CL09+RT2D
25 44 FD63/FE160 50 578 CL06+RT2G - - - - - - - - - - - -
30 52 FD/FE160 80 680 CL09+RT2H 30 45 FD63/FE160 50 585 CL06+RT2G 30 35 FD63/FE160 50 500 CL09+RT2E
37 65 FD/FE160 80 849 CL09+RT2J 37 55 FD/FE160 80(5) 800 CL09+RT2J 37 42 FD63/FE160 50 546 CL09+RT2E
45 78 FD/FE160 80 1019 CL09+RT2J 45 65 FD/FE160 100 1000 CL09+RT2J 45 49 FD63/FE160 50 637 CL09+RT2G
55 86 FD160 100 1223 CL09+RT2L 55 80 FD160 100 1100 CL09+RT2S 55 60 FD/FE160 80(5) 800 CL09+RT2J
55 94 FE160 100 1223 CK75C+RT2L 55 80 FE160 100 1100 CK75C+RT2J 75 80 FD/FE160 80(5) 1040 CL09+R2TL
75 131 FE160 160 1699 CK85B+RT3E 75 110 FE160 125 1430 CK85B+RT3D 90 100 FD160 100 1300 CL09+R2TL
90
110
163
188
FE250
FE250
250
250
2500
2500
CK95B+RT3F
CK95B+RT4P
90
110
130
156
FE160
FE160
160
160
1690
2028
CK95B+RT3E
CK95B+RT3F
90
110
100
120
FE160
FE160
100
125
1300
1560
CK85B+RT2M
CK85B+RT3E
A
132 225 FE250 250 2922 CK95B+RT4R 132 190 FE250 250 2500 CK95B+RT4P 132 140 FE160 160 1820 CK95B+RT3F
160 300 FG400 400 3900 CK10B+RT5C 160 228 FE250 250 2964 CK95B+RT4R 160 175 FE250 250 2100 CK95B+RT4N
200 360 FG400 400 4680 CK12B+RT5C 200 281 FG400 400 3653 CK10B+RT5C 200 220 FE250 250 2860 CK10B+RT4R
220
250
400
462
FG630
FG630
500
500
5200
6004
CK12B+RT5D
CK12B+RT5D
220
-
310
-
FG400
-
400
-
4030
-
CK10B+RT5C
-
220
250
240
270
FG400
FG400
250
400
3120
3510
CK10B+RT4R
CK10B+RT5C
B
300 509 FK800 800 6619 CK13B+RT5E - - - - - - - - - - - -
315 529 FK800 800 6880 CK13B+RT5E 315 445 FG630 500 5785 CK12B+RT5D - - - - - -
335 563 FK800 800 6754 CK13B+RT5E 335 460 FG630 500 5980 CK12B+RT5D 335 335 FG400 400 4355 CK10B+RT5C
355
375
596
630
FK800
FK800
800
800
6560
6930
CK13B+RT5E
CK13B+RT6A
355
375
500
530
FK800
FK800
800
800
6500
6890
CK13B+RT5E
CK13B+RT5E 375
-
400
- -
FG630
-
500
-
5200
-
CK12B+RT5D
C
- - - - - - 400 570 FK800 800 6840 CK13B+RT5E - - - - - -
- - - - - - 450 630 FK800 800 7560 CK13B+RT6A 450 480 FG630 500 6240 CK12B+RT5D
- - - - - - - - - - - - 500 530 FK800 800 6360 CK13B+RT5E
- - - - - - - - - - - - 560 580 FK800 800 6380 CK13B+RT5E D
E.29
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection (with SMR2 other classes possible)
Upstream Record PlusTM Breaker selection
Type N H L Type N H L
Icc values in kA Ue=230V AC Icc values in kA Ue=400/415V AC
FE160/250 85 100 130 FE160/250 50 80 130
FG 400/630 85 100 130 FG 400/630 50 80 130
E.30
Record Plus
Coordination type II - EN 60947-4 - Class 10 protection (with SMR2 other classes possible)
Upstream Record PlusTM Breaker selection
Type N H L Type N H L Type N H L
Icc values in kA Ue=440V AC Icc values in kA Ue=690V AC
FE160/250 42 65 130 FE160/250 - 50 80 FE160/250 - 22 50
FG 400/630 50 65 130 FG 400/630 - 50 80 FG 400/630 - 22 50
- - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - -
5.5 10.5 FE160 25 136 CL08 - - - - - - - - - - - -
7.5 14.6 FE160 25 200 CL08 7.5 12.0 FE160 25 156 CL09 - - - - - -
10 18.8 FE160 25 245 CL08 10 15.0 FE160 25 200 CL09 10 11.5 FE160 25 150 CK85B
11 20 FE160 25 265 CL08 11 18.4 FE160 25 300 CL09 - - - - - -
15 27 FE160 63 355 CL09 15 23 FE160 25 300 CL09 15 17.1 FE160 25 223 CK85B
18.5 33 FE160 63 500 CL09 18.5 29 FE160 63 371 CL10 18.5 20 FE160 25 260 CK85B
22 39 FE160 63 510 CL09 22 33 FE160 63 423 CL10 - - - - - -
25 44 FE160 63 578 CL09 - - - - - - - - - - -
30 52 FE160 63 680 CL09 30 45 FE160 63 585 CL10 30 35 FE160 63 500 CK85B
37 65 FE160 125 849 CK85B 37 55 FE160 63 800 CL10 37 42 FE160 63 546 CK85B
45 78 FE160 125 1019 CK85B - - - - - - 45 49 FE160 63 637 CK85B
55 94 FE160 125 1223 CK85B 55 80 FE160 125 1040 55 60 FE160 63 800 CK85B
75 131 FE160 160 1699 CK85B 75 110 FE160 125 1430 CK85B 75 80 FE160 125 1040 CK85B
90 163 FE250 250 2500 CK95B 90 130 FE160 160 1690 CK85B 90 100 FE160 125 1300 CK85B
110 188 FE250 250 2500 CK95B 110 156 FE160 160 2028 CK85B 110 120 FE160 125 1560 CK85B
132 225 FE250 250 2922 CK95B 132 190 FE250 250 2500 CK95B 132 140 FE160 160 1820 CK85B
160 300 FG400 400 3900 CK10C 160 228 FE250 250 2964 CK95B 160 175 FE250 250 2275 CK10C
200 360 FG400 400 4680 CK12B 200 281 FG400 400 3653 CK10C 200 220 FE250 250 2860 CK10C
220 400 FG630 500 5200 CK12B 220 310 FG400 400 4030 CK10C 220 240 FG400 250 3120 CK10C
250 462 FG630 500 6004 CK12B - - - - - - 250 270 FG400 400 3510 CK10C
-
-
-
-
-
-
-
-
-
-
-
-
-
315
-
445
-
FG630
-
500
-
5785
-
CK12B
-
-
-
-
-
-
-
-
-
-
-
-
A
- - - - - - 335 460 FG630 500 5980 CK12B 335 335 FG400 400 4355 CK10C
- - - - - - 355 500 FG630 500 6500 CK12B - - - - - -
- - - - - - - - - - - - 375 400 FG630 500 5200 CK12B
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
450
-
480
-
FG630
-
500
-
6240
-
CK12B
B
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker
C
E.31
Record Plus
Coordination type II - EN 60947-4 - Class 20(3) protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L
Icc values in kA Ue=230V AC Icc values in kA Ue=400/415V AC
FD63/160 85 100 130 FD63/160 50 80 130
FE160/250 85 100 130 FE160/250 50 80 130
FG 400/630 85 100 130 FG 400/630 50 80 130
FK 800/1250 85 100 130 FK 800/1250 50 80 100
E.32
Record Plus
Coordination type II - EN 60947-4 - Class 20(3) protection
Upstream Record PlusTM Breaker selection
Type N H L Type N H L Type N H L
Icc values in kA Ue=440V AC Icc values in kA Ue=500/525V AC Icc values in kA Ue=690V AC
FD63/160 30 50 80 FD63/160 - 36 50 FD63/160 - 6 10
FE160/250 42 65 130 FE160/250 - 50 80 FE160/250 - 22 50
0.75 1.9 FD63/FE160 3(2) 30 CL25+RT12J 0.75 1.5 FD63/FE160 3(2) 30 CL25+RT12H
1.1 2.5 FD63/FE160 3(2) 30 CL25+RT12K 1.1 2.0 FD63/FE160 3(2) 30 CL25+RT12J
1.5 3.4 FD63/FE160 3(2) 70 CL25+RT12K 1.5 2.6 FD63/FE160 3(2) 40 CL25+RT12K 1.5 2.0 FD63/FE160 3(2) 30 CL25+RT12J
2.2 4.6 FD63/FE160 7 70 CL03+RT12L 2.2 3.8 FD63/FE160 7 70 CL03+RT12L 2.2 2.9 FD63/FE160 3(2) 38 CL25+RT12K
3 6.0 FD63/FE160 7 78 CL03+RT12M 3 5.0 FD63/FE160 7 70 CL03+RT12M 3 3.5 FD63/FE160 3(2) 46 CL25+RT12K
4 7.6 FD63/FE160 12.5(4) 100 CL06+RT2AN 4 6.5 FD63/FE160 7 85 CL03+RT12M 3.7 4.6 FD63/FE160 7 70 CL03+RT12L
5.5 10.5 FD63/FE160 12.5(4) 136 CL06+RT2AN 5.5 9.0 FD63/FE160 12.5(4) 125 CL06+RT2AN 4 5.0 FD63/FE160 7 70 CL03+RT12L
7.5 14.6 FD63/FE160 20(4) 200 CL06+RT2B 7.5 12.0 FD63/FE160 12.5(4) 156 CL06+RT2BP 5.5 7.0 FD63/FE160 7 91 CL03+RT12M
10 18.8 FD63/FE160 20(4) 245 CL06+RT2B 10 15.0 FD63/FE160 20(4) 200 CL06+RT2B 7.5 9.0 FD63/FE160 12.5(4) 125 CL07+RT2AN
11 20 FD63/FE160 30(5) 300 CL06-RT2C 11 18.4 FD63/FE160 20(4) 300 CL06-RT2B 11 12.5 FD63/FE160 12.5(4) 163 CL07+RT2BP
15 27 FD63/FE160 30(5) 355 CL06-RT22D 15 23 FD63/FE160 30(5) 300 CL06-RT2C 13 16.0 FD63/FE160 20(4) 208 CL07+RT2B
18.5 33 FD63/FE160 50 500 CL06+RT22E 18.5 29 FD63/FE160 30(5) 371 CL06-RT22D 15 18.0 FD63/FE160 20(4) 234 CL07+RT2B
22 39 FD63/FE160 50 510 CL06+RT22E 22 33 FD63/FE160 50 500 CL06+RT22E 18.5 23 FD63/FE160 30(5) 300 CL09+RT2C
25 44 FD63/FE160 50 578 CL06+RT22G - - - - - - 22 25 FD63/FE160 30(5) 325 CL09+RT22D
30 52 FD/FE160 80(6) 680 CL09+RT22H 30 45 FD63/FE160 50 585 CL06+RT22G - - - - - -
37 65 FD/FE160 80(6) 849 CL09+RT22J 37 55 FD/FE160 80(6) 800 CL09+RT22J 30 35 FD63/FE160 50 500 CL09+RT22E
45 78 FD/FE160 80 1019 CL09+RT22J 45 65 FD/FE160 100 1000 CL09+RT22J 37 42 FD63/FE160 50 546 CL09+RT22F
55 94 FD160 100 1223 CL09+RT22L 55 80 FD160 100 1000 CL09+RT22J 45 49 FD63/FE160 50 637 CL09+RT22G
55 94 FE160 100 1223 CK75C+RT22L 55 80 FE160 100 1100 CK75C+RT22J 55 60 FD/FE160 80(6) 800 CL09+RT22J
75 131 FE160 160 1699 CK85B+RT32E 75 110 FE160 125 1430 CK85B+RT32D 75 80 FD/FE160 80(6) 1040 CL09+R2T2L
90
110
163
188
FE250
FE250
250
250
2500 CK95B+RT32F
2500 CK95B+RT5LB
90
110
130
156
FE160
FE160
160
160
1690 CK95B+RT32E
2028 CK95B+RT32F
90
110
100
120
FD/FE160 100
FE160 125
1300 CK85B+RT22M
1560 CK85B+RT32E
A
132 225 FE250 250 2922 CK95B+RT5LB 132 190 FE250 250 2500 CK95B+RT5LB 132 140 FE160 160 1820 CK95B+RT32F
160 300 FG400 400 3900 CK10B+RT5LC 160 228 FE250 250 2964 CK95B+RT5LB 160 175 FE250 250 2100 CK95B+RT32F
200 360 FG400 400 4680 CK12B+RT5LD 200 281 FG400 400 3653 CK10B+RT5LC 200 220 FE250 250 2860 CK10B+RT5LB
220
250
400
462
FG630
FG630
500
500
5200 CK12B+RT5LD
6004 CK12B+RT5LD
220
-
310
-
FG400
-
400
-
4030 CK10B+RT5LC
- -
220
250
240
270
FG400
FG400
250
400
3120 CK10B+RT5LB
3510 CK10B+RT5LC
B
300 509 FK800 800 6619 CK13B+RT5LE - - - - - - - - - - - -
315 529 FK800 800 6880 CK13B+RT5LE 315 445 FG630 500 5785 CK12B+RT5LD - - - - - -
335 563 FK800 800 6754 CK13B+RT5LE 335 460 FG630 500 5980 CK12B+RT5LD 335 335 FG400 400 4355 CK10B+RT5LC
355
375
596
630
FK800
FK800
800
800
6560 CK13B+RT5LE
6930 CK13B+RT5LE
355
375
500
530
FK800
FK800
800
800
6500 CK13B+RT5LE
6890 CK13B+RT5LE
-
375
-
400
-
FG630
-
500
- -
5200 CK12B+RT5LD
C
- - - - - - 400 570 FK800 800 6840 CK13B+RT5LE - - - - - -
- - - - - - 450 630 FK800 800 7560 CK13B+RT5LE 450 480 FG630 500 6240 CK12B+RT5LD
- - - - - - - - - - - - 500 530 FK800 800 6360 CK13B+RT5LE
- - - - - - - - - - - - 560 580 FK800 800 6380 CK13B+RT5LE D
E.33
Record Plus
Protection of LV/LV transformers
Transformers generally produce a very high inrush
current . The crest value of the first half cycle may
reach values of 15 to 25 times the effective rated
current .
For a protective device capable of protecting these FD160 LTMD type
units this must be taken into account . Manufacturers
data and tests have indicated that a protective device
FD160 SMR1 type
feeding a transformer must be capable of carrying the
following current values without tripping (see graph
insert).
Application guide
E.34
Record Plus
Protection of capacitor banks
(power factor improvement units)
For circuit breakers and particularly for the
Record PlusTM device, designed to offer high making Un = 230V (phase to phase voltage)
E.35
Just rel
Record Plus
The breaker
Order codes A
F.2 FD frame, plug in device (8 & 10 pole connectors)
Dimensions G
y on us
Numerical Index X
F.1
Record Plus
Recommended wiring diagrams
X... ER
Wiring diagrams
7-
gy bk
bI ye
gy - grey
bl - blue
bk - black
ye - yellow
B 41
4-
42
C
43 gy bk
4-
D 44 bI ye
gy - grey
bl - blue
E bk - black
ye - yellow
G
EL ER
85 41 75
X 8- 4- 7-
86 42 86
87 43 gy bk 77
8- 4- 7-
88 44 bI ye 78
RCD
gy - grey
bl - blue
bk - black
ye - yellow
F.2
Record Plus
EL 9 10 ER 9 10
T1 P1
Wiring diagrams
T- P-
T2 P2
T3 gy bk P3
T- P-
T4 bI ye P4
gy - grey
bl - blue
bk - black D
ye - yellow
E
FG frame, plug in device (10 pole connectors)
F
EL ER G
gy - grey
bl - blue
bk - black
ye - yellow
F.3
Record Plus
Recommended Wiring diagrams
EL ER
Wiring diagrams
T-
T-
A
FK frame 3 pole, draw out device (6 pole connectors)
B
F.4
Record Plus
Wiring diagrams
A
D
11
12
10
9
8
7
6
5
4
3
2
1
E
External CT-
External CT+
GFA - F
GFA +
ZSI_OUT -
ZSI_OUT +
ZSI_IN -
ZSI_IN +
G
Aux_GND
12 AUX GND
Target Output and Comm Adaptor
Aux_DC
11 AUX DC
Tx
Rx
10 TX
9 RX
RLY 1A
RLY 1B
X
FAMECM 434013
8 EXT_GND RLY 2A
7 +24 VDC RLY 2B
6 EXT_GND RLY 3A
5 COM + RLY 3B
4 COM + RLY 4A
3 COM_GND RLY 4B
2 COM -
- +
19 to 29 VDC
-
+ G - 1 COM -
Modbus/RS485
POWER Connect LEGEND :
SUPPLY 1.RLY - Relays are 3A/250 VAC
2
2. - Standard 3 m (0.75mm -600VAC)Cable
F.5
Just rel
Record Plus
FD & FE frame
G.2 Breakers
G.3 Phase separators
G.3 Residual current devices RCD’s
G.5 Electrical operators
G.6 Rotary handles
G.8 Plug-in version
G.9 Drawout version
G.10 Door flanges
G.11 Padlock fixed
G.12 Backplate
G.13 Terminal shields
FG frame
G.14 Breakers
G.15 Residual current devices RCD’s
G.16 Electrical operators
G.17 Rotary handles
G.18 Plug-in version The breaker
G.18 Drawout version
G.19 Mechanical interlock Order codes A
G.20 Door flanges
G.21 Padlocking fixed
Trip units B
G.21 Backplate
G.22 Terminal shields
Components & Accessories C
FK frame
G.24 Breakers
G.24 Electrical operators
Technical data D
G.25 Rotary handles
G.26 Drawout version Application guide E
G.26 Phase separators
G.27 Door flanges
Wiring diagrams F
G.28 Mechanical interlock
G.29 Terminal shields
Dimensions G
y on us
Connectivity
Numerical Index X
G.30 Connectivity-60 mm system FD and FE frames
G.1
Record Plus
Dimensional Drawings
.
. .
Dimensions
.
.
.
E
. .
F .
X
. .
. .
G.2
Record Plus
Dimensional Drawings
.
. .
. . .
FD & FE frame
. .
.
. . .
. .
.
Y2 E
Dimensions F
FD63 FE160
FD160 FE250
X2 X1
X3
X1 330 410
G
X2 245 304
X3 287,5 357
Y1 63 72,5
Y2 105,5 126
X
Y1
G.3
Record Plus
Dimensional Drawings
.
.
.
Dimensions
.
. .
.
A .
E
.
.
F
.
X
.
.
.
.
. .
G.4
Record Plus
Dimensional Drawings
185
145
FD & FE frame
49.3
50.9
79.8
83
40.5 40.5
81 108
43.5
83
33.6 A
147 87
194
155 D
E
61.9
56.9
79.8
96.4
F
52.25 52.25
104.5 139.5
G
55.25
X
83
33.6
110.5
157
G.5
Record Plus
Dimensional Drawings
52.2
1.8 25.2
214.5
27 27 7 174.5
33.8
55
28.3
Dimensions
2.5
81.5
1.5
11.7 10 70
27 76
81 121 4
C Rotary handle - Breaker and through panel mounted - FE160 and FE250
D 95
52.5 81 30
5.8 29.2
33.8
28.3
22.3
E
12.45
62.5
81.5
F
28.7
G
1.5
X 11.7
73.50
49.5
86
81
121
94.6 125
105 174.5
214.5
G.6
Record Plus
Dimensional Drawings
30.25
33.8
55
72
FD & FE frame
1.5 Min 5 Max.
67 40
64
76
145 ) H ) 250
11.7
72
A
L
=
H
-7
33
5
250 ) H ) 350
H= ) 600 (FDNRE) long Shaft
B
E
33.8
72
F
1.5 Min 5 Max.
73.5 G
86 67 40
145 ) H ) 250
72 X
L
=
H
-7
5
33
250 ) H ) 350
H= ) 600 (FDNRE) long Shaft
G.7
Record Plus
Dimensional Drawings
.
. . .
Dimensions
. .
E . .
. . . .
G.8
Record Plus
Dimensional Drawings
FD & FE frame
1) Mounting on panel/backplate or on profiles
2) Mounting through a front panel
(all electrical connection behind panel)
3) Mounting of device through door or panel
(parts for operating the drawout mechanism/breaker pass
through the door or panel*) A
*Here a door flange (model for rotary handle) can be used
4) Mounting of device behind door or panel
(all parts for operating the drawout mechanism/breaker behind
the door or panel) B
460,3
E
166,3
420
134
240,2
128,9
25,3 92,7 48
F
9,1
G
108
G.9
Record Plus
Dimensional Drawings
X W3
A W2 W1
W1
B
Dimensions
Y
R2 max. C Z
3p Breaker hole
4p Breaker hole
Dimensions
A B C Rmin W1(max) W2(max) W3(max) X Y Z
FDFF3 FD 63/160 3p 13,5 55 55 80 83,2 85,8 93,2 114 78 1...4
FDFF4 FD 63/160 4p 13,5 55 55 93,5 83,2 85,8 93,2 146 78 1...4
FEFF3 FE160/250 3p 17,5 55,5 70,5 91,75 89,2 - - 138 97 1...4
FEFF4 FE160/250 4p 17,5 55,5 70,5 102,5 89,2 - - 173 97 1...4
FEFT FE 160/250 3p/4p 17,5 55,5 70,5 93,5 93,2 - - 60 97 1...4
A
FDFF3 (RCD*) FD 63/160 3p 13,5 155 42 80 83,2 85,8 93,2 114 78 1...4
FDFF4 (RCD*) FD 63/160 4p 13,5 155 42 93,5 83,2 85,8 93,2 146 78 1...4
D
Electrical Operator X Rotary Handle
A
W1 W1
E B
Y
R2 max. C
F
3p Breaker hole
4p Breaker hole
G
Z
Z
X
Dimensions
3+4 pole versions A B C Rmin W1(max) X Y Z
FDFE FD 63/160 Electr. Operator 13.5 49.5 64.5 80 141 148.5 124.5 1...4
FEFE FE 160/250 Electr. Operator 17.5 46 80 100 170 172 124.5 1...4
FDFH FD63/160 Rotary Handle 13.5 46,25 63.75 100 125 120 120 1...4
FEFH FE 160/250 Rotary Handle 17.5 46.25 81.75 100 125 120 120 1...4
G.10
Record Plus
Dimensional Drawings
FD & FE frame
129.7
112.7
88.7
82.6
E
42.5 67 60.5
G
137
121
88.5
97
G.11
Record Plus
Dimensional Drawings
Backplate - FD63/160
Y4
Y3 Z
Dimensions
Dimensions
FD 63
FD 160
X1 230
X2 330
X1 X2 Y1 108
Y2 81
Y3 108
Y4 135
Z 1
Y2
Y1
E
Y4
Y3 Z Dimensions
FE160
F FE250
X1 310
X2 410
G X1 X2 Y1 139.5
Y2 104.5
Y3 139.5
X Y4 175
Z 1
Y2
Y1
G.12
Record Plus
Dimensional Drawings
.
.
FD & FE frame
.
. D
.
E
.
G.13
Record Plus
Dimensional Drawings
E
.
G
.
G.14
Record Plus
Dimensional Drawings
FG frame
A
F
.
. .
. . .
. .
G.15
Record Plus
Dimensional Drawings
39.7
122
143.6
30.7
Dimensions
278 69.5
69.5
174
139
71.5
124
31.7
A 238.5
141
G.16
Record Plus
Dimensional Drawings
211.25
138.7 106 55
90
16.75 45
37.75
30
FG frame
101
63.25
129
39.25 111
93 161
108.6
G.17
Record Plus
Dimensional Drawings
185.7 230.7
D 45 45
92.85
45
115.35
45 45 21.5
90
E
148.5
180.5
100
200
361
297
F
328
22.5 235 6
6 118
59 6
98.5
45
150
22.5
60
197
120
300
332
300
150
166
104.35
45 96
Backplate mounting Rear mounting Rail mounting Panel door cutout
G.18
Record Plus
Dimensional Drawings
208
460
159
420 154
302,1 138
25,3 101,6 48
10,5
FG frame
152
108
460,3
E
166,3 25,3 420 208
134 159
128,9 154
144,8
102
48
138
F
10,5
48
9,1
G
108
152
G.19
Record Plus
Dimensional Drawings
X
A W1 W1
R2 max. C Z
3p Breaker hole
4p Breaker hole
A Dimensions
A B C Rmin W1(max) X Y Z
FGFT FG 400/630 Toggle 3p/4p 22.5 73 127 100 115 95 135 1...4
B FDFF4 FG 400/630 RCD 3p/4p 22.5 297.5 68.5 93.5 115 146 78 1...4
D 159
A
79,5
CL of Breaker
B 85
E Electrical Operator
170
Rotary Handle
W1 Y CL of Breaker
R2 max. C
F 3p Breaker hole
4p Breaker hole
X
mm
X
Z
Z
Dimensions
3+4 pole versions A B C Rmin W1(max) X Y Z
FGFE FG 400/630 Electr. Operator 70.5 85 145 100 238.5 41 126 1...4
FGFH FG 400/630 Rotary Handle 22.5 72.5 129 115 161 191 181.5 1...4
G.20
Record Plus
Dimensional Drawings
56 121 138.7
69.35
54
FG frame
102
105
262
26.5
131
106
71
177
142
Backplate - FG400/630 C
Y1
D
Y2 Z
E
X1 X2 X3 X4
Dimensions G
FG400
FG630
X1 322
X2 346
X
X3 367
X4 459
Y1 (3p) 160
Y1 (4p) 205
Y2 (3p) 139
Y2 (4p) 184
Z 1.5
G.21
Record Plus
Dimensional Drawings
24.35 45 45 24.35
159.5
Dimensions
102
185.4
229.05
316.8
321.8
198.8
321.8
63 89.3
95.7
138.7 (3p) 99.3
A 183.7 (4p) 110.5
D
159.5 24.35 45 45 24.35
F
102
185.4
229.05
344.8
344.8
63 89.3
94.7
138.7 (3p) 99.3
183.7 (4p) 110.5
G.22
Record Plus
Dimensional Drawings
198 (3P)
263 (4P)
FG frame
499
A
159,5
G.23
Record Plus
Dimensional Drawings
35 140 29
35 12
98 20
9 M12 M10 5
M8
20
Dimensions
169
158
60
280
278
320
102
298
130
M8
50 70 25 70 70 135
70 70 70 70 70 140
210 280 148
25 260
E 210 280
105 105
F
142
320
G
94
51
151
X
100 140
204 220
330 max
G.24
Record Plus
Dimensional Drawings
277.5
210 260
61.5 140 70
35 35 135
52.5
28.5
FK frame
86.5
180
278
148
140 152
166.5 210
300
E
278
67 40
1.5... 5max. F
148
37.5 152 G
240... 430
X
52.5
32
25
G.25
Record Plus
Dimensional Drawings
Plug in position
Testposition
connected
211
125 273 125
out 34.5 73 23
59
Dimensions
189
189
189
20
55
140
325
325
360
74
out: 261
17
E Y2
F Dimensions
FG 400 FK 800
FG 630 FK 1250
FK 1600
G X2 X1
X3
X1 459 484
X2 - -
X3 - -
X Y1 90 135
Y2 - -
Y1
G.26
Record Plus
Dimensional Drawings
FK frame
W1
X
A
R2 max. C Z
3p Breaker hole
4p Breaker hole
A
Dimensions
A B C Rmin W1(max) X Y Z
FNFT FK 800/1250/1600 3p/4p 35 130 150 120 153 101 104 1...4 B
R2 max. C
E
3p
4p
F
Z W1
G
min
86,5
Dimensions
3 + 4 pole versions A B C Rmin W1(max) X Y Z
FNFE FK 800/1250/1600 Electr. operator 35 129 151 120 220 142 125 1...4
FNFH FK 800/1250/1600 Rotary handle 35 114 163 190 210 232.5 232.5 1...4
G.27
Record Plus
Dimensional Drawings
660 315,8
203,6
600 195,8
490 190,8
470 55,8
45 102 280,8 47,2
max. 100 33,2
Dimensions
69,2
440
410
D 221,2
172,2
167,2 660
158,2 490
151,2 470
E 61,2 102 74,5
69,2
106,9
F
440
410
G.28
Record Plus
Dimensional Drawings
140
FK frame
480
231
210 260
280
A
G.29
Record Plus
Dimensional Drawings
57 52 52
29 29
31 32
15
15
20-30
31.5
20
10 5
30
37.5
60
Dimensions
5-10
60
180
75
6.8
194
60
60
12
10.5
54
18
10.3
74
65
A 1.5
B
36
81
185 23 27 27
52.5
20-30
13.5
C
27
65
60
55
32
110
D
170
60
5-10
5-10
E 32 76
22.5
F
60
105
165
35 35
G 17.5 53
20-30
35
92.5
60
55.5
60
X
32
20-30
202
60
70.5
89.5
5-10
27 28
54 41.5 22 86
G.30
Record Plus
Dimensional Drawings
57 52 55
29 29 31 32
15
15
10-20
5
31.5
20
30
37.5
10
60
Connectivity
5-10
60
75
60
125
240
6.8
60
252
60
12 60
10.5
18
72
10.3
A
74
65
36
1.5
245 23
B
108
27 27 27
20-30
13.5 52.5
75
C
5-10 27
60
55
110
32
D
22.5
60
230
60
5-10
E
60
32 76
F
225
140
60
35 35 35
17.5 53
20-30
35 35
G
92.5
55.5
60
32
60
X
60
70.5
242
89.5
20-30
60
5-10
27 28
54 41.5
22 86
G.31
Record Plus
Dimensional Drawings
49 mm
61 mm
12
Dimensions
40
14 mm 6 mm
54 mm
4
12 mm dia
49
219
99
90
123 mm
93 mm
68 mm
39 39
40
A
50
30 mm 75
50 mm
B
D
Controller type E and E Plus, front view Cut-out for panel or door mounting
Ø6
414 414
E
4xØ6
195
179
F
179
G 430
G.32
Record Plus
Dimensional Drawings
1,4
43,2
46
60
86
91
Connectivity
1,4
28,5
47,5
57,5
C
Dimensions
axb H h E e d
BTR 175 70x175 162 85 261 46 225
D
BTR 305 115x305 226 116 402 55 360
BTR 350 150x350 271 140 460 55 415
E
Circular sensor
F
Dimensions
Ø A B C E F G
G
TTD22 22 52 21 56 27 65
TT35 35 118 90 78.5 27 104
TT60 60 143 102 94.5 27 117
X
TT80 80 163 110 114.5 27 125
TT110 110 198 140 150.5 32 155
TT160 160 248 181 200.5 32 197
TT210 210 298 210 250.5 32 227
Base for DIN-rail or
screw mounting included
TT0110 110 198 140 150.5 32 155 198
TT0210 210 298 210 250.5 32 227 296
G.33
Record Plus
Numerical index
Numerical index
G
X.1 Numerical index by catalogue number
X.7 Numerical index by reference number
X
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
BT... FDBEH3 430885 A.9 FDH36MC050ED 430019 A.7 FDKD3 430966 A.10
BTR 175 704154 A.39 FDBEH4 430886 A.9 FDH36MC080GD 430318 A.7 FDKD4 430967 A.10
BTR 305 704155 A.39 FDBES3 430887 A.9 FDH36MC100GD 430321 A.7 FDKE 617947 A.10
BTR 350 704156 A.39 FDBES4 430888 A.9 FDH36TD016ED 430020 A.6 FDKM1 436720 A.10
FA... FDBRC3 430889 A.9 FDH36TD020ED 430021 A.6 FDL36MC020ED 430065 A.7
FA1BPH 430813 A.8 FDBRC4 430890 A.9 FDH36TD025ED 430022 A.6 FDL36MC030ED 430066 A.7
FA1BR1 430088 A.8 FDBRCL2 433357 A.9 FDH36TD032ED 430023 A.6 FDL36MC050ED 430067 A.7
FA1BR2 430089 A.8 FDBRCS2 433358 A.9 FDH36TD040ED 430024 A.6 FDL36MC080GD 430498 A.7
FA1BR3 430504 A.8 FDBSS3 430891 A.9 FDH36TD050ED 430025 A.6 FDL36MC100GD 430501 A.7
FA1BR4 430505 A.8 FDBSS4 430892 A.9 FDH36TD063ED 430026 A.6 FDL36TD025ED 430070 A.6
FA1BR5 430506 A.8 FDC35TE016ED 433907 A.5 FDH36TD080GD 430338 A.6 FDL36TD032ED 430071 A.6
FA1BR6 430507 A.8 FDC35TE020ED 433911 A.5 FDH36TD100GD 430341 A.6 FDL36TD040ED 430072 A.6
By catalogue number
FA1BRH 430068 A.8 FDC35TE025ED 433914 A.5 FDH36TD125GD 430344 A.6 FDL36TD050ED 430073 A.6
FABAM01 432000 A.20 FDC35TE032ED 433918 A.5 FDH36TD160GD 435821 A.6 FDL36TD063ED 430074 A.6
FABAM10 432003 A.20 FDC35TE040ED 436117 A.5 FDH36TG025ED 430027 A.6 FDL36TD080GD 430518 A.6
FABAT01 430815 A.8 FDC35TE050ED 436118 A.5 FDH36TG032ED 430028 A.6 FDL36TD100GD 430521 A.6
FABAT10 430818 A.8 FDC35TE063ED 436133 A.5 FDH36TG040ED 430029 A.6 FDL36TD125GD 430524 A.6
FAC 430821 A.10 FDC35TE080GD 436143 A.5 FDH36TG050ED 430030 A.6 FDL36TD160GD 435845 A.6
FAECA3 436453 A.47 FDC35TE100GD 436144 A.5 FDH36TG063ED 430031 A.6 FDL436MC020ED 430077 A.7
FAECA6 872240 A.47 FDC35TE125GD 433924 A.5 FDH36TG080GD 430357 A.6 FDL436MC030ED 430078 A.7
FAECE3 872141 A.47 FDC35TE160GD 433925 A.5 FDH36TG100GD 430360 A.6 FDL436MC050ED 430079 A.7
FAECE6 872140 A.47 FDC45TE016ED 433948 A.5 FDH36TG125GD 430363 A.6 FDL436MC080GD 430537 A.7
FAMAM2 436183 A.26 FDC45TE020ED 433949 A.5 FDH36TG160GD 435824 A.6 FDL436MC100GD 430540 A.7
FAMB2 434448 A.26 FDC45TE025ED 433950 A.5 FDH436MC003ED 436398 A.7 FDL436TD025ED 430082 A.6
FAMECM 434013 A.26 FDC45TE032ED 433951 A.5 FDH436MC007ED 430032 A.7 FDL436TD032ED 430083 A.6
FAMGAM2 436185 A.26 FDC45TE040ED 433952 A.5 FDH436MC012ED 430033 A.7 FDL436TD040ED 430084 A.6
FAMGAS2 436186 A.26 FDC45TE050ED 433953 A.5 FDH436MC020ED 430034 A.7 FDL436TD050ED 430085 A.6
FAMGAT2 436187 A.26 FDC45TE063ED 433954 A.5 FDH436MC030ED 430035 A.7 FDL436TD063ED 430086 A.6
FAMGFM2 436188 A.26 FDC45TE080GD 436145 A.5 FDH436MC050ED 430036 A.7 FDL436TD080GD 430557 A.6
FAMGFS2 436189 A.26 FDC45TE100GD 436146 A.5 FDH436MC080GD 430376 A.7 FDL436TD100GD 430560 A.6
FAMGFT2 436190 A.26 FDC45TE125GD 436147 A.5 FDH436MC100GD 430379 A.7 FDL436TD125GD 430563 A.6
FAMLT1 433376 A.22 FDC45TE160GD 436148 A.5 FDH436TD016ED 430037 A.6 FDL436TD160GD 435848 A.6
FAMMT2 436191 A.26 FDDDF3 430893 A.9 FDH436TD020ED 430038 A.6 FDL456TD063ED 430087 A.6
FAMSM2 436192 A.26 FDDDF4 430896 A.9 FDH436TD025ED 430039 A.6 FDL456TD080GD 430568 A.6
FAMST2 436197 A.26 FDDFF3 430899 A.9 FDH436TD032ED 430040 A.6 FDL456TD100GD 430571 A.6
FAPF8 430823 A.9 FDDFF4 430902 A.9 FDH436TD040ED 430041 A.6 FDL456TD125GD 430574 A.6
FAPFM 430824 A.9 FDDFQ3 433489 A.9 FDH436TD050ED 430042 A.6 FDL456TD160GD 435851 A.6
FAPIP 430825 A.9 FDDFQ4 433492 A.9 FDH436TD063ED 430043 A.6 FDL46TD025ED 430090 A.6
FAPM8
FAPPS
430826
430827
A.9
A.9
FDDMP3
FDDMP4
430905
430908
A.9
A.9
FDH436TD080GD
FDH436TD100GD
430396
430399
A.6
A.6
FDL46TD032ED
FDL46TD040ED
430091
430092
A.6
A.6
A
FAR 433500 A.22 FDE36TE016ED 433649 A.5 FDH436TD125GD 430402 A.6 FDL46TD050ED 430093 A.6
FAS01D 436309 A.21 FDE36TE020ED 433651 A.5 FDH436TD160GD 435827 A.6 FDL46TD063ED 430094 A.6
FAS01L 430828 A.8 FDE36TE025ED 433653 A.5 FDH436TG025ED 430044 A.6 FDL46TD080GD 430591 A.6
FAS01R
FAS10D
430831
436310
A.8
A.21
FDE36TE032ED
FDE36TE040ED
433655
433657
A.5
A.5
FDH436TG032ED
FDH436TG040ED
430045
430046
A.6
A.6
FDL46TD100GD
FDL46TD125GD
430594
430597
A.6
A.6
B
FAS10L 430834 A.8 FDE36TE050ED 433659 A.5 FDH436TG050ED 430047 A.6 FDL46TD160GD 435854 A.6
FAS10R 430837 A.8 FDE36TE063ED 433661 A.5 FDH436TG063ED 430048 A.6 FDN13TF016EF 433316 A.5
FASHTB 430840 A.8 FDE36TE080GD 433663 A.5 FDH436TG080GD 430415 A.6 FDN13TF020EF 433322 A.5
FASHTD
FASHTF
430843
430846
A.8
A.8
FDE36TE100GD
FDE36TE125GD
433665
433667
A.5
A.5
FDH436TG100GD
FDH436TG125GD
430418
430421
A.6
A.6
FDN13TF025EF
FDN13TF032EF
433328
433334
A.5
A.5
C
FASHTH 435118 A.8 FDE36TE160GD 433669 A.5 FDH436TG160GD 435830 A.6 FDN13TF040EF 433340 A.5
FASHTJ 430849 A.8 FDE46TE016ED 433697 A.5 FDH456TD063ED 430049 A.6 FDN13TF050EF 433346 A.5
FASHTN 430852 A.8 FDE46TE020ED 433699 A.5 FDH456TD080GD 430426 A.6 FDN13TF063EF 433352 A.5
FASHTU
FAT
430855
431402
A.8
A.22
FDE46TE025ED
FDE46TE032ED
433701
433703
A.5
A.5
FDH456TD100GD
FDH456TD125GD
430429
430432
A.6
A.6
FDN13TF080GF
FDN13TF100GF
433519
433522
A.5
A.5
D
FAUVDN 430858 A.8 FDE46TE040ED 433705 A.5 FDH456TD160GD 435833 A.6 FDN13TF125GF 433525 A.5
FAUVR8 436472 A.8 FDE46TE050ED 433707 A.5 FDH456TG063ED 430050 A.6 FDN13TF160GF 433527 A.5
FAUVRB 440018 A.8 FDE46TE063ED 433709 A.5 FDH456TG080GD 430437 A.6 FDN36MC003ED 436409 A.7
FAUVRD
FAUVRF
430861
430864
A.8
A.8
FDE46TE080GD
FDE46TE100GD
433711
433713
A.5
A.5
FDH456TG100GD
FDH456TG125GD
430440
430443
A.6
A.6
FDN36MC007ED
FDN36MC012ED
430095
430096
A.7
A.7
E
FAUVRH 435120 A.8 FDE46TE125GD 433715 A.5 FDH456TG160GD 435836 A.6 FDN36MC020ED 430097 A.7
FAUVRJ 430867 A.8 FDE46TE160GD 433717 A.5 FDH46TD016ED 430051 A.6 FDN36MC030ED 430098 A.7
FAUVRN 430870 A.8 FDEMF8 430920 A.8 FDH46TD020ED 430052 A.6 FDN36MC050ED 430099 A.7
FAUVRU
FB...
430873 A.8 FDEMFD
FDEMFF
430926
430929
A.8
A.8
FDH46TD025ED
FDH46TD032ED
430053
430054
A.6
A.6
FDN36MC080GD
FDN36MC100GD
430610
430613
A.7
A.7
F
FBAD3 433443 A.43 FDEMFH 430932 A.8 FDH46TD040ED 430055 A.6 FDN36TD016ED 430100 A.6
FBAD4 433446 A.43 FDEMFJ 430935 A.8 FDH46TD050ED 430056 A.6 FDN36TD020ED 430101 A.6
FBAE3 433449 A.43 FDEMFN 430938 A.8 FDH46TD063ED 430057 A.6 FDN36TD025ED 430102 A.6
FBAE4
FBB3E
433452
433455
A.43
A.43
FDFE
FDFF3
432010
430941
A.10
A.10
FDH46TD080GD
FDH46TD100GD
430460
430463
A.6
A.6
FDN36TD032ED
FDN36TD040ED
430103
430104
A.6
A.6
G
FBB3S 433458 A.43 FDFF4 430942 A.10 FDH46TD125GD 430466 A.6 FDN36TD050ED 430105 A.6
FBB4E 433461 A.43 FDFH 430829 A.10 FDH46TD160GD 435839 A.6 FDN36TD063ED 430106 A.6
FBB4S 433464 A.43 FDH13TF016EF 433246 A.5 FDH46TG025ED 430058 A.6 FDN36TD080GD 430630 A.6
FBCI3
FBCI4
433377
433444
A.43
A.43
FDH13TF020EF
FDH13TF025EF
433255
433262
A.5
A.5
FDH46TG032ED
FDH46TG040ED
430059
430060
A.6
A.6
FDN36TD100GD
FDN36TD125GD
430633
430636
A.6
A.6
X
FBF6 883970 A.9 FDH13TF032EF 433268 A.5 FDH46TG050ED 430061 A.6 FDN36TD160GD 433572 A.6
FBTF3L12 433456 A.43 FDH13TF040EF 433274 A.5 FDH46TG063ED 430062 A.6 FDN36TG025ED 430107 A.6
FBTF4L12 433497 A.43 FDH13TF050EF 433280 A.5 FDH46TG080GD 430479 A.6 FDN36TG032ED 430108 A.6
FBTS10L12 433474 A.43 FDH13TF063EF 433286 A.5 FDH46TG100GD 430482 A.6 FDN36TG040ED 430109 A.6
FBTS1L12 433468 A.43 FDH13TF080GF 433292 A.5 FDH46TG125GD 430485 A.6 FDN36TG050ED 430110 A.6
FD... FDH13TF100GF 433298 A.5 FDH46TG160GD 435842 A.6 FDN36TG063ED 430111 A.6
FD1BPE 430876 A.8 FDH13TF125GF 433304 A.5 FDJB 430945 A.9 FDN36TG080GD 430649 A.6
FD1BRE 430877 A.8 FDH13TF160GF 433310 A.5 FDJK 430069 A.9 FDN36TG100GD 430652 A.6
FD1PF 430878 A.10 FDH36MC003ED 436396 A.7 FDJL3 430951 A.9 FDN36TG125GD 430655 A.6
FD1PR 430879 A.10 FDH36MC007ED 430015 A.7 FDJL4 430954 A.9 FDN36TG160GD 433575 A.6
FDBAM11 430880 A.8 FDH36MC012ED 430016 A.7 FDJP 430957 A.9 FDN436MC003ED 436411 A.7
FDBEA3 430883 A.9 FDH36MC020ED 430017 A.7 FDJS3 430960 A.9 FDN436MC007ED 430112 A.7
FDBEA4 430884 A.9 FDH36MC030ED 430018 A.7 FDJS4 430963 A.9 FDN436MC012ED 430113 A.7
X.1
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FDN436MC020ED 430114 A.7 FDQDS4M 431022 A.8 FEH36MC003JF 436361 A.14 FEH456TD200KF 432266 A.16
FDN436MC030ED 430115 A.7 FDS35TD016ED 430161 A.5 FEH36MC007JF 434742 A.14 FEH456TD250KF 432269 A.16
FDN436MC050ED 430116 A.7 FDS35TD020ED 430163 A.5 FEH36MC012JF 434745 A.14 FEH456TG100JF 436026 A.13
FDN436MC080GD 430668 A.7 FDS35TD025ED 430165 A.5 FEH36MC020JF 434748 A.14 FEH456TG125JF 436027 A.13
FDN436MC100GD 430671 A.7 FDS35TD032ED 430167 A.5 FEH36MC030JF 434751 A.14 FEH456TG160JF 436028 A.13
FDN436TD016ED 430117 A.6 FDS35TD040ED 430169 A.5 FEH36MC050JF 434754 A.14 FEH456TG160KF 435908 A.16
FDN436TD020ED 430118 A.6 FDS35TD050ED 430178 A.5 FEH36MC080JF 435893 A.14 FEH456TG200KF 435909 A.16
FDN436TD025ED 430119 A.6 FDS35TD063ED 432952 A.5 FEH36MC100JF 434757 A.14 FEH456TG250KF 435910 A.16
FDN436TD032ED 430120 A.6 FDS35TD080GD 432955 A.5 FEH36MC125JF 436327 A.14 FEH46AA025JBF 435863 A.14
FDN436TD040ED 430121 A.6 FDS35TD100GD 432958 A.5 FEH36MC160JF 434763 A.14 FEH46AA063JEF 435866 A.14
FDN436TD050ED 430122 A.6 FDS35TD125GD 432961 A.5 FEH36MC160KF 434766 A.16 FEH46AA125JGF 431201 A.14
FDN436TD063ED 430123 A.6 FDS35TD160GD 433602 A.5 FEH36MC200KF 436754 A.16 FEH46AA125KGF 431824 A.17
FDN436TD080GD 430688 A.6 FDS45TD016ED 430224 A.5 FEH36MC250KF 434769 A.16 FEH46AA160JJF 431204 A.14
FDN436TD100GD 430691 A.6 FDS45TD020ED 430226 A.5 FEH36SA125JGF 431138 A.15 FEH46AA160KJF 431207 A.17
FDN436TD125GD 430694 A.6 FDS45TD025ED 430228 A.5 FEH36SA160JJF 431141 A.15 FEH46AA250KKF 431210 A.17
FDN436TD160GD 433578 A.6 FDS45TD032ED 430230 A.5 FEH36SA160KJF 431144 A.17 FEH46SA125JGF 431336 A.15
FDN436TG025ED 430124 A.6 FDS45TD040ED 430232 A.5 FEH36SA250KKF 431147 A.17 FEH46SA160JJF 431339 A.15
Numerical index
FDN436TG032ED 430125 A.6 FDS45TD050ED 430241 A.5 FEH36TA025JF 434772 A.13 FEH46SA160KJF 431342 A.17
FDN436TG040ED 430126 A.6 FDS45TD063ED 432964 A.5 FEH36TA032JF 434775 A.13 FEH46SA250KKF 431345 A.17
FDN436TG050ED 430127 A.6 FDS45TD080GD 432967 A.5 FEH36TA040JF 434778 A.13 FEH46TA025JF 434883 A.13
FDN436TG063ED 430128 A.6 FDS45TD100GD 432970 A.5 FEH36TA050JF 434781 A.13 FEH46TA032JF 434886 A.13
FDN436TG080GD 430707 A.6 FDS45TD125GD 432973 A.5 FEH36TA063JF 434784 A.13 FEH46TA040JF 434889 A.13
FDN436TG100GD 430710 A.6 FDS45TD160GD 433604 A.5 FEH36TA080JF 431165 A.13 FEH46TA050JF 434892 A.13
FDN436TG125GD 430713 A.6 FDTCA1316 433400 A.9 FEH36TA100JF 431171 A.13 FEH46TA063JF 434895 A.13
FDN436TG160GD 433581 A.6 FDTCA1416 433401 A.9 FEH36TA125JF 431177 A.13 FEH46TA080JF 431363 A.13
FDN456TD063ED 430129 A.6 FDUA3 431025 A.10 FEH36TA160JF 431183 A.13 FEH46TA100JF 431369 A.13
FDN456TD080GD 430718 A.6 FDUA4 431026 A.10 FEH36TD100JF 431007 A.13 FEH46TA125JF 431375 A.13
FDN456TD100GD 430721 A.6 FDUF3 430830 A.9 FEH36TD125JF 431021 A.13 FEH46TA160JF 431381 A.13
FDN456TD125GD 430724 A.6 FDUF4 430832 A.9 FEH36TD125KF 431393 A.16 FEH46TD100JF 432287 A.13
FDN456TD160GD 433584 A.6 FDUT 433539 A.10 FEH36TD160JF 431965 A.13 FEH46TD125JF 432296 A.13
FDN456TG063ED 430130 A.6 FDY306D063ED 430150 A.7 FEH36TD160KF 431980 A.16 FEH46TD125KF 432300 A.16
FDN456TG080GD 430729 A.6 FDY306D160GD 430805 A.7 FEH36TD200KF 432076 A.16 FEH46TD160JF 432303 A.13
FDN456TG100GD 430732 A.6 FDY406D063ED 430151 A.7 FEH36TD250KF 432096 A.16 FEH46TD160KF 432307 A.16
FDN456TG125GD 430735 A.6 FDY406D160GD 430810 A.7 FEH36TG100JF 434808 A.13 FEH46TD200KF 432311 A.16
FDN456TG160GD 433587 A.6 FE... FEH36TG125JF 434811 A.13 FEH46TD250KF 432316 A.16
FDN46TD016ED 430131 A.6 FE1BPE 432011 A.20 FEH36TG160JF 434817 A.13 FEH46TG100JF 434919 A.13
FDN46TD020ED 430132 A.6 FE1BPW 432184 A.21 FEH36TG160KF 434820 A.16 FEH46TG125JF 434922 A.13
FDN46TD025ED 430133 A.6 FE1BRE 432012 A.20 FEH36TG200KF 434823 A.16 FEH46TG160JF 434928 A.13
A FDN46TD032ED
FDN46TD040ED
430134
430135
A.6
A.6
FE1BRW
FE1I2
432188
437001
A.21
A.46
FEH36TG250KF
FEH406F160JF
434826
431213
A.16
A.18
FEH46TG160KF
FEH46TG200KF
434931
434934
A.16
A.16
FDN46TD050ED 430136 A.6 FE1PF 432017 A.22 FEH406F250KF 431216 A.19 FEH46TG250KF 434937 A.16
FDN46TD063ED 430137 A.6 FEBAT01 430969 A.20 FEH436MC050JF 434829 A.14 FEJB 432073 A.22
FDN46TD080GD 430752 A.6 FEBAT10 430970 A.20 FEH436MC100JF 434832 A.14 FEJL3 432079 A.22
B FDN46TD100GD
FDN46TD125GD
430755
430758
A.6
A.6
FEBE43
FEBE44
432018
432019
A.21
A.21
FEH436MC125JF
FEH436MC160JF
436329
434838
A.14
A.14
FEJL4
FEJN3
432082
436467
A.22
A.21
FDN46TD160GD 433590 A.6 FEBE93 432020 A.21 FEH436MC160KF 434841 A.16 FEJN4 436468 A.21
FDN46TG025ED 430138 A.6 FEBE94 432021 A.21 FEH436MC200KF 436755 A.16 FEJP 432085 A.22
FDN46TG032ED 430139 A.6 FEBEA3 432022 A.21 FEH436MC250KF 434844 A.16 FEJS3 432088 A.22
C FDN46TG040ED
FDN46TG050ED
430140
430141
A.6
A.6
FEBEA4
FEBEH3
432023
432024
A.21
A.21
FEH436SA125JGF
FEH436SA160JJF
431225
431228
A.15
A.15
FEJS4
FEL306F160JF
432091
431419
A.22
A.18
FDN46TG063ED 430142 A.6 FEBEH4 432025 A.21 FEH436SA160KJF 431231 A.17 FEL306F250KF 431422 A.19
FDN46TG080GD 430771 A.6 FEBES3 432026 A.21 FEH436SA250KKF 431234 A.17 FEL36AA025JBF 435869 A.14
FDN46TG100GD 430774 A.6 FEBES4 432027 A.21 FEH436TA025JF 434847 A.13 FEL36AA063JEF 435872 A.14
D FDN46TG125GD
FDN46TG160GD
430777
433593
A.6
A.6
FEBRC3
FEBRC4
432028
432029
A.21
A.21
FEH436TA032JF
FEH436TA040JF
434850
434853
A.13
A.13
FEL36AA125JGF
FEL36AA125KGF
431405
431836
A.14
A.17
FDN66TD016ED 430143 A.5 FEBRCS3 432190 A.21 FEH436TA050JF 434856 A.13 FEL36AA160JJF 431410 A.14
FDN66TD020ED 430144 A.5 FEBRCS4 432191 A.21 FEH436TA063JF 434859 A.13 FEL36AA160KJF 431413 A.17
FDN66TD025ED 430145 A.5 FEBSS3 432032 A.21 FEH436TA080JF 431252 A.13 FEL36AA250KKF 431416 A.17
E FDN66TD032ED
FDN66TD040ED
430146
430147
A.5
A.5
FEBSS4
FEDDF3
432033
432034
A.21
A.21
FEH436TA100JF
FEH436TA125JF
431258
431264
A.13
A.13
FEL36MC003JF
FEL36MC007JF
436363
434940
A.14
A.14
FDN66TD050ED 430148 A.5 FEDDF4 432037 A.21 FEH436TA160JF 431270 A.13 FEL36MC012JF 434943 A.14
FDN66TD063ED 430149 A.5 FEDFF3 432040 A.21 FEH436TD100JF 432198 A.13 FEL36MC020JF 434946 A.14
FDN66TD080GD 430794 A.5 FEDFF4 432043 A.21 FEH436TD125JF 432205 A.13 FEL36MC030JF 434949 A.14
F FDN66TD100GD
FDN66TD125GD
430797
430800
A.5
A.5
FEDFQ3
FEDFQ4
430987
431842
A.21
A.21
FEH436TD125KF
FEH436TD160JF
432209
432214
A.16
A.13
FEL36MC050JF
FEL36MC080JF
434952
435896
A.14
A.14
FDN66TD160GD 433599 A.5 FEDMP3 432046 A.21 FEH436TD160KF 432218 A.16 FEL36MC100JF 434955 A.14
FDNFT 430968 A.8 FEDMP4 432049 A.21 FEH436TD200KF 432223 A.16 FEL36MC125JF 436331 A.14
FDNR4 430971 A.8 FEEMF8 435812 A.20 FEH436TD250KF 432227 A.16 FEL36MC160JF 434961 A.14
G FDNRC/5
FDNRCV/5
436474
436475
A.8
A.8
FEEMFD
FEEMFF
432052
432055
A.20
A.20
FEH436TG100JF
FEH436TG125JF
435902
435903
A.13
A.13
FEL36MC160KF
FEL36MC200KF
434964
436756
A.16
A.16
FDNRD/5 436476 A.8 FEEMFH 432058 A.20 FEH436TG160JF 435904 A.13 FEL36MC250KF 434967 A.16
FDNRDV/5 436477 A.8 FEEMFJ 432061 A.20 FEH436TG160KF 435905 A.16 FEL36SA125JGF 431431 A.15
FDNRE 430986 A.8 FEEMFN 432064 A.20 FEH436TG200KF 435906 A.16 FEL36SA160JJF 431434 A.15
X FDNRF/5
FDNRFV/5
436478
436479
A.8
A.8
FEEO1J
FEEO1N
437000
437003
A.47
A.47
FEH436TG250KF
FEH456SA125JGF
435907
431285
A.16
A.15
FEL36SA160KJF
FEL36SA250KKF
431437
431440
A.17
A.17
FDNRY/5 436487 A.8 FEFE 430943 A.22 FEH456SA160JJF 431288 A.15 FEL36TA025JF 434970 A.13
FDNRYV/5 436488 A.8 FEFF3 432067 A.22 FEH456SA160KJF 431291 A.17 FEL36TA032JF 434973 A.13
FDNRZ/5 436489 A.8 FEFF4 432068 A.22 FEH456SA250KKF 431294 A.17 FEL36TA040JF 434976 A.13
FDNRZV/5 436490 A.8 FEFT 432071 A.22 FEH456TA063JF 434871 A.13 FEL36TA050JF 434979 A.13
FDQDB3H 433364 A.8 FEH306F160JF 431126 A.18 FEH456TA080JF 431300 A.13 FEL36TA063JF 434982 A.13
FDQDB3M 433370 A.8 FEH306F250KF 431129 A.19 FEH456TA100JF 431306 A.13 FEL36TA080JF 431458 A.13
FDQDB4H 433373 A.8 FEH36AA025JBF 435857 A.14 FEH456TA125JF 431312 A.13 FEL36TA100JF 431464 A.13
FDQDB4M 433379 A.8 FEH36AA063JEF 435860 A.14 FEH456TA160JF 431318 A.13 FEL36TA125JF 431470 A.13
FDQDI3M 433388 A.8 FEH36AA125JGF 431112 A.14 FEH456TD100JF 432242 A.13 FEL36TA160JF 431476 A.13
FDQDI4M 433397 A.8 FEH36AA125KGF 431116 A.17 FEH456TD125JF 432250 A.13 FEL36TD100JF 432332 A.13
FDQDS3H 433542 A.8 FEH36AA160JJF 431117 A.14 FEH456TD125KF 432254 A.16 FEL36TD125JF 432341 A.13
FDQDS3M 431013 A.8 FEH36AA160KJF 431120 A.17 FEH456TD160JF 432259 A.13 FEL36TD125KF 432344 A.16
FDQDS4H 433548 A.8 FEH36AA250KKF 431123 A.17 FEH456TD160KF 432263 A.16 FEL36TD160JF 432349 A.13
X.2
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FEL36TD160KF 432353 A.16 FEL46TD125KF 432924 A.16 FEN436TG100JF 436014 A.13 FERJ3G0080 432186 A.14
FEL36TD200KF 432357 A.16 FEL46TD160JF 432927 A.13 FEN436TG125JF 436015 A.13 FERJ3G0125 432192 A.14
FEL36TD250KF 432361 A.16 FEL46TD160KF 432930 A.16 FEN436TG160JF 436016 A.13 FERJ3J0100 432189 A.14
FEL36TG100JF 435923 A.13 FEL46TD200KF 432933 A.16 FEN436TG160KF 436017 A.16 FERJ3J0160 432195 A.14
FEL36TG125JF 435926 A.13 FEL46TD250KF 432936 A.16 FEN436TG200KF 436018 A.16 FERJ3K0160 432204 A.17
FEL36TG160JF 435932 A.13 FEL46TG100JF 435992 A.13 FEN436TG250KF 436019 A.16 FERJ3K0250 432207 A.17
FEL36TG160KF 435935 A.16 FEL46TG125JF 435995 A.13 FEN456SA125JGF 431871 A.15 FERJ43B0016 432210 A.14
FEL36TG200KF 435938 A.16 FEL46TG160JF 436002 A.13 FEN456SA160JJF 431874 A.15 FERJ43B0025 432213 A.14
FEL36TG250KF 435941 A.16 FEL46TG160KF 436005 A.16 FEN456SA160KJF 431877 A.17 FERJ43E0040 432216 A.14
FEL406F160JF 431506 A.18 FEL46TG200KF 436008 A.16 FEN456SA250KKF 431880 A.17 FERJ43E0063 432219 A.14
FEL406F250KF 431509 A.19 FEL46TG250KF 436011 A.16 FEN456TA063JF 435202 A.13 FERJ43G0080 432222 A.14
FEL436MC050JF 434994 A.14 FEN306F160JF 431712 A.18 FEN456TA080JF 431886 A.13 FERJ43G0125 432228 A.14
By catalogue number
FEL436MC100JF 434997 A.14 FEN306F250KF 431715 A.19 FEN456TA100JF 431892 A.13 FERJ43J0100 432225 A.14
FEL436MC125JF 436333 A.14 FEN36AA025JBF 435881 A.14 FEN456TA125JF 431898 A.13 FERJ43J0160 432231 A.14
FEL436MC160JF 435004 A.14 FEN36AA063JEF 435884 A.14 FEN456TA160JF 431904 A.13 FERJ43K0160 432240 A.17
FEL436MC160KF 435007 A.16 FEN36AA125JGF 431698 A.14 FEN456TD100JF 433028 A.13 FERJ43K0250 432243 A.17
FEL436MC200KF 436763 A.16 FEN36AA125KGF 431920 A.17 FEN456TD125JF 433034 A.13 FERJ45E0063 432249 A.14
FEL436MC250KF 435010 A.16 FEN36AA160JJF 431703 A.14 FEN456TD125KF 433037 A.16 FERJ45G0080 432252 A.14
FEL436SA125JGF 431518 A.15 FEN36AA160KJF 431706 A.17 FEN456TD160JF 433040 A.13 FERJ45G0125 432258 A.14
FEL436SA160JJF 431521 A.15 FEN36AA250KKF 431709 A.17 FEN456TD160KF 433043 A.16 FERJ45J0100 432255 A.14
FEL436SA160KJF 431524 A.17 FEN36MC003JF 436365 A.14 FEN456TD200KF 433046 A.16 FERJ45J0160 432261 A.14
FEL436SA250KKF 431527 A.17 FEN36MC007JF 435073 A.14 FEN456TD250KF 433049 A.16 FERJ45K0160 432270 A.17
FEL436TA025JF 435013 A.13 FEN36MC012JF 435076 A.14 FEN456TG100JF 436020 A.13 FERJ45K0250 432273 A.17
FEL436TA032JF 435016 A.13 FEN36MC020JF 435079 A.14 FEN456TG125JF 436021 A.13 FERJ4B0016 432276 A.14
FEL436TA040JF 435019 A.13 FEN36MC030JF 435082 A.14 FEN456TG160JF 436022 A.13 FERJ4B0025 432279 A.14
FEL436TA050JF 435022 A.13 FEN36MC050JF 435085 A.14 FEN456TG160KF 436023 A.16 FERJ4E0040 432282 A.14
FEL436TA063JF 435025 A.13 FEN36MC080JF 435899 A.14 FEN456TG200KF 436024 A.16 FERJ4E0063 432285 A.14
FEL436TA080JF 431545 A.13 FEN36MC100JF 435088 A.14 FEN456TG250KF 436025 A.16 FERJ4G0080 432288 A.14
FEL436TA100JF 431551 A.13 FEN36MC125JF 436335 A.14 FEN46AA025JBF 435887 A.14 FERJ4G0125 432294 A.14
FEL436TA125JF 431557 A.13 FEN36MC160JF 435094 A.14 FEN46AA063JEF 435890 A.14 FERJ4J0100 432291 A.14
FEL436TA160JF 431563 A.13 FEN36MC160KF 435097 A.16 FEN46AA125JGF 431787 A.14 FERJ4J0160 432297 A.14
FEL436TD100JF 432374 A.13 FEN36MC200KF 436764 A.16 FEN46AA125KGF 431938 A.17 FERJ4K0160 432306 A.17
FEL436TD125JF 432573 A.13 FEN36MC250KF 435100 A.16 FEN46AA160JJF 431790 A.14 FERJ4K0250 432309 A.17
FEL436TD125KF 432576 A.16 FEN36SA125JGF 431724 A.15 FEN46AA160KJF 431793 A.17 FERS3B0025 432312 A.15
FEL436TD160JF 432585 A.13 FEN36SA160JJF 431727 A.15 FEN46AA250KKF 431796 A.17 FERS3E0063 432315 A.15
FEL436TD160KF 432588 A.16 FEN36SA160KJF 431730 A.17 FEN46SA125JGF 431922 A.15 FERS3G0125 432318 A.15
FEL436TD200KF 432618 A.16 FEN36SA250KKF 431733 A.17 FEN46SA160JJF 431925 A.15 FERS3J0160 432321 A.15
FEL436TD250KF 432621 A.16 FEN36TA025JF 435103 A.13 FEN46SA160KJF 431928 A.17 FERS3K0250 432327 A.17
FEL436TG100JF
FEL436TG125JF
435944
435947
A.13
A.13
FEN36TA032JF
FEN36TA040JF
435106
435109
A.13
A.13
FEN46SA250KKF
FEN46TA025JF
431931
435214
A.17
A.13
FERS43B0025
FERS43E0063
432330
432333
A.15
A.15
A
FEL436TG160JF 435950 A.13 FEN36TA050JF 435112 A.13 FEN46TA032JF 435217 A.13 FERS43G0125 432336 A.15
FEL436TG160KF 435953 A.16 FEN36TA063JF 435115 A.13 FEN46TA040JF 435220 A.13 FERS43J0160 432339 A.15
FEL436TG200KF 435956 A.16 FEN36TA080JF 431751 A.13 FEN46TA050JF 435223 A.13 FERS43K0250 432345 A.17
FEL436TG250KF
FEL456SA125JGF
435959
431578
A.16
A.15
FEN36TA100JF
FEN36TA125JF
431757
431763
A.13
A.13
FEN46TA063JF
FEN46TA080JF
435226
431949
A.13
A.13
FERS45E0063
FERS45G0125
432348
432351
A.15
A.15
B
FEL456SA160JJF 431581 A.15 FEN36TA160JF 431769 A.13 FEN46TA100JF 431955 A.13 FERS45J0160 432354 A.15
FEL456SA160KJF 431584 A.17 FEN36TD100JF 432945 A.13 FEN46TA125JF 431961 A.13 FERS45K0250 432360 A.17
FEL456SA250KKF 431587 A.17 FEN36TD125JF 432953 A.13 FEN46TA160JF 431967 A.13 FERS4B0025 432363 A.15
FEL456TA063JF
FEL456TA080JF
435037
431593
A.13
A.13
FEN36TD125KF
FEN36TD160JF
432962
432971
A.16
A.13
FEN46TD100JF
FEN46TD125JF
433061
433067
A.13
A.13
FERS4E0063
FERS4G0125
432366
432369
A.15
A.15
C
FEL456TA100JF 431599 A.13 FEN36TD160KF 432976 A.16 FEN46TD125KF 433070 A.16 FERS4J0160 432372 A.15
FEL456TA125JF 431605 A.13 FEN36TD200KF 432979 A.16 FEN46TD160JF 433073 A.13 FERS4K0250 432378 A.17
FEL456TA160JF 431611 A.13 FEN36TD250KF 432982 A.16 FEN46TD160KF 433076 A.16 FETAA3J0025 432414 A.18
FEL456TD100JF
FEL456TD125JF
432699
432747
A.13
A.13
FEN36TG100JF
FEN36TG125JF
435139
435142
A.13
A.13
FEN46TD200KF
FEN46TD250KF
433079
433082
A.16
A.16
FETAA3J0063
FETAA3J0125
432417
432420
A.18
A.18
D
FEL456TD125KF 432780 A.16 FEN36TG160JF 435148 A.13 FEN46TG100JF 435250 A.13 FETAA3J0160 432423 A.18
FEL456TD160JF 432834 A.13 FEN36TG160KF 435151 A.16 FEN46TG125JF 435253 A.13 FETAA3K0125 432004 A.19
FEL456TD160KF 432843 A.16 FEN36TG200KF 435154 A.16 FEN46TG160JF 435259 A.13 FETAA3K0160 432426 A.19
FEL456TD200KF
FEL456TD250KF
432868
432871
A.16
A.16
FEN36TG250KF
FEN406F160JF
435157
431799
A.16
A.18
FEN46TG160KF
FEN46TG200KF
435262
435265
A.16
A.16
FETAA3K0250
FETAA4J0025
432429
432432
A.19
A.18
E
FEL456TG100JF 435962 A.13 FEN406F250KF 431802 A.19 FEN46TG250KF 435268 A.16 FETAA4J0063 432435 A.18
FEL456TG125JF 435965 A.13 FEN436MC050JF 435160 A.14 FENFT 433531 A.20 FETAA4J0125 432438 A.18
FEL456TG160JF 435968 A.13 FEN436MC100JF 435163 A.14 FENR4 432099 A.20 FETAA4J0160 432441 A.18
FEL456TG160KF
FEL456TG200KF
435971
435974
A.16
A.16
FEN436MC125JF
FEN436MC160JF
436356
435169
A.14
A.14
FENRC
FENRC/5
432102
436491
A.46
A.20
FETAA4K0125
FETAA4K0160
432007
432444
A.19
A.19
F
FEL456TG250KF 435977 A.16 FEN436MC160KF 435172 A.16 FENRCV/5 436492 A.20 FETAA4K0250 432447 A.19
FEL46AA025JBF 435875 A.14 FEN436MC200KF 436765 A.16 FENRD/5 436493 A.20 FETCA1316 432156 A.21
FEL46AA063JEF 435878 A.14 FEN436MC250KF 435175 A.16 FENRDV/5 436494 A.20 FETCA1320 432157 A.21
FEL46AA125JGF
FEL46AA125KGF
431494
431890
A.14
A.17
FEN436SA125JGF
FEN436SA160JJF
431811
431814
A.15
A.15
FENRF/5
FENRFV/5
436495
436496
A.20
A.20
FETCA1323
FETCA1416
432160
432158
A.21
A.21
G
FEL46AA160JJF 431497 A.14 FEN436SA160KJF 431817 A.17 FENRW 432120 A.20 FETCA1420 432159 A.21
FEL46AA160KJF 431500 A.17 FEN436SA250KKF 431820 A.17 FENRX/5 436499 A.45 FETCA1423 432161 A.21
FEL46AA250KKF 431503 A.17 FEN436TA025JF 435178 A.13 FENRY/5 436500 A.20 FETCA630A 880954 A.21
FEL46SA125JGF
FEL46SA160JJF
431629
431632
A.15
A.15
FEN436TA032JF
FEN436TA040JF
435181
435184
A.13
A.13
FENRYV/5
FENRZ/5
436501
436502
A.20
A.20
FETCA640A
FETD30J0160
880955
432480
A.21
A.18
X
FEL46SA160KJF 431635 A.17 FEN436TA050JF 435187 A.13 FENRZV/5 436503 A.20 FETD30K0250 432483 A.19
FEL46SA250KKF 431638 A.17 FEN436TA063JF 435190 A.13 FEQDB3HJ 432132 A.20 FETD40J0160 432486 A.18
FEL46TA025JF 435049 A.13 FEN436TA080JF 431838 A.13 FEQDB3HK 432135 A.20 FETD40K0250 432489 A.19
FEL46TA032JF 435052 A.13 FEN436TA100JF 431844 A.13 FEQDB3MJ 432138 A.20 FETMC3J0012 432495 A.18
FEL46TA040JF 435055 A.13 FEN436TA125JF 431850 A.13 FEQDB3MK 432141 A.20 FETMC3J0020 432498 A.18
FEL46TA050JF 435058 A.13 FEN436TA160JF 431856 A.13 FEQDB4HJ 432144 A.20 FETMC3J0030 434736 A.18
FEL46TA063JF 435061 A.13 FEN436TD100JF 432994 A.13 FEQDB4HK 432147 A.20 FETMC3J0050 432501 A.18
FEL46TA080JF 431656 A.13 FEN436TD125JF 433001 A.13 FEQDB4MJ 432150 A.20 FETMC3J0080 436078 A.18
FEL46TA100JF 431662 A.13 FEN436TD125KF 433004 A.16 FEQDB4MK 432153 A.20 FETMC3J0100 432504 A.18
FEL46TA125JF 431668 A.13 FEN436TD160JF 433007 A.13 FERJ3B0016 432174 A.14 FETMC3J0125 436358 A.18
FEL46TA160JF 431674 A.13 FEN436TD160KF 433010 A.16 FERJ3B0025 432177 A.14 FETMC3J0160 432510 A.18
FEL46TD100JF 432907 A.13 FEN436TD200KF 433013 A.16 FERJ3E0040 432180 A.14 FETMC3K0160 432513 A.19
FEL46TD125JF 432921 A.13 FEN436TD250KF 433016 A.16 FERJ3E0063 432183 A.14 FETMC3K0200 436778 A.19
X.3
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FETMC3K0250 432516 A.19 FETTG4J0160 432777 A.18 FGH36VA630NNF 434958 A.28 FGL46AA400LLF 431330 A.25
FETMC43J0050 432528 A.18 FETTG4K0160 432786 A.19 FGH406F250LF 434234 A.29 FGL46AA400NLF 434534 A.27
FETMC43J0100 432531 A.18 FETTG4K0200 432789 A.19 FGH406F400LF 431150 A.29 FGL46AA500NNF 434770 A.27
FETMC43J0125 436359 A.18 FETTG4K0250 432792 A.19 FGH406F400NF 431153 A.30 FGL46AA630NNF 431333 A.27
FETMC43J0160 432537 A.18 FEUA3 432162 A.22 FGH406F630NF 431156 A.30 FGL46KA250LKF 436153 A.26
FETMC43K0160 432540 A.19 FEUA4 432163 A.22 FGH436BM400LLF 434669 A.25 FGL46KA350LLF 434468 A.26
FETMC43K0200 436779 A.19 FEUT 433540 A.22 FGH436BM500NNF 434672 A.27 FGL46KA400LLF 436154 A.26
FETMC43K0250 432543 A.19 FEV36TA125KF 432416 A.16 FGH436SA250LKF 434235 A.25 FGL46KA400NLF 436155 A.28
FETTA3J0025 432546 A.18 FEV36TA160KF 436798 A.16 FGH436SA400LLF 434408 A.25 FGL46KA500NNF 434782 A.28
FETTA3J0032 432549 A.18 FEV36TA200KF 431058 A.16 FGH436SA400NLF 431168 A.27 FGL46KA630NNF 434068 A.28
FETTA3J0040 432552 A.18 FEV36TA250KF 431061 A.16 FGH436SA500NNF 434621 A.27 FGL46SA250LKF 434246 A.25
FETTA3J0050 432555 A.18 FEV46TA125KF 431082 A.16 FGH436VA400LLF 434960 A.26 FGL46SA400LLF 434474 A.25
FETTA3J0063 432558 A.18 FEV46TA160KF 436817 A.16 FGH436VA630NNF 434965 A.28 FGL46SA400NLF 431449 A.27
FETTA3J0080 432561 A.18 FEV46TA200KF 431094 A.16 FGH456SA250LKF 434236 A.25 FGL46SA500NNF 434806 A.27
FETTA3J0100 432564 A.18 FEV46TA250KF 431097 A.16 FGH456SA400LLF 434414 A.25 FGL46VA400LLF 435128 A.26
FETTA3J0125 432567 A.18 FEWS3 432168 A.21 FGH456SA400NLF 431198 A.27 FGL46VA630NNF 435134 A.28
FETTA3J0160 432570 A.18 FEWS4 432171 A.21 FGH456SA500NNF 434627 A.27 FGN306F250LF 434247 A.29
Numerical index
FETTA43J0025 432391 A.18 FEY306D160JF 431988 A.15 FGH456VA400LLF 434971 A.26 FGN306F400LF 431473 A.29
FETTA43J0032 432394 A.18 FEY306D250KF 431991 A.17 FGH456VA630NNF 434977 A.28 FGN306F400NF 431488 A.30
FETTA43J0040 432397 A.18 FEY406D160JF 431994 A.15 FGH46AA250LKF 434237 A.25 FGN306F630NF 431491 A.30
FETTA43J0050 432400 A.18 FEY406D250KF 431997 A.17 FGH46AA400LLF 431106 A.25 FGN36AA250LKF 434248 A.25
FETTA43J0063 432403 A.18 FF... FGH46AA400NLF 434432 A.27 FGN36AA400LLF 431455 A.25
FETTA43J0080 432406 A.18 FFKN46NE100SQF 435450 A.36 FGH46AA500NNF 434630 A.27 FGN36AA400NLF 434561 A.27
FETTA43J0100 432409 A.18 FG... FGH46AA630NNF 431132 A.27 FGN36AA500NNF 434812 A.27
FETTA43J0125 432412 A.18 FG1BPE 431403 A.31 FGH46KA250LKF 434041 A.26 FGN36AA630NNF 431461 A.27
FETTA43J0160 432582 A.18 FG1BPW 433406 A.32 FGH46KA350LLF 434420 A.26 FGN36BM400LLF 434687 A.25
FETTA45J0063 432603 A.18 FG1BRE 431404 A.31 FGH46KA400LLF 434042 A.26 FGN36BM500NNF 434690 A.27
FETTA45J0080 432606 A.18 FG1BRW 433407 A.32 FGH46KA400NLF 434043 A.28 FGN36KA250LKF 434073 A.26
FETTA45J0100 432609 A.18 FG1I2 437005 A.46 FGH46KA500NNF 434633 A.28 FGN36KA350LLF 434483 A.26
FETTA45J0125 432612 A.18 FG1I4 437009 A.46 FGH46KA630NNF 434044 A.28 FGN36KA400LLF 436156 A.26
FETTA45J0160 432615 A.18 FG1PF 431408 A.33 FGH46SA250LKF 434238 A.25 FGN36KA400NLF 436157 A.28
FETTA4J0025 432636 A.18 FG1PR 431409 A.33 FGH46SA400LLF 434426 A.25 FGN36KA500NNF 434824 A.28
FETTA4J0032 432639 A.18 FGBEA3 431686 A.32 FGH46SA400NLF 431240 A.27 FGN36KA630NNF 436158 A.28
FETTA4J0040 432642 A.18 FGBEA4 431690 A.32 FGH46SA500NNF 434642 A.27 FGN36SA250LKF 434249 A.25
FETTA4J0050 432645 A.18 FGBEH3 431691 A.32 FGH46VA400LLF 434983 A.26 FGN36SA400LLF 434489 A.25
FETTA4J0063 432648 A.18 FGBEH4 431695 A.32 FGH46VA630NNF 435003 A.28 FGN36SA400NLF 431530 A.27
FETTA4J0080 432651 A.18 FGBES3 431696 A.32 FGJB 432840 A.33 FGN36SA500NNF 434835 A.27
FETTA4J0100 432654 A.18 FGBES4 431697 A.32 FGJM3 432846 A.33 FGN36VA400LLF 435140 A.26
A FETTA4J0125
FETTA4J0160
432657
432660
A.18
A.18
FGBRC3
FGBRC4
431701
431702
A.32
A.32
FGJM4
FGJN3
432849
436469
A.33
A.32
FGN36VA630NNF
FGN406F250LF
435146
434250
A.28
A.29
FETTD3J0100 433159 A.18 FGBRCS3 432193 A.32 FGJN4 436470 A.32 FGN406F400LF 431548 A.29
FETTD3J0125 433164 A.18 FGBRCS4 432194 A.32 FGJP 432852 A.33 FGN406F400NF 431554 A.30
FETTD3J0160 433168 A.18 FGBSS3 431981 A.32 FGJS3 432855 A.33 FGN406F630NF 431560 A.30
B FETTD3K0125
FETTD3K0160
433182
433186
A.19
A.19
FGBSS4
FGDDF3
431982
430944
A.32
A.32
FGJS4
FGJW3
432858
432861
A.33
A.33
FGN436BM400LLF
FGN436BM500NNF
434693
434696
A.25
A.27
FETTD3K0200 433191 A.19 FGDDF4 431064 A.32 FGJW4 432864 A.33 FGN436SA250LKF 434251 A.25
FETTD3K0250 433195 A.19 FGDFF3 431983 A.32 FGL306F250LF 434239 A.29 FGN436SA400LLF 435277 A.25
FETTD43J0100 433201 A.18 FGDFF4 431986 A.32 FGL306F400LF 431261 A.29 FGN436SA400NLF 431596 A.27
C FETTD43J0125
FETTD43J0160
433204
433207
A.18
A.18
FGDMP3
FGDMP4
432796
432799
A.32
A.32
FGL306F400NF
FGL306F630NF
431267
431282
A.30
A.30
FGN436SA500NNF
FGN436VA400LLF
434848
435152
A.27
A.26
FETTD43K0125 433216 A.19 FGEMF8 432811 A.31 FGL36AA250LKF 434240 A.25 FGN436VA630NNF 435158 A.28
FETTD43K0160 433219 A.19 FGEMFD 432817 A.31 FGL36AA400LLF 431246 A.25 FGN456SA250LKF 434252 A.25
FETTD43K0200 433222 A.19 FGEMFF 432820 A.31 FGL36AA400NLF 434459 A.27 FGN456SA400LLF 434504 A.25
D FETTD43K0250
FETTD45J0100
433225
433231
A.19
A.18
FGEMFH
FGEMFJ
432823
432826
A.31
A.31
FGL36AA500NNF
FGL36AA630NNF
434645
431249
A.27
A.27
FGN456SA400NLF
FGN456SA500NNF
431626
434860
A.27
A.27
FETTD45J0125 433234 A.18 FGEMFN 432829 A.31 FGL36BM400LLF 434675 A.25 FGN456VA400LLF 435164 A.26
FETTD45J0160 433239 A.18 FGEO2J 437004 A.47 FGL36BM500NNF 434678 A.27 FGN456VA630NNF 435167 A.28
FETTD45K0125 433252 A.19 FGEO2N 437007 A.47 FGL36KA250LKF 434049 A.26 FGN46AA250LKF 434253 A.25
E FETTD45K0160
FETTD45K0200
433257
433260
A.19
A.19
FGEO3J
FGEO3N
437008
437010
A.47
A.47
FGL36KA350LLF
FGL36KA400LLF
434438
434050
A.26
A.26
FGN46AA400LLF
FGN46AA400NLF
431536
434636
A.25
A.27
FETTD45K0250 433263 A.19 FGFE 430544 A.33 FGL36KA400NLF 434051 A.28 FGN46AA500NNF 434866 A.27
FETTD4J0100 433269 A.18 FGFH 430545 A.33 FGL36KA500NNF 434651 A.28 FGN46AA630NNF 431539 A.27
FETTD4J0125 433272 A.18 FGFT 432836 A.33 FGL36KA630NNF 434052 A.28 FGN46KA250LKF 436159 A.26
F FETTD4J0160
FETTD4K0125
433275
433284
A.18
A.19
FGGS0250
FGGS0400
431870
432838
A.33
A.33
FGL36SA250LKF
FGL36SA400LLF
434241
434444
A.25
A.25
FGN46KA350LLF
FGN46KA400LLF
434510
436160
A.26
A.26
FETTD4K0160 433287 A.19 FGGS0630 432839 A.33 FGL36SA400NLF 431309 A.27 FGN46KA400NLF 436161 A.28
FETTD4K0200 433290 A.19 FGH306F250LF 434231 A.29 FGL36SA500NNF 434657 A.27 FGN46KA500NNF 434872 A.28
FETTD4K0250 433293 A.19 FGH306F400LF 431050 A.29 FGL36VA400LLF 435065 A.26 FGN46KA630NNF 434092 A.28
G FETTG3J0100
FETTG3J0125
433296
432693
A.18
A.18
FGH306F400NF
FGH306F630NF
431067
431073
A.30
A.30
FGL36VA630NNF
FGL406F250LF
435071
434242
A.28
A.29
FGN46SA250LKF
FGN46SA400LLF
434254
435280
A.25
A.25
FETTG3J0160 432696 A.18 FGH36AA250LKF 434232 A.25 FGL406F400LF 431351 A.29 FGN46SA400NLF 431650 A.27
FETTG3K0160 432705 A.19 FGH36AA400LLF 431032 A.25 FGL406F400NF 431354 A.30 FGN46SA500NNF 434884 A.27
FETTG3K0200 432708 A.19 FGH36AA400NLF 433142 A.27 FGL406F630NF 431357 A.30 FGN46VA400LLF 435170 A.26
X FETTG3K0250
FETTG43J0100
432711
433311
A.19
A.18
FGH36AA500NNF
FGH36AA630NNF
434600
431038
A.27
A.27
FGL436BM400LLF
FGL436BM500NNF
434681
434684
A.25
A.27
FGN46VA630NNF
FGNFT
435176
432867
A.28
A.31
FETTG43J0125 432717 A.18 FGH36BM400LLF 434663 A.25 FGL436SA250LKF 434243 A.25 FGNRC 432873 A.46
FETTG43J0160 432720 A.18 FGH36BM500NNF 434666 A.27 FGL436SA400LLF 434453 A.25 FGNRC/5 436504 A.31
FETTG43K0160 432729 A.19 FGH36KA250LKF 436150 A.26 FGL436SA400NLF 431372 A.27 FGNRCV/5 436505 A.31
FETTG43K0200 432732 A.19 FGH36KA350LLF 434393 A.26 FGL436SA500NNF 434758 A.27 FGNRD/5 436506 A.31
FETTG43K0250 432735 A.19 FGH36KA400LLF 436151 A.26 FGL436VA400LLF 435077 A.26 FGNRDV/5 436507 A.31
FETTG45J0100 433326 A.18 FGH36KA400NLF 436152 A.28 FGL436VA630NNF 435091 A.28 FGNRE 434735 A.31
FETTG45J0125 432741 A.18 FGH36KA500NNF 434606 A.28 FGL456SA250LKF 434244 A.25 FGNRF/5 436509 A.31
FETTG45J0160 432744 A.18 FGH36KA630NNF 434028 A.28 FGL456SA400LLF 434462 A.25 FGNRFV/5 436510 A.31
FETTG45K0160 432753 A.19 FGH36SA250LKF 434233 A.25 FGL456SA400NLF 431425 A.27 FGNRW 433892 A.31
FETTG45K0200 432756 A.19 FGH36SA400LLF 434399 A.25 FGL456SA500NNF 434764 A.27 FGNRX/5 436512 A.45
FETTG45K0250 432759 A.19 FGH36SA400NLF 431091 A.27 FGL456VA400LLF 435095 A.26 FGNRY/5 436513 A.31
FETTG4J0100 433332 A.18 FGH36SA500NNF 434612 A.27 FGL456VA630NNF 435122 A.28 FGNRYV/5 436514 A.31
FETTG4J0125 432774 A.18 FGH36VA400LLF 434953 A.26 FGL46AA250LKF 434245 A.25 FGNRZ/5 436515 A.31
X.4
Record Plus
Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page Cat. no. Ref. no. Page
FGNRZV/5 436516 A.31 FGRS43LL0400 434516 A.29 FKH46NS800PPF 435375 A.35 FNECE6 436449 A.47
FGQDB3H 430856 A.31 FGRS43NL0400 433241 A.27 FKL36NE100SQF 435545 A.36 FNEMF3 435686 A.38
FGQDB3M 430860 A.31 FGRS43NN0500 434521 A.27 FKL36NE125SSF 435546 A.36 FNEMF6 435689 A.38
FGQDB4H 430865 A.31 FGRS45LK0250 434311 A.25 FKL36NE800PPF 435390 A.35 FNEMFD 435683 A.38
FGQDB4M 430869 A.31 FGRS45LL0400 434525 A.25 FKL36NM125SF 435561 A.36 FNEMFF 435680 A.38
FGRJ3LK0160 434337 A.25 FGRS45LL0400 434525 A.29 FKL36NM800PF 435539 A.35 FNEMFJ 436457 A.38
FGRJ3LK0250 434341 A.25 FGRS45NL0400 433247 A.27 FKL36NT100SF 435555 A.36 FNEMFN 436456 A.38
FGRJ3LL0250 435343 A.25 FGRS45NN0500 434530 A.27 FKL36NT125SF 435557 A.36 FNFE 435713 A.40
FGRJ3LL0400 433151 A.25 FGRS4LK0250 434315 A.25 FKL36NT630PF 435480 A.35 FNFH 435714 A.40
FGRJ3NL0250 433148 A.27 FGRS4LL0400 434537 A.25 FKL36NT800PF 435372 A.35 FNFHW 436590 A.40
FGRJ3NL0400 435182 A.27 FGRS4LL0400 434537 A.29 FKL436NM125SF 435573 A.36 FNFT 435715 A.40
FGRJ3NN0400 433154 A.27 FGRS4NL0400 433253 A.27 FKL436NM800PF 435543 A.35 FNFW 435578 A.39
By catalogue number
FGRJ3NN0630 433157 A.27 FGRS4NN0500 434542 A.27 FKL436NT100SF 435567 A.36 FNGS0800 433419 A.40
FGRJ43LK0160 434345 A.25 FGTAA3L0250 434319 A.29 FKL436NT125SF 435569 A.36 FNGS1000 433421 A.40
FGRJ43LK0250 434349 A.25 FGTAA3L0400 431718 A.29 FKL436NT630PF 435534 A.35 FNGS1250 435709 A.40
FGRJ43LL0250 435356 A.25 FGTAA3N0400 431721 A.30 FKL436NT800PF 435535 A.35 FNGS1600 436471 A.40
FGRJ43LL0400 433163 A.25 FGTAA3N0500 434893 A.30 FKL46NE100SQF 435547 A.36 FNJL3 435716 A.40
FGRJ43NL0250 433160 A.27 FGTAA3N0630 431736 A.30 FKL46NE125SSF 435549 A.36 FNJL4 435719 A.40
FGRJ43NL0400 435188 A.27 FGTAA4L0250 434323 A.29 FKL46NE800PPF 435282 A.35 FNJP 435722 A.40
FGRJ43NN0400 433166 A.27 FGTAA4L0400 431742 A.29 FKN36NE100SQF 435396 A.36 FNNRC 435726 A.46
FGRJ43NN0630 433169 A.27 FGTAA4N0400 431745 A.30 FKN36NE125SSF 435384 A.36 FNNRC/5 436517 A.38
FGRJ45LK0160 434353 A.25 FGTAA4N0500 434899 A.30 FKN36NE160TTF 435387 A.37 FNNRCV/5 436518 A.38
FGRJ45LK0250 434357 A.25 FGTAA4N0630 431748 A.30 FKN36NE800PPF 435393 A.35 FNNRD/5 436519 A.38
FGRJ45LL0250 435367 A.25 FGTCA1327 435107 A.32 FKN36NG100SQF 435414 A.36 FNNRDV/5 436520 A.38
FGRJ45LL0400 433175 A.25 FGTCA1427 435116 A.32 FKN36NG125SSF 435402 A.36 FNNRE 435738 A.38
FGRJ45LL0400 433175 A.29 FGTCA230B 433412 A.32 FKN36NG160TTF 435405 A.37 FNNRF/5 436522 A.38
FGRJ45NL0250 433172 A.27 FGTCA240B 433413 A.32 FKN36NG800PPF 435411 A.35 FNNRFV/5 436524 A.38
FGRJ45NL0400 435194 A.27 FGTKA3L0250 434201 A.29 FKN36NM125SF 435558 A.36 FNNRW 435745 A.38
FGRJ45NN0400 433178 A.27 FGTKA3L0350 434902 A.29 FKN36NM800PF 435537 A.35 FNNRX/5 436526 A.45
FGRJ45NN0630 433181 A.27 FGTKA3L0400 434202 A.29 FKN36NS100SQF 435432 A.36 FNNRY/5 436527 A.38
FGRJ45NN0630 433181 A.30 FGTKA3N0400 434203 A.30 FKN36NS125SSF 435420 A.36 FNNRYV/5 436528 A.38
FGRJ4LK0160 434361 A.25 FGTKA3N0500 434905 A.30 FKN36NS160TTF 435423 A.37 FNNRZ/5 436530 A.38
FGRJ4LK0250 434365 A.25 FGTKA3N0630 434204 A.30 FKN36NS800PPF 435429 A.35 FNNRZV/5 436531 A.38
FGRJ4LL0250 435397 A.25 FGTKA4L0250 434205 A.29 FKN36NT100SF 435550 A.36 FNPFM 435758 A.39
FGRJ4LL0400 433187 A.25 FGTKA4L0350 434908 A.29 FKN36NT125SF 435551 A.36 FNS11L 435760 A.39
FGRJ4LL0400 433187 A.29 FGTKA4L0400 434261 A.29 FKN36NT630PF 435444 A.35 FNS11R 436401 A.38
FGRJ4NL0250 433184 A.27 FGTKA4N0400 434263 A.30 FKN36NT800PF 435336 A.35 FNSHT8 435692 A.38
FGRJ4NL0400 435200 A.27 FGTKA4N0500 434911 A.30 FKN436NM125SF 435570 A.36 FNSHTD 435693 A.38
FGRJ4NN0400
FGRJ4NN0630
433190
433193
A.27
A.27
FGTKA4N0630
FGUA3
434265
432908
A.30
A.33
FKN436NM800PF
FKN436NT100SF
435541
435562
A.35
A.36
FNSHTF
FNSHTJ
435694
435695
A.38
A.38
A
FGRJ4NN0630 433193 A.30 FGUA4 432909 A.33 FKN436NT125SF 435563 A.36 FNSHTN 435696 A.38
FGRL3LK0160 436162 A.26 FGUT 433541 A.33 FKN436NT630PF 435408 A.35 FNT 435704 A.40
FGRL3LK0250 434098 A.26 FGWS3 432910 A.32 FKN436NT800PF 435300 A.35 FNTCA3327 436316 A.39
FGRL3LL0250
FGRL3LL0350
435399
435400
A.26
A.26
FGWS4
FGY306D400LF
432913
431659
A.32
A.26
FKN46NE125SSF
FKN46NE160TTF
435438
435441
A.36
A.37
FNTCA3427
FNTCA4327
436651
433438
A.39
A.39
B
FGRL3LL0400 434099 A.26 FGY306D630NF 431665 A.28 FKN46NE800PPF 435447 A.35 FNTCA4427 433439 A.39
FGRL3NL0250 435206 A.28 FGY406D400LF 431671 A.26 FKN46NG100SQF 435468 A.36 FNUA3 435762 A.40
FGRL3NL0400 435212 A.28 FGY406D630NF 431687 A.28 FKN46NG125SSF 435456 A.36 FNUA4 435763 A.40
FGRL3NN0400
FGRL3NN0500
434471
434473
A.28
A.28
FK...
FKEO4J 437011 A.47
FKN46NG160TTF
FKN46NG800PPF
435459
435465
A.37
A.35
FNUT
FNUVD6
435764
435697
A.40
A.38
C
FGRL3NN0630 434100 A.28 FKEO4N 437014 A.47 FKN46NS100SQF 435486 A.36 FNUVR1 435698 A.38
FGRL43LK0160 434101 A.26 FKEO5J 437015 A.47 FKN46NS125SSF 435474 A.36 FNUVR6 435699 A.38
FGRL43LK0250 436177 A.26 FKEO5N 437017 A.47 FKN46NS160TTF 435477 A.37 FNUVR8 435700 A.38
FGRL43LL0250
FGRL43LL0350
435410
435412
A.26
A.26
FKH36NE100SQF
FKH36NE125SSF
435288
435276
A.36
A.36
FKN46NS800PPF
FKY306DN100SF
435483
435381
A.35
A.37
FNUVRD
FNUVRF
435701
435702
A.38
A.38
D
FGRL43LL0400 436178 A.26 FKH36NE160TTF 435279 A.37 FKY306DN125SF 435489 A.37 FNUVRJ 437018 A.45
FGRL43NL0250 435218 A.28 FKH36NE800PPF 435285 A.35 FKY306DN160TF 435492 A.37 FNWS3AP 433436 A.39
FGRL43NL0400 435224 A.28 FKH36NG100SQF 435306 A.36 FKY306DN800PF 435495 A.37 FNWS3AT 435757 A.39
FGRL43NN0400
FGRL43NN0500
435419
435427
A.28
A.28
FKH36NG125SSF
FKH36NG160TTF
435294
435297
A.36
A.37
FKY406DN100SF
FKY406DN125SF
435273
435498
A.37
A.37
FNWS3WP
FNWS3WT
433434
436482
A.39
A.39
E
FGRL43NN0630 436179 A.28 FKH36NG800PPF 435303 A.35 FKY406DN160TF 435501 A.37 FNWS4AP 433440 A.39
FGRL45LK0160 434105 A.26 FKH36NM125SF 435559 A.36 FKY406DN800PF 435504 A.37 FNWS4AT 435759 A.39
FGRL45LK0250 434106 A.26 FKH36NM800PF 435538 A.35 FN... FNWS4WP 436481 A.39
FGRL45LL0250
FGRL45LL0350
434495
435266
A.26
A.26
FKH36NS100SQF
FKH36NS125SSF
435324
435312
A.36
A.36
FN1BPE
FN1BRE
435678
435679
A.38
A.38
FNWS4WT
RD...
433442 A.39 F
FGRL45LL0400 434107 A.26 FKH36NS160TTF 435315 A.37 FN1BRW1 435575 A.39 RD1D 110 872225 A.39
FGRL45NL0250 435230 A.28 FKH36NS800PPF 435321 A.35 FN1BRW2 435577 A.39 RD1D 220 872224 A.39
FGRL45NL0400 435236 A.28 FKH36NT100SF 435553 A.36 FN1BRY1 433415 A.39 RD1D 380 872226 A.39
FGRL45NN0400
FGRL45NN0500
434497
435272
A.28
A.28
FKH36NT125SF
FKH36NT630PF
435554
435426
A.36
A.35
FN1BRY2
FN1I2F
435574
433416
A.39
A.46
RD5 110
RD5 220
704175
704169
A.39
A.39
G
FGRL45NN0630 436180 A.28 FKH36NT800PF 435318 A.35 FN1I4F 437016 A.46 RD5 380 704176 A.39
FGRL4LK0160 434109 A.26 FKH436NM125SF 435571 A.36 FN1PR 433417 A.40 RD6 110 704178 A.39
FGRL4LK0250 436181 A.26 FKH436NM800PF 435542 A.35 FNBA11R 435761 A.38 RD6 220 704177 A.39
FGRL4LL0250
FGRL4LL0350
435433
435302
A.26
A.26
FKH436NT100SF
FKH436NT125SF
435565
435566
A.36
A.36
FNBES3P
FNBES3R
435706
433420
A.39
A.39
RD6 380
RDFR
704179
872227
A.39
A.49
X
FGRL4LL0400 434111 A.26 FKH436NT630PF 435462 A.35 FNBES4P 435707 A.39 TT...
FGRL4NL0250 435254 A.28 FKH436NT800PF 435354 A.35 FNBES4R 433422 A.39 TT 210 560096 A.39
FGRL4NL0400 435260 A.28 FKH46NE100SQF 435342 A.36 FNBRC3 433423 A.39 TT 35 560091 A.39
FGRL4NN0400 434501 A.28 FKH46NE125SSF 435330 A.36 FNBRC4 433425 A.39 TT 60 560092 A.39
FGRL4NN0500 435309 A.28 FKH46NE160TTF 435333 A.37 FNBRCS3 433426 A.39 TT 80 560093 A.39
FGRL4NN0630 434112 A.28 FKH46NE800PPF 435339 A.35 FNBRCS4 433427 A.39 TT110 560094 A.39
FGRS3LK0250 434303 A.25 FKH46NG100SQF 435360 A.36 FNBSS3P 435708 A.39 TT160 560095 A.39
FGRS3LL0400 435435 A.25 FKH46NG125SSF 435348 A.36 FNBSS3R 435710 A.39 TTD 22 560090 A.39
FGRS3LL0400 435435 A.29 FKH46NG160TTF 435351 A.37 FNBSS4P 435711 A.39 TTO 110 560097 A.39
FGRS3NL0400 433235 A.27 FKH46NG800PPF 435357 A.35 FNBSS4R 435712 A.39 TTO 210 560098 A.39
FGRS3NN0500 434512 A.27 FKH46NS100SQF 435378 A.36 FNECA3 436452 A.47
FGRS43LK0250 434307 A.25 FKH46NS125SSF 435366 A.36 FNECA6 436451 A.47
FGRS43LL0400 434516 A.25 FKH46NS160TTF 435369 A.37 FNECE3 436450 A.47
X.5
Record Plus
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Numerical index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X.6
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
430... 430108 FDN36TG032ED A.6 430506 FA1BR5 A.8 430883 FDBEA3 A.9
430015 FDH36MC007ED A.7 430109 FDN36TG040ED A.6 430507 FA1BR6 A.8 430884 FDBEA4 A.9
430016 FDH36MC012ED A.7 430110 FDN36TG050ED A.6 430518 FDL36TD080GD A.6 430885 FDBEH3 A.9
430017 FDH36MC020ED A.7 430111 FDN36TG063ED A.6 430521 FDL36TD100GD A.6 430886 FDBEH4 A.9
430018 FDH36MC030ED A.7 430112 FDN436MC007ED A.7 430524 FDL36TD125GD A.6 430887 FDBES3 A.9
430019 FDH36MC050ED A.7 430113 FDN436MC012ED A.7 430537 FDL436MC080GD A.7 430888 FDBES4 A.9
430020 FDH36TD016ED A.6 430114 FDN436MC020ED A.7 430540 FDL436MC100GD A.7 430889 FDBRC3 A.9
430021 FDH36TD020ED A.6 430115 FDN436MC030ED A.7 430544 FGFE A.33 430890 FDBRC4 A.9
430022 FDH36TD025ED A.6 430116 FDN436MC050ED A.7 430545 FGFH A.33 430891 FDBSS3 A.9
430023 FDH36TD032ED A.6 430117 FDN436TD016ED A.6 430557 FDL436TD080GD A.6 430892 FDBSS4 A.9
430024 FDH36TD040ED A.6 430118 FDN436TD020ED A.6 430560 FDL436TD100GD A.6 430893 FDDDF3 A.9
430025 FDH36TD050ED A.6 430119 FDN436TD025ED A.6 430563 FDL436TD125GD A.6 430896 FDDDF4 A.9
By reference number
430026 FDH36TD063ED A.6 430120 FDN436TD032ED A.6 430568 FDL456TD080GD A.6 430899 FDDFF3 A.9
430027 FDH36TG025ED A.6 430121 FDN436TD040ED A.6 430571 FDL456TD100GD A.6 430902 FDDFF4 A.9
430028 FDH36TG032ED A.6 430122 FDN436TD050ED A.6 430574 FDL456TD125GD A.6 430905 FDDMP3 A.9
430029 FDH36TG040ED A.6 430123 FDN436TD063ED A.6 430591 FDL46TD080GD A.6 430908 FDDMP4 A.9
430030 FDH36TG050ED A.6 430124 FDN436TG025ED A.6 430594 FDL46TD100GD A.6 430920 FDEMF8 A.8
430031 FDH36TG063ED A.6 430125 FDN436TG032ED A.6 430597 FDL46TD125GD A.6 430926 FDEMFD A.8
430032 FDH436MC007ED A.7 430126 FDN436TG040ED A.6 430610 FDN36MC080GD A.7 430929 FDEMFF A.8
430033 FDH436MC012ED A.7 430127 FDN436TG050ED A.6 430613 FDN36MC100GD A.7 430932 FDEMFH A.8
430034 FDH436MC020ED A.7 430128 FDN436TG063ED A.6 430630 FDN36TD080GD A.6 430935 FDEMFJ A.8
430035 FDH436MC030ED A.7 430129 FDN456TD063ED A.6 430633 FDN36TD100GD A.6 430938 FDEMFN A.8
430036 FDH436MC050ED A.7 430130 FDN456TG063ED A.6 430636 FDN36TD125GD A.6 430941 FDFF3 A.10
430037 FDH436TD016ED A.6 430131 FDN46TD016ED A.6 430649 FDN36TG080GD A.6 430942 FDFF4 A.10
430038 FDH436TD020ED A.6 430132 FDN46TD020ED A.6 430652 FDN36TG100GD A.6 430943 FEFE A.22
430039 FDH436TD025ED A.6 430133 FDN46TD025ED A.6 430655 FDN36TG125GD A.6 430944 FGDDF3 A.32
430040 FDH436TD032ED A.6 430134 FDN46TD032ED A.6 430668 FDN436MC080GD A.7 430945 FDJB A.9
430041 FDH436TD040ED A.6 430135 FDN46TD040ED A.6 430671 FDN436MC100GD A.7 430951 FDJL3 A.9
430042 FDH436TD050ED A.6 430136 FDN46TD050ED A.6 430688 FDN436TD080GD A.6 430954 FDJL4 A.9
430043 FDH436TD063ED A.6 430137 FDN46TD063ED A.6 430691 FDN436TD100GD A.6 430957 FDJP A.9
430044 FDH436TG025ED A.6 430138 FDN46TG025ED A.6 430694 FDN436TD125GD A.6 430960 FDJS3 A.9
430045 FDH436TG032ED A.6 430139 FDN46TG032ED A.6 430707 FDN436TG080GD A.6 430963 FDJS4 A.9
430046 FDH436TG040ED A.6 430140 FDN46TG040ED A.6 430710 FDN436TG100GD A.6 430966 FDKD3 A.10
430047 FDH436TG050ED A.6 430141 FDN46TG050ED A.6 430713 FDN436TG125GD A.6 430967 FDKD4 A.10
430048 FDH436TG063ED A.6 430142 FDN46TG063ED A.6 430718 FDN456TD080GD A.6 430968 FDNFT A.8
430049 FDH456TD063ED A.6 430143 FDN66TD016ED A.5 430721 FDN456TD100GD A.6 430969 FEBAT01 A.20
430050 FDH456TG063ED A.6 430144 FDN66TD020ED A.5 430724 FDN456TD125GD A.6 430970 FEBAT10 A.20
430051 FDH46TD016ED A.6 430145 FDN66TD025ED A.5 430729 FDN456TG080GD A.6 430971 FDNR4 A.8
430052
430053
FDH46TD020ED
FDH46TD025ED
A.6
A.6
430146
430147
FDN66TD032ED
FDN66TD040ED
A.5
A.5
430732
430735
FDN456TG100GD
FDN456TG125GD
A.6
A.6
430986
430987
FDNRE
FEDFQ3
A.8
A.21
A
430054 FDH46TD032ED A.6 430148 FDN66TD050ED A.5 430752 FDN46TD080GD A.6 431...
430055 FDH46TD040ED A.6 430149 FDN66TD063ED A.5 430755 FDN46TD100GD A.6 431007 FEH36TD100JF A.13
430056 FDH46TD050ED A.6 430150 FDY306D063ED A.7 430758 FDN46TD125GD A.6 431013 FDQDS3M A.8
430057
430058
FDH46TD063ED
FDH46TG025ED
A.6
A.6
430151
430161
FDY406D063ED
FDS35TD016ED
A.7
A.5
430771
430774
FDN46TG080GD
FDN46TG100GD
A.6
A.6
431021
431022
FEH36TD125JF
FDQDS4M
A.13
A.8
B
430059 FDH46TG032ED A.6 430163 FDS35TD020ED A.5 430777 FDN46TG125GD A.6 431025 FDUA3 A.10
430060 FDH46TG040ED A.6 430165 FDS35TD025ED A.5 430794 FDN66TD080GD A.5 431026 FDUA4 A.10
430061 FDH46TG050ED A.6 430167 FDS35TD032ED A.5 430797 FDN66TD100GD A.5 431032 FGH36AA400LLF A.25
430062
430065
FDH46TG063ED
FDL36MC020ED
A.6
A.7
430169
430178
FDS35TD040ED
FDS35TD050ED
A.5
A.5
430800
430805
FDN66TD125GD
FDY306D160GD
A.5
A.7
431038
431050
FGH36AA630NNF
FGH306F400LF
A.27
A.29
C
430066 FDL36MC030ED A.7 430224 FDS45TD016ED A.5 430810 FDY406D160GD A.7 431058 FEV36TA200KF A.16
430067 FDL36MC050ED A.7 430226 FDS45TD020ED A.5 430813 FA1BPH A.8 431061 FEV36TA250KF A.16
430068 FA1BRH A.8 430228 FDS45TD025ED A.5 430815 FABAT01 A.8 431064 FGDDF4 A.32
430069
430070
FDJK
FDL36TD025ED
A.9
A.6
430230
430232
FDS45TD032ED
FDS45TD040ED
A.5
A.5
430818
430821
FABAT10
FAC
A.8
A.10
431067
431073
FGH306F400NF
FGH306F630NF
A.30
A.30
D
430071 FDL36TD032ED A.6 430241 FDS45TD050ED A.5 430823 FAPF8 A.9 431082 FEV46TA125KF A.16
430072 FDL36TD040ED A.6 430318 FDH36MC080GD A.7 430824 FAPFM A.9 431091 FGH36SA400NLF A.27
430073 FDL36TD050ED A.6 430321 FDH36MC100GD A.7 430825 FAPIP A.9 431094 FEV46TA200KF A.16
430074
430077
FDL36TD063ED
FDL436MC020ED
A.6
A.7
430338
430341
FDH36TD080GD
FDH36TD100GD
A.6
A.6
430826
430827
FAPM8
FAPPS
A.9
A.9
431097
431106
FEV46TA250KF
FGH46AA400LLF
A.16
A.25
E
430078 FDL436MC030ED A.7 430344 FDH36TD125GD A.6 430828 FAS01L A.8 431112 FEH36AA125JGF A.14
430079 FDL436MC050ED A.7 430357 FDH36TG080GD A.6 430829 FDFH A.10 431116 FEH36AA125KGF A.17
430082 FDL436TD025ED A.6 430360 FDH36TG100GD A.6 430830 FDUF3 A.9 431117 FEH36AA160JJF A.14
430083
430084
FDL436TD032ED
FDL436TD040ED
A.6
A.6
430363
430376
FDH36TG125GD
FDH436MC080GD
A.6
A.7
430831
430832
FAS01R
FDUF4
A.8
A.9
431120
431123
FEH36AA160KJF
FEH36AA250KKF
A.17
A.17
F
430085 FDL436TD050ED A.6 430379 FDH436MC100GD A.7 430834 FAS10L A.8 431126 FEH306F160JF A.18
430086 FDL436TD063ED A.6 430396 FDH436TD080GD A.6 430837 FAS10R A.8 431129 FEH306F250KF A.19
430087 FDL456TD063ED A.6 430399 FDH436TD100GD A.6 430840 FASHTB A.8 431132 FGH46AA630NNF A.27
430088
430089
FA1BR1
FA1BR2
A.8
A.8
430402
430415
FDH436TD125GD
FDH436TG080GD
A.6
A.6
430843
430846
FASHTD
FASHTF
A.8
A.8
431138
431141
FEH36SA125JGF
FEH36SA160JJF
A.15
A.15
G
430090 FDL46TD025ED A.6 430418 FDH436TG100GD A.6 430849 FASHTJ A.8 431144 FEH36SA160KJF A.17
430091 FDL46TD032ED A.6 430421 FDH436TG125GD A.6 430852 FASHTN A.8 431147 FEH36SA250KKF A.17
430092 FDL46TD040ED A.6 430426 FDH456TD080GD A.6 430855 FASHTU A.8 431150 FGH406F400LF A.29
430093
430094
FDL46TD050ED
FDL46TD063ED
A.6
A.6
430429
430432
FDH456TD100GD
FDH456TD125GD
A.6
A.6
430856
430858
FGQDB3H
FAUVDN
A.31
A.8
431153
431156
FGH406F400NF
FGH406F630NF
A.30
A.30
X
430095 FDN36MC007ED A.7 430437 FDH456TG080GD A.6 430860 FGQDB3M A.31 431165 FEH36TA080JF A.13
430096 FDN36MC012ED A.7 430440 FDH456TG100GD A.6 430861 FAUVRD A.8 431168 FGH436SA400NLF A.27
430097 FDN36MC020ED A.7 430443 FDH456TG125GD A.6 430864 FAUVRF A.8 431171 FEH36TA100JF A.13
430098 FDN36MC030ED A.7 430460 FDH46TD080GD A.6 430865 FGQDB4H A.31 431177 FEH36TA125JF A.13
430099 FDN36MC050ED A.7 430463 FDH46TD100GD A.6 430867 FAUVRJ A.8 431183 FEH36TA160JF A.13
430100 FDN36TD016ED A.6 430466 FDH46TD125GD A.6 430869 FGQDB4M A.31 431198 FGH456SA400NLF A.27
430101 FDN36TD020ED A.6 430479 FDH46TG080GD A.6 430870 FAUVRN A.8 431201 FEH46AA125JGF A.14
430102 FDN36TD025ED A.6 430482 FDH46TG100GD A.6 430873 FAUVRU A.8 431204 FEH46AA160JJF A.14
430103 FDN36TD032ED A.6 430485 FDH46TG125GD A.6 430876 FD1BPE A.8 431207 FEH46AA160KJF A.17
430104 FDN36TD040ED A.6 430498 FDL36MC080GD A.7 430877 FD1BRE A.8 431210 FEH46AA250KKF A.17
430105 FDN36TD050ED A.6 430501 FDL36MC100GD A.7 430878 FD1PF A.10 431213 FEH406F160JF A.18
430106 FDN36TD063ED A.6 430504 FA1BR3 A.8 430879 FD1PR A.10 431216 FEH406F250KF A.19
430107 FDN36TG025ED A.6 430505 FA1BR4 A.8 430880 FDBAM11 A.8 431225 FEH436SA125JGF A.15
X.7
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
431228 FEH436SA160JJF A.15 431596 FGN436SA400NLF A.27 431986 FGDFF4 A.32 432207 FERJ3K0250 A.17
431231 FEH436SA160KJF A.17 431599 FEL456TA100JF A.13 431988 FEY306D160JF A.15 432209 FEH436TD125KF A.16
431234 FEH436SA250KKF A.17 431605 FEL456TA125JF A.13 431991 FEY306D250KF A.17 432210 FERJ43B0016 A.14
431240 FGH46SA400NLF A.27 431611 FEL456TA160JF A.13 431994 FEY406D160JF A.15 432213 FERJ43B0025 A.14
431246 FGL36AA400LLF A.25 431626 FGN456SA400NLF A.27 431997 FEY406D250KF A.17 432214 FEH436TD160JF A.13
431249 FGL36AA630NNF A.27 431629 FEL46SA125JGF A.15 432... 432216 FERJ43E0040 A.14
431252 FEH436TA080JF A.13 431632 FEL46SA160JJF A.15 432000 FABAM01 A.20 432218 FEH436TD160KF A.16
431258 FEH436TA100JF A.13 431635 FEL46SA160KJF A.17 432003 FABAM10 A.20 432219 FERJ43E0063 A.14
431261 FGL306F400LF A.29 431638 FEL46SA250KKF A.17 432004 FETAA3K0125 A.19 432222 FERJ43G0080 A.14
431264 FEH436TA125JF A.13 431650 FGN46SA400NLF A.27 432007 FETAA4K0125 A.19 432223 FEH436TD200KF A.16
431267 FGL306F400NF A.30 431656 FEL46TA080JF A.13 432010 FDFE A.10 432225 FERJ43J0100 A.14
431270 FEH436TA160JF A.13 431659 FGY306D400LF A.26 432011 FE1BPE A.20 432227 FEH436TD250KF A.16
431282 FGL306F630NF A.30 431662 FEL46TA100JF A.13 432012 FE1BRE A.20 432228 FERJ43G0125 A.14
431285 FEH456SA125JGF A.15 431665 FGY306D630NF A.28 432017 FE1PF A.22 432231 FERJ43J0160 A.14
431288 FEH456SA160JJF A.15 431668 FEL46TA125JF A.13 432018 FEBE43 A.21 432240 FERJ43K0160 A.17
431291 FEH456SA160KJF A.17 431671 FGY406D400LF A.26 432019 FEBE44 A.21 432242 FEH456TD100JF A.13
431294 FEH456SA250KKF A.17 431674 FEL46TA160JF A.13 432020 FEBE93 A.21 432243 FERJ43K0250 A.17
Numerical index
431300 FEH456TA080JF A.13 431686 FGBEA3 A.32 432021 FEBE94 A.21 432249 FERJ45E0063 A.14
431306 FEH456TA100JF A.13 431687 FGY406D630NF A.28 432022 FEBEA3 A.21 432250 FEH456TD125JF A.13
431309 FGL36SA400NLF A.27 431690 FGBEA4 A.32 432023 FEBEA4 A.21 432252 FERJ45G0080 A.14
431312 FEH456TA125JF A.13 431691 FGBEH3 A.32 432024 FEBEH3 A.21 432254 FEH456TD125KF A.16
431318 FEH456TA160JF A.13 431695 FGBEH4 A.32 432025 FEBEH4 A.21 432255 FERJ45J0100 A.14
431330 FGL46AA400LLF A.25 431696 FGBES3 A.32 432026 FEBES3 A.21 432258 FERJ45G0125 A.14
431333 FGL46AA630NNF A.27 431697 FGBES4 A.32 432027 FEBES4 A.21 432259 FEH456TD160JF A.13
431336 FEH46SA125JGF A.15 431698 FEN36AA125JGF A.14 432028 FEBRC3 A.21 432261 FERJ45J0160 A.14
431339 FEH46SA160JJF A.15 431701 FGBRC3 A.32 432029 FEBRC4 A.21 432263 FEH456TD160KF A.16
431342 FEH46SA160KJF A.17 431702 FGBRC4 A.32 432032 FEBSS3 A.21 432266 FEH456TD200KF A.16
431345 FEH46SA250KKF A.17 431703 FEN36AA160JJF A.14 432033 FEBSS4 A.21 432269 FEH456TD250KF A.16
431351 FGL406F400LF A.29 431706 FEN36AA160KJF A.17 432034 FEDDF3 A.21 432270 FERJ45K0160 A.17
431354 FGL406F400NF A.30 431709 FEN36AA250KKF A.17 432037 FEDDF4 A.21 432273 FERJ45K0250 A.17
431357 FGL406F630NF A.30 431712 FEN306F160JF A.18 432040 FEDFF3 A.21 432276 FERJ4B0016 A.14
431363 FEH46TA080JF A.13 431715 FEN306F250KF A.19 432043 FEDFF4 A.21 432279 FERJ4B0025 A.14
431369 FEH46TA100JF A.13 431718 FGTAA3L0400 A.29 432046 FEDMP3 A.21 432282 FERJ4E0040 A.14
431372 FGL436SA400NLF A.27 431721 FGTAA3N0400 A.30 432049 FEDMP4 A.21 432285 FERJ4E0063 A.14
431375 FEH46TA125JF A.13 431724 FEN36SA125JGF A.15 432052 FEEMFD A.20 432287 FEH46TD100JF A.13
431381 FEH46TA160JF A.13 431727 FEN36SA160JJF A.15 432055 FEEMFF A.20 432288 FERJ4G0080 A.14
431393 FEH36TD125KF A.16 431730 FEN36SA160KJF A.17 432058 FEEMFH A.20 432291 FERJ4J0100 A.14
431402 FAT A.22 431733 FEN36SA250KKF A.17 432061 FEEMFJ A.20 432294 FERJ4G0125 A.14
A 431403
431404
FG1BPE
FG1BRE
A.31
A.31
431736
431742
FGTAA3N0630
FGTAA4L0400
A.30
A.29
432064
432067
FEEMFN
FEFF3
A.20
A.22
432296
432297
FEH46TD125JF
FERJ4J0160
A.13
A.14
431405 FEL36AA125JGF A.14 431745 FGTAA4N0400 A.30 432068 FEFF4 A.22 432300 FEH46TD125KF A.16
431408 FG1PF A.33 431748 FGTAA4N0630 A.30 432071 FEFT A.22 432303 FEH46TD160JF A.13
431409 FG1PR A.33 431751 FEN36TA080JF A.13 432073 FEJB A.22 432306 FERJ4K0160 A.17
B 431410
431413
FEL36AA160JJF
FEL36AA160KJF
A.14
A.17
431757
431763
FEN36TA100JF
FEN36TA125JF
A.13
A.13
432076
432079
FEH36TD200KF
FEJL3
A.16
A.22
432307
432309
FEH46TD160KF
FERJ4K0250
A.16
A.17
431416 FEL36AA250KKF A.17 431769 FEN36TA160JF A.13 432082 FEJL4 A.22 432311 FEH46TD200KF A.16
431419 FEL306F160JF A.18 431787 FEN46AA125JGF A.14 432085 FEJP A.22 432312 FERS3B0025 A.15
431422 FEL306F250KF A.19 431790 FEN46AA160JJF A.14 432088 FEJS3 A.22 432315 FERS3E0063 A.15
C 431425
431431
FGL456SA400NLF
FEL36SA125JGF
A.27
A.15
431793
431796
FEN46AA160KJF
FEN46AA250KKF
A.17
A.17
432091
432096
FEJS4
FEH36TD250KF
A.22
A.16
432316
432318
FEH46TD250KF
FERS3G0125
A.16
A.15
431434 FEL36SA160JJF A.15 431799 FEN406F160JF A.18 432099 FENR4 A.20 432321 FERS3J0160 A.15
431437 FEL36SA160KJF A.17 431802 FEN406F250KF A.19 432102 FENRC A.46 432327 FERS3K0250 A.17
431440 FEL36SA250KKF A.17 431811 FEN436SA125JGF A.15 432120 FENRW A.20 432330 FERS43B0025 A.15
D 431449
431455
FGL46SA400NLF
FGN36AA400LLF
A.27
A.25
431814
431817
FEN436SA160JJF
FEN436SA160KJF
A.15
A.17
432132
432135
FEQDB3HJ
FEQDB3HK
A.20
A.20
432332
432333
FEL36TD100JF
FERS43E0063
A.13
A.15
431458 FEL36TA080JF A.13 431820 FEN436SA250KKF A.17 432138 FEQDB3MJ A.20 432336 FERS43G0125 A.15
431461 FGN36AA630NNF A.27 431824 FEH46AA125KGF A.17 432141 FEQDB3MK A.20 432339 FERS43J0160 A.15
431464 FEL36TA100JF A.13 431836 FEL36AA125KGF A.17 432144 FEQDB4HJ A.20 432341 FEL36TD125JF A.13
E 431470
431473
FEL36TA125JF
FGN306F400LF
A.13
A.29
431838
431842
FEN436TA080JF
FEDFQ4
A.13
A.21
432147
432150
FEQDB4HK
FEQDB4MJ
A.20
A.20
432344
432345
FEL36TD125KF
FERS43K0250
A.16
A.17
431476 FEL36TA160JF A.13 431844 FEN436TA100JF A.13 432153 FEQDB4MK A.20 432348 FERS45E0063 A.15
431488 FGN306F400NF A.30 431850 FEN436TA125JF A.13 432156 FETCA1316 A.21 432349 FEL36TD160JF A.13
431491 FGN306F630NF A.30 431856 FEN436TA160JF A.13 432157 FETCA1320 A.21 432351 FERS45G0125 A.15
F 431494
431497
FEL46AA125JGF
FEL46AA160JJF
A.14
A.14
431870
431871
FGGS0250
FEN456SA125JGF
A.33
A.15
432158
432159
FETCA1416
FETCA1420
A.21
A.21
432353
432354
FEL36TD160KF
FERS45J0160
A.16
A.15
431500 FEL46AA160KJF A.17 431874 FEN456SA160JJF A.15 432160 FETCA1323 A.21 432357 FEL36TD200KF A.16
431503 FEL46AA250KKF A.17 431877 FEN456SA160KJF A.17 432161 FETCA1423 A.21 432360 FERS45K0250 A.17
431506 FEL406F160JF A.18 431880 FEN456SA250KKF A.17 432162 FEUA3 A.22 432361 FEL36TD250KF A.16
G 431509
431518
FEL406F250KF
FEL436SA125JGF
A.19
A.15
431886
431890
FEN456TA080JF
FEL46AA125KGF
A.13
A.17
432163
432168
FEUA4
FEWS3
A.22
A.21
432363
432366
FERS4B0025
FERS4E0063
A.15
A.15
431521 FEL436SA160JJF A.15 431892 FEN456TA100JF A.13 432171 FEWS4 A.21 432369 FERS4G0125 A.15
431524 FEL436SA160KJF A.17 431898 FEN456TA125JF A.13 432174 FERJ3B0016 A.14 432372 FERS4J0160 A.15
431527 FEL436SA250KKF A.17 431904 FEN456TA160JF A.13 432177 FERJ3B0025 A.14 432374 FEL436TD100JF A.13
X 431530
431536
FGN36SA400NLF
FGN46AA400LLF
A.27
A.25
431920
431922
FEN36AA125KGF
FEN46SA125JGF
A.17
A.15
432180
432183
FERJ3E0040
FERJ3E0063
A.14
A.14
432378
432391
FERS4K0250
FETTA43J0025
A.17
A.18
431539 FGN46AA630NNF A.27 431925 FEN46SA160JJF A.15 432184 FE1BPW A.21 432394 FETTA43J0032 A.18
431545 FEL436TA080JF A.13 431928 FEN46SA160KJF A.17 432186 FERJ3G0080 A.14 432397 FETTA43J0040 A.18
431548 FGN406F400LF A.29 431931 FEN46SA250KKF A.17 432188 FE1BRW A.21 432400 FETTA43J0050 A.18
431551 FEL436TA100JF A.13 431938 FEN46AA125KGF A.17 432189 FERJ3J0100 A.14 432403 FETTA43J0063 A.18
431554 FGN406F400NF A.30 431949 FEN46TA080JF A.13 432190 FEBRCS3 A.21 432406 FETTA43J0080 A.18
431557 FEL436TA125JF A.13 431955 FEN46TA100JF A.13 432191 FEBRCS4 A.21 432409 FETTA43J0100 A.18
431560 FGN406F630NF A.30 431961 FEN46TA125JF A.13 432192 FERJ3G0125 A.14 432412 FETTA43J0125 A.18
431563 FEL436TA160JF A.13 431965 FEH36TD160JF A.13 432193 FGBRCS3 A.32 432414 FETAA3J0025 A.18
431578 FEL456SA125JGF A.15 431967 FEN46TA160JF A.13 432194 FGBRCS4 A.32 432416 FEV36TA125KF A.16
431581 FEL456SA160JJF A.15 431980 FEH36TD160KF A.16 432195 FERJ3J0160 A.14 432417 FETAA3J0063 A.18
431584 FEL456SA160KJF A.17 431981 FGBSS3 A.32 432198 FEH436TD100JF A.13 432420 FETAA3J0125 A.18
431587 FEL456SA250KKF A.17 431982 FGBSS4 A.32 432204 FERJ3K0160 A.17 432423 FETAA3J0160 A.18
431593 FEL456TA080JF A.13 431983 FGDFF3 A.32 432205 FEH436TD125JF A.13 432426 FETAA3K0160 A.19
X.8
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
432429 FETAA3K0250 A.19 432840 FGJB A.33 433216 FETTD43K0125 A.19 433474 FBTS10L12 A.43
432432 FETAA4J0025 A.18 432843 FEL456TD160KF A.16 433219 FETTD43K0160 A.19 433489 FDDFQ3 A.9
432435 FETAA4J0063 A.18 432846 FGJM3 A.33 433222 FETTD43K0200 A.19 433492 FDDFQ4 A.9
432438 FETAA4J0125 A.18 432849 FGJM4 A.33 433225 FETTD43K0250 A.19 433497 FBTF4L12 A.43
432441 FETAA4J0160 A.18 432852 FGJP A.33 433231 FETTD45J0100 A.18 433500 FAR A.22
432444 FETAA4K0160 A.19 432855 FGJS3 A.33 433234 FETTD45J0125 A.18 433519 FDN13TF080GF A.5
432447 FETAA4K0250 A.19 432858 FGJS4 A.33 433235 FGRS3NL0400 A.27 433522 FDN13TF100GF A.5
432480 FETD30J0160 A.18 432861 FGJW3 A.33 433239 FETTD45J0160 A.18 433525 FDN13TF125GF A.5
432483 FETD30K0250 A.19 432864 FGJW4 A.33 433241 FGRS43NL0400 A.27 433527 FDN13TF160GF A.5
432486 FETD40J0160 A.18 432867 FGNFT A.31 433246 FDH13TF016EF A.5 433531 FENFT A.20
432489 FETD40K0250 A.19 432868 FEL456TD200KF A.16 433247 FGRS45NL0400 A.27 433539 FDUT A.10
432495 FETMC3J0012 A.18 432871 FEL456TD250KF A.16 433252 FETTD45K0125 A.19 433540 FEUT A.22
By reference number
432498 FETMC3J0020 A.18 432873 FGNRC A.46 433253 FGRS4NL0400 A.27 433541 FGUT A.33
432501 FETMC3J0050 A.18 432907 FEL46TD100JF A.13 433255 FDH13TF020EF A.5 433542 FDQDS3H A.8
432504 FETMC3J0100 A.18 432908 FGUA3 A.33 433257 FETTD45K0160 A.19 433548 FDQDS4H A.8
432510 FETMC3J0160 A.18 432909 FGUA4 A.33 433260 FETTD45K0200 A.19 433572 FDN36TD160GD A.6
432513 FETMC3K0160 A.19 432910 FGWS3 A.32 433262 FDH13TF025EF A.5 433575 FDN36TG160GD A.6
432516 FETMC3K0250 A.19 432913 FGWS4 A.32 433263 FETTD45K0250 A.19 433578 FDN436TD160GD A.6
432528 FETMC43J0050 A.18 432921 FEL46TD125JF A.13 433268 FDH13TF032EF A.5 433581 FDN436TG160GD A.6
432531 FETMC43J0100 A.18 432924 FEL46TD125KF A.16 433269 FETTD4J0100 A.18 433584 FDN456TD160GD A.6
432537 FETMC43J0160 A.18 432927 FEL46TD160JF A.13 433272 FETTD4J0125 A.18 433587 FDN456TG160GD A.6
432540 FETMC43K0160 A.19 432930 FEL46TD160KF A.16 433274 FDH13TF040EF A.5 433590 FDN46TD160GD A.6
432543 FETMC43K0250 A.19 432933 FEL46TD200KF A.16 433275 FETTD4J0160 A.18 433593 FDN46TG160GD A.6
432546 FETTA3J0025 A.18 432936 FEL46TD250KF A.16 433280 FDH13TF050EF A.5 433599 FDN66TD160GD A.5
432549 FETTA3J0032 A.18 432945 FEN36TD100JF A.13 433284 FETTD4K0125 A.19 433602 FDS35TD160GD A.5
432552 FETTA3J0040 A.18 432952 FDS35TD063ED A.5 433286 FDH13TF063EF A.5 433604 FDS45TD160GD A.5
432555 FETTA3J0050 A.18 432953 FEN36TD125JF A.13 433287 FETTD4K0160 A.19 433649 FDE36TE016ED A.5
432558 FETTA3J0063 A.18 432955 FDS35TD080GD A.5 433290 FETTD4K0200 A.19 433651 FDE36TE020ED A.5
432561 FETTA3J0080 A.18 432958 FDS35TD100GD A.5 433292 FDH13TF080GF A.5 433653 FDE36TE025ED A.5
432564 FETTA3J0100 A.18 432961 FDS35TD125GD A.5 433293 FETTD4K0250 A.19 433655 FDE36TE032ED A.5
432567 FETTA3J0125 A.18 432962 FEN36TD125KF A.16 433296 FETTG3J0100 A.18 433657 FDE36TE040ED A.5
432570 FETTA3J0160 A.18 432964 FDS45TD063ED A.5 433298 FDH13TF100GF A.5 433659 FDE36TE050ED A.5
432573 FEL436TD125JF A.13 432967 FDS45TD080GD A.5 433304 FDH13TF125GF A.5 433661 FDE36TE063ED A.5
432576 FEL436TD125KF A.16 432970 FDS45TD100GD A.5 433310 FDH13TF160GF A.5 433663 FDE36TE080GD A.5
432582 FETTA43J0160 A.18 432971 FEN36TD160JF A.13 433311 FETTG43J0100 A.18 433665 FDE36TE100GD A.5
432585 FEL436TD160JF A.13 432973 FDS45TD125GD A.5 433316 FDN13TF016EF A.5 433667 FDE36TE125GD A.5
432588 FEL436TD160KF A.16 432976 FEN36TD160KF A.16 433322 FDN13TF020EF A.5 433669 FDE36TE160GD A.5
432603 FETTA45J0063 A.18 432979 FEN36TD200KF A.16 433326 FETTG45J0100 A.18 433697 FDE46TE016ED A.5
432606
432609
FETTA45J0080
FETTA45J0100
A.18
A.18
432982
432994
FEN36TD250KF
FEN436TD100JF
A.16
A.13
433328
433332
FDN13TF025EF
FETTG4J0100
A.5
A.18
433699
433701
FDE46TE020ED
FDE46TE025ED
A.5
A.5
A
432612 FETTA45J0125 A.18 433... 433334 FDN13TF032EF A.5 433703 FDE46TE032ED A.5
432615 FETTA45J0160 A.18 433001 FEN436TD125JF A.13 433340 FDN13TF040EF A.5 433705 FDE46TE040ED A.5
432618 FEL436TD200KF A.16 433004 FEN436TD125KF A.16 433346 FDN13TF050EF A.5 433707 FDE46TE050ED A.5
432621
432636
FEL436TD250KF
FETTA4J0025
A.16
A.18
433007
433010
FEN436TD160JF
FEN436TD160KF
A.13
A.16
433352
433357
FDN13TF063EF
FDBRCL2
A.5
A.9
433709
433711
FDE46TE063ED
FDE46TE080GD
A.5
A.5
B
432639 FETTA4J0032 A.18 433013 FEN436TD200KF A.16 433358 FDBRCS2 A.9 433713 FDE46TE100GD A.5
432642 FETTA4J0040 A.18 433016 FEN436TD250KF A.16 433364 FDQDB3H A.8 433715 FDE46TE125GD A.5
432645 FETTA4J0050 A.18 433028 FEN456TD100JF A.13 433370 FDQDB3M A.8 433717 FDE46TE160GD A.5
432648
432651
FETTA4J0063
FETTA4J0080
A.18
A.18
433034
433037
FEN456TD125JF
FEN456TD125KF
A.13
A.16
433373
433376
FDQDB4H
FAMLT1
A.8
A.22
433892
433907
FGNRW
FDC35TE016ED
A.31
A.5
C
432654 FETTA4J0100 A.18 433040 FEN456TD160JF A.13 433377 FBCI3 A.43 433911 FDC35TE020ED A.5
432657 FETTA4J0125 A.18 433043 FEN456TD160KF A.16 433379 FDQDB4M A.8 433914 FDC35TE025ED A.5
432660 FETTA4J0160 A.18 433046 FEN456TD200KF A.16 433388 FDQDI3M A.8 433918 FDC35TE032ED A.5
432693
432696
FETTG3J0125
FETTG3J0160
A.18
A.18
433049
433061
FEN456TD250KF
FEN46TD100JF
A.16
A.13
433397
433400
FDQDI4M
FDTCA1316
A.8
A.9
433924
433925
FDC35TE125GD
FDC35TE160GD
A.5
A.5
D
432699 FEL456TD100JF A.13 433067 FEN46TD125JF A.13 433401 FDTCA1416 A.9 433948 FDC45TE016ED A.5
432705 FETTG3K0160 A.19 433070 FEN46TD125KF A.16 433406 FG1BPW A.32 433949 FDC45TE020ED A.5
432708 FETTG3K0200 A.19 433073 FEN46TD160JF A.13 433407 FG1BRW A.32 433950 FDC45TE025ED A.5
432711
432717
FETTG3K0250
FETTG43J0125
A.19
A.18
433076
433079
FEN46TD160KF
FEN46TD200KF
A.16
A.16
433412
433413
FGTCA230B
FGTCA240B
A.32
A.32
433951
433952
FDC45TE032ED
FDC45TE040ED
A.5
A.5
E
432720 FETTG43J0160 A.18 433082 FEN46TD250KF A.16 433415 FN1BRY1 A.39 433953 FDC45TE050ED A.5
432729 FETTG43K0160 A.19 433142 FGH36AA400NLF A.27 433416 FN1I2F A.46 433954 FDC45TE063ED A.5
432732 FETTG43K0200 A.19 433148 FGRJ3NL0250 A.27 433417 FN1PR A.40 434...
432735
432741
FETTG43K0250
FETTG45J0125
A.19
A.18
433151
433154
FGRJ3LL0400
FGRJ3NN0400
A.25
A.27
433419
433420
FNGS0800
FNBES3R
A.40
A.39
434013
434028
FAMECM
FGH36KA630NNF
A.26
A.28
F
432744 FETTG45J0160 A.18 433157 FGRJ3NN0630 A.27 433421 FNGS1000 A.40 434041 FGH46KA250LKF A.26
432747 FEL456TD125JF A.13 433159 FETTD3J0100 A.18 433422 FNBES4R A.39 434042 FGH46KA400LLF A.26
432753 FETTG45K0160 A.19 433160 FGRJ43NL0250 A.27 433423 FNBRC3 A.39 434043 FGH46KA400NLF A.28
432756
432759
FETTG45K0200
FETTG45K0250
A.19
A.19
433163
433164
FGRJ43LL0400
FETTD3J0125
A.25
A.18
433425
433426
FNBRC4
FNBRCS3
A.39
A.39
434044
434049
FGH46KA630NNF
FGL36KA250LKF
A.28
A.26
G
432774 FETTG4J0125 A.18 433166 FGRJ43NN0400 A.27 433427 FNBRCS4 A.39 434050 FGL36KA400LLF A.26
432777 FETTG4J0160 A.18 433168 FETTD3J0160 A.18 433434 FNWS3WP A.39 434051 FGL36KA400NLF A.28
432780 FEL456TD125KF A.16 433169 FGRJ43NN0630 A.27 433436 FNWS3AP A.39 434052 FGL36KA630NNF A.28
432786
432789
FETTG4K0160
FETTG4K0200
A.19
A.19
433172
433175
FGRJ45NL0250
FGRJ45LL0400
A.27
A.25
433438
433439
FNTCA4327
FNTCA4427
A.39
A.39
434068
434073
FGL46KA630NNF
FGN36KA250LKF
A.28
A.26
X
432792 FETTG4K0250 A.19 433178 FGRJ45NN0400 A.27 433440 FNWS4AP A.39 434092 FGN46KA630NNF A.28
432796 FGDMP3 A.32 433181 FGRJ45NN0630 A.27 433442 FNWS4WT A.39 434098 FGRL3LK0250 A.26
432799 FGDMP4 A.32 433182 FETTD3K0125 A.19 433443 FBAD3 A.43 434099 FGRL3LL0400 A.26
432811 FGEMF8 A.31 433184 FGRJ4NL0250 A.27 433444 FBCI4 A.43 434100 FGRL3NN0630 A.28
432817 FGEMFD A.31 433186 FETTD3K0160 A.19 433446 FBAD4 A.43 434101 FGRL43LK0160 A.26
432820 FGEMFF A.31 433187 FGRJ4LL0400 A.25 433449 FBAE3 A.43 434105 FGRL45LK0160 A.29
432823 FGEMFH A.31 433190 FGRJ4NN0400 A.27 433452 FBAE4 A.43 434106 FGRL45LK0250 A.26
432826 FGEMFJ A.31 433191 FETTD3K0200 A.19 433455 FBB3E A.43 434107 FGRL45LL0400 A.26
432829 FGEMFN A.31 433193 FGRJ4NN0630 A.27 433456 FBTF3L12 A.43 434109 FGRL4LK0160 A.26
432834 FEL456TD160JF A.13 433195 FETTD3K0250 A.19 433458 FBB3S A.43 434111 FGRL4LL0400 A.26
432836 FGFT A.33 433201 FETTD43J0100 A.18 433461 FBB4E A.43 434112 FGRL4NN0630 A.28
432838 FGGS0400 A.33 433204 FETTD43J0125 A.18 433464 FBB4S A.43 434201 FGTKA3L0250 A.29
432839 FGGS0630 A.33 433207 FETTD43J0160 A.18 433468 FBTS1L12 A.43 434202 FGTKA3L0400 A.29
X.9
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
434203 FGTKA3N0400 A.30 434657 FGL36SA500NNF A.27 434967 FEL36MC250KF A.16 435223 FEN46TA050JF A.13
434204 FGTKA3N0630 A.30 434663 FGH36BM400LLF A.25 434970 FEL36TA025JF A.13 435224 FGRL43NL0400 A.28
434205 FGTKA4L0250 A.29 434666 FGH36BM500NNF A.27 434971 FGH456VA400LLF A.26 435226 FEN46TA063JF A.13
434231 FGH306F250LF A.29 434669 FGH436BM400LLF A.25 434973 FEL36TA032JF A.13 435230 FGRL45NL0250 A.28
434232 FGH36AA250LKF A.25 434672 FGH436BM500NNF A.27 434976 FEL36TA040JF A.13 435236 FGRL45NL0400 A.28
434233 FGH36SA250LKF A.25 434675 FGL36BM400LLF A.25 434977 FGH456VA630NNF A.28 435250 FEN46TG100JF A.13
434234 FGH406F250LF A.29 434678 FGL36BM500NNF A.27 434979 FEL36TA050JF A.13 435253 FEN46TG125JF A.13
434235 FGH436SA250LKF A.25 434681 FGL436BM400LLF A.25 434982 FEL36TA063JF A.13 435254 FGRL4NL0250 A.28
434236 FGH456SA250LKF A.25 434684 FGL436BM500NNF A.27 434983 FGH46VA400LLF A.26 435259 FEN46TG160JF A.13
434237 FGH46AA250LKF A.25 434687 FGN36BM400LLF A.25 434994 FEL436MC050JF A.14 435260 FGRL4NL0400 A.28
434238 FGH46SA250LKF A.25 434690 FGN36BM500NNF A.27 434997 FEL436MC100JF A.14 435262 FEN46TG160KF A.16
434239 FGL306F250LF A.29 434693 FGN436BM400LLF A.25 435... 435265 FEN46TG200KF A.16
434240 FGL36AA250LKF A.25 434696 FGN436BM500NNF A.27 435003 FGH46VA630NNF A.28 435266 FGRL45LL0350 A.26
434241 FGL36SA250LKF A.25 434735 FGNRE A.31 435004 FEL436MC160JF A.14 435268 FEN46TG250KF A.16
434242 FGL406F250LF A.29 434736 FETMC3J0030 A.18 435007 FEL436MC160KF A.16 435272 FGRL45NN0500 A.28
434243 FGL436SA250LKF A.25 434742 FEH36MC007JF A.14 435010 FEL436MC250KF A.16 435273 FKY406DN100SF A.37
434244 FGL456SA250LKF A.25 434745 FEH36MC012JF A.14 435013 FEL436TA025JF A.13 435276 FKH36NE125SSF A.36
Numerical index
434245 FGL46AA250LKF A.25 434748 FEH36MC020JF A.14 435016 FEL436TA032JF A.13 435277 FGN436SA400LLF A.25
434246 FGL46SA250LKF A.25 434751 FEH36MC030JF A.14 435019 FEL436TA040JF A.13 435279 FKH36NE160TTF A.37
434247 FGN306F250LF A.29 434754 FEH36MC050JF A.14 435022 FEL436TA050JF A.13 435280 FGN46SA400LLF A.25
434248 FGN36AA250LKF A.25 434757 FEH36MC100JF A.14 435025 FEL436TA063JF A.13 435282 FKL46NE800PPF A.35
434249 FGN36SA250LKF A.25 434758 FGL436SA500NNF A.27 435037 FEL456TA063JF A.13 435285 FKH36NE800PPF A.35
434250 FGN406F250LF A.29 434763 FEH36MC160JF A.14 435049 FEL46TA025JF A.13 435288 FKH36NE100SQF A.36
434251 FGN436SA250LKF A.25 434764 FGL456SA500NNF A.27 435052 FEL46TA032JF A.13 435294 FKH36NG125SSF A.36
434252 FGN456SA250LKF A.25 434766 FEH36MC160KF A.16 435055 FEL46TA040JF A.13 435297 FKH36NG160TTF A.37
434253 FGN46AA250LKF A.25 434769 FEH36MC250KF A.16 435058 FEL46TA050JF A.13 435300 FKN436NT800PF A.35
434254 FGN46SA250LKF A.25 434770 FGL46AA500NNF A.27 435061 FEL46TA063JF A.13 435302 FGRL4LL0350 A.26
434261 FGTKA4L0400 A.29 434772 FEH36TA025JF A.13 435065 FGL36VA400LLF A.26 435303 FKH36NG800PPF A.35
434263 FGTKA4N0400 A.30 434775 FEH36TA032JF A.13 435071 FGL36VA630NNF A.28 435306 FKH36NG100SQF A.36
434265 FGTKA4N0630 A.30 434778 FEH36TA040JF A.13 435073 FEN36MC007JF A.14 435309 FGRL4NN0500 A.28
434303 FGRS3LK0250 A.25 434781 FEH36TA050JF A.13 435076 FEN36MC012JF A.14 435312 FKH36NS125SSF A.36
434307 FGRS43LK0250 A.25 434782 FGL46KA500NNF A.28 435077 FGL436VA400LLF A.26 435315 FKH36NS160TTF A.37
434311 FGRS45LK0250 A.25 434784 FEH36TA063JF A.13 435079 FEN36MC020JF A.14 435318 FKH36NT800PF A.35
434315 FGRS4LK0250 A.25 434806 FGL46SA500NNF A.27 435082 FEN36MC030JF A.14 435321 FKH36NS800PPF A.35
434319 FGTAA3L0250 A.29 434808 FEH36TG100JF A.13 435085 FEN36MC050JF A.14 435324 FKH36NS100SQF A.36
434323 FGTAA4L0250 A.29 434811 FEH36TG125JF A.13 435088 FEN36MC100JF A.14 435330 FKH46NE125SSF A.36
434337 FGRJ3LK0160 A.25 434812 FGN36AA500NNF A.27 435091 FGL436VA630NNF A.28 435333 FKH46NE160TTF A.37
434341 FGRJ3LK0250 A.25 434817 FEH36TG160JF A.13 435094 FEN36MC160JF A.14 435336 FKN36NT800PF A.35
A 434345
434349
FGRJ43LK0160
FGRJ43LK0250
A.25
A.25
434820
434823
FEH36TG160KF
FEH36TG200KF
A.16
A.16
435095
435097
FGL456VA400LLF
FEN36MC160KF
A.26
A.16
435339
435342
FKH46NE800PPF
FKH46NE100SQF
A.35
A.36
434353 FGRJ45LK0160 A.25 434824 FGN36KA500NNF A.28 435100 FEN36MC250KF A.16 435343 FGRJ3LL0250 A.25
434357 FGRJ45LK0250 A.25 434826 FEH36TG250KF A.16 435103 FEN36TA025JF A.13 435348 FKH46NG125SSF A.36
434361 FGRJ4LK0160 A.25 434829 FEH436MC050JF A.14 435106 FEN36TA032JF A.13 435351 FKH46NG160TTF A.37
B 434365
434393
FGRJ4LK0250
FGH36KA350LLF
A.25
A.26
434832
434835
FEH436MC100JF
FGN36SA500NNF
A.14
A.27
435107
435109
FGTCA1327
FEN36TA040JF
A.32
A.13
435354
435356
FKH436NT800PF
FGRJ43LL0250
A.35
A.25
434399 FGH36SA400LLF A.25 434838 FEH436MC160JF A.14 435112 FEN36TA050JF A.13 435357 FKH46NG800PPF A.35
434408 FGH436SA400LLF A.25 434841 FEH436MC160KF A.16 435115 FEN36TA063JF A.13 435360 FKH46NG100SQF A.36
434414 FGH456SA400LLF A.25 434844 FEH436MC250KF A.16 435116 FGTCA1427 A.32 435366 FKH46NS125SSF A.36
C 434420
434426
FGH46KA350LLF
FGH46SA400LLF
A.26
A.25
434847
434848
FEH436TA025JF
FGN436SA500NNF
A.13
A.27
435118
435120
FASHTH
FAUVRH
A.8
A.8
435367
435369
FGRJ45LL0250
FKH46NS160TTF
A.25
A.37
434432 FGH46AA400NLF A.27 434850 FEH436TA032JF A.13 435122 FGL456VA630NNF A.28 435372 FKL36NT800PF A.35
434438 FGL36KA350LLF A.26 434853 FEH436TA040JF A.13 435128 FGL46VA400LLF A.26 435375 FKH46NS800PPF A.35
434444 FGL36SA400LLF A.25 434856 FEH436TA050JF A.13 435134 FGL46VA630NNF A.28 435378 FKH46NS100SQF A.36
D 434448
434453
FAMB2
FGL436SA400LLF
A.26
A.25
434859
434860
FEH436TA063JF
FGN456SA500NNF
A.13
A.27
435139
435140
FEN36TG100JF
FGN36VA400LLF
A.13
A.26
435381
435384
FKY306DN100SF
FKN36NE125SSF
A.37
A.36
434459 FGL36AA400NLF A.27 434866 FGN46AA500NNF A.27 435142 FEN36TG125JF A.13 435387 FKN36NE160TTF A.37
434462 FGL456SA400LLF A.25 434871 FEH456TA063JF A.13 435146 FGN36VA630NNF A.28 435390 FKL36NE800PPF A.35
434468 FGL46KA350LLF A.26 434872 FGN46KA500NNF A.28 435148 FEN36TG160JF A.13 435393 FKN36NE800PPF A.35
E 434471
434473
FGRL3NN0400
FGRL3NN0500
A.28
A.28
434883
434884
FEH46TA025JF
FGN46SA500NNF
A.13
A.27
435151
435152
FEN36TG160KF
FGN436VA400LLF
A.16
A.26
435396
435397
FKN36NE100SQF
FGRJ4LL0250
A.36
A.25
434474 FGL46SA400LLF A.25 434886 FEH46TA032JF A.13 435154 FEN36TG200KF A.16 435399 FGRL3LL0250 A.26
434483 FGN36KA350LLF A.26 434889 FEH46TA040JF A.13 435157 FEN36TG250KF A.16 435400 FGRL3LL0350 A.26
434489 FGN36SA400LLF A.25 434892 FEH46TA050JF A.13 435158 FGN436VA630NNF A.28 435402 FKN36NG125SSF A.36
F 434495
434497
FGRL45LL0250
FGRL45NN0400
A.26
A.28
434893
434895
FGTAA3N0500
FEH46TA063JF
A.30
A.13
435160
435163
FEN436MC050JF
FEN436MC100JF
A.14
A.14
435405
435408
FKN36NG160TTF
FKN436NT630PF
A.37
A.35
434501 FGRL4NN0400 A.28 434899 FGTAA4N0500 A.30 435164 FGN456VA400LLF A.26 435410 FGRL43LL0250 A.26
434504 FGN456SA400LLF A.25 434902 FGTKA3L0350 A.29 435167 FGN456VA630NNF A.28 435411 FKN36NG800PPF A.35
434510 FGN46KA350LLF A.26 434905 FGTKA3N0500 A.30 435169 FEN436MC160JF A.14 435412 FGRL43LL0350 A.26
G 434512
434516
FGRS3NN0500
FGRS43LL0400
A.27
A.25
434908
434911
FGTKA4L0350
FGTKA4N0500
A.29
A.30
435170
435172
FGN46VA400LLF
FEN436MC160KF
A.26
A.16
435414
435419
FKN36NG100SQF
FGRL43NN0400
A.36
A.28
434521 FGRS43NN0500 A.27 434919 FEH46TG100JF A.13 435175 FEN436MC250KF A.16 435420 FKN36NS125SSF A.36
434525 FGRS45LL0400 A.25 434922 FEH46TG125JF A.13 435176 FGN46VA630NNF A.28 435423 FKN36NS160TTF A.37
434530 FGRS45NN0500 A.27 434928 FEH46TG160JF A.13 435178 FEN436TA025JF A.13 435426 FKH36NT630PF A.35
X 434534
434537
FGL46AA400NLF
FGRS4LL0400
A.27
A.25
434931
434934
FEH46TG160KF
FEH46TG200KF
A.16
A.16
435181
435182
FEN436TA032JF
FGRJ3NL0400
A.13
A.27
435427
435429
FGRL43NN0500
FKN36NS800PPF
A.28
A.35
434542 FGRS4NN0500 A.27 434937 FEH46TG250KF A.16 435184 FEN436TA040JF A.13 435432 FKN36NS100SQF A.36
434561 FGN36AA400NLF A.27 434940 FEL36MC007JF A.14 435187 FEN436TA050JF A.13 435433 FGRL4LL0250 A.26
434600 FGH36AA500NNF A.27 434943 FEL36MC012JF A.14 435188 FGRJ43NL0400 A.27 435435 FGRS3LL0400 A.25
434606 FGH36KA500NNF A.28 434946 FEL36MC020JF A.14 435190 FEN436TA063JF A.13 435438 FKN46NE125SSF A.36
434612 FGH36SA500NNF A.27 434949 FEL36MC030JF A.14 435194 FGRJ45NL0400 A.27 435441 FKN46NE160TTF A.37
434621 FGH436SA500NNF A.27 434952 FEL36MC050JF A.14 435200 FGRJ4NL0400 A.27 435444 FKN36NT630PF A.35
434627 FGH456SA500NNF A.27 434953 FGH36VA400LLF A.26 435202 FEN456TA063JF A.13 435447 FKN46NE800PPF A.35
434630 FGH46AA500NNF A.27 434955 FEL36MC100JF A.14 435206 FGRL3NL0250 A.28 435450 FFKN46NE100SQF A.36
434633 FGH46KA500NNF A.28 434958 FGH36VA630NNF A.28 435212 FGRL3NL0400 A.28 435456 FKN46NG125SSF A.36
434636 FGN46AA400NLF A.27 434960 FGH436VA400LLF A.26 435214 FEN46TA025JF A.13 435459 FKN46NG160TTF A.37
434642 FGH46SA500NNF A.27 434961 FEL36MC160JF A.14 435217 FEN46TA032JF A.13 435462 FKH436NT630PF A.35
434645 FGL36AA500NNF A.27 434964 FEL36MC160KF A.16 435218 FGRL43NL0250 A.28 435465 FKN46NG800PPF A.35
434651 FGL36KA500NNF A.28 434965 FGH436VA630NNF A.28 435220 FEN46TA040JF A.13 435468 FKN46NG100SQF A.36
X.10
Record Plus
Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page Ref. no. Cat. no. Page
435474 FKN46NS125SSF A.36 435821 FDH36TD160GD A.6 436152 FGH36KA400NLF A.28 436513 FGNRY/5 A.31
435477 FKN46NS160TTF A.37 435824 FDH36TG160GD A.6 436153 FGL46KA250LKF A.26 436514 FGNRYV/5 A.31
435480 FKL36NT630PF A.35 435827 FDH436TD160GD A.6 436154 FGL46KA400LLF A.26 436515 FGNRZ/5 A.31
435483 FKN46NS800PPF A.35 435830 FDH436TG160GD A.6 436155 FGL46KA400NLF A.28 436516 FGNRZV/5 A.31
435486 FKN46NS100SQF A.36 435833 FDH456TD160GD A.6 436156 FGN36KA400LLF A.26 436517 FNNRC/5 A.38
435489 FKY306DN125SF A.37 435836 FDH456TG160GD A.6 436157 FGN36KA400NLF A.28 436518 FNNRCV/5 A.38
435492 FKY306DN160TF A.37 435839 FDH46TD160GD A.6 436158 FGN36KA630NNF A.28 436519 FNNRD/5 A.38
435495 FKY306DN800PF A.37 435842 FDH46TG160GD A.6 436159 FGN46KA250LKF A.26 436520 FNNRDV/5 A.38
435498 FKY406DN125SF A.37 435845 FDL36TD160GD A.6 436160 FGN46KA400LLF A.26 436522 FNNRF/5 A.38
435501 FKY406DN160TF A.37 435848 FDL436TD160GD A.6 436161 FGN46KA400NLF A.28 436524 FNNRFV/5 A.38
435504 FKY406DN800PF A.37 435851 FDL456TD160GD A.6 436162 FGRL3LK0160 A.26 436526 FNNRX/5 A.45
435534 FKL436NT630PF A.35 435854 FDL46TD160GD A.6 436177 FGRL43LK0250 A.26 436527 FNNRY/5 A.38
By reference number
435535 FKL436NT800PF A.35 435857 FEH36AA025JBF A.14 436178 FGRL43LL0400 A.26 436528 FNNRYV/5 A.38
435537 FKN36NM800PF A.35 435860 FEH36AA063JEF A.14 436179 FGRL43NN0630 A.28 436530 FNNRZ/5 A.38
435538 FKH36NM800PF A.35 435863 FEH46AA025JBF A.14 436180 FGRL45NN0630 A.28 436531 FNNRZV/5 A.38
435539 FKL36NM800PF A.35 435866 FEH46AA063JEF A.14 436181 FGRL4LK0250 A.26 436590 FNFHW A.40
435541 FKN436NM800PF A.35 435869 FEL36AA025JBF A.14 436183 FAMAM2 A.26 436651 FNTCA3427 A.39
435542 FKH436NM800PF A.35 435872 FEL36AA063JEF A.14 436185 FAMGAM2 A.26 436720 FDKM1 A.10
435543 FKL436NM800PF A.35 435875 FEL46AA025JBF A.14 436186 FAMGAS2 A.26 436754 FEH36MC200KF A.16
435545 FKL36NE100SQF A.36 435878 FEL46AA063JEF A.14 436187 FAMGAT2 A.28 436755 FEH436MC200KF A.16
435546 FKL36NE125SSF A.36 435881 FEN36AA025JBF A.14 436188 FAMGFM2 A.26 436756 FEL36MC200KF A.16
435547 FKL46NE100SQF A.36 435884 FEN36AA063JEF A.14 436189 FAMGFS2 A.26 436763 FEL436MC200KF A.16
435549 FKL46NE125SSF A.36 435887 FEN46AA025JBF A.14 436190 FAMGFT2 A.26 436764 FEN36MC200KF A.16
435550 FKN36NT100SF A.36 435890 FEN46AA063JEF A.14 436191 FAMMT2 A.26 436765 FEN436MC200KF A.16
435551 FKN36NT125SF A.36 435893 FEH36MC080JF A.14 436192 FAMSM2 A.26 436778 FETMC3K0200 A.19
435553 FKH36NT100SF A.36 435896 FEL36MC080JF A.14 436197 FAMST2 A.26 436779 FETMC43K0200 A.19
435554 FKH36NT125SF A.36 435899 FEN36MC080JF A.14 436309 FAS01D A.21 436798 FEV36TA160KF A.16
435555 FKL36NT100SF A.36 435902 FEH436TG100JF A.13 436310 FAS10D A.21 436817 FEV46TA160KF A.16
435557 FKL36NT125SF A.36 435903 FEH436TG125JF A.13 436316 FNTCA3327 A.39 437...
435558 FKN36NM125SF A.36 435904 FEH436TG160JF A.13 436327 FEH36MC125JF A.14 437000 FEEO1J A.47
435559 FKH36NM125SF A.36 435905 FEH436TG160KF A.16 436329 FEH436MC125JF A.14 437001 FE1I2 A.46
435561 FKL36NM125SF A.36 435906 FEH436TG200KF A.16 436331 FEL36MC125JF A.14 437003 FEEO1N A.47
435562 FKN436NT100SF A.36 435907 FEH436TG250KF A.16 436333 FEL436MC125JF A.14 437004 FGEO2J A.47
435563 FKN436NT125SF A.36 435908 FEH456TG160KF A.16 436335 FEN36MC125JF A.14 437005 FG1I2 A.46
435565 FKH436NT100SF A.36 435909 FEH456TG200KF A.16 436356 FEN436MC125JF A.14 437007 FGEO2N A.47
435566 FKH436NT125SF A.36 435910 FEH456TG250KF A.16 436358 FETMC3J0125 A.18 437008 FGEO3J A.47
435567 FKL436NT100SF A.36 435923 FEL36TG100JF A.13 436359 FETMC43J0125 A.18 437009 FG1I4 A.46
435569 FKL436NT125SF A.36 435926 FEL36TG125JF A.13 436361 FEH36MC003JF A.14 437010 FGEO3N A.47
435570
435571
FKN436NM125SF
FKH436NM125SF
A.36
A.36
435932
435935
FEL36TG160JF
FEL36TG160KF
A.13
A.16
436363
436365
FEL36MC003JF
FEN36MC003JF
A.14
A.14
437011
437014
FKEO4J
FKEO4N
A.47
A.47
A
435573 FKL436NM125SF A.36 435938 FEL36TG200KF A.16 436396 FDH36MC003ED A.7 437015 FKEO5J A.47
435574 FN1BRY2 A.39 435941 FEL36TG250KF A.16 436398 FDH436MC003ED A.7 437016 FN1I4F A.46
435575 FN1BRW1 A.39 435944 FEL436TG100JF A.13 436401 FNS11R A.38 437017 FKEO5N A.47
435577
435578
FN1BRW2
FNFW
A.39
A.39
435947
435950
FEL436TG125JF
FEL436TG160JF
A.13
A.13
436409
436411
FDN36MC003ED
FDN436MC003ED
A.7
A.7
437018
440...
FNUVRJ A.45 B
435678 FN1BPE A.38 435953 FEL436TG160KF A.16 436449 FNECE6 A.47 440018 FAUVRB A.8
435679 FN1BRE A.38 435956 FEL436TG200KF A.16 436450 FNECE3 A.47 560...
435680 FNEMFF A.38 435959 FEL436TG250KF A.16 436451 FNECA6 A.47 560090 TTD 22 A.39
435683
435686
FNEMFD
FNEMF3
A.38
A.38
435962
435965
FEL456TG100JF
FEL456TG125JF
A.13
A.13
436452
436453
FNECA3
FAECA3
A.47
A.47
560091
560092
TT 35
TT 60
A.39
A.39
C
435689 FNEMF6 A.38 435968 FEL456TG160JF A.13 436456 FNEMFN A.38 560093 TT 80 A.39
435692 FNSHT8 A.38 435971 FEL456TG160KF A.16 436457 FNEMFJ A.38 560094 TT110 A.39
435693 FNSHTD A.38 435974 FEL456TG200KF A.16 436467 FEJN3 A.21 560095 TT160 A.39
435694
435695
FNSHTF
FNSHTJ
A.38
A.38
435977
435992
FEL456TG250KF
FEL46TG100JF
A.16
A.13
436468
436469
FEJN4
FGJN3
A.21
A.32
560096
560097
TT 210
TTO 110
A.39
A.39
D
435696 FNSHTN A.38 435995 FEL46TG125JF A.13 436470 FGJN4 A.32 560098 TTO 210 A.39
435697 FNUVD6 A.38 436... 436471 FNGS1600 A.40 617...
435698 FNUVR1 A.38 436002 FEL46TG160JF A.13 436472 FAUVR8 A.8 617947 FDKE A.10
435699
435700
FNUVR6
FNUVR8
A.38
A.38
436005
436008
FEL46TG160KF
FEL46TG200KF
A.16
A.16
436474
436475
FDNRC/5
FDNRCV/5
A.8
A.8
704...
704154 BTR 175 A.39
E
435701 FNUVRD A.38 436011 FEL46TG250KF A.16 436476 FDNRD/5 A.8 704155 BTR 305 A.39
435702 FNUVRF A.38 436014 FEN436TG100JF A.13 436477 FDNRDV/5 A.8 704156 BTR 350 A.39
435704 FNT A.40 436015 FEN436TG125JF A.13 436478 FDNRF/5 A.8 704169 RD5 220 A.39
435706
435707
FNBES3P
FNBES4P
A.39
A.39
436016
436017
FEN436TG160JF
FEN436TG160KF
A.13
A.16
436479
436481
FDNRFV/5
FNWS4WP
A.8
A.39
704175
704176
RD5 110
RD5 380
A.39
A.39
F
435708 FNBSS3P A.39 436018 FEN436TG200KF A.16 436482 FNWS3WT A.39 704177 RD6 220 A.39
435709 FNGS1250 A.40 436019 FEN436TG250KF A.16 436487 FDNRY/5 A.8 704178 RD6 110 A.39
435710 FNBSS3R A.39 436020 FEN456TG100JF A.13 436488 FDNRYV/5 A.8 704179 RD6 380 A.39
435711
435712
FNBSS4P
FNBSS4R
A.39
A.39
436021
436022
FEN456TG125JF
FEN456TG160JF
A.13
A.13
436489
436490
FDNRZ/5
FDNRZV/5
A.8
A.8
872...
872052 A.47
G
435713 FNFE A.40 436023 FEN456TG160KF A.16 436491 FENRC/5 A.20 872140 FAECE6 A.47
435714 FNFH A.40 436024 FEN456TG200KF A.16 436492 FENRCV/5 A.20 872141 FAECE3 A.47
435715 FNFT A.40 436025 FEN456TG250KF A.16 436493 FENRD/5 A.20 872224 RD1D 220 A.39
435716
435719
FNJL3
FNJL4
A.40
A.40
436026
436027
FEH456TG100JF
FEH456TG125JF
A.13
A.13
436494
436495
FENRDV/5
FENRF/5
A.20
A.20
872225
872226
RD1D 110
RD1D 380
A.39
A.39
X
435722 FNJP A.40 436028 FEH456TG160JF A.13 436496 FENRFV/5 A.20 872227 RDFR A.49
435726 FNNRC A.46 436078 FETMC3J0080 A.18 436499 FENRX/5 A.45 872240 FAECA6 A.47
435738 FNNRE A.38 436117 FDC35TE040ED A.5 436500 FENRY/5 A.20 880...
435745 FNNRW A.38 436118 FDC35TE050ED A.5 436501 FENRYV/5 A.20 880954 FETCA630A A.21
435757 FNWS3AT A.39 436133 FDC35TE063ED A.5 436502 FENRZ/5 A.20 880955 FETCA640A A.21
435758 FNPFM A.39 436143 FDC35TE080GD A.5 436503 FENRZV/5 A.20 883...
435759 FNWS4AT A.39 436144 FDC35TE100GD A.5 436504 FGNRC/5 A.31 883970 FBF6 A.9
435760 FNS11L A.39 436145 FDC45TE080GD A.5 436505 FGNRCV/5 A.31
435761 FNBA11R A.38 436146 FDC45TE100GD A.5 436506 FGNRD/5 A.31
435762 FNUA3 A.40 436147 FDC45TE125GD A.5 436507 FGNRDV/5 A.31
435763 FNUA4 A.40 436148 FDC45TE160GD A.5 436509 FGNRF/5 A.31
435764 FNUT A.40 436150 FGH36KA250LKF A.26 436510 FGNRFV/5 A.31
435812 FEEMF8 A.20 436151 FGH36KA400LLF A.26 436512 FGNRX/5 A.45
X.11
Record Plus
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Numerical index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The policy of GE Consumer &
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . is. one. of .continuous
Industrial . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
improvement.
The right is reserved to alter the
.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . or any
design . structural
. . . details. .of .
the products at any time without
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
giving notice.
.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .