Moulded Case

Circuit Breakers
Type DH / DL / DG / DM
PRODUCT HIGHLIGHTS

Current Range 0.63 A to 800 A


l

1, 2, 3 and 4 pole version


l

Normal, Standard and High breaking capacities upto 65 kA


l

All MCCBs are current limiting with very low let through and cut-off
l

Operating mechanism is quick make, quick break and trip free. It is independent of manual
l

speed of operations

The entire current carrying path is designed to ensure very low power loss per pole
l

Adjustable overload releases for the entire range


l

Suitable for both AC and DC applications


l

Terminals suitable for both copper & aluminium terminations.


l

“Push to trip” facility to verify healthiness of mechanism.


l

Wide range of site fittable accessories.


l

New Rotary Operating Mechanisms for DH MCCBs are of adjustable shaft length , to take
l

panel depth variations gives clear ON / OFF / TRIP indication allows use in same quadrant
of operation allows keylocking or padlocking in OFF position with door interlock

No line load bias.


l

Housing is made of heat resistant insulating material.


l

Contacts are of silver alloy to have high electrical life. The mechanism is so designed
l

that there is no arcing on the current carrying part of the contact. The strong “wipe
action” of the contact system keeps the contact surface clean of oxide films.

1
TECHNICAL DATA

Rating 16 A 100 A

Type DM DH DL DM
Motor Duty Standard Breaking Capacity High Breaking Capacity Motor Duty
Poles 3 3/4 3 4 3
Ratings (A) 0.63,1,1.6,2.5,4,5,6.3,7.5,10,12,16 16,20,25,32,40,50,63,80,100 16,20,25,32,40,50,63,80,100 16,25,30,35,50,60,70,80
Rated Operational Voltage Ue (V) 415 415 415 415
Rated Insulation Voltage Ui (V) 690 750 750 750
Rated Impulse Voltage (kV) - 8 8 8
Operating Frequency (Hz) 50 / 60 50 / 60 50 / 60 50 / 60
Rated S.C. Making Capacity 105 52.5 143 143
at 415 V Icm (kA)
Rated Ultimate S.C. Breaking 660 V 10 5 10 10 10
Capacity Icu (kA) 550 V 25 12 25 16 25

500 V 35 16 35 25 35

415 V 50 25 65 50 50

380 V 50 25 65 50 50

240 V 85 50 85 65 65
Rated Service S.C. Breaking 100% (50 kA) 100% (25 kA) 75% 100% 100% (50 kA)
(50 kA)
Capacity at 415 V Ics (kA) as % of Icu
DC Breaking Capacity (kA) at 110 V - 16 50 -
(L/R <= 15ms) 250 V - 10 25 -
with 3 Poles in series 250 V - 16 40 -
with midpoint grounded 500 V - 10 25 -
Capacitor Rating at 415 V, 50 Hz (kVAR) - 5,8,10,13,15,20,25,25,35 5,8,10,13,15,20,25,25,35,50 -
Mechanical Life ** 30000 30000 **
Electrical Life ** 10000 10000 **
Utilisation Category
Operating Temperature 0C
Pollution Degree
Release Type Magnetic Thermal - Magnetic Thermal - Magnetic Magnetic
Overload Release Setting - 80 - 100% 80 - 100% -
Short Circuit Release Setting (+/-20%) 12*In 9*In 9*In 12*In
Terminal Capacity (Cables) mm2 - 50 50 50
(Link) mm 10 16 16 16
Weight (kg) 1 1.7 1.7 1.7
Dimensions H 130 157 157 157
W 75 90 / 120 90 / 120 90
Without Knob D 105 87 87 87
With Knob D 124 104 104 104
** Data on request

2
125 A 160 A 200 A

DH DH DL DM DH DL
Standard Breaking Capacity Standard Breaking Capacity High Breaking Capacity High Breaking Capacity Standard Breaking Capacity High Breaking Capacity
3/4 3/4 3 3 3 3
16,20,25,32,40,50,63,80,100, 125 160 100,125,160 100,120,160 200 200
415 415 415 415 415 415
750 750 750 750 750 750
8 8 8 8 8 8
50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
73.5 73.5 143 143 73.5 143

10 7 10 10 7 10
18 18 25 25 18 25
35 35 35 35 25 35
35 35 65 50 35 65
35 35 65 50 35 65
60 60 85 65 60 85
100% (35 kA) 75% (27 kA) 75% (50 kA) 100% (50 kA) 50% (18 kA) 100% (50 kA)

16 16 50 - 16 50
10 10 25 - 10 25
16 16 40 - 16 40
10 10 25 - 10 25
5,8,10,13,15,20,25,25,35,50 70 35,50,70 - 50,70,70 80
22000 22000 20000 ** 22000 20000
7500 7000 5000 ** 7000 5000

Thermal - Magnetic Thermal - Magnetic Thermal - Magnetic Magnetic Thermal - Magnetic Thermal - Magnetic
80 - 100% 80 - 100% 70 - 100% - 80 - 100% 70 - 100%
9*In 8*In 8*In 12*In 6*In 9*In
70 70 95 185 150 185
25 25 36 36 30 36
1.7 1.8 4.8 4.8 2.4 4.6
157 215 338 338 215 338
90 / 120 90 / 120 108 108 90 140
87 87 104.5 104.5 87 104.5
104 104 131.5 131.5 104 131.5

3
TECHNICAL DATA

Rating 250 A

Type DH DL DM
Standard Breaking Capacity High Breaking Capacity Motor Duty
Poles 3 3 3
Ratings (A) 200, 250, 320, 400, 500, 630 200, 250 200, 230, 250
Rated Operational Voltage Ue (V) 415 415 415
Rated Insulation Voltage Ui (V) 750 750 750
Rated Impulse Voltage (kV) 8 8 8
Operating Frequency (Hz) 50/60 50/60 50/60
Rated S.C. Making Capacity 73.5 143 105
at 415 V Icm (kA)
Rated Ultimate S.C. Breaking 660 V 7 10 10
Capacity Icu (kA) 550 V 18 25 25

500 V 25 35 35

415 V 35 65 50

380 V 35 65 50

240 V 60 85 65
Rated Service S.C. Breaking 100% (35 kA) 75% (35 kA) 100% (50 kA)
Capacity at 415 V Ics (kA) as % of Icu
DC Breaking Capacity (kA) at 110 V 35 35 -
(L/R <= 15ms) 250 V 25 25 -
with 3 Poles in series 250 V 40 40 -
with midpoint grounded 500 V 25 25 -
Capacitor Rating at 415 V, 50 Hz (kVAR) 80 100 80 100 -
Mechanical Life 18000 18000 **
Electrical Life 15000 15000 **
Utilisation Category
Operating Temperature 0C
Pollution Degree
Release Type Thermal - Magnetic Thermal - Magnetic Magnetic
Overload Release Setting 80 - 100% 80 - 100% -
Short Circuit Release Setting (+/-20%) 6*In 6*In 12*In
Terminal Capacity (Cables) mm2 300 300 300
(Link) mm 40 40 40
Weight (kg) 5.2 5.2 5.2
Dimensions H 266 266 266
W 140 140 140
Without Knob D 105 105 105
With Knob D 137 137 137
** Data on request

4
400 A 630 A

DH DL DM DH DL
Standard Breaking Capacity Standard Breaking Capacity Motor Duty Standard Breaking Capacity High Breaking Capacity
3 3 3 3 3
320, 400 320, 400 275, 325, 350, 400 500, 630 500, 630
415 415 415 415 415
750 750 750 750 750
8 8 8 8 8
50/60 50/60 50/60 50/60 50/60
73.5 143 105 73.5 105

7 10 10 7 10
18 25 25 18 25
25 35 35 25 35
35 65 65 35 50
35 65 65 35 50
60 85 85 60 65
100% (35 kA) 75% (50 kA) 75% (50 kA) 100% (35 kA) 100% (50 kA)

35 35 - 35 35
25 25 - 25 25
40 40 - 40 40
25 25 - 25 25
120 160 120 160 - 120 160 120 160
18000 18000 ** 15000 15000
12000 12000 ** 2500 2500
A
-5 to +55
III
Thermal - Magnetic Thermal - Magnetic Magnetic Thermal - Magnetic Thermal - Magnetic
80 - 100% 80 - 100% - 80 - 100% 80 - 100%
6*In 6*In 12*In 6*In 6*In
300 300 300 400 400
40 40 40 40 40
5.2 5.2 5.2 6 6
266 266 266 266 266
140 140 140 140 140
105 105 105 105 105
137 137 137 137 137

5
ACCESSORIES

INTERNAL ACCESSORIES

AUXILIARY CONTACT UNDER VOLTAGE SHUNT RELEASE TRIP ALARM


RELEASE CONTACT

EXTERNAL ACCESSORIES

Extended rotary handle with key lock Direct rotary handle

6
EARTH FAULT MODULE

Earth Fault Moudles Type GF1, GF2 and GF11. These FEATURES :
moudles are to be used with MCCBs for earth fault
lCompact in size
protection. The principle of operation is based on detection
of the residual current in the system. They combine safety lProtection against earth faults.
and versatility, conforming to the high performance
standards, the characteristic of all L&T products. lSolid state design.
lBuilt-in moulded CBCT for GF1 & GF2.
External CTs are to be used for GF11.
lSuitable for both 3 phase 3 wire & 3 Phase 4 wire
systems. In case of 3 phase 4 wire system, the natural
cable/twisted link should also be passed through the
EARTH FAULT MODULE GF1 CBCT along with the 3 phase links / cables.
GF1 is suitable up to DH / DG / DM / DL 200
lBuilt-in test facility.
lSelection facility for nominal current rating (In).
lEarth fault setting is adjustable from 10% to 50% of set
current
lSelectable trip times (100 ms, 200 ms).
EARTH FAULT MODULE GF2
GF2 is suitable for DH / DL / DG / DM from lManual reset for positive fault acknowledgment.
250 A to 400 A MCCBs
lPotential free NO contact to trip
MCCB (through 240 V shunt release).
lWindow dimensions suitable for
Cable / Link connection in GF1 and GF2.

Note: MCCBs need to be fitted with


EARTH FAULT MODULE GF11
GF11 is suitable All MCCBs. 110 V / 240 V as shunt release for Earth
Fault Module operation.
TECHNICAL DATA
SPECIFICATION TYPE GF1 / GF2 / GF11
1 Current Setting Range (Is) 10% to 50% of nominal current rating (In)
Continuously adjustable
2 Auxiliary Supply 240 V AC ±20%
3 Time Delay (ms) 100 / 200 ms Field selectable
4 Pick-up Accuracy ±10% Is
5 Output Contact 1 NO contact manual reset Type
contact rating 5 A 240 V AC
6 Indication a) Power On LED
b) Trip LED (manual reset)
7 Operating Temperature +100C to +550C
8 Insulation 2 kV 50 Hz for one minute across independent circuit
1 kV 50 Hz for one minute across open contacts
9 Mounting Baseplate mounting type
10 Window for Cable / Busbar entry (mm) GF1 - 110 x 32
GF2 - 165 x 61.5
11 Weight (kg) GF1 - 1.2
GF - 2.2
GF11 - 0.9

7
CHARACTERISTIC CURVES TYPE DH

DH 100, DH 125 DH 160


10000 10000
7 7
5 5
2 2
1000 1000
7 7
5 5
2 2
100 100
7 7
5 5
2 2
TIME IN SECONDS

TIME IN SECONDS
10 10
7 7
5 5
2 2
1 1
7 7
5 5
2 2
0.1 0.1
7 7
5 5
2 2

0.01 0.01
1 2 4 6 8 10 2 4 6 8 100 2 1 2 4 6 8 10 2 4 6 8 100 2

MULTIPLES OF SET CURRENT MULTIPLES OF SET CURRENT

NOTE : MAGNETIC TRIPPING VALUES INDICATED AS NOTE : MAGNETIC TRIPPING VALUES INDICATED AS
MULTIPLE OF RATED CURRENT MULTIPLE OF RATED CURRENT

DH 200 DH 250/400/630
10000 100000
7 7
5 5

2 2

1000 10000
7
7 5
5
2 2
1000
100 7
7 5
5
2
2 100
TIME IN SECONDS

TIME IN SECONDS

7
10 5
7
5 2
2 10
7
1 5
7
5 2
2 1
7
0.1 5
7
2
5
0.1
2 7
5

2
0.01 0.01
1 2 3 4 5 6 7 9 10 2 3 4 5 6 7 100
1 2 4 6 8 10 2 4 6 8 100 2

MULTIPLES OF SET CURRENT MULTIPLES OF SET CURRENT

NOTE : MAGNETIC TRIPPING VALUES INDICATED AS NOTE : MAGNETIC TRIPPING VALUES INDICATED AS
MULTIPLE OF RATED CURRENT MULTIPLE OF RATED CURRENT

8
CHARACTERISTIC CURVES TYPE DL

DL 100 DL 160
10000 10000
7 7
5 5
2 2
1000 1000
7 7
5 5
2 2
100 100
7 7
5 5
2 2
TIME IN SECONDS

TIME IN SECONDS
10 10
7 7
5 5
2 2
1 1
7 7
5 5
2 2
0.1 0.1
7 7
5 5
2 2

0.01 0.01
1 2 4 6 8 10 2 4 6 8 100 2 1 2 4 6 8 10 2 4 6 8 100 2

MULTIPLES OF SET CURRENT MULTIPLES OF SET CURRENT

NOTE : MAGNETIC TRIPPING VALUES INDICATED AS NOTE : MAGNETIC TRIPPING VALUES INDICATED AS
MULTIPLE OF RATED CURRENT MULTIPLE OF RATED CURRENT

DL 200 DL 250/400/630
100000
7
5
100000
2 7
5
10000
7 2
5
10000
7
2 5
1000 2
7
5 1000
7
2 5

100 2
7 100
TIME IN SECONDS

TIME IN SECONDS

5 7
5
2
10 2
7 10
5 7
5
2
2
1 1
7 7
5
5
2 2
0.1 0.1
7 7
5 5

2 2
0.01
0.01 1 2 3 4 5 6 7 9 10 2 3 4 5 6 7 100
2 3 4 5 6 7 8 10 20

MULTIPLES OF SET CURRENT MULTIPLES OF SET CURRENT

NOTE : MAGNETIC TRIPPING VALUES INDICATED AS NOTE : MAGNETIC TRIPPING VALUES INDICATED AS
MULTIPLE OF RATED CURRENT MULTIPLE OF RATED CURRENT

9
OVERALL DIMENSIONS

DH 100/125/160/200, DM/DL 100


M4 - 4 Nos. BREAKER MOUNTING HOLES.
PHASE BARRIER 4 Nos.
146
90 120
25 33
10

13

10

13

26 18
53
137
70

130
193
256
137

193
130
70

49
215
157
5
30 4 MOUNTING
LINK 87 HOLES (M4)
40 40 39 37 39

38.5
104
27

3 Pole 4 Pole

130
51
TERMINAL SCREWS - M8
Tightening Torque : 0.85 kg f-m

Spreaders provided as standard from 100 A rating onwards MOUNTING AND CUT-OUT DETAILS

DM 16 DM 160, DL 160/200
75
75 108
35 35 131.5
17.5 17.5 104.5
19 14

39.5

28

123.9
115
64

130

50

253
282
338
72

98.5
25
105
124
25 25
25
21
32

32 32
71.5

35
115

109

FOR FIXING THE BR4EAKER


253
72
32

USE SCREW M4x 79-2 Nos.

36
24
75
MOUNTING AND FOR FIXING THE BREAKER
DOOR CUT-OUT DETAILS USE SCREW M4x40-4 Nos.

ALL DIMENSIONS ARE IN mm

10
OVERALL DIMENSIONS

DH/DG/DL/DM 250/400/630

FOR FIXING THE BREAKER


140 USE SCREW M4x40-4 Nos.
137
27.5 105 52.5

112
16

45.5
224

79
0

133.5

43.5
370
234

266

MOUNTING AND
DOOR CUT-OUT DETAILS
45.2

4 mm thick for DH 250


40 5 mm thick for DH 450
43.5 43.5 26.5 6 mm thick for DH 630
42
58.3

25

23
157

BOTTOM TERMINAL TOP TERMINAL

Spreaders included as standard.

DTH 800

206
105 141.5
_ _
+0.2
70+0.2 70 104.50

O13

70
59

50.75
92.5

184
90.5

12.5
410

184
190

33 33
68 FOR FIXING THE BREAKER
USE SCREW M4x50-4 Nos.

6
6.5 MOUNTING AND
O13
DOOR CUT-OUT DETAILS

40 35±0.2 35±0.2

ALL DIMENSIONS ARE IN mm

11
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM

DH 100/125/160/200, DL 100/160, DM 100


160 15

20
41

40
45
32
±0 2.5
40
2 HOLES Ø4
FOR MOULDING
HANDLE COUPLING

DH 250/400/630, DL 250/400/630, DM 250/400


Breaker Mounting Holes
43.5
204

41
SCREW MAX 32-4 Nos
PLAIN WASHER
100.5

40 SPRING WASHER
40

Ø32±0.25
2 HOLES-
Ø4 FOR
MOUNTING
HANDLE

DM 16
12.5
178
20

41
40±0.25
45

±0.25
32
±0.25
40

2 HOLES Ø4
FOR MOULDING
HANDLE COUPLING

ALL DIMENSIONS ARE IN mm

12
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM

DL 200, DM 160

203.5
176
108 57
35

100 ± 005
85 ± 05
189.5

206
165
68
BREAKER MOUNTING
HOLES

CUT OUT DETAILS

149.5

DTH 800

228.5 201.5
103.0
57.0

35
100.0

±0.05
85
290

165.0
206

BREAKER
68.0 MOUNTING
HOLES
153.5
206

ALL DIMENSIONS ARE IN mm

13
MOUNTING DIMENSIONS OF NEW EXTENDED ROM

L2
I 50
0

L3
45
I 76

N I 4

L1

L= LENGTH OF SHAFT REQUIRED FOR PANEL DEPTH L1 REFER PANEL CUT DETAILS

L2
L3

Cat. No. L1 Min. L1 Max. L L2 L3


N
CM99103OOOO 178 377 L1-1 27 22 62

CM99101OOOO
203 401.5 L1-1 52 27.5 84
CM99101OOOA

CM99102OOOO 227 425.5 L1-1 76 38.7 5 121.7

ALL DIMENSIONS ARE IN mm

14
DIMENSIONAL DETAILS FOR
EARTH FAULT MODULES

GF1

Terminal Block

24 110

108
32
20

158 50

195

=
30
=

175
USE M4 SCREW

GF2 GF11

Terminal Block
8.5 274.5 60
71.5

71.5
105.5

Cable / Busbar entry


8

( 165 mm x 61.5 mm )
5 2

175 15 54

158 50

195

USE M6 SCREW 30 Terminals for external CT


secondary connection
=
66

30
96
74

Terminal
Block 90 90 175
= =
USE M4 SCREW

ALL DIMENSIONS ARE IN mm

15
FUSELESS MOTOR PROTECTION SYSTEM

SELECTION CHART : FUSELESS PROTECTION FOR DOL STARTER FEEDERS WITH MCCBs, type 'DM'
TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz. as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Sr. No. HP KW FLC RELAY CONTRACTOR MCCB
(A) TYPE RANGE (A) TYPE RATING
1 0.125 0.09 0.4 MNX-R3 0.3 - 0.5 MNX 9 DM 16 0.63
2 0.16 0.12 0.45 MNX-R3 0.45 - 0.75 MNX 9 DM 16 0.63
3 0.2 0.15 0.57 MNX-R3 0.45 - 0.75 MNX 9 DM 16 1
4 0.25 0.19 0.75 MNX-R3 0.6 - 1 MNX 9 DM 16 1
5 0.33 0.25 0.9 MNX-R3 0.6 - 1 MNX 9 DM 16 1
6 0.5 0.37 1.2 MNX-R3 0.9 - 1.5 MNX 9 DM 16 1.6
7 0.75 0.55 1.6 MNX-R3 1.4 - 2.3 MNX 9 DM 16 1.6
8 1 0.75 2.1 MNX-R3 1.4 - 2.3 MNX 9 DM 16 2.5
9 1.5 1.1 2.7 MNX-R3 2.0 - 3.3 MNX 9 DM 16 2.5
10 1.75 1.3 3 MNX-R3 2.0 - 3.3 MNX 9 DM 16 4
11 2 1.5 3.8 MNX-R3 3.0 - 5.0 MNX 9 DM 16 4
12 2.5 1.8 4.8 MNX-R3 4.5 - 7.5 MNX 9 DM 16 5
13 3 2.25 5 MNX-R3 4.5 - 7.5 MNX 9 DM 16 5
14 4 3 6.4 MNX-R3 4.5 - 7.5 MNX 9 DM 16 7.5
15 5 3.7 7.9 MNX-R3 6 - 10 MNX 9 DM 16 7.5
16 6 4.5 9 MNX-R4 9 - 15 MNX 32 DM 16 10
17 7.5 5.5 11.4 MNX-R4 9 - 15 MNX 32 DM 16 12
18 10 7.5 15.4 MNX-R4 14 - 23 MNX 80 DM 16 16
19 12.5 9.3 19.5 MNX-R4 14 - 23 MNX 80 DM 100 25
20 15 11 23 MNX-R4 20 - 33 MNX 80 DM 100 25
21 17.5 13 24 MNX-R4 20 - 33 MNX 80 DM 100 30
22 20 15 29 MNX-R4 20 - 33 MNX 80 DM 100 35
23 25 18.6 38.5 MNX-R4 30 - 50 MNX 80 DM 100 50
24 30 22.5 43 MNX-R4 30 - 50 MNX 80 DM 100 50
25 35 26 47 MNX-R4 45 - 75 MNX 80 DM 100 60
26 40 30 59 MNX-R4 45 - 75 MNX 80 DM 100 70
27 45 33.5 60 MNX-R4 45 - 75 MNX 80 DM 100 70
28 50 37 69 MNX-R4 45 - 75 MNX 80 DM 100 80
29 60 45 80 MNX-R4 66 - 110 MNX 95 DM 160 100
30 75 55 100 MNX-R4 66 - 110 MNX 110 DM 160 120
31 90 67.5 120 MNX-R5 90 - 150 MNX 140 DM 160 160
32 100 75 135 MNX-R5 90 - 150 MNX 140 DM 160 160
33 110 80 139 MNX-R5 90 - 150 MNX 185 DM 250 200
34 125 90 165 MNX-R5 135 - 225 MNX 225 DM 250 200
35 150 110 200 MNX-R5 135 - 225 MNX 265 DM 400 275
36 175 130 230 MNX-R5 180 - 300 MNX 265 DM 400 325
37 197 147 260 MNX-R5 180 - 300 MNX 265 DM 400 325
38 200 150 275 MNX-R5 180 - 300 MNX 325 DM 400 325
39 215 160 280 MNX-R5 180 - 300 MNX 325 DM 400 350
40 225 168 300 MNX-R5 270 - 450 MNX 325 DM 400 350
41 245 180 320 MNX-R5 270 - 450 MNX 325 DM 400 400
42 270 200 340 MNX-R5 270 - 450 MNX 400 DM 400 400

SELECTION CHART : FUSELESS PROTECTION FOR STAR-DELTA STARTER FEEDERS WITH MCCBs, type 'DM'
TYPE '2' Co-ordination, Iq=50 kA at 415 V, 3Ø, 50 Hz.
as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1

MOTOR MCCB CONTACTOR RELAY


hp kW I line I phase Rating (In) Type I mag Star Delta Main Range Type
(A) (A) (A) (A) (A)
12.5 9.3 19.5 11.3 30 DM 100 360 MNX 80 MNX 80 MNX 80 9 - 15 MNX-R4
15 11 23 13.3 35 DM 100 420 MNX 80 MNX 80 MNX 80 9 - 15 MNX-R4
20 15 29 16.7 50 DM 100 600 MNX 80 MNX 80 MNX 80 14 - 23 MNX-R4
25 18.6 38.5 22.2 50 DM 100 600 MNX 80 MNX 80 MNX 80 14 - 23 MNX-R4
30 22.5 43 24.8 60 DM 100 720 MNX 80 MNX 80 MNX 80 20 - 33 MNX-R4
40 30 59 34.1 100 DM 160 1200 MNX 95 MNX 95 MNX 95 30 - 50 MNX-R4
50 37 69 39.8 100 DM 160 1200 MNX 95 MNX 95 MNX 95 30 - 50 MNX-R4
75 55 100 57.7 160 DM 160 1920 MNX 95 MNX 95 MNX 95 45 - 75 MNX-R4
100 75 135 78 200 DM 250 2400 MNX 140 MNX 140 MNX 140 60 - 100 MNX-R5
125 90 165 95.3 250 DM 250 3000 MNX 140 MNX 140 MNX 140 90 - 150 MNX-R5
150 110 200 115.5 325 DM 400 3900 MNX 225 MNX 225 MNX 225 90 - 150 MNX-R5
175 125 230 133 325 DM 400 3900 MNX 225 MNX 225 MNX 225 90 - 150 MNX-R5
200 150 275 159 400 DM 400 4800 MNX 265 MNX 265 MNX 265 135 - 225 MNX-R5
NOTES 1) Selection chart is for standard 3 Phases, Squirrel Cage Motor with average power factor and efficiency. 2) Motor ratings at 415 V, 50 Hz.
3) Open Transition is assumed for change over from star to Delta mode. 4) Contractor ratings indicated are the minimum rating suitable
for the application, higher size rating can be used. 5) Normal motor starting time (< = 15 sec.) Is assumed. For higher starting time refer
16 back to L&T.
17
For selection and product demonstration, please contact any of our branch offices listed below:

REGISTERED OFFICE AND L&T House A28,Indira Nagar


HEAD OFFICE Group MIG - 5 Faizabad Road
L&T House, Ballard Estate Padmanabhpur Lucknow 226 016
P. O. Box 278 Durg 491 001 Uttar Pradesh
Mumbai 400 001 Tel: 0788-2213833 / 14 / 28 / 29 Tel: 0522-4040905 / 903 / 904
Tel: 022-67525656 Fax: 0788-2213820 Fax: 0522-2311671
Fax: 022-67525858 e-mail: esp-Lko@Lntebg.com
Website: www.Larsentoubro.com A1/11, Astronauts Avenue
Bidhan Nagar Plot No. 518
ELECTRICAL STANDARD PRODUCTS (ESP) Durgapur 713 212 4th Main Road
501, Sakar Complex Tel: 0343-2536493 / 39 K. K. Nagar
Opp. Gandhigram Rly. Station Fax: 0343-2536493 Madurai 625 020
Ashram Road e-mail: esp-dgp@Lntebg.com Tel: 0452-2537404 / 303
Ahmedabad 380 009 Fax: 0452-2537552
Tel: 079-66304007-11, 55304000/1 (Faridabad Switchgear Works) e-mail: esp-mdu@Lntebg.com
Fax: 079-26580491 12/4, Delhi-Mathura Road
e-mail: esp-ahm@Lntebg.com Faridabad 121 003 North Wing, Level II,
Tel: 0129-2565147 / 8 Gate 7, Powai
38, Cubbon Road, Post Box 5098 Fax: 0129-2275405 Mumbai 400 072
Bangalore 560 001 e-mail: esp-fbd@Lntebg.com Tel: 022-67050505
Tel: 080-25020100 / 25583613 Fax: 022-67051112
Fax: 080-25580525 Milanpur Road, Bamuni Maidan e-mail: esp-bom@Lntebg.com
e-mail: esp-blr@Lntebg.com Guwahati 781 021
Tel: 0361-2550565 8B, Farmland, Ramdaspeth
131/1, Zone II Fax: 0361-2551308 Behind Hotel Radhika
Maharana Pratap Nagar e-mail: esp-gau@Lntebg.com Nagpur 440 010
Bhopal 462 011 Tel: 0712-2420641 / 24
Tel: 0755-6454906 / 7 / 8 / 9 5-10-173, Fateh Maidan Road Fax: 0712-2420619
Fax: 0755-2769264 P. O. Box 12 e-mail: esp-ngp@Lntebg.com
e-mail: esp-bho@Lntebg.com Hyderabad 500 004
Tel: 040-66720251 32, Shivaji Marg, P.O. Box 6223
Plot No. 559, Annapurna Complex Fax: 040-23242356 New Delhi 110 015
Lewis Road e-mail: esp-hyd@Lntebg.com Tel: 011-51419500 / 1 , 51419515
Bhubaneswar 751 014 Fax: 011-51419600
Tel: 0674-2537301, 2436696 D-24, Prithvi Raj Road e-mail: esp-del@Lntebg.com
Fax: 0674-2537309 C-Scheme
e-mail: esp-bbi@Lntebg.com Jaipur 302 001 L&T House, P.O. Box 119
Tel: 0141-2377374 / 2361064 191/1, Dhole Patil Road
SCO 32, Sector 26-D Fax: 0141-2373280 Pune 411 001
Madhya Marg, P. O. Box 14 e-mail: esp-jai@Lntebg.com Tel: 020-66033395 / 88 / 89
Chandigarh 160 026 Fax: 020-26129586
Tel: 0172-4646841 / 2 / 3 / 4 / 5 / 6 / 7 Akashdeep Plaza, 2nd Floor e-mail: esp-pnq@Lntebg.com
Fax: 0172-4646802 P. O. Golmuri
e-mail: esp-chd@Lntebg.com Jamshedpur 831 003 3rd Floor, Vishwakarma Chambers
Jharkhand Majura Gate, Ring Road
10, Club House Road Tel: 0657-2340864, 2340308 Surat 395 002
Chennai 600 002 Fax: 0657-2341250 Tel: 0261-2473726
Tel: 044-28462072 / 4 e-mail: esp-jam@Lntebg.com Fax: 0261-2477078
Fax: 044-28462102 e-mail: esp-sur@Lntebg.com
e-mail: esp-maa@Lntebg.com Skybright Bldg.
M. G. Road Radhadaya Complex
67, Appuswamy Road Ravipuram Junction Old Padra Road
Post Bag 7156 Ernakulam Near Charotar Society
Opp. Nirmala College Kochi 682 016 Vadodara 390 015
Coimbatore 641 045 Tel: 0484-4409422 / 23 / 24 / 25 / 26 / 27 Tel: 0265-6613611
Tel: 0422-2588120, 2588121 / 3 Fax: 0484-4409430 Fax: 0265-2336184
Fax: 0422-2588148, e-mail: esp-cok@Lntebg.com e-mail: esp-bar@Lntebg.com
e-mail: esp-cbe@Lntebg.com
3-B, Shakespeare Sarani 48-8-16, Dwarakanagar
Kolkata 700 071 Visakhapatnam 530 016
Tel: 033-44002301 / 2 / 3 / 4 / 5, 44002572 Tel: 0891-2755493, 2704928
Fax: 033-22821025 Fax: 0891-2746075
e-mail: esp-ccu@Lntebg.com e-mail: esp-viz@Lntebg.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products


Larsen & Toubro Limited
Powai Campus, Mumbai 400 072
Tel: 022-6705 0505
Fax: 022-6705 1746
E-mail: esp@LNTEBG.com
Website: www.LNTEBG.com

SP 50438 120707
L&T SWITCHGEAR
SAFE & SURE

Moulded Case
Circuit Breakers
Introduction

Larsen & Toubro infuses engineering with imagination. The Company offers a wide range of
advanced solutions in the field of Engineering, Construction, Electrical & Automation,
Machinery and Information Technology.

L&T Switchgear, a part of the Electrical & Automation business, is India's largest
manufacturer of low voltage switchgear, with the scale, sophistication and range to meet
global benchmarks. With over five decades of experience in this field, the Company today
enjoys a leadership position in the Indian market with a growing international presence.

It offers a complete range of products including powergear, controlgear, industrial


automation, building electricals & automation, reactive power management, energy meters,
and protective relays. These products conform to Indian and International Standards.

The range, a new generation of MCCBs, stands out due to its state-of-the-art
design, contemporary user-friendly features, wide choice of protective releases,
ergonomics, aesthetics and compactness.

The range complies with the latest standards like IEC 60947-2, EN 60947-2 & IS
13947-2.The products conform to international standards, carry markings and are
& CB certified. The range is specially designed for tropical conditions, ensuring
reliable performance at high ambient and humid environments.

The range is designed to meet the changing needs of users after extensive
analysis and user feedback. The range can satisfy the most demanding system
requirements.

The range, complimented by a wide range of accessories, offer total solution to


customer applications ensuring operational safety, reliability and versatility.

Switchgear Factory, Mumbai


Contents

Range 1

Protection Releases 2

State-of-the-art technology 5

Accessories 7

Technical Data 11

Time - Current Characteristic Curves 13

Overall Dimensions 16

DN0 DN1 DN2 DN3 DN4


The Complete Range

Features
Æ From 20 A to 1250 A
Æ 3 Pole & 4 Pole
Æ Choice of 36kA/50kA/70kA breaking capacities.
Æ With protection releases in Microprocessor, Thermal-Magnetic and only Magnetic
Æ MCCBs for motor backup protection
Æ MCCBs for distribution and SD versions
Æ Manual, rotary or motorised versions
Æ Wide range of internal and external accessories

DN0
Rated Current 20, 25, 32, 40, 50, 63, 80, 100 A
Release Thermal-Magnetic
DN1
Rated Current 100, 125, 160, 200, 250 A
Release Thermal-Magnetic
DN2
Rated Current 32, 40, 50, 63, 80, 100, 125, 160, 200, 250 A 40, 63, 100, 160, 250 A
Release Thermal-Magnetic Microprocessor
DN3
Rated Current 320, 400, 500, 630 A 160, 250, 400, 630 A
Release Thermal-Magnetic Microprocessor
DN4
Rated Current 800, 1000, 1250 A
Release Microprocessor

Breaking Capacities

Breaking Old Type New Type


capacity Designation Designation

36kA S (35kA) D

50kA H N

70kA L S

Note : Since there is no change in the constructional aspect of the MCCBs, the product Certification with old designation
remain valid with new type designation.
1
Protection Releases

Thermal-Magnetic Release

Features of Thermal-Magnetic Release


Adjustable
Æ overload settings
Adjustable
Æ short circuit settings
True RMS sensing
Æ
No contact with live parts
Æ
Protection Settings

DN0 & DN1 DN2 & DN3

Overload 80% - 100% In 80% - 100% In

Short circuit 9 In (fixed) 6 - 10 In

Earth fault External External

Microprocessor Release

6 1 2 3 4 5 Features of RC10 Microprocessor Release


Æ Overload protection with inverse time delay j
Æ Short circuit protection with selectable time delay k
Æ Instantaneous over ride protection
Æ Earth fault protection with selectable time delay l
Æ Neutral protection with selectable time delay m
Æ Push to trip button n
Æ Port for release testing and thermal memory bypass o
Æ Power ON LED p
7 Æ Self powered protections
Æ True RMS sensing

RC10
Rated Current In (A) From 40 to 1250 A
Overload (Phase)
Current setting, Ir (Ir = XIn) OFF, 0.4 to 1.0 in steps of 0.1
Time delay, tr (Inverse) 10 sec at 6Ir
Protection mode ON / OFF
Overload (Neutral)
0.5,0.75 & 1.00 Ir
Current setting, Ir (Ir = XIn)
Inverse 10 sec at 6 Ir / Fixed 200ms
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is =XIr) 1.5, 4 & 6Ir, 8Ir
Time delay, ts Inst. / 100 msec
Protection mode ON / OFF
Instantaneous Over ride
Current setting, Ip DN2-8In, DN3-400-12In, DN3-630-8In, DN4-8In
Earth Fault
Current setting, Ig 0.2 to 0.5In steps of 0.1
Time delay, tg 100 / 200 msec
Protection mode ON / OFF

2
Protection Releases

Microprocessor Release

Features of RC20 - Communication Capable


Communication
Æ using RS 485
Power
Æ on LED
Backlit LCD display
Æ
Scroll buttons
Æ
Push to trip button
Æ
All features of RC10 release are incorporated
Æ
Metering for current parameters
Æ
Protection against unbalanced load / single phasing
Æ
I2t protection
Æ
Neutral protection
Æ
Cold load protection
Æ
User friendly navigation system
Æ
Self powered
Æ
MODBUS RTU protocol
Æ

RC20
Rated Current In (A) From 160 to 630 A
Overload (Phase)
Current setting (A), Ir (Ir = xIn) 0.4 to 1.0 in steps of 0.1
Time delay, tr (s) (Inverse) 3, 6, 10, 15, 30 at 6Ir
Protection mode ON / OFF
Preset trip alarm setting 0.8 to 1.0Ir in steps of 0.05
Thermal memory ON / OFF
Overload (Neutral)
Current setting (A), Ir 50%, 100%, 150% Ir
Protection mode ON / OFF
Short Circuit
Current setting (A), Is 1.5, 4, 6, 8Ir
For – I²t OFF 20 to 200 in steps of 20
Time delay (ms), ts
For – I²t ON 60 to 200 in steps of 20
Protection mode ON / OFF
Preset trip alarm setting 0.8 to 1.0 times Is in steps of 0.05 Is
Cold load pickup Enable / Disable
Instantaneous
Instantaneous 1.5 to 8In in steps of 0.5In / Ir
Protection mode ON / OFF
Cold load pickup Enable / Disable
Instantaneous Over ride
Current setting (A), Ip DN2-8In, DN3-400-12In, DN3-630-8In, DN4-8In
Earth Fault
Current setting (A), Ig 0.2 to 0.5In steps of 0.1In
Time delay (ms), tg 0.1, 0.2, 0.5, 1, 3 sec.
Preset trip alarm setting 0.8 to 1.0 Ig in steps of 0.05
Protection mode ON / OFF
Cold load pickup Enable / Disable

3
Protection Releases

Additional Features of RC20


Current Unbalance
Current setting (A) xIn 10% to 100% In in steps of 5%
Time delay (s) 1 to 10 in steps of 0.5
Protection mode ON / OFF
Cold load pickup Enable / Disable
Temperature Rise
Alarm / Trip At 80ºC / At 100ºC
Metering
Current Phase, Neutral and Earth
Display Backlit LCD
Communication*
Protocol MODBUS RTU
Link used RS 485
Event records Pickup, Trip, Alarm upto 128 records-volatile memory
Trip history Last 5 trips records - non volatile memory
Trip counter record Counts for total number of trips

Only Magnetic release Frame 250 A 400 A 630 A


(for Motor backup protection) Type DN2-250M DN3-400M DN3-630M

Only magnetic
Æ with instantaneous protection upto 10In Current Range (A) 100-250 320-400 500-630

Fault level
Æ protection for complete starter upto 50kA Poles 3P only

Type 2 charts available for DOL & Star/delta starters


Æ Icu(kA) @ 415V AC, 50Hz 50

Frame 250 A 400 A 630 A

Switch Disconnector version Type DN2-250SD DN3-400SD DN3-630SD

(without protection release) Current Range (A) 100-250 320-400 500-630

Poles 3/4 3/4 3/4


Can be
Æ used as switching or Isolator devices
Icw (kA) for 1sec. 3.6 6 6
Higher withstand capacities
Æ
Wide range of accessories for remote operation
Æ

* To establish communication with computer every MCCB with RC20 will require a communication module.

4
State-of-the-art technology

Faster
Æ tripping
The unique speed contact system accelerates the opening of
contacts during short circuit. This ensures faster tripping an
ultimate current limiting feature. The result-very low let-through,
cut-off current and fault clearing time

Mechanical
Æ Anti-reclosing
This unique feature ensures that under short circuit conditions,
the contacts open and latch even before the release gives a trip
command to the mechanism. This avoids contact re-closing
and bounce

Low
Æ watt loss
The entire current carrying path is optimally designed to achieve
very low watt loss

Positive
Æ Isolation
The MCCB knob indicates the true position of the
contacts

Double
Æ Insulation
U e : 4 15V, 5 0 / 6 0Hz.
U im p : 8k V
DN3-630N
The internal accessories are housed in insulated
CAT: A
I cu : 50 kA,I cs :100%I cu
IS 13947-2 IEC 60947-2
EN 60947-2
casings to ensure first level of insulation. When the
front cover is opened for the fixing of internal
accessories, the MCCB is totally insulated ensuring
the double insulation

Marking
Æ

CE Marking ensures use of superior engineering


plastic, meeting all requirements of flammability and
glow wire testing path is optimally designed to
Extra Grip achieve very low watt loss
on Handle

5
State-of-the-art technology

Common
Æ Internal accessories
V
0 H z. U imp : 8k

The internal accessories remain same across DN0 / DN1 U e : 4 1 5 V, 5 0 /6 DN3-630N


I cu C AT: A
I cu : 50 k A ,I cs :100% 2
EN 60 947-
I E C 609 47-2
IS 1394 7- 2

& DN2 / DN3 / DN4* and they are easy to install snap fit U e :41 5 V, 5 0/6
0 Hz. U im p :8kV
I cu :70kA, I cs :100%I
cu
CAT: A

EN 6 09 4 7-
2
DN2-250S

-2
I EC 6 0 94 7

type
I S 1 3 94 7 -2

LINE
No load
Æ line bias
Either side of MCCB terminal can be used as load or line
U i m p :8 k V DN2-250S
U e :415V, 50/60Hz. CAT:A
I cu :70 k A,I cs :100%I
cu

-2
2 EN 60947
2 I E C 60 9 47-
IS 13947-

LOAD

Terminal
Æ finger proofing
Front terminal plates conceal the terminals to prevent human
contact thus achieving complete finger proofing

Release
Æ shrouding
Release is shrouded from the front thus preventing tampering
by unauthorized person

Safer
Æ release adjustments
No live parts are in contact during release adjustments

Common
Æ front adjustments for protection release
Overload & short circuit setting can be adjusted from front
using a common knob for all the poles

Visibility
Æ

Push to trip button and release ratings are visible even when
release plate is fitted

* Except under voltage release.

6
Accessories

Internal Accessories

Range of MCCBs are offered with snap-fit type,


easily installable internal accessories. There is no need to
open main cover and no live parts are accessed during
installation. TAC, Aux+TAC to be fitted in the right cavity &
under voltage release to be fitted in left cavity.

Auxiliary Contact

List of Internal Accessories U i mp : 8 k V


U e :41 5 V, 50/60H
I c u : 7 0kA,I c s :
z. U im p :8kV
100 % I c uCAT:A
EN 60947
-2
DN2-250S

U e :41 5 V, 50/60Hz. DN2-250S IS 13947-


2 IE C 6 0947-2
CAT:A
I c u : 7 0kA,I cs :100%I
cu

-2

Auxiliary Contact 1 C/O


EN 6 0947
IEC 60947-2

Æ
IS 13947-2

Auxiliary
Æ Contact 2 C/O
Trip Alarm Contact
Æ
Auxiliary & Trip Alarm Contact
Æ
Shunt Release
Æ
Under Voltage Release
Æ

MCCB with mid cover opened


& Internal accessories fitted

External Accessories

Extended Rotary Handle (Panel Mounted)


Æ ROM mounts directly on MCCB without removal
of mid cover
Æ Clear ON/OFF/TRIP indication
Æ Clear view of MCCB rating label with
ROM mounted U e : 4 1 5V,

IS 139 4 7-2
5 0 / 6 0 H z.
,I :100% c u
I cu : 50kA c s
IEC 6 0947-2
U imp: 8 k V
I C AT: A
EN 6 0947-2
DN3-630N

Æ Direct access to push to trip button with


ROM mounted
Æ IP 54 degree of protection with extended
rotary handle
Æ Unique coupling to allow +3mm tolerance
Æ Door interlock in ON position, with defeat facility
Æ Door interlock in OFF condition with Panel Door Mounted
Extended Rotary Key lock
padlock feature (To be used along with
Handle:
Æ Auto restoration of door interlock Panel Mounted extended rotary handles)
Æ External keylock for mechanical interlocking

Rotary Operating Mechanism


The rotary operating mechanism (ROM) for MCCBs are available in
U e : 41 5 V,
50 /60 Hz .
,I :100 % cu
U : 8kV
im p

I C AT: A
DN3-630N
Direct & Extended versions.
I c u : 50kA cs E N 60947-2
IEC 60947-2
IS 13947-2

Direct rotary handle (MCCB mounted)


These versions are available for the entire family of
MCCBs.

7
Accessories

Mechanical Interlocking Schemes

1. Mechanical Interlocking Kit:


Two MCCBs can be interlocked using base plate
mechanism, in side-by-side configuration.

Features
For 3 Pole
Æ & 4 Pole versions U e : 4 1 5 V, 5
0 /6 0H z . U imp
I cu : 50 k A,I cs
:10 0 %I cu CA
I EC 60 9 47
-2
: 8 kV
T: A
E N 60 9 47 -
2
DN3-630N

IS 1 3 947-2

For DN2
Æ & DN3 frames U e : 41 5V, 5
0/ 60 H z . U imp
I cu : 50kA,I cs
IS 1 3 94 7 - 2
:1 0 0% I cu CAT:
: 8k V

E N 6 09 47 -
I EC 60 9 47
-2
A
2
DN3-630N

Site fittable
Æ

MIL with Base Plate

2. Mechanical Interlocking using Key locks:


For mechanical interlocking through Extended Rotary operating mechanism,
a panel mounted key lock is available. The selection of the key lock as per the
following details,

2 l/C Any 1 type of lock for both MCCBs

2 I/C and 1 B/C Lock 1 and Lock 2 for I/C and Lock 12 for B/C

3 I/C and 2 B/C Locks 1, 2, 3 for I/Cs and Locks 12, 23 for B/Cs

Key Lock Selection


I/C1 I/C2 I/C3

Incommers (I/C)
Lock 1 Lock 2 Lock 3

Bus couplers (B/C)


Lock 12 Lock 23

B/C1 B/C2

Type of lock Exclusively operable by Key Nos.

1 1

2 2

3 3

12 1, 2 & 12

23 2, 3 & 23

8
Accessories

External Neutral CTs

Features
Add on
Æ accessory for 3P MCCB
Reliable
Æ solution for Earth / Neutral fault protection
for 3 Phase 4 wire system

Stored Energy Electrical Operating Mechanism

Features
Æ ON / OFF & Charged/Discharged indication
Æ Foolproof mounting
Æ Selector switch for Auto/Manual operation
Æ Padlock facility for locking in OFF position(3 nos locks)
Æ Resetting time < 250msec & Closing time< 90 msec
Æ Higher mechanical & electrical endurance
Æ Back up fuse for extended motor protection
Æ Easy access to the protection setting on MCCB
Æ True indication for ON/OFF & Trip

DN3 SE EOM data sheet

Operating voltage (V AC) 240

Operating voltage (%) 85-110%

Closing time (ms) 90

Opening time (ms) 250

Power consumption (VA) 500

Life / No. of operations 5000

Door cut out (mmXmm) 96X96

IP protection, on the front IP30

Operating frequency 1/min

Min. control impulse time (ms) 200

9
Accessories

Automatic Source Transfer Switch Controller AuXC-1000

The AuXC-1000 controller brings simplicity and


AUTO TRANSFER CONTROLLER AuXC-1000
flexibility to an auto source transfer system. It has been

448 448
LINE 1 LINE 2

ALARM
developed to control and supervise the automatic or
TEST
manual transfer of a utility load from a principal power
L1 L2 L3 Hz L1 L2 L3 Hz

TEST
supply source to a stand-by. It sets a new benchmark in
Auto source transfer switch controller technology.
AUTO

ON ON It includes all the necessary features to supervise and


OFF OFF MANUAL
control power supply sources, composed by energy
ON ON
WITHDRAWN
TRIP
WITHDRAWN
TRIP
distribution systems or generating sets, and the relative
OFF/RESET
transfer equipment, such as contactors, motorized
LOAD
A01 LOW BATTERY VOLTAGE A04 LINE 2 SWITCH FAULT A07 LOAD NOT POWERED T. OUT
moulded case circuit breakers and air circuit breakers.
A02 HIGH BATTERY VOLTAGE A05 LINE 1 WRONG PHASE SEQ. A08 GENERATOR NOT READY
A03 LINE 1 SWITCH FAULT A06 LINE 2 WRONG PHASE SEQ. A09 EMERGENCY STOP

The automatic transfer takes place through AuXC-1000 whenever


conditions predefined by the user take place, for example:
Æ Power supply source not respecting programmed limits
Æ The need to have a very reliable power source
Æ The need to use the most economical power source

Some of the key features of this controller are:


Æ Front display for monitoring the system voltage and frequency and for
onsite controller programming
Æ Six programmable inputs and five programmable outputs
Æ Front test feature to simulate the operation of the diesel generator set
Æ Status indication through 22 LEDs
Æ Flush mounting arrangement
Æ Communication capable

The AuXC-1000 controller is compatible with U-Power range of Air circuit


breakers, range of MCCBs and MCX range of contactors.

+
AuXc-1000

MIL with Base Plate & EOM

10
Technical Data

TESTED

Frame 100 A 250 A 250 A 400 A 630 A 800 / 1000 / 1250 A


DN0-100 DN1-250 DN2-250 DN3-400 DN3-630 DN4-1250
Type
D N D N S D N S D N S N S
Current Range (A) 20, 25, 32, 40, 50, 63, 80 & 100 A 100, 125, 160, 200, 250 A 32, 40, 50, 63, 100, 125, 160, 200 & 250 A 63, 160, 250, 320, 400 63, 160, 250, 320, 400, 630 A 800, 1000, 1250
Poles 3/4 3/4 3/4 3/4 3/4 3/4
Impulse withstand Voltage (kV) 6 6 8 8 8 8
Rated Operational Voltage (V) (MAX) 600 600 690 690 690 690
Rated Insulation Voltage (V) 690 690 750 750 750 750
Utilisation Category A A A A A A
Standard IEC / EN / IS IEC / EN / IS IEC / EN / IS IEC / EN / IS IEC / EN / IS IEC / EN / IS
230 / 240 V 65 65 65 70 100 65 70 100 65 70 100 70 100
400 / 415 V 36 50 36 50 70 36 50 70 36 50 70 50 70
500 V 10 10 36 36 36
IEC-60947-2

25 42 25 42 25 42 25 36
550 V 8 8 18 25 36 15 20 25 15 20 25 20 25
Icu
(kA) 600 V 5 5 16 18 22 12 18 22 12 18 22 16 20
690 V 10 15 20 8 15 20 8 10 15 10 18
250 V DC (3P in series) 15 15 15 25 36 15 25 36 15 25 36 - -
500 V DC (3P in series) L/ R<15msec 5 10 5 10 20 5 10 20 5 10 16 - -
Ics as % lcu 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Life span Mechanical 30000 10000 25000 15000 15000 8000
Electrical @1.0 In 4000 3000 10000 4000 2000 750
Operating Frequency (Hz) 50 / 60
Total Opening Time <10 msec <20 msec
Finger-proof Terminals Yes
0 0
Ambient Temperature -5 to 55 C
Storage Temperature -350 to 700 C
Mounting Positions Vertical and 900 in both directions
Dimensions (W x D x H) 3-Pole 75 x 60 x 130 105 x 60 x 165 105 x 96 x 179 140 x 111.5 x 266 140 x 111.5 x 266 278 x 143 x 370
3
mm 4-Pole 100 x 60 x 130 140 x 60 x 165 140 x 96 x 179 183.5 x 111.5 x 266 183.5 x 111.5 x 266 278 x 143 x 370
Weight (kg) (3/4 Pole) 1 / 1.25 1.45 / 1.8 2.5 / 3.3 5.5 / 7.2 6 / 7.8 15 / 16
Auxiliary Contact 1C/O or 2C/O 1C/O or 2 C/O 1C/O or 2C/O 1C/O or 2C/O 1C/O or 2C/O 1C/O or 2C/O
A
Trip Alarm Contact 1C/O or 2C/O 1C/O or 2 C/O 1C/O 1C/O 1C/O 1C/O
C
Auxiliary & Trip Alarm Contact 1C/O + 1C/O 1C/O + 1 C/O 1C/O + 1C/O 1C/O + 1C/O 1C/O + 1C/O 1C/O + 1C/O
C Internal
Shunt Release $ 240 / 415 V AC 50 / 60 Hz 240 / 415 V AC 50 / 60 Hz 110 / 415 V AC 50 / 60 Hz, 110 / 220 V DC 110 / 415 V AC 50 / 60 Hz,110 / 220 V DC 110 / 415 V AC 50 / 60 Hz,110 / 220 V DC 110 / 415 V AC 50 / 60 Hz, 110 / 220 V DC
E
Under Voltage Release 240 V AC 50 Hz 240 V AC 50 Hz 220 - 240 V AC 50 Hz 220 - 240 V AC 50 Hz 220 - 240 V AC 50 Hz 220 - 240 V AC 50 Hz
S
Rotary Operating Mechanism P P P P P P
S
Electrical Operating Mechanism x x P P P x
O
Earth Fault Release Available with external GF module with TM release Available with external GF module with TM release and Inbuilt protection with Microprocessor release
R External
Mechanical Interlock x x P P P x
I
Spreader Links P P P P P P
E
Key lock x x P P P P
S
Pad lock through ROM P
# P P P P P
$ : ‘NO’ of control contactor to be connected in series for 220V DC application.
Note: l Any two internal accessories can be mounted at a time
l For special application like capacitor switching, DC please contact nearest branch office
l For motor application, use ‘M’ series MCCBs (DN2M, DN3M)
* Available on request.
# Direct Pad locking available

11 12
Time - Current Characteristic Curves

Thermal-Magnetic Release

DN0-100 DN1-250
10000 10000

1000 1000

100
100
Time in Seconds

Time in Seconds
10
10

1
1

0.1
0.1

0.01
0.01
2 4 6 8 1 10 100
1 10 20

Multiples of Current Multiples of Current

DN2-160/250 DN3-400/630
10000 10000

1000 1000

100 100
Time in Seconds

Time in Seconds

10 10

1 1

0.1 0.1

0.01 0.01

2 4 6 8 2 4 6 8 2 2 4 6 8 2 4 6 8 2
1 10 100 1 10 100
Multiples of Current Multiples of Current

13
Time - Current Characteristic Curves

Microprocessor Release-RC10

DN2-250A DN3-400A
10000 10000

1000 1000

100 100
Time in Seconds

Time in Seconds
10 10

1 1

100% In 40% In 100% In 40% In


0.1 0.1

0.01 0.01
2 4 6 8 2 4 2 4 6 8 2 4
1
1 10 10
Multiples of Current Multiples of Current

DN3-630A DN4-1250A
10000 10000

1000 1000

100 100
Time in Seconds

Time in Seconds

10 10

1 1

100% In 40% In
100% In 40% In
0.1 0.1

0.01 0.01
2 4 6 8 2 4 2 4 6 8 2 4
1 10 1 10
Multiples of Current Multiples of Current

14
Time - Current Characteristic Curves

Microprocessor Release-RC20

DN2-250A DN3-400A
10000 10000

30 sec
1000 1000 30 sec
15 sec
15 sec
10 sec
10 sec
6 sec
6 sec
3 sec
3 sec
100 100
Time in Seconds

Time in Seconds
10 10

1 1

100% In 40% In
100% In 40% In
0.1 0.1

0.01 0.01
2 4 6 8 2 4 2 4 6 8 2 4
1 10 1 10
Multiples of Current Multiples of Current

DN3-630A DN4-1250A
10000 10000

1000 30 sec 1000 30 sec


15 sec 15 sec
10 sec 10 sec
6 sec 6 sec
3 sec 3 sec
100 100
Time in Seconds

Time in Seconds

10 10

1 1

100% In 40% In 100% In 40% In


0.1 0.1

0.01 0.01
2 4 6 8 2 4 2 4 6 8 2 4
1 10 1 10
Multiples of Current Multiples of Current

15
Overall Dimensions

DN0-100 MCCB
100 (4 pole) 20
12.5
25 25 25
75 (3 pole)
6.9

61.5
62.5

58
38
45
130
116.4

N
s
60
85

Suitable for 35 x 7.5


Top Hat Rail Mounting
25.5 25
M3-Ø2.4

2.25
29.5
48.5

52

76
25
112

Recommended CAT number for DN0 spreaders


Cut-out 1
3P 4P
39
46

or
CM97785OOOO CM97921OOOO
Cut-out 2

Note : Spreaders are available as spare

Mounting & Door Cutout Details

DN0-100 with Spreader Links

92 127
86.1
35 35 35
35 35 60

20 2
130
116.4
194.2

N
172.2

130

s
30.2

35 35 35 20
127
11

22

Note : Spreaders are available as spare. It is recommended to use spreader links


for enhancing termination capacity
All dimension are in mm

16
Overall Dimensions

DN1-250 MCCB

60

35 35 35
18
Mounting Panel
35 35
17.5
126
165

145

126
N

35 35 For Four Pole


64.5
105(3P)

140(4P)

93.7

DN1-250 with Spreader Links

18
35 35 4
18
38

54 54 54

197
221
257

Spreader Link 4P MCCB

Hardware

54.5 54.5 18

72 72

Spreader Link 3P MCCB

All dimension are in mm

17
Overall Dimensions

DN2-250 MCCB
120 35 35

97.5

8
17.5 17.5
28.6

61
72.7

157
163

ON

46.5
N TRIP
OFF
179

45
43 43
86
35 35 35 17.5

105
A Mounting & Door
140 Cut-out Details

Terminal width = 25.5.mm

DN2-250 3P DN2-250 4P
with Spreader Links with Spreader Links
28.6
54.5 54.5 54.5
35 4

18
18

38

Ø10
38

ON
275

ON
239

TRIP N TRIP
OFF OFF

4 Wider gap 20 35
54.5 54.5
A = =
= =
144 198.5

Rating Dimension (A)

125-250A TM 26

63-100A TM 25.5 Recommended CAT number for DN2 spreaders


32-50A 26.25
3P 4P
RC breakers 28
ST98053OOOO CM92007OOOO

Note : Spreaders are available as spare. It is recommended to use


spreader links for enhancing termination capacity.
All dimension are in mm

18
Overall Dimensions

DN3-400/630 MCCB

43.5 43.5
183.4
= =
140

16

82.7
136.8
142

ON
234

224
TRIP

78
OFF

43.5 26.5

43.5 43.5 121

= =

Mounting & Door


Cut-out Details
Terminal width = 28mm

DN3-400/630 3P DN3-400/630 4P
with Spreader Links with Spreader Links
165 177.8
224.5
62 60.5 62 111.5
62.5 62.5
22 Wider gap
A

Ø13
ØF
142

266

ON
234

ON
TRIP TRIP
E

OFF OFF
C

43.5 26.5 B 5

43.5 43.5 142


Wider gap 22.5
23

40

Type DN3-400 DN3-630

A 39 41

B 37 38
Recommended CAT numbers for DN3 spreaders
C 45 55

D 324 344 Rating 3P 4P


E 370 390 400A ST98065OOOO ST98066OOOO

Note : Spreaders are available as spare. It is recommended to use F 13 11 630A ST98054OOOO CM92004OOOO
spreader links for enhancing termination capacity.
All dimension are in mm

19
Overall Dimensions

DN4-800/1000/1250 MCCB

143
4 POLE 182

68 68 68 57
C

85
20

109.5
132.5

326

107
24

370

105
68 68
330

N
85

46
179.5 195

- 46 (N version)
278
* 42 (S version)

DN4-800 MCCB DN4-1000/1250 MCCB DN4-800/1000/1250 MCCB


with Spreader Links with Spreader Links 195
A A A A A A 143
46
15
15

Wider 28
gap
C
85

132.5
510

510

105
370

N N
85
15

15

60 24 60 24 46
B B

Dimensions Recommended CAT numbers for DN4 spreaders


Type A B C Rating 3P 4P

800A 88 324 6 800A ST90361OOOO ST90362OOOO

1000/1250/1600A 80 300 20 1000A /1250A ST98055OOOO ST98058OOOO

Note : Spreaders are available as spare. It is recommended to use


spreader links for enhancing termination capacity.
All dimension are in mm

20
ROM Door cut-out details

Direct ROM door cut-out detail

L5

L4
N

L3
L2

L1

L1 = Mounting Depth Type L1 L2 L3 L4 L5


L2/L3 = Panel Cut-out
DN0 96.5 58 52 43.5 37
L4/L5 = Breaker Mounting Refer
DN1 96.5 73 52 56.5 54

DN2 122 96 63 53 66

DN3 146 121 87 78 82

Extended ROM door cut-out detail

L2
Ø50

0
45
L3

Ø76

N Ø4

L1=Minimum Panel Depth suggested

L
Refer Panel Cut Details
Refer Panel Cut Details
L = Length of Shaft Required for Panel Depth L1
Total Length of Shaft =275mm
TYPE L1 L L2 L3

DN0 169 L1 - 119 7.5 69.5

DN1 169 L1 - 119 24.5 81.7

DN2 202 L1 - 152 27 84

DN3 233 L1 - 183 39 122

DN4 302 L1 - 252 69 170

All dimension are in mm

21
Overall Dimensions

MCCB with EOM (Stored Energy)


DN3
264
256
43.5

Mounting holes for MCCB = =


Door

45 49

62.1
94

Door cut out

N
94
224

Cat. No.

CM98130OOOO

Panel Mounted Key Lock

72 48.5 2 Holes, Ø4.2


Ø76

Ø50
Ø50
450
136

68

68

Cut-out for Handle Assembly


12

58 52

Ø29
Cut-out for Panel Mounted Key Lock
2.2

All dimension are in mm

22
Overall Dimensions

DN2 MIL Kit

372
Ø10 Mounting Holes
141 141
36

179
209
239

Holes for Breaker Mounting


141 141

DN3 MIL Kit

Ø10 Mounting Holes


436

161 161 56
346
316

266

161 161 Holes for Breaker Mounting

All dimension are in mm

23
Overall Dimensions

External Neutral CTs

DN2 / DN3
K

G
B

F
D

G
H
J

Bottom Side Bottom Side

ØF

A B C D E F G

DN2 250A 93 59 47 81 35 10.2 77

DN3 400A 93.5 58 46 81.5 40 13 63.5

DN3 630A 93.5 58 46 81.5 40 10.5 63.5


Adaptor Terminal

H J K L M

DN2 250A 153 189 26 4 55

DN3 400A 153.5 199.5 39 5 60

DN3 630A 173.5 219.5 39 5 60

ON

TRIP

Note: Adapter Terminals shown are not available with product. OFF
kindly refer accessories data for ordering separately.
Circuit Breaker shown for reference only.

Bottom Side

>M

All dimension are in mm

24
Overall Dimensions

External Neutral CTs

DN4
M N
H

G
K
D
A

ØF
E

DN4 A B C D E F G

800A 132 88.5 73.5 117 60 12.5 92

1000/1250A 132 88.5 73.5 117 60 12.5 92

DN4 H J K L M N

800A 24 302 272 80 73.5 6

1000/1250A 24 302 272 80 73.5 20

Note: Adapter Terminals shown are not available with product.


kindly refer accessories data for ordering separately.
Circuit Breaker shown for reference only.

Special Note: Adapter Terminals for DN4 range of product are not symmetrical.
Kindly insure proper orientation in assembly as shown in figure below.

>L

All dimension are in mm

25
Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND L&T House, Group MIG-5 No: 73, Karpaga Nagar, 8th Street
HEAD OFFICE Padmanabhpur K. Pudur
L&T House, Ballard Estate Durg 491 001 Madurai 625007
P. O. Box 278 Tel: 0788-2213833 / 14 / 21 / 29 Tel: 0452-2537404, 2521068
Mumbai 400 001 Fax: 0788-2213820 Fax: 0452-2537552
Tel: 022-67525656 e-mail: esp-durg@LNTEBG.com e-mail: esp-mdu@LNTEBG.com
Fax: 022-67525858
Website: www.Larsentoubro.com Khairasol, Degaul Avenue EBG North Wing Office-Level 2
Durgapur 713 212 Gate 7, Powai Campus
ELECTRICAL STANDARD PRODUCTS (ESP) Tel: 2559848, 2559849, 2559844 Mumbai 400 072
501, Sakar Complex I Fax: 0343-2553614 Tel: 022-67052874 / 2737 / 1156
Opp. Gandhigram Rly. Station e-mail: esp-dgp@LNTEBG.com Fax: 022-67051112
Ashram Road e-mail: esp-bom@LNTEBG.com
Ahmedabad 380 009 Milanpur Road, Bamuni Maidan
Tel: 079-66304006-11 Guwahati 781 021 12, Shivaji Nagar
Fax: 079-66304025 Tel: 0361-2550562 / 65 North Ambazari Road
e-mail: esp-ahm@LNTEBG.com Fax: 0361-2551308 Nagpur 440 010
e-mail: hazrasudipto@LNTEBG.com Tel: 0712-2260012/3
38, Cubbon Road, P. O. Box 5098 Fax: 0712-2260020/30
Bangalore 560 001 II Floor, Vasantha Chambers e-mail: esp-nag@LNTEBG.com
Tel: 080-25020100/25020324 5-10-173, Fateh Maidan Road
Fax: 080-25580525 Hyderabad 500004 32, Shivaji Marg
e-mail: esp-blr@LNTEBG.com Tel: 040-66720250 P. O. Box 6223
Fax: 040-23296468 New Delhi 110 015
131/1, Zone II e-mail: esp-hyd@LNTEBG.com Tel: 011-41419514 / 5 / 6
Maharana Pratap Nagar Fax: 011-41419600
Bhopal 462 011 D-24, Prithvi Raj Road, C-Scheme e-mail: esp-del@LNTEBG.com
Tel: 0755-4098721/7/ 8 / 9 Jaipur 302 001
Fax: 0755-2769264 Tel: 0141-2385915 / 16 / 17 / 18 L&T House
e-mail: esp-bho@LNTEBG.com Fax: 0141-2373280 P. O. Box 119
e-mail: esp-jai@LNTEBG.com 191/1, Dhole Patil Road
Plot No. 559, Annapurna Complex Pune 411 001
Lewis Road Akashdeep Plaza, 2nd Floor Tel: 020-26135048/26164048
Bhubaneswar 751 014 P. O. Golmuri Fax: 020-26124910, 26135048
Tel: 0674-6451342, 2436696 Jamshedpur 831 003 e-mail: esp-pnq@LNTEBG.com
Fax: 0674-2537309 Jharkhand
e-mail: esp-bbi@LNTEBG.com Tel: 0657-2312205 / 38 3rd Floor
Fax: 0657-2341250 Vishwakarma Chambers
SCO 32, Sector 26-D e-mail: esp-jam@LNTEBG.com Majura Gate, Ring Road
Madhya Marg, P. O. Box 14 Surat 395 002
Chandigarh 160 026 Skybright Bldg; M. G. Road Tel: 0261-2473726
Tel: 0172-4646840, 4646853 Ravipuram Junction, Ernakulam Fax: 0261-2477078
Fax: 0172-4646802 Kochi 682 016 e-mail: esp-sur@LNTEBG.com
e-mail: esp-chd@LNTEBG.com Tel: 0484-4409420 / 4 / 5 / 7
Fax: 0484-4409426 Radhadaya Complex
10, Club House Road, e-mail: esp-cok@LNTEBG.com Old Padra Road
Annasalai Near Charotar Society
Chennai 600 002 3-B, Shakespeare Sarani Vadodara 390 075
Tel: 044-28462072 / 4 / 5 / 2109 Kolkata 700 071 Tel: 0265-6613610 / 1 / 2
Fax: 044-28462102 / 3 Tel: 033-44002572 / 3 / 4 Fax: 0265-2336184
e-mail: esp-maa1@lntebg.com Fax: 033-22821025/7587 e-mail: esp-bar@LNTEBG.com
e-mail: esp-ccu@LNTEBG.com
67, Appuswamy Road 48-8-16, Dwarakanagar
Post Bag 7156 A28, Indira Nagar, Faizabad Road Visakhapatnam 530 016
Opp. Nirmala College Lucknow 226 016 Tel: 0891-6620411-2 / 3
Coimbatore 641 045 Tel: 0522-2312904 / 5 / 6 Fax: 0891-6620416
Tel: 0422-2588120 / 1 / 5 Fax: 0522-2311671 e-mail: esp-viz@LNTEBG.com
Fax: 0422-2588148 e-mail: esp-Lko@LNTEBG.com
e-mail: esp-cbe@LNTEBG.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products


Larsen & Toubro Limited
Powai Campus, Mumbai 400 072
Customer Interaction Center (CIC)
BSNL / MTNL (toll free) : 1800 233 5858
Reliance (toll free) : 1800 200 5858
Tel : 022 6774 5858
Fax : 022 6774 5859
E-mail : cic@LNTEBG.com
Website : www.LNTEBG.com

SP 50290 R4 160112
Moulded Case Circuit Breakers
DU Series
About us

Larsen & Toubro is a technology-driven company that infuses engineering with


imagination. The Company offers a wide range of advanced solutions in the field of
Engineering, Construction, Electrical & Automation, Machinery and Information
Technology.

L&T Switchgear, a part of the Electrical & Automation business, is India's largest
manufacturer of low voltage switchgear, with the scale, sophistication and range to
meet global benchmarks. With over five decades of experience in this field, the
Company today enjoys a leadership position in the Indian market with a growing
international presence.

It offers a complete range of products including powergear, controlgear, industrial


automation, building electricals & automation, reactive power management, energy
meters, and protective relays. These products conform to Indian and International
Standards.

Switchgear Factory, Baroda

Index

Description Page No.


Introduction 2

Salient Features 2

Technical Specifications 3

I-T Characteristics Curves 4

Overall Dimensions 5
Introduction

The DU Series, a new generation of MCCBs, stands out due to its state-of-the-art design, contemporary user-
friendly features, ergonomics, aesthetics and compactness.

DU100H/DU250 Series complies with the latest standards like IEC 60947-2, EN 60947-2 & IS/IEC 60947-2.The
products conform to international standards, carry marking and are & CB certified. The range is
specially designed for tropical conditions, ensuring reliable performance at high ambient and humid
environments. The range can satisfy the most demanding system requirements.

The DU Series, has a wide range of accessories, ensuring operational safety, reliability and versatility.

Salient Features

Ergonomic design &


Technology user friendliness Compact
Specially
l designed arc suction effect Knob
l designed for better grip Compact
l size
& speedo quench contact system Color
l indication of ON/TRIP/OFF* Common
l depth throughout the range
No load line bias: Either side of
l Current rating on the knob
l Suitable for side by side mounting
l
MCCB terminal can be used as load Overload adjustment from front*
l Suitable for use in Distribution Board
l
and line* Easy ON/OFF/RESET operations
l
Wide variety of snap fit accessories*
l

Internal Accessories External Accessories Easy to Install


Auxiliary
l contacts Direct
l & Extended ROM 45mm
l door cutout*
Trip alarm
l contacts* Spreader
l links Optional
l DIN rail mounting
Combined Auxiliary + Trip alarm
l Padlock is available (with ROM)
l available**
contacts* SS Enclosure**
l
Shunt release
l GF module for earth fault protection
l
Under Voltage release*
l

Safe to Use
Finger
l proof terminals
Lockable
l shroud on thermal knob to prevent unauthorized operation*
l marked range*
Double Insulation: The internal accessories are housed in insulated casings to ensure
l
first level of insulation. When the front cover is opened for the fixing of internal
accessories, the MCCB is totally insulated ensuring the double insulation*

* For DU100H & DU250 3P & 4P MCCBs


** For DU100 & DU100H 2
Technical Specifications

DU Series
Technical Parameters Specification

Type Designation DU100 DU100H DU250

No. of Poles 3 2/3/4 3/4

Rated Current In (A) 16,20,25,32,40,50,63,80,100 20,25,32,40,50,63,80,100 100,125,160,200,250

Impulse withstand voltage Uimp (kV) 6

Rated operational voltage Ue (V) 415

Rated insulation voltage Ui (V) 690

Operational frequency (Hz) 50 / 60


Utilisation Category A
0
Reference Temperature 50 C 40°C
Operating Temperature -5°C to + 55°C
240V a.c. 25 65 65
415V a.c. 10 30 36
Icu (kA)
250V d.c (3P in series) L/R<15 msec 5 15 15

500V d.c. (3P in series) L/R<15 msec - 5 5

Rated Service S. C. Breaking


50% of lcu
Capacity (Ics)

Mechanical Life No. of operations 20000 30000 10000

Electrical Life No. of operations 6000 4000 3000

IP Protection (from front side) IP40

Pollution Degree III

Type of Release Thermal - Magnetic

Thermal Fixed Variable (0.8 - 1.0In)

Magnetic Fixed (9In)

Terminal Capacity (without spreaders)

Cables with Lug (mm2) 50 35 120

Link (mm) <17 <26

Overall Dimensions

Width (mm) 75 75/75/100 105/140

Height (mm) 130 130 165

Mounting Depth (mm) 60 60 60

Weight (2/3/4 Pole) (kg) 0.68 0.6/0.73/1 1.45/1.8

3
I-T Characteristics Curves

DU100/DU100H
10000

1000

100
Time in Seconds

10

0.1

0.01

0.001
-1 2 3
10 1 10 10 10

Current multiples

DU250
10000

1000

100
Time in Seconds

10

0.1

0.01

0.001
10-1 1 10 102 103

Current multiples

4
Overall Dimensions
DU100
3-Pole 3-Pole with spreaders 3-Pole
75
12.5 25 25 60
7.5

10

115

171

130
193
115

110

45
28
75 2
25 25 Screw M6 Terminal
Ø9 26
27.4

35 35
79.6
92

10
24

DU100H
3-Pole, 4-Pole 3-Pole with 4-Pole with 3-Pole, 4-Pole
spreaders spreaders
86.1
100 (4 pole) 92 127
35 35 65
12.5 35 35 35 61
25 25 25
75 (3 pole)
6.9
9

Terminal
4.5
194.2
172.2
116.4

116.4
130

130

N N
s s
11 30.2

20
32.1

22 35 35 35
127

For 2-Pole MCCB, refer 3-Pole dimensions. Spreader links are available as spare. It is recommended to use spreader links for enhancing termination capacity.

DU250
3-Pole, 4-Pole 3-Pole with 4-Pole with 3-Pole, 4-Pole
spreaders spreaders
35 35 35 35 35 60
18

35 35 35
38
221
126
165

145

126
165
145
257

N N

35 35
64.5
105 (3P)
4
140 (4P) 54.5 54.5 54 54 54 18
72 72 197 93.7
105 (3P)
140 (4P)

Spreader links are available as spare. It is recommended to use spreader links for enhancing termination capacity.

5 All dimensions are in mm


Panel Cut-out Dimension
DU100 DU100H DU250
For Fixing Mounting Panel 35 35
the MCCB
25 25 25 M3-F2.4
Use Screw 70.5 70.5
M4x55-4 Nos.
2.25
29.5

48.5
52
25 76
141
141

58.6
112
26 108
Cut-out 1 42.6
47

39
46

126
110

OR
Cut-out 2

46
N

Neutral Pole Door Cut-out Dimensions


M4-Ø3.5

For Four Pole 38.8

ROM Mounting Dimension


Direct ROM

L5
L4

Type L1 L2 L3 L4 L5

DU100 133 - - - -
L3

DU100H 96.5 58 52 44 37

DU250 96.5 75 52 56.5 55


L2
Panel Cut-out
L1 = Mounting Depth
L2/L3 = Panel Cut-out
L4/L5 = Breaker Mounting Reference
Panel Breaker Mounting Holes
L1

Extended ROM

MCCB Mounting Holes


As Viewed From the Front

Ø51
45°
References as per L2
L3

MCCB Mounting
Ø76

Ø4

L1

Panel Cut Details

275

Type L1 L L2 L3
L = Length of Shaft required for
L DU100H 169 L1-119 7.5 69.5 Panel Depth L1 (mm)
L1 = Min. Panel depth (mm)
DU250 169 L1-119 24.5 81.7
Cut The Shaft to the Required Length = L

All dimensions are in mm 6


Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND Khairasol, Degaul Avenue EBG North Wing Office-Level 2
HEAD OFFICE Durgapur 713 212 Gate 7, Powai Campus
L&T House, Ballard Estate Tel: 2559848, 2559849, 2559844 Mumbai 400 072
P. O. Box 278 Fax: 0343-2553614 Tel: 022-67052874 / 2737 / 1156
Mumbai 400 001 e-mail: esp-dgp@LNTEBG.com Fax: 022-67051112
Tel: 022-67525656 e-mail: esp-bom@LNTEBG.com
Fax: 022-67525858 Milanpur Road, Bamuni Maidan
Website: www.Larsentoubro.com Guwahati 781 021 12, Shivaji Nagar
Tel: 0361-2550562 / 65 North Ambazari Road
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 0361-2551308 Nagpur 440 010
501, Sakar Complex I e-mail: hazrasudipto@LNTEBG.com Tel: 0712-2260012 / 3
Opp. Gandhigram Rly. Station Fax: 0712-2260020 / 30
Ashram Road II Floor, Vasantha Chambers e-mail: esp-nag@LNTEBG.com
Ahmedabad 380 009 5-10-173, Fateh Maidan Road
Tel: 079-66304006-11 Hyderabad 500 004 32, Shivaji Marg
Fax: 079-66304025 Tel: 040-67015052 P. O. Box 6223
e-mail: esp-ahm@LNTEBG.com Fax: 040-23296468 New Delhi 110 015
e-mail: esp-hyd@LNTEBG.com Tel: 011-41419514 / 5 / 6
38, Cubbon Road, P. O. Box 5098 Fax: 011-41419600
Bangalore 560 001 Monarch Building, 1st Floor e-mail: esp-del@LNTEBG.com
Tel: 080-25020100 / 25020324 D-236 & 237, Amrapali Marg
Fax: 080-25580525 Vaishali Nagar L&T House
e-mail: esp-blr@LNTEBG.com Jaipur 302 021 P. O. Box 119
Tel: 0141-4385914 to 18 191/1, Dhole Patil Road
131/1, Zone II Fax: 0141-4385925 Pune 411 001
Maharana Pratap Nagar e-mail: esp-jai@LNTEBG.com Tel: 020-26164048
Bhopal 462 011 Fax: 020-26164048/26164910
Tel: 0755-3080511 / 3080508 Akashdeep Plaza, 2nd Floor e-mail: esp-pnq@LNTEBG.com
Fax: 0755-2559264 P. O. Golmuri
e-mail: esp-bho@LNTEBG.com Jamshedpur 831 003 Crystal Tower, Plot No. 606/1
Jharkhand 4th Floor, G. E. Road
Plot No. 559, Annapurna Complex Tel: 0657-2312205 / 38 Telibandha
Lewis Road Fax: 0657-2341250 Raipur - 492 006
Bhubaneswar 751 014 e-mail: esp-jam@LNTEBG.com Tel: 0771-4283214
Tel: 0674-6451342, 2436696 e-mail: esp-raipur@LNTEBG.com
Fax: 0674-2537309 Skybright Bldg; M. G. Road
e-mail: esp-bbi@LNTEBG.com Ravipuram Junction, Ernakulam 3rd Floor
Kochi 682 016 Vishwakarma Chambers
SCO 32, Sector 26-D Tel: 0484-4409420 / 4 / 5 / 7 Majura Gate, Ring Road
Madhya Marg, P. O. Box 14 Fax: 0484-4409426 Surat 395 002
Chandigarh 160 019 e-mail: esp-cok@LNTEBG.com Tel: 0261-2473726
Tel: 0172-4646840, 4646853 Fax: 0261-2477078
Fax: 0172-4646802 3-B, Shakespeare Sarani e-mail: esp-sur@LNTEBG.com
e-mail: esp-chd@LNTEBG.com Kolkata 700 071
Tel: 033-44002572 / 3 / 4 Radhadaya Complex
L&T Construction Campus Fax: 033-22821025 / 7587 Old Padra Road
TC-1 Building, II Floor e-mail: esp-ccu@LNTEBG.com Near Charotar Society
Mount-Poonamallee Road Vadodara 390 007
Manapakkam A28, Indira Nagar, Faizabad Road Tel: 0265-6613610 / 1 / 2
Chennai 600 089 Lucknow 226 016 Fax: 0265-2336184
Tel: 044-2270 6800 Tel: 0522-4929905/04 e-mail: esp-bar@LNTEBG.com
Fax: 044-22706940 Fax: 0522-2311671
e-mail: esp-maa1@LNTEBG.com e-mail: esp-Lko@LNTEBG.com 48-8-16, Dwarakanagar
Visakhapatnam 530 016
67, Appuswamy Road No: 73, Karpaga Nagar, 8th Street Tel: 0891-670 1125 to 1130
Post Bag 7156 K. Pudur Fax: 0891- 670 1139
Opp. Nirmala College Madurai 625 007 e-mail: esp-viz@LNTEBG.com
Coimbatore 641 045 Tel: 0452-2537404, 2521068
Tel: 0422-2588120 / 1 / 5 Fax: 0452-2537552
Fax: 0422-2588148 e-mail: esp-mdu@LNTEBG.com
e-mail: esp-cbe@LNTEBG.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Larsen & Toubro Limited


Electrical Standard Products
Powai Campus, Mumbai 400 072
Customer Interaction Center (CIC)
BSNL / MTNL (toll free) : 1800 233 5858
Reliance (toll free) : 1800 200 5858
Tel : 022 6774 5858, Fax : 022 6774 5859
E-mail : cic@LNTEBG.com
Website : www.LNTEBG.com

SP 50520 R1 290113