Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Requirements For Medium-Voltage Transformers and Transformers For Internal Power Supply For Sunny Central and Sunny Central Storage

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Technical Information

Requirements for medium-voltage transformers


and transformers for internal power supply for
SUNNY CENTRAL and SUNNY CENTRAL
STORAGE

ENGLISH SC_Trafo-TI-en-71 | Version 7.1


Table of Contents SMA Solar Technology AG

Table of Contents
1 Information on this Document..................................................................................................... 3
1.1 Validity ............................................................................................................................................................. 3
1.2 Limited statutory warranty ............................................................................................................................... 3
2 Technical requirements for the MV transformer........................................................................ 4
2.1 General Requirements..................................................................................................................................... 4
2.2 Requirements for two-winding transformers used to connect one inverter ................................................... 5
2.3 Requirements for four-winding transformers used to connect two inverters ................................................. 6
2.4 Requirements for multi-winding transformers used to connect three inverters.............................................. 8
2.5 Requirements for multi-winding transformers used to connect four inverters................................................ 8
3 Technical requirements for the transformer for internal power supply .................................. 9
3.1 General Requirements..................................................................................................................................... 9
3.2 Requirements for the connection to the park-side utility grid ........................................................................ 9
3.3 Requirements for the connection to the AC output of the inverter ................................................................ 10
4 Appendix ...................................................................................................................................... 11
4.1 Technical data of the inverter ......................................................................................................................... 11
4.2 Technical Data of the Transformers ................................................................................................................ 15

2 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 1 Information on this Document

1 Information on this Document


1.1 Validity
This document applied to all device types of the Sunny Central inverter.
It describes the requirements for MV transformers and transformers for internal power supply that are connected to
Sunny Central inverters and provided by the customer.
Please note that not all Sunny Central inverters can be combined with all MV transformers. For more details, please
refer to the following pages.

1.2 Limited statutory warranty


SMA Solar Technology AG only provides statutory warranty for products purchased from SMA Solar Technology AG.
SMA Solar Technology AG America LLC only provides statutory warranty for products purchased from
SMA Solar Technology AG America LLC.
The statutory warranty for the inverters and other products purchased from SMA does not apply if the requirements
described in this document are not met.

Technical Information SC_Trafo-TI-en-71 3


2 Technical requirements for the MV transformer SMA Solar Technology AG

2 Technical requirements for the MV transformer


2.1 General Requirements
☐ The MV transformer can be of the liquid-immersed transformer type (for example, with mineral oil or organic oil)
or of the dry-type transformer.
☐ The MV transformer must be designed at its low-voltage windings for voltages that arise during pulsed mode of
the inverter.
☐ The power connection used must have suitable insulation resistance since voltages to ground of ±2400 V at the
most occur when the inverter is in pulsed mode (see Section 4.1 "Technical data of the inverter", page 11).

Figure 1: AC voltage level for SC 2500-EV

☐ The low‑voltage windings of the MV transformer must be designed for voltages that are capable of a rate of rise
in voltage dV/dt of up to 500 V/µs to ground. The line-to-line voltages are sinusoidal.
☐ It is recommended to provide a shield winding grounded on the tank between the low‑voltage windings and the
high‑voltage windings. This serves as an additional dV/dt filter.
☐ Each inverter requires a separate, galvanically insulated low-voltage winding. Therefore, the parallel operation of
several inverters on one low-voltage winding is not permissible.
☐ The voltages at the low-voltage windings of the MV transformer must match the AC output voltage of the inverter
(see Section 4.1 "Technical data of the inverter", page 11).
☐ The voltage level on the high-voltage side of the MV transformer must be selected according to the grid-
connection point. The MV transformer must be connected to the medium-voltage grid or the high-voltage grid.
Connection to the low-voltage grid is not permissible.
☐ When connecting to the medium-voltage grid, the use of a MV transformer with tap changer on the high voltage
side is recommended. MV transformer with tap changer on the high-voltage side enables an adaptation to the
voltage level of the medium-voltage grid.
☐ The MV transformer must be rated according to the temperature-dependent power behavior of the inverter.
☐ For thermal design, the load curve of the MV transformer and the ambient conditions at the respective mounting
location must be taken into account. When operating with an additional reactive power supply, the increased
loads in the design of the MV transformer are to be observed (for information about the reactive power supply of
the inverter, see the inverter documentation).
☐ When designing the MV transformer for use with the Sunny Central Storage, it is important to remember that due
to battery operation the MV transformer hardly cools down at all at night.

4 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 2 Technical requirements for the MV transformer

☐ The MV transformer must be designed for the AC output currents of the inverter (see Section 4.1 "Technical data
of the inverter", page 11).
☐ If grounding of the MV transformer on the medium voltage side is required, the type of grounding regarding the
entire system including the MV transformer must be taken into consideration.
☐ The consequences of any error, such as a short circuit, ground fault or voltage failure, must be taken into account
when considering the overall system.
☐ The country-specific power frequency must be taken into account.
☐ The applicable country-specific standards and directives must be taken into account.
☐ SMA reserves the right to measure the currents of the sine-wave filter capacitors during commissioning and, if
necessary, to optimize the entire system.

2.2 Requirements for two-winding transformers used to connect


one inverter
☐ The following vector groups are recommended for handling the corresponding neutral points.
Insulated neutral point on Resonant grounding on medium- Low-resistance grounded
medium-voltage side voltage side neutral point
Dy11, Dy5, Dy1, Dd0, Dd6 YNy0 YNy0
Yd11, Yd5, Yd1 YNd11, YNd5, YNd1
☐ If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or
connected.

Figure 2: Circuit diagram of two-winding transformers (example)

Technical Information SC_Trafo-TI-en-71 5


2 Technical requirements for the MV transformer SMA Solar Technology AG

☐ The relative impedance voltage Vk of the MV transformer between grid-connection point and AC output of the
inverter must be between the minimum value Vk min and the maximum value Vk max. The relative impedance voltage
is based the nominal power of the MV transformer (see Section 4.2 "Technical Data of the Transformers",
page 15).

2.3 Requirements for four-winding transformers used to connect


two inverters
A four-winding transformer (double story transformer) consists of two high-voltage windings and two low-voltage
windings.
☐ It is recommended for four-winding transformers to provide a separate shield winding that is grounded at the tank,
between each low-voltage winding and high-voltage winding.

A B C
D

G
E F

Figure 3: Four-winding transformers with separate shield windings

Position Designation
A Core
B Low-voltage winding 1
C High-voltage winding 1
D Shield winding 1
E Low-voltage winding 2

6 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 2 Technical requirements for the MV transformer

Position Designation
F High-voltage winding 2
G Shield winding 2
☐ Four-winding transformers with varying vector groups can be used. The following vector groups are recommended
for handling the corresponding neutral points.
Insulated neutral point on Resonant grounding on medium- Low-resistance grounded
medium-voltage side voltage side neutral point
Dy11y11, Dy5y5, Dy1y1, Dd0d0, YNy0y0 YNy0y0
Dd6d6 YNd11d11, YNd5d5, YNd1d1
Yd11d11, Yd5d5, Yd1d1
• If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or
connected.

Figure 4: Circuit diagram of four-winding transformers (example)

☐ Four-winding transformers must be designed for an asymmetrical load flow in the low-voltage systems. This means
that for long-term operation, the transformer must be designed for the feed-in of one inverter only.
☐ Four-winding transformers must be designed for the use of inverters of the Sunny Central Storage series so that full
power can be fed in at one of the low-voltage windings and that full power can be used at the other low-voltage
winding. The transformer must be designed for continuous operation in this operating state.
☐ The relative impedance voltage Vk of the MV transformer between grid-connection point and AC output of the
inverter must be between the minimum value Vk min and the maximum value Vk max. The relative impedance voltage
is based on half the nominal power of the MV transformer (see Section 4.2 "Technical Data of the Transformers",
page 15).
☐ The difference of the relative impedance voltages between the grid-connection point of the AC outputs of the two
inverters must not exceed 0.5% (see Section 4.2 "Technical Data of the Transformers", page 15).

Technical Information SC_Trafo-TI-en-71 7


2 Technical requirements for the MV transformer SMA Solar Technology AG

Example: Permissible Difference of Impedance Voltages Vk dif max


The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.0%. The
value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 5.6%. The
deviation of the relative impedance voltages is permissible since the difference amounts to 0.4% and is thus smaller
than 0.5%.

Example: Non-Permissible Difference of Impedance Voltages Vk dif max


The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.0%. The
value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 5.4%. The
deviation of the relative impedance voltages is not permissible since the difference amounts to 0.6% and is thus
greater than 0.5%.

☐ The value of the relative impedance voltage Vk 1-2 between the two low-voltage winding must be at least 9%. The
impedance voltage is based on half the nominal power of the MV transformer. This value can be determined by
shorting a low-voltage winding and increasing the voltage on the other low-voltage winding until the nominal
current of a low-voltage system flows. During this time, the high-voltage windings are in no-load operation.

Figure 5: Circuit diagram for determining the impedance voltage Uk 1-2 in four-winding transformers (example)

2.4 Requirements for multi-winding transformers used to connect three


inverters
The requirements for MV transformers to which three inverters are to be connected are the same as for two-winding
transformers. Three two-winding active parts are mounted in a tank. All three active parts must be set up with separated
cores.

2.5 Requirements for multi-winding transformers used to connect four


inverters
The requirements for MV transformers to which four inverters are to be connected are the same as for four-winding
transformers. Two four-winding active parts of double story design are mounted in a tank. Both active parts must be set
up with separated cores.

8 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 3 Technical requirements for the transformer for internal power supply

3 Technical requirements for the transformer for internal power supply


3.1 General Requirements
The inverters are equipped by default with an internal transformer for internal power supply. However, the inverters
can also be supplied externally.

General Requirements
☐ The transformer for internal power supply must be of three-phase design.
☐ The secondary side of the transformer for internal power supply must supply a voltage of 230 V/400 V (3/N/PE)
to connect to the inverter.
☐ The transformer for internal power supply must be designed for an asymmetric load of 80%.
☐ A transformer for internal power supply with the Dyn5 or Dyn11 vector group is recommended.
☐ A shield winding that has to be grounded at the enclosure must be provided between the windings of the
transformer for internal power supply.
☐ The transformer for internal power supply must be equipped with an external protection against overload.
☐ The ambient conditions of the transformer for internal power supply must be taken into account.
☐ The country-specific power frequencies must be taken into account.
☐ The applicable country-specific standards and directives must be taken into account.
☐ The transformer for internal power supply must provide a power of at least 8.4 kVA per inverter.
☐ Several inverters can be supplied by one transformer for internal power supply if this transformer can provide a
power of at least 8.4 kV per inverter.
☐ The transformer for internal power supply must have external short-circuit protection ensuring that any potential
short-circuit currents are limited to 10.0 kA at the inverter.

3.2 Requirements for the connection to the park-side utility grid

Figure 6: Connection of the transformer for internal power supply to the park-side utility grid

Technical Information SC_Trafo-TI-en-71 9


3 Technical requirements for the transformer for internal power supply SMA Solar Technology AG

☐ For the connection to the park-side utility grid, the primary voltage of the transformer for internal power supply
must be equal to the grid voltage.

3.3 Requirements for the connection to the AC output of the inverter

Figure 7: Connection of the transformer for internal power supply to the inverter's AC output

☐ The primary voltages of the transformer for internal power supply must correspond to the AC output voltages of
the inverter (see Section 4.1 "Technical data of the inverter", page 11).
☐ On the primary side, the transformer for internal power supply must be suitable for the pulsed mode of an inverter.
☐ On the primary side, the transformer for internal power supply must be suitable for voltages that arise from pulsed
mode of the inverter.
☐ The power connection used must have suitable insulation resistance since voltages to ground of ±2,400 V at the
most occur when the inverter is in pulsed mode (see Section 4.1 "Technical data of the inverter", page 11).
☐ On the primary side, the transformer for internal power supply must be designed for voltages reaching a rate of
rise in voltage dV/dt of up to 500 V/µs to ground. The line-to-line voltages are sinusoidal.
☐ The windings of the transformer for internal power supply must be galvanically insulated. Do not use
autotransformers.

10 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 4 Appendix

4 Appendix
4.1 Technical data of the inverter
Sunny Central
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 35°C at 50°C

SC 2200 1100 V 385 V ±1800 V 3300 A 3000 A


SC 2475 1100 V 434 V ±1800 V 3292 A 2993 A
SC 2500-EV 1500 V 550 V ±2400 V 2624 A 2362 A
SC 2750-EV 1500 V 600 V ±2400 V 2646 A 2406 A
SC 3000-EV 1500 V 655 V ±2400 V 2646 A 2380 A

Sunny Central UP
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 35°C at 50°C

SC 2660 UP 1500 V 600 V ±2400 V 2566 A 2309 A


SC 2800 UP 1500 V 630 V ±2400 V 2566 A 2309 A
SC 2930 UP 1500 V 660 V ±2400 V 2566 A 2309 A
SC 3060 UP 1500 V 690 V ±2400 V 2566 A 2309 A
SC 4000 UP 1500 V 600 V ±2400 V 3850 A 3465 A
SC 4200 UP 1500 V 630 V ±2400 V 3850 A 3465 A
SC 4400 UP 1500 V 660 V ±2400 V 3850 A 3465 A
SC 4600 UP 1500 V 690 V ±2400 V 3850 A 3465 A

Sunny Central US
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 35°C at 50°C

SC 1760-US 1000 V 385 V ±1800 V 2640 A 2640 A


SC 1850-US 1000 V 385 V ±1800 V 2774 A 2774 A
SC 2000-US 1000 V 385 V ±1800 V 3300 A (ap- 3000 A
parent current)
3000 A (active
current)

Technical Information SC_Trafo-TI-en-71 11


4 Appendix SMA Solar Technology AG

Inverter type DC voltage AC voltage AC peak volt- AC current


age to
ground at 35°C at 50°C

SC 2000-EV-US 1500 V 550 V ±2400 V 2310 A (ap- 2310 A (ap-


parent current) parent current)
2100 A (active 2100 A (active
current) current)
SC 2200-US 1000 V 385 V ±1800 V 3300 A 3000 A
SC 2500-EV-US 1500 V 550 V ±2400 V 2624 A 2362 A
SC 2750-EV-US 1500 V 600 V ±2400 V 2646 A 2406 A

Sunny Central UP-US
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 35°C at 50°C

SC 2660 UP-US 1500 V 600 V ±2400 V 2566 A 2309 A


SC 2750 UP-US 1500 V 630 V ±2400 V 2520 A 2270 A
SC 2800 UP-US 1500 V 630 V ±2400 V 2566 A 2309 A
SC 2930 UP-US 1500 V 660 V ±2400 V 2566 A 2309 A
SC 3060 UP-US 1500 V 690 V ±2400 V 2566 A 2309 A
SC 4000 UP-US 1500 V 600 V ±2400 V 3850 A 3465 A
SC 4200 UP-US 1500 V 630 V ±2400 V 3850 A 3465 A
SC 4400 UP-US 1500 V 660 V ±2400 V 3850 A 3465 A
SC 4600 UP-US 1500 V 690 V ±2400 V 3850 A 3465 A

Sunny Central Storage
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 25°C at 50°C

SCS 1900 1100 V 337 V ±1800 V 3260 A 2960 A


SCS 2200 1100 V 385 V ±1800 V 3300 A 3000 A
SCS 2475 1100 V 434 V ±1800 V 3292 A 2993 A
SCS 2500-EV 1500 V 550 V ±2400 V 2624 A 2362 A
SCS 2750-EV 1500 V 600 V ±2400 V 2646 A 2406 A
SCS 2900 1100 V 520 V ±1800 V 3265 A 2968 A
SCS 3000-EV 1500 V 655 V ±2400 V 2646 A 2380 A

12 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 4 Appendix

Sunny Central Storage UP
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 25°C at 50°C

SCS 2750 UP 1500 V 600 V ±2400 V 2646 A 2406 A


SCS 3450 UP 1500 V 600 V ±2400 V 3320 A 2822 A
SCS 3600 UP 1500 V 630 V ±2400 V 3320 A 2822 A
SCS 3800 UP 1500 V 660 V ±2400 V 3320 A 2822 A
SCS 3950 UP 1500 V 690 V ±2400 V 3320 A 2822 A

Sunny Central Storage UP-XT


Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 25°C at 50°C

SCS 2300 UP-XT 1500 V 600 V ±2400 V 2566 A 2181 A


SCS 2400 UP-XT 1500 V 630 V ±2400 V 2566 A 2181 A
SCS 2530 UP-XT 1500 V 660 V ±2400 V 2566 A 2181 A
SCS 2630 UP-XT 1500 V 690 V ±2400 V 2566 A 2181 A
SCS 3450 UP-XT 1500 V 600 V ±2400 V 3850 A 3272 A
SCS 3600 UP-XT 1500 V 630 V ±2400 V 3850 A 3272 A
SCS 3800 UP-XT 1500 V 660 V ±2400 V 3850 A 3272 A
SCS 3950 UP-XT 1500 V 690 V ±2400 V 3850 A 3272 A

Sunny Central Storage US
Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 25°C at 50°C

SCS 2200-US 1000 V 385 V ±1800 V 3300 A 3000 A


SCS 2475-US 1000 V 434 V ±1800 V 3292 A 2993 A
SCS 2500-EV-US 1500 V 550 V ±2400 V 2624 A 2362 A
SCS 2750-EV-US 1500 V 600 V ±2400 V 2646 A 2406 A
SCS 2900-US 1000 V 520 V ±1800 V 3265 A 2968 A

Sunny Central Storage UP-US


Inverter type DC voltage AC voltage AC peak volt- AC current
age to
ground at 25°C at 50°C

SCS 2750 UP-US 1500 V 600 V ±2400 V 2646 A 2646 A

Technical Information SC_Trafo-TI-en-71 13


4 Appendix SMA Solar Technology AG

Inverter type DC voltage AC voltage AC peak volt- AC current


age to
ground at 25°C at 50°C

SCS 3450 UP-US 1500 V 600 V ±2400 V 3320 A 2822 A


SCS 3600 UP-US 1500 V 630 V ±2400 V 3320 A 2822 A
SCS 3800 UP-US 1500 V 660 V ±2400 V 3320 A 2822 A
SCS 3950 UP-US 1500 V 690 V ±2400 V 3320 A 2822 A

Sunny Central Storage UP-XT-US


Inverter type DC voltage AC voltage AC peak AC current
voltage to
ground at 25°C at 50°C

SCS 2300 UP-XT-US 1500 V 600 V ±2400 V 2566 A 2181 A


SCS 2400 UP-XT-US 1500 V 630 V ±2400 V 2566 A 2181 A
SCS 2530 UP-XT-US 1500 V 660 V ±2400 V 2566 A 2181 A
SCS 2630 UP-XT-US 1500 V 690 V ±2400 V 2566 A 2181 A
SCS 3450 UP-XT-US 1500 V 600 V ±2400 V 3850 A 3272 A
SCS 3600 UP-XT-US 1500 V 630 V ±2400 V 3850 A 3272 A
SCS 3800 UP-XT-US 1500 V 660 V ±2400 V 3850 A 3272 A
SCS 3950 UP-XT-US 1500 V 690 V ±2400 V 3850 A 3272 A

14 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 4 Appendix

4.2 Technical Data of the Transformers


Sunny Central
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SC 2200 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2475 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2500-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2750-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 3000-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %

Sunny Central UP
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SC 2660 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 2800 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 2930 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 3060 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4000 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4200 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4400 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4600 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

Sunny Central US
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SC 1760-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 1850-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2000-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2000-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2200-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2500-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SC 2750-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %

Technical Information SC_Trafo-TI-en-71 15


4 Appendix SMA Solar Technology AG

Sunny Central UP-US
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SC 2660 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 2750 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 2800 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 2930 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 3060 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4000 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4200 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4400 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SC 4600 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

Sunny Central Storage
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 1900 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2200 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2475 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2500-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2750-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2900 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 3000-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %

Sunny Central Storage UP
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 2750 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3450 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3600 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3800 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3950 UP 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

16 SC_Trafo-TI-en-71 Technical Information


SMA Solar Technology AG 4 Appendix

Sunny Central Storage UP-XT
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 2300 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 2400 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 2530 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 2630 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3450 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3600 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3800 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3950 UP-XT 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

Sunny Central Storage US
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 2200-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2475-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2500-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2750-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %
SCS 2900-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 %

Sunny Central Storage UP-US
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 2750 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3450 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3600 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3800 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3950 UP-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

Sunny Central Storage UP-XT-US
Type of the Two-winding transformers Four-winding transformers
Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 2300 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

Technical Information SC_Trafo-TI-en-71 17


4 Appendix SMA Solar Technology AG

Type of the Two-winding transformers Four-winding transformers


Inverter
Vk min Vk nom Vk max Vk min Vk nom Vk max Vk dif max Vk 1-2 min
SCS 2400 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 2530 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 2630 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3450 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3600 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3800 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %
SCS 3950 UP-XT-US 6.0 % - 8.5 % 6.0 % - 8.5 % 0.5 % 9.0 %

18 SC_Trafo-TI-en-71 Technical Information


www.SMA-Solar.com

You might also like