Usage Manual: Carel Electrical Regulation For Air-Cooled Heat Pumps With High Efficiency Scroll Compressor
Usage Manual: Carel Electrical Regulation For Air-Cooled Heat Pumps With High Efficiency Scroll Compressor
Español
USAGE MANUAL
Carel electrical regulation for air-cooled heat pumps with
high efficiency scroll compressor
MANUAL DE INSTRUCCIONES
Ajuste eléctrico Carel para bombas de calor condensadas
con aire con compresor scroll de alta eficiencia
he
List of parameters 5
Alarms 7
Characteristics of the regulation
The control panel allows the quick all the settings saved after every with a red indicator light (alarm). With
setting of the working parameters of modification and used for the restarting the installation of the remote control
the machine, their visualisation in any after an interruption owing to power panel PRD (accessory) on the other
moment, and an immediate summary failure. hand, it is possible to repeat from a
of the machine's working state. The With the installation of the remote distance all the functionalities of the
display is made up of 3 figures and 4 control panel PR1 (accessory), it is on-machine controls. The panel has 4
LEDs, to signal the type of working, possible to control from a distance multi-function keys: by pressing one
the visualisation of the parameters set the switching on and off, the setting of
x100h
or two keys at the same time, you can
or measured, and any alarms that have the way of working (cold-hot), and the control all the parameters and the
been activated. The card memorises visualisation of the alarms summary, functions of the unit.
SEL
User interface
Characteristics:
Row number 1
Column number 3
x100h
Character height (mm) 10
SEL
µ chiller compact
Remote connections
• PRV • PR1
Intelligent remote Simplified remote
panel, repeats the panel, carries out
functions of on- A basic controls, can
L
x100h
machine command, A
R
be used at up to
M
can be used at up to 30m.
SEL 150m.
3
Use of keys
4
Parameter list
WORKING PARAMETERS (THE VALUES SHOWN IN THE WINDOWS ARE THE DEFAULT ONES):
[°C]
Temperature coil probe cond. (B3) [°C] --- Visualisation Visualisation Visualisation
5
WORKING THERMOSTAT
OFF
0%
TIA
Set
r1 r2
Po
ON
100 %
Key:: OFF
Po: Power rendered 0%
TIA: Water inlet temperature
TIA
r1: cold setting
r2: differential in cold mode Set
r3: hot setting r4 r3
r4: differential in hot mode
6
ALARMS
The signalling of particular working states messages, use the table below. When an the display
of the unit, or the emergence of an alarm alarm is activated, the following actions are • visualisation on the display of the alarm
condition, are communicated by the micro generally carried out: code, alternated with the temperature
chiller controller, with codified messages • activation of alarm relay
visualised on the display; to decode these • flashing of the temperature visualisation on
S r1 Defrosting error If the defrosting finishes according to maximum time, when the conclusion for the
reaching of temperature threshold, or outside contact, is selected, the machine
shows the sign r1. The message is disactivated by cancelling the alarms, or by
carrying out another, correct defrosting cycle. The alarm relay is not activated.
S Cn Error of communication with In the event of a communication error between the panel on the
the remote terminal machine, and the remote terminal PRD, the message Cn is visualised;
check the connection cable. The alarm relay is not activated.
A H1 high pressure The compressor is immediately switched off, the alarm relays are activated, and the
display flashes. The fans are activated at maximum speed for 60 seconds, to contrast
the alarm situation, then they are switched off. The heat pumps can also indicate the
intervention of the thermal protection of the compressor. The restoration is manual.
A L1 low pressure The alarm leads to the immediate switching off of the compressor, or its non-starting.
The alarm relays are activated, and the display flashes. The restoration is automatic.
A A1 Antifreeze The alarm is sensed by the water outlet probe of the evaporator (SUW). The
alarm immediately switches off the compressor and the fans, while the
alarm relays are activated and the display flashes. The restoration is manual.
A FL FLOW SWITCH The alarm switches off the pump, the compressor and fans. The display
flashes and the alarm relays are activated; The restoration is manual.
A E1, E2, Probe alarms The presence of a probe alarm leads to the disactivation of
the compressor, the fans and the pump; the relay alarms are
E3
activated and the display flashes. The restoration is automatic.
E1: Water inlet probe
E2: Water outlet probe
E3: Coil probe
A E4 Compensation probe alarm The presence of a probe alarm leads to the disactivation of
the compressor, the fans and the pump; the relay alarms are
activated and the display flashes. The restoration is automatic.
A EU/EO Error of low or high supply In the event of a supply voltage that is too low, the message EU appears;
voltage if too high, the indication is EO. In these cases, the correct working
of the unit is no longer guaranteed. In the event of EO alarm, the
compressor, pump and fans are switched off; the restoration is automatic.
A EP/EE Eeprom alarm error A problem in the non-volatile memory of the machine (eeprom). If it is a case
of EE, the unit continues to work until the first loss of power supply. When
power supply is restored, if the error is still present, the display begins to flash,
showing the sign EP, and the unit doesn't start up; the restoration is automatic
A EL Error of line disturbance Appears if a loud noise is present in the power supply. In this case, the fans (if driven
with the DCPX accessory) will begin to work On/Off for the time that the disturbance
continues. The restoration is automatic.
A Er Error of expansion module for The presence of an expansion module alarm leads to the disactivation
of the compressor, the fans and the pump; the relay alarms are
compensation probe
activated and the display flashes. The restoration is automatic
A Ht High temperature of return In the event that the temperature of the return water is higher
than the set limit, the working cycle of the unit is interrupted;
water
the alarm relay is not activated. The restoration is automatic.
Key::
S: Signalling RESETTING OF THE ALARMS
A: ALARM With the disappearance of the automatically restored alarms (or the contemporary pressing of
and for five seconds for the manually restored alarms), the following actions are obtained:
• disactivation of the alarm relays;
• suspension of the flashing temperature on the display;
• suspension of the visualisation of the alarm code.
If the alarm condition continues, the procedure for signalling the alarm is repeated.
7
Índice
Lista de parámetros 12
ALARMAS 14
Características del ajuste
El tablero de mandos de la unidad En la tarjeta se memorizan todas las visualización del historial de alarmas
permite programar rápidamente los programaciones guardadas en cada con un indicador rojo (alarmas). Si,
parámetros de funcionamiento de la modificación y utilizadas cuando se por el contrario, se instala el mando
máquina, visualizarlos en cualquier vuelve a encender la unidad después de accesorio de control remoto PRD, es
momento y comprobar inmediatamente un apagado por falta de tensión. posible realizar a distancia todas las
el estado de funcionamiento de la Con la instalación del mando accesorio funciones del control a bordo de
máquina. El visor está formado por 3 de control remoto PR1 es posible la máquina. El control dispone de
cifras y 4 led que indican el tipo de controlar a distancia el encendido y cuatro teclas multifunción: al pulsar
funcionamiento, la visualización de los apagado, la programación del modo una o dos teclas al mismo tiempo, es
parámetros programados o medidos, de funcionamiento (frío-calor), y la
x100h
posible controlar todos los parámetros y
y de las posibles alarmas activadas. funciones de la unidad.
SEL
Características:
Número de filas 1
Número de columnas 3
x100h
Altura carácter (mm) 10
SEL
µ chiller compact
Conexiones remotas
• PRV • PR1
Mando de control Mando de control
remoto inteligente: remoto simplificado:
reproduce las A realiza todas las
L
x100h
funciones del mando A
R
funciones básicas
M
de la máquina a una a una distancia
SEL distancia máxima de máxima de 30 m.
150 m.
9
Uso de las teclas
10
Lista de parámetros
PARÁMETROS DE FUNCIONAMIENTO (LOS VALORES QUE APARECEN EN LAS VENTANAS SON LOS DE POR DEFECTO):
Temp. sonda batería cond. (B3) [°C] --- Visualización. Visualización. Visualización.
11
TERMOSTATO DE FUNCIONAMIENTO
OFF
0%
TIA
Set
r1 r2
Po
ON
100 %
Leyenda: OFF
Po : Potencia rendimiento 0%
TIA : Temperatura entrada agua
TIA
r1 : - set frío
r2 : Diferencial en funcionamiento frío Set
r3 : - set calor r4 r3
r4 : Diferencial en funcionamiento en calor
12
Alarmas
El controlador micro chiller informa de más abajo para descodificar dichos mensajes. visor parpadea
determinados estados de funcionamiento Al producirse una alarma, se producen, por • Aparece en el visor el código de
de la unidad o de que se ha producido una lo general, las siguientes acciones: alarma alternativamente a la temperatura
situación de alarma mediante mensajes • El relé de alarma se activa
codificados en el visor. Consulte la tabla de • La visualización de la temperatura del
A E1, E2, Alarmas sonda Al activarse una alarma sonda, se desactivan el compresor, los ventiladores y la bomba;
el relé de alarma se activa y parpadea el visor. Se reajusta de forma automática.
E3
E1: sonda entrada agua
E2 : Sonda salida agua
E3 : Sonda batería
A E4 Alarma sonda compensación Al activarse una alarma sonda, se desactivan el compresor, los ventiladores y la bomba;
el relé de alarma se activa y parpadea el visor. Se reajusta de forma automática.
A EU/EO Error de baja o alta tensión de En caso de tensión de alimentación demasiado baja, aparece el mensaje EU;
alimentación si la tensión es demasiado alta, aparece EO. En estos casos, no se garantiza
el funcionamiento correcto de la unidad. En caso de alarma EO se apagan el
compresor, la bomba y los ventiladores; se reajusta de forma automática.
A EP/EE Error alarma eeprom Es un problema en la memoria no volátil de la máquina (eeprom). Si se trata de
EE, la unidad sigue funcionando hasta la primera interrupción de la alimentación.
Cuando vuelva la tensión, si persiste el error, el visor empezará a parpadear con
el mensaje EP y la unidad no se encenderá; se reajusta de forma automática.
A EL Error de irregularidades de Aparece si hay fuertes irregularidades en la alimentación. En tal caso, los ventiladores,
se están controlados por el accesorio DCPX, empezarán a funcionar On/Off mientras
línea
duren las irregularidades. Se reajusta de forma automática.
A Ht Alta temperatura agua de Si la temperatura del agua de retorno del sistema sobrepasa el
límite fijado, se interrumpe el ciclo de funcionamiento de la unidad;
retorno
el relé de alarma no se activa. Se reajusta de forma automática.
Leyenda:
S : Señal REAJUSTE DE LAS ALARMAS
A : Alarma Al desaparecer las alarmas de reajuste automático o al apretar simultáneamente y durante
cinco segundos, en el caso de alarma de reajuste manual, se producen las acciones siguientes:
• El relé de alarma se desactiva.
• Deja de parpadear la visualización de la temperatura en el visor.
• Desaparece la indicación del código de alarma.
Si la situación de alarma perdura, se repetirá el procedimiento de indicación de alarma.
13
AERMEC S.p.A.
37040 Bevilacqua (VR) - Italy carta riciclata
Via Roma, 44 - Tel. (+39) 0442 633111 ISO 9001 - Cert. n° 0128/4 recycled paper
Telefax (+39) 0442 93730 – (+39) 0442 93566 papier recyclé
www.aermec.com recycled Papier
Los datos técnicos contenidos en este documento no son vinculantes. The technical data in the following documentation are not binding.
AERMEC se reserva la facultad de aportar, en cualquier momento, todas las Aermec reserves the right to make all the modifications considered
modificaciones consideradas necesarias para la mejora del producto. necessary for improving the product at any time.