ECS-10HT1 Temperature Controller Instruction
ECS-10HT1 Temperature Controller Instruction
1.Product Overview
ECS-01HT1 Universal temperature controller can convert Fahrenheit, Celsius display display,
switching cooling / heating mode. The allocation of cabinet temperature sensor and defrosting control
sensor. Optional defrost relay output and copy card function.
2.operation and display panel
4.Technical parameters
1)Measuring range : -50~99℃/℉ (only refers to the sensor calibration value is set to 0)
2)Temperature resolution : 9.9~-9.9 , 0.1℃/℉ , the others,1℃/2℉
3)Measurement accuracy : -40℃~50℃ , ±1℃ , 50℃~70℃ , ±2℃ , the others : ±3℃
or -40℉~99℉, ±2℉ , the others : ±6℉
4)Temperature controlling range : -50~99℃/℉
5)Power supply : 220±10%(VAC) , 50/60Hz
6)power consumption : <3W
7)Rated current of the relays :
Refrigeration : 30A/220VAC , it can directly drive 1.5 HP (220VAC) compressor , single phase
17A/220VAC , it can directly drive 1.0HP (220VAC) compressor , single phase
Defrost: 10A/220VAC( suggest connect the max 1.4 KW electric heating wire)
8) Front panel water proof : IP65
9)The back shell water proof : None
10) Operation condition : 0℃~55℃
11) Storage condition : -25℃~75℃,
12) Relative humidity : 20%~85% (relative humidity )
On Parameter settings
Setting set
Off working order
On Cooling / heating
6.Parameter Table
Menu Functions Setting range Default Level
St Temperature setting value Maximum ~Minimum Set Point 3 Pr0
0.1~10℃
Hy Hysteretic value 2 Pr1
1~25℉
-50℃~St
LS Minimum set point -50 Pr2
-50℉~St
St~99℃
US Maximum set point 99 Pr2
St~99℉
-9.9~9.9℃
ot Cabinet sensor calibration 0 Pr1
-20~20℉
y:Enable
P2 Evaporator sensor selection y Pr1
n:Forbidden
-9.9~9.9℃
oE Evaporator sensor calibration 0 Pr2
-20~20℉
Outputs activation delay at start
od 0~99min 0 Pr2
up
AC Anti-short cycle delay 0~50min 1 Pr1
Compressor running time in the
Cy mode of “Run/stop in a 0~99min 15 Pr2
proportional time”
Compressor stop time in the
Cn mode of “Run/stop in a 0~99min 30 Pr2
proportional time”
CL:Cooling
CH Cooling /Heating CL Pr2
Ht:Heating
C:℃
CF ℃/℉ C Pr2
F:℉
P1:Display the cabinet sensor
P2:Display the evaporator sensor
Ld Default Display P1 Pr2
SP:Display the temperature
setpoint
-50~90℃
dE Defrost termination temperature 2 Pr1
-50~90℉
id Defrost cycle 0~99hour 8 Pr1
Md The maximum time of defrost 1~99min 20 Pr1
rt : Display cabinet temperature
It : Display start-defrost cabinet
temperature
dF Defrost status display it Pr2
St : Display temperature setting
value
dF : Display “dF”
Cabinet temperature upper limit (AL+1)~99℃
AU 99 Pr1
alarm value (AL+1)~99℉
Cabinet temperature lower limit -50℃~(AU-1)
AL -50 Pr1
alarm value -50℉~(AU-1)
Ad Temperature alarm delay 0~99min 15 Pr2
Exclusion of temperature alarm
dA 0~99min 90 Pr2
at startup
Success of “uP” 、
Upload the data to copy card Pressing the keys for 1s
Failure of "Er”
1) Push and immediately release the SET key, the set point will be showed and the “ ”LED
starts lighting ;
2) Push and immediately release the SET key or wait about 15s to return to normal visualisation.
HOW TO CHANGE THE SET POINT :
1) Push the SET key for more than 2 seconds to change the set point value ;
2) The value of the set point will be displayed and the “set ”LED starts lighting ;
3) To change the Set value press the ▲or ▼ within 15s ;
4) To memorise the new set point value push the SET key again or wait 15s.
HOW TO CHANGE A PARAMETER VALUE :
To change the parameter’s value operate as follows:(first level Pr1)
1)Enter the Programming mode by pressing the SET+ ▼keys for 3s , the “set” LED starts to light ;
2)Select the required parameter. Press the SET key to display its value ;
3)Use▲ or ▼to change its value ;
4)Press SET to store the new value and move to the following parameter ;
5)To exit : Press SET+▲ or wait 15s without pressing a key .
HIDDEN MENU(the second level Pr2)
(The hidden menu includes all the parameters of the instrument (Pr1 and Pr2))
1) Enter the Programming mode by pressing the SET+▼ keys for 3s the” set “LED starts to light ;
2) Then push again the SET+▼ keys for more than 7s. The L2 label will be displayed immediately
followed from the Hy parameter ;
3) Select the required parameter ;
4) Press the SET key to display its value ;
5) Use ▲or ▼to change its value ;
6) Press SET to store the new value and move to the following parameter ;
7) To exit: Press SET+▲ or wait 15s without pressing a key.
NOTE: If none parameter is present in L1, after 3s the “nP” message is displayed. Keep the keys pushed
till the L2 message is displayed.
HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND
VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL”
(user level) by pressing SET+ ▼.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
8.Output
1 Cooling/Heating :
Cooling :
Normal status : When the cabinet temperature is higher than the set point + hysteresis (Hy),and finish
the Anti-short cycle delay time(AC), cooling will start ;
When the cabinet temperature is lower than the set point, cooling will stop.
For the first time the power on ,and the time up to (od) value , if the cabinet temperature is higher than
the set point + hysteresis (Hy) , cooling will start.
Heating:
Normal status : When the cabinet temperature is lower than the set point , and finish the Anti-short cycle
delay time(AC), heating will start ;
When the cabinet temperature is higher than the set point + hysteresis (Hy), heating will stop.
For the first time the power on ,and the time up to (od) value , if the cabinet temperature is lower than
the set point , heating will start.
If the cabinet sensor is fault , the compressor will run and stop according to the set time.( running
time Cy and stop time Cn).
2 Defrost:
1) If the defrost cycle (id=0) , the defrost will be forbidden .
2) id≠0:
① The Evaporator sensor start to work (P2=y), the evaporator’s sensor temperature is higher than
the defrost termination temperature(dE) , it can’t open the defrost function .
② The Evaporator sensor start to work (P2=y) and the evaporator’s sensor temperature is lower
than the defrost termination temperature(dE) or (P2=n) , the defrost function will start when fit one of the
next conditions :
a) The controller will start defrost according to the set defrost cycle.
b) Press for 2s,start defrost.
3) Under the defrost state(Any of the following conditions can be closed defrosting):
①The evaporator sensor start to work (P2=y) ,Evaporator sensor temperature > Defrost
termination temperature(d7),defrost is closed
②Maximum time of defrost(Md)runs out,defrost is closed;
③ Press for 2s,stop defrost;
3 Fault Alarm :
Mess. Cause Outputs
P1 Cabinet temperature sensor fault Compressor output according to “Cy” e “Cn”
P2 Evaporator sensor fault Defrost relay will working fellow the preset of “id”
Mess. Cause Outputs
and “Md”
HA Cabinet high temperature alarm Outputs unchanged
LA Cabinet low temperature alarm Outputs unchanged
Evaporator sensor is
nP forbidden ,display screen show
the evaporator’s temperature
Er Hot key program failure
1) When the temperature sensor is fault , it is display P1 or P2, it will recover when the problem is
solved.
2) Cabinet over temperature alarm :
When the cabinet temperature is beyond the (AU) set point , Ad and (dA) all finished , it will display
HA, when the temperature is lower than the (AU) , the alarm will stop.
When the cabinet temperature is below the( AL) set point , Ad and (dA) all finished , it will display LA,
when the temperature is higher than the (AL) , the alarm will stop.
9.Hot key
1) Upload
① Program one controller with the front keypad.
② Insert the “Hot key” and push ▲key; the "uP" message appears.
③ Turn OFF the instrument remove the “Hot Key”, then turn the controller ON again.
2) Download
① Insert the “Hot key”, push the ▼key, the controller will display “do”.
② Turn OFF the instrument remove the “Hot Key”, then turn he controller ON again.
NOTE: The “Er” message is displayed for failed programming.
In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the
operation.
★ Pelase make sure that the power is stable during this time.
10.Wiring diagram
11.Safety rules
★Danger :
1) Strictly distinguish the power wire, relay output, sensor down-lead and data line, and the relay
could not be overloaded.
2) Prohibit connecting the wire terminals without electricity cut-off.
★Warning :
Prohibit using this unit under the environment of over damp, high temp., strong electromagnetism
interference or strong corrosion.
★Notice:
1) The power supply should conform to the voltage value indicated in the instruction, and make sure a
steady power supply.
2) To avoid the possible interference, the sensor down-lead/data line and power wire should be kept in
a proper distance.
3) When evaporator sensor is installed, the sensor should be well connected with the copper tube
which is 5cm away from evaporator inlet.