Ratings Definitions
Ratings at 0.8 power factor. www.FGWilson.com
Prime
These ratings are applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased power.
There is no limitation to the annual hours of operation and this
model can supply 10% overload power for 1 hour in 12 hours.
Standby
These ratings are applicable for supplying continuous electrical
power (at variable load) in the event of a utility power failure. No
overload is permitted on these ratings. The alternator on this model
is peak continuous rated (as defined in ISO 8528-3).
Technical Data
Engine Make & Model: Perkins 404D-22G1
Alternator Model: LL1014L
No. of Cylinders/Alignment: 4 / In Line
Displacement: litres (cu.in) 2.2 (135.2)
Bore/Stroke: mm (in) 84.0 (3.3)/100.0 (3.9)
Compression Ratio: 23.3:1
Induction: Naturally Aspirated
Frequency: 50 Hz 60 Hz
Engine Speed: 1500 RPM 1800 RPM
Gross Engine Power: kW (hp) 18.0 (24.0) 21.5 (29.0)
BMEP: kPa (psi) 649.0 (94.2) 647.0 (93.8)
Piston Speed: m/sec (ft/sec) 5.0 (16.4) 6.0 (19.7)
Fuel Tank Capacity: litres (US gal) 45 (11.9) 45 (11.9)
Fuel Consump, Prime l/hr (USg/hr) 4.4 (1.2) 5.2 (1.4)
Fuel Consump, Standby l/hr (USg/hr) 4.8 (1.3) 5.7 (1.5)
Heat Rejected to
Exhaust System: kW (Btu/min) 11.6 (660) 12.8 (728)
Heat Rejected to
Water & Lube Oil: kW (Btu/min) 15.2 (864) 17.2 (978)
Heat Radiation to Room: kW (Btu/min) 3.1 (176) 3.2 (182)
Exhaust Gas Temperature: °C (°F) 394 (740) 434 (812)
Radiator Cooling
Air Flow: m³/min (cfm) 33.0 (1165) 41.4 (1462)
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.
P18-4
Generating set pictured may include optional accessories.