1-Calculation of The Peak Power Output of The PV System

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

1- Calculation of the Peak Power Output of the PV system :

* PV Module output DC Voltage = 32.5 Volt

Total ouput DC Voltage of one set of


* 13 PCs of PV modules connected in = 358 volt
series

* Max. Power output / Module = 300 Watt

* Total no. of PV Modules = 55 PCs

* Total PV system Power Output = 16500 watt

* Idc ( DC current ) = 46 Amps.

* DC Disconnecting Switch Rating = 58 Amps.

The Suitable DC Disconnecting Switch Rating shall be = 63 Amps.

The Suitable DC/AC Inverter Size = 20000 Watt , (200-800)Vdc/400Vac

* Iac ( AC current ) = 36 Amps.

* AC Disconnecting Switch Rating = 45 Amps.

The Suitable AC Disconnecting Switch Rating shall be = 63 Amps.

2- Calculation of The Average Power Output of the PV system :

* PV Module output DC Voltage = 32.5 Volt

Total ouput DC Voltage of one set of


* 13 PCs of PV modules connected in = 358 volt
series

* Max. Power output / Module = 300 Watt

* Total no. of PV Modules = 55 PCs

* Temperature Derating Factor = 0.89

* Dirt & Dust Derating Factor = 0.93

Page 1 of 2
PV Modules mismatch & wiring
* = 0.95
losses
* DC/AC converter losses = 0.90

* Total PV system Power Output = 11677 Watt

* Idc ( DC current ) = 33 Amps.

* DC Disconnecting Switch Rating = 41 Amps.

The Suitable DC Disconnecting Switch Rating shall be = 50 Amps.

The Suitable DC/AC Inverter Size = 16000 Watt , (200-800)Vdc/400Vac

* Iac ( AC current ) = 29 Amps.

* AC Disconnecting Switch Rating = 36 Amps.

The Suitable AC Disconnecting Switch Rating shall be = 40 Amps.