Baudouin GenSet Catalog
Baudouin GenSet Catalog
Baudouin GenSet Catalog
IC 07/A
LD SC - 12-2012
Reference conditions
Ambiant tempeature 25 °C / 77 ° F
Barometric pressure 100 kPa
Relative humidity 30 %
Raw water temperature 25 °C / 77 ° F
Fuel oil
Relative density 0,840 ± 0,005
Lower calorific power 42 700 kJ/kg
Consumption tolerances ±5%
Air inlet limit de temperature 35 °C / 95 °F
Not contractual picture
Electrical power
Power in kVA declared at pf 0.8
GENERAL DATA
Models Nb cyl Arrangement Bore (mm) Stroke (mm) Swept vol. (l) Flywheel housing
4 W105S 4 in line 105 130 4.50 SAE 3
6 W105S 6 in line 105 130 6.75 SAE 3
6 W126S 6 in line 126 155 11.56 SAE 1
6 M19.3 6 in line 126 155 11.56 SAE 1
6 M26.2 6 in line 150 150 15.90 SMB
8 M26.2 8 in V 150 150 21.20 SAE 0
12 M26.2 12 in V 150 150 31.80 SAE 0
Continuous power (COP) Prime running power (PRP) Limited time running power (consult us)
Rated load without time or load Variable load with mean power calculated on Variable load with mean power calculated on
factor limitation 250 running hours 250 running hours
No restriction on use if mean power ≤ 75% of No overload
nominal power Typical hours per year 500 hours (with mean
Total operating time at 100% nominal power power ≤ 85% of rated power)
shall not exceed 500 hours per year Total operating time at 100% rated power shall
10% overload available 1 hour each 12 hours not exceed 25 hours per year
Maximum continuous running time at 100%
rated power: 1 hour each 12 hours
3 PHASES SYNCHRONOUS GENERATOR OPTIONAL EQUIPMENTS (extract)
Moteurs Baudouin reserve the right to modify these specifications, without notice. Document not contractual.
DIMENSIONS
kVA kVA
A B C Kg (dry)
50 Hz 60 Hz
4 W105S 85 105 1 680 870 1 285 1 100
6 W105S 100 / 150 120 / 170 2 187 800 1 216 1 500
C
170 / 260 205 / 300 2 584 994 1 619 2 145
6 W126S
270 - 340 325 / 350 2 726 994 1 619 2 371
6 M19.3 400 450 3 239 994 1 320 3 025
6 M26.2 420 430 3 043 1 164 1 414 3 550
A B 8 M26.2 555 580 2 996 1 482 1 575 4 585
12 M26.2 875 875 3 878 1 456 1 575 6 130