Technical Manual FFQN
Technical Manual FFQN
Technical Manual FFQN
TECHNICAL MANUAL
Split Unit Air Conditioner
Ceiling Cassette C & E Series
FCQN-E, FFQN-C, FCRN-E, FFRN-C
— Cooling only & Heatpump [50Hz] —
Table of Contents
Nomenclature......................................................................................................................1
Indoor ............................................................................................................................1
Outdoor..........................................................................................................................1
Product Line-Up.............................................................................................................2
Application Information .....................................................................................................5
Operating Range ...........................................................................................................5
Refrigerant Circuit Diagrams (C Series) ........................................................................6
Refrigerant Circuit Diagrams (E Series) ........................................................................8
Installation Guideline ................................................................................................... 11
Sound Data........................................................................................................................16
Sound Pressure Level .................................................................................................16
NC Curve .....................................................................................................................17
Engineering & Physical Data ...........................................................................................21
Performance Data .............................................................................................................26
Calculation Steps.........................................................................................................26
Performance Tables .....................................................................................................28
Outline & Dimension ........................................................................................................50
Wiring Diagram .................................................................................................................53
Service & Maintenance ....................................................................................................64
Troubleshooting ...............................................................................................................66
Nomenclature
Indoor
FFRN 25 C X V1
Power Supply
V1: 1 phase 50 Hz 220-240V
Production
X: OYLM
Product Series
C: C Series
E: E Series
Capacity
25: 2.5 kW
Model
FFRN: Ceiling Cassette 2”x2” (Cooling Only)
FCRN: Ceiling Cassette 3”x3” (Cooling Only)
FFQN: Ceiling Cassette 2”x2” (Heatpump)
FCQN: Ceiling Cassette 3”x3” (Heatpump)
Outdoor
R(Y)N 25 C X V1
Power Supply
V1: 1 phase 50 Hz 220-240V
Y1: 3 phase 50 Hz 380-415V
Production
X: OYLM
Product Series
C: C Series
D: D Series
Capacity
25: 2.5 kW
Model
RR & RN: Single Split Condensing Unit (Cooling
Only)
RYN & RQ: Single Split Condensing Unit (Heatpump)
Product Line-Up
Indoor Unit
FCQN-E, FFQN-C, FCRN-E, FFRN-C
Classification
Refrigerant Control
Panel (Handset)
PCB
Fin
Nomenclature
BYC20CXW (BRC52A61)
BYC50EXW (BRC52A61)
BC20CXW (BRC52A62)
BC50EXW (BRC52A62)
Hydrophilic (Blue)
Cap Tube
FFRN25CXV1 X X X X
FFRN35CXV1 X X X X
FFRN50CXV1 X X X X
COOLING
FCRN50EXV1 X X X X
FCRN60EXV1 X X X X
FCRN71EXV1 X X X X
FCRN100EXV1 X X X X
FCRN125EXV1 X X X X
FFQN25CXV1 X X X X
FFQN35CXV1 X X X X
FFQN50CXV1 X X X X
HEATPUMP
FCQN50EXV1 X X X X
FCQN60EXV1 X X X X
FCQN71EXV1 X X X X
FCQN100EXV1 X X X X
FCQN125EXV1 X X X X
Outdoor Unit
R(Y)N / RR / RQ
Classification
Refrigerant Control
Safety Devices
Compressor
Others
Fin
Nomenclature
Phase Sequencer
Hydrophilic (Blue)
Bare Aluminium
Drain Elbow
Cap Tube
Contactor
Rotary
Scroll
TXV
RN25CXV1 X X X
RN25CGXV1 X X X
RN35CXV1 X X X
RN35CGXV1 X X X
RN50CXV1 X X X
RN50CGXV1 X X X
RN60CXV1 X X X
RN60CGXV1 X X X
COOLING
RR71CXV1 X X X
RR71CGXV1 X X X
RR90DXV1 X X X X X
RR90DGXV1 X X X X X
RR100DXV1 X X X X X
RR100DGXV1 X X X X X
RR100DXY1 X X X X X X X
RR100DGXY1 X X X X X X X
RR125DXY1 X X X X X X X
RR125DGXY1 X X X X X X X
Classification
Refrigerant Control
Safety Devices
Compressor
Others
Fin
Nomenclature
Phase Sequencer
Hydrophilic (Blue)
Bare Aluminium
Drain Elbow
Cap Tube
Contactor
Rotary
Scroll
TXV
RYN25CXV1 X X X X
RYN25CGXV1 X X X X
RYN35CXV1 X X X X
RYN35CGXV1 X X X X
RYN50CXV1 X X X X
RYN50CGXV1 X X X X
RYN60CXV1 X X X X
RYN60CGXV1 X X X X
HEATPUMP
RQ71CXV1 X X X X
RQ71CGXV1 X X X X
RQ90DXV1 X X X X X X
RQ90DGXV1 X X X X X X
RQ100DXV1 X X X X X X
RQ100DGXV1 X X X X X X
RQ100DXY1 X X X X X X X X
RQ100DGXY1 X X X X X X X X
RQ125DXY1 X X X X X X X X
RQ125DGXY1 X X X X X X X X
Application Information
Operating Range
Cooling
Outdoor
DB (°C)
46
43
19
14 19 23 Indoor WB (°C)
Heating
Outdoor
WB (°C)
18
10
-9
15 20 27 Indoor DB (°C)
10
Installation Guideline
Safety Precautions
• Installation and maintenance should be performed Please take note of the following important points
by qualified persons who are familiar with local code when installing.
and regulation, and experienced with this type of • Do not install the unit where leakage of flammable
appliance. gas may occur.
• All field wiring must be installed in accordance with If gas leaks and accumulates around the unit, it
the national wiring regulation. may cause fire ignition.
• Ensure that the rated voltage of the unit corresponds
to that of the name plate before commencing wiring • Ensure that drainage piping is connected properly.
work according to the wiring diagram. If the drainage piping is not connected properly,
• The unit must be GROUNDED to prevent possible it may cause water leakage which will dampen
hazard due to insulation failure. the furniture.
• All electrical wiring must not touch the refrigerant
piping or any moving parts of the fan motors. • Do not overcharge the unit.
• Confirm that the unit has been switched OFF before This unit is factory pre-charged. Overcharge will
installing or servicing the unit. cause over-current or damage to the compressor.
• Disconnect from the main power supply before
• Ensure that the unit’s panel is closed after service
servicing the air conditioner unit.
or installation.
• DO NOT pull out the power cord when the power is
ON. This may cause serious electrical shocks which Unsecured panels will cause the unit to operate
may result in fire hazards. noisily.
• Keep the indoor and outdoor units, power cable and • Sharp edges and coil surfaces are potential
transmission wiring, at least 1m from TVs and radios, locations which may cause injury hazards. Avoid
to prevent distorted pictures and static. {Depending from being in contact with these places.
on the type and source of the electrical waves, static • Before turning off the power supply, set the remote
may be heard even when more than 1m away}. controller’s ON/OFF switch to the “OFF” position
to prevent the nuisance tripping of the unit. If this is
not done, the unit’s fans will start turning automatically
when power resumes, posing a hazard to service
personnel or the user.
• Do not operate any heating apparatus too close to the
air conditioner unit. This may cause the plastic panel to
melt or deform as a result of the excessive heat.
• Ensure the color of wires of the outdoor unit and
the terminal markings are same to the indoors
respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
• Do not use joined and twisted wires for incoming
power supply.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products
shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the
refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and
national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling
and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative
consequences for the environment and human health. Please contact the installer or local authority for more
information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant
local and national legislation.
11
Clearance must be provided for the indoor unit from wall and obstacles as shown in figure below.
Beam
Max. 0.3 m
Max. 3.0 m
Min 0.5 m Min 0.5 m Min 0.5 m
Obstacles
Floor
The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or more.
Outdoor unit must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth
air flow. Select the coolest possible place where intake air should not hotter than the outside temperature
(Max. 45°C).
ALL MODELS A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm
12
3) Cable Size
Cooling only
FFRN25/35CXV1 FFRN50CXV1 FCRN50EXV1
Model Unit
RN25/35CXV1 RN50CXV1 RN50CXV1
Power supply cable size 1.5 2.5 2.5
mm²
Number of wire 3 3 3
Interconnection cable size 1.5 2.5 2.5
mm²
Number of wire 3 3 3
Recommended fuse A 15 20 13
Heatpump
FFQN25/35CXV1 FFQN50CXV1 FCQN50EXV1
Model Unit
RYN25/35CXV1 RYN50CXV1 RYN50CXV1
Power supply cable size 1.5 2.5 2.5
mm2
Number of wire 3 3 3
Interconnection cable size 1.5 2.5 2.5
mm2
Number of wire 5 5 5
Recommended fuse A 15 20 13
13
4) Refrigerant Piping
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases,
system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result
the compressor may become defective. Always choose the shortest path and follow the recommendation as
tabulated below:
FCRN100EXV1 FCRN125EXV1
Indoor
FCQN100EXV1 FCQN125EXV1
Model
RR90/100DXV1 RR100DXY1 RR125DXY1
Outdoor
RQ90/100DXV1 RQ100DXY1 RQ125DXY1
Max. Length, m 45 45
Max. Elevation, m 25 25
Max. No. of Bends 10 10
RR71CXV1 RR90DXV1
Model R(Y)N60CXV1
RQ71CXV1 RQ90DXV1
Liquid, mm / in 6.35 / 1/4 9.52 / 3/8 9.52 / 3/8
Suction, mm / in 15.88 / 5/8 15.88 / 5/8 15.88 / 5/8
14
5) Additional Charge
• The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
• When the piping length is more than 7.6m, please use the table below (unit in gram).
Cooling Only
Indoor FFRN25CXV1 FFRN35CXV1 FFRN50CXV1
Outdoor RN25CXV1 RN35CXV1 RN50CXV1
Add. Charge, g/m 11 9 10
Heatpump
Indoor FFQN25CXV1 FFQN35CXV1 FFQN50CXV1
Outdoor RYN25CXV1 RYN35CXV1 RYN50CXV1
Add. Charge, g/m 15 18 12
Example: FCRN60EXV1 & RN60CXV1 with 13m piping length, additional piping length is 5.5m. Thus,
Additional Charge = 5.5m x 10 g/m
= 55g
15
Sound Data
Sound Pressure Level
1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 42 45 40 35 27 20 10 41 35
FF(R)(Q)N25CXV1 Med 40 42 37 32 24 15 7 38 32
Low 38 40 34 28 20 10 5 35 29
High 45 45 40 35 27 20 11 41 35
FF(R)(Q)N35CXV1 Med 41 42 37 32 23 15 9 38 32
Low 38 38 33 28 18 9 8 34 28
High 48 47 43 38 30 24 14 44 38
FF(R)(Q)N50CXV1 Med 46 45 40 35 26 19 9 41 35
Low 44 40 36 31 21 12 5 37 31
High 37 38 35 26 17 8 6 34 30
Med 35 35 34 22 12 6 6 32 29
FC(R)(Q)N50EXV1
Low 34 31 31 18 9 6 6 30 25
Quiet 32 28 29 16 7 4 5 28 23
High 39 40 37 29 22 12 6 37 32
Med 37 37 34 25 17 8 4 34 29
FC(R)(Q)N60EXV1
Low 37 37 34 23 15 7 7 33 29
Quiet 36 36 33 22 12 7 8 32 28
High 46 44 43 36 30 23 12 42 38
Med 39 40 38 30 23 15 7 38 37
FC(R)(Q)N71EXV1
Low 38 38 35 26 19 9 5 35 34
Quiet 36 36 33 24 15 6 5 33 30
High 51 48 47 41 33 31 18 47 43
Med 52 44 44 37 28 24 11 44 39
FC(R)(Q)N100EXV1
Low 50 41 40 33 23 15 8 40 35
Quiet 46 36 37 26 15 6 6 36 32
High 52 50 48 44 35 34 22 49 44
Med 53 45 44 39 29 28 14 45 39
FC(R)(Q)N125EXV1
Low 53 43 42 37 27 24 10 43 37
Quiet 51 41 39 32 23 16 6 39 34
FF(R)(Q)N25/35/50CXV1
FC(R)(Q)N50/60/71EXV1
1.4m
Microphone
Standard : JIS C 9612
FC(R)(Q)N100EXV1
FC(R)(Q)N125EXV1 1.5m
Microphone
Standard: JIS B 8616
16
NC Curve
FF(R)(Q)N25CXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 NC-40
H
M NC-35
30 L NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
FF(R)(Q)N35CXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 NC-40
H
NC-35
M
30 L NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
17
FF(R)(Q)N50CXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
NC-50
NC-45
H
40
NC-40
M
L NC-35
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
FC(R)(Q)N50EXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30 NC-30
H
NC-25
M
20 NC-20
L
10
Q
0
125 250 500 1000 2000 4000 8000
18
FC(R)(Q)N60EXV1
70
Sound pressure level (dB, ref 20μPa)
60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
H
30 NC-30
M
L NC-25
20 NC-20
Q
10
0
125 250 500 1000 2000 4000 8000
FC(R)(Q)N71EXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 NC-40
H
NC-35
M
30 NC-30
L
NC-25
20 Q NC-20
10
0
125 250 500 1000 2000 4000 8000
19
FC(R)(Q)N100EXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
NC-50
NC-45
H
40
NC-40
M
NC-35
30 L
NC-30
NC-25
Q
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
FC(R)(Q)N125EXV1
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
NC-50
H NC-45
40
NC-40
M
NC-35
30 L
NC-30
Q
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
20
DRIVE DIRECT
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE CLASS B
FAN MOTOR RATED INPUT POWER W 55 65 59 59
RATED RUNNING CURRENT A 0.24 0.29 0.25 0.25
MOTOR MAX OUTPUT W 19 23 28 28
POLES 6
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE
DIAMETER mm 7
COIL MATERIAL ALUMINIUM (SLIT FIN)
FIN FACE AREA m2 0.318
ROW 1 2
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR WITHOUT PAINT
AIR FLOW I/s / CFM 396 / 840 453 / 960 614 / 1300 614 / 1300
SOUND PRESSURE LEVEL dBA 46 49 52 52
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 540 X 700 X 250 540 X 700 X 250 651 X 855 X 328 651 X 855 X 328
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 620 X 810 X 330 620 X 810 X 330 710 X 990 X 415 710 X 990 X 415
UNIT WEIGHT (RN / RYN) kg 28 30 47 47
TYPE FLARE VALVE
PIPE
LIQUID mm 6.35 6.35 6.35 6.35
CONNECTION SIZE
GAS mm 9.52 12.70 12.70 12.70
TYPE PROPELLER
FAN
DRIVE DIRECT
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP22 IP22 IP23 IP23
INSULATION GRADE CLASS B CLASS B CLASS F CLASS F
FAN MOTOR RATED INPUT POWER W 57 70 80 80
RATED RUNNING CURRENT A 0.25 0.31 0.36 0.36
MOTOR OUTPUT W 24 35 42 42
OUTDOOR UNIT
POLES 6 6 6 6
TYPE ROTARY
OIL TYPE RB68A or FREOL ALPHA68M RB68A or FREOL ALPHA68M
OIL AMOUNT cm3 350 430 670 670
RN RATED INPUT POWER W 788 1165 1551 1693
RATED INPUT POWER
W 788 1165 1551 1693
(COOLING)
RYN
COMPRESSOR RATED INPUT POWER
W 718 881 1571 1643
(HEATING)
RATED RUNNING CURRENT A 3.51 5.3 7.11 7.49
RATED RUNNING CURRENT
A 3.51 5.3 7.11 7.49
(COOLING)
RATED RUNNING CURRENT
A 3.21 3.98 7.14 7.29
(HEATING)
LOCKED ROTOR AMP. A 19 24 26 26
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE
DIAMETER (RN/RYN) mm 7 7 / 9.52 7 7
COIL MATERIAL ALUMINIUM (RAISE LANCE)
FIN FACE AREA m2 0.36 0.51
ROW 1 1 2 2
CASING COLOUR LIGHT GREY
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING HEATING
INDOOR: 27°C DB/ 19°C WB INDOOR: 20°C DB
OUTDOOR: 35°C DB/ 24°C WB OUTDOOR: 7°C DB/ 6°C WB
21
22
FAN
DRIVE DIRECT
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE CLASS B
FAN MOTOR RATED INPUT POWER W 176 176 221
RATED RUNNING CURRENT A 0.79 0.79 0.97
MOTOR MAX OUTPUT W 60 100
POLES 6
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE
DIAMETER mm 7
COIL MATERIAL ALUMINIUM (SLIT FIN)
FIN FACE AREA m2 0.461 0.464
ROW 3
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR WITHOUT PAINT
AIR FLOW I/s / CFM 1605 / 3400 2171 / 4600
SOUND PRESSURE LEVEL dBA 58 60
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 852 X 1030 X 400
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 1010 x 1180 x 514
UNIT WEIGHT (RN / RYN) kg 86 95 98
TYPE FLARE VALVE
PIPE
LIQUID mm 9.52
CONNECTION SIZE
GAS mm 15.88
TYPE PROPELLER
FAN
DRIVE DIRECT
TYPE INDUCTION
INDEX OF PROTECTION (IP) N/A N/A IP20
INSULATION GRADE CLASS B CLASS B CLASS F
FAN MOTOR RATED INPUT POWER W 257 257 276
RATED RUNNING CURRENT A 1.1 1.1 1.34
MOTOR OUTPUT W 145
OUTDOOR UNIT
POLES 8
TYPE SCROLL
OIL TYPE MOBIL EAL ARCTIC 22C
OIL AMOUNT cm3 1242 1951 1656
RN RATED INPUT POWER W 2337 3487 3893
RATED INPUT POWER
W 2337 3487 3893
(COOLING)
RYN
COMPRESSOR RATED INPUT POWER
W 2117 3307 3513
(HEATING)
RATED RUNNING CURRENT A 4.57 16 7.03
RATED RUNNING CURRENT
A 4.57 16 7.03
(COOLING)
RATED RUNNING CURRENT
A 4.37 15.40 6.53
(HEATING)
LOCKED ROTOR AMP. A 48 136 74
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE
DIAMETER (RN/RYN) mm 7 7 7
COIL MATERIAL ALUMINIUM (CORR.FIN)
FIN FACE AREA m 2
0.87
ROW 2
CASING COLOUR LIGHT GREY
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING HEATING
INDOOR: 27°C DB/ 19°C WB INDOOR: 20°C DB
OUTDOOR: 35°C DB/ 24°C WB OUTDOOR: 7°C DB/ 6°C WB
23
Safety Device
FFRN25/35CXV1 FFRN50CXV1
INDOOR
MODEL FFQN25/35CXV1 FFQN50CXV1
OUTDOOR R(Y)N25CXV1 R(Y)N50CXV1
TYPE N/A
HIGH PRESSURE
OPEN kPa / psi N/A
SWITCH
CLOSE kPa / psi N/A
SAFETY TYPE N/A
DEVICE LOW PRESSURE
OPEN kPa / psi N/A
SWITCH
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISC. THERMOSTAT SETTING °C / F N/A
FCRN50/60/71EXV1
INDOOR
FCQN50/60/71EXV1
MODEL
R(Y)N50/60CXV1
OUTDOOR
R(R )(Q)71CXV1
TYPE N/A
HIGH PRESSURE
OPEN kPa / psi N/A
SWITCH
CLOSE kPa / psi N/A
SAFETY TYPE N/A
DEVICE LOW PRESSURE
OPEN kPa / psi N/A
SWITCH
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISC. THERMOSTAT SETTING °C / F N/A
INDOOR FCRN100EXV1
MODEL
OUTDOOR RR90DXV1 RR100DXV1 RR100DXY1
TYPE NC
HIGH PRESSURE
OPEN kPa / psi 4140 / 600.46
SWITCH
CLOSE kPa / psi 3310 / 480.07
SAFETY TYPE NC
DEVICE LOW PRESSURE
OPEN kPa / psi 48 / 6.96
SWITCH
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A 130 / 266
INDOOR FCRN125EXV1
MODEL
OUTDOOR RR125DXY1
TYPE NC
HIGH PRESSURE
OPEN kPa / psi 4140 / 600.46
SWITCH
CLOSE kPa / psi 3310 / 480.07
SAFETY TYPE NC
DEVICE LOW PRESSURE
OPEN kPa / psi 48 / 6.96
SWITCH
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F 130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
24
INDOOR FCQN100EXV1
MODEL
OUTDOOR RQ90DXV1 RQ100DXV1 RQ100DXY1
TYPE NC
HIGH PRESSURE
OPEN kPa / psi 4140 / 600.46
SWITCH
CLOSE kPa / psi 3310 / 480.07
SAFETY TYPE NC
DEVICE LOW PRESSURE
OPEN kPa / psi 48 / 6.96
SWITCH
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A 130 / 266
INDOOR FCQN125EXV1
MODEL
OUTDOOR RQ125DXY1
TYPE NC
HIGH PRESSURE
OPEN kPa / psi 4140 / 600.46
SWITCH
CLOSE kPa / psi 3310 / 480.07
SAFETY TYPE NC
DEVICE LOW PRESSURE
OPEN kPa / psi 48 / 6.96
SWITCH
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F 130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
25
Performance Data
Calculation Steps
Interpolation method can be used to get the total Solution:
cooling capacity, TC and sensible cooling capacity, Based on the Performance Table,
SC and power input, PI at those temperatures which
1. Refer to the Indoor DB column,
are not stated out in the table. Extrapolation method
- 25°C is located between 24°C & 27°C
is not allowed to be used.
for 16°C WB.
Example: - 25°C is located between 24°C & 27°C
for 19°C WB.
Model: FFRN25CXV1 - RN25CXV1 - Thus, Interpolation needs to be applied.
Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB 2. Refer to the Indoor WB column,
Fan Speed: High - 17°C is located between 16°C & 19°C
for 25°C DB.
- Thus, Interpolation needs to be applied.
3. Refer to the Outdoor DB column,
- 37°C is located between 35°C & 40°C.
- Thus, Interpolation needs to be applied.
Details of Calculation:
1st Step: By Interpolation Method
To obtain the TC, SC & PI for 25°C – 24°C x1 – 3.20kW
⇒ =
27°C – 24°C 3.30kW – 3.20kW
(a) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 35°C DB ⇒ x1 = 3.23kW
Outdoor temperature Similarly,
EWB EDB 35°C
y1 = 3.23kW
TC SC PI
z1 = 1.27kW
26
Repeat the same process for (c) & (d) in 1st Step
(c) x3 = 2.98 kW; y3 = 2.98 kW; z3 = 1.38 kW (d) x4 = 3.22 W; y4 = 2.53 kW; z4 = 1.40 kW
3rd Step:
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Outdoor temperature
EWB EDB 35°C 37°C 40°C
TC SC PI TC SC PI TC SC PI
27
Performance Tables
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
28
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
29
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
30
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
31
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
32
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
33
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
34
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
35
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
36
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
37
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
38
R410A Heatpump
Model: FFQN25CXV1 - RYN25CXV1
Cooling Mode
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 2.62 2.08 0.68 2.53 2.03 0.74 2.43 1.97 0.80 2.34 1.92 0.87 2.15 1.78 0.94 1.98 1.68 1.04
24°C 2.63 2.49 0.68 2.53 2.44 0.74 2.44 2.38 0.80 2.34 2.32 0.87 2.15 2.15 0.94 1.99 1.99 1.04
16°C
27°C 2.65 2.65 0.69 2.56 2.56 0.74 2.47 2.47 0.80 2.37 2.37 0.87 2.19 2.19 0.95 2.04 2.04 1.04
30°C 2.73 2.73 0.69 2.65 2.65 0.75 2.57 2.57 0.81 2.49 2.49 0.88 2.30 2.30 0.95 2.16 2.16 1.05
24°C 2.89 1.94 0.69 2.79 1.89 0.75 2.69 1.84 0.81 2.58 1.79 0.88 2.37 1.67 0.96 2.19 1.57 1.06
27°C 2.89 2.22 0.69 2.79 2.17 0.75 2.69 2.12 0.81 2.58 2.07 0.88 2.37 1.94 0.96 2.20 1.84 1.06
330 19°C
30°C 2.90 2.74 0.69 2.80 2.69 0.75 2.70 2.63 0.82 2.60 2.56 0.88 2.39 2.39 0.96 2.22 2.22 1.06
33°C 2.93 2.93 0.70 2.84 2.84 0.75 2.75 2.75 0.82 2.65 2.65 0.89 2.45 2.45 0.96 2.29 2.29 1.07
27°C 3.18 1.90 0.71 3.07 1.86 0.77 2.96 1.81 0.83 2.84 1.76 0.90 2.61 1.64 0.98 2.42 1.55 1.08
30°C 3.18 2.32 0.71 3.07 2.27 0.77 2.96 2.22 0.83 2.84 2.16 0.90 2.62 2.03 0.98 2.42 1.92 1.08
22°C
33°C 3.18 2.71 0.71 3.07 2.66 0.77 2.96 2.60 0.83 2.85 2.55 0.90 2.62 2.39 0.98 2.43 2.27 1.08
36°C 3.19 3.07 0.71 3.09 3.01 0.77 2.98 2.95 0.83 2.87 2.87 0.90 2.65 2.65 0.98 2.46 2.46 1.08
21°C 2.73 2.17 0.69 2.63 2.11 0.75 2.53 2.06 0.81 2.43 2.00 0.88 2.23 1.86 0.95 2.05 1.75 1.05
24°C 2.74 2.63 0.69 2.64 2.57 0.75 2.54 2.51 0.81 2.44 2.44 0.88 2.24 2.24 0.95 2.07 2.07 1.05
16°C
27°C 2.77 2.77 0.69 2.68 2.68 0.75 2.58 2.58 0.81 2.49 2.49 0.88 2.30 2.30 0.96 2.14 2.14 1.05
30°C 2.88 2.88 0.70 2.80 2.80 0.75 2.72 2.72 0.82 2.63 2.63 0.89 2.43 2.43 0.97 2.27 2.27 1.07
24°C 3.00 2.05 0.70 2.90 2.00 0.76 2.79 1.95 0.82 2.68 1.90 0.89 2.46 1.77 0.97 2.27 1.67 1.07
27°C 3.01 2.37 0.70 2.90 2.31 0.76 2.79 2.26 0.82 2.68 2.21 0.89 2.46 2.06 0.97 2.28 1.95 1.07
360 19°C
30°C 3.02 2.92 0.70 2.92 2.85 0.76 2.81 2.79 0.82 2.71 2.71 0.89 2.49 2.49 0.97 2.31 2.31 1.07
33°C 3.07 3.07 0.70 2.98 2.98 0.76 2.89 2.89 0.83 2.79 2.79 0.90 2.58 2.58 0.98 2.42 2.42 1.08
27°C 3.30 2.01 0.71 3.19 1.96 0.77 3.07 1.91 0.84 2.94 1.86 0.91 2.71 1.74 0.99 2.50 1.64 1.09
30°C 3.31 2.47 0.71 3.19 2.42 0.77 3.07 2.36 0.84 2.95 2.31 0.91 2.71 2.16 0.99 2.51 2.05 1.09
22°C
33°C 3.31 2.89 0.71 3.20 2.84 0.77 3.08 2.78 0.84 2.96 2.72 0.91 2.72 2.55 0.99 2.52 2.42 1.09
36°C 3.33 3.27 0.72 3.22 3.21 0.78 3.11 3.11 0.84 3.00 3.00 0.91 2.77 2.77 0.99 2.58 2.58 1.09
21°C 2.83 2.27 0.70 2.72 2.21 0.75 2.62 2.15 0.81 2.51 2.09 0.88 2.30 1.95 0.96 2.12 1.83 1.06
24°C 2.84 2.75 0.70 2.74 2.69 0.75 2.64 2.62 0.82 2.53 2.53 0.88 2.32 2.32 0.96 2.15 2.15 1.06
16°C
27°C 2.89 2.89 0.70 2.79 2.79 0.76 2.70 2.70 0.82 2.60 2.60 0.89 2.41 2.41 0.97 2.24 2.24 1.07
30°C 3.03 3.03 0.70 2.94 2.94 0.76 2.85 2.85 0.83 2.76 2.76 0.90 2.56 2.56 0.98 2.39 2.39 1.08
24°C 3.11 2.17 0.71 3.00 2.12 0.77 2.89 2.06 0.83 2.77 2.01 0.90 2.54 1.87 0.98 2.35 1.77 1.07
27°C 3.12 2.51 0.71 3.01 2.46 0.77 2.90 2.40 0.83 2.78 2.34 0.90 2.55 2.19 0.98 2.36 2.07 1.08
410 19°C
30°C 3.15 3.09 0.71 3.04 3.03 0.77 2.93 2.93 0.83 2.82 2.82 0.90 2.59 2.59 0.98 2.41 2.41 1.08
33°C 3.22 3.22 0.71 3.12 3.12 0.77 3.03 3.03 0.84 2.93 2.93 0.91 2.71 2.71 0.99 2.54 2.54 1.09
27°C 3.42 2.13 0.72 3.29 2.08 0.78 3.17 2.03 0.85 3.04 1.97 0.92 2.80 1.84 0.99 2.58 1.74 1.10
30°C 3.42 2.62 0.72 3.30 2.57 0.78 3.18 2.51 0.85 3.05 2.46 0.92 2.80 2.30 1.00 2.59 2.18 1.10
22°C
33°C 3.43 3.07 0.72 3.32 3.02 0.78 3.19 2.95 0.85 3.07 2.89 0.92 2.82 2.71 1.00 2.62 2.57 1.10
36°C 3.47 3.47 0.72 3.36 3.36 0.78 3.24 3.24 0.85 3.12 3.12 0.92 2.89 2.89 1.00 2.69 2.69 1.11
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
39
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
40
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
41
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
42
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
43
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
44
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
45
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
46
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
47
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
48
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
49
Note: Dimension in mm
Model: FC(R)(Q)N50/60/71/100/125EXV1
B F
C
D E
H
K
A
G
I
J
Dimension
A B C D E F G H I J K
Model
FC(R)(Q)N50/60/71EXV1 820 820 340 300 40 990 990 627 627 607 430
FC(R)(Q)N100/125EXV1 820 820 375 335 40 990 990 627 627 607 430
Note: Dimension in mm
50
Outdoor Unit
Model: R(Y)N25/35CXV1
L K L
N
M
Q
N
A
C
O D G H
F
E
B
S
R
I J
P
Dimension
A B C D E F G H I J K L M N O P Q R S
Model
R(Y)N25/35CXV1 700 521 250 478 175 36 95 94 86 68 440 130 110 15 21 19 278 80 65
Note: Dimension in mm
L K L
N
M
Q
N
C
A
G H
F
O D
E
B
S
R
I J
P
Dimension
A B C D E F G H I J K L M N O P Q R S
Model
R(Y)N50CXV1 855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 23 362 73 75
R(Y)N60CXV1 /
855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 23 362 73 75
R(R)(Q)71CXV1
Note: Dimension in mm
51
J I J
N
M
N
A O C
K D
MADE IN MALAYSIA
B
F
E
G H
L
Dimension
A B C D E F G H I J K L M N O
Model
R(R)(Q)90/100DXV1 /
1030 826 400 410 57 72 90 40 746 142 60 26 448 22 28
R(R)(Q)100/125DXY1
Note: Dimension in mm
52
Wiring Diagram
Cooling Only
Indoor Unit Outdoor Unit
Model: FFRN25/35CXV1 Model: RN25/35CXV1
53
54
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
CN STP
COMP. N2
N1
SILENT
HIGH
L
WTP
LOW
MED
4WV
OF
LIVE
G/Y
DP
AS
KEY:
BLUE
RED
RED
PURPLE PURPLE FH
BLUE
BLUE
RED
BLUE
COMP. N1 L N
M.C
220-240V/1PH/50Hz
WHITE
C
RED
S
CM CAPACITOR
R BLUE BLUE
BLUE
GREEN/YELLOW
BLUE
CAPACITOR
RED
FM BLACK
KEY:
CM - COMPRESSOR MOTOR COMP N
FM - FAN MOTOR
- FIELD SUPPLY WIRING
PART NO. : 08 02 4 072886
55
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
CN STP
COMP. N2
N1
SILENT
HIGH
L
LOW
MED
WTP
4WV
OF
LIVE
G/Y
DP
AS
KEY:
BLUE
RED
RED
PURPLE PURPLE FH
BLUE BLUE
BLUE
RED
COMP. L N
M.C
E
(FROM POWER SUPPLY) N
L
WHITE
RED
CAP.
L N S R COMP. L N
BLUE
BLUE
G/Y
7A
RED RED RED
RED 8 7 WHITE
WHITE
BLACK
FM
GREEN/YELLOW
S R
WHITE BROWN
C
CRANKCASE
COMPRESSOR HEATER
56
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
CN STP
COMP. N2
N1
SILENT
HIGH
L
LOW
MED
WTP
4WV
OF
LIVE
G/Y
DP
AS
KEY:
BLUE
RED
RED
PURPLE PURPLE FH
BLUE BLUE
BLUE
RED
COMP. L N
M.C
E
N
350~410V
T
3PH/50Hz
S
R
R S T N COMP. L N
G/Y G/Y
RED RED
7A
BLUE
BLACK
WHITE
RED
WHITE
BLUE
BLACK
WHITE
BLUE
RED
BLUE
RED
RED
WHITE
BLACK
T2 T3
T1
BROWN
G/Y
COMP. CRANKCASE
HEATER
FM
BROWN
57
Heatpump
Indoor Unit Outdoor Unit
Model: FFQN25/35CXV1 Model: RYN25/35CXV1
WIRED OR
RETURN AIR SENSOR WIRELESS
CN2 CN6
REMOTE
ROOM CONTROLLER
CN5
ID
INDOOR COIL SENSOR
OD TRANSFORMER
OUTDOOR COIL SENSOR TWIN
T-FULL
COMP.
FLOAT SWITCH
L
N1
RED
4WV
HIGH MED
OF
AS
LOW
WTP
LIVE
N2
PURPLE FH PURPLE
ORANGE FM ORANGE
BROWN FL BROWN
BLUE
RED BLUE
BLUE
BLUE
WHITE
RED
BLUE
PURPLE
BROWN
DP
BLACK
RED
G/Y G/Y
BLUE AS BLUE
AC IC G/Y
MC
4WV OF COMP L N N
FAN MOTOR
KEY :
FIELD SUPPLY WIRING E 1 PHASE
AS : AIR SWING MOTOR N 220/240VAC 50Hz OR
DP : DRAIN PUMP L 208/230VAC 60Hz
N COMP OF 4W V
4WV BLACK
BLACK
BLACK
RED FM
CAPACITOR
BLACK
BLACK
BLUE
BLUE
GREEN/YELLOW
BLUE BLUE R
TH2
CAPACITOR CM
S
RED
C
OLP
WHITE WHITE
PART NO. : 08 02 4 111953A
58
WIRED OR
RETURN AIR SENSOR WIRELESS
CN2 CN6
REMOTE
ROOM CONTROLLER
CN5
ID
INDOOR COIL SENSOR
OD TRANSFORMER
OUTDOOR COIL SENSOR TWIN
T-FULL
COMP.
FLOAT SWITCH
L
N1
RED
4WV
OF HIGH MED
AS
LOW
WTP
LIVE
N2
PURPLE FH PURPLE
ORANGE FM ORANGE
BROWN FL BROWN
BLUE
RED BLUE
BLUE
BLUE
WHITE
RED
BLUE
PURPLE
BROWN
DP
BLACK
RED
G/Y G/Y
BLUE AS BLUE
AC IC G/Y
MC
4WV OF COMP L N N
FAN MOTOR
KEY :
FIELD SUPPLY WIRING E 1 PHASE
AS : AIR SWING MOTOR N 220/240VAC 50Hz OR
DP : DRAIN PUMP L 208/230VAC 60Hz
N COMP OF 4W V
4WV BLACK
BLACK
BLACK
RED
FM
CAPACITOR
BLACK
BLACK
BLUE
BLUE
GREEN/YELLOW
BLUE BLUE R
TH2
CAPACITOR CM
S
RED
C
WHITE
PART NO. : 08 02 4 113354
59
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
TO OUTDOOR DEFROST SENSOR
COMP. CN STP
N2
L N1
SILENT
HIGH
LOW
MED
WTP
4WV
OF
LIVE
G/Y
DP
AS
KEY:
PURPLE PURPLE FH
BLUE
PURPLE
BROWN
BLACK
BLUE
RED
BLUE G/Y
4WV OF COMP. N1 L N
E A.C I.C G/Y
220~240V
N
1PH/50Hz
L M.C
WHITE
C
RED
S
CAPACITOR
CM
TH2
R BLUE BLUE
GREEN/YELLOW
BLUE
BLUE
BLACK
BLACK
RED CAPACITOR
FM
BLACK
BLACK
BLACK 4WV
KEY:
CM - COMPRESSOR MOTOR 4WV OF COMP N
FM - FAN MOTOR
4WV - 4 WAY VALVE
TH2 - OUTDOOR THERMISTER
FIELD SUPPLY WIRING
60
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
TO OUTDOOR DEFROST SENSOR
CN STP
COMP.
N2
KEY:
SILENT
L
HIGH
WTP
MED
LOW
4WV
OF
LIVE
AS - AIR SWING MOTOR
DP - DRAIN PUMP G/Y
AS DP
PINK PINK FS
BROWN BROWN FL
ORANGE ORANGE FM
PURPLE
BROWN
BLACK
BLUE
RED
RED
PURPLE PURPLE FH
BLUE
BLUE
RED
A 4WV OF COMP. L N
M.C
E
220~240V
N
1R/50Hz
L
L N A 4WV OF COMP L N
7A
RED RED
BLUE
G/Y G/Y
RED
WHITE
A1
BLUE
4WV
U/2/T1 W/6/T3 32 A2
14 V/4/T2 (NC)
BLACK
(NO)
BLUE
BLUE
RED RED
WHITE
BLUE
WHITE
WHITE
BROWN BROWN
O/D COIL SENSOR
WHITE
C CRANKCASE
BLACK
RED
61
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
TO OUTDOOR DEFROST SENSOR
CN STP
COMP.
N2
KEY:
SILENT
L
HIGH
WTP
MED
LOW
4WV
OF
LIVE
AS - AIR SWING MOTOR
DP - DRAIN PUMP G/Y
AS DP
PINK PINK FS
BROWN BROWN FL
ORANGE ORANGE FM
PURPLE
BROWN
BLACK
BLUE
RED
RED
PURPLE PURPLE FH
BLUE
BLUE
RED
A 4WV OF COMP. L N
M.C
E
N
380~410V
T
3R/50Hz
S
R
R S T N A 4WV OF COMP L N
G/Y
G/Y
BLACK
WHITE
BLUE
RED
BLUE
7A
RED RED
BLUE
BLACK
WHITE
WHITE
BLACK
BLACK
BLACK
RED
NRST
BLUE
BLUE
NO DT
COM
BLUE
RED HIGH
PRESSURE
SWITCH
3/L2 (NC) BLUE BLACK
1/L1 5/L3 21 4WV
A1
WHITE
2/T1 6/T3 22
4/T2 (NC) A2
RED
BROWN
BROWN
CRANKCASE
BLACK
O/D COIL SENSOR
WHITE
HEATER
BLUE
RED
T2 T3
OUTDOOR
FAN MOTOR
T1 COMP.
62
FLOAT SWITCH
TRANSFORMER
CN_DSP
INDOOR AIR SENSOR
TO OUTDOOR DEFROST SENSOR
CN STP
COMP.
N2
KEY:
SILENT
L
HIGH
WTP
MED
LOW
4WV
OF
LIVE
AS - AIR SWING MOTOR
DP - DRAIN PUMP G/Y
AS DP
PINK PINK FS
BROWN BROWN FL
ORANGE ORANGE FM
PURPLE
BROWN
BLACK
BLUE
RED
RED
PURPLE PURPLE FH
BLUE
BLUE
RED
A 4WV OF COMP. L N
M.C
E
N
380~410V
T
3R/50Hz
S
R
R S T N A 4WV OF COMP L N
G/Y
G/Y
WHITE
BLACK
BLUE
RED
BLUE
7A
RED RED
BLUE
BLACK
WHITE
WHITE
RED
BLACK
BLACK
BLACK
NRST
BLUE
BLUE
NO DT
RED COM
BLUE
HIGH
PRESSURE
SWITCH
3/L2 (NC) BLUE BLACK
1/L1 5/L3 21 4WV
A1
WHITE
2/T1 6/T3 22
4/T2 (NC) A2
RED
BROWN
BROWN
CRANKCASE
O/D COIL SENSOR
BLACK
WHITE
HEATER
RED
BLUE
T2 T3
OUTDOOR
FAN MOTOR
T1 COMP.
63
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
• When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
• For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.
64
Outdoor Models
The design of the RN/RYN/RR/RQ-C/D outdoor series allows servicing to be carried out easily. The removal
of the top, front and side panels makes almost every part accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface
once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must
be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and
proper operation. Otherwise, the systems life span may be shortened.
• Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to
high temperature and pressure.
• It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test.
65
Troubleshooting
Indicator Lights
LED Indicator Light Display - Cooling Only LED Indicator Light Display - Heatpump
/
POWER TIMER SLEEP POWER TIMER HEAT / SLEEP
Error Operation /
Action
Code Faulty Indication
GREEN ORANGE RED RED
- Cooling mode -
- Timer On -
- Sleep mode On -
- Heating mode -
Auto Mode in cooling
- -
operation
Auto Mode in heating
- -
operation
Check room sensor
Room air sensor contact
E1 connection / change room air
1 time loose / short
sensor
Check indoor coil sensor
Indoor coil sensor contact
E2 connection / change indoor
2 times open
coil sensor
Check outdoor coil sensor
Outdoor coil sensor contact
E3 connection / change outdoor
3 times open
coil sensor
If running ampere highly
Compressor overload
increase, change the
E4 protection / Indoor or Outdoor
1 time compressor. If not, replace
coil sensor short
the coil sensor.
Clear the clogging at drain
E6 Pump fault pipe. If pump is not working,
2 times
change the pump.
Top up refrigerant / check for
E5 Gas leak
3 times leakage
ON BLINKING
66
Phase Sequencer
The unit with Scroll Compressor only can rotate in one direction. For this reason, a protective device (phase
sequencer) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not
connected correctly, the phase sequencer operates, and the unit will not start.
The following table shows the LED indicator light for phase sequencer under normal operation and fault
conditions.
LED PW P_R P_S P_T Actions
Description (Red) (Yellow) (Yellow) (Yellow)
Normal Operation -
Reverse Phase Switch off the unit. Check the 3 phase wiring.
T Phase Missing Switch off the unit. Check the 3 phase wiring.
S Phase Missing Switch off the unit. Check the 3 phase wiring.
R Phase Missing Switch off the unit. Check the 3 phase wiring.
S & T Phase
Switch off the unit. Check the 3 phase wiring.
Missing*
High discharge temperature.
Overload*
Check refrigerant system.
Sensor Missing* Switch off the unit. Plug in sensor.
ON OFF BLINK
Note:
1. “ * ” indicates additional function for PP01 phase sequencer.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (COMMON) and 81 (NO) will cut off.
3. The unit will check discharge sensor availability only during power up.
4. All errors can only recover through manually reset.
67
68
Diagnostic Guidelines
A little high
Probable cause
A little low
Too high
Too low
Circuit Normal
High side • 1. Overcharged with refrigerant.
Low side • 2. Non-condensable gases in refrigerant circuit (e.g. air).
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side • 1. Poor compression /no compression (compressor
Low side • defective)
2. Reversing valve leaking.
High side • 1. Undercharged with refrigerant.
Low side • 2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up
(heating).
6. Outdoor fan locked / seized (heating).
High side • 1. Outdoor fan blocked (cooling).
Low side • 2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air).
High side • 1. Air intake temperature of indoor unit too high.
Low side •
69