Larsen & Toubro Limited: Distribution Transformer Sizing Calculation
Larsen & Toubro Limited: Distribution Transformer Sizing Calculation
on to any third person or firm not authorised by us, nor be copied/made use of in full or part by such person or firm without our prior permission
CLIENT : CONSULTANT :
SUPPLIER / CONTRACTOR:
writing
APPD DM 29/12/07
CODE REV.
DOC. No. S 0 0 0 0 - E - I E - G E - D C - 0 0 0 2
0
DESIGN CALCULATION
INDEX
3.0.0 ASSUMPTIONS 4
9.0.0 RESULT 7
Page6 of 33
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION
S0000-E-IE-GE-DC-0003 12/29/2007
DM Design Margin
f Supply Frequency Hz
XT Transformer reactance Ω
Z Transformer impedance %
3.0.0 ASSUMPTIONS
The power transformer is with OLTC which compensates the voltage drop due to source during steady state condition and 100 % voltage is
maintained at the source.
The voltage drop due to bus duct / cable between primary and source has been neglected.
4.1.3 Frequency f : 50 Hz
4.1.9.3 Full load power factor CosØ : 0.8 (Refer Motor data sheet)
4.1.9.4 Starting power factor Cosqs : 0.3 (Refer Motor data sheet)
Sinqs : 0.954
Page10 of 33
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION
S0000-E-IE-GE-DC-0003 12/29/2007
No of runs : 1
NA
: 1737.4
(1 - 0.2)
: 2172 kVA
: 1678 kVA
: BL * 1000
√3 * 415
: 2334.51 A
Page11 of 33
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION
S0000-E-IE-GE-DC-0003 12/29/2007
: 55 * 1000
√3*415**0.8 * 0.9
: 106.276 A
: 765.1872 A
: 550.00 kVA
: 550.002 + 1678
: 2228 kVA
: 5000 kVA
So over load withstand capacity of the Transformer
: 0.0285 * 0.172225
XSO : 0.005 Ω
Is Xso 3.69 V
Vb
Is Xm 8.30 V
Page13 of 33
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION
S0000-E-IE-GE-DC-0003 12/29/2007
Vm IS Rm
220.26 V
Vm Sinqs
Vm Cosqs IS
69.2627 7
Page14 of 33
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION
S0000-E-IE-GE-DC-0003 12/29/2007
8.1.5 Calculation
Also, bus voltage Vb : (Vm cos qs+ IS Rm)2 + (Vm sin qs +IS Xm)2 ----------(c)
Putting the Equations (a), (b) & (c) in Equation (I) we get)
2 2
Vph2 = Vm Cosqs + Ist Rm Vm + Vm Sinqs + Ist Vm (Xm+ XSO) + XSO Im1 (Vph-Vb)
Vph Vph Vb
Vm : 230.88 V
: 96.36 %
Vb : 240.98 V
: 100.58 %
Im2 : 2334.512*239.608
240.98
: 2321.221 A
IS : 737.301 A
9.0.0 RESULT
Voltage available at motor terminal during motor starting 96.36% 85% 0.00%
Page15 of 33
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION
S0000-E-IE-GE-DC-0003 12/29/2007
As all the conditions are satisfied, the selected transformer size of 2.5 MVA is Safe