Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Transformer Specification - GTP (25MVA)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GUARANTEED TECHNICAL PARTICULARS OF

400 /11 KV AIS 20/25MVA TRANSFORMER


S.No Description Technical data
1 Type of Transformer Power Transformer
2 Service OUTDOOR
3 Continuos Rating 20/25MVA
4 Rated Voltage :
HV Winding 400KV
LV Winding 11KV
5 Terminal arrangement:
HV (kV/Amp) 420/800
LV (kV/Amp) 36/2000
Neutral (kV/Amp) 36/800
6 Frequency 50Hz
7 Number of Phases 3
8 Connections :
HV Winding STAR
LV Winding DELTA
9 Connection symbol
HV – LV YNd1
10 Tapings : (ON-load) ON-load
Range +10% to -10%
Number of steps In step of @ 1.25% each
For high voltage variation High voltage variation
Make of ON Load Tap Changer CTR/EASun MR/BHEL
RTCC with AVR and TPI. Required
11 Losses
No Load Loss 25KW MAX
Load Loss at Normal ratio@75 Deg C including auxillary loss if
96KW MAX @ 25MVA
any
Total Loss @ Rated Voltage, rated output, rated frequency
12
@75Deg C
Normal Voltage Tap kW 121max at 25MVA base
Maximum Voltage Tap kW 119 approx. at 25MVA base
Minimum Voltage Tap kW 138 approx. at 25MVA base
13 Impedance Voltage at Normal @75Deg C
Normal Voltage Tap % 12.5(Tol.+ 7.5%)
Maximum Voltage Tap % 13(Tol.+ 10%)
Minimum Voltage Tap % 12(Tol.+ 10%)
14 Maximum temperature
oil by Thermometer 50 K
Winding by Resistance 55 K
By Hot spot temperature adopted 66 K
Ambient temperature adopted 50 Deg C
15 Type of Cooling ONAN/ONAF
16 Current Density <300@ Principal tap
17 Flex Density 1.727 Max tesla
18 List of fittings As per Standard
19 Reference Standard & Tolerance As per IS standard
20 Spares As per Standard

NOTE:

1 Insulation liquid: Loose Oil should be supplied in sealed oil drum with 10% extra over and above.

You might also like