Ceiling Diffusers: Type ADLQ
Ceiling Diffusers: Type ADLQ
Ceiling Diffusers: Type ADLQ
Ceiling diffusers
Type ADLQ
Type Page
ADLQ General information ADLQ – 2
Function ADLQ – 3
Technical data ADLQ – 4
Quick sizing ADLQ – 5
Specification text ADLQ – 7
Order code ADLQ – 8
Variants ADLQ – 9
Dimensions and weight ADLQ – 11
Product details ADLQ – 14
Installation examples ADLQ – 15
Installation details ADLQ – 16
Commissioning ADLQ – 18
Basic information and nomenclature ADLQ – 20
Schematic illustration of the ADLQ, with plenum box for horizontal duct connection
⑤
⑥
④
⑨
② ①
⑬ ⑩
⑫ ⑪
ADLQ-A, ADLQ-AR (supply air), sound power level and total differential pressure
Δpt LWA
Nominal size
l/s m³/h Pa dB(A)
20 72 3 18
50 180 20 30
250
80 288 50 41
105 378 86 50
35 126 3 <15
80 288 14 24
300
125 450 35 35
175 630 68 50
75 270 2 <15
175 630 13 25
400
280 1008 34 38
385 1386 65 50
135 486 3 <15
270 972 10 25
500
505 1818 36 47
545 1962 42 50
220 792 3 21
380 1368 9 33
600
535 1926 17 42
675 2430 27 50
250 900 3 20
390 1404 7 33
625
540 1944 13 43
665 2394 19 50
ADLQ-AK (supply air), sound power level and total differential pressure
Damper blade position
0° 45° 90°
Nominal size
Δpt LWA Δpt LWA Δpt LWA
l/s m³/h Pa dB(A) Pa dB(A) Pa dB(A)
20 72 5 <15 6 <15 11 <15
40 144 20 30 24 29 42 30
250
60 216 46 42 54 41 95 42
85 306 92 51 108 51 190 52
35 126 6 <15 9 <15 20 18
70 252 26 30 37 32 81 38
300
100 360 52 41 75 43 166 48
130 468 89 50 126 51 280 57
75 270 9 <15 15 19 32 29
130 468 27 31 44 38 95 45
400
185 666 54 42 90 48 192 58
230 828 84 50 138 56 297 69
135 486 12 15 18 23 42 35
210 756 29 32 45 39 101 49
500
285 1026 53 42 82 48 185 60
360 1296 84 50 131 57 295 71
220 792 12 22 19 25 50 34
330 1188 27 33 43 39 112 46
600
440 1584 48 43 77 49 198 55
540 1944 72 50 116 56 299 63
250 900 14 22 27 33 63 39
330 1188 25 32 47 42 110 47
625
410 1476 38 39 73 50 170 53
575 2070 75 50 143 64 333 67
ADLQ
Type Accessories
ADLQ Ceiling diffuser No entry: without accessories
L With lip seal (only with plenum box)
Connection
A Diffuser face only Nominal size [mm]
AR Vertical, with connecting frame 250
AG Vertical, with blades (not for nominal 300
size 250) 400
C Vertical, with butterfly damper 500
ZH Horizontal, supply air, with plenum box 600
AH Horizontal, extract air, with plenum box 625
ADLQ/600 ADLQ/625
ADLQ-A
□Q
H₂
H₁ □Q₁
ADLQ-A
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 140 248 13 29 0.5
300 190 298 13 29 0.7
400 290 398 13 29 1.3
500 390 498 13 29 1.8
600 490 598 13 29 2.5
625 515 623 13 29 2.6
ADLQ-AR
□Q
H₂
□Q₁
H₁
ADLQ-AR
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 52 0.7
300 193 298 13 52 1.0
400 293 398 13 52 1.7
500 393 498 13 52 2.3
600 493 598 13 52 3.0
625 518 623 13 52 3.2
ADLQ-C
□Q
H₂
□Q₁
H₁
ADLQ-C
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 52 1.2
300 193 298 13 52 1.7
400 293 398 13 52 2.9
500 393 498 13 52 4.2
600 493 598 13 52 5.9
625 518 623 13 52 6.3
ADLQ-AG
□Q
H₂
□Q₁
H₁
ADLQ-AG
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 95 0.9
300 193 298 13 95 1.4
400 293 398 13 95 2.5
500 393 498 13 95 3.6
600 493 598 13 95 5.0
625 518 623 13 95 5.6
Square diffuser face with plenum box for horizontal duct connection
□Q₃ C
∅D
H₃
A
□Q₁
H₁
ADLQ-AK
Plenum
□Q1 H1 □Q3 H3 ØD A C m
Nominal size box
mm mm mm mm mm mm mm kg
AK-Uni-
250 248 13 216 250 158 139 50 2.7
008
AK-Uni-
300 298 13 266 250 158 139 50 3.4
009
AK-Uni-
400 398 13 372 295 198 164 50 5.8
002
AK-Uni-
500 498 13 476 345 248 189 48 8.5
010
AK-Uni-
600 598 13 567 410 313 222 50 11.6
011
AK-Uni-
625 623 13 567 410 313 222 50 11.8
011
Weights apply to the supply air variant
□Q₂
□Q₁ 500 498 448 0.0675
600 598 548 0.1100
625 623 573 0.1230
① Duct
② Suspension hole
③ Diffuser face
X
④ X
① Plenum box
② Diffuser face
③ Seal
④ Ceiling tile
② ①
① Diffuser face
② Cross bar
③ Central fixing screw
④ Decorative cap
– Fix the plenum box to the ceiling – Fix plenum box (including diffuser face, if necessary)
– The ceiling tile of the grid ceiling is independent of the to the ceiling
ceiling diffuser – Adjust plasterboard ceiling tile as required
– Fix the diffuser face after the ceiling has been – If necessary, fix the diffuser face after the ceiling has
completed been completed
AK-Uni-...-MN Volume flow rate balancing AK-Uni-...-MN Volume flow rate balancing
①
①
① ②
③
X
⑦
④
⑤
X
① ②
① Measuring tube
② Pressure tap
③ Damper blade for volume flow rate balancing
④ White cord for opening the damper blade
⑤ Green cord for closing the damper blade
⑥ Digital manometer
⑦ Text label indicating plenum box variant
Volume flow rate calculation for air density Volume flow rate calculation for other air
1.2 kg/m³ densities
LWA [dB(A)] Δpt [Pa]
A-weighted sound power level of air-regenerated Total differential pressure
noise
Aeff [m²]
[m³/h] and [l/s] Effective air discharge area
Volume flow rate
All sound power levels are based on 1 pW.
Δtz [K]
Supply air to room air temperature difference, i.e.