A1700 Direct Connected or CT Metering: The Power To Change..
A1700 Direct Connected or CT Metering: The Power To Change..
A1700 Direct Connected or CT Metering: The Power To Change..
Direct Connected or •
CT Metering •
•
•
•
•
•
•
•
•
A1700 Features
• Accuracy Class 0.2s or 0.5s for CT operation and Class 1 or The A1700 offers outstanding measurement and complex
Class 2 for direct connected, CT or CT/VT operation tariff capabilities for use in both industrial and commercial
• EC Directive 2004/22/EC (MID) Class A, B or C direct connected, CT and CT/VT operated applications. The
• Direct connected, CT or CT/VT operated meter can operate as a stand alone unit or as part of a
comprehensive metering system.
• Comprehensive tariff structure
• 2 line, multilingual dot matrix display The A1700 features include a fully programmable customer
• Instantaneous instrumentation values defined display and an optical port for local
• Instrumentation monitoring communications. Two slots are provided for the addition of
• Instrumentation profiling an input (or output) and a communications module. Load
• Extensive load profile data profile data can be stored for up to 900 days. As an
• 2 module slots for extended functionality alternative the meter can store 450 days of load profile
and 370 days of instrumentation profile data. Data stream
• Voltage imbalance detection
mode communications allows up to 90 days of 30 minute
• Temperature compensation to maintain RTC accuracy
profile data to be collected in less than 30 seconds.
during power outages
• Summation of 5 input values Communications modules can be RS232 or RS485.
• 5 co-incident demand values A range of communications media (PSTN, GSM, Ethernet,
• 2 kVA registers PAKNET) plug into a module directly under the meter
• High security design terminal cover.
An optional input module provides the ideal solution for
multi-utility metering. As an alternative, a module with four
Options outputs can be provided to increase the number of outputs
to eight.
• Up to 8 outputs
• Interchangeable input/output modules A module with battery can be provided to read meter data
• Communication modules (RS232 or RS485) when power has been removed from the meter.
• Communications media (PSTN, GSM, Ethernet, PAKNET) WindowsTM ‘Power Master Unit’ software programs or
• Data stream mode communications reads the meter data.
• Transformer loss compensation The meter can be supplied to meet accuracy Class 0.2s or
• Short terminal cover 0.5s for CT operation and Class 1 or Class 2 for direct
• Display backlight connected, CT or CT/VT operation.
• Replaceable RTC backup battery EC Directive 2004/22/EC (MID): Class A, B or C.
• Read without power
• Auxiliary a.c. supply
Measured Quantities Communications
kWh total import/export Local: IEC 62056-21 (formerly IEC 61107)
kvarh Q1, Q2, Q3, Q4 Remote: Interchangeable modules (RS232, RS485 or
kVAh (2 calculated values) customer specific)
3 customer defined registers -
summation of up to 5 values Media : GSM, PSTN, Ethernet, PAKNET
4 inputs for external meters (if fitted)
Case
Tariff Structure Sealed flip-up lid
32 Time of use registers • Conceals utility/reset pushbutton
8 Maximum demand registers (block or sliding) • Provides for customers own information to be
5 Co-incident demands securely added to the nameplate
2 Sliding demands • Allows visual identification of modules fitted
12 Seasons
Options
24 Season changeover dates
• ANSI communications port
96 Switching times
• 9.5 mm terminal block
64 Exclusion dates
The above may vary according to firmware version
Technical Data
Programmable deferred tariff and display Current Range CT operated – 5-6A, 5-10A, 1-2A, 1-1.2A
Direct connected – 10-100A (widest range)
Voltage Range 57.5 - 240V (3 phase 4 wire)
Data Storage 100 - 415V (3 phase 3 wire)
Programmable integration period Frequency 50Hz or 60Hz
Burden
Load profile storage or instrumentation quantity
Voltage Circuits (230V) Single element - 1.92W, 4.17VA
Demand & instrumentation integration periods independently Two/three element - 1.12W, 2.45VA
defined Current Circuits CT operated – 0.12VA @ 5A/phase, 0.02VA @
1A/phase
Number of days based on 30 minute period, 1 channel Direct connected – 0.2VA @ 100A/phase
Measured load profile Instrumentation profile Insulation 4kV RMS 50Hz
900 0 Impulse Withstand 12kV 1.2/50μs 50ohm source
Display 2 line, 16 character dot matrix
450 0
liquid crystal display
450 370 8mm digits
0 450 Baud Rates 1200, 2400, 4800, 9600
Product Life 15 years
Up to 36 sets of historical data. Fully customer defined, Certified Product Life 10 years (by OFGEM)
multilingual Temperature -25° to + 55° C (Operational range)
-25o to +70o C (Optional operating range)
-25° to + 70° C (Storage)
Input/Output Humidity Annual mean 75% (for 30 days spread over
one year, 95%)
Four input module - End of billing, end of integration period,
Pulse Width / Value Programmable
inputs from external meters Relay Specification 240V a.c.
100mA
Four output relay module - Retransmit pulses from energy 1 x 5A relay (option, module only)
registers, customer defined registers or any time-of-use register Dimensions 279mm (high) x 170mm (wide) x 81mm (deep)
Weight 1500 grams
Option of three solid-state relays and one 5A relay or four solid- Specifications IEC 62052-11 and IEC 62053 -21, -22, -23
state relays EC Directive 2004/22/EC (MID) Class A, B or C
Case IP53 to IEC 60529:1989
• Increase network availability by reducing failover time to zero through IEC® 62439 PRP/HSR and • Alarm Panel
IEEE® 802.1D/RSTP
• Scalable solutions for I/O units (Up to 192 DI or 48 DO depending on the model) EnerVista Software
• Significant savings in installation costs with support for up to two remote CAN Bus IO modules
• Sophisticated software for configuration and
commissioning
Applications • LaunchPad: document and software archiving
• Bay control and substation automation for solidly grounded, high impedance grounded or management system
resonant (Peterson Coil) grounded systems • EnerVista™ Integrator providing easy
• Bus blocking/Interlocking schemes integration of data in the C650 into new or
existing monitoring and control systems
• Throw over schemes (bus transfer scheme applications)
• Load shedding schemes based on voltage and frequency elements or pre-defined shedding
scenarios
• Programmable Logic Control
C650 Bay Control & Monitoring System
Technical Specifications
CONTROL CONTROL EVENTS VOLTAGE INPUTS
AUTORECLOSE (79) Capacity: 128 events programmable through PLC VAC inputs do not need varistors, as the impulse test
Labeling time tag: 1 ms using an internal clock of is applied to 100% of the transformers
Schemes: Three-phase pole tripping schemes
100 µs Metering range: From 2 to 275 Vac
No. of reclosing shots: Up to 4 reclose attempts
before lockout Accuracy: 1 ms (using the IRIG-B synchronization LoadRelay Burden: 0.05 VA at 120 Vac (50 or 60 Hz)
input) Voltage withstand:
Dead time: Independent dead time setting before
each shot adjustable between 0 and 900 s in steps Trigger: By any digital signal programmable through 260 Vac permanent
of 0.01 s PLC
Continuous at 275 V to neutral
Reclaim time: 0.00 to 900.00 s in steps of 0.01 s Alarm: Possibility to display the event as an alarm
420 Vac during 1 min/hr at 420 to neutral
on the alarms panel. Information available always
Condition permission: Selectable by setting DIGITAL INPUTS
through Communications for all models and also in
Hold time: 0.00 to 900.00 s in steps of 0.01 s HMI for models with graphical display (M in ordering Voltage Threshold: Programmable from 20 up to
Reset time: 0.00 to 900.00 s in steps of 0.01 s code). 230Vdc in steps of 1 V
Snapshot Events: Selectable by setting Storage: Permanent in non volatile memory (flash) Impedance: > 100 kOhm
Possibility to modify protection settings after each without battery Load for voltage supervision inputs:
shot DEMAND 2 mA + V/100 kOhm
SYNCHRONISM CHECK (25) Channels: 9 Maximum error: ±10% setting or ± 5 V
Dead/live levels for line and bus: Parameters: Ia(kA RMS), Ib(kA RMS), Ic(kA RMS), Ig(kA Acknowledgement time: < 1 ms
0.00 to 300.00 in steps of 0.01 V RMS), Isg(kA RMS), I2 (KA), P(MW), Q (MVAr) and S (MVA) Debounce time: 1 to 50 ms in steps of 1 ms
Maximum voltage difference: Current and Power Method: Thermal Exponential, REMOTE INPUTS
block interval, Rolling demand No of input points: 32, configured from 64 incoming
2.00 to 300.00 V in steps of 0.01 V
Metering Measurements: Each channel shows the bit pairs
Maximum angle difference:
present and maximum measured value, with date No of remote devices: 16
2.0º to 80.0º in steps of 0.1º and time for the maximum recorded value.
Maximum frequency slip: Default states on loss of comms: On, Off, Latest/on,
Samples: 5, 10, 15, 20, 30, 60 minutes. Latest/off
10 to 5000 mHz in steps of 10 mHz Accuracy: ±1%
Synchronism time: 0.01 to 1.00 s in steps of 0.01 s
ANALOG INPUTS (DCMA)
DATA LOGGER Current inputs: 0 to -1; 0 to +1; -1 to +1; 0 to 5; 0 to
Angle accuracy: 3º Channels: 1 to 16 10; 0 to 20, 4 to 20
Dead Source function: Parameters: Any of the analog Metering actual values Conversion range: -1 to 20 dcmA
• None Samples: 1 second, 1, 5, 10, 15, 20, 30, 60 minutes. Accuracy: +/-0.2% of full scale
• (DL-DB) Dead Line - Dead Bus Capacity: Fixed, (32768 measures) Type: Passive
• (LL-DB) Live Line-Dead Bus IRIG-B TIME SYNCHRONIZATION INPUT
METERING Type: Demodulated input (no carrier)
• (DL-LB) Dead Line – Live Bus
Snapshot Events: Selectable by setting CURRENT Formats: B000(*) B001, B002 and B003(*)
BREAKER MAINTENANCE Accuracy: Level: TTL
Kl2t BKR Ph A, B, C Cnt: 0.00 to 9999.99 in steps of • ±0.5% of the reading ± 10 mA from 0.1 to 10 A Load: 1.5 mA
0.01 (KA)2s (for phases and ground) (*) Signal combinations recognized in accordance
BKR Openings Cnt: 0 to 9999 in steps of 1 with IRIG Standard 200-95
• ±1.5% of the reading ± 1 mA from 0.005 to 5 A
BKR Closings Cnt: 0 to 9999 in steps of 1 REAL TIME CLOCK
(for sensitive ground)
BREAKER SETTINGS Accuracy: Typical 20 ppm
• ±1.5% of the reading for higher values
Switchgear number: 1 to16 Backup energy: More than 1 week
VOLTAGE
Maximum KI2t: 0.00 to 9999.99 in steps of 0.01 (KA)2s
Accuracy: ±1% reading, from 10 to 208 V
KI2t integ. Time: 0.03 : 0.25 s in steps of 0.01s INPUTS
POWER
Maximum openings: 0 to 9999 in steps of 1 CURRENT INPUTS
Active:
Maximum Openings in an hour: 1 to 60 in steps of 1 Rated current: Appropriate for 1 or 5 A
±2,5% of the reading from power factor ±0.8 to 1
SWITCHGEAR LoadRelay Burden: < 0.04 Ohm
Reactive:
Switchgear number: 1 to16 Overload: 20 A permanent
±2,5% of the reading from power factor ±0.2 to 0
Switchgear: 1 to16 (configurable). 500 A during 1 second
Apparent: ±2,5% of the reading
Current Withstand:
ENERGY
MONITORING Watts- hour (positive and negative) • Continuous at 20 A
TRIP/CLOSE COIL MONITORS Accuracy: 2,5% • 1 second at 500 A for phases and ground
Detect open trip and close circuits Range: ±0 to 2147 MWh • 1 second at 50 A for sensitive ground
OSCILLOGRAPHY Parameters: three-phase VOLTAGE INPUTS
Records: Up to 20 oscillography records. Updating Time: 100 ms VAC inputs do not need varistors, as the impulse test
Samples: Programmable to 4, 8, 16, 32 or 64 samples Var-hour (positive and negative) is applied to 100% of the transformers
per cycle Accuracy: 2,5% Metering range: From 2 to 275 Vac
Trigger position: 5% to 95% of total length Range: ±0 to 2147 MVArh LoadRelay Burden: 0.05 VA at 120 Vac (50 or 60 Hz)
Trigger: Programmable via programmable logic Updating Time: 100 ms Voltage withstand:
Data: POWER FACTOR • 260 Vac permanent
• 5 current channels and 4 voltage channels Accuracy: 0.02 • Continuous at 275 V to neutral
• Up to 16 digital channels selectable from FREQUENCY • 420 Vac during 1 min/hr at 420 to neutral
the available internal states programmable Accuracy: ±50 mHz DIGITAL INPUTS
through PLC Accuracy angle: 2º Voltage Threshold: Programmable from 20 up to
Storage: Permanent in non volatile memory (flash) 230Vdc in steps of 1 V
without battery In non-volatile memory (flash)
without battery INPUTS Impedance: > 100 kOhm
Format: International Standard COMTRADE ASCII - CURRENT INPUTS Load for voltage
IEEE C37.111-1999. supervision inputs: 2 mA + V/100 kOhm
Rated current: Appropriate for 1 or 5 A
Maximum error: ±10% setting or ± 5 V
SNAPSHOT EVENTS LoadRelay Burden: < 0.04 Ohm
Acknowledgement time: < 1 ms
Capacity: 479 scrolling events Overload:
Debounce time: 1 to 50 ms in steps of 1 ms
Labeling time tag: 1 ms using an internal clock of • 20 A permanent
100 µs REMOTE INPUTS
Accuracy: 1 ms (using the IRIG-B synchronization • 500 A during 1 second No of input points: 32, configured from 64 incoming
input) Current Withstand: bit pairs
Trigger: • Continuous at 20 A No of remote devices: 16
• By pickup or dropout or operate of any element • 1 second at 500 A for phases and ground Default states on loss of comms: On, Off, Latest/on,
Latest/off
• By change of state in a Digital input/output • 1 second at 50 A for sensitive ground
change of state
• By virtual inputs and control events
Storage: Permanent in non volatile memory (flash)
without battery
8 GEDigitalEnergy.com
C650 Bay Control & Monitoring System
TYPE TEST
REFERENCE REFERENCE
CATEGORY TEST TEST LEVEL CATEGORY TEST TEST LEVEL
STANDARD STANDARD
Dielectric voltage IEC60255-27 2 KV / 2.3 KV Sinusoidal Vibration IEC60255-21-1 Class 1
withstand IEC60255-21-2 Class 1
Shock & Bump
SAFETY Impulse voltage IEC60255-27 5 KV
Seismic IEC60255-21-3 Class 2
withstand MECHANICAL
IEC60255-27 500 V (test level) Enclosure Protection IEC60255-27/ IP52
Insulation resistance IEC60529
Electrostatic IEC60255-26/ Level 4
Discharge Immunity IEC61000-4-2
IEC60255-26/ Level 3 Cold test (storage) IEC60068-2-1 -40˚C @ 16 hrs
Radiated RF
Electromagnetic Field IEC61000-4-3 Cold test IEC60068-2-1 -20˚C @ 16 hrs
Immunity (operational)
Surge Immunity IEC60255-26/ Zone A Dry heat test IEC60068-2-2 85˚C @ 16 hrs
IEC61000-4-5 (storage)
Conducted RF IEC60255-26/ Level 3
Dry heat test IEC60068-2-2 60˚C @ 16 hrs
Immunity IEC61000-4-6
CLIMATIC (operational)
Power magnetic IEC60255-26/ Level 5
Change of IEC60068-2-14 5 cycles (3+3)
Immunity IEC61000-4-8
Temperature -20˚C/60˚C
EMC IEC60255-26/ Zone A
Power Frequency IEC60068-2-30 6 cycles (12+12)
IEC61000-4-16 Damp Heat Humidity
Immunity 55˚C @ 93% R.H.
Cyclic
Damped Oscillatory IEC60255-26/ 2.5 KV Common
Damp Heat steady IEC60068-2-78 40˚C @ 93% R.H.
Wave Immunity IEC61000-4-18 Mode/1 KV Diff.
Mode state
Voltage Dips & IEC60255-26/ Levels based on
Interruptions IEC61000-4-11 IEC61000-4-11 &
IEC61000-4-29 IEC61000-4-29
Ripple on DC IEC60255-26/ 15% Rated DC
IEC61000-4-17 value
Radiated & IEC60255-26/ Class A
Conducted Emissions CISPR11/CISPR22
GEDigitalEnergy.com 9
Grid Solutions
2 GEGridSolutions.com
UR & URPlus Family
Family Overview
Transmission & Distribution (Continued) Industrial & Network
F60 T35 M60
Feeder Protection with Hi-Z Fault Detection Basic Transformer Protection, Multiple CTs Motor Protection
The F60 provides comprehensive feeder The T35 is a basic transformer protection The M60 offers comprehensive protection and
protection, control, advanced communications, system capable of protecting combined main control solutions for large-sized three-phase
monitoring and metering in an integrated, power transformers and up to five feeders motors. The M60 provides superior protection,
economical, and compact package and more. downstream. The T35 provides automatic or control, and diagnostics that includes thermal
user-definable magnitude reference winding model with RTD and current unbalance biasing,
F35 selection for CT ratio matching, automatic stator differential, reverse and low forward
phase shift compensation and allows users to power, external RRTD module, two-speed
Multiple Feeder Protection
enable removal of the zero-sequence current motors, reduced voltage starting, broken rotor
The F35 is a cost-effective device for primary even for delta connected transformer windings. bar detection, and more.
feeder protection. F35’s modular design allows
customers to protect groups of feeders as C90Plus N60
follows: independent current and voltage inputs,
Breaker Automation and Controller Network Stability and Synchrophasor
independent current and common voltage
Measurement
inputs or independent current inputs only. The C90 Plus
is a powerful logic controller
designed to be used in substation environments The N60 is intended to be used on load shedding,
C70 and for the unique automation requirements remedial action, special protection and wide
of industrial and utility power systems. The area monitoring and control schemes. Like no
Capacitor Bank Protection
C90Plus provides unmatched logic processing one device before, the N60 shares real-time
The C70 is an integrated protection, control, and ability combined with a powerful math engine operational data to remote N60s so the system
monitoring device for shunt capacitor banks. with deterministic execution of logic equations can generate intelligent decisions to maintain
The current and voltage-based protection regardless of the configuration of the number of power system operation.
functions are designed to provide sensitive lines of logic.
protection for grounded, ungrounded single and
parallel capacitor banks and banks with taps. C60
Breaker Controller
T60
The C60 is a substation hardened controller that
Medium to Large Transformers
provides a complete integrated package for the
The T60 is a fully featured transformer protection protection, control, and monitoring of circuit
system suitable for power transformers of any breakers, supporting dual-breaker busbar
size that require current differential function. configurations, such as breaker-and-half or ring
The T60 provides automatic or user-definable bus schemes.
magnitude reference winding selection for CT
ratio matching, and performs automatic phase C30
shift compensation for all types of transformer
I/O Logic Controller
winding connections.
The C30 is designed to perform substation
control logic that can also expand the I/O
capability of protection devices and replace
existing Sequence of Events (SOE) recorders.
GEGridSolutions.com 3
UR & URPlus Family
UR Family
Selector Guide
Features ANSI B30 B90 B95Plus C30 C60 C70 C90Plus D30 D60 D90Plus
Protection
Family Overview
Disturbance Detector • • • • •
Mho Distance, Phase (No. of Zones) 21P 5 5 5
Mho Distance, Ground or Neutral Phase (No. of Zones) 21G/N 5 5 5
Quadrilateral Distance, Phase (No. of Zones) 21P 5 5 5
Quadrilateral Distance, Ground or Neutral (No. of Zones) 21G/N 5 5 5
Permissive Pilot Logic • •
Sub-Cycle Distance •
Overexcitation Protection (V/Hz) 24
Synchronism Check or Synchronizing 25 • • • • •
Undervoltage, Phase 27P • • • • • • • • •
Undervoltage, Auxiliary 27X • • • • •
Stator Ground (3rd Harmonic) 27TN
Sensitive Directional Power 32S • •
Loss of Excitation – Based on Reactive Power 40Q
Loss of Excitation – Based on Impedance Element 40
Current Unbalance 46
Broken Conductor Detection 46BC
IOC, Negative Sequence 46/50 • • • • •
TOC, Negative Sequence 46/51 • • • • •
Current Directional, Negative Sequence 46/67 • • • • •
Reverse Phase Sequence Voltage 47 •
Thermal Model 49
Inadvertent/Accidental Energization 50/27
End of Fault Protection • • •
Motor Mechanical Jam
Motor Start Supervision
Motor Acceleration Time
User Programmable Curves • • • • • • •
Breaker Failure 50BF • • • • • • Logic • •
IOC, Phase 50P • • • • • • • • •
IOC, Ground 50G • • • • • • •
IOC, Neutral 50N • • • • • • •
IOC, Sensitive Ground 50SG • • • •
High Impedance Fault Detection
TOC, Phase 51P • • • • • • • • •
TOC, Ground 51G • • • • • • •
TOC, Neutral 51N • • • • • • •
TOC, Sensitive Ground 51SG • • • •
TOC, Voltage Restrained 51V • • • • • • •
Overvoltage, Phase 59P • • • • •
Overvoltage, Auxiliary 59A • • • • • • •
Overvoltage, Neutral 59N • • • • • • •
Negative Sequence Overvoltage 59-2 • • • • •
100% Stator Ground Protection 64TN
Current Directional, Phase 67P • • • •
Current Directional, Neutral 67N • • • •
Current Directional, Negative Sequence 46/67 • • • •
Power Swing Blocking 68 • • •
Out-of-Step Tripping 78 • • •
AC Reclosing (No. of Shots) 79 4 4 4 4 •
Switch on to Fault (Line Pickup) SOTF • • •
Voltage Transformer Fuse Failure VTFF • • • • • •
Current Transformer Supervision 50/74 • • •
Load Encroachment Logic • • •
Underfrequency 81U • • •
Overfrequency 810 • • •
Anti-Islanding Protection/Frequency Rate of Change 81R • •
Lockout Functionality 86 • • • • • • • • • •
Bus Differential 87B 2 2 2
Line Current Differential 87L
Ground Differential 87G
Stator Differential 87S
Transformer Differential 87T
Line Phase Comparison 87PC
Voltage Differential •
Capacitor Bank Overvoltage •
Neutral Voltage Unbalance •
Automatic Voltage Regulation •
Time of Day Control •
Instantaneous Differential 50/87 • • •
Split Phase Protection
Line Current Differential Trip Logic
CT Failure • •
12 GEGridSolutions.com
UR & URPlus Family
Features F35 F60 G30 G60 L30 L60 L90 M60 N60 T35 T60
Protection
Family Overview
Disturbance Detector • • • • •
Mho Distance, Phase (No. of Zones) 3 3 5 5
Mho Distance, Ground or Neutral Phase (No. of Zones) 3 3 5
Quadrilateral Distance, Phase (No. of Zones) 3 3 5
Quadrilateral Distance, Ground or Neutral (No. of Zones) 3 3 5
Permissive Pilot Logic •
Sub-Cycle Distance
Overexcitation Protection (V/Hz) • • •
Synchronism Check or Synchronizing • • • • • • • •
Undervoltage, Phase • • • • • • • • • •
Undervoltage, Auxiliary • • • • • • • • •
Stator Ground (3rd Harmonic) • •
Sensitive Directional Power • • • • •
Loss of Excitation – Based on Reactive Power • • •
Loss of Excitation – Based on Impedance Element • •
Current Unbalance • • •
Broken Conductor Detection •
IOC, Negative Sequence • • • •
TOC, Negative Sequence • • • •
Current Directional, Negative Sequence • • • • •
Reverse Phase Sequence Voltage •
Thermal Model • • •
Inadvertent/Accidental Energization • •
End of Fault Protection
Motor Mechanical Jam •
Motor Start Supervision •
Motor Acceleration Time •
User Programmable Curves • • • • • • • • • • •
Breaker Failure Logic • Logic • • • • • Logic Logic Logic
IOC, Phase • • • • • • • • • •
IOC, Ground • • • • • • • • •
IOC, Neutral • • • • • • • • •
IOC, Sensitive Ground • • • • • • • • •
High Impedance Fault Detection •
TOC, Phase • • • • • • • • • •
TOC, Ground • • • • • • • • • •
TOC, Neutral • • • • • • • • •
TOC, Sensitive Ground • • • • • • • • •
TOC, Voltage Restrained • • • • • • • • •
Overvoltage, Phase • • • • • • • • •
Overvoltage, Auxiliary • • • • • • • • •
Overvoltage, Neutral • • • • • • • • •
Negative Sequence Overvoltage • • • •
100% Stator Ground Protection •
Current Directional, Phase • • • • • • •
Current Directional, Neutral • • • • • • •
Current Directional, Negative Sequence • • • • •
Power Swing Blocking • • • • •
Out-of-Step Tripping • • • • •
AC Reclosing (No. of Shots) 4 4 4 4 4
Switch on to Fault (Line Pickup) • •
Voltage Transformer Fuse Failure • • • • • • • • • •
Current Transformer Supervision • • •
Load Encroachment Logic • • • •
Underfrequency • • • • • • •
Overfrequency • • • • •
Anti-Islanding Protection/Frequency Rate of Change • • • • • •
Lockout Functionality • • • • • • • • • •
Bus Differential
Line Current Differential • •
Ground Differential • • • • • •
Stator Differential • • •
Transformer Differential • • •
Line Phase Comparison •
Voltage Differential
Capacitor Bank Overvoltage
Neutral Voltage Unbalance
Automatic Voltage Regulation
Time of Day Control
Instantaneous Differential • •
Split Phase Protection • •
Line Current Differential Trip Logic •
CT Failure • • • • • • • •
GEGridSolutions.com 13
UR & URPlus Family
UR Technical Specifications
PROTECTION PROTECTION PROTECTION
100% STATOR GROUND BREAKER FAILURE Timing accuracy: ±3% or 4 ms, whichever is greater
Operating quantity: V_neutral_3rd/(V_neutral_3rd + Mode: 1-pole, 3-pole Current supervision:
V_zero_3rd) Current supervision: phase, neutral current Level: neutral current (3I_0)
Pickup level: 0.000 to 0.250 pu in steps of 0.001 Current supv. 0.02 to 30.000 pu in steps of 0.001 Pickup: 0.050 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup pickup: Dropout: 97 to 98%
Level accuracy: ±2% of reading from 1 to 120 V Current supv. 97 to 98% of pickup Memory duration: 5 to 25 cycles in steps of 1
Pickup delay: 0 to 600.00 s in steps of 0.01 dropout: Voltage supervision 0 to 5.000 pu in steps of 0.001
3rd harmonic 0.0010 to 0.1000 pu in steps of 0.0001 Current supv. accuracy: pickup (series
supervision level: 0.1 to 2.0 × CT ±0.75% of reading or ±2% of rated compensation
Time accuracy: ±3% or ±20 ms, whichever is greater rating: (whichever is greater) applications):
above 2 × CT rating: ±2.5% of reading Operation time: 1 to 1.5 cycles (typical)
Family Overview
Pickup level: 0.02 to 3.000 pu in steps of 0.001 Level accuracy: ±0.5% or ±0.1% of rated, whichever 29
Level accuracy: ±0.5% of reading from 0.1 to 2.0 × Pickup delay: 0 to 65.535 s in steps of 0.001 26
14 GEGridSolutions.com
UR & URPlus Family
UR Technical Specifications
PROTECTION PROTECTION PROTECTION
MECHANICAL JAM OPEN POLE DETECTOR Memory duration: 5 to 25 cycles in steps of 1
Operating condition: Phase overcurrent Detects an open pole condition, monitoring breaker auxiliary VT location: all delta-wye and wye-delta
Arming condition: Motor not starting contacts, the current in each phase and optional voltages on transformers
Pickup level: 1.00 to 10.00 × FLA in steps of 0.01 the line CT location: all delta-wye and wye-delta
Dropout level: 97 to 98% of pickup Current pickup level: 0.02 to 30.000 pu in steps of 0.001 transformers
Level accuracy: at 0.1 to 2.0 × CT: ±0.5% of reading Line capacitive 300.0 to 9999.9 sec. W in steps of 0.1 Voltage supervision 0 to 5.000 pu in steps of 0.001
at > 2.0 × CT rating: ±1.5% of reading reactances (XC1, pickup (series
Pickup delay: 0.10 to 600.00 s in steps of 0.01 XC0): compensation
Reset delay: 0.00 to 600.00 s in steps of 0.01 Remote current 0.02 to 30.000 pu in steps of 0.001 applications):
Time accuracy: ±3% or ±20 ms, whichever is greater pickup level: PHASE DISTANCE OPERATING TIME CURVES
MOTOR START SUPERVISION Current dropout Pickup + 3%, not less than 0.05 pu The operating times are response times of a microprocessor
Family Overview
Maximum no. of 1 to 16 in steps of 1 level: part of the relay. See output contacts specifications for
starts: OVERFREQUENCY estimation of the total response time for a particular
Monitored time 1 to 300 minutes in steps of 1 Pickup level: 20.00 to 65.00 Hz in steps of 0.01 application. The operating times are average times including
interval: Dropout level: Pickup - 0.03 Hz variables such as fault inception angle or type of a voltage
Time between starts: 0 to 300 minutes in steps of 1 Level accuracy: ±0.01 Hz source (magnetic VTs and CVTs).
Restart delay: 0 to 50000seconds in steps of 1 Time delay: 0 to 65.535 s in steps of 0.001 30
NEGATIVE SEQUENCE DIRECTIONAL OC Timer accuracy: ±3% or 4 ms, whichever is greater 29
Restraint, K: 0.000 to 0.500 in steps of 0.001 I2 x Z - V2: 0.005 to 15.00 pu in steps of 0.01 18
SIR=20
Characteristic angle: 0 to 90° in steps of 1 dI2 / dt: 0.01 to 5.00 pu in steps of 0.01 17 SIR=30
SIR=60
dI1 / dt: 0.01 to 5.00 pu in steps of 0.01
16
Limit angle: 40 to 90° in steps of 1, independent for 15
Pickup level: 0.05 to 30.00 pu in steps of 0.01 I2 x Z - V2: 0.005 to 15.00 pu in steps of 0.01 10
0 20 40 60 70 80
Dropout level: 97 to 98% dI2 / dt: 0.01 to 5.00 pu in steps of 0.01 Fault Location (%)
Operation time: < 16 ms at 3 × Pickup at 60 Hz dI1 / dt: 0.01 to 5.00 pu in steps of 0.01
NEGATIVE SEQUENCE IOC Signal Symmetry PHASE/NEUTRAL/GROUND IOC
Current: Phasor Adjustment: -0.5 to 5.0 ms in steps of 0.1 Pickup level: 0.02 to 30.000 pu in steps of 0.001
Pickup level: 0.02 to 30.000 pu in steps of 0.001 Channel Delay 0.000 to 30.00 ms in steps of 0.001 Dropout level: 97 to 98% of pickup
Dropout level: 97 to 98% of Pickup Adjustment: Level accuracy:
Level accuracy: Channel channel delay and signal symmetry 0.1 to 2.0 × CT ±0.5% of reading or ±1% of rated
0.1 to 2.0 × CT ±0.5% of reading or ±1% of rated Adjustments: compensation rating: (whichever is greater)
rating: (whichever is greater)> 2.0 × CT rating: Operate Time 3/4 cycle for single phase comparison > 2.0 × CT rating: ±1.5% of reading
±1.5% of reading (Typical): Overreach: <2%
Overreach: < 2% Trip Security: First coincidence or enhanced Pickup delay: 0.00 to 600.00 s in steps of 0.01
Pickup delay: 0.00 to 600.00 s in steps of 0.01 Second Coincidence 10 to 200 ms in steps of 1 Reset delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01 Timer: Operate time: <16ms at 3 × pickup at 60Hz (Phase/
Operate time: < 20 ms at 3 × Pickup at 60 Hz Enhanced Stability 40 to 180° in steps of 1 Ground IOC) <20ms at 3 × pickup at
Timing accuracy: Operate at 1.5 × Pickup ±3% or ± 4 ms Angle: 60Hz (Neutral IOC)
(whichever is greater) PHASE DIRECTIONAL OVERCURRENT Timing accuracy: Operate at 1.5 × Pickup ±3% or ±4 ms
NEGATIVE SEQUENCE OVERVOLTAGE Relay connection: 90° (quadrature) (whichever is greater)
Pickup level: 0.004 to 1.250 pu in steps of 0.001 Quadrature voltage: PHASE/NEUTRAL/GROUND TOC
Dropout level: 97 to 98% of Pickup ABC phase seq.: phase A (VBC), phase B (VCA), Current: Phasor or RMS
Level accuracy: ±0.5% of reading from 10 to 208 V phase C (VAB) Pickup level: 0.02 to 30.000 pu in steps of 0.001
Pickup delay: 0 to 600.00 s in steps of 0.01 ACB phase seq.: phase A (VCB), phase B (VAC), Dropout level: 97% to 98% of Pickup
Reset delay: 0 to 600.00 s in steps of 0.01 phase C (VBA) Level accuracy: for 0.1 to 2.0 × CT: ±0.5% of reading
Time accuracy: ±3% or ±20 ms, whichever is greater Polarizing voltage 0.004 to 3.000 pu in steps of 0.001 or ±1% of rated (whichever is greater)
Operate time: < 30 ms at 1.10 × Pickup at 60 Hz threshold: for > 2.0 × CT: ±1.5% of reading > 2.0
NEGATIVE SEQUENCE TOC Current sensitivity 0.05 pu × CT rating
Current: Phasor threshold: Curve shapes: IEEE Moderately/Very/Extremely
Pickup level: 0.02 to 30.000 pu in steps of 0.001 Characteristic angle: 0 to 359° in steps of 1 Inverse; IEC (and BS) A/B/C and Short
Dropout level: 97% to 98% of Pickup Angle accuracy: ±2° Inverse; GE IAC Inverse, Short/Very/
Operation time: (FlexLogic elements): Extremely Inverse; I2t; FlexCurves.
Level accuracy: ±0.5% of reading or ±1% of rated (programmable); Definite Time (0.01 s
(whichever is greater from 0.1 to 2.0 Tripping (reverse < 12 ms, typically
load, forward fault): base curve)
x CT rating ±1.5% of reading > 2.0 x
CT rating Blocking (forward < 8 ms, typically Curve multiplier: Time Dial = 0.00 to 600.00 in steps
load, reverse fault): of 0.01
Curve shapes: IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short PHASE DISTANCE Reset type: Instantaneous/Timed (per IEEE)
Inverse; GE IAC Inverse, Short/Very/ Characteristic: Mho (memory polarized or offset) Timing accuracy: Operate at > 1.03 × actual Pickup
Extremely Inverse; I2t; FlexCurves. or Quad (memory polarized or non- ±3.5% of operate time or ±½ cycle
(programmable); Definite Time (0.01 s directional), selectable individually (whichever is greater)
base curve) per zone PHASE OVERVOLTAGE
Curve multiplier 0.00 to 600.00 in steps of 0.01 Number of zones: Up to 5 Voltage: Phasor only
(Time dial): Directionality: Forward, Reverse, or Non-Directional Pickup level: 0.004 to 3.000 pu in steps of 0.001
Reset type: Instantaneous/Timed (per IEEE) and per zone Dropout level: 97 to 98% of Pickup
L ear Reach (secondary W): 0.02 to 250.00 in steps of 0.01 Level accuracy: ±0.5% of reading from 10 to 208V
Timing accuracy: Operate at > 1.03 × Actual Pickup Reach accuracy: ±5% including the effect of CVT Pickup delay: 0.00 to 600.00 in steps of 0.01 s
±3.5% of operate time or ±½ cycle transients up to an SIR of 30 Operate time: < 30 ms at 1.10 × Pickup at 60 Hz
(whichever is greater) Distance: Timing accuracy: ±3% or ±4 ms (whichever is greater)
NEUTRAL DIRECTIONAL OVERCURRENT Characteristic angle: 30 to 90° in steps of 1 PHASE UNDERVOLTAGE
Directionality: Co-existing forward and reverse Comparator limit 30 to 90° in steps of 1 Voltage: Phasor only
Polarizing: Voltage, Current, Dual, Dual-I, Dual-V angle: Pickup level: 0.004 to 3.000 pu in steps of 0.001
Polarizing voltage: V_0 or VX Directional supervision: Dropout level: 102 to 103% of Pickup
Polarizing current: IG Characteristic angle: 30 to 90° in steps of 1 Level accuracy: ±0.5% of reading from 10 to 208V
Operating current: I_0 Limit angle: 30 to 90° in steps of 1 Curve shapes: GE IAV Inverse; Definite Time (0.1s
Level sensing: 3 × (|I_0| - K × |I_1|), IG Right blinder (Quad only): base curve)
Restraint, K: 0.000 to 0.500 in steps of 0.001 Reach: 0.02 to 500 in steps of 0.01 Curve multiplier: Time Dial = 0.00 to 600.00 in steps
Characteristic angle: -90 to 90° in steps of 1 Characteristic angle: 60 to 90° in steps of 1 of 0.01
Limit angle: 40 to 90° in steps of 1, independent for Left Blinder (Quad only): Timing accuracy: Operate at < 0.90 × Pickup ±3.5% of
forward and reverse Reach: 0.02 to 500 in steps of 0.01 operate time or ±4 ms (whichever is
Angle accuracy: ±2° Characteristic angle: 60 to 90° in steps of 1 greater)
Offset impedance: 0.00 to 250.00W in steps of 0.01 Time delay: 0.000 to 65.535 s in steps of 0.001 PILOT-AIDED SCHEMES
Pickup level: 0.05 to 30.00 pu in steps of 0.01 Timing accuracy: ±3% or 4 ms, whichever is greater Direct Underreaching Transfer Trip (DUTT)
Dropout level: 97 to 98% Current supervision: Permissive Underreaching Transfer Trip (PUTT)
Operation time: < 16 ms at 3 × Pickup at 60 Hz Level: line-to-line current Permissive Overreaching Transfer Trip (POTT)
NEUTRAL OVERVOLTAGE Pickup: 0.050 to 30.000 pu in steps of 0.001 Hybrid POTT Scheme
Pickup level: 0.004 to 3.000 pu in steps of 0.001 Dropout: 97 to 98% Directional Comparison Blocking Scheme
Polarizing: Voltage, Current, Dual, Dual-I, Dual-V Customizable version of the POTT and DCB schemes (POTT1
Level accuracy: ±0.5% of reading from 10 to 208 V and DCB1)
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Timing accuracy: ±3% or ±20 ms (whichever is greater)
Operate time: < 30 ms at 1.10 × Pickup at 60 Hz
GEGridSolutions.com 15
UR & URPlus Family
UR Technical Specifications
PROTECTION PROTECTION PROTECTION
POWER SWING DETECT THERMAL MODEL TRIP OUTPUT
Functions: Power swing block, Out-of-step trip Thermal overload Standard curve, FlexCurve, Collects trip and reclose input requests and issues outputs to
Characteristic: Mho or Quad curves: voltage dependent curve control tripping and reclosing.
Measured impedance: Positive-sequence Standard Curve Time 0.00 to 600.00 in steps of 0.01 Communications timer 0 to 65535 s in steps of 0.001
Blocking / tripping 2-step or 3-step Multiplier: delay:
mozes: Thermal Overload pu = overload factor x FLA Evolving fault timer: 0.000 to 65.535 s in steps of 0.001
Tripping mode: Early or Delayed Pickup: Timing accuracy: ±3% or 4 ms, whichever is greater
Current supervision: Overload (OF): 1.00 to 1.50 in steps of 0.001 UNDERFREQUENCY
Pickup level: 0.050 to 30.000 pu in steps of 0.001 Standard Overload Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Dropout level: 97 to 98% of Pickup Curve: Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Fwd / reverse reach 0.10 to 500.00W in steps of 0.01 trip time = Dropout level: Pickup + 0.03 Hz
Family Overview
16 GEGridSolutions.com
UR & URPlus Family
UR Technical Specifications
MONITORING USER-PROGRAMMABLE ELEMENTS INPUTS
PHASOR MEASUREMENT UNIT CONTROL PUSHBUTTONS AC CURRENT
Output format: per IEEE C37.118 standard Number of pushbuttons: 3 (standard), 16 (UR Enhanced CT rated primary: 1 to 50000 A
Number of channels: 14 synchrophasors, 16 analogs, 16 HMI) or 8 plus 10 soft CT rated secondary: 1 A or 5 A by connection
digitals pushbuttons (UR color HMI) Nominal frequency: 20 to 65 Hz
TVE (total vector error): <1% Operation: drive FlexLogic. operands Relay burden: < 0.2 VA at rated secondary
Triggering: frequency, voltage, current, power, FLEXCURVES Conversion range:
rate of change of frequency, user- Number: 4 (A through D) Standard CT: 0.02 to 46 × CT rating RMS
defined Reset points: 40 (0 through 1 of pickup) symmetrical
Reporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, 60 or Operate points: 80 (1 through 20 of pickup) Sensitive Ground/HI-Z CT module:
120 times per second Time delay: 0 to 65535 ms in steps of 1 0.002 to 4.6 × CT rating RMS
Number of clients: One over TCP/IP port, two over UDP/ FLEXLOGIC symmetrical
Family Overview
IP ports Programming language: Reverse Polish Notation with Current withstand: 20 ms at 250 times rated
TAC ranges: As indicated in appropriate graphical visualization (keypad 1 sec. at 100 times rated
specifications sections programmable) continuous at 3 times rated
Network reporting 16-bit integer or 32-bit IEEE floating Lines of code: 1024 continuous 4xInom; URs equipped
format: point numbers Internal variables: 128 with 24 CT inputs have a maximum
Network reporting Rectangular (real and imaginary) Supported operations: NOT, XOR, OR (2 to 16 inputs), operating temp. of 50°C
style: or polar (magnitude and angle) AND (2 AC VOLTAGE
coordinates to 16 inputs), NOR (2 to 16 VT rated secondary: 50.0 to 240.0 V
Filtering: P and M class inputs), VT ratio: 1.00 to 24000.00
Calibration: Angle ±5°, magnitude +/-5% per NAND (2 to 16 inputs), Latch Nominal frequency: 20 to 65 Hz For the L90, the nominal
phase (Reset Dominant), Edge system frequency should be chosen as
Compensation: -180 to 180° in steps of 30° (current Detectors, 50 Hz or 60 Hz only.
and voltage components) Timers Relay burden: < 0.25 VA at 120 V
Mode of operation: Normal and test Inputs: any logical variable, contact, or Conversion range: 1 to 275 V
PMU Recording: 46 configurable channels virtual input Voltage withstand: continuous at 260 V to neutral
(14 syncrophasor, 16 digital, Number of timers: 64 1 min./hr at 420 V to neutral
16 analogs) Pickup delay: 0 to 60000 (ms, sec., min.) in CONTACT INPUTS
METERING steps of 1 Dry contacts: 1000 W maximum
RMS CURRENT: PHASE, NEUTRAL, AND GROUND Dropout delay: 0 to 60000 (ms, sec., min.) in Wet contacts: 300 V DC maximum
Accuracy at: steps of 1 Selectable 17 V, 33 V, 84 V, 166 V
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated FLEXELEMENTS thresholds:
(whichever is greater) Number of elements: 16 Tolerance: ±10%
> 2.0 × CT rating: ±1.0% of reading Operating signal: any analog actual value, or two Contacts Per 4
RMS VOLTAGE values in Differential mode Common Return:
Accuracy: ±0.5% of reading from 10 to 208 V Operating signal mode: Signed or Absolute Value Recognition time: < 1 ms
REAL POWER (WATTS) Operating mode: Level, Delta Debounce timer: 0.0 to 16.0 ms in steps of 0.5
Accuracy: ±1.0% of reading at -0.8 < PF < -1.0 Comparator direction: Over, Under Continuous Current 3mA (when energized)
and 0.8 < PF < 1.0 Pickup Level: -30.000 to 30.000 pu in steps Draw:
REACTIVE POWER (VARS) of 0.001 CONTACT INPUTS WITH AUTO-BURNISHING
Accuracy: ±1.0% of reading at -0.2 < PF < 0.2 Hysteresis: 0.1 to 50.0% in steps of 0.1 Dry contacts: 1000 W maximum
APPARENT POWER (VA) Delta dt: 20 ms to 60 days Wet contacts: 300 V DC maximum
Accuracy: ±1.0% of reading Pickup & dropout delay: 0.000 to 65.535 s in steps of Selectable 17 V, 33 V, 84 V, 166 V
WATT-HOURS (POSITIVE AND NEGATIVE) 0.001 thresholds:
Accuracy: ±2.0% of reading FLEXSTATES Tolerance: ±10%
Range: ±0 to 2 × 109 MWh Number: up to 256 logical variables Contacts Per 2
Parameters: 3-phase only grouped Common Return:
Update rate: 50 ms under 16 Modbus addresses Recognition time: < 1 ms
VAR-HOURS (POSITIVE AND NEGATIVE) Programmability: any logical variable, contact, or Debounce timer: 0.0 to 16.0 ms in steps of 0.5
Accuracy: ±2.0% of reading virtual input Continuous Current 3mA (when energized)
Range: ±0 to 2 × 109 Mvarh LED TEST Draw:
Parameters: 3-phase only Initiation: from any digital input or user- Auto-Burnish Impulse 50 to 70 mA
Update rate: 50 ms programmable condition Current:
CURRENT HARMONICS Number of tests: 3, interruptible at any time Duration of Auto- 25 to 50 ms
Harmonics: 2nd to 25th harmonic: per phase, Duration of full test: approximately 3 minutes Burnish Impulse:
displayed as a % of f1 (fundamental Test sequence 1: all LEDs on DCMA INPUTS
frequency phasor) THD: per phase, Test sequence 2: all LEDs off, one LED at a time Current input (mA 0 to -1, 0 to +1, -1 to +1, 0 to 5, 0 to 10,
displayed as a % of f1 on for 1 s DC): 0 to 20, 4 to 20 (programmable)
Accuracy: Test sequence 3: all LEDs on, one LED at a time Input impedance: 379 ±10%
Harmonics: 1. f1 > 0.4pu: (0.20% + 0.035% / off for 1 s Conversion range: -1 to + 20 mA DC
harmonic) of reading or 0.15% of NON-VOLATILE LATCHES Accuracy: ±0.2% of full scale
100%, whichever is greater Type: Set-dominant or Reset- Type: Passive
2. f1 < 0.4pu: as above plus %error dominant DIRECT INPUTS
of f1 Number: 16 (individually programmed) Number of input 32
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / Output: Stored in non-volatile memory points:
harmonic) of reading or 0.20% of Execution sequence: As input prior to protection, No. of remote 16
100%, whichever is greater control, and FlexLogic. devices:
2. f1 < 0.4pu: as above plus %error SELECTOR SWITCH Default states on On, Off, Latest/Off, Latest/On
of f1 Number of elements: 2 loss of comms.:
DEMAND Upper position limit: 1 to 7 in steps of 1 Ring configuration: Yes, No
Measurements: Phases A, B, and C present and Selecting mode: Time-out or Acknowledge Data rate: 64 or 128 kbps
maximum measured currents Time-out timer: 3.0 to 60.0 s in steps of 0.1 CRC: 32-bit
3-Phase Power (P, Q, and S) present Control inputs: step-up and 3-bit CRC alarm:
and maximum measured currents Power-up mode: restore from non-volatile Responding to: Rate of messages failing the CRC
Accuracy: ±2.0% memory or synchronize to a Monitoring message 10 to 10000 in steps of 1
FREQUENCY 3-bit control input count:
Accuracy at ±0.01 Hz (when voltage signal is used USER-DEFINABLE DISPLAYS Alarm threshold: 1 to 1000 in steps of 1
V = 0.8 to 1.2 pu: for frequency measurement) Number of displays: 16 Unreturned message alarm:
I = 0.1 to 0.25 pu: ±0.05 Hz Lines of display: 2 × 20 alphanumeric characters Responding to: Rate of unreturned messages in the
I > 0.25 pu: ±0.02 Hz (when current signal is used Parameters: up to 5, any Modbus register ring configuration
for frequency measurement) addresses Monitoring message 10 to 10000 in steps of 1
VOLTAGE HARMONICS Invoking and scrolling: keypad, or any user- count:
Harmonics: 2nd to 25th harmonic: per phase, programmable condition, Alarm threshold: 1 to 1000 in steps of 1
displayed as a % of f1 (fundamental including pushbuttons IRIG-B INPUT
frequency phasor) THD: per phase, USER-PROGRAMMABLE LEDS Amplitude 1 to 10 V pk-pk
displayed as a % of f1 Number: 48 plus Trip and Alarm (UR modulation:
Accuracy: Enhanced HMI), 8 plus Trip and DC shift: TTL
Harmonics: 1. f1 > 0.4pu: (0.20% + 0.035% / Alarm (UR Color HMI) Input impedance: 22 kW
harmonic) of reading or 0.15% of Programmability: from any logical variable, Isolation: 2 kV
100%, whichever is greater contact, or virtual input REMOTE INPUTS (IEC 61850 GSSE)
2. f1 < 0.4pu: as above plus %error Reset mode: Self-reset or Latched Number of input 32, configured from 64 incoming bit
of f1 USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL) points: pairs
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / Number of pushbuttons: 13 (standard), 16 (UR Enhanced Number of remote 16
harmonic) of reading or 0.20% of HMI) or 8 plus 10 soft devices:
100%, whichever is greater pushbuttons (UR color HMI) Default states on On, Off, Latest/Off, Latest/On
2. f1 < 0.4pu: as above plus %error Mode: Self-Reset, Latched loss of comms.:
of f1 Display message: 2 lines of 20 characters each RTD INPUTS
8-BIT SWITCH Types (3-wire): 100 W Platinum, 100 W &
Number of elements: 6 120 W Nickel, 10 W Copper
Input signals: two 8-bit integers via FlexLogic Sensing current: 5 mA
operands Range: -50 to +250°C
Control: any FlexLogic operand Accuracy: ±2°C
Response time: < 8 ms at 60 Hz, < 10 ms at Isolation: 36 V pk-pk
50 Hz
GEGridSolutions.com 17
UR Technical Specifications
OUTPUTS COMMUNICATIONS INTER-RELAY COMMUNICATIONS
CONTROL POWER EXTERNAL OUTPUT RS232 * Note: Typical distances listed are based on the following
(FOR DRY CONTACT INPUT) Front port: 19.2 kbps, Modbus® RTU, DNP 3.0 assumptions for system loss. Actual losses will vary from one
Capacity: 100 mA DC at 48 V DC RS485 installation to another, the distance covered by your system
Isolation: ±300 Vpk 1 or 2 rear ports: Up to 115 kbps, Modbus® RTU, DNP may vary.
DCMA OUTPUTS 3.0 isolated together at 36 Vpk CONNECTOR LOSSES (TOTAL OF BOTH ENDS)
Range: -1 to 1 mA, 0 to 1 mA, 4 to 20 mA Typical distance: 1200 m ST connector 2dB
Max. load resistance: 12 k for -1 to 1 mA range Isolation: 2 kV FIBER LOSSES
12 k for 0 to 1 mA range ETHERNET PORT 820 nm multimode 3 dB/km
600 for 4 to 20 mA range Up to Three 100Base-F: 1310 nm, multi-mode, supports 1300 nm mulimode 1 dB/km
Accuracy: half-duplex/full-duplex fiber optic 1300 nm singlemode 0.35 dB/km
±0.75% of full-scale for 0 to 1 mA with ST or LC connector 1550 nm singlemode 0.25 dB/km
range Power budget: 10 dB Splice losses: One splice every 2 km, at 0.05 dB
±0.5% of full-scale for -1 to 1 mA Max optical input power: -14 dBm loss per splice
range Max optical output SYSTEM MARGIN
±0.75% of full-scale for 0 to 20 mA power: -20 dBm 3 dB additional loss added to calculations to compensate for
range Receiver sensitivity: -30 dBm all other losses.
99% Settling time to a 100 ms Typical distance: 2 km Compensate difference in transmitting and receiving (channel
step change: Redundabcy: Hot-stanby, PRP asymmetry) channel delays using GPS satellite clock: 10 ms
Isolation: 1.5 kV Up to three 10/100BaseT: Twisted pair, RJ45 connector
Driving signal: any FlexAnalog quantity SNTP Clock (redundant) <10 ms (typical) POWER SUPPLY
Upper & lower limit for -90 to 90 pu in steps of 0.001 synchronization error LOW RANGE
the driving signal: Nominal DC voltage: 24 to 48 V at 3 A
DIRECT OUTPUTS PROTOCOLS Min/max DC voltage: 20 / 60 V
Output points: 32 RS232 RS485 10BaseF 10BaseT 100BaseT * NOTE: Low range is DC only.
FORM-A CURRENT MONITOR IEC 61850 • • • HIGH RANGE
Threshold current: approx. 80 to 100 mA DNP 3.0 • • • • • Nominal DC voltage: 125 to 250 V at 0.7 A
FORM-A RELAY Min/max DC voltage: 88 / 300 V
Make & carry for 0.2s: 30 A as per ANSI C37.90 Modbus • • • • •
Nominal AC voltage: 100 to 240 V at 50/60 Hz, 0.7 A
Carry continuous: 6A IEC104 • • • Min/max AC voltage: 88 / 265 V at 25 to 100 Hz
Break at L/R of 40 ms: 1 A DC max. at 24 V EGD • • • ALL RANGES
0.5 A DC max. at 48 V Volt withstand: 2 × Highest Nominal Voltage for 10 ms
0.3 A DC max. at 125 V INTER-RELAY COMMUNICATIONS Voltage loss hold-up: 50 ms duration at nominal
0.2 A DC max. at 250 V SHIELDED TWISTED-PAIR INTERFACE OPTIONS Power consumption: Typical = 15 VA; Max. = 30 VA
Operate time: < 4 ms INTERNAL FUSE
INTERFACE TYPE TYPICAL DISTANCE
Contact material: Silver alloy RATINGS
FORM-A VOLTAGE MONITOR RS422 1200m Low range power 8 A / 250 V
Applicable voltage: approx. 15 to 250 V DC G.703 100m supply:
Trickle current: approx. 1 to 2.5 mA High range power 4 A / 250 V
* NOTE: RS422 distance is based on transmitter power and supply:
INPUT VOLTAGE IMPEDANCE
does not take into consideration the clock source provided INTERRUPTING CAPACITY
2W RESISTOR 1W RESISTOR by the user. AC: 100 000 A RMS symmetrical
250 V DC 20 K 50K DC: 10 000 A
120 V DC 5K 2K LINK POWER BUDGET Hold up time: 200 ms
48 V DC 2K 2K EMITTER, TRANSMIT RECEIVED
FIBER TYPE POWER SENSITIVITY
POWER BUDGET TYPE TESTS
24 V DC 2K 2K Electrical fast transient:ANSI/IEEE C37.90.1
820nm LED -20dBm -30dBm 10dB IEC 61000-4-4
Multimode
FORM-C AND CRITICAL FAILURE RELAY IEC 60255-22-4
Make & carry for 0.2 s: 30 A 1300 nm LED -21dBm -30dBm 9dB Oscillatory transient: ANSI/IEEE C37.90.1
Multimode
Carry continuous: 8A IEC 61000-4-12
Break at L/R of 40 ms: 0.25 A DC max. at 48 V 1300 nm ELED
Multimode -21dBm -30dBm 9dB Insulation resistance: IEC 60255-5
0.10 A DC max. at 125 V Dielectric strength: IEC 60255-6
Operate time: < 8 ms 1300 nm Laser -1dBm -30dBm 29dB
Singlemode ANSI/IEEE C37.90
Contact material: Silver alloy Electrostatic discharge: EN 61000-4-2
1550 nm Laser
FAST FORM-C RELAY Singlemode +5dBm -30dBm 35dB Surge immunity: EN 61000-4-5
Make & carry: 0.1 A max. (resistive load) RFI susceptibility: ANSI/IEEE C37.90.2
Minimum load impedance: * NOTE: These power budgets are calculated from the IEC 61000-4-3
Operate time: < 0.6 ms manufacturers’ worst-case transmitter power and worst-case IEC 60255-22-3
Internal Limiting 100, 2 receiver sensitivity. Ontario Hydro C-5047-77
Resistor: Conducted RFI: IEC 61000-4-6
IRIG-B OUTPUT MAXIMUM OPTICAL INPUT POWER Voltage dips/interruptions/variations:
Amplitude: 10 V peak-peak RS485 level IEC 61000-4-11
Maximum load: 100 ohms EMITTED, FIBER TYPE MAX. OPTICAL INPUT POWER
IEC 60255-11
Time delay: 1 ms for AM input Power frequency magnetic field immunity:
40 µs for DC-shift input 820 nm LED, Multimode -7.6 dBm
1300 nm LED, Multimode -11 dBm IEC 61000-4-8
Isolation: 2 kV 1300 nm ELED, Singlemode -14 dBm Vibration test IEC 60255-21-1
LATCHING RELAY 1300 nm Laser, Singlemode -14 dBm (sinusoidal):
Make & carry for 0.2 s: 30 A as per ANSI C37.90 1500 nm Laser, Singlemode -14 dBm Shock and bump: IEC 60255-21-2
Carry continuous: 6A * NOTE: Type test report available upon
Break at L/R of 40 ms: 0.25 A DC max. request.
Operate time: < 4 ms TYPICAL LINK DISTANCE
Contact material: Silver alloy CONNECTOR PRODUCTION TESTS
EMITTED TYPE FIBER TYPE TYPICAL DISTANCE
Control: separate operate and reset inputs TYPE THERMAL
Control mode: operate-dominant or reset- 820 nm LED Multimode -7.6 dBm 1.65 km Products go through an environmental test based upon an
dominant accepted quality level (AQL) sampling process
REMOTE OUTPUTS (IEC 61850 GSSE) 1300 nm LED Multimode -11 dBm 3.8 km ENVIRONMENTAL
Standard output points: 32 1300 nm ELED Singlemode -14 dBm 11.4 km OPERATING TEMPERATURES
User output points: 32 1300 nm Laser Singlemode -14 dBm 64 km Cold: IEC 60028-2-1, 16 h at -40°C
SOLID-STATE OUTPUT RELAY Dry Heat: IEC 60028-2-2, 16 h at +85°C
Operate & release time: <100 µs 1500 nm Laser Singlemode -14 dBm 105 km
OTHER
Maximum voltage: 265 V DC Humidity(noncondensing):
Maximum continuous 5 A at 45°C; 4 A at 65°C IEC 60068-2-30, 95%, Variant
current: 1,6days.
Make & carry for 0.2 s: as per ANSI C37.90 Altitude: Up to 2000 m
For 0.3s: 300 A Installation Category: II
Breaking capacity: APPROVALS
UTILITY UL Listed for the USA and Canada
IEC 647-5/UL508 APPLICATION INDUSTRIAL Manufactured under an ISO9000 registered system.
(AUTORECLOSE APPLICATION
SCHEME) LVD 73/23/EEC: IEC 1010-1
5000 ops 5 ops/
1 s-On, 9 s-Off .2 s-On, 10000 ops/
EMC 81/336/EEC: EN 50081-2, EN 50082-2
Operations/ 0.2 s-Off
interval 0.2 s-On,
1000 ops within 1 30 s-Off
0.5 s-On, 0.5 s-Of minute
3.2 A
Break L/R = 10 ms
capability 1.6 A 10 A 10 A IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
(0 to 250 VDC) L/R = 20 ms L/R = 40 ms L/R = 40 ms
0.8 A
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
L/R = 40 ms Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.