Selectivity Catalog Domestic 291015
Selectivity Catalog Domestic 291015
Selectivity Catalog Domestic 291015
Absolute Selectivity
1 ABOUT US
In an electrical power distribution system, loads are connected to the power source via multiple
protection schemes which consist of switching and protective devices. The safety of the electrical system
completely relies on the performance of protection devices.
The reliability of protection scheme depends upon the co-ordination among the protection devices.
In any well co-ordinated protection scheme it is normally desired that:
The fault should be cleared immediately on its occurrence by a protective device closest to the
location of fault
On the occurrence of fault, the healthy feeder should not get isolated and continuity of electrical
supply must be ensured
The system should be stressed least and outage / power interruption is kept to a minimum level
The term 'Selectivity' (popularly known as 'discrimination') implies co-ordination of the operating
characteristics of two or more over-current protective devices such that, on the incidence of over-currents
within stated limits, the device intended to operate within these limits does so, while other(s) does (do)
not.
In simple terms, in case of over-current fault, only the nearest protective device should trip, to isolate the
faulty part of the system, without affecting the supply to the healthy part of the system, and upstream
device should not trip.
OVERLOAD FAULTS:
For achieving proper co-ordination under over-load faults, the SCPDs must be selected such that, the
time-current characteristics of the upstream protection device should lie above the time-current
characteristics of downstream protection device. In other terms, the trip characteristic of downstream
protection device should be faster than that of upstream protection device. Care should be taken while
doing the over current setting of the protection device as the time-current characteristic is a function of
over current setting.
3 TECHNICAL BRIEF
SHORT-CIRCUIT FAULTS:
Selectivity under short-circuit condition can be achieved by three means:
The current selectivity is result of the difference between the magnetic thresholds (instantaneous trip
setting) of the successive circuit breakers (SCPDs). Current selectivity can be achieved for all faults lower
than the instantaneous trip setting of the upstream circuit breaker.
In time selectivity, a definite time delay is set in the sensing of protection release of the upstream circuit
breaker. Hence all the faults will be cleared by the downstream circuit breaker as the upstream circuit
breaker will wait till the set delay time. In case the downstream device fails to clear the fault, then
upstream circuit breaker will trip and clear the fault providing back-up protection. The time delay setting
can be progressively increased in the circuit breakers as it gets closer to the supply source and if used
along with ZSI, popularly used in ACB, electrodynamic stress can be minimized.
The Time selectivity is most effective and foolproof method of selectivity for all fault levels.
In energy selectivity, the upstream device and downstream device operate based on the fault energy seen
by the units during the short circuit faults. The selectivity is achieved based on the quantum of arc energy
seen and the amount of energy required to operate the device. An ideal example of energy selectivity is
HRC fuses, where to achieve total selectivity, pre-arcing energy of upstream fuse should be sufficiently
higher than the operating energy of the downstream fuse.
All of the above means for achieving total selectivity have their own advantages and limitations. It is ideal
to have time selectivity between upstream and downstream device to achieve failsafe selectivity. However
selection of means to achieve selectivity completely depends upon the Power system network and design
parameters.
In order to achieve the prime objectives of continuous availability of energy & safety of system & various
devices like ACB, MCCB & MCB, will require higher sizing of devices and higher insulation grades of cables
making solution expensive. A judicious selection of upstream and downstream devices can also be done
with partial selectivity which can take care of practical faults at different points of the installation. This can
help the user to optimize the size and cost of the installation while safeguarding the system against
dangerous conditions like short circuit faults.
TECHNICAL DATASHEET 4
The current limiting MCCBs are designed to clear the short circuit faults in minimum time so as to limit
the electrodynamic stresses on the electrical system. On the contrary the same current limiting MCCBs
should withstand short circuit fault current to achieve total selectivity. To resolve this challenge, dsine
MCCBs offer a solution with a microprocessor release having an optimized time delay. These
microprocessor MCCBs will not trip till the full fault level of downstream MCCBs, however if the down
stream MCCB fails to clear the fault, this MCCB will trip & clear the fault.
Note:
$ 'NO' of control contactor to be connected in series for 220V DC, 24V DC.
Any two internal accessories can be mounted at a time.
Characteristic curves for o/l settings & short circuit settings are same as DN2-250 & DN3-630 frames. Please contact sales office
for ordering information.
Dimensional details are same as DN2-250 & DN3-630 frames.
5 SELECTIVITY CHARTS
50kA 1000 T T T T T T T
1250 T T T T T T T
1600 T T T T T T T
800 - T T T T T T
1000 - T T T T T T
65kA 1250 - T T T T T T
1600 - T T T T T T
UW1 MTX
2000 - T T T T T T
2500 - T T T T T T
800 - - T - T T T
1000 - - T - T T T
1250 - - T - T T T
80kA
1600 - - T - T T T
2000 - - T - T T T
2500 - - T - T T T
2500 - - - T T T T
65kA
3200 - - - T T T T
UW2 MTX
2500 - - - - T T T
80kA
3200 - - - - T T T
4000 - - - - - T T
80kA 5000 - - - - - T T
6300 - - - - - T T
UW3 MTX
4000 - - - - - - T
100kA 5000 - - - - - - T
6300 - - - - - - T
Note:
The 'Current' and 'Time' setting of upstream device should be kept such that the Time-Current characteristic of upstream device
should not intersect with Time-Current characteristic of downstream device.
Rating of upstream device (In) has to be equal or higher than the rating of downstream device (In).
SELECTIVITY CHARTS 6
25kA TM 250
£ T T T T T T T
DN1-250
50kA TM 250
£ T T T T T T T
36kA T T T T T T T
70kA - T* T T* T T T
36kA T T T T T T T
70kA - T* T T* T T T
36kA T T T T T T T
70kA - T* T T* T T T
50kA T T T T T T T
DN4-1250 MTX 1250
£
70kA - T* T T* T T T
Note:
The Short Time Setting (STS) DN3-630T & DN2-250T MCCB has to be kept at 'INST'.
The 'Current' and 'Time' setting of upstream device should be kept such that the Time-Current characteristic of upstream device should
not intersect with Time-Current characteristic of downstream device.
*Selectivity up to 65kA.
7 SELECTIVITY CHARTS
20 T T T T T T T T T T
25 T T T T T T T T T T
32 - T T T T T T T T T
40 - T T T T T T T T T
DN0-100 25kA TM
50 - - T T T - T T T T
63 - - T T T - T T T T
80 - - - T T - T T T T
100 - - - T T - T T T T
125 - - - - T - - T T T
160 - - - - T - - T T T
DN1-250 25kA TM
200 - - - - - - - - T T
250 - - - - - - - - T T
20 T T T T T T T T T T
25 T T T T T T T T T T
32 - T T T T T T T T T
40 - T T T T T T T T T
DN0-100 36kA TM
50 - - T T T - T T T T
63 - - T T T - T T T T
80 - - - T T - T T T T
100 - - - T T - T T T T
63 - - T T T - T T T T
80 - - - T T - T T T T
100 - - - T T - T T T T
TM 125 - - - - T - - T T T
160 - - - - T - - T T T
200 - - - - - - - - T T
DN2-250 36kA
250 - - - - - - - - T T
40 - T T T T T T T T T
63 - - T T T - T T T T
MTX 100 - - - T T - T T T T
160 - - - - T - - T T T
250 - - - - - - - - T T
SELECTIVITY CHARTS 8
40 - - - - - T T T T T
63 - - - - - - T T T T
160 - - - - - - - T T T
250 - - - - - - - - T T
320 - - - - - - - - - T
DN3B-400 36kA TM
400 - - - - - - - - - T
320 - - - - - - - - - T
TM
DN3-400 36kA 400 - - - - - - - - - T
MTX 400 - - - - - - - - - T
125 - - - - - - - T T T
160 - - - - - - - T T T
DN1-250 50kA TM
200 - - - - - - - - T T
250 - - - - - - - - T T
63 - - - - - - T T T T
80 - - - - - - T T T T
100 - - - - - - T T T T
TM 125 - - - - - - - T T T
160 - - - - - - - T T T
200 - - - - - - - - T T
DN2-250 50kA
250 - - - - - - - - T T
40 - - - - - T T T T T
63 - - - - - - T T T T
MTX 100 - - - - - - T T T T
160 - - - - - - - T T T
250 - - - - - - - - T T
320 - - - - - - - - - T
TM
DN3-400 50kA 400 - - - - - - - - - T
MTX 400 - - - - - - - - - T
Note:
The Short Time Setting (STS) DN2-250T & DN3-630T MCCB has to be kept at 'INST'.
The 'Current' and 'Time' setting of upstream device should be kept such that the Time-Current characteristic of upstream device
should not intersect with Time-Current characteristic of downstream device.
DN2-250T to be used on downstream side only if there is any MCCB below DN2-250T.
Notes:
Notes:
Electrical Standard Products (ESP) Offices:
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA CIN: L99999MH1946PLC004768
SP 50758 201015