Design of Column
Design of Column
C COLUMN
WHAT IS A COLUMN:
Columns are the structural members that are subjected to axial compressive force
as the main force.
TYPES OF COLUMN:
W.r.t to point of application of load
1- Concentrically Loaded Column:
The columns that are subjected to only axial load is called concentrically/axially
load column.
2- Eccentrically Loaded column:
The columns that are subjected to load at an eccentricity resulting in combined
action of axial compression and bending moments are called eccentrically loaded
column.
W.r.t to slenderness ratio
1- Short Column
The column that fails in crushing. l/r < 40
2- Intermediate column
The column that fails in crushing and buckling . l/r = 40 to 100
3- Long Column (Slender column)
The column that fails in buckling. l/r > 100
Solution
Given data:
Size of column
𝑃𝑢 +2𝑀𝑢𝑥 +2𝑀𝑢𝑥 1500×1000
𝐴𝑔(𝑡𝑟𝑖𝑎𝑙) = 0.43𝑓𝑐 ′ +0.008𝑓𝑦
= 0.43(20)+0.008(300)
Longitudinal bars
By using #19 and # 16 bars (Ab=199 mm2) = 4-#19 and 4-#16 (1932mm2)
Transverse bars
Smax=250mm
Provide #10 @ 250mm c/c
4#16
375mm
4#19
Circular column
Size of column
𝑃𝑢 +2𝑀𝑢𝑥 +2𝑀𝑢𝑥 1500×1000
𝐴𝑔(𝑡𝑟𝑖𝑎𝑙) = 0.5𝑓𝑐 ′ +0.01𝑓𝑦
= 0.5(20)+0.01(300) =115385mm2
Longitudinal Bars
1500,000 𝜋
(𝑃𝑢 /0.6375)−0.85𝑓𝑐 ′ 𝐴𝑔 ( )−(0.85×20× ×3852 )
0.6375 4
𝐴𝑠 = = ≈1324.7mm2
𝑓𝑦 −0.85𝑓𝑐 ′ 300−(0.85×20)
𝜋
𝐴𝑠(min)=0.01× 𝐴𝑔 =0.01× 4 × 3852 =1103.9 mm2
As 𝐴𝑠 >𝐴𝑠(min) (ok)
The column should be of rectangular section with at least one side should not larger than 375mm.
Factored Load
Size of column
𝑃𝑢 +2𝑀𝑢𝑥 +2𝑀𝑢𝑦 (1080+2×205.6)×1000
𝐴𝑔(𝑡𝑟𝑖𝑎𝑙) = = =135564mm2= 375 × 375𝑚𝑚
0.43𝑓𝑐 ′ +0.008𝑓𝑦 0.43(20)+0.008(300)
Longitudinal Bars
Pu 1080×1000
= =7.68 MPa
Ag 375×375
Mu 205.6×1000×1000
Ag ℎ
= 375×375×375
=3.90 MPa
375−2(40)−2(10)−32
𝛾= 375
= 0.65 ≈ 0.6
Using 𝛾=0.6, the required steel ratio becomes greater than 3%. It is better to revise the size of
column.
Mu 205.6×1000×1000
Ag ℎ
= 375×400×400
=3.43 MPa
400−2(40)−2(10)−32
𝛾= 400
= 0.67 ≈ 0.6
Third Trial: Again it is larger of 3%. Take column size of 375 × 425𝑚𝑚
Pu 1080×1000
Ag
= 375×425
=6.78 MPa
Mu 205.6×1000×1000
Ag ℎ
= 375×425×425
=3.04 MPa
425−2(40)−2(10)−32
𝛾= 425
= 0.69 ≈ 0.6 ,0.75
Third Trial: Again it is larger of 3%. Take column size of 375 × 450𝑚𝑚
Pu 1080×1000
= =6.4 MPa
Ag 375×450
Mu 205.6×1000×1000
Ag ℎ
= 375×450×450
=2.70 MPa
450−2(40)−2(10)−32
𝛾= 450
= 0.71 ≈ 0.75
Transverse bars
Smax=300mm