Voltage Supply Control Device Load
Voltage Supply Control Device Load
Voltage Supply Control Device Load
Objectives-Week 1
Identify wire colour coding (grounded and ungrounded wires)
Identify the basic symbols used for wiring diagrams
Draw a basic wiring diagram
List CEC rules for colour coding of wires
The layout diagram is also known as a block diagram. It is a single line diagram, making use of
squares, rectangles, circles, etc…, to indicate the parts used, and t he location of each part.
F ──────── S ──────────
Voltage Supply Control Device Load
4. The Schematic Diagram
The schematic diagram is used to indicate, and trace the current paths. It is a single line diagram,
making use of symbols and colour code.
7. Rule 12-506 (1) The cable (Non Metallic Sheathed Cable) shall be run in continuous lengths
between outlet boxes, junction boxes, and panel boxes as a loop system and the joints, splices,
and taps shall be made in the boxes.
A wiring diagram represents this requirement by laying out the loops(circuits) running from
box to box with the cable terminating at devices inside the box. It also communicates exactly
how our circuit is connected.
It also indicates the bonding and grounding connections as required by the CEC.
8.
9. Conductor Identification
CEC requires that the grounded (identified) conductor have an outer finish that is white or
gray, or three continuous white stripes. 4-030 (1)
The white grounded conductor is commonly referred to as the neutral, CEC Rule 4-030(2).
Ungrounded conductors must not use green, white, gray, or three continuous white stripes.
4-038 (3)
The ungrounded conductors are commonly referred to as “hot or phase conductors.”
The equipment bonding conductor is green or bare, CEC Rule 4-036.
10. CEC 4038 (3) (a) (b)
Non-metallic-sheathed cable (Romex) and armoured cable (BX) are colour-coded as follows:
Two-wire:
one black ("hot" phase conductor)
one white (grounded "identified" conductor)
one bare (equipment bonding conductor)
Or
one black ("hot" phase conductor)
one red ("hot" phase conductor)
one bare (equipment bonding conductor)
Three-wire:
one black ("hot" phase conductor)
one white (grounded "identified” conductor)
one red ("hot" phase conductor)
one bare (equipment bonding conductor)
11.
12.
13.
14.
(1) When using NMSC or AC the identified conductor can be changed to another colour
(2) For use in switch loops it can stay white as long as it carries the switched feed to the outlet
only
(3) When not used cut it off
(4) Installed so that devices can be disconnected without interrupting the continuity of the
identified conductor
GROUNDING
SLOT
19. What about the BARE wire???
10-808
(1) Tells us that bonding conductor splices must be made in boxes
(2) Tells us that all bonding conductors shall be connected together using the screws provided
in the box or a combination of the screws plus a wireless connector. Also in such a way so
that the removal of a device does not interrupt the bonding continuity.
10-814
Bonding Conductor Size shall use Table 16A
Our Residential wiring contains an appropriately sized bonding conductor.
• A single pole switch is used when a light or group of lights is to be controlled from one
point.
• The switch is identified by its two terminals and the toggle marked on/off.
• A three way switch differs from a single pole switch in that the three way switch does not
have an on/off position.
• It has a common (the terminal that is always connected) and two traveler terminals.
28.
29.
31.
32. Double Pole Switch
• A double pole (two pole) switch may be
used when two separate circuits are to
be controlled with one switch.
• It may also be used to control a 240
volt load.
33.
34.
35.
36.
37. Conductors
Electrical wires are sized to the American Wire Gauge (AWG) standard.
The larger the AWG number, the smaller the diameter of the wire.
Electrical wires can be solid or stranded.
Conductors that are No. 8 AWG and larger are generally stranded.
38. Conductors (continued)
The Canadian Electrical Code (CEC 4-002) states that the minimum size permitted in house wiring
is #14 AWG (Exceptions see section 16 Table 12)
39. AMPACITY:
Is the current in amperes a conductor can carry continuously under the condition of use without
exceeding its temperature rating.
40. Circuit Rating
CEC Rule 12-100 requires that insulation on conductors be suitable for the conditions in
which they are installed.
The insulation must completely surround the metal conductor, have a uniform thickness,
and run the entire length of the wire or cable.
One type of insulation used on wires is a thermoplastic material (T90 Nylon or TEW)
42. Any insulation with a designation that starts with a "T," such as T90 Nylon or TEW, is a
thermoplastic.
A thermoplastic will deform and melt when excess heat is applied to it.
Any insulation that starts with "R," such as R90XLPE, is a thermoset material.
A thermoset material will not soften and deform when heat is applied to it. When heated above its
rated temperature, it will char and crack.
Table 19 (CEC 2015 pg 342) list the various conductors insulations and applications
43. The insulation covering wires and cables used in house wiring is usually rated at 300 volts or
less.
Conductors are also rated for the temperature they can withstand.
For example:
Type TWN 60° C
Type TWN75 75°C
Type T90 Nylon 90° C
Type RW90-XLPE 900 C
Description
Type NMD90 (Dry or Damp) has a flame-retardant, moisture-resistant non-metallic covering over
the conductors and is suitable for both dry and damp locations.
Types NMW (Wet) and NMWU (Wet, Underground) have a flame-retardant, moisture-resistant,
corrosion-resistant, fungus-resistant non-metallic covering over the conductors.
NMWU is designed especially to use in wet and direct burial locations. Sometimes called Romex
or Loomex.
46. Non-metallic-sheathed cable has an uninsulated copper conductor that is used for bonding purposes
only.
This bonding conductor is not intended for use as a current-carrying circuit wire.
47. Equipment bonding requirements are specified in CEC Rules 10-400 to 10-408, 10-808 and 10-
814. These rules require that all boxes and fixtures in the residence be bonded to ground.
48.
CEC rules
12-100 Types of Conductors-must suitable for conditions of use (CEC Table 19)
12-112 Conductor joints and splices
12-116 Termination of conductors
There are many different brands and types of solderless connectors designed to establish Code-
compliant electrical connections.
There are several wiring methods described in CEC that are used in dwellings.
Non-metallic-sheathed cable (NMSC) is a cable with an assembly of two, three, or four insulated
conductors contained in a non-metallic sheath.
It is a wiring method where the cable can be fastened directly to the surface in either exposed or
concealed locations.
Its advantage over the open wiring method is that the sheath gives abrasion protection over the
entire length of the conductor.
Rules 12-502 to 12-526 list the requirements for non-metallic-sheathed cable installation.
54. 12-502 Maximum voltage between any two conductors-300 V
12-504 Can be used in buildings of combustible construction
55. 12-506 (1) The cable shall be run in continuous lengths between outlet boxes, junction
boxes, and panel boxes as a loop system and the joints, splices, and taps shall be made in
the boxes.
12-506 (4) Where NMSC is run near heating sources heat transfer must be minimized using
an air space.
12-506 (5) A thermal barrier may be allowed.
56. 12-506 (6) Two conductor cable cannot be stapled on edge.
12-508 The cable shall not be bent, handled or stapled so that the conductors are damaged.
57. 12-510
(1) NMSC shall be supported by straps, cable ties approved for the purpose (a) within 300 mm
of every box or fitting; and (b) at intervals not more than 1.5 m throughout the run.
(2) Cables run through holes in joists or studs shall be considered to be supported.
(3) If cable is run in walls already closed in, the above can be omitted.
(4) 150 mm of free conductor shall be left
58. CEC Rule 12-516: Protection for cable in concealed installations
Rule 12-516 requires that the cables be protected from damage by either location or mechanical
means (see Figure 12-17). Subrule (1) requires that when cables pass through studs, joists, or
similar members, protection be provided where the outer surface of the cable is less than 32 mm
from the nearest edge of a member. Protection may be in the form of a plate, which is approved for
this specific purpose, that covers the width of the member; or a cylindrical bushing, which is
approved for this specific purpose, that allows the cable to pass through and is sized for the hole
through the member, extending a minimum of 13 mm beyond both sides of the member. This
protection is intended to safeguard the cable from damage from such causes as penetration by nails
or drywall screws.
59. 12-516 (2) Steel Stud Installation of NMSC
64.
AC90 is the most common and sometimes referred to as BX. The other two types are
ACWU90 and TECK90 (see Table D1).
Armoured cable is available with two, three or four conductors in sizes from No. 14AWG
to 2000 kcmil.
66. AC90 is approved for dry locations only (see Table 19)
Armoured Cable must have an internal bonding wire to meet the bonding requirements of
10-802.
Armoured cable can be used in more applications than NMSC.
A review of Table 19 lists the various uses of different types of armoured cable.
• Underground installations
• May be embedded in concrete
• May be exposed to weather
Electrical and mechanical continuity shall be maintained throughout the run. It shall be secured to
all equipment that it is attached to.
(1) Must have an approved bushing to protect the conductors from the armour.
(3) Must be left visible for inspection.
Must not be bent so that the radius of the curve is less than six times the external diameter of the
cable.
Care must be taken to avoid nicking the conductor insulation and exposing the conductor.
71. Range and Oven Requirements
• CEC Rule 26-744 covers supply connections for electric ranges, counter-mounted cooking
units and wall-mounted ovens.
• (4) & (7) Free-standing range units must have cord- and plug-connection method.
72. NEMA Blade and Slot Configurations
• The National Electrical Manufacturers Association (NEMA) sets slot configurations for
standard receptacles and plug and cord sets. CEC Diagram 1
• CEC 26-744 (4) & (7)
• This is to prevent ranges being plugged into a receptacle of a different rating than the plug.
75. (2) & (3) Cord sets rated 30 amperes are referred to as dryer cords.
• (4), (5), (7) & (8) Cord sets rated 40, 45, or 50 amperes are referred to as range cords.
• 30-amp rated receptacles …dryer receptacles.
• 50-amp rated receptacles …range receptacles.
• Common ratings are 30-, 40-, and 50-ampere in three-pole, three-wire or four-pole, four-
wire configurations.
80. Terminal Identification (Receptacles and Cords)
Receptacles and cords are marked:
– “X” and “Y” for ungrounded conductors.
– “W” for white grounded conductor.
– “G” for equipment bonding conductor.
• The most common method is to install a four-wire, 30-ampere receptacle on the wall
behind the dryer.
• EMT may be run to a point close to the appliance and then transition to flexible metal
conduit completing the run to the junction box on the dryer.
“Any channel designed for holding wires, cables, or busbars, and, unless otherwise qualified in the
Rules of this Code, the term includes conduit (rigid and flexible, metal and non-metallic), electrical
metallic and non-metallic tubing, underfloor raceways, cellular floors, surface raceways, wire ways,
cable trays, bus ways, and auxiliary gutters.”
In buildings of cinder block, cement block or poured concrete, it is necessary to make the electrical
installation in conduit.
All conduit runs should be level, straight, plumb, and neat: show good workmanship
12-1404 Restriction on use-shall not be used where subject to mechanical damage, subject to
vapour or for direct burial
12-1406 Supports-1m within box, spacing see 12-1010 12-1408 Minimum tubing size-16mm
Similar to armored cable, except that conductors are installed by the electrician
For armored cable, cable armor is wrapped around conductors at the factory to
form a complete cable assembly
Flexible metal and nonmetallic conduit is commonly used to connect recessed
luminaires
Simplifies installation
Stops the transfer of vibrations
Metal and nonmetallic fittings listed for use with various types of Liquid tight
flexible nonmetallic conduit will be marked with “A,” “B,” or “C” designations
Where flexibility is required, don’t forget a bonding wire must be installed as well,
always.
Can be threaded on the job, or non-threaded fittings may be used where permitted
When rigid metal conduit is threaded on the job, thread must be coated
with approved electrically conductive, corrosion resistant compound
RMC bends can be purchased, or they can be made using special bending
tools
12-1002 Use-may be used in combustible or non-combustible buildings; when used in damp or wet
locations must be threaded and made watertight
12-1004 Minimum size of conduits-16mm
12-1006 Conduit threads-tapered, use table 40 for number of threads, no running threads
12-1008 Thread engagement-3 threads
102. 12-1114 Spacing of support-PVC shall be securely attached and supported with spacings not
greater than:
The change in length, in millimetres, of a run of rigid PVC conduit, due to the maximum expected
variation in temperature, is found by multiplying the length of the run, in metres, by the maximum
expected temperature change, in degrees Celsius, and by the coefficient of linear expansion.
∆I = L x ∆T x C
Where
∆I = the change in length, in millimetres, of a run of PVC due to the maximum variation in temperature
L = the length of a run of conduit in metres
∆T = the maximum expected temperature change, in °C
C = the coefficient of linear expansion
105.
∆I = L x ∆T x C
For a 20 m run of rigid PVC conduit when the minimum expected temperature is –40 °C and the
maximum expected temperature is 30 °C, the change in length is: ???
Solution:
20 × (40 + 30) × 0.0520 = 73 mm
Rules12-1500 to 12-1514
Specs for commercial building allows use of ENT for feeders, branch circuits, and
phone wiring where raceway is 53mm or smaller
ENT fittings
• Wall and ceiling boxes are available with knockouts for trade sizes 16mm,
21mm, and 27mm
• ENT can also be connected to any PVC box
• ENT mud boxes listed for luminaire support are available with knockouts
for trade sizes 16mm, 21mm, and 27mm
Overhead Service
Usually from the transformer on the pole to the point of attachment on the service mast.
Underground Service
From the transformer to the line side of the meter base.
Rule 6–408. This will usually be within 1 m from the front of the house and 1.8 m above
grade to the centre of the socket.
The mast service is often used on buildings with low roofs, such as ranch-style dwellings,
to ensure adequate clearance between the ground and the lowest service conductor.
The point of attachment of the conductors to the building must not be higher than 9 m
above grade, and minimum clearances from the conductors to grade should not be less
than:
5.5 m for highways, lanes, and alleys
5.0 m commercial and industrial driveways
4.0 m for residential driveways
3.5 m for sidewalks
The service conductors must not be less than 1 m from a window, door, or porch,
Rule 6–112(3).
Normally there must be a clearance of 915 mm between the point of attachment and the
roof.
This may be reduced if a minimum of 600 mm is maintained between the roof and the
bottom of the drip loops on the supply conductors.
The underground service is the cable installed underground from the customer’s meter
socket to the utility’s supply. This cable is usually, but not always, supplied by the utility
company.
The utility runs the services to the lot line, and the electrical contractor completes the
installation.
The main service disconnect means shall be installed at a readily accessible location so that
the service entrance conductors within the building are as short as possible.
The requirements for disconnecting the electrical services are covered in Rule 6–200.
Rule 6–200(1) requires that each consumer’s service be provided with a single service box.
However, Rule 6-200(2) sets out the circumstances in which more than one service box is
permitted.
When the main service panel is located some distance from areas having many circuits
and/or a heavy load concentration, it is recommended that load centres be installed near
these concentrations of loads.
To determine the proper size of conduit, the conduit fill is calculated using the necessary
data in Tables 8, 9, and 10
If all the wires in the conduit are the same size, Table 6 may be used for sizing the conduit.
Electrical systems and their conductors are grounded to minimize voltage spikes when
lightning strikes, or when other line surges occur. Grounding stabilizes the normal voltage
to ground.
Proper grounding means that over current devices can operate faster when responding to
ground faults.
In the grounding electrode system, rather than grounding a single item such as the neutral
conductor, the electrician must be concerned with grounding and bonding together an entire
system.
The term system means the service neutral conductor, the grounding electrode, cold water
pipes, gas pipes, service entrance equipment, and jumpers installed around meters
This means that all parts of the system must be tied (bonded) together (Figure 4-17).
131. The following steps illustrate what can happen if an entire system is not bonded.
1. A live wire contacts the gas pipe. The bonding jumper (A) is not installed originally.
2. The gas pipe now has 120 volts with respect to ground. The pipe is hot.
3. The insulating joint in the gas pipe results in a poor path to ground; assume the resistance is
8 ohms.
5. If a person touches the hot gas pipe and the water pipe at the same time, current flows
through the person’s body. If the body resistance is 12 000 ohms, the current is:
I =E/R =120/12000 = 0.01amperes
6. The overcurrent device is “seeing” (15 + 0.01) amperes 15.01 amperes; however, it still
does not open.
7. If the system grounding concept had been used, bonding jumper A would have kept the
voltage difference between the water pipe and the gas pipe at zero, Rule 10–406(2)(a) and
(4). Thus, the overcurrent device would open. If 3.05 m of No. 6 AWG copper wire is used
as the jumper, the resistance of the jumper is 0.00395 ohms.
Rule 10–002 sets out the objectives of grounding and bonding, summarized as follows:
Rule 10–002 sets out the objectives of grounding and bonding, summarized continued:
to limit voltage on a circuit when exposed to lightning
to limit AC circuit voltages to ground to 150 volts or less on circuits supplying
interior wiring systems.
Section 0 provides definitions for the terms associated with grounding and bonding
electrical systems.
Grounding A permanent path to earth with sufficient ampacity to carry any fault current
liable to be imposed on it.
Grounding Conductor The conductor used to connect the service equipment to the
grounding electrode.
The potential voltage differences between the parts of the system are minimized,
reducing the shock hazard.
The impedance of the ground path is minimized. This results in a higher current
flow in the event of a ground fault: the lower the impedance, the higher the current
flow. This means that the overcurrent device will open faster under fault
conditions.
135. Bonding
Bonding must be done at service entrance equipment. Rule 10–606 lists the methods approved for
bonding this equipment.
If equipment is not properly bonded, the potential for an electrical shock is present.
The shock hazard exists whenever the user can touch both the defective equipment and
grounded surfaces.
There are many receptacle locations that are required to be GFCI protected.
Receptacles located near water must be GFCI protected.
GFCI breakers protect the entire circuit.
GFCI receptacles can be wired to protect “downstream” receptacles.
A GFCI device prevents current from leaving the circuit pathways and flowing into a
human body.
GFCI does not protect from all types of shocks, only the ground-fault type.
A ground fault is an unwanted pathway between a hot and a grounded surface. This
unwanted pathway may be through a human body!
It is wise to test GFCI devices regularly.
The integral test buttons on a GFCI device can be used to test the device
The receptacle outlets in this residence are installed outdoors, in the bathrooms, on the
kitchen counter near the sink, and specific ones in the basement are protected by GFCIs.
Swimming pools also have special requirements for GFCI protection.
Never ground a system neutral conductor except at the service equipment; otherwise, the
GFCI will be inoperative, Rule 10–204(1).
Never connect the neutral of one circuit to the neutral of another circuit.
Means the circuit which carries the electric signals directing the performance of a control device,
but does not carry the power which the device controls.
Means any electrical circuit, other than a communication circuit, which supplies energy to a device
which gives a recognizable signal, such as circuits for doorbells, buzzers, code-calling systems,
signal lights, and the like.
CLASS 1 CIRCUIT
Extra Low Voltage Power Circuits Examples
Circuits which are supplied from sources having limitations in accordance with Rule 16-100.
Class 1 extra low voltage power circuits shall be supplied from a source having a rated output of
not more than 30 V and 1000 VA
Class 1 remote-control and signal circuits shall be supplied by a source not exceeding 600 Volts
Circuits which are supplied from sources having limitations in accordance with Rule 16-200
0 to 20 Volts, maximum 5 Amps, unless from batteries with short circuit under 7.5 Amps
after 1 minute or, a current limiting device not to exceed 5 amps.
Over 20 Volts to a maximum of 150 Volts, not to exceed 100 VA or batteries under fault
conditions that will not exceed 5 amps after 1 minute, or a device having energy-limiting
characteristics not to exceed 100VA.
150. Examples
• Bells
• Buzzers
• Thermostats
• Remote Control Circuits
• Signal Circuits
• Burglar Alarms
• Low Voltage Switching
• PLC Circuits
EXAMPLES
Class 2 is power limited to 100 VA and under 4 voltage classes up to 150 volts and should
not deliver enough energy to start a fire. Any wiring method supplied by a class 2 power
supply. 16-200. LVT up to 30 volts. Open splicing permitted.
Class 1 is low voltage but not nearly as power limited, 1000 VA and under 30 volts except
that class 1 control and signal circuits can be up to 600 volts. Wiring method is the mostly
the same as for power. 16-100. No LVT here and splices must be done in a box or
approved device but not open like in power circuits.
155. Section 32 — Fire alarm systems, fire pumps, and carbon monoxide alarms (See Appendix G)
32-100 Conductors
32-100 Wiring Methods
32-104 Equipment Bonding
32-106 Electrical Supervision
32-108 Current Supply
32-110 Installation of smoke alarms and carbon monoxide alarms in dwelling units Fire Pumps