A.1.3 Modbus Measured Variables With The Function Codes 0x03 and 0x04

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Appendix

A.1 Modbus

A.1.3 Modbus measured variables with the function codes 0x03 and 0x04

Addressing the measured variables


You can use the Modbus function codes 0x03 and 0x04 on all the measured variables listed
below.

Note
Error in the case of inconsistent access to measured values
Please ensure the start offset of the register is correct for read access operations.
Please ensure the start offset and the number of registers are correct for write access
operations.
If a value consists of two registers, a read command applied in the second register, for
example, will generate an error code. The device will also output an error code if, for
example, a write operation ends in the middle of a multi-register value.

Table A- 3 Meaning of the abbreviations in the "Access" column of the table headed "Available measured variables" be-
low

Abbreviation Meaning
R Read; read access
W Write; write access
RW Read Write; read and write access

Table A- 4 Available measured variables

Offset Number of Name Format Unit Value range Access


registers
1 2 Voltage L1-N Float V – R
3 2 Voltage L2-N Float V – R
5 2 Voltage L3-N Float V – R
7 2 Voltage L1-L2 Float V – R
9 2 Voltage L2-L3 Float V – R
11 2 Voltage L3-L1 Float V – R
13 2 Current L1 Float A – R
15 2 Current L2 Float A – R
17 2 Current L3 Float A – R
19 2 Apparent power L1 Float VA – R
21 2 Apparent power L2 Float VA – R
23 2 Apparent power L3 Float VA – R
25 2 Active power L1 Float W – R
27 2 Active power L2 Float W – R

PAC3120 and PAC3220


Equipment Manual, 10/2019, 113
Appendix
A.1 Modbus

Offset Number of Name Format Unit Value range Access


registers
29 2 Active power L3 Float W – R
31 2 Reactive power L1 (VAR1) Float var – R
33 2 Reactive power L1 (VAR1) Float var – R
35 2 Reactive power L1 (VAR1) Float var – R
37 2 Power factor L1 Float – 0…1 R
39 2 Power factor L2 Float – 0…1 R
41 2 Power factor L3 Float – 0…1 R
43 2 THD-R voltage L1 Float % 0 … 100 R
45 2 THD-R voltage L2 Float % 0 … 100 R
47 2 THD-R voltage L3 Float % 0 … 100 R
49 2 THD-R current L1 Float % 0 … 100 R
51 2 THD-R current L2 Float % 0 … 100 R
53 2 THD-R current L3 Float % 0 … 100 R
55 2 Frequency Float Hz 45 … 65 R
57 2 Average voltage UL-N Float V – R
59 2 Average voltage UL-L Float V – R
61 2 Average current Float A – R
63 2 Total apparent power Float VA – R
65 2 Total active power Float W – R
67 2 Total reactive power Float var – R
69 2 Total power factor Float – – R
71 2 Amplitude unbalance voltage Float % 0 … 100 R
73 2 Amplitude unbalance current Float % 0 … 200 R
75 2 Maximum voltage L1-N Float V – R
77 2 Maximum voltage L2-N Float V – R
79 2 Maximum voltage L3-N Float V – R
81 2 Maximum voltage L1-L2 Float V – R
83 2 Maximum voltage L2-L1 Float V – R
85 2 Maximum voltage L3-L1 Float V – R
87 2 Maximum current L1 Float A – R
89 2 Maximum current L2 Float A – R
91 2 Maximum current L3 Float A – R
93 2 Maximum apparent power L1 Float VA – R
95 2 Maximum apparent power L2 Float VA – R
97 2 Maximum apparent power L3 Float VA – R
99 2 Maximum active power L1 Float W – R
101 2 Maximum active power L2 Float W – R
103 2 Maximum active power L3 Float W – R
105 2 Maximum reactive power L1 Float var – R
(VARn)
107 2 Maximum reactive power L1 Float var – R
(VARn)

PAC3120 and PAC3220


114 Equipment Manual, 10/2019,
Appendix
A.1 Modbus

Offset Number of Name Format Unit Value range Access


registers
109 2 Maximum reactive power L1 Float var – R
(VARn)
111 2 Maximum power factor L1 Float – 0…1 R
113 2 Maximum power factor L2 Float – 0…1 R
115 2 Maximum power factor L3 Float – 0…1 R
117 2 Maximum THD-R voltage L1-L2 Float % 0 … 100 R
119 2 Maximum THD-R voltage L2-L3 Float % 0 … 100 R
121 2 Maximum THD-R voltage L3-L1 Float % 0 … 100 R
123 2 Maximum THD-R current L1 Float % 0 … 100 R
125 2 Maximum THD-R current L2 Float % 0 … 100 R
127 2 Maximum THD-R current L3 Float % 0 … 100 R
129 2 Maximum frequency Float – 45 … 65 R
131 2 Maximum average voltage UL-N Float V – R
133 2 Maximum average voltage UL-L Float V – R
135 2 Maximum average current Float A – R
137 2 Maximum total apparent power Float VA – R
139 2 Maximum total active power Float W – R
141 2 Maximum total reactive power Float var – R
(VARn)
143 2 Maximum total power factor Float – – R
145 2 Minimum voltage L1-N Float V – R
147 2 Minimum voltage L2-N Float V – R
149 2 Minimum voltage L3-N Float V – R
151 2 Minimum voltage L1-L2 Float V – R
153 2 Minimum voltage L2-L1 Float V – R
155 2 Minimum voltage L3-L1 Float V – R
157 2 Minimum current L1 Float A – R
159 2 Minimum current L2 Float A – R
161 2 Minimum current L3 Float A – R
163 2 Minimum apparent power L1 Float VA – R
165 2 Minimum apparent power L2 Float VA – R
167 2 Minimum apparent power L3 Float VA – R
169 2 Minimum active power L1 Float W – R
171 2 Minimum active power L2 Float W – R
173 2 Minimum active power L3 Float W – R
175 2 Minimum reactive power L1 Float var – R
(VARn)
177 2 Minimum reactive power L1 Float var – R
(VARn)
179 2 Minimum reactive power L1 Float var – R
(VARn)
181 2 Minimum power factor L1 Float – 0…1 R

PAC3120 and PAC3220


Equipment Manual, 10/2019, 115
Appendix
A.1 Modbus

Offset Number of Name Format Unit Value range Access


registers
183 2 Minimum power factor L2 Float – 0…1 R
185 2 Minimum power factor L3 Float – 0…1 R
187 2 Minimum frequency Float Hz 45 … 65 R
189 2 Minimum average voltage UL Float V – R
191 2 Minimum average voltage UL-L Float V – R
193 2 Minimum average current Float A – R
195 2 Minimum total apparent power Float VA – R
197 2 Minimum total active power Float W – R
199 2 Minimum total reactive power Float var – R
(VARn)
201 2 Minimum total power factor Float var – R
203 2 Limit violations Unsigned long – Byte3 Bit0 Limit 0 R
Byte3 Bit1 Limit 1
Byte3 Bit2 Limit 2
Byte3 Bit3 Limit 3
Byte3 Bit4 Limit 4
Byte3 Bit5 Limit 5
Byte0 Bit0 Limit comb.
205 2 PMD diagnostics and status Unsigned long – Byte0 global state R
Byte1 local state
Byte2 global diag.
Byte3 local diag.
207 2 Digital outputs status Unsigned long – Byte3 Bit0 Output 0.0 R
Byte3 Bit1 Output 0.1
209 2 Digital inputs status Unsigned long – Byte3 Bit0 Input 0.0 R
Byte3 Bit1 Input 0.1
211 2 Active tariff Unsigned long – 0 = Tariff 1 R
1 = Tariff 2
213 2 Operating hours counter Unsigned long s 0 … 999999999 RW
215 2 Counter (configurable) Unsigned long – 0 … 999999999 RW
217 2 Counter basic parameter changes Unsigned long – – R
219 2 Counter all parameter changes Unsigned long – – R
221 2 Counter limit value changes Float – – R
223 2 Current N Float A – R
225 2 Maximum current N Float A – R
227 2 Minimum current N Float A – R
231 2 Configurable energy counter Float kWh, – R
kvarh
233 2 Status digital outputs module 1 Unsigned long – Byte3 Bit0 Output 4.0 R
Byte3 Bit0 Output 4.1

PAC3120 and PAC3220


116 Equipment Manual, 10/2019,
Appendix
A.1 Modbus

Offset Number of Name Format Unit Value range Access


registers
235 2 Status digital inputs module 1 Unsigned long – Byte3 Bit0 Input 4.0 R
Byte3 Bit1 Input 4.1
Byte3 Bit2 Input 4.2
Byte3 Bit3 Input 4.3
237 2 Status digital outputs module 2 Unsigned long – Byte3 Bit0 Output 8.0 R
Byte3 Bit0 Output 8.1
239 2 Status digital inputs module 2 Unsigned long – Byte3 Bit0 Input 8.0 R
Byte3 Bit1 Input 8.1
Byte3 Bit2 Input 8.2
Byte3 Bit3 Input 8.3
501 2 Cumulated average active power Float W – R
import
503 2 Cumulated average reactive pow- Float var – R
er import
505 2 Cumulated average active power Float W – R
export
507 2 Cumulated average reactive pow- Float var – R
er export
509 2 Maximum active power reading Float W – R
during demand period
511 2 Minimum active power reading Float W – R
during demand period
513 2 Maximum reactive power reading Float var – R
during demand period
515 2 Minimum reactive power reading Float var – R
during demand period
517 2 Length of the current demand Unsigned long s – R
period
519 2 Time since start of current de- Unsigned long s – R
mand period
799 2 Date/time Unix_ts – – RW
801 4 Total active energy import tariff 1 Double Wh Overflow 1.0e+12 RW
805 4 Total active energy import tariff 2 Double Wh Overflow 1.0e+12 RW
809 4 Total active energy export tariff 1 Double varh Overflow 1.0e+12 RW
813 4 Total active energy export tariff 2 Double varh Overflow 1.0e+12 RW
817 4 Total reactive energy import tar- Double Wh Overflow 1.0e+12 RW
iff 1
821 4 Total reactive energy import tar- Double Wh Overflow 1.0e+12 RW
iff 2
825 4 Total reactive energy export tar- Double varh Overflow 1.0e+12 RW
iff 1
829 4 Total reactive energy export tar- Double varh Overflow 1.0e+12 RW
iff 2
833 4 Total apparent energy tariff 1 Double VAh Overflow 1.0e+12 RW
837 4 Total apparent energy tariff 2 Double VAh Overflow 1.0e+12 RW

PAC3120 and PAC3220


Equipment Manual, 10/2019, 117
Appendix
A.1 Modbus

Offset Number of Name Format Unit Value range Access


registers
841 4 L1 active energy import tariff 1 Double Wh Overflow 1.0e+12 RW
845 4 L1 active energy import tariff 2 Double Wh Overflow 1.0e+12 RW
849 4 L1 active energy export tariff 1 Double varh Overflow 1.0e+12 RW
853 4 L1 active energy export tariff 2 Double varh Overflow 1.0e+12 RW
857 4 L1 reactive energy import tariff 1 Double Wh Overflow 1.0e+12 RW
861 4 L1 reactive energy import tariff 2 Double Wh Overflow 1.0e+12 RW
865 4 L1 reactive energy export tariff 1 Double varh Overflow 1.0e+12 RW
869 4 L1 reactive energy export tariff 2 Double varh Overflow 1.0e+12 RW
873 4 L1 apparent energy tariff 1 Double VAh Overflow 1.0e+12 RW
877 4 L1 apparent energy tariff 2 Double VAh Overflow 1.0e+12 RW
881 4 L2 active energy import tariff 1 Double Wh Overflow 1.0e+12 RW
885 4 L2 active energy import tariff 2 Double Wh Overflow 1.0e+12 RW
889 4 L2 active energy export tariff 1 Double varh Overflow 1.0e+12 RW
893 4 L2 active energy export tariff 2 Double varh Overflow 1.0e+12 RW
897 4 L2 reactive energy import tariff 1 Double Wh Overflow 1.0e+12 RW
901 4 L2 reactive energy import tariff 2 Double Wh Overflow 1.0e+12 RW
905 4 L2 reactive energy export tariff 1 Double varh Overflow 1.0e+12 RW
909 4 L2 reactive energy export tariff 2 Double varh Overflow 1.0e+12 RW
913 4 L2 apparent energy tariff 1 Double VAh Overflow 1.0e+12 RW
917 4 L2 apparent energy tariff 2 Double VAh Overflow 1.0e+12 RW
921 4 L3 active energy import tariff 1 Double Wh Overflow 1.0e+12 RW
925 4 L3 active energy import tariff 2 Double Wh Overflow 1.0e+12 RW
929 4 L3 active energy export tariff 1 Double varh Overflow 1.0e+12 RW
933 4 L3 active energy export tariff 2 Double varh Overflow 1.0e+12 RW
937 4 L3 reactive energy import tariff 1 Double Wh Overflow 1.0e+12 RW
941 4 L3 reactive energy import tariff 2 Double Wh Overflow 1.0e+12 RW
945 4 L3 reactive energy export tariff 1 Double varh Overflow 1.0e+12 RW
949 4 L3 reactive energy export tariff 2 Double varh Overflow 1.0e+12 RW
953 4 L3 apparent energy tariff 1 Double VAh Overflow 1.0e+12 RW
957 4 L3 apparent energy tariff 2 Double VAh Overflow 1.0e+12 RW

PAC3120 and PAC3220