1 en 13 Chapter OnlinePDF
1 en 13 Chapter OnlinePDF
1 en 13 Chapter OnlinePDF
net/publication/266030727
CITATIONS READS
5 432
1 author:
Reza Sirjani
Eastern Mediterranean University
42 PUBLICATIONS 474 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Reza Sirjani on 15 May 2019.
Reza Sirjani
Keywords STATCOM Power loss Modal analysis Optimization techniques
Harmony search algorithm
R. Sirjani (&)
Faculty of Engineering, Cyprus International University, Nicosia, Mersin 10,
Northern Cyprus, Turkey
e-mail: rsirjani@ciu.edu.tr
13.1 Introduction
From the categories, the heuristic optimization techniques have been widely
applied in solving the optimal STATCOM placement problem. In this chapter, a
comprehensive analysis of the heuristic optimization techniques for optimal
placement and sizing of STATCOMs that have been proposed recently by various
researchers is presented. This analysis includes important heuristic optimization
techniques such as Evolution Strategies (ES), Genetic Algorithms (GA), Particle
Swarm Optimization (PSO), and Harmony Search (HS) algorithms used in solving
power system optimization problems. In addition, applications of hybrid techniques
in optimal STATCOM placement problems are discussed.
In the next stage, a new optimization technique, the GHS algorithm is used to
find the optimal placement and sizing of STATCOM in power systems. The har-
mony search algorithm is a meta-heuristic optimization method that is inspired by
musicians adjusting the pitches of their instruments to find better harmony [8]. It
has several advantages over other methods, such as not requiring initial value
settings for the decision variables and handling both discrete and continuous
variables. In this research, the suitable buses are first identified using modal anal-
ysis. Next, the global harmony search algorithm is employed to determine the
amount of shunt compensation required for loss minimization and voltage
improvement with respect to the size of the STATCOM. The results obtained using
the proposed algorithm in 57 and 118-bus test systems are compared with other
optimization methods for validation.
The ES optimization technique was introduced in the early 1960s and developed
further in the 1970s by Rechenberg and Schwefel at the University of Berlin in
Germany. It was originally created to solve technical optimization problems, and its
first application was in the area of hydrodynamics [18]. Nowadays, the ES is
recognized as a very strong optimization method capable of solving large scale,
multimodal, highly constrained, nonlinear problems. The main search procedure in
the ES is the mutation operator that generates random samples around search points
(solution candidates) selected from a population of different search points. The
original strategy, denoted by 1 + 1, generates one offspring from a single parent by
applying mutation. If the child performs better than its ancestor, it will be the parent
of the next generation [19].
An ES was developed to obtain the best points of operation of FACTS devices
[20]. The objective function was defined to adjust the control variables of the SVC,
STATCOM, and UPFC in order to improve the power system operation by
reducing losses that electric network suffers under a certain load condition, taking
into account the voltage drop constraints and operation limits of the devices. The
ES developed in this paper was applied to various power systems with satisfactory
results and low computational effort.
Other techniques only choose those individuals with a fitness value greater than a
given arbitrary constant. Taken together, crossover and mutation are called repro-
duction which is analogous to biological crossover and mutation [9]. The advan-
tages and disadvantages of GA are described as follows [9, 11]:
The advantages of GA:
• It can solve every optimization problem which can be described with the
chromosome encoding.
• It solves problems with multiple solutions.
• Since GA execution technique is not dependent on the error surface, it can be
used for solving multi-dimensional, non-differential, non-continuous, and even
non-parametrical problems.
• GA is a technique which is easy to be understood and it practically does not
demand the knowledge of mathematics.
• GA is easily transferred to existing simulations and models.
The disadvantages of GA:
• Certain optimization problems cannot be solved by GA probably due to poorly
known fitness functions which generate bad chromosome blocks.
• There is no absolute assurance that a GA will find a global optimum.
• GA cannot assure constant optimization response times. In addition, the dif-
ference between the shortest and the longest optimization response times is
much larger than with conventional gradient methods. This disadvantage limits
the use of GA in real time applications.
• GA application in real time control is limited because of random solutions and
convergence. This means that while the entire population is improving, there is
no assurance that an individual within this population will converge to its
specified value. Therefore, it is unreasonable to use GA for on-line control in
real systems without testing it first on a simulation model.
A GA based optimization procedure has been implemented to find the best
placement, type, and size of selected FACTS devices for reducing total financial
losses in the network caused by voltage sags [21]. Three types of FACTS devices
were considered, namely, SVC, STATCOM, and Dynamic Voltage Restorer
(DVR).
Another GA based allocation of FACTS devices considered the cost function of
FACTS devices and power system losses [22]. Simulation of the test system for
different scenarios showed that the placement of multi-type FACTS devices leads to
an improvement in the voltage stability margin of power system and reduction of
losses.
An optimization method termed “the Queen Bee assisted GA” has been explored
to obtain optimal placement of FACTS devices for voltage profile enhancement
[23]. The proposed algorithm is a modification of the standard GA incorporating
the evolution of a queen bee in a hive. This algorithm converges much faster than
the standard GA with smaller number of parameters and reduced computational
burden. A performance criterion using a voltage stability index was defined to
442 R. Sirjani
quantify voltage stability at any given bus. The effectiveness of the approach was
confirmed through simulation results.
Tavakoli et al. [24] examined the average model of STATCOM in the time
domain and then adapted its power flow analysis. A combinatorial optimization was
arranged which focused on voltage stability, reactive power, and losses of trans-
mission lines as three main objectives for the power system. GA was employed to
seek the optimal solution for sizing and placing STATCOMs across the IEEE
14-bus network, while a correcting power ratio was defined for adapting the opti-
mized values with those obtained by the average model.
An approach based on sensitivity analysis and GA was applied to optimally
locate STATCOM in a distribution network [25]. A step-by-step sensitivity analysis
approach is utilized to find optimal placement of compensators. In this process, a
compound voltage-loss sensitivity index is used to meet various optimization
requirements. In the next step, reactive power injection of the STATCOM is defined
by the GA. The objective function takes into account voltage stability, reduction of
active losses and reduction of reactive power in a power network.
PSO techniques has been proposed to minimize total losses in a power system with
FACTS devices [33]. The problem was decomposed into two sub-problems in
which the first sub-problem considered optimal placement of FACTS devices using
a line loss sensitivity index and the second sub-problem considered load flow with
FACTS parameters using the MSA/PSO techniques.
Fig. 13.1 Number of papers published on different optimization techniques for optimal
STATCOM placement
446 R. Sirjani
X
n
Pi ¼ Vi2 Gii Vi Vm ½Gim cosðhi hm Þ þ Bim sinðhi hm Þ ð13:1Þ
m¼1
X
n
Qi ¼ Vi2 Bii þ Vi Vm ½Gim cosðhi hm Þ Bim cosðhi hm Þ ð13:2Þ
m¼1
With the addition of a STATCOM connected at bus k, the system power flow
equations remain the same as the equations of a system without a STATCOM for
all buses given by (13.1) and (13.2) except for bus k. The power flow equations for
Fig. 13.2 STATCOM representation a VSC connected to the AC network via a transformer,
b Shunt solid-state voltage source [34]
13 Optimal Placement and Sizing of STATCOM … 447
the STATCOM in a two-bus system shown in Fig. 13.2b are derived by first
considering the voltage source and the complex power which are given by,
By substituting (13.3) into (13.4), the active and reactive power equations at the
converter terminal and bus k are obtained as follows [6]:
PvR ¼ VvR
2
GvR Vk VvR ½GvR cosðdvR hk Þ þ BvR sinðdvR hk Þ ð13:5Þ
QvR ¼ VvR
2
BvR þ Vk VvR ½BvR cosðdvR hk Þ GvR sinðdvR hk Þ ð13:6Þ
Pk ¼ Vk2 GvR Vk VvR ½GvR cosðhk dvR Þ þ BvR sinðhk dvR Þ ð13:7Þ
Qk ¼ Vk2 BvR þ Vk VvR ½BvR cosðhk dvR Þ GvR sinðhk dvR Þ ð13:8Þ
These equations for two-bus power system are obtained. Thus, for an n-bus
power system, the active and reactive power equations at bus k (i.e. the bus where
the STATCOM is connected) are given as follows:
PK ¼ VvR
2
GvR VK VvR ½GvR cosðdvR hK Þ þ BvR sinðdvR hK Þ
Xn ð13:9Þ
þ VK2 GKK VK Vm ½GKm cosðhK hm Þ þ Bim sinðhK hm Þ
m¼1
.
448 R. Sirjani
Modal or eigenvalue analysis of the Jacobian (J) matrix of system load flow
equation, near the point of voltage collapse, has been widely used to identify buses
vulnerable to voltage collapse and locations for injecting reactive power into the
system [6]. The participation of each load in the critical mode determines the
importance of the load in voltage collapse. The degree of participation is determined
from an inspection of the entries of the left eigenvector of the critical mode. Right
eigenvector components indicate the degree to which given variables are involved in
a given mode. The use of both left and right eigenvector information leads to the
notion of participation factors that indicate which generators should be motivated to
inject more active or reactive power into the system [35]. Here, modal analysis is
used for determining optimal placement of VAr compensators which are normally
installed in power transmission systems for voltage stability improvement.
In the modal analysis method, the Jacobian matrix of the operating point of a
power system is calculated [36]. For this purpose, the power flow equation line-
arized around the operating point is considered and given as follows:
DP J JPV Dh
¼ Ph ð13:12Þ
DQ JQh JQV DV
where ΔP is the incremental change in the bus active power, ΔQ is the incremental
change in the bus reactive power, Δθ is the incremental change in the bus voltage
angle, and ΔV is the incremental change in the bus voltage magnitude. Jpθ, JPV, JQθ,
and JQV are the Jacobian matrix elements representing the sensitivity of the power
flow to bus voltage changes.
System voltage stability is affected by both P and Q, however, at each operating
point, P can be kept constant and voltage stability can be evaluated by considering
the incremental relationship between Q and V. If the active power P is kept constant
in (13.1), then DP ¼ 0 and (13.12) becomes,
DQ ¼ JR DV ð13:13Þ
The power network modes can be defined by the eigenvalues and eigenvectors
of JR which can be written as
JR ¼ n K g ð13:15Þ
13 Optimal Placement and Sizing of STATCOM … 449
where n is the right eigenvector matrix of JR, g is the left eigenvector matrix of JR,
and K is the diagonal eigenvalue matrix of JR.
The inverse of JR is then given by,
DV ¼ ðn K1 gÞ DQ ð13:17Þ
or
X ðni gÞ
DV ¼ i
DQ ð13:18Þ
i
ki
where ki is the ith eigenvalue, ni is the ith column right eigenvector of JR, and gi is
the ith row left eigenvector of JR. ki , ni , and gi define the ith mode of the system.
The ith modal reactive power variation is given by,
DQmi ¼ ji ni ð13:19Þ
From (13.21), the stability of mode i with respect to reactive power changes is
defined by the modal eigenvalue, ki . Large values of ki suggest small changes in the
modal voltage for reactive power changes. As the system is stressed, the value of ki
becomes smaller, and the modal voltage becomes weaker. If the magnitude of ki is
equal to zero, the corresponding modal voltage collapses because it undergoes an
infinite change for a finite reactive power change. A system is therefore defined as
voltage stable if all the eigenvalues of JR are positive. The bifurcation or voltage
stability limit is reached when at least one eigenvalue reaches zero, i.e., when one or
more modal voltages collapse. If any of the eigenvalues are negative, the system is
unstable. The magnitude of the eigenvalues provides a relative measure of the
proximity of the system to voltage instability [36, 37].
The left and right eigenvectors corresponding to the critical modes in the system
can provide information concerning the mechanism of voltage instability by
450 R. Sirjani
identifying the elements involved in these modes. The bus participation factor that
measures the participation of the kth bus in the ith mode can be defined as
X
n X
n X
n
Ploss ¼ Rl Il2 ¼ ½Vi2 þ Vj2 2Vi Vj cosðhi hj ÞYij cos uij ð13:23Þ
l¼1 l¼1 j¼1;i6¼j
where n is the number of lines, Rl is the resistance of line l, Il is the current through
line l, Vi and θi are the voltage magnitude and angle at node i, respectively, and Yij
and φij are the magnitude and angle of the line admittance, respectively.
Voltage deviation: The voltage improvement index of a power system is defined
as the deviation from unity voltage magnitude at a bus. Thus, for a given system,
the voltage improvement index is given by [38]:
vffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
u n
uX Viref Vi 2
Lv ¼ t ð13:24Þ
i¼1
Viref
where n is the number of buses, Viref is the reference voltage at bus i, and Vi is the
actual voltage at bus i.
Voltage stability margin: From the voltage stability viewpoint, critical modes
with the lowest eigenvalues are considered very important. The minimum eigen-
value should be increased to maximize the voltage stability margin [37].
13 Optimal Placement and Sizing of STATCOM … 451
Total injected reactive power: The total injected reactive power of VAr com-
pensator is given by [5]:
X
ns
QST ¼ Qj ð13:25Þ
j¼1
where ns is the number of VAr compensators, and Qj is the injected reactive power
of the VAr compensators.
Investment cost: Shunt VAr compensators are expensive devices and therefore
the investment cost for installing such controllers must be considered to justify the
economic viability of the devices. The total cost also depends on the size of fixed
and controlled portion of the shunt controllers. The FACTS equipment cost rep-
resent only half of the total FACTS project cost. Other costs like civil works,
installation, commissioning, insurance, engineering and project management con-
stitute the other half of the FACTS project cost.
The objective of using shunt VAr compensator is to control system variables
such as the active and reactive line power flows and bus voltages, and therefore the
following constraints are considered:
Power flow balance equations: The balance of active and reactive powers must be
satisfied at each bus. Power balance with respect to a bus can be formulated as [38] :
X
n
PGi PLi ¼ Vi ½Vj ½G0ij cosðdi dj Þ þ B0ij sinðdi dj Þ ð13:26Þ
j¼1
X
n
QGi QLi ¼ Vi ½Vj ½G0ij sinðdi dj Þ B0ij sinðdi dj Þ ð13:27Þ
j¼1
where PGi and QGi are the generated active and reactive powers and PLi and QLi are
the load active and reactive powers at node i. The conductance G′ik and the sus-
ceptance B′ik represent the real and imaginary components of element Y′ij of the
[Y′nn] matrix, which are obtained by modifying the initial nodal admittance matrix.
Power flow limit: The apparent power that is transmitted through a branch l must
not exceed its limiting value, Sl max, which represents the thermal limit of a line or
transformer in steady-state operation:
Sl Sl max ð13:28Þ
Bus voltage limits: For several reasons, such as stability and power quality, the bus
voltages must be maintained within limits around its nominal value which is given by
The fitness function for solving the optimal sizing of VAr compensator problem
is calculated using the objective functions described in Sect. 13.3.3. The constraints
of this problem do not explicitly contain the variables. Therefore, the effect of the
constraints must be included in the fitness function value. The constraints are
separately checked, and the violations are handled using a penalty function
approach. Incorporating all of the constraints in the same mathematical function is
impossible because the three objectives are different. Thus, an overall fitness
function, in which each objective function is normalized with respect to the base
system without a VAr compensator, is considered. This fitness function is given by,
Ploss Lv kCrticalðbaseÞ Costshunt
Minff ðxÞg ¼ Min x1 P þ x2 P þ x3 þ x4
DLossbase DVbase kCritical CostMax
)
Xnr X
n X
n
v1 : bali v2 : thermalk v3 : voltagek
i¼1 k¼1 k¼1
ð13:30Þ
Subject to:
x1 þ x2 þ x3 þ x4 ¼ 1
ð13:31Þ
0\x1 ; x2 ; x3 ; x4 \1
where Ploss, Lv, λCritical, and Costshunt are the total active power loss, voltage
deviation index, smallest eigenvalue, and total VAr compensator cost, respectively.
ω1, ω2, ω3, and ω4 are the coefficients of the corresponding objective functions,
P
P DLossbase is the total active power loss in the network of the base system,
Vbase is the total voltage deviation of the base system, λCritical(base) is the smallest
eigenvalue of the base case, and CostMax is the maximum cost.
In Eq. (13.30), the power loss as well as voltage deviation should be minimized
and the base case values are written in denominator whereas, for voltage stability
enhancement the eigenvalue should be maximized and the critical eigenvalue at
base case is written in numerator.
The bali element in (13.30) is a factor equal to 0 if the power balance constraint
at bus i is not violated; otherwise, bali is equal to 1. The sum of these violations
represents the total number of buses in the network that do not follow constraints
(13.26) and (13.27). This sum is multiplied by a penalty factor that increases the
fitness function to an unacceptable value, which results in an infeasible solution
that must be discarded. The second and third sums in the fitness function represent
the total number of violations of constraints (13.28) and (13.29), respectively, and
are also multiplied by penalty factors. The last three sums in this fitness function are
the measures of infeasibility for each candidate solution. The penalty factors used in
this study are χ1, χ2, and χ3, and each is set to a value equals to 100.
STATCOM is an expensive device and therefore optimum placement and sizing
of only one STATCOM in a transmission system is considered. For calculating the
13 Optimal Placement and Sizing of STATCOM … 453
cost of STATCOM there is no specific equation like the SVC [5]. Hence, the fourth
objective function component in Eq. (13.30) has been defined to having the min-
imum possible STATCOM sizes regarding to the control of STATCOM, instead of
considering the total STATCOM cost [5]. Since only one STATCOM has been
considered, it is reasonable that:
CostST QST
ffi ð13:32Þ
CostMAX QSTmax
|fflfflfflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflfflfflffl}
For One STATCOM
where QST is the STATCOM size and QSTmax is the maximum possible STATCOM
size.
Thus, the fitness function in Eq. (13.30) has been redefined by considering
STATCOM size. The new fitness function is given by
Ploss Lv kCrticalðbaseÞ QST
MinffSTATCOM ðxÞg ¼ Min x1 P þ x2 P þ x3 þ x4
DLossbase DVbase kCritical QSTmax
)
Xnr X
n X
n
v1 : bali v2 : thermalk v3 : voltagek
i¼1 k¼1 k¼1
ð13:33Þ
Minimize F ð xÞ subject to xi 2 Xi ; i ¼ 1; 2; 3; . . . N:
where F(x) is the objective function, x is the set of design variables (xi), Xi is the set
of the range of possible values for each design variable (Lxi < Xi < Uxi) and N is the
number of design variables. The following HS algorithm parameters are also
specified: the harmony memory size (HMS), or number of solution vectors in the
harmony memory; the harmony memory considering rate (HMCR); the pitch
adjusting rate (PAR); the number of decision variables (N); the number of impro-
visations (NI) and the stopping criterion.
Step 2: Initialisation of the Harmony Memory
The harmony memory (HM) matrix shown in Eq. (13.34) is filled with HMS
randomly generated solution vectors and sorted by the values of the objective
function f(x).
2 3
x11 x12 ... x1N1 x1N ) f ðxð1Þ Þ
6 x2 x22 ... x2N1 x2N 7) f ðxð2Þ Þ
6 1 7
6 7
6 7
HM ¼ 6
6 7
7 ð13:34Þ
6 7
6 7
4 xHMS1 x1HMS1 ... HMS1
xN1 xNHMS1 5
) f ðxðHMS1Þ Þ
1
xHMS
1 xHMS
1 ... xHMS
N1 xHMS
N ) f ðxðHMSÞ Þ
• Pitch Adjustment: Every component of the new harmony vector x′ = (x1′, x2′,…
xn′) is examined to determine whether it should be pitch-adjusted. After the
value xi′ is randomly picked from the HM in the memory consideration process,
it can be further adjusted by adding a certain amount to the value with proba-
bility PAR. This operation uses the PAR parameter, which is the probability of
pitch adjustment, given as follows:
Yes with probablity PAR
x0i ð13:36Þ
No with probablity ð1 PARÞ
The value of (1-PAR) sets the probability of doing nothing. If the pitch
adjustment decision for xi′ is yes, then xi′ is replaced as follows:
ii. The GHS algorithm modifies the improvisation step of the HS algorithm and
this modification is represented by the following pseudo code.
Here, “best” and “worst” are the indexes of the global best harmony and the
worst harmony in HM, respectively. r1i, r2i and r3i are all the uniformly generated
random numbers in [0, 1]. r1i is used for position updating, r2i determines whether
the GHS should carry out genetic mutation, and r3i is used for genetic mutation.
Figure 13.3 illustrates the principle of position updating [40].
stepi = |xbest
i − xworst
i | is defined as adaptive step of the ith decision variable. The
region between P and R is defined as trust region for the ith decision variable. The
trust region is actually a region near the global best harmony. In the early stage of
optimization, all solution vectors are sporadic in solution space, so most trust
regions are wide, which is beneficial to the global search of the GHS; while in the
late stage of optimization, all non-best solution vectors are inclined to move to the
global best solution vector, so most solution vectors are close to each other. Here,
most trust regions are narrow, which is beneficial to the local search of the GHS
algorithm. A reasonable design for adaptive step can guarantee that the proposed
algorithm has strong global search ability in the early stage of optimization, and has
strong local search ability in the late stage of optimization. Dynamically adjusted
stepi keeps a balance between the global search and the local search [40, 41]. As for
genetic mutation operation with a small probability, it is carried out for the worst
harmony of HM after updating position, so as to enhance the capacity of escaping
from the local optimum for the proposed algorithm.
iii. The GHS algorithm replaces the worst harmony xworst in HM with the new
harmony x′ even if x′ is worse than xworst.
For clarity, the GHS algorithm is described in terms of a flow chart as shown in
Fig. 13.4.
In modified improvisation steps, adaptive step and trust region are defined for the
GHS, and according to these two factors, a novel position updating equation is
designed to make the worst harmony of harmony memory move to the global best
harmony in each iteration. Using position updating equation can accelerate the
convergence rate of the GHS, however, it also accelerates the premature conver-
gence of the GHS and make it get into the local optimum. To overcome these
disadvantages, genetic mutation with a small probability is introduced in the GHS
algorithm [40, 41].
The procedures for implementing the GHS algorithm in the optimal placement and
sizing of STATCOM are described follows:
i. Input the system parameters such as bus, branch, and generator data.
ii. Form the Jacobian matrix and calculate the eigenvalues for the base case.
iii. Calculate the eigenvectors and determine bus participation factors for the
smallest eigenvalue.
iv. Determine buses with large participation factors and consider these buses as
possible locations for STATCOM installation.
v. Randomly add one STATCOM for reactive power compensation at the bus
among suitable buses. Each STATCOM set is considered a harmony vector.
The HM arrays are randomly initialized using (13.34). The number of col-
umns in the HM is equal to the number of buses in the test system. The
optimal parameters of the test system, xLi and xUi, are assumed to have
minimum and maximum values of STATCOM in MVar, respectively. The
HMS value is assumed to be 10.
vi. Improvise a new harmony through position updating and genetic mutation.
In this step, the genetic mutation probability is assumed as pm = 0.2.
vii. Run the power flow program to calculate power loss, voltage deviation, and
the eigenvalues.
viii. Calculate the objective function using (13.30).
ix. Replace the worst harmony in HM with the new harmony.
x. Evaluate whether the stopping criterion (maximum generation ≥5,000) is
satisfied. If not, return to step (vi) and repeat the procedure.
xi. Determine the optimal VAr compensator set (i.e., the best harmony) that
provides maximum power loss reduction, minimum voltage deviation,
maximum voltage satiability enhancement and minimum STATCOM size.
458 R. Sirjani
Start
i=1
xR = 2xiworst - xibest
No
No
i= i+1
xiNew= xiworst+r1i (xR -xiworst)
No
No
Replace the worst harmony (xiworst) in HM with the new harmony (xinew)
even if xinew is worse than xiworst
Is stopping criterion
satisfied ?
Yes
End
Start
Find the Most Critical Buses with Large Participation Factors Using
Modal Analysis Method
Randomly Add One STATCOM at the Bus Among the Suitable Buses
and Initialize the HM
K=1
Improvise a new harmony using the position updating and genetic mutation
K=K+1
Replace the Worst Harmony in HM with the New Harmony
No K ≥ K Max
Yes
End
Fig. 13.5 Procedures used in solving the optimal STATCOM placement and sizing problem
Figure 13.5 shows a schematic diagram of the procedures used in solving the
optimal STATCOM placement and sizing problem using modal analysis and the
GHS algorithm.
460 R. Sirjani
The smallest eigenvalue for this system at base case is found to be 0.2344. The bus
participation factor values for the smallest eigenvalue of the reduced Jacobian
matrix are calculated for all load buses and sorted as shown in Table 13.1.
Considering the results of modal analysis shown in Table 13.1, the ten buses
with high participation factor values are considered suitable for STATCOM
installation. The identified ten buses are buses 24, 25, 30, 31, 32, 33, 34, 35, 36 and
40. Table 13.2 shows the place and size of STATCOM using the five optimization
techniques. The results obtained from the IHS and GHS algorithms are compared
with results obtained using the GA, PSO and conventional HS algorithm.
Table 13.2 also shows the total power loss, voltage deviation and the smallest
eigenvalue after the installation of the STATCOM. This study is performed with the
restriction that the injected Q does not exceed 50 MVar.
Table 13.2 shows that STATCOM placement using the GHS algorithm not only
produces greater voltage stability enhancement and greater reductions in power loss
and voltage deviation than GA, PSO and conventional HS algorithm, but it also
gives the lowest fitness function value compared to other optimization techniques. It
is also observed that the result of STATCOM placement using the IHS algorithm in
terms of power loss reduction, voltage deviation minimization and voltage stability
enhancement is comparable to the GHS algorithm. However, the STATCOM size
found by the GHS algorithm is lower than that found by the IHS algorithm.
The smallest eigenvalue of the IEEE 118-bus test system at the base case which
is without STATCOM installation is calculated as 3.9425. The bus participation
Table 13.1 The participation factor values of all load buses in the IEEE 57-bus test system
Bus Participation Bus Participation Bus Participation
no. factor no. factor no. factor
31 0.1833 21 0.0067 52 0.0005
33 0.1744 22 0.0067 14 0.0004
32 0.1704 38 0.0057 53 0.0004
30 0.133 20 0.0043 11 0.0002
25 0.1004 44 0.0041 13 0.0002
34 0.0306 27 0.0038 15 0.0002
35 0.0229 41 0.0038 18 0.0002
40 0.0177 48 0.0037 51 0.0002
36 0.0176 47 0.0031 7 0.0001
24 0.0165 19 0.0024 10 0.0001
39 0.0142 49 0.0024 54 0.0001
37 0.014 28 0.0015 4 0
26 0.0138 46 0.0015 5 0
57 0.0114 50 0.0014 16 0
56 0.0092 45 0.0013 17 0
23 0.0072 43 0.0008 55 0
42 0.0070 29 0.0006
462 R. Sirjani
Table 13.2 A comparison of different optimization techniques for optimal placement and sizing
of STATCOM in the IEEE 57-bus test system
Objective function Base case GA PSO HS IHS GHS
Optimum location (Bus no.) – 33 32 31 31 31
Size of STATCOM (MVar) – 17.44 15.35 12.87 12.41 12.37
Total power losses (MW) 28.41 28.19 28.02 27.88 27.76 27.74
Total voltage deviation 0.265 0.209 0.215 0.181 0.178 0.177
Smallest eigenvalue 0.234 0.302 0.261 0.291 0.314 0.322
Fitness function value 1.000 0.802 0.839 0.765 0.743 0.736
factor values for the smallest eigenvalue of the reduced Jacobian matrix are cal-
culated for all load buses. Among all load buses the bus participation factor values
of six buses are sorted and shown in Table 13.3. The bus participation factor values
of other load buses are found to be 0. It means that only six buses have participation
to the critical mode. From the table, the buses with participation factors correspond
to the critical system buses which are at buses 20, 21, 22, 23, 37 and 38. These
buses are considered as suitable locations for STATCOM installation.
The proposed IHS and GHS algorithms were implemented to determine the
optimal location and size of only one STATCOM in the IEEE 118-bus test system.
The coefficient values for the objective functions are assumed to be the same as
those in the IEEE 57-bus test system. This study is performed with the restriction
that the injected Q does not exceed 120 MVar. As shown in Table 13.3, the most
critical buses in the system are buses 20, 21, 22, 23, 37 and 38 and these buses are
considered as candidate location for STATCOM installation.
Table 13.4 shows a comparison of the optimal STATCOM placement results of
the IHS and GHS algorithms with the other optimization techniques in terms of
total power loss, voltage deviation, smallest eigenvalue and size of STATCOM.
The results in the table show that the GHS algorithm gives the lowest fitness
function value and the greatest reduction in terms of power loss and voltage
deviation as compared to GA, PSO, conventional HS and IHS algorithms.
The convergence characteristics of the different optimization techniques for the
optimal placement and sizing of STATCOM in the IEEE 118-bus test system are
shown in Fig. 13.7. From the figure, the GHS algorithm converges faster compared
with the other optimization techniques.
Table 13.4 A comparison of different optimization techniques in optimal placement and sizing of
STATCOM in the IEEE 118-bus test system
Objective function Base case GA PSO HS IHS GHS
Optimum location – 20 22 21 21 21
(Bus no.)
Size of STATCOM – 69.11 71.39 64.11 64.17 64.23
(MVar)
Total power losses (MW) 132.86 132.57 132.56 131.52 131.43 131.23
Total voltage deviation 0.294 0.291 0.290 0.289 0.287 0.285
Smallest eigenvalue 3.9425 5.108 5.166 5.282 5.284 5.292
Fitness function value 1.000 0.875 0.865 0.857 0.853 0.845
Fig. 13.7 Convergence characteristics of different optimization techniques in the IEEE 118-bus
test system
Table 13.5 Accuracy of different optimization techniques for the optimal STATCOM placement
and sizing in the IEEE 118-bus test system
Fitness function value GA PSO HS IHS GHS
Minimum 0.8583 0.8605 0.8567 0.8529 0.8451
Maximum 0.9163 0.8661 0.8581 0.8532 0.8451
Mean 0.8753 0.8651 0.8572 0.8531 0.8451
Standard deviation 5.80e−04 5.61e−05 1.42e−05 3.78e−06 3.47e−08
The minimum, maximum, mean and standard deviation of the fitness function
values from 50 executions of the GA, PSO, HS, IHS and GHS algorithm are shown
in Table 13.5. From the table, it is noted that the GHS algorithm gives the lowest
fitness function values and lowest standard deviation values compared to other
optimization techniques. This proves that the proposed GHS algorithm for solving
the optimal placement and sizing of STATCOM in the IEEE 118-bus test system is
more accurate than GA, PSO, conventional HS and IHS algorithms.
464 R. Sirjani
Appendix 1
Tables 13.6–13.8
Appendix 2
Fig. 13.8 Network diagram for the IEEE 118-bus test system
13
13 L 34 16 53 L 23 11 93 L 12 7
14 L 14 1 54 G 113 32 94 L 30 16
15 G 90 30 55 G 63 22 95 L 42 31
16 L 25 10 56 G 84 18 96 L 38 15
17 L 11 3 57 L 12 3 97 L 15 9
18 G 60 34 58 L 12 3 98 L 34 8
19 G 45 25 59 G 277 113 99 G 42 0
20 L 18 3 60 L 78 3 100 G 37 18
21 L 14 8 61 G 0 0 101 L 22 15
22 L 10 5 62 G 77 14 102 L 5 3
23 L 7 3 63 L 0 0 103 G 23 16
(continued)
467
Table 13.9 (continued)
468
References
FACTS devices. In: 11th international conference on optimization of Electrical and Electronic
equipment, pp 209–214
23. Sundareswaran K, Bharathram P, Siddharth M, Vaishnavi G, Shrivastava NA, Sarma H (2009)
Voltage profile enhancement through optimal placement of FACTS devices using queen-bee-
assisted GA. In: Third international conference on power systems, pp 1–5
24. Bina TM, Siahbidi JR, Kanzi K (2005) Application of averaging technique to the power
system optimum placement and sizing of static compensators. In: The 7th international power
engineering conference, pp 1–6
25. Samimi A, Golkar MA (2011) A novel method for optimal placement of STATCOM in
distribution networks using sensitivity analysis by DIgSILENT software. Asia-Pacific power
and energy Engineering conference, pp 1–5
26. Del-Valle Y, Hernandez JC, Venayagamoorthy GK, Harley RG (2006) Optimal STATCOM
sizing and placement using particle swarm optimization. In: Proceedings of the IEEE
transmission and distribution conference and exposition Latin America, pp 1–6
27. Hernandez JC, Del-Valle Y, Venayagamoorthy GK, Harley RG (2006) Optimal allocation of a
STATCOM in a 45 bus section of the Brazilian power system using particle swarm
optimization. In: Proceedings of the IEEE swarm intelligence symposium, pp 69–75
28. Panda S, Padhy NP (2008) Optimal location and controller design of STATCOM for power
system stability improvement using PSO. J Franklin Inst 345:166–181
29. Del-Valle Y, Venayagamoorthy GK, Harley RG (2009) Comparison of enhanced-PSO and
classical optimization methods: a case study for STATCOM placement. In: Proceedings of the
IEEE 15th international conference on intelligent system applications to power systems, pp 1–7
30. Varshney S, Srivastava L, Pandit M (2011) Comparison of PSO models for optimal placement
and sizing of STATCOM. In: 2nd international conference on sustainable energy and
intelligent system, pp 346–351
31. Lee K, Geem Z (2005) A new meta-heuristic algorithm for continuous engineering
optimization: harmony search theory and practice. Comput Methods Appl Mech Eng 194
(2005):3902–3933
32. Sirjani R, Mohamed A, Shareef H (2012) Optimal placement and sizing of static synchronous
compensators in power systems using improved harmony search algorithm. Int Rev Electr Eng
7(2):4183
33. Majumdar S, Chakraborty AK, Chattopadhyay PK (2009) Active power loss minimization
with FACTS devices using SA/PSO techniques. In: 3rd international conference on power
systems, pp 1–5
34. Acha E, Fuerte-Esquivel CR, Ambriz-Perez H, Angeles-Camacho C (2004) FACTS modelling
and simulation in power network. Wiley, New York
35. Zhang XP, Rehtanz C, Pal B (2006) Flexible AC transmission systems modelling and control.
Springer, Berlin
36. Kundur P (1994) Power system stability and control. McGraw-Hill Inc
37. Sharma C, Ganness MG (2007) Determination of power system voltage stability using modal
analysis. IEEE Int Conf Power Eng, Energy Electri Drives, POWERENG 2007:381–387
38. Pisica I, Bulac C, Toma L, Eremia M (2009) Optimal SVC placement in electric power
systems using a genetic algorithms based method. In: IEEE Bucharest power tech conference,
pp 1–6
39. Kazemi A, Parizad A, Baghaee H (2009) On the use of harmony search algorithm in optimal
placement of FACTS devices to improve power system security. In: Proceedings of the IEEE
EUROCON, pp 570–576
40. Zou D, Gao L, Li S, Wu J, Wang X (2010) A novel global harmony search algorithm for task
assignment problem. J Syst Softw 83(10):1678–1688
41. Zou D, Gao L, Wu J, Li S, Li Y (2010) A novel global harmony search algorithm for
reliability problems. Comput Ind Eng 58(2):307–316
42. Power Systems Test Case Archive, Uni. of Washington, http://www.ee.washington.edu/
research/pstca/