Model CR Commercial Riser: Table A
Model CR Commercial Riser: Table A
Model CR Commercial Riser: Table A
Features
• Cast stainless steel body for 1-1/2” models and 2” threaded
model
• Schedule 10 welded body for 2” - 8” grooved versions
• Optional schedule 40 manifold for 2” - 4” sizes
• Approved for vertical or horizontal installation
Product Description
The Reliable Model CR Commercial Riser arrives factory
assembled with water flow switch, pressure gauge, and main
drain for a cost-effective system riser or floor control assembly.
The Model CR is cULus listed (VEOY.EX5980) and FM approved
as a unit. The main drain is available with a ball valve or Reliable
3” (80mm) welded Commercial Riser
Test and Drain valve, which is available with a wide selection of
w/ 175psi Pressure Relief Kit and Test & Drain Valve (K5.6)
test orifice K-factor choices. An optional pressure relief valve kit,
available in 175, 185, 210, 260, and 310 psi (12, 13, 14, 18, and
21 bar) rating, is also available.
*Note: K-factor must be equal to or less than the K-factor of the smallest K-factor installed on the sprinkler system. For sprinkler sys-
tems where the smallest K-factor sprinkler on the system is greater than the largest available valve K-factor, use any valve K-factor that
will provide a minimum flow of 10gpm (38 lpm) as required to operate a UL Listed Waterflow Switch.
www.reliablesprinkler.com
Model CR Commercial Riser Threaded End
Assemblies (1-1/2” [40mm] & 2” [50mm]) Figure 1
Manifold A B C D E Weight
End
Pipe Size in in in in in lbs
Connection
in (mm) (mm) (mm) (mm) (mm) (mm) (kg)
12-
1-1/2 10-1/2 3 5-1/2 8-1/4 8.3
1/8
(40) (267) (80) (140) (210) (3.8)
Threaded (308)
Ends
(See Fig. 1) 12-
2 10-3/4 3-1/4 5-3/4 8-1/4 9.1
1/8
(50) (273) (83) (146) (210) (4.1)
(308)
Manifold A B C D E Weight
End
Pipe Size in in in in in lbs
Connection
in (mm) (mm) (mm) (mm) (mm) (mm) (kg)
12-
1-1/2 14-1/4 3 5-1/2 8-1/4 8.3
1/8
Threaded (40) (362) (80) (140) (210) (3.8)
(308)
Ends
(See Fig. 1) 12-
2 14-1/2 3-1/4 5-3/4 8-1/4 9.1
1/8
(50) (368) (83) (146) (210) (4.1)
(308)
Maintenance
The owner is responsible for maintaining the fire protection system
in proper operating condition. Any system maintenance or testing
that involves placing a system out of service may eliminate the fire
protection that is provided by the fire protection system. Notify any
required authorities having jurisdiction and implement appropriate
precautions prior to proceeding.
Guarantee
For Reliable Automatic Sprinkler, Co., Inc. guarantee, terms, and
conditions, visit www.reliablesprinkler.com.
Ordering Information
Specify:
Notes:
1. All Model CR Commercial Riser Assemblies come with a 300
psi (20.7 bar) UL Listed and FM Approved pressure gauge
for 175 psi (12.1 bar) applications. If the Model CR Com-
mercial Riser Assembly is to be installed in a higher pressure
application, please purchase a 600 psi (41.4 bar) (P/N
98248005) pressure gauge. This gauge may or may not be
UL Listed and/or FM Approved at the time of purchase.
2. Unless specified at the time of ordering, pressure relief kits
are installed at the factory.
6A X X 0C P Y Y Z
Notes:
1. 1-1/2” and 2” manifolds have a 1” threaded drain outlet.
2. 2-1/2” and 3” manifolds have a 1-1/4” grooved outlet for Test & Drain valve or a 1-1/4” threaded outlet for ball valve drain.
3. 4”, 6”, and 8” manifolds have a 2” grooved outlet for Test & Drain valve or 2” threaded outlet for ball valve drain.
P/N 9999970536