DAR Stair Case Pressurization
DAR Stair Case Pressurization
Pressure Level : 25 Pa
1- Air volume required when all doors are closed : Q1= 0.827 x AE x P1/n
Although the effective leakage area is known, there are other leaks we are not aware of.
To account for these leaks, Q is increased by 50%, hence:
Minimum Number of Opened Doors = main escape doors + 10% of remaining straiwell doors
= 1 + 1
Open door area = Area of escape doors + 50% of the area of the other doors
= 1.89 + 0.945
= 2.84 m 2
Q2 = A x V => Q2 = 5.67 m3 / s
3- Total Air Supplied by the fan :
Pressure Level : 25 Pa
1- Air volume required when all doors are closed : Q1= 0.827 x AE x P1/n
Although the effective leakage area is known, there are other leaks we are not aware of.
To account for these leaks, Q is increased by 50%, hence:
Minimum Number of Opened Doors = main escape doors + 10% of remaining straiwell doors
= 1 + 1
Open door area = Area of escape doors + 50% of the area of the other doors
= 1.89 + 0.945
= 2.84 m 2
Q2 = A x V => Q2 = 5.67 m3 / s
3- Total Air Supplied by the fan :
Pressure Level : 25 Pa
1- Air volume required when all doors are closed : Q1= 0.827 x AE x P1/n
Although the effective leakage area is known, there are other leaks we are not aware of.
To account for these leaks, Q is increased by 50%, hence:
Minimum Number of Opened Doors = main escape doors + 10% of remaining straiwell doors
= 1 + 1
Open door area = Area of escape doors + 50% of the area of the other doors
= 1.89 + 0.945
= 2.84 m 2
Q2 = A x V => Q2 = 5.67 m3 / s
3- Total Air Supplied by the fan :
Approved by:
450 x 400
3840 lps
Four
400 x 400
3200 lps
Three
400 x 350
2560 lps
NTV
350 x 350
1920 lps
NTV
350 x 250
1280 lps
Mezzanine
350 x 150
640 lps
Ground
SR 500x150
640 lps Typical
Data
Double Leaf Doors with or without Central Rebate 2 m x 1.6 m 9.2 0.03
7.2.1.4.5
The forces required to fully open any door manually in a means of egress shall not exceed 15 lbf (67 N) to release
the latch, 30 lbf (133 N) to set the door in motion, and 15 lbf (67 N) to open the door to the minimum required width.
Opening forces for interior side-hinged or pivoted-swinging doors without closers shall not exceed 5 lbf (22 N).
These forces shall be applied at the latch stile.
Page 14
Design calculation sheet
Project no: Date: Sheet no.: of Computed by:
Approved by: