GENERAL DATA
Model DAU/O100M
Version
Frame
Primary circuit type DIRECT EXPANSION AIR COOLED
No. Circuits N° 2
Refrigerant R410A

MAIN CIRCUIT

DESIGN CONDITIONS
Dry bulb temperature °C 24.0
Relative humidity % 50
Altitude m 0
Air flow m³/h 28000
ESP External Static Pressure Pa 20
Outdoor air temperature °C 35.0
Coil working pressure -

PERFORMANCE AT DESIGNED CONDITIONS


Total cooling capacity gross kW 103
Sensible cooling capacity gross kW 96.4
Net cooling capacity kW 96.2
Net sensible cooling capacity kW 89.6
SHR 0.94
EER (Indoor unit) kW/kW 3.34
Total power input (Comp.+fans) kW 30.8
Leaving air temperature °C 13.8
Leaving air relative humidity % 92
Effective heat exchange area -

COMPRESSORS
Compressor type SCROLL
Compressors nr. N° 2
Compressors power absorption kW 24.0

FANS
Fans type EC fan
Quantity N° 2
Air flow m³/h 28000
Fans power input kW 6.80
SPF (Specific Power Factor) W / l/s 0.87

ACCESSORIES

ELECTRICAL HEATER
Heater description Tubular-Finned 18kW
Quantity N° 1
Steps N° 3
Eletrical power abs. kW 18.0
Max absorbed current (FLA) A 27.4
Power supply V/ph/Hz 380/3/50

HUMIDIFIER
Humidifier type Steam Humidifier 8kg/h
Quantity N° 1
Capacity kg/h 8.0
Elettrical power abs. kW 6.00
Max absorbed current (FLA) A 9.12
Power supply V/ph/Hz 380/3/50

FILTERS
Accessory filter type COARSE 60% (ISO EN 16890)

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.3.0
TECHNICAL SELECTION Page 2 / 3

DAU/O100M
Software version: ELCA World 1.5.1.0
Database version: 1.6.1.0
User: Budianto Wun
Print data: 03/02/2021 11:10

NOISE DATA
Spectrum Hz 63 125 250 500 1000 2000 4000 8000 Tot
dB dB dB dB dB dB dB dB dB(A)
Sound Power 72 81 82 79 80 79 74 66 85
Sound Pressure 55 64 65 62 63 62 57 49 68
Distance m 1

Note
Average sound pressure level, at 1 m distance, unit in a free field on a reflective surface according
Note to ISO3744. Non-binding value obtained from the sound power level.

WEIGHT & DIMENSIONS


A mm 2180
B mm 990
H mm 1990
Weight kg 700

ELECTRICAL DATA (refer to indoor unit)


Power supply V/ph/Hz 380/3+N/50
Max Electrical power absorbed (FLI) kW 47.2
Max absorbed current (FLA) A 87.9
Max inrush current (SA) A 228
Power input (OI) kW 30.8

REMOTE CONDENSER

MAIN CIRCUIT

REMOTE CONDENSER
Code C74
Quantity N° 2
Version STD
Circuits N° 1
Outdoor air temperature °C 35.0
Condensing temperature °C 47.8
Air flow m³/h 26000
Rejection capacity kW 126

FANS
Fans power input kW 1.77
Quantity N° 3
Project pressure Pa 0

WEIGHT & DIMENSIONS


Dimension A mm 3488
Dimension B mm 1108
Dimension H mm 830
Weight kg 180
Packaged dimension A mm 3823
Packaged dimension B mm 1130
Packaged dimension H mm 1405
Package weight kg 242

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.3.0
TECHNICAL SELECTION Page 3 / 3

DAU/O100M
Software version: ELCA World 1.5.1.0
Database version: 1.6.1.0
User: Budianto Wun
Print data: 03/02/2021 11:10

ELECTRICAL DATA
Power supply V/ph/Hz 220/1/50
Power input (OI) kW 1.77
Total power input kW 1.90
Max absorbed current A 9.00

AIR SUPPLY REMOTE CONDENSER


Supply air direction None air delivery selected

NOISE DATA
Spectrum Hz 63 125 250 500 1000 2000 4000 8000 Tot
dB dB dB dB dB dB dB dB dB(A)
Sound Power - - - - - - - - -
Sound Pressure - - - - - - - - -
Distance m 1

Note
Average sound pressure level, at 1 m distance, unit in a free field on a reflective surface according
Note to ISO3744. Non-binding value obtained from the sound power level.