Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Technical Selection

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

TECHNICAL SELECTION

Software version: ELCA World v. 1.7.6.0


User: Yakir Weizman
Database version: 1.8.6.0
Print data:12/02/2023 11:11

TECHNICAL SELECTION
NECS-Y /B 0452T
Chiller, air source for outdoor installation

Code NECS-Y /B 0452T


Version B
Size 0452T
Power supply V/ph/Hz 400/3+N/50
ELCA_Engine ver.4.7.6.0
INDEX
Data Book
NECS-Y 0202T - 0512T_202302_EN R410A

1 TECHNICAL SELECTION pg.3

1.1 Performance at design conditions pg.3

1.2 Exchangers pg.3

1.3 Fans pg.4

1.4 Compressors pg.4

1.5 Noise data pg.5

1.6 Accessories pg.5

1.7 Weight & dimensions pg.7

2
1 TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS

1.1 PERFORMANCE AT DESIGN CONDITIONS


RUNNING CONDITIONS
HEAT EXCHANGER USER SIDE
Fluid type WATER
Glycol % 0
Fouling factor h ft2 °F /Btu 0.00000
Fluid inlet temperature (cooling mode) °C 12.00
Fluid outlet temperature (cooling mode) °C 7.00
Water flow m³/h 19.92
Pressure drop at the heat exchanger kPa 17.7
Available unit head kPa 204
OUTDOOR CONDITION
Air temperature (cooling mode) °C 35.0

COOLING (Gross value)


Cooling capacity kW 115.7
Compressor power input kW 37.67
Fans power input (cooling mode) kW 2.00
Total power input kW 39.67
EER kW/kW 2.91
ESEER CALCULATED kW/kW 3.70

1.2 EXCHANGERS
HEAT EXCHANGER USER SIDE

Typology SHELL&TUBE
Quantity N° 1
Type of connections [B1] - Male threaded pipe (EN 10226 - R: external taper thread)
Diameter of connections 2"1/2
Min flow m³/h 12.80
Max flow m³/h 32.30
Heat exchanger water content l 37.5
Minimum water content admitted in the plant l 280

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

3
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS

1.3 FANS
Fans type AXIAL AC
Quantity N° 8
Total fans power input kW 2.00
F.L.I. kW 8x0.25
F.L.A. A 8x1.1

COOLING

Total fans power input kW 2.00


Air flow m³/s 9.88
Available static pressure Pa 0

1.4 COMPRESSORS
COMPRESSORS
Compressor type SCROLL
Compressors nr. N° 2
No. Circuits N° 2
Number of capacity steps N° 2
Min. capacity step % 50
Regulation STEPS
Oil charge kg 11.0
F.L.I. - Max absorbed power kW 1x22.3+1x27.4
F.L.A. - Max absorbed current A 1x36.1+1x45.8
L.R.A. - Locked rotor amperes for single compressor A 1x225+1x272

REFRIGERANT
Refrigerant R410A
Theoretical refrigerant charge kg 17.3
GWP100 value (from IPCC AR5) 1924
CO2 equivalent t 33.3

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

4
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS

1.5 NOISE DATA


SOUND DATA COLD

Frequencies Hz 63 125 250 500 1000 2000 4000 8000


Sound power (spectrum) dB 85 83 87 84 80 78 71 70
Total sound power level in cooling dB(A) 86
Sound pressure level (spectrum) dB 53 51 55 52 48 46 39 38
Total sound Pressure dB(A) 54

Note

Distance m 10
Average sound pressure level at 10 m distance, unit in a free field
on a reflective surface; non-binding value calculated from the
Note sound power level.
Sound power on the basis of measurements taken in compliance
with ISO 9614.

1.6 ACCESSORIES
HYDRONIC GROUPS

HEAT EXCHANGER USER SIDE


Accessory code 3346
Accessory description HYDRONIC KIT 2 CENTRIFUG. PUMPS 2 POLES HH
Min flow m³/h 12.80
Max flow m³/h 32.30
COOLING
Water flow m³/h 19.92
Available unit head kPa 204

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

5
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS

GRAPH OF RESIDUAL PRESSURE HEAD

DIMENSION AND ELECTRIC DATA VARIATION

FLA hydronic group A 6


FLI hydronic group kW 3.000
Additional weight kg 105
Additional length mm 0
Additional width mm 0
Additional height mm 0
Additional Sound pwr. dB(A) 0.0
Buffer tank l 0.00

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

6
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS

1.7 WEIGHT & DIMENSIONS


A mm 2745
B mm 1120
H mm 1465
Operating weight kg 1095
R1 mm 1000
R2 mm 1000
R3 mm 600
R4 mm 600

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

7
Head Ofice:
Via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
Tel (+39) 0424 509 500 - Fax (+39) 0424 509 509
www.melcohit.com