Technical Selection
Technical Selection
Technical Selection
TECHNICAL SELECTION
NECS-Y /B 0452T
Chiller, air source for outdoor installation
2
1 TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS
1.2 EXCHANGERS
HEAT EXCHANGER USER SIDE
Typology SHELL&TUBE
Quantity N° 1
Type of connections [B1] - Male threaded pipe (EN 10226 - R: external taper thread)
Diameter of connections 2"1/2
Min flow m³/h 12.80
Max flow m³/h 32.30
Heat exchanger water content l 37.5
Minimum water content admitted in the plant l 280
The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0
3
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS
1.3 FANS
Fans type AXIAL AC
Quantity N° 8
Total fans power input kW 2.00
F.L.I. kW 8x0.25
F.L.A. A 8x1.1
COOLING
1.4 COMPRESSORS
COMPRESSORS
Compressor type SCROLL
Compressors nr. N° 2
No. Circuits N° 2
Number of capacity steps N° 2
Min. capacity step % 50
Regulation STEPS
Oil charge kg 11.0
F.L.I. - Max absorbed power kW 1x22.3+1x27.4
F.L.A. - Max absorbed current A 1x36.1+1x45.8
L.R.A. - Locked rotor amperes for single compressor A 1x225+1x272
REFRIGERANT
Refrigerant R410A
Theoretical refrigerant charge kg 17.3
GWP100 value (from IPCC AR5) 1924
CO2 equivalent t 33.3
The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0
4
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS
Note
Distance m 10
Average sound pressure level at 10 m distance, unit in a free field
on a reflective surface; non-binding value calculated from the
Note sound power level.
Sound power on the basis of measurements taken in compliance
with ISO 9614.
1.6 ACCESSORIES
HYDRONIC GROUPS
The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0
5
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS
The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0
6
TECHNICAL SELECTION NECS-Y /B 0452T
Software version: ELCA World v. 1.7.6.0
Database version: 1.8.6.0
User: Yakir Weizman
Print data:12/02/2023 11:11
Calculation type:EUROPEAN GROSS
The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0
7
Head Ofice:
Via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
Tel (+39) 0424 509 500 - Fax (+39) 0424 509 509
www.melcohit.com