Design Conditions Datasheet: Unit Tag Qty Model No Net Cooling Capacity (Ton.r) Nominal Voltage Refrigerant Type

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Design Conditions Datasheet

Net Cooling
Unit Tag Qty Model No Nominal Voltage Refrigerant Type
Capacity (ton.R)
ACC-1 1 YVFA0209AOK46AAVNXO 102.7 460-3-60.0 R-134a

PIN:
YVFA0209AO K46AAVNXOX SAXLXXXX43 43XDXXXV15 4W1SXXA2BM XKXXXOXXXX XXXAX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Evaporator Data Free Cooling Data Performance Data


EWT (°F) 55.74 Free Cooling Type Open Loop EER (Btu/W∙h) 9.290
LWT (°F) 43.00 Fluid Concentration N/A IPLV.IP (Btu/W∙h) 18.29
Net Cooling Capacity
Design Flow Rate (USGPM) 205.6 0.0000 NPLV.IP (Btu/W∙h) 15.52
ASHRAE 90.1 at 50 °F (ton.R)
100% Free Cooling Ambient
Total Press. Drop (ft H2O) 2.82 32.0
Temp. * (°F)
Mechanical Mode Press. Drop
(ft H2O)
2.82 Condenser Data Physical Data
Propylene
Fluid 30 Ambient Temp. Design (°F) 94.0 Rigging Wt. (lb) 17558
Glycol (%)
Fouling Factor (h.ft².F/Btu) 0.000100 Altitude (ft) 0.000 Operating Wt. (lb) 18984
VSD Screw - Semi
Fluid Volume (USGAL) 48.08 Compressor Type Refrigerant Charge (lb) 361.6
Hermetic
Min. Flow Rate (USGPM) 200.0
Max. Flow Rate (USGPM) 700.0

Electrical Data
Circuit 1 2 3 4
Compressor kW 69.2 49.5
Compressor RLA 152 108
Fan QTY/FLA (each) 7 / 3.8 5 / 3.8

Single Point
Min. Circuit Ampacity 348
Max. Fuse / CB Rating (A) 500
Unit Short Circuit Withstand (STD) 50 [kA]
Wires Per Phase 3
Wire Range (Lug Size) #2 - 600 kcmil
Operating Condition Electrical Data
Compressor kW 118.6
Total kW 132.7

Notes:

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units
may be found in the AHRI Directory at www.ahridirectory.org.
Unit contains freeze protection fluids in the evaporator with a leaving chilled fluid temperature
above 32 DEG F [0 DEG C] and is certified when rated per the Standard with water. Auxiliary
components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included
in the compressor and fan power

Min DSD (Factory Purpose/Use only): 48 psig


Country of Origin: Monterrey, Mexico
Use Copper Conductors only
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option
selected. Calculated value is available by request.

* 100% Free Cooling Ambient Temperature is provided for comparison purposes only. For maximum efficiency, energy optimization controls may utilize
mechanical cooling below this temperature.
Minimum and maximum evaporator flow information are for full load ratings with Propylene Glycol.
Total Pressure Drop includes evaporator and free cooling heat exchangers and is to be used for pump sizing.

MLP Effective Date:6/15/2022 NewProject


Generated on2022-07-21 E.21.5.27676.0-D.94.0002(REV. v8_41.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW21.05a Page_1_of_3
Design Conditions Datasheet
Mechanical mode pressure drop includes the evaporator and factory provided pipework inside the chiller frame.
Selected full load capacity of chiller is at low end of chiller operating range. Minimum chiller unloading may be as high as 30% of full load and must be
confirmed to meet operating requirements.

MLP Effective Date:6/15/2022 NewProject


Generated on2022-07-21 E.21.5.27676.0-D.94.0002(REV. v8_41.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW21.05a Page_2_of_3
Design Conditions Datasheet

Part Load Rating Data


Unit Efficiency
Load % Ambient (°F) Capacity (ton.R) Total kW
(Btu/W∙h)
100 94.0 102.7 132.7 9.290
75 79.4 77.02 74.80 12.36
50 64.9 51.35 35.70 17.26
25 55.0 25.67 14.96 20.60

Sound Power Levels (In Accordance with AHRI 370)


Ambient 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Load % LWA
(°F) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB)
100 94.0 92 102 99 97 95 92 87 84 100
75 79.4 88 98 95 94 91 85 80 75 96
50 64.9 83 94 91 92 87 82 76 72 92
25 55.0 80 88 85 86 84 76 72 68 88

Note: Unit is equipped with High Airflow Fans with Variable Speed Control.
Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.
Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the
rating metric.
For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation
model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given distance
from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models pertaining to air-
cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.
Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band, +/-
4dB in all other octave bands and +/- 3dB for the overall dBA.
Tolerance limits are based on uncertainties associated with:
1. Measurement Test Procedure
2. Repeatability
3. Production / Manufacturing Variability
Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels. Note
that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.
Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.

Performance at AHRI Conditions


Evaporator Data Condenser Data Performance Data
EWT (°F) 54.00 Ambient Temp. (°F) 95.0 EER (Btu/W∙h) 10.89
LWT (°F) 44.00 Altitude (ft) 0.000 IPLV.IP (Btu/W∙h) 18.29
Net Cooling Capacity
Flow Rate (USGPM) 245.8 102.7
(ton.R)
Pressure Drop (ft H2O) 4.62
Fluid Water
Fouling Factor (h.ft².F/Btu) 0.000100
Fluid Volume (USGAL) 48.08

Note: Unit rated at design condition capacity.


Note: YVFA with open loop requires use of glycol for freeze protection. IPLV information is provided for comparison purposes only.

MLP Effective Date:6/15/2022 NewProject


Generated on2022-07-21 E.21.5.27676.0-D.94.0002(REV. v8_41.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW21.05a Page_3_of_3