158TR Chiller Selection PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Detailed Performance Summary For 30XA

Project: Project 04/09/2017


Prepared By: 10:38AM

Non contractual photo

PackagedChillerReport:DoNotEdit

30XA0602-A Air Cooled Screw Chiller


Cooling Mode Unit Information
Performance Information Manufacturing Source: Montluel, France
Cooling Capacity: 555.4 kW Refrigerant: R-134a
Cooling Efficiency (EER): 2.40 kW/kW Minimum Capacity: 15 %
Seasonal Efficiency (IPLV.SI): 4.33 kW/kW Number of Refrigerant Circuit: 2
Unit Power Input: 231.09 kW Operating/Shipping Weight: 6097/6013 kg
Evaporator Information Unit Dimensions (LxWxH): 7186/2253/2297 mm
Fluid Type: Fresh Water
Fouling Factor: 0.0176 (sqm-K)/kW MCHE Coating Requirements Information
Number of Passes: 2 Distance from coast (km): 5.0 km
Leaving Temperature: 7.2 °C Average Annual Temperature: 46.0 °C
Entering Temperature: 12.8 °C Average Annual Relative Humidity: 30.0 %
Fluid Flow: 23.77 l/s
Total Pressure Drop: 32.0 kPa Electrical Information
Condenser Information Unit Voltage: 400(+/-10%)-3-50 V-Ph-Hz
Altitude: 0 m Standby Power: 0.22 kW
Number of Fans: 11 Power Factor: 0.88
Entering Air Temperature: 46.1 °C
Electrical Electrical
Amps (Un) Circuit 1 Circuit 2
Acoustic Information (cooling mode) Maximum Current In (A): 423 None
Sound Power Level (LwA): 98 dB(A) Start Up Current (A) 583 None
Sound Pressure Level at 10.0m (LpA): 66 dB(A) Current at Eurovent 320 None
Conditions (A)

Accessories and Installed Options


Opt. 119 High Efficiency Option
Opt. 20A IP 54 Protection
Middle East Market Only
Opt. 279 Unit with Compressor Enclosure

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Packaged Chiller Builder EMEA 3.39c Page 1 of 2


Detailed Performance Summary For 30XA
Project: Project 04/09/2017
Prepared By: 10:38AM

Integrated Part Load Value (AHRI)


IPLV.SI: 4.33 kW/kW

Unit Performance
Percent Full Load Capacity, % 100 75 50 25
Percent Full Load Power, % 100.0 59.8 35.3 15.1
Unloading Sequence B B B B
Cooling Capacity, kW 605.7 454.3 302.8 151.4
Unit Power Input, kW 192.0 114.8 67.7 28.9
Efficiency, kW/kW 3.16 3.96 4.47 5.23
Evaporator Data
Fluid Entering Temperature, °C 12.0 10.4 9.2 7.9
Fluid Leaving Temperature, °C 7.0 7.0 7.0 7.0
Fluid Flow Rate, l/s 28.95 28.95 28.95 28.95
Fouling Factor, (sqm-K)/kW 0.0176 0.0176 0.0176 0.0176
Condenser Data
Entering Air Temperature, °C 35.0 27.0 19.0 13.0

Values given are interpolated and are not directly measurable under laboratory conditions.

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Packaged Chiller Builder EMEA 3.39c Page 2 of 2