158TR Chiller Selection PDF
158TR Chiller Selection PDF
158TR Chiller Selection PDF
PackagedChillerReport:DoNotEdit
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Unit Performance
Percent Full Load Capacity, % 100 75 50 25
Percent Full Load Power, % 100.0 59.8 35.3 15.1
Unloading Sequence B B B B
Cooling Capacity, kW 605.7 454.3 302.8 151.4
Unit Power Input, kW 192.0 114.8 67.7 28.9
Efficiency, kW/kW 3.16 3.96 4.47 5.23
Evaporator Data
Fluid Entering Temperature, °C 12.0 10.4 9.2 7.9
Fluid Leaving Temperature, °C 7.0 7.0 7.0 7.0
Fluid Flow Rate, l/s 28.95 28.95 28.95 28.95
Fouling Factor, (sqm-K)/kW 0.0176 0.0176 0.0176 0.0176
Condenser Data
Entering Air Temperature, °C 35.0 27.0 19.0 13.0
Values given are interpolated and are not directly measurable under laboratory conditions.