Project: QN 21090714 Devine Mercy Hospital Consultant: DAVEEN

Location: Bangladesh Date: 9/30/21 2:18 PM

PRICE SUMMARY

Tag Model Location Qty


CHILLER DCLC M-1 DCLCH57H59FDV 1

355100 30-Sep-21 Page 1 of 3 SPEC-Cindy ver. 7.0, 18928


Project: QN 21090714 Devine Consultant: DAVEEN

Location: Bangladesh Date: 9/30/21 2:18 PM


Tag: CHILLER DCLC M-1
PERFORMANCE SUMMARY
Location:

Magnetic Centrifugal Compressor Water Cooled Package Chiller


Model # DCLC400MFDH579E Rating version DCLC1.27
Quantity 1 Refrigerant R-134a
Manufacturer DBM

Physical Specifications
Compressor(s) TT700 Unit Height (in) 81.42
Unit Length (in) 191.50 Shipping weight (lb) 12685
Unit Width (in) 74.65 Operating weight (lb) 15748
Approx. refrigerant charge (lb) 1,146

Conditions of service
Percent of full load 100% Unit power (kW) 215.1
Capacity (Tons) 400.0 Cooling Efficiency (kW/Ton) 0.5378
NPLV.IP (kW/Ton) 0.2932

Evaporator Condenser
Model (Qty) H57(1) Model (Qty) H59(1)
Number of passes 2 Number of passes 2
Fluid Water Fluid Water
Fluid flow rate (USgpm) 1063 Fluid flow rate (USgpm) 1245
Entering fluid temp. (°F) 53.60 Entering fluid temp. (°F) 86.00
Leaving fluid temp. (°F) 44.60 Leaving fluid temp. (°F) 95.00
Fouling factor (h·ft²·°F/Btu) 0.000100 Fouling factor (h·ft²·°F/Btu) 0.000250
Pressure drop (psi/ft.H2O) 14.1/32.5 Pressure drop (psi/ft.H2O) 10.9/25.1
Fluid freezing point (°F) 32.00 Fluid freezing point (°F) 32.00

Electrical characteristics
Unit power supply 400V/3/50 Unit Running Current (Amp) 315
Motor starter mode VFD Unit Min. Circuit Ampacity (Amp) 354
Unit Max. Fuse Size (Amp) 600

Notes
- Certified in accordance with the AHRI Water Cooled Water-Chilling and Heap Pump Water-Heating Packages Using the Vapor
Compression Cycle Certification Program, which is based on AHRI Standard-550/590(I-P) and AHRI Standard 551/591(SI). Certified
units may be found in the AHRI Directory at www.ahridirectory.org.

Sound Data

Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level (free field) at 3.28 ft 43 52 62 68 75 73 66 67 78
*Sound Pressure Level (free field) ± 3 dB(A) Tolerance

NPLV.IP Points

% Full Evap.EFT Evap.LFT Evap Evap Cond.EFT Cond.LFT Cond Cond


load Tons Unit kW kW/Ton (°F) (°F) Flow(USgp PD(psi) (°F) (°F) Flow(USgp PD(psi) Type
100% 400.0 215.1 0.5378 53.60 44.60 1063 14.1 86.00 95.00 1245 10.89 Actual
75% 300.0 115.8 0.3860 51.35 44.60 1063 14.2 75.47 81.99 1245 11.26 Actual
50% 200.0 50.53 0.2525 49.10 44.60 1063 14.3 65.00 69.19 1245 11.66 Actual
25% 100.0 22.96 0.2300 46.85 44.60 1063 14.3 65.00 67.08 1245 11.66 Actual

355100 30-Sep-21 Page 2 of 3 SPEC-Cindy ver. 7.0, 18928


Project: QN 21090714 Devine Consultant: DAVEEN

Location: Bangladesh Date: 9/30/21 2:18 PM


Tag: CHILLER DCLC M-1
PERFORMANCE SUMMARY
Location:

Part load points

% Full Evap.EFT Evap.LFT Evap Evap Cond.EFT Cond.LFT Cond Cond


load Tons Unit kW kW/Ton (°F) (°F) Flow(USgp PD(psi) (°F) (°F) Flow(USgp PD(psi) Type
100% 400.0 215.1 0.5378 53.60 44.60 1063 14.1 86.00 95.00 1245 10.89 Actual
90% 360.0 174.1 0.4836 52.70 44.60 1063 14.1 81.79 89.78 1245 11.03 Actual
80% 320.0 133.3 0.4166 51.80 44.60 1063 14.1 77.58 84.59 1245 11.18 Actual
70% 280.0 100.5 0.3589 50.90 44.60 1063 14.2 73.36 79.40 1245 11.33 Actual
60% 240.0 73.81 0.3075 50.00 44.60 1063 14.2 69.15 74.27 1245 11.50 Actual
50% 200.0 50.53 0.2525 49.10 44.60 1063 14.3 65.00 69.19 1245 11.66 Actual
40% 160.0 40.63 0.2537 48.20 44.60 1063 14.3 65.00 68.35 1245 11.66 Actual
30% 120.0 28.51 0.2375 47.30 44.60 1063 14.3 65.00 67.52 1245 11.66 Actual
20% 80.00 18.62 0.2325 46.40 44.60 1063 14.4 65.00 66.66 1245 11.66 Actual
10% 40.00 11.57 0.2899 45.50 44.60 1063 14.4 65.00 65.83 1245 11.66 Actual

Standard Equipment
Code compliance Refrigerant Specialties
▪ Certified in accordance with the AHRI Water-Chilling Packages ▪ Evaporator sight glass ▪ Replaceable filter core
Using the Vapor Compression Cycle Certification Program
Evaporator/Condenser
▪ Cleanable integral fin copper tubes ▪ Relief valves
▪ Removable water headers ▪ Water flow switch (1nos) shipped loose for Evap.
▪ Victaulic groove water connections ▪ Evaporator 25mm insulation
Standard Electrical Components Units
▪ Single power point connection ▪ One(1) year warranty ▪ R134a refrigerant charged
▪ Main power supply monitoring module. Protection on under or limited to parts only ▪ Liquid isolation valves
over voltage, phase reversal,phases losses and imbalance
▪ Transformer for control voltage
Unit Protection
▪ High condensing pressure and low evaporating pressure ▪ Sensor fault
▪ Freeze protection ▪ Compressor high motor temperature
▪ Motor over current ▪ Compressor surge protection
▪ Chilled water flow loss
Controls Compressor
▪ DB Director(DDC controller) with color touch screen graphical ▪ Semi-Hermetic centrifugal ▪ Direct driven with
user interface. compressor permanent magnet DC
▪ Built-in communication protocol(Modbus RS485) ▪ Magnetic bearing oil free motor
▪ Programmable unit Operating Schedule ▪ 2 Stage impeller ▪ VFD operation with inlet
▪ Alarm histories guide vane
▪ Compressors rotation
Readouts Status
▪ Leaving and entering chilled water temperature ▪ Compressor status
▪ Leaving and entering condenser water temperature ▪ Water flow status
▪ Evaporator and condenser refrigerant pressure ▪ Unit Start/stop command
▪ Percentage of motor current ▪ Compressors run hours
▪ Cavity Temperature

355100 30-Sep-21 Page 3 of 3 SPEC-Cindy ver. 7.0, 18928


Dunham-Bush Holding Bhd (129358-X), Lot 5755-6, Kidamai Industrial Park, Bukit Angkat, 43000 Kajang, Selangor Darul Ehsan, Malaysia.
Tel:603-8924 9000 Fax:603-8739 5020 Email:info@dunham-bush.com