Unit Information
Chiller Model --------------------- CCWG550EVD# Number of Stage--------------------------------- 2
Oil Type ----------------------------------- Oil Free Compressor Code ---------------------- M3 Series
Oil Charge -------------------------------------- 0 L Motor Code -------------------- EKBT-280K Series
Refrigerant --------------------------------- R134a Unit Power Supply ------------ 380V/50Hz 3P+PE
Refrigerant Charge -------------------------750 kg Control Power Supply -------- 380V/50Hz 3P+PE
Shipping Weight ------------------------ 12170 kg Starting Type ---------------------- Magnetic VFD
Running Weight ------------------------- 13520 kg Mounted Type of Starter Panel --- Unitmounted
Length -----------------------------------5050 mm Width ------------------------------------ 2000 mm
Height -----------------------------------2200 mm
*Due to additional options and manufacturing deviation, the weight and dimension data in this
report are for reference only, and the actual weight and dimension of the unit are subject to the
actual product.
*The refrigerant charge amount in this report is for reference only. The refrigerant charge amount
is subject to the product nameplate.
# is the production serial number. The specific model please refer to the actual product.
Performance Information
Cooling Capacity ------------------------ 1934 kW Cooling Input Power -------------------- 299.6 kW
COP.R ------------------------------- 6.455 kW/kW NPLV.IP(AHRI) ---------------------- 10.82 kW/kW
Power Input per Capacity(COP) - 0.5447 kW/Ton Power Input per Capacity(NPLV) 0.3249 kW/Ton
Evaporator Information
Entering Fluid Temp --------------------- 12.00 ℃ Code -------------------------------------- J2 Series
Leaving Fluid Temp ----------------------- 6.00 ℃ Tubing ----------------- EI-3/4in,0.635mm,Copper
Flow Rate ----------------------------- 276.6 m3/h Passes -------------------------------------------- 2
Fluid Pressure Drop ---------------------- 38.6 kPa Waterboxes ---------- Nozzle-in-Head / 1.0 MPa
Fouling Factor ----------------- 0.0176 m2-℃/kW Nozzle ------------------------------------- DN300
Fluid Type ---------------------------- FreshWater Concentration --------------------------------- 0 %
Condenser Information
Entering Fluid Temp --------------------- 30.00 ℃ Code ------------------------------------- N2 Series
Leaving Fluid Temp ---------------------- 35.00 ℃ Tubing ---------------- CI-3/4in,0.635mm,Copper
Flow Rate ----------------------------- 384.4 m3/h Passes -------------------------------------------- 2
Electrical Information
Full Load Amps ---------------------------- 489.4 A Locked Rotor Amps ------------------------ NaN A
Starting Current ---------------------------- NaN A
General
Refrigerant Shipment ----- Shipped inside Chiller Oil Shipment ------------------------------ Oil Free
Hot Gas Bypass --------------------------- Installed Insulation Thickness ----------------------- 20mm
Anti-vibration Configuration ----- Spring Isolator Motor Protection ---------------------------- IP54
Shipping Method ------ Whole Machine Delivery Packaging OptionsRefinement Packaging (wooden case + steel ba
Waterboxes
Evaporator
Nozzle ArrangementsRight Side of Control Panel Connection ------------------------------- Victaulic
Condenser
Nozzle ArrangementsRight Side of Control Panel Connection ------------------------------- Victaulic
Sound
Compressor Silencer ---------------- Not Installed Condenser Sound Reduction ------- Not Installed
Discharge Line Sound Reduction --- Not Installed
Electrical
Communication ---------------------------- RS485 Controller ----------------------- Midea Controller
Protocol -----------------------------Modbus RTU Switch Gear Brand ------------------------ Default
Screen Size ---------------------------------- 10 in. Starter Panel Line Arrangement --------------------- Top in
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating
Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
551/591 (SI). Certified units may be found in the AHRI Directory at: www.ahridirectory.org.
Calculation:Loadline 1
Note:
Hot Gas Bypass device(s) is included.
6
COP(kW/kW)
5
4
1
0
10 20 30 40 50 60 70 80 90 100
Percent of Full Load(%)
Calculation:CEPT
CondEWT(℃) 100% 90% 80% 70% 60% 50% 40% 30% 20% 10%
32 5.965 6.004 5.956 6.144 6.574 6.795 6.720 6.171 4.942 2.755
28 7.120 7.119 7.160 7.166 7.679 8.042 8.048 7.659 6.536 3.561
24 8.364 8.513 8.674 8.735 9.049 9.547 9.763 9.540 8.510 4.620
20 10.04 10.38 10.60 10.61 10.83 11.22 12.16 12.22 11.06 7.540
18 10.88 11.37 11.87 11.85 12.34 12.40 13.82 13.81 12.90 9.512
Note:
Evaporator brine leaving temperature, flow rate and condenser flow rate are the same as the
selection operation condition.
Hot Gas Bypass device(s) is included.
Calculation:CEPT
15
12
COP(kW/kW)
3
32℃ 28℃ 24℃ 20℃ 18℃
0
10 20 30 40 50 60 70 80 90 100
Percent of Full Load(%)
A mm 5050
B mm 2000
C mm 2200