Centrifugal Chiller Report

Project Name:New Project Tag Name:CCWG550EVD

Unit Information
Chiller Model --------------------- CCWG550EVD# Number of Stage--------------------------------- 2
Oil Type ----------------------------------- Oil Free Compressor Code ---------------------- M3 Series
Oil Charge -------------------------------------- 0 L Motor Code -------------------- EKBT-280K Series
Refrigerant --------------------------------- R134a Unit Power Supply ------------ 380V/50Hz 3P+PE
Refrigerant Charge -------------------------750 kg Control Power Supply -------- 380V/50Hz 3P+PE
Shipping Weight ------------------------ 12170 kg Starting Type ---------------------- Magnetic VFD
Running Weight ------------------------- 13520 kg Mounted Type of Starter Panel --- Unitmounted
Length -----------------------------------5050 mm Width ------------------------------------ 2000 mm
Height -----------------------------------2200 mm
*Due to additional options and manufacturing deviation, the weight and dimension data in this
report are for reference only, and the actual weight and dimension of the unit are subject to the
actual product.
*The refrigerant charge amount in this report is for reference only. The refrigerant charge amount
is subject to the product nameplate.
# is the production serial number. The specific model please refer to the actual product.

Acoustic Data [dBA]


100%Load 75%Load 50%Load 25%Load
79.91 75.51 74.66 73.27
100% Load Spectrum
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
38.28 52.76 64.53 69.3 70.49 70.82 77.73 65.72
Sound Pressure (dB) measured in accordance with ANSI/AHRI Standard 575-2017(A-weighted)
TOLERANCES: The sound level of identical unit selections can vary due to manufacturing tolerance
and test repeatability.Variations of ±3 dBA on the Acoustic Data is possible.

Performance Information
Cooling Capacity ------------------------ 1934 kW Cooling Input Power -------------------- 299.6 kW
COP.R ------------------------------- 6.455 kW/kW NPLV.IP(AHRI) ---------------------- 10.82 kW/kW
Power Input per Capacity(COP) - 0.5447 kW/Ton Power Input per Capacity(NPLV) 0.3249 kW/Ton

Evaporator Information
Entering Fluid Temp --------------------- 12.00 ℃ Code -------------------------------------- J2 Series
Leaving Fluid Temp ----------------------- 6.00 ℃ Tubing ----------------- EI-3/4in,0.635mm,Copper
Flow Rate ----------------------------- 276.6 m3/h Passes -------------------------------------------- 2
Fluid Pressure Drop ---------------------- 38.6 kPa Waterboxes ---------- Nozzle-in-Head / 1.0 MPa
Fouling Factor ----------------- 0.0176 m2-℃/kW Nozzle ------------------------------------- DN300
Fluid Type ---------------------------- FreshWater Concentration --------------------------------- 0 %

Condenser Information
Entering Fluid Temp --------------------- 30.00 ℃ Code ------------------------------------- N2 Series
Leaving Fluid Temp ---------------------- 35.00 ℃ Tubing ---------------- CI-3/4in,0.635mm,Copper
Flow Rate ----------------------------- 384.4 m3/h Passes -------------------------------------------- 2

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 1/7 MCS
Centrifugal Chiller Report
Project Name:New Project Tag Name:CCWG550EVD
Fluid Pressure Drop ---------------------- 40.6 kPa Waterboxes ---------- Nozzle-in-Head / 1.0 MPa
Fouling Factor ----------------- 0.0440 m2-℃/kW Nozzle ------------------------------------- DN300
Fluid Type ---------------------------- FreshWater Concentration --------------------------------- 0 %
Heat Rejection Capacity ---------------- 2221 kW

Electrical Information
Full Load Amps ---------------------------- 489.4 A Locked Rotor Amps ------------------------ NaN A
Starting Current ---------------------------- NaN A

General
Refrigerant Shipment ----- Shipped inside Chiller Oil Shipment ------------------------------ Oil Free
Hot Gas Bypass --------------------------- Installed Insulation Thickness ----------------------- 20mm
Anti-vibration Configuration ----- Spring Isolator Motor Protection ---------------------------- IP54
Shipping Method ------ Whole Machine Delivery Packaging OptionsRefinement Packaging (wooden case + steel ba

Waterboxes
Evaporator
Nozzle ArrangementsRight Side of Control Panel Connection ------------------------------- Victaulic
Condenser
Nozzle ArrangementsRight Side of Control Panel Connection ------------------------------- Victaulic

Sound
Compressor Silencer ---------------- Not Installed Condenser Sound Reduction ------- Not Installed
Discharge Line Sound Reduction --- Not Installed

Electrical
Communication ---------------------------- RS485 Controller ----------------------- Midea Controller
Protocol -----------------------------Modbus RTU Switch Gear Brand ------------------------ Default
Screen Size ---------------------------------- 10 in. Starter Panel Line Arrangement --------------------- Top in

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating
Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
551/591 (SI). Certified units may be found in the AHRI Directory at: www.ahridirectory.org.

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 2/7 MCS
Centrifugal Chiller Report
Project Name:New Project Tag Name:CCWG550EVD

Calculation:Loadline 1

Percentage of Cooling Input Power COP.R Evaporator Condenser Weighti IPLV/NP


Full Load Capacity Power Input EEFT ELFT Flow Fluid CEFT CLFT Flow Fluid ng LV/CPLV
per Rate Pressure Rate Pressure Factor
Capacity Drop Drop
Tons kW kW/Ton kW/kW ℉ ℉ GPM ft wg ℉ ℉ GPM ft wg - kW/kW
100.0 % 550.0 299.6 0.5447 6.455 53.60 42.80 1218 12.9 86.00 95.00 1693 13.6 0 0.000
90.0 % 495.0 266.4 0.5381 6.534 52.52 42.80 1218 13.0 86.00 94.09 1693 13.6 0
80.0 % 440.0 237.2 0.5390 6.523 51.43 42.80 1218 13.0 86.00 93.19 1693 13.6 0
70.0 % 385.0 209.2 0.5433 6.471 50.35 42.80 1218 13.1 86.00 92.30 1693 13.6 0
60.0 % 330.0 162.8 0.4933 7.128 49.27 42.80 1218 13.1 86.00 91.33 1693 13.6 0
50.0 % 275.0 130.0 0.4728 7.436 48.19 42.80 1218 13.2 86.00 90.42 1693 13.6 0
40.0 % 220.0 105.1 0.4776 7.361 47.11 42.80 1218 13.2 86.00 89.54 1693 13.6 0
30.0 % 165.0 83.64 0.5069 6.936 46.03 42.80 1218 13.3 86.00 88.67 1693 13.6 0
20.0 % 110.0 67.37 0.6125 5.741 44.96 42.80 1218 13.3 86.00 87.83 1693 13.6 0
10.0 % 55.00 57.57 1.047 3.359 43.88 42.80 1218 13.4 86.00 87.05 1693 13.6 0

Note:
Hot Gas Bypass device(s) is included.

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 3/7 MCS
Centrifugal Chiller Report
Project Name:New Project Tag Name:CCWG550EVD

6
COP(kW/kW)

5
4

1
0
10 20 30 40 50 60 70 80 90 100
Percent of Full Load(%)

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 4/7 MCS
Centrifugal Chiller Report
Project Name:New Project Tag Name:CCWG550EVD

Calculation:CEPT

CondEWT(℃) 100% 90% 80% 70% 60% 50% 40% 30% 20% 10%
32 5.965 6.004 5.956 6.144 6.574 6.795 6.720 6.171 4.942 2.755
28 7.120 7.119 7.160 7.166 7.679 8.042 8.048 7.659 6.536 3.561
24 8.364 8.513 8.674 8.735 9.049 9.547 9.763 9.540 8.510 4.620
20 10.04 10.38 10.60 10.61 10.83 11.22 12.16 12.22 11.06 7.540
18 10.88 11.37 11.87 11.85 12.34 12.40 13.82 13.81 12.90 9.512

Note:
Evaporator brine leaving temperature, flow rate and condenser flow rate are the same as the
selection operation condition.
Hot Gas Bypass device(s) is included.

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 5/7 MCS
Centrifugal Chiller Report
Project Name:New Project Tag Name:CCWG550EVD

Calculation:CEPT

15

12
COP(kW/kW)

3
32℃ 28℃ 24℃ 20℃ 18℃
0
10 20 30 40 50 60 70 80 90 100
Percent of Full Load(%)

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 6/7 MCS
Centrifugal Chiller Report
Project Name:New Project Tag Name:CCWG550EVD

A mm 5050
B mm 2000
C mm 2200

Program Version:v2.2.6 Sales Manager:User


Database Version:V2.2.6 Selected by:Support
Date:11/8/2023 Page 7/7 MCS